You are on page 1of 10

Lombok GECC Power Plant (PEAKER) Date : 13-Sep-18

PT. TRACON INDUSTRI 130 - 150 MW


DOC. NO Page : 01 of 02

HYDROSTATIC TEST REPORT

CUSTOMER : PT.PP EQUIPMENT NAME PIPE P48-03


JOB NO : 17-7006 DESIGN PRESSURE : 5 barG / 72.52 psi
DRAWING NO : GLPP-000200-TRC-P1-GAD-004 TEST PRESSURE : 7.5 barG / 108.78 psi
DATE OF TEST : 13-Sep-18 TEST MEDIUM : FRESH WATER

( 30 mnt ) ( 120 mnt ) ( 30 mnt )

barG P2 P0 : 0 barG
P1 : 5 barG
P1 P3
P2 : 7.5 barG
P3 : 5 barG
P0 P4
0 1 4 5 6 7 9 P4 : 0 barG
2 3 8 10

No PRESSURE (barG) TEMPERATURE (C°)

0~1 8:00 - 9:11 0 bar - 5 bar Ambient


1~2 9:11 - 10:05 5 bar Ambient
2~3 10:05 - 10:21 5 bar - 7.8 bar Ambient
3~4 10:21 - 11:37 7.8 bar Ambient
4~5 11:37 - 12:18 7.8 bar Ambient
5~6 12:18 - 12:32 7.8 bar Ambient
6~7 12:32 - 13:00 7.8 bar Ambient
7~8 13:00 - 13:41 7.8 bar - 5 bar Ambient
8~9 13:41 - 14:17 5 bar Ambient
9~10 14:17 - 16:07 5 bar - 0 bar Ambient

WITNESSED BY & REVIEWED BY :

NO COMPANY DATE NAME SIGNATURE

1 PT. SRM 13-Sep-18 Bandi Subandi

2 PT TRACON INDUSTRI 13-Sep-18 Djuang Marhendra

3 PT PP

4 PT. PLN PUSMANCONG

5 PT. JAYA CM

6 PT. PLN UPP KITTRING

REMARKS :

Hydrotest result is acceptable, no leakage and no deformation.


Lombok GECC Power Plant (PEAKER) Date : 13-Sep-18
PT. TRACON INDUSTRI 130 - 150 MW
DOC. NO Page : 02 of 02

HYDROSTATIC TEST REPORT


DOCUMENTATION

Hydrotest on Pipe 48"


P48-03
13 September 2018

9:11 @ 5 bar 10:05 @ 5 bar 10:21 @ 7.8 bar

12:32 @ 7.8 bar

11:37 @ 7.8 bar 12:18 @ 7.8 bar 13:00 @ 7.8 bar

13:41 @ 5 bar 14:17 @ 5 bar 15:07 @ 2 bar 16:07 @ 0 bar


Lombok GECC Power Plant (PEAKER) Date : 13-Sep-18
PT. TRACON INDUSTRI 130 - 150 MW
DOC. NO Page : 01 of 02

HYDROSTATIC TEST REPORT

CUSTOMER : PT.PP EQUIPMENT NAME PIPE P40-03


JOB NO : 17-7006 DESIGN PRESSURE : 5 barG / 72.52 psi
DRAWING NO : GLPP-000200-TRC-P1-GAD-004 TEST PRESSURE : 7.5 barG / 108.78 psi
DATE OF TEST : 13-Sep-18 TEST MEDIUM : FRESH WATER

( 30 mnt ) ( 120 mnt ) ( 30 mnt )

barG P2 P0 : 0 barG
P1 : 5 barG
P1 P3
P2 : 7.5 barG
P3 : 5 barG
P0 P4
0 1 4 5 6 7 9 P4 : 0 barG
2 3 8 10

No PRESSURE (barG) TEMPERATURE (C°)

0~1 8:00 - 8:48 0 bar - 5 bar Ambient


1~2 8:48 - 9:12 5 bar Ambient
2~3 9:12 - 10:54 5 bar - 8 bar Ambient
3~4 10:21 - 11:37 8 bar Ambient
4~5 11:37 - 12:19 8 bar Ambient
5~6 12:19 - 12:32 8 bar Ambient
6~7 12:32 - 13:01 8 bar Ambient
7~8 13:01 - 13:40 8 bar - 5 bar Ambient
8~9 13:40 - 14:17 5 bar Ambient
9~10 14:17 - 16:07 5 bar - 0 bar Ambient

WITNESSED BY & REVIEWED BY :

NO COMPANY DATE NAME SIGNATURE

1 PT. SRM 13-Sep-18 Bandi Subandi

2 PT TRACON INDUSTRI 13-Sep-18 Djuang Marhendra

3 PT PP

4 PT. PLN PUSMANCONG

5 PT. JAYA CM

6 PT. PLN UPP KITTRING

REMARKS :

Hydrotest result is acceptable, no leakage and no deformation.


Lombok GECC Power Plant (PEAKER) Date : 13-Sep-18
PT. TRACON INDUSTRI 130 - 150 MW
DOC. NO Page : 02 of 02

HYDROSTATIC TEST REPORT


DOCUMENTATION

Hydrotest on Pipe 40"


P40-03
13 September 2018

8:48 @ 5 bar 9:12 @ 5 bar 10:54 @ 8 bar

12:19 @ 8 bar

11:37 @ 8 bar 12:32 @ 8 bar 13:01 @ 8 bar

13:40 @ 5 bar 14:17 @ 5 bar 15:07 @ 2 bar 16:07 @ 0 bar


Lombok GECC Power Plant (PEAKER) Date : 13-Sep-18
PT. TRACON INDUSTRI 130 - 150 MW
DOC. NO Page : 01 of 02

HYDROSTATIC TEST REPORT

CUSTOMER : PT.PP EQUIPMENT NAME PIPE P36-02


JOB NO : 17-7006 DESIGN PRESSURE : 5 barG / 72.52 psi
DRAWING NO : GLPP-000200-TRC-P1-GAD-004 TEST PRESSURE : 7.5 barG / 108.78 psi
DATE OF TEST : 13-Sep-18 TEST MEDIUM : FRESH WATER

( 30 mnt ) ( 120 mnt ) ( 30 mnt )

barG P2 P0 : 0 barG
P1 : 5 barG
P1 P3
P2 : 7.5 barG
P3 : 5 barG
P0 P4
0 1 4 5 6 7 9 P4 : 0 barG
2 3 8 10

No PRESSURE (barG) TEMPERATURE (C°)

0~1 8:00 - 8:46 0 bar - 5 bar Ambient


1~2 8:46 - 9:12 5 bar Ambient
2~3 9:12 - 10:58 5 bar - 7.5 bar Ambient
3~4 10:58 - 11:36 7.5 bar Ambient
4~5 11:36 - 12:20 7.5 bar Ambient
5~6 12:20 - 12:33 7.5 bar Ambient
6~7 12:33 - 13:01 7.5 bar Ambient
7~8 13:01 - 13:40 7.5 bar - 5 bar Ambient
8~9 13:40 - 14:16 5 bar Ambient
9~10 14:16 - 16:06 5 bar - 0 bar Ambient

WITNESSED BY & REVIEWED BY :

NO COMPANY DATE NAME SIGNATURE

1 PT. SRM 13-Sep-18 Bandi Subandi

2 PT TRACON INDUSTRI 13-Sep-18 Djuang Marhendra

3 PT PP

4 PT. PLN PUSMANCONG

5 PT. JAYA CM

6 PT. PLN UPP KITTRING

REMARKS :

Hydrotest result is acceptable, no leakage and no deformation.


Lombok GECC Power Plant (PEAKER) Date : 13-Sep-18
PT. TRACON INDUSTRI 130 - 150 MW
DOC. NO Page : 02 of 02

HYDROSTATIC TEST REPORT


DOCUMENTATION

Hydrotest on Pipe 36"


P36-02
13 September 2018 8:46 @ 5 bar 10:58 @ 7.5 bar 11:36 @ 7.5 bar

12:20 @ 7.5 bar

12:33 @ 7.5 bar 13:01 @ 7.5 bar 13:40 @ 5 bar

14:16 @ 5 bar 15:06 @ 2 bar 16:06 @ 0 bar


Lombok GECC Power Plant (PEAKER) Date : 13-Sep-18
PT. TRACON INDUSTRI 130 - 150 MW
DOC. NO Page : 01 of 02

HYDROSTATIC TEST REPORT

CUSTOMER : PT.PP EQUIPMENT NAME PIPE P32-02


JOB NO : 17-7006 DESIGN PRESSURE : 5 barG / 72.52 psi
DRAWING NO : GLPP-000200-TRC-P1-GAD-004 TEST PRESSURE : 7.5 barG / 108.78 psi
DATE OF TEST : 13-Sep-18 TEST MEDIUM : FRESH WATER

( 30 mnt ) ( 120 mnt ) ( 30 mnt )

barG P2 P0 : 0 barG
P1 : 5 barG
P1 P3
P2 : 7.5 barG
P3 : 5 barG
P0 P4
0 1 4 5 6 7 9 P4 : 0 barG
2 3 8 10

No PRESSURE (barG) TEMPERATURE (C°)

0~1 8:00 - 9:04 0 bar - 5 bar Ambient


1~2 9:04 - 10:03 5 bar Ambient
2~3 10:03 - 10:52 5 bar - 7.5 bar Ambient
3~4 10:52 - 11:36 7.5 bar Ambient
4~5 11:36 - 12:19 7.5 bar Ambient
5~6 12:19 - 12:33 7.5 bar Ambient
6~7 12:33 - 13:01 7.5 bar Ambient
7~8 13:01 - 13:40 7.5 bar - 5 bar Ambient
8~9 13:40 - 14:16 5 bar Ambient
9~10 14:16 - 16:06 5 bar - 0 bar Ambient

WITNESSED BY & REVIEWED BY :

NO COMPANY DATE NAME SIGNATURE

1 PT. SRM 13-Sep-18 Bandi Subandi

2 PT TRACON INDUSTRI 13-Sep-18 Djuang Marhendra

3 PT PP

4 PT. PLN PUSMANCONG

5 PT. JAYA CM

6 PT. PLN UPP KITTRING

REMARKS :

Hydrotest result is acceptable, no leakage and no deformation.


Lombok GECC Power Plant (PEAKER) Date : 13-Sep-18
PT. TRACON INDUSTRI 130 - 150 MW
DOC. NO Page : 02 of 02

HYDROSTATIC TEST REPORT


DOCUMENTATION

Hydrotest on Pipe 32"


P32-02
13 September 2018 9:04 @ 5 bar 10:03 @ 5 bar 10:52 @ 7.5 bar

11:36 @ 7.5 bar 12:19 @ 7.5 bar 12:33 @ 7.5 bar 13:01 @ 7.5 bar

13:40 @ 5 bar 14:16 @ 5 bar 15:06 @ 2 bar 16:06 @ 0 bar


Lombok GECC Power Plant (PEAKER) Date : 14-Sep-18
PT. TRACON INDUSTRI 130 - 150 MW
DOC. NO Page : 01 of 02

HYDROSTATIC TEST REPORT

CUSTOMER : PT.PP EQUIPMENT NAME PIPE P28-01


JOB NO : 17-7006 DESIGN PRESSURE : 5 barG / 72.52 psi
DRAWING NO : GLPP-000200-TRC-P1-GAD-004 TEST PRESSURE : 7.5 barG / 108.78 psi
DATE OF TEST : 14-Sep-18 TEST MEDIUM : FRESH WATER

( 30 mnt ) ( 120 mnt ) ( 30 mnt )

barG P2 P0 : 0 barG
P1 : 5 barG
P1 P3
P2 : 7.5 barG
P3 : 5 barG
P0 P4
0 1 4 5 6 7 9 P4 : 0 barG
2 3 8 10

No PRESSURE (barG) TEMPERATURE (C°)

0~1 8:00 - 9:20 0 bar - 5 bar Ambient


1~2 9:20 - 10:37 5 bar Ambient
2~3 10:37 - 11:06 5 bar - 7.5 bar Ambient
3~4 11:06 - 11:28 7.5 bar Ambient
4~5 11:28 - 12:07 7.5 bar Ambient
5~6 12:07 - 13:07 7.5 bar Ambient
6~7 13:07 - 13:36 7.5 bar Ambient
7~8 13:36 - 14:15 7.5 bar - 5 bar Ambient
8~9 14:15 - 14:53 5 bar Ambient
9~10 14:53 - 16:04 5 bar - 0 bar Ambient

WITNESSED BY & REVIEWED BY :

NO COMPANY DATE NAME SIGNATURE

1 PT. SRM 14-Sep-18 Bandi Subandi

2 PT TRACON INDUSTRI 14-Sep-18 Djuang Marhendra

3 PT PP

4 PT. PLN PUSMANCONG

5 PT. JAYA CM

6 PT. PLN UPP KITTRING

REMARKS :

Hydrotest result is acceptable, no leakage and no deformation.


Lombok GECC Power Plant (PEAKER) Date : 14-Sep-18
PT. TRACON INDUSTRI 130 - 150 MW
DOC. NO Page : 02 of 02

HYDROSTATIC TEST REPORT


DOCUMENTATION

9:20 @ 5 bar 10:37 @ 5 bar 11:06 @ 7.5 bar 11:28 @ 7.5 bar

12:07 @ 7.5 bar 13:07 @ 7.5 bar 13:36 @ 7.5 bar 14:15 @ 5 bar

14:53 @ 5 bar 16:04 @ 5 bar