Professional Documents
Culture Documents
Specification 11.01
MAMTECH SERVICES LIMITED
Specification 11.01
12/12/15 1
SECTION
1.0 SCOPE
3.0 REQUIREMENTS
4.1 General
5.4 Rotameters
Page 1 of 25
MAMTECH SERVICES LIMITED
Specification 11.01
SECTION
APPENDIX
Page 2 of 25
MAMTECH SERVICES LIMITED
Specification 11.01
P&IDs
Flow Diagrams
Data Sheets
Engineering Specifications
2.1 The contractor shall consider the most recent edition of applicable
standards and codes issued by the following associations and approved
bodies as part of this specification:
3.0 REQUIREMENTS
Page 3 of 25
MAMTECH SERVICES LIMITED
Specification 11.01
4.1 General
4.1.5 Contractor shall visually inspect instrument equipment upon receipt for
damage and for conformance to the specifications and purchase
requisition(s). Any damage to equipment or deviation from the
specifications or requisitions shall be noted and reported immediately to
Company and to the party responsible for the equipment procurement.
4.1.6 Unless otherwise specified, Contractor shall provide all material and
hardware required for mounting instrument equipment, instrument
piping/tubing, and related equipment and accessories. Contractor shall
furnish instrument stands, supports, or mounts as required.
Page 4 of 25
MAMTECH SERVICES LIMITED
Specification 11.01
4.3.1 Control valves, relief valves, level devices, and other instruments that
will be installed in piping or on vessels shall be protected so that foreign
matter cannot enter the fittings, diaphragms, tubes, and other internal
parts of the instrument.
4.3.3 Components shall not be placed in a position that will allow foreign
material such as sandblasting materials, metal shavings, paint spray,
and rust scale to contaminate the interior. Completed units shall not be
transported until all unused openings are properly sealed or covered.
4.3.4 Tubing, piping, fittings, and valves used in the installation of pneumatic
instruments shall be kept free from moisture and foreign matter. All
connections and ports shall be kept sealed during storage and handling.
4.3.5 Contractor shall ensure that instruments and equipment are installed so
they are accessible for maintenance and replacement.
4.3.6 Instrumentation system design and final installation shall be suitable for
the environmental conditions specified in the Project Technical
Requirements.
Page 5 of 25
MAMTECH SERVICES LIMITED
Specification 11.01
Gas and vapor flow Standard cubic feet per hour (SCFH)
at 14.7
pounds per square inch absolute (PSIA) at
60oF
(0.987 Bars at 16oC)
5.2.5 Pneumatic instruments shall not be located in areas where the ambient
Page 6 of 25
MAMTECH SERVICES LIMITED
Specification 11.01
5.2.10 Local instruments shall be mounted no more than 30 feet from the point
of measurement.
5.2.12 Local control and transmitting instruments shall be mounted such that
the centerline of the device is 4 feet, 6 inches above the platform deck.
Local indicators may be mounted up to 7 feet, 6 inches above the
platform deck.
5.2.16 The capillary tubing of filled and sealed instruments shall be adequately
supported and protected from damage. Capillary tubing shall not be cut
or removed. Any extra length of tubing shall be neatly coiled at the
instrument end. The manufacturer's minimum recommended bending
radius shall be followed for any required bends.
5.2.17 Junction boxes shall be mounted in the vertical plane. Unused entry
hubs and holes shall be plugged and sealed.
Page 7 of 25
MAMTECH SERVICES LIMITED
Specification 11.01
5.4 Rotameters
5.5.1 Orifice plates shall be installed with the beveled edge facing
downstream.
5.7.1 Pressure gauges shall be liquid filled and shall have a minimum
Page 8 of 25
MAMTECH SERVICES LIMITED
Specification 11.01
5.7.3 Process liquid shall not be piped directly to instruments in the control
rooms. Process liquids shall be piped to a local transmitter with output
to a control room indicating device.
5.7.4 Pressure transmitters and controllers shall be provided with supply and
output pressure gauges.
5.9.1 Nominal instrument air supply pressure shall be 100 PSIG. Supply
pressure can be as low as 80 PSIG or as high as 125 PSIG.
5.9.3 Instrument air supply tubing from the instrument air header to
instrument pressure regulators shall be 1/2-inch O.D., 0.049-inch wall
thickness stainless steel tubing.
5.9.4 A 1/2-inch, 316 stainless steel ball valve shall be installed upstream of
each regulator.
Page 9 of 25
MAMTECH SERVICES LIMITED
Specification 11.01
5.10.1 Tubing
5.10.1.1 All tubing shall be 316 stainless steel, seamless, conforming to ASTM
A269. The tubing shall be supplied in standard 10 or 20 foot lengths.
Coiled or bundled tubing is not acceptable.
5.10.1.2 Process tubing shall be 1/2-inch O.D. with a .065-inch minimum wall
thickness (W.T.). Manual deluge, control signal, fusible plug loop, and
instrument air supply tubing (downstream of regulators) shall be 3/8-
inch O.D., 0.049 W.T. All other installations shall use 1/4-inch O.D., .035-
inch wall thickness tubing.
5.10.2.1 Tubing fittings shall be 316 stainless steel and shall conform to ASTM
A269.
5.10.2.2 Tubing fittings shall have standard NPT threads. Male threads shall be
rolled. Nuts shall be prelubricated.
5.10.2.3 All fittings for an entire facility including packaged and sub-contractor
supplied equipment shall be of the manufacture specified in the Project
Specification and of the same design.
5.10.2.4 Fittings for pressures above 4000 PSIG shall be approved by Company.
5.10.3 Valves
5.10.3.2 Process tubing valves shall have 316 stainless steel bodies, stems and
trim.
5.10.3.3 Valves in systems with working pressures below 4000 PSIG may have
compression type tubing connectors.
5.10.3.4 Valves in systems with working pressures above 4000 PSIG shall have
barstock bodies with non-rotating stems and threaded end connections.
5.10.3.5 Teflon packing may be provided for services below 400F (204C).
5.10.3.6 Packing shall be flexible graphite with braided carbon/graphite end rings
for services above 400F (204C).
Page 10 of 25
MAMTECH SERVICES LIMITED
Specification 11.01
5.10.5.1 General
Page 11 of 25
MAMTECH SERVICES LIMITED
Specification 11.01
k. All tubing shall be identified with tags at both ends and at all
devices connected to the tubing run. Tags shall be installed on
both sides of bulkheads. On panel or control room interiors, an
engraved, phenolic, black on white bulkhead layout diagram
showing associated tube numbers shall be provided in addition to
individual tags. Tags shall be 1 1/2-inch diameter, 20 gauge 316
stainless steel, with 1/4-inch high characters.
b. Control signal tubing run in electrical cable trays shall meet the
following requirements.
Offset (kicks) for union and tees shall be through the bottom of
the tray.
Page 13 of 25
MAMTECH SERVICES LIMITED
Specification 11.01
5.11.1 General
b. Solenoid valves shall function as pilot devices only and shall not
control process flow.
d. Solenoid valves shall have 316 stainless steel bodies and trim.
e. Solenoid valve diaphragm material shall be Buna-N or Viton.
5.11.4 Enclosures
Process fluids that can congeal upon cooling if heat tracing of the
instrument is not practicable.
5.13 Purging
5.14.1 Nameplates
Manufacturer
Model
Serial number
5.16.1 General
Instrument (component)
Manufacturer
Type
Model number
Material specifications
Performance characteristics
Page 22 of 25
MAMTECH SERVICES LIMITED
Specification 11.01
Page 24 of 25
MAMTECH SERVICES LIMITED
Specification 11.01
INDUSTRY ASSOCIATIONS
Page 25 of 25