Professional Documents
Culture Documents
The airflow patterns should, in principle, be organized in order that new air is
brought to the head of the occupants, so that they get fresh, clean air, and that
contaminants be evacuated as quickly as possible, before being mixed with indoor
air. However, air, as any other fluid, always follows the easiest path. This means
that the airflow does not necessarily follow expected patterns. Since air is
transparent, unexpected airflow patterns are noticed only when things go wrong.
Depending on the airflow distribution in rooms and for a given airflow rate, the
concentration of contaminants in the occupied space may vary by a factor of two or
more. Therefore, measurements may be useful to check if the airflow patterns are as
expected. Such measurements allow checks to ensure that:
• the air change efficiency is as large as possible
• clean air is supplied to the right places,
• air contaminants are quickly removed.
The measurement of the age of the air allows for the detection of possible shortcuts
and dead zones and for the checking of the general airflow pattern in the room or in
a building.
3.1 Definitions
The quantities defined below are explained in greater detail elsewhere (Sandberg,
1984; Sutcliffe, 1990) and are only briefly described here.
The local mean age of air at a point r is defined by the average age of all the air
particles arriving at that point:
∞ ∞
τ r = ∫ tf r (t )dt = ∫ Fr (t ) dt (3.2)
0 0
The room mean age of air <τ> is defined by the average of the ages of all the air
particles in the room.
f(τ) 4.0
3.5 η
3.0 25%
2.5 50%
2.0 66%
1.5 80%
1.0 90%
0.5 99%
0.0
0 0.5 1 1.5 2 2.5 3
τ
Figure 3.2: Typical probability density curves for the age of the air.
The parameter is the air exchange efficiency.
The air exchange efficiency in this very theoretical case is 100 per cent. At 99 per
cent air exchange efficiency, there is already some spreading of the ages around an
average still equal to the nominal time constant. When probability density function
spreads out and the probability function smoothens, the mean age at exhaust
remains the same, but there are more young air particles and more aged ones. In
addition, the most probable age (the time of the maximum of the curve) is reduced.
At 66 per cent air change efficiency, this most probable age is already half the
nominal time constant. At 50 per cent efficiency or complete mixing, the
probability density of the age of the air at exhaust is an exponential: There are more
young particles than old ones reaching the exhaust. With this distribution, the most
probable age is zero, but the mean age is still equal to the nominal time constant.
The last curve, with 25 per cent efficiency, represents a situation with a shortcut.
Figure 3.3 shows the corresponding probability curves for the age of the air at
exhaust, still with one hour as nominal time constant. This function shows the
percentage of particles at exhaust that are older than the value given on the
ordinate. At 100 per cent efficiency, all particles are exactly one hour (one time
constant) old. When the efficiency decreases, the function progressively changes to
become an exponential at 50 per cent efficiency or complete mixing. When the
efficiency decreases, there are less and less young particles and more and more old
ones at exhaust. At 25 per cent efficiency, which is very poor, 10 per cent of the
volume of the air at exhaust is older than three time constants!
F(τ ) 1.0
0.9 η
0.8 25%
0.7 50%
0.6 66%
0.5 80%
0.4 90%
0.3 99%
0.2 100
0.1
0.0
0 0.5 1 1.5 2 2.5 τ 3
Figure 3.3: Typical probability curves for the age of the air.
Note that these theoretical curves are for illustration. Some of them, in particular at
very high efficiency, are not likely to be found in practice.
0.0
-0.2
log[F(t)]
-0.4
-0.6
-0.8
-1.0
Step-up
-1.2 Decay Time [s]
-1.4
0 200 400 600 800 1000
Figure 3.5: Probability functions of the age of air, calculated from the recorded
concentration illustrated in Figure 3.4. Left is with a linear scale, right with a
logarithmic scale, showing an exponential decay after 700 s.
Figure 3.5 shows the concentration ratio calculated from the recorded concentration
illustrated in Figure 3.4.
The local mean age of air at any location is the integral (or zero moment) of the
probability distribution:
∞
τ r = μ 0 = ∫ Fr (t ) dt (3.8)
0
If there is only one single exhaust, the room mean age of air can be deduced from
tracer concentration measurements in the exhaust duct, Ce(t):
∞
⎛μ ⎞ ∫ tFe (t ) dt
τ = ⎜⎜ 1 ⎟⎟ = 0∞ (3.10)
⎝ μ0 ⎠e ∫ Fe (t ) dt
0
In this case, the nominal time constant of the ventilated space, τn, which is the ratio
of the space volume and the volumetric airflow rate, is equal to the mean age of air
at the exhaust:
∞
τ n = τ e = ∫ Fe (t ) dt (3.11)
0
Therefore, the air exchange efficiency, ηa, can be assessed directly by measuring
the evolution of the concentration at the exhaust:
τn τ ⎛ μ2 ⎞
η a= = e = ⎜⎜ 0 ⎟⎟ (3.12)
2〈τ 〉 2〈τ 〉 ⎝ 2 μ1 ⎠ e
with
2 2
( ) ⎛ F + F N N −1 ⎞
N −1
⎛ Δt ⎞
= ⎜ ⎟ (δF0 ) 2 + (δFN ) 2 + (Δt )2 ∑ δF j2 + ⎜⎜ 0 + ∑ F j ⎟⎟ (δΔt ) + (δε 0 )
2 2
f μ0
⎝ 2⎠ J =1 ⎝ 2 j =1 ⎠
(3.22)
and:
2 2
( ) ⎛ N F N N −1 ⎞
N −1
⎛ Δt ⎞
= ⎜ ⎟ (δF0 ) 2 + (δFN ) 2 + (Δt )2 ∑ j 2 δF j2 + ⎜⎜ + ∑ jF j ⎟⎟ (δΔt ) + (δε1 )
2 2
f μ1
⎝ 2⎠ J =1 ⎝ 2 j =1 ⎠
(3.23)
in which:
and
where δτd is the confidence interval resulting from the exponential fit.
Finally we get:
δτ n = δτ e = δμ0 ( Fe ) (3.26)
⎛ ⎞ 1
δ τ =⎜ ⎟ (μ1 ( Fe ))2 (δμ 0 ( Fe ))2 + (δμ1 ( Fe ))2 (3.27)
(
⎜ μ (F ) 2 ⎟
⎝ 0 e ⎠ )
δμ 1 ( Fe )
and: δη a = (3.28)
(2μ 0 ( Fe ) )
2
3.5 Example of application
The ventilation system of a 60 seats conference room was retrofitted to improve
indoor air quality. The old, mixing type installation was replaced by a displacement
ventilation system. as shown in Figure 3.6. The conference room is 8 m by 10 m
wide and 3 m high. It is completely embedded in an old, massive building. Its
walls, floor or ceiling have no contact with the outdoor environment. It has no
windows, but leaky entrance doors leading to a hall.
Air inlets
Exhaust grids
Conference
room
Hall
Office
Hall
Office
Figure 3.7: Arrangement of the conference room after improvement. (Roulet et al.,
1998)
A second measurement campaign was performed, showing a significant
improvement of the ventilation efficiency (see Figure 3.8). The air change
efficiency was doubled; and the mean age of air was maintained despite a reduction
of the ventilation rate – and of energy use - by a factor two.
Figure 3.8: Room ventilation characteristics before and after improvement (Roulet
et al., 1998).
3.6 References
Roulet, C.-A., 2004, Santé et qualité de l'environnement intérieur dans les
bâtiments: Lausanne, PPUR, 368 p.
Roulet, C.-A., F. Foradini, P. Cretton, and M. Schoch, 1998, Measurements of
ventilation efficiency in a retrofitted conference room.: EPIC'98, p. 498-
503.
Roulet, C.-A., and P.Cretton, 1992, Field comparison of age of air measurement
techniques: Roomvent'92, p. 213-229.
Sandberg, M., 1984, The multi-chamber theory reconsidered from the viewpoint of
air quality studies: Building and Environment, v. 19, p. 221-233.
Sutcliffe, H. C., 1990, A guide to air changes efficency: AIVC technical note, v. 28.