You are on page 1of 18

Self-

consolidating
concrete
in congested
sections:
Mixture
character-
istics and
assessment of
performance
Lawrence F. Kahn
and Kimberly E. Kurtis

Self-consolidating concrete (SCC) promises better quality


and better finish and requires less labor than conventional
concrete. Because of these potential advantages over con-
ventional concrete, SCC is used regularly and successfully
at many precast concrete plants around the country.1–7

However, while SCC offers significant potential advan-


tages for the production of precast concrete sections that
are highly congested with reinforcement, this application
Editor’s quick points has not been well examined in the literature. The flow of
SCC through congested reinforcement presents additional
n  Standard self-consolidating concrete (SCC) test methods— challenges that must be accommodated through special-
including slump flow, VSI, L-box, and U-box tests—may not ac- ized mixture proportioning and appropriate testing.8 The
curately predict mixture performance during casting. Mock-up purpose of this research was to identify the SCC mixture-
sections and analysis of cores are necessary for assessing SCC proportion characteristics and quality-assurance methods
quality in highly congested sections. most appropriate for highly congested precast, prestressed
concrete bridge girders and congested bridge diaphragms
n  Class C fly ash, Class F fly ash, and slag all performed well as and end walls.
supplementary cementitious materials with up to 40% replace-
ment of cement. Mixtures were assessed through standard methods (for
example, slump flow, visual stability index [VSI], U-box,
n  Individual gradation of each aggregate and the combined gra- and L-box tests). Performance of each mixture in the wall
dation of both coarse and fine aggregates should be taken into or beam mock-ups was assessed through visual inspection
account when designing a workable SCC. of the cast surfaces, comparisons of compressive strength

Wi n t e r 2010 | PCI Journal 79


Figure 1. The mock-ups were 6-in.-thick × 6-ft-deep × 6-ft-wide (150 mm × 1.8 m × 1.8 m) wall panels.

between cores obtained at different locations and compan- cast at Tindall Corp. in Atlanta, Ga., and eight 13-ft-long
ion samples cast in the laboratory, and assessment of the (4.0 m) PCI bulb-tee (BT-72) beam sections (Fig. 2) cast
uniformity of aggregate distribution by visual inspection at Standard Concrete Products in Atlanta. Different mix-
and digital image analysis of cut sections. ture proportions were used for the wall panels and beams
because of variations in aggregate sources, supplementary
Experiment cementitious materials (SCMs), and chemical admixtures
used at the two facilities.
Overview
To assess the performance of each mixture, the mock-ups
The primary research objective was to develop different were inspected for their surface conditions and were saw
SCCs and to assess their performance in sections congested cut to examine segregation and filling ability along their
with reinforcement. Mixtures were proportioned to vary lengths and depths. Cores were taken from the mock-ups
from relatively simple (and inexpensive) to more complex and compared with companion cylinders cast from the
(which included those from Ramage et al.’s laboratory-based same mixtures.
study8 and included blended aggregates and supplementary
cementitious materials). All of the mixtures that were con- Materials and mixture proportions
sidered satisfied standard quality-control tests for flowabil-
ity and stability and could be cast at commercial precast Ramage et al.8 examined the impact of different fine and
concrete plants to fabricate full-sized mock-up samples. coarse aggregates from sources throughout the state of
Georgia, the use of fly ash and slag, the use of different
The mock-ups were eight planar 6-in.-thick × 6-ft-deep × cements, and the chemical admixtures from three different
6-ft-wide (150 mm × 1.8 m × 1.8 m) wall sections (Fig. 1) suppliers on the characteristics of SCC. High-quality SCCs

80 W int e r 2 0 1 0 | PCI Journal


Top web
Bottom web
Center web

Bottom flange

Figure 2. This photo shows a 13-ft-long (4.0 m) BT-72 mock-up with notations showing locations for bubble-count (air-void) analysis.

were developed using the different admixtures, making with mixture W-3. Standard slump flow (inverted cone)
each one unique. Natural and manufactured sand were used and U-box and L-box tests were conducted. Table 1 gives
independently and were blended. Blending natural sands, the ratio of height of the SCC after the gate to that before
manufactured sands, and coarse aggregates to create a the gate H2/H1 for the U-box. For the L-box, it gives the
smooth gradation was necessary to ensure good flow, pass- ratio of the height of the SCC at the end of the box to that
ing ability, and segregation resistance. just after the gate Hf /HS1.

Use of both Class F fly ash and slag combined for up to For the bulb-tee sections, five trial SCCs were developed in
40% of the cementitious content proved to enhance SCC the laboratory and used at the precasting plant. Slump flow,
qualities. Use of aggregate larger than no. 7 stone,9 which L-box, and U-box tests were conducted, and the surface fin-
has a maximum-sized aggregate less than 1/2 in. (12.5 mm), ishes of highway barriers cast with the SCCs were inspect-
caused diminished passing ability in the L-box and U-box ed. Class C fly ash and Type III cement were used rather
tests where clear spacing between the bars was 11/2 in. than Class F fly ash and Type I cement because the precast-
(38 mm). The 11/2 in. spacing was used to model the spacing er wanted to ensure rapid early-strength development.
between typical prestressing strands in bridge girders. The
three resulting best-performing mixture proportions were The four mixtures in Table 2 were selected to make the
used as a basis for the field-based research in this paper. BT-72 mock-ups, which included two beams for each
mixture. As with the wall panels, smaller maximum-sized
Table 1 gives the three mixture proportions used for the coarse aggregate (no. 7, 1/2 in. [13 mm] stone) mixtures,
wall panels. Mixtures W-1 and W-2 were based on the which are more typical for SCC, were compared with mix-
mixtures from Ramage et al.8 Mixture W-3, with its larger tures containing larger maximum-sized aggregate (no. 67,
maximum-sized aggregate, was the SCC used at the plant 3
/4 in. [19 mm] stone9), which is more typical of standard
for casting precast concrete slab sections. Three walls were precast-concrete-plant mixtures.
cast with mixture W-1, four with mixture W-2, and one

PCI Journal | Wi n t e r 2010 81


Table 1. Mixture proportions for SCC used in wall panels

Mixture W-1 W-2 W-3

Mixture components S-slag/ash G-slag T-cement

Cementitious materials, lb/yd3

Cement, Type I 720 730 750

Slag 200 225 n.a.

Fly ash, Class F 90 n.a. n.a.

Water 306 350 288

w/cm 0.30 0.37 0.38

Coarse aggregate, lb/yd3

No. 67 stone n.a. n.a. 1465

No. 7 stone 1030 910 n.a.

No. 89 stone 555 485 n.a.

Fine aggregate, lb/yd3

Natural sand (FM = 2.35) 615 600 1331

Manufactured sand (FM = 2.90) 395 580 n.a.

Admixtures, fl oz/cwt

High-range water-reducing admixture Type 1: 7.1 Type 2: 6.9 Type 2: 5.5

Air-entraining admixture n.a. n.a. 0.4

SCC properties

Slump-flow diameter, in. 34 26 18

U-box H2/H1, % 100 100 50

L-box Hf /HS1, % 100 75 50

Visual stability index 1 0 1.5

Concrete compressive strength f c' , psi 11,600 8600 8600

Compressive strength cores, psi 11,000 8600 6650

Note: FM = fineness modulus; H1 = height of SCC before the gate; H2 = height of SCC after the gate; Hf = height of SCC at the end of the box; HS1 =
height of SCC after the gate; n.a. = not appplicable; SCC = self-consolidating concrete; w/cm = water–cementitious materials ratio. No. 7 aggregate
= 1/2 in. diameter; no. 67 aggregate = 3/4 in. diameter; no. 89 aggregate = 3/8 in. diameter. 1 in. = 25.4 mm; 1 lb/yd3 = 0.5933 kg/m3; 1 fl oz/cwt =
68.2 mL/100 kg.

Construction details In addition, eight 13-ft-long (40 m) PCI BT-7210 mock-ups


were constructed (Fig. 4).
Figure 3 illustrates the reinforcing cage for the wall
panels. The cage on each face was made of 1/2-in.-diameter The reinforcement included twenty-six 0.6-in.-diameter
(13 mm) prestressing strand spaced about 9 in. × 11 in. (15 mm) strands in the bottom flange, an additional four-
(23 mm × 28 mm) on center. Two walls each of mixtures teen 0.6-in.-diameter strands draped to a midpoint harp,
W-1 and W-2 were vibrated externally for about 5 sec, as and two strands in the top flange. The cover thickness was
was one wall using mixture W-3, to determine if vibration 1 in. (25 mm). Shear reinforcement included no. 5 (M16)
resulted in an improved surface finish. two-leg stirrups spaced at 12 in. (30 mm) on center and
five no. 6 (M19) stirrups spaced 3 in. (76 mm) on center at

82 W int e r 2 0 1 0 | PCI Journal


Table 2. Mixture proportions for BT-72 mock-up beams

Mixture Mixture 1 Mixture 2 Mixture 4 Mixture 5

Beam 7N 7Nv 67N 67Nv 7BL 7BLv 67M 67Mv

Cementitious materials, lb/yd3

Cement, Type III 780 765 780 750 776 754 770 768

Fly ash, Class C 166 163 156 146 163 147 153 156

Water 297 300 277 293 305 308 294 303

w/cm 0.31 0.32 0.30 0.33 0.32 0.34 0.32 0.33

Coarse aggregate, lb/yd3

No. 67 0 0 1164 1176 n.a. n.a. 1439 1443

No. 7 1254 1250 0 0 1259 1223 0 0

No. 89 194 208 215 218 204 182 0 0

Fine aggregate, lb/yd3

Natural sand (FM = 2.30) 1210 1280 1339 1320 199 211 0 0

Manufactured sand (FM = 2.73) 0 0 0 0 1139 1155 1357 1206

Admixtures, fl oz/cwt

High-range water-reducing admixture 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0

Low-range water-reducing admixture 2.1 1.9 2.1 1.9 2.1 1.9 2.0 2.0

Air-entraining admixture 0.15 0.11 0.18 0.18 0.15 0.18 0.18 0.33

SCC properties

Slump-flow diameter, in. 23 27 22 25 29 28 27 27

U-box H2/H1, % 100 100 86 100 100 100 100 100

L-box Hf /HS1, % 75 75 n.d. n.d. 75 100 n.d. n.d.

Visual stability index 1 1.5 1.5 0 1.5 1 1 1

Note: BL = blend of manufactured and natural sand; FM = fineness modulus; H1 = height of SCC before the gate; H2 = height of SCC after the gate;
Hf = height of SCC at the end of the box; HS1 = height of SCC after the gate; M = manufactured sand; N = natural sand; n.a. = not applicable; n.d. = no
data; SCC = self-consolidating concrete; v = vibration of beam for 5 sec; w/cm = water–cementitious materials ratio. No. 7 aggregate = 1/2 in. diam-
eter; no. 67 aggregate = 3/4 in. diameter; no. 89 aggregate = 3/8 in. diameter. 1 in. = 25.4 mm; 1 lb/yd3 = 0.593 kg/m3; 1 fl oz/cwt = 68.2 mL/100 kg.

each end. Each end also was reinforced with five horizon- were cured in a fog room at 100% humidity and 73 °F
tal layers of no. 4 (M13) bars, four flange confinement (23 °C) until age 28 days.
bars at 12 in. (30 mm) on center, and lifting loops made of
three 1/2-in.-diameter (13 mm) strands. A diaphragm pocket Digital image analysis
was located at the center. This section was considered to
represent a typical, heavily reinforced Georgia Department To quantitatively assess the aggregate distribution in sec-
of Transportation (GDOT) bridge girder. As with the wall tions cut from the hardened SCC, a digital-image-analysis
panels, an external vibrator was attached to one form for method was developed.11 A digital image was taken of ev-
each bulb-tee section and was activated for 5 sec. ery cross section cut through the bulb-tee beams. Using the
shareware ImageJ 1.34, the color images were transformed
The mock-ups were cured under a blanket without steam to 8-bit grayscale images. Next, the threshold level of each
for 18 hours along with test cylinders. Thereafter the image was adjusted. By setting lower and upper threshold
mock-ups remained outside while the control cylinders values, the image was segmented into features of interest

PCI Journal | Wi n t e r 2010 83


9 in.
Seven spaces
5 in. at 9 in. on center 5 in. 6 in.
Lift point location

2 in.
No. 4 reinforcing bar at each end

Two at 6 in.
1
/2 in. strand 1
/2 in. strand

Four spaces at 11 in.


each face

72 in.
No. 4 No. 4
reinforcing bar reinforcing bar
each face

Two at 6 in.
72 in.

2 in.
Figure 3. This diagram shows the reinforcement layout for the wall panels. Note: no. 4 = 13M; 1 in. = 25.4 mm.

and background. In this study, one feature of interest was Surface-finish evaluation Both visual and quan-
the coarse aggregate (in this case, those of size greater than titative inspections of the SCC wall panels were used to
the no. 8 sieve, or 0.1 in. [2.5 mm]), and the background assess the quality of their surface finishes. The walls cast
would constitute the mortar fraction. with mixtures W-1 and W-2 displayed excellent surface
finishes, but the external vibration did not make any dif-
Pixels with brightness values greater than or equal to the ference to the quality of the finish. However, the wall cast
lower threshold and less than or equal to the upper thresh- with mixture W-3 exhibited poor concrete consolidation
old were displayed in red. When the desired threshold level and honeycombing. The larger aggregates of mixture W-3
was achieved, the picture was then converted into a binary were trapped within the wall’s reinforcement, thus blocking
image where aggregates were represented in white and the the flow (Fig. 6). The lower slump flow of the W-3 mixture
paste in black. Using the shareware’s histogram tool, the may have exacerbated the blockage.
fraction of pixels for each color tablet was analyzed. Fig-
ure 5 illustrates the digital-image-analysis process applied Compressive strength of core samples To
in this study. evaluate the in-place properties of the SCCs, 3-in.-diameter
(76 mm) cores were taken at nine locations on each wall,
Results three across the length and three through the height. The
cores were drilled and tested 56 days after casting of the
Wall panels walls. Table 3 gives the strengths of the cores. A single
core was taken at each of the nine positions, and the near
Table 1 reports slump-flow, VSI, U-box, and L-box results. end was that where the SCC was placed. Cores were mois-
Based on visual inspection and testing, the wall-panel ture conditioned per ASTM C42.12
mixtures W-1 and W-2 had better flow and passing char-
acteristics than the W-3 mixture. The wall panels were cast A statistical analysis showed that for mixtures W-1 (made
from each SCC through a single funnel, located just toward with slag and fly ash) and W-2 (made with slag), the
the middle of the wall adjacent to a lifting hook. The SCC vibration, horizontal location, and vertical location of the
flowed from the central placing location to fill the form. cores were not significant factors in the results. That is,
the strength could be considered consistent throughout the
wall panels. Mixture W-3 showed significant horizontal

84 W int e r 2 0 1 0 | PCI Journal


Figure 4. Eight 13-ft-long (4.0 m), 72-in.-deep (1.8 m) bulb-tee (BT-72) mock-up beams were constructed with forty-two 0.6-in.-diameter (15 mm) strands.

and vertical variation in strength. It was concluded that the Bulb-tee beams
reinforcement significantly inhibited the flow of mixture
W-3 with its larger aggregate and lower slump flow. Based on visual inspection and testing (Table 2), each
bulb-tee mixture was considered to be good-quality SCC.
Aggregate distribution Each of the wall panels was Each 3.0 yd3 (0.76 m3) batch was delivered from the batch
sawed vertically to analyze the distribution of aggregates location about 300 ft (90 m) to the beam using a conveyor
throughout their cross sections. A vertical cut was made truck. The SCC was placed in each beam at a single point
about 1 ft (30 mm) away from each end of each wall. When about 20 in. (510 mm) from one end between the pickup
looking at the walls cast with slag and with slag plus, an loops and the no. 6 (M19) stirrups. The pickup loops
even distribution of the aggregates was noticed for all did inhibit flow of the SCC. The beams are designated
sections. No voids were found beneath or around the rein- based on the maximum size of aggregate, type of sand,
forcement at any level, indicating that there was excellent and whether vibration was used, so beam 7Nv used no. 7
consolidation and that there was no bleeding. However, for stone, natural sand, and vibration. The M and BL stand for
mixture W-3 with portland cement only, the far-end surface manufactured sand and blended natural and manufactured
was characterized by large air voids and loose aggregate sand, respectively.
without surrounding paste.

PCI Journal | Wi n t e r 2010 85


Cropping of color image of cut beam cross section Transformation to grayscale image

Threshold definition Final binary image

Figure 5. The digital-image-analysis method quantified the coarse-aggregate distribution.

Figure 6. The larger aggregates of mixture W-3 were trapped within the wall’s reinforcement, thus blocking the flow.

Surface finish In all beams, except for beam 7BL of atively good test results. The air bubbles and bleeding were
mixture 4, air bubbles and bleeding marks were clustered particularly noticeable at the lifting loops and the draped
around the areas of heavier reinforcement, despite their rel- strands. The bleeding marks were thicker and more com-

86 W int e r 2 0 1 0 | PCI Journal


Table 3. Core compressive strength of the self-consolidating concrete wall panels

Mixture W-1 (S-slag/ash, f c' of 11.6 ksi, vibrated) Mixture W-1 (S-slag/ash, f c' of 11.6 ksi, vibrated)

Near end Center Far end Near end Center Far end

Top 10.9 10.5 9.8 Top 11.4 9.7 10.7

Middle 11.5 11.3 11.0 Middle 11.5 10.9 10.9

Bottom 11.4 11.5 11.2 Bottom 11.4 11.0 11.2

Mixture W-1 (S-slag/ash, f c' = 11.6 ksi, nonvibrated) Mixture W-3 (T-cement, f c' = 8.6 ksi, vibrated)

Near end Center Far end Near end Center Far end

Top 11.7 10.1 10.7 Top 9.8 2.2 3.7

Middle 11.2 11.0 10.7 Middle 2.9 5.9 9.3

Bottom 11.2 10.8 10.7 Bottom 9.3 8.0 8.8

Mixture W-2 (G-slag, f c' = 8.6 ksi, vibrated) Mixture W-2 (G-slag, f c' = 8.6 ksi, vibrated)

Near end Center Far end Near end Center Far end

Top 8.8 8.6 8.8 Top 8.6 8.5 8.4

Middle 9.6 9.5 9.0 Middle 8.2 8.2 8.5

Bottom 9.5 8.7 8.8 Bottom 8.2 8.4 8.1

Mixture W-2 (G-slag, f c' = 8.6 ksi, vibrated) Mixture W-2 (G-slag, f c' = 8.6 ksi, vibrated)

Near end Center Far end Near end Center Far end

Top 7.8 7.7 8.4 Top 9.3 9.1 9.0

Middle 8.2 8.3 8.5 Middle 8.6 8.6 9.0

Bottom 8.1 7.9 8.1 Bottom 8.9 8.8 8.8

Note: All measurements are in ksi. f c' = 56-day control cylinder concrete compressive strength. 1 ksi = 6.895 MPa.

mon at the end of the beams where the SCC was placed. In Beams 7BL and 7BLv of mixture 4 presented surface fin-
general, vibrated and nonvibrated beams presented similar ishes that were similar to one another. Both beams showed
surface-finish quality. smooth and clean surfaces with minimal presence of air
bubbles, especially beam 7BLv. The top surface of bot-
Beams 67M and 67Mv of mixture 5 both showed a particu- tom flanges of these beams appeared to be of the highest
larly poor surface finish. Large voids (honeycombing) and quality compared with the rest of the mixtures. Although
bleeding lines around the area of the draped strands were the finish of the bottom flanges was not completely free
observed for both beams. However, the central area of of air voids, the sizes of the bubbles were small and the
the web of these beams displayed a smooth, good-quality bubbles were reduced in number. Materials engineers with
surface finish. This difference in the quality of the sur- GDOT and production personnel with Standard Concrete
face finish within the beams showed that beams 67M and Products said that the surface finish of the beams with 7BL
67Mv were self-flowing but showed limited ability to flow and 7BLv was superior to that obtained in vibrated beams
through the highly congested reinforcement of the BT-72 using conventional concretes.
sections.

PCI Journal | Wi n t e r 2010 87


30 30
Top web vibrated Top web vibrated
Top web nonvibrated Top web nonvibrated
25 Center web vibrated 25 Center web vibrated
Center web nonvibrated Center web nonvibrated

Number of air bubbles


Bottom web vibrated
Number of air bubbles

Bottom web vibrated


Bottom web nonvibrated 20 Bottom web nonvibrated
20 Bottom flange vibrated
Bottom flange vibrated
Bottom flange nonvibrated Bottom flange nonvibrated
15 15

10 10

5 5

0 0
1/8 1/4 3/8 > 7/16 1/8 1/4 3/8 > 7/16
Diameter of air bubbles, in. Diameter of air bubbles, in.

Mixture 1, 7N and 7Nv Mixture 4, 7BL and 7BLv

25 25
Top web vibrated Top web vibrated
Top web nonvibrated Top web nonvibrated
Center web vibrated Center web vibrated
20 20
Center web nonvibrated Center web nonvibrated
Number of air bubbles

Number of air bubbles


Bottom web vibrated Bottom web vibrated
Bottom web nonvibrated Bottom web nonvibrated
15 Bottom flange vibrated 15 Bottom flange vibrated
Bottom flange nonvibrated Bottom flange nonvibrated

10 10

5 5

0 0
1/8 1/4 3/8 > 7/16 1/8 1/4 3/8 > 7/16
Diameter of air bubbles, in. Diameter of air bubbles, in.

Mixture 2, 67N and 67Nv Mixture 5, 67M and 67Mv

Figure 7. This graph plots the number of surface bubbles within ±1/16 in. of the different sizes of bubbles. Note: Mixture proportions are listed in Table 2. BL = blend of
manufactured and natural sand; M = manufactured sand; N = natural sand; v = vibration of beam for 5 sec. 1 in. = 25.4 mm.

Four 1-ft-square (0.3 m) zones were selected for a bubble- 4 in. × 8 in. (100 mm × 200 mm) control cylinders and by
count quantitative surface analysis (Fig. 2). These were at testing 3 in. × 6 in. (76 mm × 152 mm) cores taken from the
the near top, center web, far bottom, and top of the bottom beams. The compressive strength of the mixtures was tested
flange. Figure 7 plots the number of surface bubbles at 1 day, 3 days, 7 days, 28 days, and 56 days, according to
within ±1/16 in. of the following bubble sizes: 1/8 in., 1/4 in., ASTM C39 specifications.14
3
/8 in., and > 7/16 in. (3 mm, 6 mm, 10 mm, and > 11 mm).
The average of four cylinders was reported at each time
For all beams, the region with the greatest number of air period for every mixture. Figure 8 shows the mean com-
bubbles was the top of the bottom flanges. The greater pressive strength achieved by all mixtures used in casting
presence of large bubbles in beams 67N and 67M, includ- of the beams at different ages.
ing 3/8 in. and > 7/16 in. (10 mm and >11 mm) diameter,
were an indication of the poorer consolidation of these Table 4 shows the compressive-strength results for each of
mixtures. The maximum area fractions of air bubbles to nine 3-in.-diameter (75 mm) cores taken from the web of
surface of the beams for beams 67N and 67M were 2.11% each beam. The side surface of the cores showed the same
and 3.41%, respectively. Both were greater than the 2% air-void distributions as did the surface of the beams. The
maximum of entrapped air typical for properly consoli- coefficient of variation (COV) of the compressive strength
dated concrete.13 For beams 7N and 7BL, the maximum air of the cores within a given beam varied among the mixtures,
bubbles to surface ratios were only 0.90% and 0.45%. but all remained below 9.5%, indicating good reproducibil-
ity of the test results. The majority of the mixtures displayed
Compressive strength Compressive strengths of the a COV that ranged from 4.6% to 6.4%, including beams
various mixtures were determined using laboratory-cured 67M and 67Mv (mixture 5). There was not a statistically

88 W int e r 2 0 1 0 | PCI Journal


16,000

14,000

12,000
Compressive strength, psi

10,000

8000

6000
7N 7Nv
7BL 7BLv
4000 67N 67Nv
67M 67Mv
2000

0
0 7 14 21 28 35 42 49 56
Time, days

Figure 8. This graph compares the mean compressive strengths achieved by the mixtures used in casting the beams at different ages taken from the 4 in. × 8 in. (100 mm
× 200 mm) control cylinders. Note: Mixture proportions are listed in Table 2. BL = blend of manufactured and natural sand; M = manufactured sand; N = natural sand; v =
vibration of beam for 5 sec. 1 psi = 6.895 kPa.

significant difference in compressive strength within any was labeled the far end. A visual inspection of the sawed
single beam. Differences in the water–cementitious materi- surfaces revealed no significant differences in the aggregate
als ratio (w/cm) were determined to be the main cause of distribution for any of the beams, with the exception of
differences among the SCCs of the beams. beam 67M (mixture 5). No major variations were observed
between top and bottom areas in a given cross section
No significant differences were observed between the (Fig. 9) or between the near- and far-end surfaces. Also, no
strength of cores and laboratory-cured cylinders, with the voids were observed around the reinforcement in any of the
exception of beams 7N, 7Nv, and 67N (Table 5). For these beams but 67N and 67M, indicating good consolidation of
three mixtures, the cores’ adjusted compressive strengths the concrete with no evidence of internal bleeding.
were about 15% weaker than the control-cylinder strengths
(Table 5). This suggests that proper consolidation was However, beams 67M and 67Mv presented noticeable
not achieved for beams 7N, 7Nv, and 67N in the bulb-tee differences in coarse-aggregate distribution throughout
beams. In contrast, the compressive strength of core sam- the beams. That is, although no perceptible differences
ples from beams 67M and 67Mv (mixture 5) was similar to were observed within a given sawed surface, considerable
that of their control cylinders. This confirmed that proper change in the aggregate–to–concrete area ratio was de-
consolidation was achieved by these mixtures in the upper tected when comparing the near-end surface with the far-
areas of the beams where the cores were taken and where end surface for these two mixtures. Coarse aggregate at the
less-congested reinforcement was present. near-end surface occupied a larger percentage of the area
of the bottom flange of the beams, and a similar amount
Aggregate distribution The beams were sawed ver- was present at the middle surface of the beams. However,
tically at three locations: 24 in. (610 mm) from each end the bottom flange at the far-end surface showed a consid-
and at midlength. The cut closer to the casting point was erable reduction of the area occupied by the aggregate.
defined as the near-end surface; the cut at the opposite end

PCI Journal | Wi n t e r 2010 89


Table 4. Compressive strength of cores taken from the eight beams

Beam 7N Beam 7Nv

Near end Center Far end Near end Center Far end

Top 11.5 11.5 11.0 9.6 10.2 Top 10.3 10.8 12.0 11.0 11.2

Middle 12.1  n.d. 11.2  n.d. 9.0 Middle 10.8  n.d. 12.1  n.d. 10.5

Bottom  n.d.  n.d. 11.0  n.d.  n.d. Bottom  n.d.  n.d. 12.0  n.d.  n.d.

Beam 67N Beam 67Nv

Near end Center Far end Near end Center Far end

Top 12.1 11.1 11.8 11.8 13.0 Top 9.8 9.0 9.4 9.6 9.3

Middle 13.0  n.d. 10.6  n.d. 12.3 Middle 8.9  n.d. 10.4  n.d. 9.8

Bottom  n.d.  n.d. 11.8  n.d.  n.d. Bottom  n.d.  n.d. 10.4  n.d.  n.d.

Beam 7BL Beam 7BLv

Near end Center Far end Near end Center Far end

Top 11.6 12.4 12.7 12.4 11.5 Top 9.3 8.6 8.5 9.3 8.5

Middle 11.2  n.d. 12.9  n.d. 12.6 Middle 9.8  n.d. 9.3  n.d. 9.3

Bottom  n.d.  n.d. 12.6  n.d.  n.d. Bottom  n.d.  n.d. 8.0  n.d.  n.d.

Beam 67M Beam 67Mv

Near end Center Far end Near end Center Far end

Top 11.1 11.8 11.9 11.9 11.0 Top 10.8 10.8 10.7 10.3 10.4

Middle 10.5  n.d. 11.9  n.d. 11.0 Middle 10.9  n.d. 10.5  n.d. 10.9

Bottom  n.d.  n.d. 12.0  n.d.  n.d. Bottom  n.d.  n.d. 10.5  n.d.  n.d.

Note: Table 2 lists mixture proportions for the beams. All measurements are in ksi. BL = blend of manufactured and natural sand; M = manufactured
sand; N = natural sand; n.d. = no data; v = vibration of beam for 5 sec. 1 ksi = 6.895 MPa.

Further analysis to quantify the amount of aggregate seg- mum COV within a beam was 9.4% for beam 67M (mix-
regation was performed with digital image analysis. Every ture 5), which was greater than the required 6% specified
beam cross section was divided into five regions: top and in ASTM C9415 for uniformity of the concrete. Beam 7N
bottom flanges and three 18-in.-long (460 mm) regions had a COV at the upper limit of 6%; yet the COVs for the
in the depth of the web. Table 6 illustrates the digital- rest of the beams were about 3.5%.
image-analysis results obtained for each beam. Based on
the mixture proportions, the nominal value for the coarse The quantitative results obtained in the digital image anal-
aggregate–to–concrete ratio of the mixtures by volume was ysis corresponded with the qualitative visual inspection of
32.7%, except for beams 67N and 67Nv (mixture 2), which the sawed surfaces. No significant aggregate segregation
was 31.5%. was found in the studied cross sections, except for those of
beams 67M and 67Mv (mixture 5). For the beams where
The general trend found with the digital-image-analysis no segregation was observed, the maximum difference
method was that the greatest differences in percentage of obtained between the theoretical and in-place aggregate
aggregate occurred when comparing the bottom flange at percentage was 4.6%, which is about equal to the COV
the near end with the top flange at the far end. The maxi- obtained for these beams.

90 W int e r 2 0 1 0 | PCI Journal


Table 5. Comparison of average compressive strength at 56 days of control cylinders versus core samples of self-consolidated concrete beams

Beam f c' of 4 in. × 8 in. control cylinders, psi f c' of 3 in. × 6 in. cores, psi Strength ratio: core/control, %

7N 13,000 10,600 81.5

7Nv 13,200 11,000 83.3

7BL 11,400 12,000 105.3

7BLv 9300 8800 94.6

67N 14,000 11,800 84.3

67Nv 10,300 9500 92.2

67M 11,300 11,200 99.1

67Mv 10,600 10,500 99.1

Note: 3 in. × 6 in. core strength was adjusted to equivalent 4 in. × 8 in. cylinder strength by multiplying the strength by a factor of 0.98. BL = blend of
manufactured and natural sand; f c' = concrete compressive strength; M = manufactured sand; N = natural sand; v = vibration of beam for 5 sec. Note:
1 in. = 25.4 mm; 1 psi = 6.895 kPa.

In general, the aggregate-to-concrete ratio was lower at the Initial and final compressive strengths were more depen-
far end than at the near end. Also, the ratio was lower at dent on the w/cm than the fly-ash class or whether slag or
the top than at the bottom. These two trends showed that fly ash was the SCM used. However, the size and grada-
there was some, though slight, aggregate segregation as the tion of the aggregates should be considered the most im-
SCC flowed from the near end to far end and as it filled the portant factors affecting the performance of SCC mixtures.
beam from bottom to top. Not only the individual gradation of each aggregate but
the combined gradation of both coarse and fine aggregates
Discussion should be taken into account when designing a workable
SCC mixture.
Overall, the mock-up tests using wall panels and PCI BT-
72 sections showed similar results. That is, the use of either Figure 10 illustrates the aggregate gradation for selected
Type I (walls) or Type III (BT-72) cement did not signifi- mixtures, with good-performing mixtures represented
cantly influence the flowability or passing ability of the with solid lines and those mixtures with poor performance
mixtures. Different SCMs were used with no significant represented with dashed lines. The mixtures with the best
differences in flow and filling ability of the SCCs depend- plastic performance showed a lower percentage of stones
ing on the type or percentage of SCM employed. That is, retained on larger-sized sieves, such as 3/4 in. (19 mm) and
the slag and Class F fly-ash mixtures in the walls worked 1
/2 in. (13 mm). This result was intuitive: the larger the size
as well as the Class C fly ash used in the BT-72 sections. of the stone used, the greater the blockage potential of the

Figure 9. A beam made from mixture 7N shows that no major variations were observed between top and bottom areas in the far-end cut of the beam.

PCI Journal | Wi n t e r 2010 91


Table 6. Aggregate distribution for self-consolidating concrete beams, aggregate–to–total concrete area ratio, %

Beam 7N Beam 7Nv

Near end Center Far end Near end Center Far end

TF 30.7 27.9 24.0 TF 29.6 28.7 29.1

TW 29.2 27.8 26.4 TW 29.7 29.3 30.8

MW 28.1 28.6 26.3 MW 29.5 29.3 30.2

BW 29.3 29.7 28.7 BW 31.6 31.7 29.2

BF 29.5 30.1 28.6 BF 32.4 31.6 30.7

Beam 67N Beam 67Nv

Near end Center Far end Near end Center Far end

TF 28.7 28.9 27.4 TF 29.4 26.9 28.1

TW 27.9 29.5 27.7 TW 29.6 29.6 29.2

MW 28.7 30.2 28.1 MW 30.3 29.5 29.7

BW 29.3 30.0 29.6 BW 30.5 30.3 30.7

BF 30.9 30.5 30.0 BF 30.6 29.8 30.9

Beam 7BL Beam 7BLv

Near end Center Far end Near end Center Far end

TF 32.4 29.2 30.9 TF 30.0 32.3 31.2

TW 31.4 29.8 30.4 TW 31.9 31.7 31.8

MW 32.1 30.0 30.5 MW 32.2 31.8 31.3

BW 32.5 30.8 30.8 BW 32.3 32.1 32.8

BF 32.3 31.9 31.2 BF 32.2 32.7 32.6

Beam 67M Beam 67Mv

Near end Center Far end Near end Center Far end

TF 31.5 30.4 26.2 TF 31.1 30.4 28.4

TW 32.8 30.7 26.3 TW 31.2 30.7 30.4

MW 32.5 31.8 23.6 MW 30.3 31.8 31.0

BW 32.8 28.7 29.3 BW 30.4 28.7 30.1

BF 32.5 32.4 29.1 BF 32.5 32.4 32.4

Note: Table 2 lists mixture proportions. BF = bottom flange; BL = blend of manufactured and natural sand; BW = bottom web; M = manufactured sand;
MW = midweb; N = natural sand; TF = top flange; TW = top web; v = vibration of beam for 5 sec.

mixture when flowing through congested reinforcement. data for mixtures with larger maximum-sized coarse ag-
In addition, larger stones were more susceptible to segre- gregate, such as in beam 67M.
gation, as further evidenced by the digital-image-analysis

92 W int e r 2 0 1 0 | PCI Journal


35
G-slag
30
7BLv
Weight retained, %

25 67M
T-cement
20

15

10

0
16

30

50

n
8
4
.

.
.

in

in
in

10

Pa
o.

o.
2

8
4

o.

o.

o.

o.
N

N
1/

3/
3/

N
Sieve size

Figure 10. This graph illustrates the aggregate gradation for selected mixtures, with good-performing mixtures represented by solid lines and those mixtures with poor
performance represented by dashed lines. Note: BL = blend of manufactured and natural sand; M = manufactured sand; v = vibration of beam for 5 sec. 1 in. = 25.4 mm.

In addition, the workable mixtures displayed a smoother with only no. 67 (3/4 in. [19 mm]) stone9 as coarse aggre-
gradation of the fine aggregate, with a maximum differ- gate and manufactured sand as fine aggregate (beams 67M
ence of 7% between the weight of aggregates retained on and 67Mv) showed good results. Nevertheless, casting of
sieve no. 16 (0.047 in. [1.18 mm]) and that retained on BT-72 mock-up beam sections using these mixtures pro-
sieve no. 50 (0.012 in. [300 μm]).16 This type of gradation duced beams with honeycombing and multiple air voids in
was not achieved by mixture W-3, which displayed large the surface finish. This suggests that construction of mock-
gaps for both coarse and fine aggregates and corresponded up sections and subsequent analysis of cores and cut cross
with its poor performance in wall construction. Poorly sections are necessary for assessing the quality of SCCs
performing beam 67M showed smooth fine-aggregate considered for casting highly congested sections.
gradation similar to that of good-performance mixtures,
yet it slightly differed from those in its coarse-aggregate Conclusion
gradation, demonstrating the importance in limiting the
maximum aggregate size to produce good-quality SCC for This research examined the performance of seven different
congested sections. SCC mixtures, with wall panel mock-ups cast from three
mixtures and bulb-tee-beam mock-ups cast from four mix-
Indicators proposed by Ramage et al.8 for good stability tures. Performance was assessed by measuring compres-
and self-consolidating qualities of SCC in laboratory mix- sive strength, where the strengths of cores obtained from
tures, including fresh VSI numbers from 0 to 1, slump-flow different locations in the mock-ups were compared with
spread from 22 in. to 28 in. (560 mm to 710 mm), and more companion samples cast in the laboratory, and by assess-
than 85% H2/H1 in the U-flow test, agreed with the results ment of coarse-aggregate distribution in sections cut in
of good-quality SCCs in this study of field applications. the mock-ups. In addition to qualitative visual inspection,
digital image analysis for the quantification of coarse-
However, those measurements were not sufficient for aggregate distribution at section cuts was developed and
predicting a mixture’s performance in congested sections. applied.
As an example, fresh-state testing of trial batches produced

PCI Journal | Wi n t e r 2010 93


Among other factors, the research examined the influence Hodgins of Sika Chemical Corp. generously donated time,
of aggregate maximum size and gradation and the influ- knowledge, and materials for this project. Joe Golden
ence of some external vibration on the quality of mock-up at Tindall Concrete and Craig Thompson, John Howell,
sections produced with highly congested reinforcement. and Richard Potts at Standard Concrete Products were
The maximum size and combined gradation of the aggre- extremely helpful and cooperative in conducting the field
gates were considered the most important factors affecting research. Georgia Institute of Technology student Alen
the performance of SCC mixtures. Good-quality SCCs Horta, with assistance from Robert Haines, Richard Jen-
used a blend of coarse and fine aggregates, which cre- nings, Mauricio Lopez, Javier Silva, Ford Burgher, and
ated a smoother aggregate gradation than those mixtures Catherine Prince, conducted the experimental research.
using a single type of stone. The good-quality mixtures
included a blend of no. 7 (1/2 in. [13 mm]) stone and no. 89 We especially thank the paper reviewers and Emily Lorenz
(3/8 in. [10 mm]) stone and also a blend of fine aggregates, and Carrie Wyrick for their careful editing of the manu-
including natural and manufactured sand. The use of no. script.
67 (3/4 in. [19 mm]) stone was shown to be inappropriate
when the clear distance between reinforcement was 1.5 in. The opinions and conclusions expressed herein are those
(38 mm) or less. Aggregate segregation and honeycombing of the authors and do not represent the opinions, conclu-
occurred when this type of mixture was used in the end- sions, policies, standards, or specifications of GDOT or of
wall panels and BT-72 beam sections. the other sponsoring and cooperating organizations.

The application of 5 sec of external vibration on the References


forms was found to have no effect on the external surface
finish compared with samples with no vibration. Further 1. Do, Nam, Blake Stanton, and W. Micah Hale. 2006.
research should consider whether vibration for a longer High Strength SCC Mixtures for Prestressed Bridge
duration would improve surface finish without causing Girders. In Proceedings PCI National Bridge Confer-
segregation. ence, Grapevine, TX, October 2006. CD-ROM.

Of significance is the observation that for sections with 2. Burgueno, Rigoberto, and David Bendert. 2006.
highly congested reinforcement, standard SCC test Experimental Evaluation and Field-Monitoring of
methods—including slump flow, VSI, L-box, and U-box Self-Compacting Concrete Prestressed Box Beams for
tests—may not accurately predict mixture performance Demonstration Bridge. In Proceedings PCI National
during casting. Although standard testing suggested good Bridge Conference, Grapevine, TX, October 2006.
performance for mixtures 67M and 67Mv, they showed ex- CD-ROM.
tensive honeycombing and poor surface finish when used
to cast bulb-tee beams with congested reinforcement. 3. American Concrete Institute (ACI) Committee 237.
2007. Self-Consolidating Concrete. ACI 237R-07.
Based on these findings, construction of mock-up sections Farmington Hills, MI: ACI.
is recommended when developing and characterizing SCC
mixtures for use in deep sections with highly congested 4. Hughes, D. G., G. F. Knight, and E. F. Manski. 2002.
reinforcement. While the use of aggregate gradation and Self-Consolidating Concrete: Case Studies Show
standard slump flow, L-box, and U-box tests are recom- Benefits to Precast Concrete Producers. In First North
mended for development of good SCC mixture propor- American Conference on the Design and Use of Self-
tions, construction and inspection of prototype samples are Consolidating Concrete, pp. 361–366. Chicago, IL:
required to ensure a good-quality product. Digital-image- Hanley-Wood LLC.
analysis methods may also be used to quantitatively assess
the quality of in-place SCC. SCC that passed the standard 5. Hughes, J. J. 2002. Evaluation of Self-Consolidating
laboratory-type evaluations had difficulty passing the Concrete Summary Report. In First North American
highly congested reinforcement in deep sections. Conference on the Design and Use of Self-Consoli-
dating Concrete, pp. 259–265. Chicago, IL: Hanley-
Acknowledgments Wood LLC.

The research presented in this paper was sponsored by the 6. Ozyildirim, C., and S. Lane. 2003. Evaluation of Self-
Georgia Department of Transportation under GDOT task Consolidating Concrete. Final report for the Virginia
order no. 02-07, research project no. 2042. Transportation Research Council, Charlottesville, VA,
www.virginiadot.org/vtrc/main/online_reports/pdf/
Valuable support and guidance from GDOT were provided 03-r13.pdf.
by Paul Liles and Myron Banks. Gary Knight of Holcim
Cement and Bruce Strickland, Darrell Barbee, and Ralph

94 W int e r 2 0 1 0 | PCI Journal


7. PCI. 2003. Guidelines for Self-Consolidating Concrete
in Precast/Prestressed Concrete Institute Member Notation
Plants. TR-6-03. Chicago, IL: PCI.
COV = coefficient of variation
8. Ramage, Brooke, Lawrence Kahn, and Kimberly
Kurtis. 2004. Evaluation of Self-Consolidating Con- f c' = concrete compressive strength
crete for Bridge Structure Applications: Laboratory
Investigation. Research report 04-2, p. 263, School of H1 = height of self-consolidating concrete before the
Civil & Environmental Engineering, Georgia Institute gate in the U-box
of Technology, Atlanta, GA.
H2 = height of self-consolidating concrete after the gate
9. ASTM C33-05. Standard Specification for Concrete in the U-box
Aggregates. In Annual Book of ASTM Standards,
American Society for Testing and Materials. West Hf = height of self-consolidating concrete at the end of
Conshohocken, PA: ASTM International. the box in the L-box

10. PCI Bridge Design Manual Steering Committee. 1999. HS1 = height of self-consolidating concrete after the gate
Precast Prestressed Concrete Bridge Design Manual. in the L-box
MNL-133. Chicago, IL: PCI.
w/cm = water–cementitious materials ratio
11. Horta, Alen. 2005. Evaluation of Self-Consolidating
Concrete for Bridge Structure Applications. Mas-
ter’s thesis, p. 228, Georgia Institute of Technology,
Atlanta, GA.

12. ASTM C42-05. Standard Test Method of Obtaining


and Testing Drilled Cores and Sawed Beams of Con-
crete. In Annual Book of ASTM Standards, American
Society for Testing and Materials. West Conshohock-
en, PA: ASTM International.

13. Walker, Hollis N. 1992. Petrographic Methods of Ex-


amining Hardened Concrete: A Petrographic Manual.
FHWA/VA-R14. Virginia Transportation Research
Council, Virginia Dept of Transportation, Charlottes-
ville, VA.

14. ASTM C39-05. Standard Test Method for Compres-


sive Strength of Cylindrical Concrete Specimens. In
Annual Book of ASTM Standards, American Society
for Testing and Materials. West Conshohocken, PA:
ASTM International.

15. ASTM C94-05. Standard Specification for Ready-


Mixed Concrete. In Annual Book of ASTM Standards,
American Society for Testing and Materials. West
Conshohocken, PA: ASTM International.

16. ASTM C136-05. Standard Specification for Sieve


Analysis of Fine and Coarse Aggregates. In Annual
Book of ASTM Standards, American Society for Test-
ing and Materials. West Conshohocken, PA: ASTM
International.

PCI Journal | Wi n t e r 2010 95


About the authors of the SCC throughout the depth and length of the
elements. Analysis included the use of digital image
Lawrence F. Kahn, PhD, P.E., is analysis. While conventional SCC testing by slump
a professor in the School of Civil flow, U-flow, and L-box methods suggested that most
and Environmental Engineering of the mixtures were of good quality, this research
at Georgia Institute of Technol- showed that such test methods were not sufficient for
ogy in Atlanta, Ga. predicting a mixture’s performance in congested sec-
tions. Only construction of mock-up sections showed
the true self-consolidating performance in congested
Kimberly E. Kurtis, PhD, is an sections.
associate professor in the School
of Civil and Environmental Keywords
Engineering at Georgia Institute
of Technology. Digital image analysis, flowability, SCC, segregation,
self-consolidating concrete.

Review policy
Synopsis
This paper was reviewed in accordance with the
Eight planar 6-in.-thick × 6-ft-deep × 6-ft-wide (150 Precast/Prestressed Concrete Institute’s peer-review
mm × 1.8 m × 1.8 m) wall sections and eight 13-ft- process.
long (4.0 m) bulb-tee (BT-72) beam sections, all with
highly congested reinforcement, were fabricated in Reader comments
two precast concrete plants using self-consolidating
concrete (SCC). The compressive strengths of cores, Please address any reader comments to PCI Journal
taken at different locations on each of the walls and editor-in-chief Emily Lorenz at elorenz@pci.org or
beams, were compared to determine whether proper- Precast/Prestressed Concrete Institute, c/o PCI Journal,
ties varied with location. Also, the specimens were cut 209 W. Jackson Blvd., Suite 500, Chicago, IL 60606. J
vertically at different locations to assess segregation

96 W int e r 2 0 1 0 | PCI Journal

You might also like