You are on page 1of 10

System Overview

A guide to Most commercial and industrial premises


are nowadays required to have a fire alarm
system installed to BS 5839. The system
is better described as a fire detection &

BS5839 alarm system, as it’s primary function is


firstly to detect a fire or fire condition, and
secondly to sound audible alarms in all of
part of the building.
At its simplest, the system may be
BS5839: Part 1: 1988 TESTING AND operated purely by Break Glass Units
MAINTENANCE (called a manual system). At it’s most
DAILY INSPECTION complex, the system may have very many
Check that the Charger On indicator shows. different types of smoke, heat other types
Inspect for any fault indicator showing or of detectors spread throughout the building
sounder operating. Inform the designated and possibly linked with other buildings.
responsible person of any fault. Is essential that the fire alarms are
WEEKLY TEST correctly designed, specified and installed.
Ensure that all indicators show by resetting The system may primarily be designed to
according to the instructions provided with protect life (although the premises are may
the panel and check that the internal protected) hence reliable, long term
sounder operates. Operate a call point or operation is essential.
detector to test the system. Check that the The design and installation details of the fire
sounders operate. Reset the fire alarm alarm should always be agreed with all
panel. Each week choose a different zone relevant parties including the Local Fire
in rotation, so that way all call points are Office (Fire Brigade), the local District
tested in rotation. Check all call points and Surveyor (Council), Insurers, site Fire
detectors and ensure that none are Officers, as well as architects, and
obstructed in any way. Enter results of structural engineers. All may impose
tests into log book. specific requirements relevant to their field.
QUARTERLY TEST The over-riding standard for the design of
Check all previous log book entries and the system is BS 5839. This is a
clarify that any remedial action has been comprehensive document and is nearly
taken. Check the battery and its always cited as the required standard. It
connections. Operate a call point or includes requirements such as for the
detector in each zone to test the fire alarm detection cabling to be fire proof (hence the
as per above. Remove mains supply and common use of MICC in fire alarm
check that the battery is capable of systems), battery backup to be provided
supplying the alarm sounders. and a wealth of other design features.
ANNUAL TEST It is common for the fire alarm system in a
As per above. Additionally test all detectors building to be classified in accordance with
and call points and check for operation. classifications noted in BS 5839.
EVERY 2 - 3 YEARS These are:-
Clean smoke detectors to ensure correct Systems for protecting life.
operation and freedom from false alarms. Type M - Manual System - A system that
Special equipment is required for cleaning relies upon manual Break Glass Units
smoke detectors. (BGU) being operated by building
EVERY 4 YEARS occupants. If a BGU is smashed then the
Replace sealed lead acid batteries. If the alarms sound. This system depends upon
operating temperature exceeds 25oC the presence of people.
continuously, then the battery may need to Type L1 - Life 1 - A system with automatic
be replaced sooner. detectors installed throughout the building,
including escape routes, stairs, every room,
store and void. In addition, BGUs are
installed on all exits and between zones.
This system will operate even when people
are not present.
Type L2 - Life 2 - A system with automatic risk exists throughout or where a small fire
detectors installed along all escape routes could easily spread and cause extensive
as well as in high risk areas, such as plant damage.,
rooms, storage facilities or any other area P2
where a fire would cause a high risk to life. A listed building or older style premises
In addition, BGUs are installed on all exits where fire damage could be expensive.
and between zones. This system will System audibility is required to be 65db or
operate even when people are not present. 10db above background noise. Special
Type L3 - Life 3 - A system with automatic requirements existing for buildings housing
detection installed only along escape people who are sleeping such as hotels and
routes and in areas where free passage is care homes etc. The requirements for
essential to protect life. BGUs are also audibility are not linked with or dependent
installed at exits and between zones. on, the type of system installed. All areas
Systems for protection property. must have sufficient audibility.
Type P1 - Property 1 - A system with
automatic detectors installed throughout
the building, including escape routes, Systems Available and Applications
stairs, every room, store and void. In
addition, BGUs are installed on all exits Break Glass Units (BGU).
and between zones. This system will A small devices (approx 100x100mm)
operate even when people are not present. usually mounted adjacent to fire exits and
In most cases a P1 system can be taken where an escape route leaves a zone.
as having the same cover as an L1 system. Smashing the glass will cause a circuit to
Type P2 - Property 2 - A system with be either made or broken.
automatic detectors installed only in high Automatic detectors.
risk areas, such as plant rooms, storage These devices all constantly monitor the
facilities or any other area where there is a surroundings and in the event of a fire
high risk of fire. In addition, BGUs are condition will cause a circuit to be either
installed on all exits and between zones. made or broken.
Note that an P2 system does not Smoke Detectors.
necessarily cover escape routes and may May be either optical or ionisation type.
not provide adequate life protection. These devices detect the actual presence
The type of system used will depend upon of smoke in the surroundings. Strict rules
the building however the following exist regarding the location and siting of
arrangements are common. Note that the these devices. Very sensitive devices “Very
actual requirements MUST BE VERIFIED Early Smoke Detection & Alarm ( VESDA)
these are a guide only. “ exist and are used in very high risk areas.
BS5839 Classification Type of System Heat Detectors. May be either fixed
Type of premises temperature or rate of rise devices. The
M devices monitor the temperature of the
Small office building with clear escape ambient air. If the temp rises above a fixed
routes and occupants who know the temp or rise too quickly, then an alarm is
building initiated.
L1 Flame Detectors These devices monitor
A residential care home or hotel. Or room or areas surfaces and initiate an
building with specific access/structural alarm if a flame is detected
risks. Beam Sensors These devices rely on a
L2 infra-red beam being transmitted across a
A large complex office building where many room or space at high level. A sensor picks
people work. An older style building with up the beam and if the beam has been
many corridors and small rooms. obstructed or reduced in strength (by
L3 smoke) then an alarm is initiated.
A medium sized office building, retail Sounders These devices produce a high
premises or factory. Where large numbers volume sound and are located throughout
of people are present, but escape is the building. In the event of fire, all the
relatively easy. sounders will be energised (unless the fire
P1 offices states otherwise) and they will
A large complex office building where a high continue until silenced at the panel.
Several types of sounder exists. The most device operates then the panel only
common type used to be the familiar bell indicated the appropriate zone. The actual
but nowadays, electronic sounders are device which operates is not indicated.
more common due to the range of types, Such systems are still commonly used for
sizes and tones available. Specific small buildings, or where cheap simple
guidelines are included in BS 5839 operation is required
regarding the type of sound and required Addressable Systems These systems rely
audibility. on modern multiplexing technology to
Fire Alarm Panel The fire alarm panel is individually address each device in the
the heart of the fire alarm system. It system. When a device operates, the panel
monitors the detection wiring and devices indicates both the appropriate zone and the
for faults and operation. If an alarm actual device number or even room location.
condition is identified then the panel This considerably helps fire location and
activates the sounders as well as any other helps fire crews to get to the point of fire
controlled equipment such as remote origin very quickly.
communicators. The panel is fitted with Such systems are wired on by means of
various indicators and internal buzzers. The one or more loops with only the loop ends
zone in which the alarm originates is being connected at the panel. Obvious
shown, also with addressable systems, the cable savings can be made using an
actual device number and location may be addressable system.
given. Radio Addressable Systems. As above
The fire alarm panel may contain standby but wireless with many obvious benefits
batteries (else they are located remotely). including substantial cost savings on some
The panel may operate on an addressable designs with rapid installation time.
or conventional basis. Remote communication In buildings
The fire alarm panel must always be which may be unoccupied or which may be
situated in a position where the Fire occupied but unsupervised at night, it is
Brigade can easily see and find it (normally often the requirement of the local fire office
by a front entrance). It is hence best to to provide a form of remote communication,
obtain their agreement prior to installation. such as a signal to a central monitoring
Special arrangements may existing in large station or an autodialler which dials a
complex sites with secondary or “repeater” telephone number and repeats a recorded
panels being common in areas such as message. Such systems can greatly
security desks, second entrances and fire reduce the time in which the Fire Brigade
control points. attends.
Zoning. All but the smallest building will Wiring. BS 5839 is slightly “woolly” in
require segregation as far as the fire alarm regards to the type of wiring that is
system is concerned. The primary purpose required. It is clear that all sounder cabling
of zoning is to aid the identification and to (and any other wiring that must function
speedily locate a fire. In essence, the after a fire has been detected) must be
building should be split up into small areas fireproof. However, the detection cabling
(zones) in which operation of any devices in can be treated differently. It is considered
the zone will cause a zone indication at the that detection wiring is only needed to
panel. Zone divisions are dependent upon detect the fire (i.e.: until the alarms sound)
many factors, all detailed in BS 5839. from then on, strictly speaking, the cabling
However, it is common for zone divisions to is not needed.
be closely related to the building fire In reality however, it is generally accepted
compartmentation. A zone should not that fire resisting cabling is to be used
exceed 2000m² throughout the system for both detection
Technology. Many, many different forms of and alarm cabling. MICC cable is
technology exist in fire alarm systems, and considered by some to be the best form of
all manufacturers use their own methods of cabling for fire alarm applications, although
monitoring and alarm. However, most other more flexible alternatives are
systems fall into one of two categories:- nowadays available.
Conventional systems. These systems Levels of Protection
rely on fairly old technology, with a series of BS 5839 : Part 6 defines five different
radial cables running from the main alarm ‘Levels of Protection’. The level of protection
panel to the devices on each zone. If a will determine the rooms and areas in which
smoke alarms must be installed. Levels smoke alarm should be provided in the
beginning with the letters LD indicate that lounge to give early warning of fire.
the objective is to protect the occupants. Where any doubt exists as to the need for,
Levels beginning with the letters PD or appropriate locations of, additional
indicate that the objective is property smoke alarms, the advice of the fire brigade
protection. Since smoke alarms will or other fire safety specialists should be
normally be used only to protect sought. Advice can also be provided by the
occupants, only the three LD levels are TTS Fire & Security Ltd.
considered in this Guide**. These are Locating and Siting Smoke Alarms
defined as follows: Smoke alarms should be sited in
LD1 : Detectors installed in all circulation accordance with the following guidance to
spaces (e.g. hallways and staircases) and ensure both adequate detection and alarm
in all rooms and areas in which fire might sounder audibility:
start, other than toilets, bathrooms and ¯ At least one smoke alarm should be
shower rooms. located between the sleeping areas and the
Thus, if a specification calls for a type LD1 most likely sources of fire (living room and
system, smoke alarms should be installed kitchen).
in all rooms and areas of the house, except ¯ In a single storey dwelling, one smoke
those, such as kitchens, that are alarm may be sufficient, in which case it
unsuitable for smoke alarms; heat should be sited as close as possible to the
detectors should be installed in these living accommodation. If there are rooms
rooms. (other than toilets, bathrooms or shower
LD2 : Detectors installed in all circulation rooms) on either side of a bedroom, a
spaces that form Although BS 5839 : Part 6 smoke alarm should be sited in the
recommends type LD3 protection as the hallway, mid-way between these rooms.
minimum standard of protection for those ¯ In a two storey house, at least one
single-family dwellings in which smoke smoke alarm should be located on each
alarms are suitable, it should be stressed storey.
that the Standard recommends the ¯ In a conventional two storey house, one
installation of additional smoke alarms (so smoke alarm should be sited on the ground
providing LD2, or in some cases even LD1, floor between the staircase and any room in
protection) if: which fire might start. A further smoke
The risk to occupants is higher than in a alarm should be sited on the upstairs
‘typical’ dwelling. Possible examples could landing.
be the need for smoke alarms to be ¯ Additional smoke alarms should be
installed in living rooms and dining rooms if provided in long hallways of all dwellings.
the occupiers smoke, or in bedrooms if Within such circulation areas, no door to
they smoke in bed. It might also be any room should be further than 7.5 m from
appropriate to install smoke alarms in the nearest smoke detector.
rooms, particularly bedrooms, in which ¯ In open-plan accommodation, where a
portable heaters or solid-fuel fires are used stair may be open to a living/dining area,
during the night, or in which electric the living/dining area should be treated as a
blankets are used, particularly by high-risk circulation area.
groups such as the elderly. Houses in ¯ Under flat ceilings, the distance from any
which the principal occupant is elderly or in point in the room or area that is to be
which there are several elderly occupants or protected to the nearest smoke alarm
young children may warrant additional should never be more than 7.5 m. (or 5.3 m
smoke alarms. If occupants’ mobility is in the case of a heat detector).
impaired, additional smoke alarms may ¯ Smoke alarms should preferably be
also provide greater time for them to escape mounted on ceilings, unless the ceiling
in the event of fire. temperature is likely to be significantly
The means of escape from the dwelling greater than the general air temperature. If
suffers from some shortcoming. A particular ceiling mounting is not possible, wall
example would be a lounge, dining room or mounting may be considered in small
bedroom with no suitable window for rooms or short hallways. However, smoke
escape, located off another room e.g. a alarms should not be mounted on poorly
bedroom off a lounge. A fire in the lounge insulated external walls.
could trap people in the bedroom, and a
¯ If smoke alarms are mounted on walls in avoided by careful siting of the smoke
small rooms or short hallways, they should alarms, rather than using ionisation
be mounted so that: chamber detectors.
the smoke entry grille is between 150 mm
and 300 mm below the ceiling; and Alarm Sound Levels
the smoke entry grille is above the top of
any doorway. It is essential that, whenever any of the
¯ Smoke alarms should not be mounted smoke alarms in the dwelling detects a fire,
adjacent to, or directly above, heaters or the sound level of the alarm (from either that
air-conditioning vents. smoke alarm or other smoke alarms
¯ Smoke alarms should be sited in interconnected with it) is sufficient to wake
positions that are reasonably accessible, up at least the adult members of the
particularly in the case of models household. The sound level in any bedroom
containing batteries, so that the False is likely to be satisfactory if there is a
Alarm Control (‘hush button’) can be smoke alarm in the bedroom,
operated and that the smoke alarm may be interconnected to all other smoke alarms in
de-mounted to change batteries. the dwelling. However, if this is not the
¯ Smoke alarms should not be located case, the nearest interconnected smoke
closer than 300 mm to walls or light fittings. alarm to the bedroom, capable of sounding
¯ In order that the smoke alarms will wake an alarm whenever fire is detected
people from sleep, there is a need to anywhere in the dwelling, should not be
ensure that there is a smoke alarm within 3 further than 3 m from the bedroom door.
m of each bedroom door. In some dwellings, such as flats,
NOTE: maisonettes and houses in multiple
The above guidance will ensure only occupation, doors to rooms may be fire
protection of circulation spaces (a type LD3 doors, which tend to attenuate the sound
system). Such protection cannot be from smoke alarms more than normal,
depended upon to save the life of anyone in domestic doors. In these cases, great care
the room in which fire starts. In many should be taken to ensure that the sound
circumstances, the risk of fire may justify a level in bedrooms is sufficient. In some
type LD2 or LD1 system. This will houses in multiple occupation, the local
necessitate detectors (whether heat or authority may demand that the sound level
smoke) in some rooms of the dwelling. In at the bedheads in some or all bedrooms is
houses of multiple occupancy a manual call 75dB(A) when the bedroom doors are
point should be installed by exit doors and closed. This should be determined before
on each floor level. finalising the number of smoke alarms
required, because 75dB(A) is unlikely to be
False Alarms produced at the bedhead unless there is a
Occasional false alarms from smoke smoke alarm within the bedroom.
alarms are inevitable, but installers should If occupants suffer from severe hearing
site smoke alarms in such a way as to impairment, BS 5839 : Part 6 recommends
avoid unnecessary false alarms. However, that special alarm devices, such as high
avoidance of false alarms should never take intensity beacons and vibrating pillow or
precedence over effective fire detection. mattress pads, be provided.
Guidance on selection of the most suitable
type of smoke alarm in order to provide User Instructions
optimum fire detection while avoiding Occupiers should be provided with suitable
unnecessary false alarms. Note that the instructions on the smoke alarms installed.
smoke alarm nearest to any kitchen should BS 5839 : Part 6 sets out the information
be of the optical type. This will normally be that should be contained in these
the case, because all smoke alarms in instructions.
circulation spaces should normally be of
the optical type. However, optical smoke Certification
alarms should not be sited close to Once the installation has been completed
bathrooms, showers or rooms from which and instructions have been handed over to
steam may escape. Nevertheless, because the occupier (or the owner in the case of a
these rooms normally open off circulation house in multiple occupation), a certificate
spaces, false alarms should normally be of compliance with BS 5839 : Part 6 should
be issued. It should be noted that, because BS 7807:1995 “Code of practice for design,
BS 5839 : Part 6 is only a code of practice, installation and servicing of integrated
as opposed to a rigid set of regulations, it systems incorporating fire detection and
may have been appropriate to deviate from alarm systems and/or other security
its recommendations, subject to the systems for buildings other than dwellings”
agreement of the purchaser and any Provides recommendations for the
relevant enforcing authority (normally integration of a security system with other
building control in the case of new dwellings security systems for use in and around
or the environmental health officer in the buildings.
case of houses in multiple occupation). The BS 5839:Part 1:1988 “Fire detection and
certificate should specify the type and alarm systems for buildings. Code of
grade of system, and should indicate any practice for system design, installation and
deviations from the recommendations of the servicing” Covers all systems, from simple
British Standard in respect of this type and manual installations with several manual
grade of system. call points to complex automatic
A model installation certification is installations with manual call points,
contained in BS 5839 : Part 6. detectors, connection to the fire service and
The IEE Wiring Regulations further require initiation of ancillary services.
the issue of a certificate for the entire BS 5839:Part 2:1983 “Fire detection and
electrical installation in the case of a new alarm systems for buildings. Specification
house. for manual call points”
Gives requirements and methods of testing
Legislation & Guidelines .
The design and installation of a fire alarm BS 5839:Part 3:1988 “Fire detection and
system is governed by a range of alarm systems for buildings. Specification
regulations and legislation. However, in for automatic release mechanisms for
many situations, legislation on covers the certain fire protection equipment.”
objective of the system i.e.: to adequately Constructional and performance
protect. requirements for mechanisms intended to
The sure way ensure compliance is to hold open (or closed) fire protection
discuss fully with the relevant authorities equipment such as fire doors, dampers
and to above all ensure full compliance with etc., releasing on manual operation or
BS5839. receipt of a fire signal.
BS 5839:Part 4:1988 “Fire detection and
British Standards. alarm systems for buildings. Specification
Also refer to The British Standards for control and indicating equipment”
Institution Requirements and tests for the equipment,
BS 5446:Part 1:1990 “Components of including any associated power supply unit.
automatic fire alarm systems for residential Does not cover indicating equipment
premises”. Specification for self-contained installed at remote manned centres.
smoke alarms and point-type smoke BS 5839:Part 5:1988 “Fire detection and
detectors alarm systems for buildings”. Specification
BS 4422:Part 3:1990 “Glossary of terms for optical beam smoke detectors
associated with fire. Fire detection and Requirements, methods of test and
alarm” Terms used to describe the performance criteria for detectors with
operation of fire alarms systems and ranges between 1 m and 100 m.
specific types of fire detectors. BS 5839:Part 6:1995 “Fire detection and
BS 7671:1992 “Requirements for electrical alarm systems for buildings”. Code of
installations”. IEE Wiring Regulations. practice for the design and installation of
Sixteenth edition. This is the all fire detection and alarm systems in
encompassing “Bible” in relation to the dwellings
design, installation and use of electrical BS 5839-8:1998 “Fire detection and alarm
installations and equipment in buildings. It systems for buildings. Code of practice for
is relevant here due to the need to the design, installation and servicing of
segregate LV cabling (which fire alarm voice alarm systems”. Provides
cables normally are), also for the recommendations for the planning, design,
installation of associated controls and installation and servicing of voice alarm
equipment. systems in and around buildings
BS 6387:1994 “Specification for requirements for the welfare of persons
performance requirements for cables working in industrial environments.
required to maintain circuit integrity under Offices, Shops & Railway Premises Act
fire conditions” Applicable to cables rated at 1963. This act includes the legal
voltages not exceeding 450/750 V and for requirement for premises operators to
mineral-insulated cables complying with BS ensure fire precautions.
6207. Electricity Act 1989 - In the words of the
Combined Standards official HMSO title. “An Act to provide for
BS EN 54-1:1996 Fire detection and fire the appointment and functions of a Director
alarm systems. General of Electricity Supply and of
BS EN 50130-4:1996 Alarm systems. consumers’ committees for the electricity
Electromagnetic compatibility. Product supply industry; to make new provision with
family standard: Immunity requirements for respect to the supply of electricity through
components of fire, intruder and social electric lines and the generation and
alarm systems transmission of electricity for such supply;
International Standards to abolish the Electricity Consumers’
See also IEC search page Council and the Consultative Councils
IEC 60331 (1970-01) “Fire resisting established under the Electricity Act 1947;
characteristics of electric cables to provide for the vesting of the property,
Performance requirements, sample and test rights and liabilities of the Electricity
conditions, source of heat and test Boards and the Electricity Council in
procedure”. Has the status of a group companies nominated by the Secretary of
safety publication in accordance with IEC State and the subsequent dissolution of
Guide 104. those Boards and that Council; to provide
IEC 60332-2 (1989-03) “Tests on electric for the giving of financial assistance in
cables under fire conditions. Part 2: Test on connection with the storage and
a single small vertical insulated copper wire reprocessing of nuclear fuel, the treatment,
or cable” Specifies a method of testing a storage and disposal of radioactive waste
small insulated wire under fire conditions and the decommissioning of nuclear
when the method specified in IEC 332-1 is installations; to amend the Rights of Entry
not suitable because some small (Gas and Electricity Boards) Act 1954 and
conductors may melt during the application the Local Government (Scotland) Act 1973;
of the flame. Has the status of a group and for connected purposes.”
safety publication in accordance with IEC Electricity at Work Regulations 1989 -
Guide 104. Regulations covering the whole aspect of
ensuring that the workplace is safe in
Legislation regards to the use of electrical equipment.
Refer also to the Her Majesty’s Stationary (a part of the H&S at Work act)
Office (HMSO) Government Web Site for Construction (design & management)
further items of legislation and literature. regulations 1994 - Another wide reaching
Health & Safety at Work Act 1974 - set of regulations which cover the whole
Massive item of legislation which process of construction safety. It focuses
encompasses all aspects of Health & on carrying out risk assessments and
Safety in the workplace. This has been altering the design or management process
constantly added to over the years. It now to account for such risks. Again this forms
comprises and references a whole series of part of the H&S at work act 1974.
separate regulations and codes of practice
documents.
Fire Precautions (workplace) Regulations BS 5839 Part 6
1997 Introduction
Fire Precautions Act 1972. Comprehensive The purpose of this simple guide is to
act covering all aspects of building assist specifiers and installers in complying
construction means to avoid fire. Includes with the recommendations of BS 5839 :
specific requirements for the application of Part 6 when installing smoke alarms in
fire alarm systems. dwellings and while every reasonable
endeavor has been made to ensure the
Factories Act 1962. Act covering working accuracy of the information, it is the
practices, conditions and environmental responsibility of the reader to ensure that
they satisfy the recommendations of the detectors should never be installed in
British Standard in any particular case. No circulation spaces that form escape routes
liability is accepted for the consequences of from the house; smoke alarms must be
any errors or omissions in this guide. The used in these areas.
guide is not intended to be a substitute for
the British Standard, the contents of which Applications
should be carefully studied by contractors It should first be ensured that standard
installing smoke alarms in dwellings. There smoke alarms are a suitable form of fire
are a lot of similarities between the latter detection. Smoke alarms are suitable for
part 6 of BS 5839 1995 and the earlier BS most flats, maisonettes and single or two
5839 Part 1 for commercial properties but in storey houses (including houses in multiple
essence part 1 demands a fully monitored occupation) unless they are:
centrally controlled system with alert (i) very large (more than 200 m² on any
devices throughout the premises achieving floor);
at least 65 Db(A) with the following levels or (ii) unusually high (with the upper floor
most commonly implicated but there are more than 4.5m above ground level).
others. Larger properties need a form of fire
detection and alarm system with a central
Scope control panel. The system then becomes
BS 5839 pt6 covers all residential BS 5839 Part 1 design. However, in a
dwellings, both new and old. This part house in multiple occupation, regardless of
applies to bungalows, multi storey houses, size, smoke alarms may be used to give
individual flats and maisonettes, mobile warning to occupants of a fire in their own
homes, sheltered houses, NHS housing in accommodation, while communal escape
the community for mentally handicapped or routes are protected by a full fire detection
mentally ill people, mansions and houses and alarm system.
divided into several self contained family For new dwellings, battery operated smoke
dwelling units. It does not apply to hostels, alarms should not be used. These should
caravans or boats (other than permanently only be used for retrofitting in existing
moored boats used solely as residential bungalows, flats and owner occupied two
premises), or to the communal parts of storey houses in which there is adequate
purpose built sheltered housing and blocks means of escape in the event of fire. Mains
of flats or maisonettes. Compliance with the operated smoke alarms should be used for
standard does not of itself confer immunity all new dwellings and for retrofitting in
from legal obligations. rented maisonettes and two storey houses.
(They should also be used for single storey
The Products bungalows and flats if, for example,
The British Standard recommends that all occupants could be trapped in a lounge,
smoke alarms should conform to BS 5446 : dining room or bedroom, due to a fire in
Part 1. It also recommends that they another room through which it is necessary
should have been type tested, and to pass in order to escape from the
preferably have been approved under a property; this might occur if, for example,
recognised approval scheme. All TTS there is a bedroom off a lounge, and there
smoke alarms fully meet the requirements is no window in the bedroom suitable for
of BS 5446 : Part 1 and have BSI kitemark escape.) Mains operated smoke alarms
and CE approval. This facilitates should also be used in preference to battery
incorporation of a domestic heat detector, operated devices if the occupants are
which can be used to trigger a nearby considered to be at high risk from fire or if
smoke alarm to which it is wired. Heat they may not be able to replace batteries
detectors are very much slower in their soon after a low battery fault warning is
response to fire than smoke detectors. given.
They should only be used as Both the ionisation chamber and optical
supplementary protection to smoke alarms, smoke alarms have a wide application
in rooms, such as kitchens, where constant range, and either type will be effective in
false alarms would occur if smoke alarms giving a sufficiently early warning of fire in
were installed (or, less commonly, in rooms many circumstances. However, the optical
in which a fire would not cause an early smoke alarm responds better to some
threat to escape routes). In particular, heat types of fire than the ionisation chamber
type, whereas other fires are more readily electrical equipment should be connected
detected by the ionisation chamber smoke to this circuit. The circuit should preferably
alarm. Avoidance of false alarms may also not be protected by any r.c.d., whether
dictate the use of one type of smoke alarm dedicated to the circuit or common to all
in a particular location, rather than the circuits derived from the distribution board.
other. If, however, r.c.d. protection is essential for
The most common cause of false alarms is electrical safety, the British Standard
fumes generated by cooking. Optical recommends two options:
smoke alarms are generally less sensitive (i) The r.c.d. should be dedicated to the
to, for example, smoldering toast than smoke alarm circuit (which should then not
ionisation chamber smoke alarms (although be served by any other r.c.d.); or
the optical smoke alarm will respond if the (ii) The r.c.d. protection should be arranged
toast catches fire). Because of this, BS so that the r.c.d. serving the smoke alarm
5839 : Part 6 recommends that the smoke circuit operates independently of any r.c.d.
alarm nearest to a kitchen should be of the protection for circuits supplying socket
optical type. For effective fire detection, the outlets or portable equipment. (For
British Standard also recommends that example, this could be satisfied by a
optical smoke alarms should be used in the distribution board with a time delayed
circulation areas of the house. Accordingly, 100mA r.c.d. serving the entire board, and
to comply with the British Standard, optical 30mA r.c.d. protection on socket outlets,
smoke alarms should be used in the etc. It would be expected that, in the event
hallways and staircases. This should be of earth leakage on a socket outlet circuit,
particularly noted if compliance with the the 30mA r.c.d. would operate without the
British Standard is a requirement of a 100mA r.c.d. necessarily operating.)
building control authority. BS 5839 : Part 6 recommends that there be
In other locations, smoke alarm choice a method of silencing or disabling smoke
should depend mainly on the type of fire alarms in the event of a prolonged false
that may be expected. In many cases, this alarm, perhaps due to a fault or a build up
will be something of an unknown, and, of pollution in the detector chamber.
often, either type of detector can be used. However, to comply with BS 5839 : Part 6,
Under these circumstances, avoidance of there must be a means of silencing or
false alarms should be taken into account. disablement. This recommendation can be
In some dwellings, electricity supplies may satisfied if the dedicated circuit serving the
be disconnected because the occupiers are smoke alarms is protected by a miniature
unable to pay for supplies. Disconnection circuit breaker (as opposed to a fuse); the
may be at a coin or card operated meter or British Standard recognises a miniature
may be due to deliberate disconnection by circuit breaker as a suitable and readily
the supplier. If this is likely to occur, smoke accessible means of silencing.
alarms with battery back-up should be Because of the back-up batteries, these
installed. In practice, in many cases, there smoke alarms can be connected to either:
will be insufficient information regarding the (i) a single dedicated circuit at the
occupiers, who may, in any case change. distribution board.
Accordingly, TTS recommend the use of or (ii) a separately electrically protected,
smoke alarms with battery back-up in most regularly used local lighting circuit.
circumstances, as is now quite common However, if the smoke alarms are
practice. connected to a lighting circuit, isolation of
the detector for maintenance may be less
Connection to Mains Supply convenient due to the need to isolate the
Warning: Installation of mains powered lighting circuit.
smoke alarms should be undertaken only For models with battery back-up, the British
by a qualified electrician. Installation should Standard does not specifically recommend
be undertaken in accordance with BS 5839 against r.c.d. protection of the relevant
: Part 6 and BS 7671 (IEE Wiring circuit. However, TTS would still advise that
Regulations). it be ensured that the circuit used is not
Mains-only smoke alarms with no battery subject to nuisance tripping due to r.c.d.
back-up should be connected on a single protection.
independent, dedicated circuit at the
dwelling’s distribution board. No other
Interconnection of Smoke Alarms each with an integral standby supply, such
If two or more smoke alarms are installed, as a battery.
they should normally be interconnected to The grades are intentionally defined in such
maximise the extent of the audible warning a way that higher grades are always of a
when one detects a fire. In new dwellings, better standard than lower grades. So, if a
smoke alarms should always be specification calls for a Grade F system,
interconnected. It is essential that this can always be satisfied by installing
interconnected smoke alarms are all mains powered smoke alarms. Similarly, if
supplied from a single common circuit. a specification calls for a Grade E system,
Wiring the requirement can be satisfied by
installing mains-powered smoke alarms
All wiring should be installed in accordance either with or without battery back-up.
with BS 7671 (IEE Wiring Regulations). The Grade C systems comprise one or more
wiring of smoke alarms need not be fire smoke detectors / alarms with a central
resisting. The mains supplies, and any control panel, however, Grade C systems
interconnections between smoke alarms, may also comprise 12V smoke detectors
may be wired in any suitably rated cable integrated with an intruder alarm system,
designed for a.c. mains installations. subject to the integrated system complying
However, care should be taken to ensure with BS 5839: Part 6.
that the mains supply cable, and the cable Grade A and B systems are not considered
used for interconnection of smoke alarms, in this Guide. Smoke alarms cannot be
is not exposed to damage. BS 5839 : Part used to satisfy the recommendations of the
6 recommends that the cables are British Standard for Grade A or B systems;
protected, by for example capping under these systems use complete fire detection
plaster, conduit, or trunking, in any areas and alarm systems with separate
where they may be subject to impact, detectors, sounders and control equipment.
abrasion or rodent attack.
Where cables pass through walls, a
smooth clearance hole should be provided.
If additional mechanical protection is
necessary, a smooth-bore sleeve should be
sealed into the wall. Care should be taken
to ensure that the ends of the sleeve are
free from sharp edges. Cable penetrations
should be filled and should maintain the fire
resistance of any fire resisting walls or
floors. This information has been complied from a
Joints in cables should be avoided but, number of sources on the Internet.
where unavoidable, should be enclosed in a
suitable and accessible junction box.
Reliable termination methods should be
adopted.
Grades of System
BS 5839 : Part 6 defines various ‘Grades’ of
system. These will be used by enforcing
authorities and specifiers to specify the
type of fire detection equipment that is to
be installed. Smoke alarms can be used in
Grade C*, D, E and F systems, which are
suitable for protection of most normal flats,
maisonettes and houses.
Grade F systems comprise one or more
battery-powered smoke alarms.
Grade E systems comprise one or more
mains-powered smoke alarms.
Grade D systems comprise one or more
mains-powered smoke alarms,

DJT Consultancy - www.djtelectraining.co.uk

You might also like