You are on page 1of 70

Condenser Performance Monitoring Practices

1007309
Condenser Performance Monitoring
Practices

1007309

Technical Update, September 2002

EPRI Project Manager


J. Stallings

EPRI • 3412 Hillview Avenue, Palo Alto, California 94304 • PO Box 10412, Palo Alto, California 94303 • USA
800.313.3774 • 650.855.2121 • askepri@epri.com • www.epri.com
DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITIES
THIS DOCUMENT WAS PREPARED BY THE ORGANIZATION(S) NAMED BELOW AS AN
ACCOUNT OF WORK SPONSORED OR COSPONSORED BY THE ELECTRIC POWER RESEARCH
INSTITUTE, INC. (EPRI). NEITHER EPRI, ANY MEMBER OF EPRI, ANY COSPONSOR, THE
ORGANIZATION(S) BELOW, NOR ANY PERSON ACTING ON BEHALF OF ANY OF THEM:

(A) MAKES ANY WARRANTY OR REPRESENTATION WHATSOEVER, EXPRESS OR IMPLIED, (I)


WITH RESPECT TO THE USE OF ANY INFORMATION, APPARATUS, METHOD, PROCESS, OR
SIMILAR ITEM DISCLOSED IN THIS DOCUMENT, INCLUDING MERCHANTABILITY AND FITNESS
FOR A PARTICULAR PURPOSE, OR (II) THAT SUCH USE DOES NOT INFRINGE ON OR
INTERFERE WITH PRIVATELY OWNED RIGHTS, INCLUDING ANY PARTY'S INTELLECTUAL
PROPERTY, OR (III) THAT THIS DOCUMENT IS SUITABLE TO ANY PARTICULAR USER'S
CIRCUMSTANCE; OR

(B) ASSUMES RESPONSIBILITY FOR ANY DAMAGES OR OTHER LIABILITY WHATSOEVER


(INCLUDING ANY CONSEQUENTIAL DAMAGES, EVEN IF EPRI OR ANY EPRI REPRESENTATIVE
HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES) RESULTING FROM YOUR
SELECTION OR USE OF THIS DOCUMENT OR ANY INFORMATION, APPARATUS, METHOD,
PROCESS, OR SIMILAR ITEM DISCLOSED IN THIS DOCUMENT.

ORGANIZATION(S) THAT PREPARED THIS DOCUMENT

John L. Tsou Consulting Service

ORDERING INFORMATION
Requests for copies of this report should be directed to EPRI Orders and Conferences, 1355 Willow
Way, Suite 278, Concord, CA 94520. Toll-free number: 800.313.3774, press 2, or internally x5379;
voice: 925.609.9169; fax: 925.609.1310.

Electric Power Research Institute and EPRI are registered service marks of the Electric Power
Research Institute, Inc. EPRI. ELECTRIFY THE WORLD is a service mark of the Electric Power
Research Institute, Inc.

Copyright © 2002 Electric Power Research Institute, Inc. All rights reserved.
CITATIONS

This report was prepared by

John L. Tsou Consulting Service


56 Williams Lane
Foster City, CA 94404

Principal Investigator
J. Tsou

This report describes research sponsored by EPRI.

The report is a corporate document that should be cited in the literature in the following manner:

Condenser Performance Monitoring Practices, EPRI, Palo Alto, CA: 2002. 1007309

iii
ABSTRACT

Steam surface condensers and associated systems cause significant loss of generation and heat
rate degradation in both nuclear and fossil-fired power plants. The purpose of this report is to
provide the engineering and operating personnel of the power industry with a guide for selecting
and using the practices available for monitoring condenser performance.

Strictly speaking, only condenser backpressure needs to be monitored. However, the cause of
high condenser backpressure cannot be determined without monitoring other operating
parameters. Common causes for high condenser backpressure include the following:

• High inlet cooling water temperature

• Low cooling water flow

• Partially filled waterbox

• Excessive heat load

• Fouled tubes

• Excessive air in-leakage

• Vacuum equipment problem

• Tube bundle design problem

It is not the intent of this paper to address the causes and remedies of high condenser
backpressure. This report does provide details of specialty instruments used in condenser
performance monitoring. References for in-depth studies and sources for obtaining the specialty
instruments, services and cost are also included.

v
CONTENTS

1 INTRODUCTION....................................................................................................................1-1
Background.............................................................................................................................1-1
Purpose...................................................................................................................................1-2
Scope .....................................................................................................................................1-2
Organization of the Report........................................................................................................1-3
Reference................................................................................................................................1-3

2 TEMPERATURE MONITORING PRACTICES .....................................................................2-1


Background.............................................................................................................................2-1
Instruments .............................................................................................................................2-1
Cooling Water Inlet Temperature ..............................................................................................2-2
Cooling Water Outlet Temperature ............................................................................................2-2
Condenser Shell Temperature ...................................................................................................2-4
Hotwell Temperature ...............................................................................................................2-4
Condensate Temperature ..........................................................................................................2-4
References ..............................................................................................................................2-4

3 PRESSURE MONITORING PRACTICES ..............................................................................3-1


Background.............................................................................................................................3-1
Instruments .............................................................................................................................3-1
Cooling Water Inlet Pressure ....................................................................................................3-3
Condenser Backpressure...........................................................................................................3-3
Reference................................................................................................................................3-4

4 FLOW MONITORING PRACTICES ......................................................................................4-1


Background.............................................................................................................................4-1
Instruments .............................................................................................................................4-1
Periodic Cooling Water Flow Measurement ...............................................................................4-2

vii
Dye Dilution Test................................................................................................................4-2
Velocity Traversing Method.................................................................................................4-3
CW Pump Curves and Total Dynamic Head Method ..............................................................4-5
Heat Balance Method ..........................................................................................................4-5
Continuous Cooling Water Flow Measurement...........................................................................4-6
Differential Producer Method...............................................................................................4-6
Ultrasonic Time of Travel Method.............................................................................................4-9
Air In-Leakage Flow Monitoring.............................................................................................4-11
Rotameter.........................................................................................................................4-11
Orifice Plate ..........................................................................................................................4-12
Electronic Air In-Leakage Monitor..........................................................................................4-14
Summary ..............................................................................................................................4-15
References ............................................................................................................................4-17

5 FOULING MONITORING PRACTICES ................................................................................5-1


Background.............................................................................................................................5-1
Instruments .............................................................................................................................5-1
Off-Line Microfouling Monitor.................................................................................................5-2
On-Line Microfouling Monitor .................................................................................................5-3
Bridger Scientific Continuous Side-Stream Reduced-Scale On-Line Microfouling Monitor .......5-3
Bridger Scientific Continuous Small On-Line Microfouling Monitor ............................................5-3
Conco Systems Continuous Side-Stream Reduced Scale On-Line Microfouling Monitor................5-5
Periodic In-Situ On-Line Microfouling Monitor..........................................................................5-6
EPRI Continuous In-Situ On-Line Microfouling Monitor ............................................................5-6
Taprogge Continuous In-Situ On-Line Microfouling Monitor ......................................................5-7
On-Line Macrofouling Monitor.................................................................................................5-9
Intake On-Line Macrofouling Monitor ..................................................................................5-9
Tubesheet On-Line Macrofouling Monitor ...............................................................................5-10
Summary ..............................................................................................................................5-12
References ............................................................................................................................5-13

6 LEVEL MONITORING PRACTICES.....................................................................................6-1


Background.............................................................................................................................6-1
Instruments .............................................................................................................................6-1
Hotwell...................................................................................................................................6-2

viii
Waterboxes .............................................................................................................................6-2
Intake .....................................................................................................................................6-2
Summary ................................................................................................................................6-5
References ..............................................................................................................................6-6

7 DISSOLVED OXYGEN MONITORING PRACTICES............................................................7-1


Background.............................................................................................................................7-1
Instruments .............................................................................................................................7-1
References ..............................................................................................................................7-2
LIST OF FIGURES

Figure 2-1 Circulating Water Discharge Temperature vs. Distance from Inside Edge of Pipe ...............2-3
Figure 2-2 BBC Circulating Water Outlet Temperature Measurement ...............................................2-3
Figure 3-1 Condenser Pressure-Sensing Basket Tip Source: ASME PTC 12.2 ...................................3-2
Figure 3-2 Condenser Pressure-Sensing Guide Plate Source: ASME PTC 12.2..................................3-2
Figure 3-3 The Four-Tap Selector Connects the Basket Tips to the Pressure Transducer and
Purge Supply........................................................................................................................3-4
Figure 4-1 Recommended Velocity Traverse Locations Source: ASME PTC 12.2 .............................4-4
Figure 4-2 Water Flow Through Condenser ....................................................................................4-8
Figure 4-3 Flow Through an Abrupt Contraction .............................................................................4-8
Figure 4-4 Elbow Differential Pressure Method...............................................................................4-9
Figure 4-5 Diagram of Four-Path Ultrasonic Flow Meter................................................................4-10
Figure 4-6 Schematic of Rotameter ..............................................................................................4-11
Figure 4-7 Orifice Plate Installation..............................................................................................4-12
Figure 4-8 Schematic for Differential Pressure Transmitter Installation ...........................................4-13
Figure 5-1 Conco Heat Transfer Testing Unit ..................................................................................5-2
Figure 5-2 DATS Heat Exchanger Cross-Section View ....................................................................5-3
Figure 5-3 ProDATS Probe and its Schematic .................................................................................5-4
Figure 5-4 Conco Portable Test Condenser .....................................................................................5-5
Figure 5-5 On-Line Fouling Monitor ..............................................................................................5-7
Figure 5-6 Taprogge Monitoring System ........................................................................................5-8
Figure 5-7 Typical Cooling Water Intake System ............................................................................5-9
Figure 5-8 Typical Ultrasonic Microfouling Monitoring System .....................................................5-10
Figure 5-9 TVA Tubesheet Macrofouling Monitor.........................................................................5-11
Figure 6-1 Typical Installation of Capacitance Level Monitor...........................................................6-3
Figure 6-2 Typical Installation of Submersible Differential Pressure Level Monitor............................6-3
Figure 6-3 Typical Installation of Bubbler Level Monitor.................................................................6-4

xi
LIST OF TABLES

Table 4-1 Circulating Water Flow Monitors ..................................................................................4-15


Table 4-2 Air In-Leakage Flow Monitor ......................................................................................4-16
Table 5-1 Microfouling Monitor ..................................................................................................5-12
Table 6-1 Remote Level Monitors..................................................................................................6-5

xiii
1
INTRODUCTION

Background

Steam surface condensers and associated systems cause significant loss of generation and heat
rate degradation in both nuclear and fossil-fired power plants. The loss of generation due to
condenser backpressure increase can be estimated from a plant turbine thermal kit. The deviation
of heat rate due to condenser backpressure increase is 204 Btu/kWh/in Hg on the utility average
based on an earlier EPRI report[1-1]. Simply speaking, only condenser backpressure needs to be
monitored. However, the cause of high condenser backpressure cannot be determined without
monitoring other operating parameters. Common causes for high condenser backpressure include
the following:

• High inlet cooling water temperature

• Low cooling water flow

• Partially filled waterbox

• Excessive heat load

• Fouled tubes

• Excessive air in-leakage

• Vacuum equipment problem

• Tube bundle design problem

Some of the causes of high condenser backpressure, such as high inlet cooling water temperature
and excessive heat load, cannot be controlled. Other causes require remedial action. It is not the
intent of this paper to address the causes and remedies of high condenser backpressure. However,
any remedial action involves additional cost. To avoid unnecessary cost, it is important to isolate
the true cause of high condenser backpressure. This is the reason that it is essential to monitor the
performance of the condenser on a routine basis to ascertain that it is performing properly based
on current operating conditions. If a condenser is not performing properly, the true cause of the
deficiency most likely can be determined from condenser performance monitoring.

1-1
Introduction

Unfortunately, performance analysis of condenser problems is complicated by the difficulty in


measuring critical parameters, such as heat rejection rate, and cooling water outlet temperature
and flow rate. Of the three parameters, only two are required for analyzing the performance of
a particular condenser. The heat rejection rate can be calculated from the turbine heat balance.
If the heat rejection rate is known, the outlet temperature can be calculated from the flow rate,
or the flow rate can be calculated from the outlet temperature. If the heat rejection rate is not
known, then both outlet temperature and flow rate are required. This paper will address common
practices used in the power industry to monitor and analyze condenser performance.

The performance factor, a.k.a. cleanliness factor or fouling factor, is generally calculated.
However, it can also be measured directly with on-line or side-stream specialty instruments.
This paper will address various devices available for this purpose.

Local instruments provide adequate data for most of the analysis. Data transmitted to a remote
location, such as a control room, provide opportunities to record and to trend the data. Trending
provides additional insight into the causes of performance deficiency.

Purpose

The purpose of this paper is to provide the engineering and operating personnel of the power
industry with a guide for selecting and using the practices available for monitoring condenser
performance.

It is not the purpose of this paper to evaluate or to recommend practices required for proper
condenser performance monitoring. In fact, it is neither necessary nor economically feasible to
use all the monitoring practices. However, sufficient information will be provided to allow for
choosing and specifying suitable monitoring practices based on one’s needs.

Scope

This paper covers a range of practices used by the power industry to monitor condenser
performance. The monitoring practices for each parameter discussed in this paper are as follows:

• Temperature: cooling water inlet and outlet, hotwell and condensate.

• Pressure: cooling water inlet and outlet, condenser backpressure.

• Flow: cooling water flow, air in-leakage.

• Fouling: microfouling and macrofouling, on-line and side-stream.

• Level: hotwell, waterboxes and intake.

• Dissolved oxygen: condensate.

1-2
Introduction

This report will provide details of specialty instruments used in condenser performance
monitoring. This report will not provide details of commonly used instruments, such as for
temperature and pressure monitoring. A brief evaluation based on the author’s own opinion will
be provided. References for in-depth study and sources for obtaining the specialty instruments,
services and cost are also provided.

Since this report is not about performance analysis or diagnosis, detailed procedures for these
will not be included.

Organization of the Report

This report contains seven sections. After the introduction, the subsequent six sections each
cover one monitored parameter.

Each of the sections 2 through 7 contain subsections covering background, instruments,


monitoring practices, and references. The objective and purpose of monitoring each parameter
will be provided in the background subsection. Instruments and methods used to monitor the
parameters will be briefly discussed in the instrument subsection. Detailed discussion including
instrument type, monitoring location, source, cost, and author’s comments will be provided in
the monitoring practice subsections. References cited in the text will be provided in the reference
subsection.

Reference

[1-1] Heat Rate Improvement Guidelines for Existing Fossil Plants, EPRI Report CS-4554, EPRI
May 1986.

1-3
2
TEMPERATURE MONITORING PRACTICES

Background

Cooling water inlet temperature has the greatest impact on condenser performance. It is also the
easiest parameter to be monitored, and every plant does so. If no other problem exists, normal
condenser backpressure can be found from the thermal kit at the particular operating load. There
is not anything a plant can do if the cooling water source is from a natural body. However, if the
cooling water is from a cooling tower, the cooling tower should be investigated for possible
problems.

Cooling water outlet temperature is used to establish terminal temperature difference (TTD),
which is the temperature difference between the steam saturation temperature corresponding
to the backpressure and the outlet cooling water temperature. TTD is a starting point used in
diagnosing many condenser problems. Outlet temperature is also used to establish the differential
temperature (∆T) between the inlet and outlet cooling water. Higher than normal ∆T indicates
insufficient cooling water flow. Cooling water outlet temperature is used to calculate heat load
and fouling factors. Unfortunately, accurate cooling water outlet temperature is very difficult to
determine. A workable solution is recommended by the ASME Performance Test Code on Steam
[2-1].
Surface Condensers (PTC 12.2 –1998)

Condenser shell temperature is not normally measured but is inferred from condenser
backpressure. As mentioned before, it is used to calculate TTD.

Hotwell temperature is compared to shell temperature. A large differential between shell


temperature and hotwell temperature may indicate an excessive steam pressure drop, which
suggests a condenser design deficiency. Hotwell temperature is also compared to condensate
temperature. A larger than normal difference indicates condensate subcooling, which causes
higher dissolved oxygen and heat rate degradation.

Instruments

Instruments used in condenser temperature monitoring are the same as those used elsewhere in
power plants. Thermometers are used for local temperature monitoring. Thermocouples (TCs),
thermistors, and resistance temperature detectors (RTDs) are used remote temperature readings.
The ASME Performance Test Code cited above recommends type E thermocouples, 100-ohm
platinum RTDs, and thermistors with a nominal impedance of greater than 100 ohms at 32oF
o
(0 C). For RTDs and thermistors the four-wire method is recommended. All temperature
o o
monitors should be calibrated initially and periodically to within 1 F (0.6 C) using traceable

2-1
Temperature Monitoring Practices

standards. All monitors should be protected from debris and other potentially damaging
elements. If a thermal well is used, it should have sufficient length to extend into the flow stream
to measure the actual temperature. Heat conducting gel and spring-loaded elements should be
used to insure accurate readings.

Cooling Water Inlet Temperature

Cooling water inlet temperature is generally uniform, and its measurement does not present a
special challenge. A monitor mounted in any convenient location will be sufficient. Redundancy
may be desirable to insure accuracy and backup.

Cooling Water Outlet Temperature

Cooling water outlet temperature is difficult to determine accurately, because the temperature of
the cooling water that exits from the tube bundle is not uniform. Tubes located in the outer tube
bundle will transfer more heat than the tubes in the inner tube bundle. Consequently, the cooling
water that exits from the outer tubes will have a higher temperature than that from the inner
tubes. The degree of non-uniformity depends on the mixing effect of the condenser waterbox, its
outlet configuration and the piping configuration. Figure 2-1 shows temperature readings from a
thermocouple traverse immediately below the discharge waterbox of a condenser[2-2]. Note that
the temperature will be more uniform if the measuring point is further away from the condenser
outlet waterbox.

The measuring point should be located as far downstream from the condenser as possible, where
the discharge is well mixed and the temperature is uniform. It may be necessary to traverse the
discharge pipe to confirm temperature uniformity. The location is acceptable if there is no
significant heat loss and there are no other significant flows mixed in.

If an acceptable, well-mixed downstream location cannot be found, then the outlet temperature
[2-1]
has to be determined from an array of temperature measurements. PTC 12.2 recommends one
2
temperature measurement point for every 1.5 square feet (0.14 m ) of pipe flow area. These
points are located at the centroid of each area, and the measured temperatures are averaged with
equal weight.

In practice, the number of measuring points may be judiciously reduced as long as the accuracy
of the outlet temperature is within the tolerance. The number and length of thermal wells may be
determined by traversing the pipe. Figure 2-2 shows a temperature probe arrangement by one of
[2-3]
the condenser manufacturers . It consists of a total of nine probes. Three longer probes extend
1/3 diameter of the pipe into the pipe and six shorter probes extend 2/15 diameter into the pipe.
The readings from the nine probes are averaged for the true water temperature.

2-2
Temperature Monitoring Practices

Figure 2-1
Circulating Water Discharge Temperature vs. Distance from Inside Edge of Pipe

Figure 2-2
BBC Circulating Water Outlet Temperature Measurement

2-3
Temperature Monitoring Practices

Condenser Shell Temperature

As mentioned earlier the condenser shell temperature cannot be measured accurately because the
incoming steam may contain superheat. The shell temperature is generally inferred based on the
backpressure.

Hotwell Temperature

Hotwell temperature can be measured above the hotwell condensate level with conventional
temperature measuring devices.

Condensate Temperature

Condensate temperature is normally measured at the suction side of the condensate pump.

References

[2-1] Performance Test Code on Steam Surface Condensers, ASME PTC 12.2 –1998. ASME,
New York, 1998.

[2-2] Bell, R.J., Mussalli, Y. G., “Instrumentation and Techniques for Condenser Performance
Monitoring”, presented at the Joint ASME/ANS Nuclear Engineering Conference, Portland,
Oregon, July 1982.

[2-3] The High Reliability Condenser Design Study, EPRI Report CS-3200, July 1983.

2-4
3
PRESSURE MONITORING PRACTICES

Background

The most important pressure to be monitored is the condenser backpressure, which determines
the condenser performance. Backpressure varies with heat load, cooling water temperature,
cooling water flow rate, tube fouling, and other factors, and is monitored by every plant.
Condenser backpressure is not difficult to monitor. However, the measured pressure is not
always accurate. Backpressure is used in conjunction with cooling water outlet temperature to
establish TTD.

Another pressure parameter to be monitored is the cooling water pressure. Low cooling water
pressure indicates deficient cooling water flow due to poor cooling water pump performance or
low water level in the intake bay. High cooling water pressure indicates blockage of the flow
pass.

Monitoring the differential pressure between the inlet and outlet can indicate blockage of the
tubes or tubesheet due to macrofouling. Differential pressure is also used to monitor cooling
water flow. The details will be discussed in the fouling and flow section.

Instruments

Basket tips (Figure 3-1) and guide plates (Figure 3-2) are the most common condenser
backpressure-sensing instruments. Because the guide plates have to be installed parallel to the
steam flow direction, which may be difficult to predict, the author believes the basket tips are
more forgiving and more accurate on average. The pressure measurement device includes non-
mercury manometers and electronic absolute pressure transmitters.

Cooling water pressure measurement devices include mechanical pressure gages and electronic
pressure transmitters.

Differential pressure measurement devices include mechanical differential pressure gages and
electronic differential pressure transmitters.

3-1
Pressure Monitoring Practices

Figure 3-1
Condenser Pressure-Sensing Basket Tip
Source: ASME PTC 12.2

Figure 3-2
Condenser Pressure-Sensing Guide Plate
Source: ASME PTC 12.2

Basket tips and guide plates can be ordered from turbine manufacturers and parts vendors. The
basket tip costs around $500. The guide plate can probably be made in most plant maintenance
shops at considerably less cost. Due to the construction of the basket tip, orientation with steam
flow may be less critical with this device. The guide plate, on the other hand, may be less
accurate if it is not oriented correctly. However, the guide plates are less likely to be damaged
in highly turbulent steam flow areas. The electronic transmitters can be ordered from most
instrument manufacturers.

3-2
Pressure Monitoring Practices

Cooling Water Inlet Pressure

Pressure taps for cooling water pressure measurement should be located in a convenient spot
between the cooling water pump and the inlet waterbox. Care should be taken to avoid locating
the measurement point in areas of local high velocity or local flow separation zones. The tap
should be deburred and cleaned on the inside. Isolation valves and fill lines should be installed
between the sensing point and the gauge or transmitter. The sensing point should be periodically
back flushed to purge any debris from the sensing point.

Condenser Backpressure

Most plants are equipped with basket tips or guide plates as part of the turbine package. As such,
they are located in the transition between the turbine and the condenser. Their location may be
[3-1]
subject to higher velocity and pressure variation. ASME PTC 12.2 recommends that the
sensing elements be located at least one foot (30 mm) but no more than three feet (90 mm) above
each tube bundle. A tube bundle is considered to be all tubes connected to a single-inlet
waterbox. For single-shell and multiple-shell condensers, there should be at least three
measurement points per tube bundle in each shell. For single-shell multi-pressure condensers,
there should be at least two pressure measurement points per tube bundle. If tube bundles are
arranged one on top of the other, measurement points need only be provided for the uppermost
bundle. Where three measurement points per tube bundle are required, they should be located
lengthwise near the quarter-points of the tube bundle. Where two measurement points per bundle
are required, they should be located lengthwise near the third-points of the tube bundle. In any
case, the lateral position of the measurement points should be as close to the lateral midpoint of
the bundle as possible.
[3-1]
ASME PTC 12.2 requirements are intended to establish rules for performing condenser
acceptance tests. For routine performance monitoring, the code requirements may be
unnecessary. If the existing pressure-sensing elements produce acceptable results, no
modification is required.

The second problem with many existing plant pressure-sensing elements is their installation.
[3-1]
PTC 12.2 recommends that basket tips be installed at an angle of 30 to 60 degrees from the
mean flow direction. The guide plates should be oriented so that the steam flow is parallel to the
guide plates. Pressure-sensing piping for pressure measurement should conform to the general
[3-2]
requirements of subsection 4.3 of PTC 19.2 .

The third problem with many exist plant sensing elements is the piping leading to the transmitter.
If there are any water pockets caused by condensation, they will influence the accuracy of the
reading. It is essential to slope the piping from the sensing element to the transmitter in a
continuous upward slope to allow any accumulated condensations to drain naturally to the basket
tip.

To further ensure the complete absence of water pockets in the sensing line, EPRI suggests using
automatic air purging before every reading. The schematic of the setup is shown in Figure 3-3[3-3].

3-3
Pressure Monitoring Practices

Figure 3-3
The Four-Tap Selector Connects the Basket Tips to the
Pressure Transducer and Purge Supply

Reference

[3-1] Performance Test Code on Steam Surface Condensers, ASME PTC 12.2 –1998. ASME,
New York, 1998.

[3-2] Performance Test Code on Instruments and Apparatus: Pressure Measurement, ASME
PTC 19.2 –1987. ASME, New York, 1987.

[3-3] MARK I Performance Monitoring Products, EPRI Report GS/EL-5648, September 1989.

3-4
4
FLOW MONITORING PRACTICES

Background

As mentioned previously, the cooling water (CW) flow rate is required to analyze condenser
performance. CW flow measurement is the most difficult task because of the large conduit and
the turbulent flow profile. The conduit can be as large as eight to ten feet (2 to 3 m) in diameter.
The flow pattern exiting the CW pump is turbulent. The limited straight length of conduit is not
long enough to establish laminar flow. To further complicate the measurement problem, most of
the conduit is buried underground, and access to sensing locations is very limited.

CW flow measurement methods are either periodic or continuous. Periodic CW flow


measurement methods include the dye dilution test and the velocity traversing method. Periodic
methods are frequently used to calibrate continuous flow measurement instruments. Periodic
water flow measurement is also used to determine the circulating water pump performance.

Over the years, a number of direct and indirect continuous flow measurement methods have been
developed. The direct flow measurement methods include the differential producer method and
the ultrasonic time-of-travel method. The indirect flow measurement methods include the
circulating water pump motor load method and the heat balance method.

Air in-leakage may cause high backpressure and increased dissolved oxygen in the condensate,
which in turn can increase corrosion potential and oxygen-scavenging chemical consumption.
Generally, air in-leakage flow monitoring is performed at the ejector or vacuum pump discharge.
The measured flow includes both non-condensible gas and moisture, and needs to be corrected to
indicate dry air flow rate.

Instruments

Rhodamine WT fluorescing dye is most commonly used for the dye dilution test. A precision
positive displacement pump is used to inject the concentrated dye solution, and a calibrated
precision fluorometer is used to measure the dye concentration.

The Fechheimer and Keil Pitot static-type probe, the insertion-type fiber-optic laser Doppler
velocimeter, and the insertion low-drag turbine flow meter are used for velocity traversing.

A precision differential pressure transmitter is used for the differential producer method.
Multiple-channel ultrasonic flow meters are employed for the time-of-travel flow measurement.

4-1
Flow Monitoring Practices

Total dynamic head readings are entered into the pump characteristic curve to determine the
flow.

The instruments used for air in-leakage monitoring include rotameters, orifice plates, and
electronic air in-leakage monitors.

Periodic Cooling Water Flow Measurement

Dye Dilution Test

The principle of the dye dilution test is that an unknown flow rate can be determined by adding
a known quantity of an easily identifiable tracer, mixing fully, and then measuring the resulting
concentration of the tracer in the flow. If this dye is injected at a constant rate, the relationship
between the concentration and the flow is as follows:

Q1 C1 = Q2 C2
Where: Q1 = dye injection rate
C1 = concentration of injected dye
Q2 = flow rate to be determined
C2 = concentration of diluted dye in water stream

Thus: Q2 = Q1 x C1/C2
C1/C2 is known as the “dilution factor” (DFt)

Rhodamine WT fluorescing dye is the most commonly used dye because it is non-toxic and
exhibits a minimal tendency to be adsorbed onto organic and in-organic surfaces. The dilution
factor of a solution cannot be measured directly, but it can be determined by comparing its
fluorescence (which is proportional to its concentration) with that of a specially prepared
“standard solution” of precisely known dilution. This standard solution is prepared by diluting
a sample of the injected dye by approximately the same amount as it will undergo when injected
into the system. The fluorescence levels of a test sample and of the standard solution are
measured in a fluorometer, and the dilution factor of the test sample is determined as follows:
DFt = DFs x Fs/Ft

Where: DFt = dilution factor of test sample


DFs = dilution factor of standard solution
Ft = fluorescence level of test sample
Fs = fluorescence level of standard solution

The flow to be measured is then:

Q2 = Q1 x DFs x Fs/Ft

4-2
Flow Monitoring Practices

The principle seems simple, but the accuracy of this method depends greatly on the experience
and accuracy of the tester. A detailed test procedure is given in Reference [4-1]. Numerous
companies provide this type of service.

The dye injection point for the test should be at the circulating water pump inlet. The sampling
point should be as far downstream as possible. A CW piping system with many twists and turns
provides better mixing and more accurate results. If the sample can be taken at the CW
discharge, then there will be no need to tap into the pipe. Samples from various cross-sections
of the sampling point should be taken to ensure the dye concentration is uniform. Chemical
injection, such as chlorine, into the CW must be stopped before the test. The dye should be
injected until the fluorescence level in the sample reaches a steady state before flow
determination data can be taken. The test sample should be allowed to reach the same
temperature as the standard solution prior to analysis, as the fluorescence intensity of the dye
varies with temperature. A well-conducted test can achieve accuracy within 2%.

Care must be taken to ensure that no flow is introduced or removed during the test. This method
may not be suitable for a CW system with high concentrations of organic growth and silt.
Additional information and applications can be found in references [4-2] and [4-3]. The method
is widely used in the hydroelectric industry to test the turbine efficiency. Typical costs range
from $10,000 to $20,000, depending on geographical location, number of tests, required support
for test preparations, and desired details of test reports.

Velocity Traversing Method

The velocity traversing method of CW flow measurement actually measures the local velocity of
the water in the conduit. The average velocity of the entire flow is then calculated based on the
local velocity on a volumetric weight basis. Since the diameter of the conduit is known, the
average velocity is used to calculate the water flow rate using the following equation:

Water Flow Rate = Water density x Velocity x Conduit diameter


[4-2]
The PTC 12.2 recommends the traverse be taken along at least three equally spaced diameters.
The traverse locations should follow the Chebyshef weighing scheme with at least ten points
along each diameter (Figure 4-1).

4-3
Flow Monitoring Practices

Figure 4-1
Recommended Velocity Traverse Locations
Source: ASME PTC 12.2

The water flow emerging from pumps, elbows, or piping diameter changes is very turbulent.
As a result, the velocity profile can be irregular and cannot be accurately measured. The flow
generally will straighten itself out over a straight length of pipe. PTC 12.2[4-2] recommends that
the traverse point be located with at least ten diameters of straight, unobstructed piping upstream
and five diameters of piping downstream. In practice, these restrictions may be relaxed
somewhat if the repeatability is good.

The measurement procedure depends on the traverse instruments used. Each instrument has its
[4-2]
limitations. Some work better than others in certain situations. PTC 12.2 lists some of these
limitations. Encor-America uses a low-drag insertion turbine flow meter that is believed to work
well without fully developed flow profiles[4-4].

4-4
Flow Monitoring Practices

Comparing the dye dilution test with the velocity traverse method, one can draw the conclusion
that the dye dilution tests work well with a complex piping system that increases the mixing
factor. On the other hand, the velocity traverse methods work well with a fully developed flow
profile. The dye dilution tests work better with a relatively clean piping system, while organic
growth and silt have no negative impact on velocity traverse methods. The dye dilution test will
have minimum intrusion into the piping system, but the velocity traverse method requires
tapping into the pipe. The velocity traverse method also requires that the pipe be full of water
at the measuring point. The dye dilution test does not have this requirement. Typical costs for
velocity traversing range from $3,000 to $10,000, depending on geographical location, number
of tests, required support for test preparations, and desired details of test reports.

CW Pump Curves and Total Dynamic Head Method

Pump total dynamic head (TDH) is the measure of energy added to the flow by the pump. It is
the algebraic sum of the static discharge head, the velocity head at the measurement point, and
the vertical distance from the measurement point to the water level in the pump bay (lift). TDH
is usually expressed in feet of water.

The static discharge head can be measured with piezometers, manometers, or calibrated pressure
gauges. If any of these instruments are located above or below the measurement point, the
distance should be subtracted from or added to the static discharge head. The velocity head is
calculated based on the estimated velocity of the water at the measurement point. The lift can be
measured with any suitable method, such as measuring tape or a fixed ruler. The computed TDH
in feet of water is entered into the pump characteristic curve to obtain the cooling water flow.

This simple method has a minimal need for additional instruments. It accuracy depends on the
accuracy of the pump curve. If the pump impeller is worn, the pump curve will not be accurate.
It is recommended that the pump curve accuracy be verified by one of the more accurate flow
tests, such as a dye dilution test.

It is possible to make this method a continuous cooling water flow monitoring method by
automating its measurements. The static discharge head can be measured with a pressure
transducer. The velocity head can be estimated. The lift can be measured with a remote-reading
level gauge (see Section 6 for details). All the data can be fed into a suitable computer or
processor, and the TDH will be automatically calculated and compared to the built-in pump
curve to obtain the flow rate. If one automates the system, the costs should be between $2,000
and $5,000. Otherwise, the costs are negligible. The verification of pump curves is not included
in this estimate.

Heat Balance Method

This method is not a direct measurement of cooling water flow. Instead, a heat balance is
performed on the turbine cycle to determine the heat rejection rate to the condenser (condenser
duty). With the known condenser duty, and the inlet and outlet cooling water temperatures, the
circulating water flow rate can be calculated.

4-5
Flow Monitoring Practices

Since the circulating water flow rate is calculated from the condenser duty and the cooling water
outlet temperature, the accuracy of the flow rate depends on the accuracy of these two
[4-2]
measurements. ASME PTC 12.2 recommends that the determination of the condenser duty
should be performed according to applicable sections of ASME PTC 6[4-5] for the testing of
turbines. Because of the complexity of this test, it is recommended that the condenser be tested
at the same time as the turbine. The advantage of this method is that the condenser duty is
determined directly without measurement, and therefore no instrument is required for the cooling
water flow. If the flow rate determined from this method is deemed accurate, this method may be
used to calibrate other continuous cooling water flow measurement devices. The cost is minimal,
assuming one does not include the turbine test and the cooling water outlet temperature
measurement.

Continuous Cooling Water Flow Measurement

Differential Producer Method

Differential-pressure flow meters have been used for decades. They provide a simple, reliable
method of measuring fluid flow with good results. The simplest meter is the orifice flow meter.
The pressure drop across an orifice is measured to determine the flow, which is proportional to
the square root of the differential pressure produced, according to the following equation:

____
W = C x √(∆H)

Where: W = flow rate


C = flow coefficient
∆H = pressure difference

The flow coefficient C depends on the geometry of the flow restriction. If C and the pressure
difference ∆H are known, the flow rate can be calculated.

The pressure difference ∆H can be determined by installing pressure taps upstream and
downstream of the flow restriction and measuring the pressure difference between them.
The pressure difference can be measured with any suitable device, such as a manometer or
an electronic differential pressure transmitter.

The flow coefficient C must be determined from calibration. To calculate C, one can pass a
known flow rate through the meter and measure the pressure difference ∆H, using the following
equation:
____
C = W √(∆H)

4-6
Flow Monitoring Practices

In condenser applications, the flow rate is determined using either the dye dilution test or the
velocity traverse method.

The traditional differential producer method of flow measurement uses orifice plates, flow
nozzles, venturi meters, or weir plates. However, none of these are suitable for condenser
applications because of the large size of the conduit and the low pressure head available for
measurement.

Two types of differential producers have been developed for condenser application. The first
uses the condenser outlet waterbox as the location for the differential producer. The second uses
any elbow in the conduit. Both types are based on the same operating principle, and only the
sensing points are different.

The TVA Engineering Laboratory first investigated the outlet waterbox as a location to produce
[4-6]
differential pressure for CW flow measurement . The schematic plan view and end view of the
setup are shown in Figures 4-2 and 4-3. The approach uses the existing abrupt contraction
created by the changing configuration from waterbox to pipe at the condenser outlet waterbox.
Because of the contraction, there is a flow separation in the pipe joining the condenser waterbox.
At this point the water pressure will be lower than the pressure in the waterbox. Tapping into
these two points and connecting them to a differential pressure (DP) transmitter provides the
flow measurement. The flow will be proportional to the DP between these two points. The flow
coefficient can then be determined on-line using either the dye dilution test or the velocity
traverse method.

The second method is to determine the DP across an elbow. When fluid moves around the
curved path of an elbow, it is subjected to an angular acceleration. The resulting centrifugal force
creates a DP between the inner and outer radii. The high-pressure tap is on the outside of the
[4-4]
elbow and the low-pressure tap is on the inside, as shown in Figure 4-4 . This flow measuring
device must also be calibrated on-line.

4-7
Flow Monitoring Practices

Figure 4-2
Water Flow Through Condenser

Figure 4-3
Flow Through an Abrupt Contraction

4-8
Flow Monitoring Practices

Figure 4-4
Elbow Differential Pressure Method

Tests show that the elbow-flow DP method and the waterbox-to-pipe DP method track each
other closely. Both methods require that the measuring point be full of water. The elbow-flow
DP method requires that the elbow bend in only one plane. According to one vendor, the elbow-
flow DP method has several advantages over the waterbox DP method: (1) a higher DP is
available for measurement, and (2) the elbow-flow DP method may be applied in the event the
waterbox approach is not feasible. For example, if the condenser has one conduit supplying
water to two waterboxes/bundles in parallel, it would be easier to take the DP across the elbow
before the separation. In another case, when the circulating water downstream of a condenser is
below atmospheric pressure, the outlet waterbox is not a suitable location to measure DP,
because it may not be full of water. The elbow in the supply line would be a better location.

The maintenance required for these two DP methods includes routine blowdown of the pressure-
sensing line and the periodic calibration of the pressure transmitter. The cost for each of these
systems is in the range of $20,000 to $30,000, including instruments and calibration.

Ultrasonic Time of Travel Method

There are a number of ultrasonic flow meters available on the market. They include the time-of-
travel system, the sing-around system, the leading-edge system, and the Doppler system. Only
the multiple-pass time-of-travel system provides sufficient accuracy for measuring water flow

4-9
Flow Monitoring Practices

through large conduits and open channels such as a circulating water system. This method
involves the measurement of travel times of acoustic energy transmitted forward and backward
along a number of chordal paths (typically four) positioned on an angled acoustic plane across a
pipe, as shown in Figure 4-5.

Figure 4-5
Diagram of Four-Path Ultrasonic Flow Meter

This system uses a high-frequency sonic wave that is beamed at an acute angle across the pipe,
as depicted in Figure 4-5. When the wave is transmitted through the water in the direction of the
flow, its velocity increases. When the wave is transmitted through the water against the direction
of the flow, its velocity decreases. Given the speed of the sound wave in water and the angle
between its direction and the flow pass, the average water velocity on the flow path can be
calculated. Since the velocity in the pipe is not uniform, a four-path system provides an average
water velocity. The flow rate is calculated from the average velocity.
[4-2]
The ASME PTC 12.2 recommends that the metering section should be preceded by at least ten
diameters and followed by at least three diameters of straight pipe. In practice, this restriction
may be relaxed somewhat. In a case where there is a very short straight run (less than five pipe
diameters) upstream of the measuring section, it is likely that the flow will be very turbulent.
The manufacturer recommends that a second “crossed path” be installed at 90 degrees to the first
crossed path to eliminate the cross-flow error.

To calibrate this system, precise measurements of the distance between the transducers, the angle
of the transducers with respect to the centerline of the pipe, and the physical dimension of the
pipe are required. No on-line calibration, such as in the dye dilution or velocity traverse tests, is
required. An accuracy of 1% can be accomplished with this system. Entrained air bubbles in the

4-10
Flow Monitoring Practices

water, silt and other particulate in the water, and a partially full water pipe can all affect the
accuracy.

Periodic cleaning of the transducers is required to prevent algae growth, which in turn affects the
measurement. The transducers can be installed from inside the pipe. However, for ease of
maintenance, tapping into the pipe and mounting the transducers on a flanged, removable plate
is desirable.

EPRI tested one ultrasonic flow meter widely used in the hydroelectric industry[4-7]. Even though
it was installed in a rectangular channel, favorable results were reported[4-8]. The cost for this
system is in the range of $100,000 to $150,000.

Air In-Leakage Flow Monitoring

Rotameter

Most plants are equipped with a rotameter for air in-leakage monitoring. The rotameter is a
variable-area flow meter. It is composed of a tapered metering tube, mounted vertically with the
small end at the bottom, and a float that is free to move up and down in the tube. Flow enters the
rotameter at the bottom, passes around the float and leaves the meter at the top. Figure 4-6 shows
a schematic of a typical rotameter.

Figure 4-6
Schematic of Rotameter

Under no-flow conditions, the float rests at the bottom of the tapered tube. When flow enters the
tube, it passes through an annular space between the float and the tube wall, creating a pressure
drop across the float. This pressure drop raises the float to increase the flow area between the
float and the tube to reach dynamic equilibrium. At this equilibrium the upward forces on the
float are balanced by the weight of the float. Any further increase in flow causes the float to rise
higher in the tube; a decrease in flow causes the float to drop. For a fluid of a given density and
viscosity, the float position corresponds to a unique flow rate. Flow rate is determined by direct

4-11
Flow Monitoring Practices

observation of the position of the float in the metering tube. The tube is marked to indicate the
flow rate. The calibration is completed in the factory.

In power plant air in-leakage applications, the rotameter is located at the steam jet ejector or
vacuum pump discharge on a bypass line. Normally, the exhaust is vented through the main line.
When taking rotameter readings, the main line is closed with a butterfly valve.

Fluctuations in temperature change the fluid density and viscosity, which in turn affect the
accuracy of the rotameter. Therefore, the rotameter provides only an approximate indication of
the air in-leakage rate. To improve accuracy, temperature and pressure readings may be taken at
the condenser vent connection, and these can be used to correct the air in-leakage rate, according
[4-2]
to Appendix H of ASME PTC 12.2 .

The second drawback of the rotameter is that it creates an additional pressure drop when taking
the reading, and thus affects the accuracy of the reading. The third drawback is that the rotameter
is read manually. Continuous reading of a rotameter is very difficult, although a magnetic
technique to determine float location has been used to take continuous readings. The advantage
of the rotameter is that it is inexpensive. There will be no cost incurred if the unit is already
equipped with a rotameter.

Orifice Plate

The principle of using an orifice plate for flow measurement is similar to using the condenser
outlet waterbox. A differential pressure transmitter may be installed across the orifice plate for
continuous reading. A schematic of the installation is shown in Figures 4-7 and 4-8.

Figure 4-7
Orifice Plate Installation

4-12
Flow Monitoring Practices

Figure 4-8
Schematic for Differential Pressure Transmitter Installation

ASME PTC 12.2[4-2] recommends using an orifice plate for non-condensible flow measurement.
The orifice plate should meet the specifications described in ASME-MFC-3M[4-9]. Detailed
[4-10]
installation requirements are given in ASME PTC 19.5 .

The orifice plate air in-leakage system offers better accuracy and is more suitable for continuous
flow monitoring. To improve accuracy, temperature and pressure readings may be taken at the
condenser vent connection to correct the air in-leakage rate, according to Appendix H of ASME
PTC 12.2[4-2]. Installation of the orifice plate air in-leakage monitor will require some piping
modifications and will be more expensive than a rotameter. The cost is estimated to be in the
$7,000-to-$10,000 range per vacuum equipment discharge location.

4-13
Flow Monitoring Practices

Electronic Air In-Leakage Monitor

The electronic air in-leakage monitor consists of one or more insertion probes, a digital
processor, and interconnect cables. The probe is an assembly of four primary sensors that
measure flow, temperature, pressure, and relative saturation. The total mass flow of the water-
vapor/air mixture is measured. Actual water vapor flow rate is subtracted from the total mixture,
yielding the precise air in-leakage flow rate.

Because the electronic air in-leakage monitor measures all four parameters, and the digital
processor is capable of subtracting water vapor from the total mixture in these measurements,
it is a more precise instrument for air in-leakage monitoring. The drawback is that it is very
expensive. Since the monitor includes many sensing instruments, the maintenance costs may
also be high. The installed cost is approximately $20,000 to $25,000 per measurement point.
While small units usually have three measurement points, a large unit can have up to twelve.

4-14
Summary
Table 4-1
Circulating Water Flow Monitors

Monitor Type Cost Pro Con


Dye dilution test $10K- Suitable for complex piping system. Organic growth and silt affect accuracy.
$20K No tapping into the pipe required. No flow introduced or removed.
Pipe need not be full of water. Not suitable if dye mixing is incomplete.
Not suitable for continuous monitoring.
Velocity Traversing $3K- Not affected by organic growth or silt. Not suitable for complex piping system.
$10K Tapping into the pipe required.
Pipe must be full of water.
Not suitable for continuous monitoring.
Pump Curves & TDH $5K Minimum additional instruments required. Accuracy depends on accuracy of the pump curve and
May be made into a continuous flow monitor. condition of the pump.
Periodic testing is required to verify the accuracy of the
pump curve.
Heat Balance $0 Inexpensive if tested with steam turbine testing. Accuracy depends on the accuracy of condenser duty and
No additional instruments required. the outlet water temperature.
May be used to calibrate other monitor. Not suitable for continuous monitoring.
DP outlet waterbox $20K- Inexpensive. Pipe must be full of water.
$30K Suitable for continuous monitoring. On-line calibration required.
DP Elbow $20K- Inexpensive. Pipe must be full of water.
$30K Higher DP than outlet waterbox method. The elbow must bend in one plane.
Suitable for multiple waterbox/bundle. On-line calibration required.
More choice of monitoring point.
Suitable for continuous monitoring.
Ultrasonic Flow meter $100K Provides continuous monitoring. Entrained air bubbles, silt, and partially filled pipe may affect
No on-line calibration is required. accuracy.

4-15
Flow Monitoring Practices

Table 4-2
Air In-Leakage Flow Monitor

Monitor Type Cost Pro Con

Rotameter $0 - $2K Inexpensive. Less accurate.

Additional pressure drop.

Not suitable for continuous monitoring.

Orifice Plate $7K-$10K More accurate. Additional pressure drop.

Continuous reading. More expensive.

Electronic Monitor $20K- Most accurate. Most expensive.


$25K
Continuous reading. Maintenance cost may be high.

4-16
References

[4-1] Calibration of Dye Dilution Method of Flow Measurement, CEA No. 320 G 396,
December 1987

[4-2] Performance Test Code on Steam Surface Condensers, ASME PTC 12.2 –1998. ASME,
New York, 1998.

[4-3] Schagunn, J., Missimer, J., “Demonstration of Dye Dilution for Determining of Circulation
Water Flow Rate”, Presented at the EPRI/ASME Heat Rate Improvement Conference,
Knoxville, TN, 1989.

[4-4] Diaz-Tous, I. A., Leggett, M., Hill, D., Low-Drag Insertion Turbine Flow Measurement
Technology for Circulating Water Systems Without Fully-Developed Flow Profiles, EPRI Report
TR-106781, August 1996.

[4-5] Performance Test Code on Steam Turbines, ASME PTC 6 –1996. ASME, New York,
1998.

[4-6] March, P. A., Almquist, C. W., Technique for Monitoring Flowrate and Hydraulic Fouling
of Main Steam Condenser, EPRI Report CS-5942-SR, September 1988.

[4-7] MARK I Performance Monitoring Products, EPRI Report GS/EL-5648, September 1989.

[4-8] On-Line Condenser Cooling Water Flow Measurement, EPRI FS-9102, 1991.

[4-9] Measurement of Fluid Flow in Pipe Using Orifice, Nozzle and Venturi, MFC-3M-1989,
ASME, New York, 1990.

[4-10] Instruments and Apparatus: Part II of Fluid Meters, ASME PTC 19.5, ASME, New York,
1972.

4-17
5
FOULING MONITORING PRACTICES

Background

Fouling reduces the condenser performance in a number of ways. Fouling is further classified
as microfouling and macrofouling. Microfouling consists of biological fouling, precipitation
fouling, particulate fouling, and corrosion fouling. Microfouling forms deposits inside the
condenser tubes. It mainly increases the heat transfer resistance between the steam and water
and in turn decreases the amount of heat that can be dissipated through the cooling water.

Macrofouling consists of marine animals and plants, biological growth, and debris carried over
by water. The macrofouling can foul the cooling water system, including the intake system and
the flow conduit, and block the tubesheet flow area. It mainly increases the flow resistance,
which in turn reduces the cooling water flow rate and again decreases the amount of heat that
can be dissipated through the cooling water.

Reducing heat dissipation in the condenser in turn increases the condenser backpressure and
turbine cycle heat rate. For this reason, it is important to monitor fouling. When the monitor
indicates that the condenser is excessively fouled, appropriate remedial action can be taken.

Using other condenser performance data, including backpressure, heat rejection rate, cooling
water inlet and outlet temperatures, and cooling water flow rate; the condenser performance
factor (also known as the cleanliness factor or fouling factor) can be calculated. This is a method
to monitor condenser performance. However, the reduction in condenser performance may or
may not be solely due to fouling. For this reason, it is desirable to use fouling monitors to
monitor the actual fouling of the condenser tubes or other components in the system.

Instruments

Microfouling monitors can be classified as on-line or off-line monitors. On-line fouling monitors
include both in-situ and side-stream monitors. The in-situ fouling monitor also consists of
periodic and continuous monitors. The side-stream fouling monitor includes full-scale and
reduced-scale monitors, and is very useful in simultaneous evaluation of treatment options.
Off-line fouling monitors are also used to evaluate treatment options and effectiveness. All the
microfouling monitors are specialty products. The operating principles, construction details, and
sources will be discussed in the text.

Macrofouling monitors are all on-line. One uses the differential water level between the intake
and the pump bay to monitor macrofouling of the traveling water screen. The other uses the

5-1
Fouling Monitoring Practices

differential water pressure between the inlet and outlet waterboxes to monitor the tubesheet
fouling.

Off-Line Microfouling Monitor

Conco Systems (www.concosystems.com) offers an off-line condenser fouling test apparatus


(Figure 5-1). This test apparatus consists of four removable tubes (36 inches [91 cm] long) in
a shell. Cooling water is circulated through the tubes. Steam is generated in the shell using an
electric heater. Tubes to be evaluated are sent to Conco from the condenser in question. These
tubes are loaded into the test apparatus. Testing is conducted at the customer specified heat flux,
water velocity, and range of water temperature. Comparisons can be made between the as
received tubes (fouled) and the new, mechanically cleaned or chemically cleaned tubes. Results
of each test are expressed as overall heat transfer coefficients, fouling factors, and cleanliness
factors. The costs of the tests are $1,900 for start-up of the apparatus and the first U coefficient,
and $500 for each additional U coefficient determination.

Figure 5-1
Conco Heat Transfer Testing Unit

Strictly speaking, this apparatus is an off-line fouling test apparatus rather than a fouling
monitor. As such, it is ideal for evaluating the effectiveness of cleaning methods. The drawback
of this method is that it requires removal of a tube from the operating condenser. The removed
tube must be representative of the fouling condition, and must also be carefully preserved and
packed for shipping to Conco to prevent a change in fouling condition, such as drying out.

5-2
Fouling Monitoring Practices

On-Line Microfouling Monitor

Bridger Scientific Continuous Side-Stream Reduced-Scale On-Line Microfouling


Monitor

Bridger Scientific’s (www.bridgersci.com) DATS side-stream fouling monitor has been in


existence for a long time. This monitor consists of a tube wrapped with an electric heater block
(five inches [13 cm] long) (Figure 5-2). A side-stream of cooling water is fed through the tube
section at a controlled rate. The electric heater block surrounding the tube simulates the actual
heat load of the condenser tube. Calibrated temperature probes measure both the fluid and heater
temperatures. These data, the flow rate and heat flux are used to automatically calculate the heat
transfer resistance. All heat transfer data are then provided as analog output. Changes over time
accurately reflect the accumulation of the fouling deposit. The cost for the system is $9,500.

Figure 5-2
DATS Heat Exchanger Cross-Section View

The advantage of this monitor is that it is relatively small and inexpensive. Since it is off-line, it
can also be used to evaluate other treatment programs. The drawback of this monitor is that the
heated section is very small. It is not possible to simulate the fouling of the entire condenser
tube.

Bridger Scientific Continuous Small On-Line Microfouling Monitor

Bridger Scientific’s (www.bridgersci.com) new ProDATS insertion fouling probe is in the final
testing stage (Figure 5-3). This device consists of two independent sensing assemblies in a single
probe configuration. The probe may be directly inserted into any pipe two inches (5 cm) or
greater via a “hot tap” assembly, or it can be operated as a side-stream system with the addition
of a clamp-on assembly. The primary sensing element is a heat transfer sensor, which is
complemented by a secondary magnetic flow sensor. Mounted below the flow sensor are two
identical 0.25 inch (0.64 cm) tubular sections, each electrically isolated from the other and
wound with electrically heated wire. Cooling water flows through these two tube sections.
Electric current flowing through the wound wire causes the temperature of the tube to rise, which
can be accurately monitored by measuring the wire resistance. Cooling water flowing through
the tubes removes heat from the tubes thereby reducing their temperature rise. Since clean tubes

5-3
Fouling Monitoring Practices

will transfer heat to the cooling water with higher efficiency for the same flow rate, the sensing
elements will experience a relatively small temperature rise compared to the fouled tube. By
measuring the temperature rise of the sensing elements above that of the cooling water, and
knowing the flow passage dimensions, a heat transfer value can be calculated which over time is
related to the fouling deposit buildup on each heated surface. The total fouling can be determined
this way.

Figure 5-3
ProDATS Probe and its Schematic

The second use of this probe is to measure the difference between these two tube sections and in
turn determine fouling caused by different mechanisms. There are several ways to make the two
sensing sections foul in different modes. One way is to periodically inject chemicals to prevent
one tube section from microbial fouling. The second way is to generate chlorine
electrochemically in a seawater-cooled system by applying electric currents to one tube section.
The two sections will experience the same abiotic fouling (scaling) but different microbial
fouling. If one subtracts this component from the untreated sensing element, one will have a
measure of just the microbial component. By using this approach, one can quantify the total
fouling, microbial fouling and abiotic fouling occurring, which can be very useful in developing
an overall optimal treatment or control program. The cost for the system is approximately $2,500
to $3,000.

The advantages of this monitor are that it is very small, inexpensive and can be inserted on-line.
It can also be used to differentiate microbial fouling from scaling. The primary drawback is that
the heated section is very small. It is not possible to simulate the fouling of the entire condenser
tube.

5-4
Fouling Monitoring Practices

Conco Systems Continuous Side-Stream Reduced Scale On-Line


Microfouling Monitor

Conco Systems (www.concosystems.com) offers a portable test condenser (Figure 5-4). The
portable test condenser is a single-tube (36 inches [91 cm] long), self-contained model
condenser. The portable condenser is installed alongside the unit condenser.

Figure 5-4
Conco Portable Test Condenser

The portable test condenser is a shell-and-tube heat exchanger with an integral electric heater.
Demineralized water and water vapor occupy the shell space. Air is removed from the shell prior
to startup with a vacuum pump. Cooling water is passed through the test tube section, and the
electric heater is energized to generate steam. Steam is condensed on the tube to transfer heat to
the tube wall and cooling water.

Fouling detection is accomplished by monitoring the initial temperature difference (ITD), which
equals steam temperature minus inlet water temperature. When a tube is fouled, the heat transfer
capability of the tube will decrease, causing the steam temperature and, in turn, the ITD to
increase. As with an actual surface condenser, ITD will vary with inlet water temperature.
This necessitates the preparation of a calibration curve. A comparison of measured ITD to
the calibration curve allows for detection of fouling and/or relative degree of fouling.

Foulant mass can be quantified by removing the deposit with a mechanical cleaner and
determination of weight. Fouling can also be determined by comparing the ITD before and after
cleaning with a mechanical cleaner or with chemical cleaning. The portable test condenser can
also be used to evaluate the chemical treatment program. The cost for the system is $12,000 to
$18,000, depending on the configuration.

The advantage of this test condenser is that it is portable. A utility can move the monitor around
and test the fouling tendency in more than one condenser. The foulant mass can easily be

5-5
Fouling Monitoring Practices

quantified. It can also be used to evaluate corrosion control optimization and the replacement
tube material. The drawback of this test condenser is that the tube is relatively short. It may not
duplicate the fouling occurring in the actual condenser.

Periodic In-Situ On-Line Microfouling Monitor

ASME PTC 12.2[5-1] recommends an in-situ on-line fouling monitor. This monitor uses a pair of
condenser tubes. During an outage, it is either cemented to the tubesheet or installed on a tube
extension that attaches RTDs or thermocouples to the outlet of this pair of tubes. One tube is
thoroughly cleaned. By comparing the performance of these two tubes, the fouling factor can be
determined. Details of the installation and other requirements are contained in PTC 12.2[5-1].
Strictly speaking, this is a fouling test rather than a monitoring method.

The advantage of this method is that it is simple and effective with minimal additional
investments. It determines the current fouling condition of the entire tube. The major drawback
of this method is that it is not continuous monitoring. It requires an outage to install the
temperature sensors and to clean the reference tube. The existing plant instruments are relied
on for backpressure and cooling water flow rate measurements. These data may or may not be
accurate. If these data were inaccurate, the accuracy of the fouling factor would be inaccurate,
although the impact would be proportionally less. The cost of conducting this test depends on
what needs to be done and whether the tester can complete the test in one trip.

Thermal Engineering Consultants (www.tecus.com) offers a service to conduct fouling tests with
this method.

EPRI Continuous In-Situ On-Line Microfouling Monitor

EPRI funded Bridger Scientific, Inc. in the development of this in-situ on-line fouling monitor
(Figure 5-5). This monitor uses a pair of actual adjacent condenser tubes. One tube is designated
as an “active” tube, and the other is designated as an “inactive” tube, which is plugged on both
ends. The monitor is mounted on the outlet tubesheet of these two tubes. The part of the monitor
connected to the active tube contains the ultrasonic flow sensor and the discharge cooling water
temperature sensor. The part of the monitor connected to the inactive tube contains an inlet
cooling water temperature sensor and two spring-loaded steam temperature sensors, which are
inserted into the tube to measure the steam temperature in the first half and the second half of the
tube. The measurements are digitized locally and transmitted to the outside via an RS-485 link to
a remote computer through an appropriate opening on the condenser waterbox. A critical feature
of this monitor is that the inside diameter of each monitor assembly is machined to precisely
match the condenser tube. Typically, four monitors are used for each condenser to provide
diversity and redundancy.

5-6
Fouling Monitoring Practices

Figure 5-5
On-Line Fouling Monitor

Knowing cooling water flow velocity, inlet and outlet cooling water temperature, and steam
temperature, the heat transfer coefficient can be calculated. The calculated heat transfer
coefficient is compared to the HEI or ASME theoretically achievable heat transfer coefficient
based on the operating conditions. The fouling factors and cleanliness factors are deducted from
this comparison. The detailed design of the monitor and the calculation procedure are contained
[5-2]
in an EPRI report . The cost for the system is approximately $55,000, including four probes
and software.

The advantage of this monitor is that it directly measures the heat transfer of an entire operating
condenser tube. The inlet and outlet cooling water temperatures are measured directly. The steam
temperature is measured directly rather than from pressure measurement. Because there is no
cooling water flow in the blocked-off tube, the wall temperature comes into equilibrium with the
surroundings and represents the steam temperature at that position of the condenser. The cooling
water velocity is also measured directly and represents the actual cooling water flow through that
tube. The drawbacks of this monitor are that it is more expensive, and it requires plugging of
some tubes and a short outage to install the monitors.

Taprogge Continuous In-Situ On-Line Microfouling Monitor

The Taprogge (www.taprogge.com) condenser monitoring system (Figure 5-6) was developed
mainly for monitoring and controlling the Taprogge tube cleaning system, which uses sponge
balls circulating through the tubes to clean them. Since the sponge ball will wear out over time,
the need to replace these balls is determined by measuring the effectiveness of the sponge ball
wiping action. This monitor is also used to measure and control ball circulation.

5-7
Fouling Monitoring Practices

Figure 5-6
Taprogge Monitoring System

The monitoring system utilizes a row of six tubes in the operating condenser. The two outer
tubes are used to anchor the sensor probe. One tube is plugged on both ends with spring-loaded
thermocouples to measure the steam temperature. Six thermocouples are located at the inlet and
outlet of three tubes to measure the inlet and outlet cooling water temperature. One of these tubes
is used to measure the cooling water velocity. This is accomplished by periodically injecting hot
water at the tube inlet end. Measuring the time required for the hot water to travel to the outlet
end determines the water velocity. The other two tubes are used to measure the effectiveness of
the sponge balls. This is accomplished by comparing the outlet cooling water temperature of
these two tubes when a sponge ball enters one of the tubes. The corresponding software
calculates the heat transfer coefficient of the individual tubes from the measured temperature
difference and, in turn, determines the effectiveness of the sponge ball. The cost for the system,
including software and four probes, is $150,000 to $200,000, depending on the configuration.

The advantage of this system is that it monitors not only the condenser performance but also the
effectiveness of the sponge ball cleaning system. The major drawback of this system is that it is
very expensive. It would not be cost effective if the condenser in question did not have a sponge
ball cleaning system. It also requires plugging some tubes and a short outage to install the
monitors.

5-8
Fouling Monitoring Practices

On-Line Macrofouling Monitor

Intake On-Line Macrofouling Monitor

A typical cooling water intake system is shown in Figure 5-7. Here the trash bars and traveling
water screens are used to protect the condenser and the circulating water system from
macrofouling. However, when the trash bars and traveling water screens are overloaded, the
water level in the pump bay will decrease, providing less net positive suction head (NPSH) and
reducing the circulating water pump efficiency, which results in less cooling water flow through
the condensers. Generally, the macrofouling situation is monitored manually by operator
observation. The purpose of the on-line macrofouling monitor is to provide early warning about
any potential problem.

Figure 5-7

Typical Cooling Water Intake System

The principle of the on-line macrofouling monitor is to monitor the water level in the water
source, in the fore bay behind the trash bar, and in the pump bay. Whenever the difference in
water levels between these three places exceeds a preset limit, a warning signal will alert the
operator to take appropriate action. There are a number of ways to measure the water level
remotely, including capacitance, ultrasonic, differential pressure, and bubbler level detectors.
The details of these level detectors will be discussed in Section 6. A typical application using
an ultrasonic level detector is shown in Figure 5-8.

5-9
Fouling Monitoring Practices

Figure 5-8
Typical Ultrasonic Microfouling Monitoring System

Tubesheet On-Line Macrofouling Monitor

The tubesheet on-line fouling monitor measures the differential pressure between the inlet and
outlet waterbox. Pressure taps are installed at the inlet and outlet waterbox and connected to a
manometer or pressure transducer. Any significant increase in differential pressure indicates
macrofouling of the tubesheet. Since the differential pressure is also a function of the flow rate,
additional pressure taps are installed to monitor the flow rate. This setup was tried at TVA in
[5-3]
conjunction with a flow measurement investigation . The TVA installation is shown in
Figure 5-9.

5-10
Fouling Monitoring Practices

Figure 5-9
TVA Tubesheet Macrofouling Monitor

5-11
Summary
Table 5-1
Microfouling Monitor

Monitor Type Cost Pro Con


Conco Tube HT Tester $3.4K Ideal for evaluating cleaning method and Not a continuous monitoring method.
effectiveness. Requires removal of tube.
Removed tube must be representative of fouling
condition.
Removed tube must be preserved during
shipping.
DATS $9.5K Relatively small and inexpensive. Heated section is very small.
Can be used to evaluate water treatment
program.
ProDATS $2.5K –$3K Very small and inexpensive. Tube diameter and heated section are very
Can differentiate microbial fouling and scaling. small.
Portable Test Condenser $12K- Portable. Test tube is short.
$18K Corrosion and replacement tube evaluation.

ASME Method N.A. Minimal additional investment. Not a continuous monitoring method.
Measures entire tube. Requires outage to install sensor and to clean
tube.
Relies on plant instrument for backpressure and
flow measurements.
EPRI On-line Monitor $55K Direct measurement of fouling of an entire More expensive.
tube. Requires plugging of some tubes and a short
Accurate cooling water inlet/outlet and steam outage to install.
temperature measurement.
Accurate cooling water velocity measurement.
Taprogge On-Line Monitor $150K- Direct measurement of fouling of an entire Most expensive.
$200K tube. Requires plugging of some tubes and a short
Accurate cooling water inlet/outlet and steam outage to install.
temperature measurement.
Accurate cooling water velocity measurement.
Also monitors sponge ball effectiveness.

5-12
References

[5-1] Performance Test Code on Steam Surface Condensers, ASME PTC 12.2 –1998. ASME,
New York.

[5-2] On-line Condenser Fouling Monitor Development, EPRI Report TR-109232, EPRI,
December 1997.

[5-3] March, P. A., Almquist, C. W., Technique for Monitoring Flowrate and Hydraulic Fouling
of Main Steam Condenser, EPRI Report CS-5942-SR, September 1988.

5-13
6
LEVEL MONITORING PRACTICES

Background

In a condenser system, the water level needs to be monitored in four places: the condenser
hotwell, the inlet and outlet waterboxes, and the intake.

In the hotwell, the condensate level needs to be maintained to provide net positive suction head
(NPSH) for the condensate pump.

In the inlet and outlet waterboxes, the water level needs to be monitored to make sure the
waterboxes are full of water. If the waterboxes are not full, the tubes on the top portion of the
tube bundle will not have water flowing through them, and those tubes will not condense steam.
Condenser backpressure will suffer as a result.

In the intake, especially the pump bay, the water level needs to be monitored to make sure there
is sufficient NPSH for the circulating water pump. If the NPSH is not sufficient, the pump will
cavitate, resulting in a reduction in water rate and possible damage to the pump. See Section 5
on Macrofouling Monitoring for more details.

Instruments

Sight glasses are most commonly used to monitor water level locally. Flexible transparent tubes
are used to monitor water level in the waterboxes. These are simple devices and need not be
elaborated on.

There are a number of ways to measure the water level remotely, including capacitance,
ultrasonic, differential pressure, and bubbler level monitors. All of these are suitable for
monitoring the water level in the intake.

The capacitance level detectors measure the changes in electric capacitance that occur between
the sensing conductors as the water level changes. A capacitance level measuring system consists
of a probe lowered into the bottom of the water body and connected to a transmitter mounted on
a platform above the highest anticipated water level.

Operation of the ultrasonic level detector is based on the time required for a sonic wave to travel
from a transducer to the water level being measured and back to the transducer. The total travel
time is proportional to the water level. The transducer is mounted on a platform above the
highest anticipated water level.

6-1
Level Monitoring Practices

Operation of the pressure differential level detector is based on measuring the pressure difference
sensed by the unit between its high- and low-pressure sides. The high-pressure side of the unit is
connected to the bottom of the bay and the low-pressure side is open to the atmosphere. The
measured hydraulic head is directly proportional to the water level. The differential pressure
transmitter is mounted on a platform above the highest anticipated water level.

The bubbler level detector is a differential pressure level detector with an air purge system.
Operation of this instrument is based on the differential pressure required for an air flow stream
to overcome the liquid head of the water. The pressure reading is proportional to the water level.
The air supply transmitter is mounted on a platform above the highest anticipated water level.

Details of these instruments are contained in Reference [6-1].

Hotwell

The hotwell is usually equipped with a sight glass and a float or other suitable liquid level
controller.

Waterboxes

Waterboxes are usually equipped with a sight glass. However, many sight glasses do not reach
the top of the waterbox. If the waterbox is not completely full, the sight glass will not provide the
necessary indication. This situation is especially common with outlet waterboxes, because water
pressure in many outlet waterboxes is below atmospheric pressure. It is recommended that a
transparent flexible tube be used to monitor the water level in the inlet and outlet waterboxes.
The top connection for the transparent flexible tube should be at the highest point of the
waterbox.

Many sight glasses installed on condenser waterboxes are fouled to the point that the water level
is impossible to observe due to algae growth. It is difficult to clean the sight glass. In comparison,
a transparent flexible tube is inexpensive, and one can simply replace it when fouled. It is
essential to make sure the flexible tube connection is air tight to prevent air from leaking into
the system, especially if the waterbox is under negative pressure.

Intake

Typical cooling water intake systems, using ultrasonic level indicators and macrofouling
monitoring systems, are discussed in Section 5. Additional typical installations using other level
detectors are shown in Figures 6-1, 6-2, and 6-3.

6-2
Level Monitoring Practices

Figure 6-1
Typical Installation of Capacitance Level Monitor

Figure 6-2
Typical Installation of Submersible Differential Pressure Level Monitor

6-3
Level Monitoring Practices

Figure 6-3
Typical Installation of Bubbler Level Monitor

The accuracy of the monitoring system is not that important. The cost for each of these systems
varies from approximately $3,000 to $5,000. The choice depends on personal preference,
availability of process supply (electricity and air), and local conditions. For example, the bubbler
detector requires compressed air. If compressed air were not available at the intake, it would be
expensive to run a compressed air line to that location. Water level turbulence (barge traffic),
foaming, floating debris, and biofouling often make one detector more favorable than the other.
Refer to the summary subsection for details.

6-4
Summary
Table 6-1
Remote Level Monitors

Monitor Type Pro Con

Capacitance No moving parts, minimum maintenance. Grease buildup can affect accuracy, needs cleaning.

Not affected by foam and floating debris. Barge traffic will give false reading.

Ultrasonic No moving parts, minimum maintenance. Affected by foam and floating debris.

Barge traffic will give false reading.

Differential Pressure No moving parts, minimum maintenance. Barge traffic will give false reading.

Not affected by foam and floating debris.

Bubbler Not affected by foam and floating debris. Air supply required.

Not affected by barge traffic. Pressure regulator, flow controller and flow tube require maintenance.

Fouling will affect accuracy.

6-5
References

[6-1] Instrumentation Handbook for Integrated Power Plant Water Management, EPRI Report
CS-5873, July 1988.

6-6
7
DISSOLVED OXYGEN MONITORING PRACTICES

Background

Dissolved oxygen (DO) in the condensate causes corrosion of power plant components. Oxygen-
scavenging chemical consumption increases as the amount of dissolved oxygen increases. It is,
therefore, important to monitor oxygen content in the condensate and take appropriate action
when needed.

The condenser is the major source of dissolved oxygen in the condensate. The oxygen comes
from air in-leakage and make-up water. For boiling water reactor power plants, additional
oxygen may come from the reactor. A properly designed condenser and non-condensible
removal system should be capable of producing condensate with the desired oxygen content
(from 7 ppb to 42 ppb) as defined in Reference [7-1]. A sub-cooled condensate will contain more
oxygen. Therefore, a properly designed condenser should reheat the condensate before reaching
the hotwell.
[7-2]
ASME PTC 12.1 recommends that the sampling point for DO be located at the condensate
outlet piping as close to the hotwell as possible. At this point, the condensate is under vacuum,
and a pump is required to extract condensate from the pipe. There is also the potential for air to
leak into the condensate if the sample line from the pipe to the pump is not completely airtight.
To make sample extraction easier, many utilities elect to take the sample at the discharge of the
condensate pump. In this case, the potential for air ingress exists if the condensate pump seal is
not completely airtight.

DO monitoring methods include wet chemical analysis and in-line DO analyzers. Wet chemical
analysis will not be discussed here. The reader can refer to References [7-3] and [7-4] for more
information.

Instruments

Several companies make DO analyzers. They all have similar construction and are based on the
same operating principle. The analyzer consists of a probe containing the oxygen measuring cell
and the electronics, which are housed in a waterproof case. The probe may be installed in the
pipe or in its own flow-through chamber. The probe is covered with an oxygen permeable
membrane. Inside the probe is the actual measuring cell. The cell consists of an insulating
substrate that supports two types of noble metal electrodes immersed in an electrolytic solution.

7-1
Dissolved Oxygen Monitoring Practices

In operation, the oxygen diffuses through the membrane into the electrolyte. Electric potential is
applied between the electrodes to reduce the oxygen. The electric current required to reduce the
oxygen is interpreted as specific units of measurement on the instrument display.

One should follow the manufacturer’s instructions for installing and calibrating the analyzer.
Frequent maintenance, including electrolyte and membrane change and recalibration, is required
to insure accuracy.

References

[7-1] Standards for Steam Surface Condensers, Heat Exchange Institute, Ninth Edition, 1995.

[7-2] Performance Test Code on Steam Surface Condensers, ASME PTC 12.2 –1998. ASME,
New York.

[7-3] Deaerators, ASME PTC 12.3-1997. ASME, New York.

[7-4] Test Method for Dissolved Oxygen in Water, ASTM Standard D888-87.

7-2
About EPRI
EPRI creates science and technology
solutions for the global energy and energy
services industry. U.S. electric utilities
established the Electric Power Research
Institute in 1973 as a nonprofit research
consortium for the benefit of utility members,
their customers, and society. Now known
simply as EPRI, the company provides a wide
range of innovative products and services to
more than 1000 energy-related organizations
in 40 countries. EPRI’s multidisciplinary team
of scientists and engineers draws on a
worldwide network of technical and business
expertise to help solve today’s toughest
energy and environmental problems.

EPRI. Electrify the World

© 2002 Electric Power Research Institute (EPRI), Inc. All


rights reserved. Electric Power Research Institute and EPRI
are registered service marks of the Electric Power Research
Institute, Inc. EPRI. ELECTRIFY THE WORLD is a service
mark of the Electric Power Research Institute, Inc.

1007309

Printed on recycled paper in the United States


of America

EPRI • 3412 Hillview Avenue, Palo Alto, California 94304 • PO Box 10412, Palo Alto, California 94303 • USA
800.313.3774 • 650.855.2121 • askepri@epri.com • www.epri.com

You might also like