NOTES:

STRAINER

GENERAL ARRANGEMENT OF METER CHAMBERS CONCRETE SUPPORT BELOW STRAINER

WITHIN BLOCKPAVING AREAS


CLASS 20/10/S SOLID CONCRETE BLOCKWORK WALLS
SEE NOTE NO. 11

VARIES
100 100 CEMENT SCREED OVER EXTERIOR BLOCK WORK SURFACES
100 200 VARIES 200 100
CONCRETE/BRICK
SUPPORT FOR BOTH

200 100 100


150X150X100MM 4`Y' 12`L' SHAPPED
IP68 PVC JB VALVES
TRIMMER BARS TOP & BOTTOM

FOR COMMUNICATION

HDPE BOX 200X200X200 RECESSED


IN INTERLOCK PAVED AREA

TO LV/ELECTRICAL ROOM THRUST BLOCK FOR ELBOW


SMART
DOUBLE FLANGED WATER METER
G F
300 * RISE OUTLET PIPE
BOTH SIDES F G
300 DOUBLE FLANGED
A
A

VARIES

VARIES
DOOR HINGES

B
FLOW OF WATER

CONSUMER SIDE VALVE


SPIGOT FLANG B `Y '12@150 c/c
ADAPTOR
BOTHWAYS TOP & BOTTOM
THRUST BLOCK
F B C D E F G

200
FOR ELBOW G
VARIES

100
GRE SPOOL WALL
DOUBLE FLANGED

100
DOUBLE FLANGED 200MM DIA CIRCULAR CI STEEL CHAMBER COVER
10MM NEOPRENE GRP LADDER
BURIED SUMP PIT COVER FOR VALVE
MEMBRANS 2 GATE VALVE
GATE VALVE 300x300x150mm
LAYERS SLIP AND
DOUBLE FLANGED MASTIC SEALANT
AS SPECIFIED
CLASS 20/10/S SOLID CONCRETE
BLOCKWORK SUPPORT WITH
CEMENT MORTAR 1:3
REINFORCEMENT DETAILS
SOCKET
GATE VALVE
DOUBLE FLANGED STRAINER SPIGOT FLANGE ADAPTOR
GRE SPIGOT
SOCKET ELECTRO
FLANG ADAPTOR GATE VALVE
MAGNETIC WATER
METER DOUBLE FLANGED
GRE 'T' TWO SIDE MAIN LINE
SPIGOT ONE SIDE
FLANGED

PLAN CEMENT MORTAR(1:3) BEDDING M.S.CHEQURED PLATE COVER


VALVE AND FLOW METER ARRANGEMENT
TO BLOCKPAVING
10 THK.CEMENT MORTAR (1:3) SEATING
FOR MANHOLE COVER
LIFTING HOOKS TO BE SEALED
WITH CEMENT MORTAR (1:3) CHAMBER COVER FRAME TO BE BOLTED
AFTER PLACING TO THE PRECAST CONCRETE COVER SLAB

BLOCKPAVING LEVEL CLASS 30/20/S PRECAST CONCRETE


COVER SLAB

WATER PROOFING MEMBRANE


AND PROTECTION BOARD BOTH WAY
50mm THK.CEMENT MORTAR (1:3)
AS SPECIFIED TOP&BOTTOM
SEATING FOR PRECAST CONCRETE COVER SLAB 35sq
M.S.CHEQURED PLATE COVER VARIES
CLASS 20/10/S SOLID G.R.P LADDER
15mm THICK PLASTERING FINISHED SMOOTH
CEMENT MORTAR(1:3) BEDDING CONCRETE BLOCKWORK WALLS 28.7sq
TO BLOCKPAVING SEE NOTE NO.11
LIFTING HOOKS TO BE SEALED 10 THK.CEMENT MORTAR (1:3) SEATING POINTING INSIDE
WITH CEMENT MORTAR (1:3) FOR MANHOLE COVER
AFTER PLACING

HDPE BOX 200x200x200

BLOCKPAVING LEVEL CLASS 30/20/S PRECAST CONCRETE


COVER SLAB

300 Slope
75 50 200

300
PROTECTIVE SCREED

CLASS 20/20/S CONCRETE BLINDING

PVC CONDUIT GRP FITTING AS SPECIFIED WATER PROOFING MEMBRANE


50mm THK.CEMENT MORTAR (1:3) SEATING CONSUMER SIDE VALVE
25MM CPVC CONDUIT FOR PRECAST CONCRETE COVER SLAB
TO LV ROOM FOR METER CLASS 30/20/S RC BOTTOM SLAB
WATER PROOFING MEMBRANE 150X150X100MM
COMMUNICATION 15mm THICK PLASTERING
AND PROTECTION BOARD IP68 PVC JB
AS SPECIFIED FINISHED SMOOTH BOTH WAY 2 LAYERS SLIP MEMBRANE
VARIES

CLASS 20/10/S SOLID


CONCRETE BLOCKWORK WALLS STRAINER
TO CONSUMER
TOP & BOTTOM
SECTION 'B-B' BETWEEN SUPPORT AND CHAMBER FLOOR

316L GRADE STAINLESS


SEE NOTE NO.11 WATER METER POINTING INSIDE STORAGE TANK
BOTH SIDES STEEL NUT BOLT
300 300 *
M.S.CHEQURED PLATE COVER
THRUST BLOCK FOR ELBOW
VARIES

FLOW OF 10 THK.CEMENT MORTAR (1:3) SEATING


WATER FOR MANHOLE COVER
300

OUTLET PIPE
DOUBLE FLANGED CHAMBER COVER FRAME TO BE BOLTED
PROTECTIVE SCREED TO THE PRECAST CONCRETE COVER SLAB
200

GRE SPIGOT
FLANG ADAPTOR
50

CLASS 20/20/S CONCRETE BLINDING BLOCKPAVING LEVEL CLASS 30/20/S PRECAST CONCRETE
COVER SLAB
75

CONCRETE SUPPORT BELOW WATER PROOFING MEMBRANE


GAP BETWEEN BLOCKWORK
AND PIPE TO BE STRAINER WITH
RUBBER PACKING CLASS 30/20/S RC BOTTOM SLAB
SEALED AS SPECIFIED
2 LAYERS SLIP MEMBRANE BETWEEN CONCRETE/BRICK SUPPORT
SUPPORT AND CHAMBER FLOOR FOR BOTH VALVES WITH
BOTH WAY
TOP & BOTTOM RUBBER PACKING

BOTH WAY
TOP&BOTTOM Y16 @ 200
VARIES

WATER PROOFING MEMBRANE

SECTION 'A-A' AND PROTECTION BOARD


AS SPECIFIED Y12 @ 200

30/20/S REINFORCED CONCRETE WALL

WATER STOPER
SUMP PIT 300x300x150mm
CONSTRUCTION JOINT

300 Slope
75 50 200

300

CLASS 20/20/S CONCRETE BLINDING

WATER PROOFING MEMBRANE


AMI (ADVANCED METERING INFRASTRUCTURE)
GRP FITTING AS SPECIFIED
WATER METER INSTALLATION
CLASS 30/20/S RC BOTTOM SLAB

BOTH WAY
TOP & BOTTOM SECTION 'B-B' 2 LAYERS SLIP MEMBRANE
BETWEEN SUPPORT AND CHAMBER FLOOR
AMI - WATER
STEEL DETAIL IN CASE OF RCC WALL BULK WATER METERS IN CHAMBER (FOR BULK
METERS 50MM TO 300MM DIA. CONNECTION)