You are on page 1of 2

Exceptions to G3.1.2.

10: If any of these exceptions apply, drives, and systems serving less than 120,000 ft2 shall be
exhaust air energy recovery shall not be included in the modeled as riding the pump curve.
baseline building design. G3.1.3.6 Piping Losses (Systems 1, 5, 7, and 8). Piping
(a) Systems serving spaces that are not cooled and that losses shall not be modeled in either the proposed or baseline
are heated to less than 60°F. building designs for hot water, chilled water, or steam piping.
G3.1.3.7 Type and Number of Chillers (Systems 7 and
(b) Systems exhausting toxic, flammable, or corrosive
fumes or paint or dust. This exception shall only be
8). Electric chillers shall be used in the baseline building
used if exhaust air energy recovery is not used in the
design regardless of the cooling energy source, e.g., direct-
proposed design.
fired absorption, absorption from purchased steam, or pur-
(c) Commercial kitchen hoods (grease) classified as
chased chilled water. The baseline building design’s chiller
Type 1 by NFPA 96. This exception shall only be
plant shall be modeled with chillers having the number and
used if exhaust air energy recovery is not used in the
type as indicated in Table G3.1.3.7 as a function of building
proposed design.
conditioned floor area.
(d) Heating systems in climate zones 1 through 3.
(e) Cooling systems in climate zones 3c, 4c, 5b, 5c, 6b, G3.1.3.8 Chilled Water Design Supply Temperature
7, and 8. (Systems 7 and 8). Chilled water design supply temperature
(f) Where the largest exhaust source is less than 75% of shall be modeled at 44°F and return water temperature at
the design outdoor air flow. This exception shall 56°F.
only be used if exhaust air energy recovery is not G3.1.3.9 Chilled Water Supply Temperature Reset
used in the proposed design. (Systems 7 and 8). Chilled water supply temperature shall be
(g) Systems requiring dehumidification that employ reset based on outdoor dry-bulb temperature using the follow-
energy recovery in series with the cooling coil. This ing schedule: 44°F at 80°F and above, 54°F at 60°F and
exception shall only be used if exhaust air energy below, and ramped linearly between 44°F and 54°F at temper-
recovery and series-style energy recovery coils are atures between 80°F and 60°F.
not used in the proposed design. G3.1.3.10 Chilled Water Pumps (Systems 7 and 8). The
G3.1.3 System-Specific Baseline HVAC System baseline building design pump power shall be 22 W/gpm.
Requirements. Baseline HVAC systems shall conform with Chilled water systems serving 120,000 ft2 or more shall be
provisions in this section, where applicable, to the specified modeled as primary/secondary systems with variable-speed
baseline system types as indicated in section headings. drives on the secondary pumping loop. Chilled water pumps
G3.1.3.1 Heat Pumps (Systems 2 and 4). Electric air- in systems serving less than 120,000 ft2 shall be modeled as a
source heat pumps shall be modeled with electric auxiliary primary/secondary systems with secondary pump riding the
heat. The systems shall be controlled with multi-stage space pump curve.
thermostats and an outdoor air thermostat wired to energize G3.1.3.11 Heat Rejection (Systems 7 and 8). The heat
auxiliary heat only on the last thermostat stage and when out- rejection device shall be an axial fan cooling tower with two-
door air temperature is less than 40°F. speed fans. Condenser water design supply temperature shall
G3.1.3.2 Type and Number of Boilers (Systems 1, 5, be 85°F or 10°F approach to design wet-bulb temperature,
and 7). The boiler plant shall use the same fuel as the pro- whichever is lower, with a design temperature rise of 10°F.
posed design and shall be natural draft, except as noted under The tower shall be controlled to maintain a 70°F leaving water
G3.1.1.1. The baseline building design boiler plant shall be temperature where weather permits, floating up to leaving
modeled as having a single boiler if the baseline building water temperature at design conditions. The baseline building
design plant serves a conditioned floor area of 15,000 ft2 or design condenser water pump power shall be 19 W/gpm. Each
less and as having two equally sized boilers for plants serving chiller shall be modeled with separate condenser water and
more than 15,000 ft2. Boilers shall be staged as required by chilled water pumps interlocked to operate with the associ-
the load. ated chiller.
G3.1.3.3 Hot Water Supply Temperature (Systems 1, G3.1.3.12 Supply Air Temperature Reset (Systems 5
5, and 7). Hot water design supply temperature shall be mod- through 8). Supply air temperature shall be reset based on
eled as 180°F and design return temperature as 130°F. zone demand from the design temperature difference to a
G3.1.3.4 Hot Water Supply Temperature Reset (Sys-
tems 1, 5, and 7). Hot water supply temperature shall be reset TABLE G3.1.3.7 Type and Number of Chillers
based on outdoor dry-bulb temperature using the following Building-Conditioned
schedule: 180°F at 20°F and below, 150°F at 50°F and above, Floor Area Number and Type of Chiller(s)
and ramped linearly between 180°F and 150°F at tempera-
tures between 20°F and 50°F. ≤ 120,000 ft2 1 screw chiller
G3.1.3.5 Hot Water Pumps (Systems 1, 5, and 7). The > 120,000 ft2, < 240,000 2 screw chillers sized equally
baseline building design hot water pump power shall be 19 W/ ft2
gpm. The pumping system shall be modeled as primary-only ≥ 240,000 ft2 2 centrifugal chillers minimum with
with continuous variable flow. Hot water systems serving chillers added so that no chiller is
120,000 ft2 or more shall be modeled with variable-speed larger than 800 tons, all sized equally

178 ANSI/ASHRAE/IESNA STANDARD 90.1-2004


TABLE 6.8.1C Water Chilling Packages–Minimum Efficiency Requirements

Subcategory or
Equipment Type Size Category Rating Condition Minimum Efficiencya Test Procedureb
Air Cooled, with Condenser, All Capacities 2.80 COP ARI 550/590
Electrically Operated 3.05 IPLV
Air Cooled, All Capacities 3.10 COP
without Condenser, 3.45 IPLV
Electrically Operated
Water Cooled, Electrically Operated, Posi- All Capacities 4.20 COP ARI 550/590
tive Displacement 5.05 IPLV
(Reciprocating)

Water Cooled, <150 tons 4.45 COP ARI 550/590


Electrically Operated, 5.20 IPLV
Positive Displacement
(Rotary Screw and Scroll)
≥150 tons and 4.90 COP
<300 tons 5.60 IPLV

≥300 tons 5.50 COP


6.15 IPLV

Water Cooled, Electrically Operated, Cen- <150 tons 5.00 COP ARI 550/590
trifugal 5.25 IPLV

≥150 tons and 5.55 COP


<300 tons 5.90 IPLV

≥300 tons 6.10 COP


6.40 IPLV

Air-Cooled Absorption All Capacities 0.60 COP ARI 560


Single Effect
Water-Cooled Absorption All Capacities 0.70 COP
Single Effect
Absorption Double Effect, All Capacities 1.00 COP
Indirect-Fired 1.05 IPLV
Absorption Double Effect, All Capacities 1.00 COP
Direct-Fired 1.00 IPLV
a The chiller equipment requirements do not apply for chillers used in low-temperature applications where the design leaving fluid temperature is <40°F.
b Section 12 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure.

ANSI/ASHRAE/IESNA STANDARD 90.1-2004 47

You might also like