CM3 series
CM3E series electronic
CM3L series incorporating residual
current protection Moulded case circuit breaker
CM3DC series direct current

CV

CW

CM

CB CK CR CA

CJR CJD CD CH CE

2014.10

CHANGSHU SWITCHGEAR MFG. CO.,LTD.


(FORMER CHANGSHU SWITCHGEAR PLANT)
CHANGSHU SWITCHGEAR MFG. CO.,LTD.
TRINITY AND COMPLETE SOLUTIONS FOR YOUR SYSTEMS

CV1-12 CV2-12 CV1-24 CV1-40.5

CW1 CW2 CW3 CW3V

CM1 CM1 E CM1 Z CM1 L CM1E L

CM 2 CM2Z CM2L CM 3 CM3E CM3L

CM5 CM5Z CM5L CM5ZL CM5Z/iP CM5G


●Low-voltage distribution protection
◆ CM3,CM3E,CM3L distribution breakers can be used in AC50/60Hz TN,TT,IT distribution systems.They
meet demand of GB50054-2011 “about device selection”.
◆CM3DC breaker can be used in systems of no-grounding,negative grounding,core point grounding.
◆Reliable contact indication and isolating function of all series breakers meet demand of GB50054 isolating device.
●Motor circuit protection
◆ CM3, CM3E, CM3L breakers for motor protection can provide over current for motor-starter, cable, and
motor.The protecting characteristic meets GB14048.4,The application meets GB50055.
◆ The width of CM3-250C, 100C and CM3-63 is only 60mm,can be installed in controlling box to protect
equipment.
●Residual current protect
◆ CM3L breaker provide protection of persons against hazardous voltage due to defective insulation. it also provide
,
protection against fire due to defective insulation.example cable s insulation is defected.
◆CM3L breaker of 30mA rated residual operating current can provide additional protection of persons against direct
contact.
◆ CM3L breaker can provide type A residual current protection of residual alternating current superimposed on a
smooth direct current.It meats selecting demand of GB50054,GB13955 for residual current protection device.
◆Actuating time meets calss co-ordination of GB13955.
◆Providing solution of AC690V residual current protection.
◆Achiving residual current automatic re-closing function by matching automatic re-closing module
●Switching function
◆ Two breakers of mounting mechanical interlock mechanism can achive two equipment manual switching of two
supplies for one equipment or two equipment for one supply.
◆ Achiving two supplies automatic switching by two mechanical and electrical interlock breakers matching
controlling (seeing catalog of CA1/CA1B series automatic transfer switching).

1
PRODUCT SERIES DESCRIPTION

CM3 CM3E CM3L CM3DC

CM3,CM3E,CM3L,CM3DC moulded case circuit breakers (hereafter reffered to as simply breakers) CM1 series
upper class products by my company. They are classified four series:
——Thermal/magnetic CM3 breakers,having six frames of 63A,100A,250A,400A,630A,800A,current is 10A to
800A.
——Electronic CM3E breakers,having five frames of 100A,250A,400A,630A,800A,current is 12.5A to 800A.
—— In cor p orat i ng res i d ua l cu rr en t p r otec tion CM 3L bre ak er s ,ha ving fou r fr ame s of
100A,225A,400A,630A,current is 10A to 630A, residual current is 30mA to 30A.
——Direct current CM3DC breakers,having frames of 100A,250A,400A,630A,800A,current 10A~800A.

◆ The breakers,according to rated limited shirt-circuit breaking capacity values,are classified four classes of type
C(basic),type L (standard),type M (second high breaking),type H (high breaking).
◆ CM3 breaker of breaking capacity C,L,M classes and CM3E breaker of breaking capacity M class can be
connected into outgoing line when AC400V distribution system.
◆All seres breakers can be installed horizontally (transverse) or vertically (upright) or lying down flatly.
◆All seres breakers have isolating function and corressponding synbol is shown as .
◆ The breakers of CM3-100/250 type L/M/H,and CM3-400,630 type C/L/M/H,and CM3-800 type L/M/H and
neutral type A,B of four poles above specifications,can be with for specical "overload alarm and no-tripping", This
eusure supply continuity and meet demand of GB50054 6.3.6 item.
◆ CM3L breaker can be with for leakage alarm and no-tripping module,This avoids that power cut gives rise to
heavy losses,It meets demand of GB13955-2005 4.6 item.
◆The breakers are complimance with following standards:
IEC 60947-1 Low-voltage switchgear and cintrolgear General rules.
IEC 60947-2 Low-voltage switchgear and cintrolgear Circuit-breakers.
IEC 60947-4-1 Low-voltage switchgear and cintrolgear Electromechanical Contactors and motor starters (including
motor protector)

2
ENVIRONMENT CONDITIONS FOR OPERATION AND INSTALLATION

●Ambient temperature: -5℃~+40℃;


●Elevation≤2000m;
●Relative humidity: not exceed 50% at the maximum ambient temperature of +40℃, but higher relative humidity at
the lower temperature, for example, 90% at 20℃. Special measures should be taken considering the dews on product
surface due to temperature change;
●Pollution protection: 3 grade;
● The breakers are tested by GB/T2423.10,can withstand vibration of frequency range 2Hz~13.2Hz,displacement
±1mm and frequency range 13.2Hz~100Hz,acceleration ± 0.7g;
●Installing categories: Ⅲ for the main circuit;Ⅱ for other auxiliary and control circuits;
●The breaker is suitable in electromagnetic environment A;
● Damp heat type(TH)breakers are tested by GB/T2423.4、GB/T2423.18,can bear the influence of moisture in
the air of salt fog and oil fog or mould;
● There must be not any explosive medium, and there must be not any gas which would corrode metal or any
conducting dust which would destory the insulation;
●The place would not be invaded by rain and snow;
●Sevice condition:
The breakers are tested by GB/T 2423.1 and GB/T2423.2,ambient temperature lower -25℃ ,higher +70℃
( temperature over +40℃ ,the breakers are used by reducing capacity;please seeing“ power consumption and
capacity lowering coefficient”);
Elevation over 2500m,the breakers are used by reducing capacity,please seeing “ capacity-reducing for high-
elevation ”.
●Storage condiction:ambient temperature -40℃~+70℃.

3
,
BREAKER S MAIN TECHNICAL PERFORMANCE INDEX
4
BREAKER QUICK SELECTION

8
CM 3 BREAKER

A. Distrobution usage type


CM3 breakers of distribution are classificated two release:
——thermal + electro-magnetic release for code 3,for example selecting type is CM3-63M/3300.
——only electro-magnetic release for code 2,for example selecting type is CM3-63M/3200.
● Release pattern code is 3,thermal+electro-magnetic release

Protection function Frame size Rated current In(A) Operate characteristic


Overload protection All series
By I2t operate
Overload alarm and 1.05In (cold) ,don,t operate within 1h (In≤63A)
no-tripping
1.3In (thermal),≤1h operate (In≤63A)
,
1.05In (cold),don t operate within 2h (In>63A)
1.3In (thermal),≤2h operate (In>63A)

Protection function Frame size Rated current In(A) Short-circuit protection current setting value Ir(A) Operate time
Short-circuit protection Instantanous operate

(Can provide 5In ,


note when order)

Operate tolerance

Rated current In(A) Overload protection current setting value for neutral pole (A)
Protection function Frame size short-circuit protection current setting value for neutral pole (A)

Neutral protection type C/D


(four poles breaker)

Can provide overload


p r o t e c ti o n cu r r e n t
setting value In,and
short-circuit protection
setting value Ir for
neutral.please no te
when order.

Type A/B all series Without protection

15
CM 3 BREAKER

●Release pattern code is 2, only electro-magnetic release

Protection function Frame size Rated current In(A) Short-circuit protection current setting value Ir(A) Operate time
Short-circuit protection Instantanous operate

(Can provide 5In ,


note when order)

Operate tolerance
Neutral protection type C/D
(four poles breaker)

(Can provide 10In ,note when order)

(Can provide 10In ,


note when order)

Type A/B all series Without protection

16
CM 3 BREAKER

C.CM3 breaker protection characteristic curve


The characteristic curves are obtained in the cold and three phases load.
CM3-63L/M time/current characteristic curve
10000
5000

2000
1000
500

200
100
Current-temperature characteristic 50

20
32~63A
130 10
5

2
120 1
10~25A 0.5

0.2
110
32~63A 0.1
0.05

100 0.02
0 10 20 30 40 0.01
0.005
Ambient temperature (℃)
0.002
0.001
0.5 0.6 0.8 1 2 3 4 5 6 8 10 20 30 40 50 60 80 100 200 300
×In
Note: 10~25A instantanous operate current of CM3-63L.M is 300A ±20%.

CM3-100C time/current characteristic curve


10000
5000

2000
1000
500

200
100
Current-temperature characteristic 50

20
32~100A
130 10
5

2
120 1
0.5
10~25A
0.2
110
0.1
32~100A
0.05

100 0.02
40
0 10 20 30 0.01
0.005
Ambient temperature (℃)
0.002
0.001
0.5 0.6 0.8 1 2 3 4 5 6 8 10 20 30 40 50 60 80 100 200 300
×In

Note: 10~25A instantanous operate current of CM3-100C is 300A ±20%.

19
CM 3 BREAKER

CM3-100L/M/H time/current characteristic curve


10000
5000

2000
1000
500
Current-temperature characteristic
200
100
130 50

20
10~25A 10
120 5

2
32~100A 1
110
0.5

0.2
100
0.1
0 10 20 30 40 0.05

Ambient temperature (℃) 0.02


0.01
0.005

0.002
0.001
0.5 0.6 0.8 1 2 3 4 5 6 8 10 20 30 40 50 60 80 100 200 300
×In

CM3-250C time/current characteristic curve


10000
5000

2000
1000
500

200

Current-temperature characteristic 100


50

130 20
10
5

120 2
1
0.5
110 0.2
0.1
0.05
100
0 10 20 30 40 0.02
0.01
Ambient temperature (℃)
0.005

0.002
0.001
0.5 0.6 0.8 1 2 3 4 5 6 8 10 20 30 40 50 60 80 100 200 300
×In

20
CM 3 BREAKER

CM3-250L/M/H time/current characteristic curve


10000
5000

2000
1000
500

200
Current-temperature characteristic 100
50

130 20
10
5

120 2
1
0.5
110 0.2
0.1
0.05
100
0 10 20 30 40 0.02
0.01
Ambient temperature (℃)
0.005

0.002
0.001
0.5 0.6 0.8 1 2 3 4 5 6 8 10 20 30 40 50 60 80 100 200 300
×In

CM3-400C/L/M/H time/current characteristic curve


10000
5000

2000
1000
500

200
Current-temperature characteristic 100
50

130 20
10
5

120 2
1
0.5
110 0.2
0.1
0.05
100
0 10 20 30 40 0.02
0.01
Ambient temperature (℃)
0.005

0.002
0.001
0.5 0.6 0.8 1 2 3 4 5 6 8 10 20 30 40 50 60 80 100 200 300
×In

21
CM3 BREAKER OUTLINE AND MOUNTING DIMENSIONS

● CM3-63(L/M) front connected (3P/4P)


X-X、Y-Y as the center of 3P breaker
75
50
25
81
64.5
Y
60
Y
M8 16 24

22

X X X X

16.8 φ3.5

4
25

Y
Interphase barrier
75 Y
100 Mounting plate cutout dimensions
of front connected

● CM3-63(L/M) rear connected (3P/4P)


X-X、Y-Y as the center of 3P breaker

A
33
Y
8 Direction A
50

58.5
57(3P)
82(4P )

X X
φ20 φ5.5

98.5

Y
Mounting plate cutout dimensions
of rear connected

38
CM3 BREAKER OUTLINE AND MOUNTING DIMENSIONS

● CM3-63(L/M) plug-in front connected (3P)


X-X、Y-Y as the center of 3P breaker Y

50

77(min)

50
X φ5.5 X

3
25 35
Y
Mounting plate cutout dimensions
of plug-in front connected

● CM3-63(L/M) plug-in rear connected (3P/4P)


X-X、Y-Y as the center of 3P breaker

Y
65.2
51.5 102(4P )
77(min)(3P)

50(3P)
75(4P)

X X
φ5.5

18.8 M8
77.2
Y
Mounting plate cutout dimensions
of plug-in rear connected

39
CM3 BREAKER OUTLINE AND MOUNTING DIMENSIONS

● CM3-63(L/M) 8E/2 or 8E/4 rear connected of MNS assembly (guide rail mounting) (3P)

30
7 80.6

5
35

● CM3-100C front connected (3P/4P)


X-X、Y-Y as the center of 3P breaker

75
50
25
81
64.5
60
Y
Y
M8 16 24

22

X X X X

16.8 φ3.5

4
25

Y
Interphase barrier
75 Y
100
Mounting plate cutout dimensions
of front connected

40
CM3 BREAKER OUTLINE AND MOUNTING DIMENSIONS

● CM3-100C rear connected (3P/4P)


X-X、Y-Y as the center of 3P breaker

A
Y
33
8 Direction A 50

58.5
57(3P)
82(4P )

X X
φ20 φ5.5

98.5

Y
Mounting plate cutout dimensions
of rear connected

● CM3-100C plug-in front connected (3P)


X-X、Y-Y as the center of 3P breaker

Y
50

77(min)

50
X φ5.5 X

3
25 35
Y
Mounting plate cutout dimensions
of plug-in front connected

41
CM3 BREAKER OUTLINE AND MOUNTING DIMENSIONS

● CM3-100C plug-in rear connected (3P/4P)


X-X、Y-Y as the center of 3P breaker
Y
65.2
51.5 102(4P )
77(min)(3P)

50(3P)
75(4P)

X
φ5.5

18.8 M8

77.2
Y
Mounting plate cutout dimensions
of plug-in rear connected

● CM3-100C 8E/2 rear connected of MNS assembly (3P)

30
7 80.6

5
35

42
CM3 BREAKER OUTLINE AND MOUNTING DIMENSIONS

● CM3-100(L/M/H) front connected (3P/4P)


X-X、Y-Y as the center of 3P breaker
90
60
35
30

Y
104
87.2
Y
83
M8 17.5
24

22

X X X
X

20 φ4.5
4

30
Y
Interphase barrier
85
92 Y
122
Mounting plate cutout dimensions
of front connected

● CM3-100(L/M/H) rear connected (3P/4P)


X-X、Y-Y as the center of 3P breaker

A
35 Y
10 Direction A

53
60
72(3P)
102(4P )

X X
φ5.5
φ22

93

Y
Mounting plate cutout dimensions
of rear connected

43
CM3 BREAKER OUTLINE AND MOUNTING DIMENSIONS

● CM3-100(L/M/H) plug-in front connected (3P/4P)


X-X、Y-Y as the center of 3P breaker
Y
60

94(min)

60
X φ6.5 X

3
24 36
Y
Mounting plate cutout dimensions
of plug-in front connected

● CM3-100(L/M/H) plug-in rear connected (3P/4P)


X-X、Y-Y as the center of 3P breaker

Y
76
64
125(min)(4P)
50
94(min)(3P)

60(3P)
90(4P)
X φ6.5
X

17.5 M8

Y
Mounting plate cutout dimensions
of plug-in rear connected

44
CM3 BREAKER OUTLINE AND MOUNTING DIMENSIONS

● CM3-250C front connected (3P/4P)


X-X、Y-Y as the center of 3P breaker
35
20×6

Y 88
M8 67.1 Y
60
24 4

22

X
X X
X

22.1
φ4.5

35

Connecting busbar(optional)

Interphase barrier
Y Y
70 Mounting plate cutout dimensions
105
140 of front connected

● CM3-250C rear connected (3P/4P)


X-X、Y-Y as the center of 3P breaker

35 Direction A Y
10
100
55

87(3P)
φ8.5
122(4P)
X
X
13
φ24 φ5.5

Y
M8 70
105

Mounting plate cutout dimensions


of rear connected

45
CM3 BREAKER OUTLINE AND MOUNTING DIMENSIONS

● CM3-250C plug-in front connected (3P)


X-X、Y-Y as the center of 3P breaker

Y
70

110(min)

70 φ6.5
X X

4
24 41 Y
Mounting plate cutout dimensions
of plug-in front connected

● CM3-250C plug-in rear connected (3P/4P)


X-X、Y-Y as the center of 3P breaker

86.5
71.5
Y
145(min)(4P)
50
110(min)(3P)

70(3P)
105(4P)
X X
φ6.5

17.5 M8

Y
Mounting plate cutout dimensions
of plug-in rear connected

46
CM3 BREAKER OUTLINE AND MOUNTING DIMENSIONS

● CM3-250(L/M/H) front connected (3P/4P)


X-X、Y-Y as the center of 3P breaker

Y
105
70
35
20×6 127 Y
M8
104.5
102.5
M8 24

22

X X X X

φ4.5
23.5

35

Connecting busbar(optional)

Interphase barrier
99
107
142 Y
Y

● CM3-250(L/M/H) rear connected (3P/4P)


X-X、Y-Y as the center of 3P breaker

A
Y
Direction A
35
10 100

55
87(3P)
φ8.5 122(4P)

X X
φ5.5
13 φ24

M8
70
105
Y
Mounting plate cutout dimensions
of rear connected

47
CM3 BREAKER OUTLINE AND MOUNTING DIMENSIONS

● CM3-250(L/M/H) plug-in front connected (3P)


X-X、Y-Y as the center of 3P breaker

Y
70

110(min)
70
φ6.5
X X

4 Y
24 41 Mounting plate cutout dimensions
of plug-in front connected

● CM3-250(L/M/H) plug-in rear connected (3P/4P)


X-X、Y-Y as the center of 3P breaker

86.5
71.5 Y
50
110(min)(3P)

70(3P)
105(4P)
X φ6.5
X

145(4P)

17.5 M8
Y
Mounting plate cutout dimensions
of plug-in rear connected

48
CM3 BREAKER OUTLINE AND MOUNTING DIMENSIONS

● CM3-400(C/L/M/H) front connected (3P/4P)


X-X、Y-Y as the center of 3P breaker
3.5

Y 144
96
48 146.5
44 Y
106.7
11 30×8
Φ13 98.7
38
M10

6
65

X X X X

φ7
57

44
Connecting busbar(optional)

Interphase barrier
Y
139
150
198
Y
Mounting plate cutout dimensions
of front connected

● CM3-400(C/L/M/H) rear connected (3P/4P)


X-X、Y-Y as the center of 3P breaker

A 37 Direction A Y
12

108.5
48.5

124(3P)
172(4P)

X X
φ10.5
φ 6.5
φ32

M10 96
144
Y
Mounting plate cutout dimensions
of rear connected

49
CM3 BREAKER OUTLINE AND MOUNTING DIMENSIONS

● CM3-400(C/L/M/H) plug-in front connected (3P)


X-X、Y-Y as the center of 3P breaker
Y
118

152(min)

60

X X
φ8.5

6
38.3 52
Y
Mounting plate cutout dimensions
of plug-in front connected

● CM3-400(C/L/M/H) plug-in rear connected (3P/4P)


X-X、Y-Y as the center of 3P breaker

Y
106.5
83.5
60
152(min)(3P)

60(3P)
108(4P)

X X
φ8.5

21 M10 200(min)(四极)

Y
Mounting plate cutout dimensions
of plug-in rear connected

50
CM3 BREAKER OUTLINE AND MOUNTING DIMENSIONS

● CM3-400(C/L/M/H) draw-out connected (3P/4P)


X-X、Y-Y as the center of 3P breaker
Y φ11 Front connected Y

96(3P)
Rear connected φ6.5

N
X X X X
77

144(4P)

48 48 48 17.5
Y
YW
221 Mounting plate cutout dimensions
Poles W of draw-out connected
3P 223

4P 271

● CM3-630(C/L/M/H) front connected (3P/4P)


X-X、Y-Y as the center of 3P breaker
Y
3

174
10 116
58
φ13
150 Y
110
105
M12 43 3.2

65

X X X X
φ7
58

58
Connecting busbar(optional)

Interphase barrier 40×10


170
182
240 Y
Y Mounting plate cutout dimensions
of front connected

51
MOUNTING SAFETY CLEARANCE

A:to conductive circuit (including without shelter or with earthed metal)


B:the terminals of breaker to the botton wall
C:the side case of breaker to the side wall (including without shelter or with earthed metal)
D:to non-conductive parts
C note:E:the interphase barrier the interphace barriers or zero arcventing covers should be installed
C

CM3/CM3E/CM3L breaker mounting safety clearance


Unit:mm

A
Type B C D
Without zero arcventing cover With zero arcventing cover
CM3-63 50 25 25 25 25
CM3-100 50 25 25 25 25
CM3-250 50 25 25 25 25
CM3-400 100 25 25 25 25
CM3-630 100 25 25 25 25
CM3-800 100 25 25 25 25

CM3E-100 50 25 25 25 25
CM3E-250 50 25 25 25 25
CM3E-400 100 25 25 25 25
CM3E-630/800 100 25 25 25 25
CM3L-100 50 25 25 25 25
CM3L-225 50 25 25 25 25
CM3L-400 100 25 25 25 25
CM3L-630 100 25 25 25 25

CM3DC breake mounting safety clearance


Unit:mm

Type A B C D

CM3DC-100 50 25 25 25

CM3DC-250 50 25 25 25

CM3DC-400 100 25 25 25

CM3DC-630 100 25 25 25

CM3DC-800 100 25 25 25

79