2 Introduction
© Siemens AG 2018
All dimensions in mm.
Siemens · 04/2018
© Siemens AG 2018
Introduction
■ Overview
Degree of protection
With cover IP55 IP55
Without cover IP41 IP41
(with door sealing frame)
Dimensions 3-/4-pole W mm 320/410 460/590 460/590 704/914 410 460/590
W D Fixed H mm 434 434 434 434 434 434
D mm 291 291 291 291 291 291
With- H mm 465.5 465.5 465.5 465.5 -- 465.5
H
NSE0_01109a
NSE0_01108a
NSE0_01107a
NSE0_01106a
NSE0_01111a
Rating Plug
2 Siemens · 04/2018
© Siemens AG 2018
Introduction
Breaking capacity
Size I II III
Type 3WL11 3WL12 3WL13
Breaking capacity N S H N S H C H C C
N S H N S H C H C C
3-pole 4-pole
Rated short-circuit breaking capacity
Rated operational voltage Ue
up to 415 V AC
Icu kA 55 66 85 66 80 100 130 100 150 130
Ics kA 55 66 85 66 80 100 130 100 150 130
Icm kA 121 145 187 145 176 220 286 220 330 286
Rated operational voltage Ue
up to 500 V AC
Icu kA 55 66 85 66 80 100 130 100 150 130
Ics kA 55 66 85 66 80 100 130 100 150 130
Icm kA 121 145 187 145 176 220 286 220 330 286
Rated operational voltage Ue
up to 690 V AC
Icu kA 42 50 66 50 75 85 100 85 150 130
Ics kA 42 50 66 50 75 85 100 85 150 130
Icm kA 88 105 145 105 165 187 220 187 330 286
Rated operational voltage Ue
up to 1000 V/1150 V AC
Icu kA -- -- 509) -- -- 50 -- 50 704) 704)
Ics kA -- -- 509) -- -- 50 -- 50 704) 704)
Icm kA -- -- 1059) -- -- 105 -- 105 1544) 1544)
Rated short-time withstand current
Icw of the circuit breakers3)
0.5 s kA 55 66 75 66 80 100 100 100 100 100
1s kA 42 50 66 55 66 85 100 100 100 100
2s kA 29.5 35 46 39 46 651)/702) 70 80 80 80
3s kA 24 29 44 32 44 501)/652) 65 65 65 65
Rated conditional short-circuit
current Icc of the non-automatic air
circuit breakers
Up to 500 V AC kA 55 66 75 66 80 100 130 100 100 100
Up to 690 V AC kA 42 50 66 50 75 85 100 85 100 100
Up to 1000 V/1150 V AC kA -- -- 509) -- -- 504) -- 5010) 704) 704)
Size I II
DC DC
N Circuit breakers with ECO breaking capacity N Abbreviations* English long text Explanation
(functions)
S Circuit breakers with standard breaking capacity S
L Long Time Delay Overload protection
H Circuit breakers with high breaking capacity H
S Short Time Delay Short-circuit protection
Circuit breakers with very high breaking capacity C (short-time delayed)
C
Non-automatic air circuit breakers with DC breaking capacity I Instantaneous Short-circuit protection
DC (instantaneous)
These breaking capacities are indicated in the corresponding tables N Neutral Protection Neutral conductor protection
by the symbols shown on orange backgrounds. G Ground Fault Ground-fault protection
* Designations according to IEC 60947-2, Annex K.
1)
Size II with In max 2500 A.
2)
Size II with In max = 3200 A and In max = 4000 A.
3) 6) At Ue = 300 V DC
At a rated voltage of 690 V, the Icw value of the circuit breaker cannot be
greater than the Icu or Ics value at 690 V. 7) At Ue = 600 V DC
4) 8)
Rated operational voltage Ue = 1150 V. At Ue = 1000 V DC
5) 9)
At Ue = 220 V DC Values also apply to 690 V + 20% version with Z option "A16".
10) Rated operational voltage Ue = 1000 V.
Siemens · 04/2018 3
© Siemens AG 2018
Introduction
3WL1 air circuit breakers:
3WL1 air circuit breakers offer highly flexible application and
consistent communication capability. With the 3WL1 circuit
breakers, just three sizes cover a performance range of 630 A to
6300 A. All models are characterized by the same design, the
same operation and the same comprehensive accessories.
7
2
3 8
5
4
9
1
25
21
10
19
22 11
23
12
24 18 13
17
14
NSE0_01887d
20
16
15
4 Siemens · 04/2018
© Siemens AG 2018
Introduction
Communication-capable circuit breakers (with ETU45B or ETU76B Electronic Trip Unit)
20
Ethernet
18
19
PROFIBUS
PROFINET
13 14 15 16 17 7
4 5 6 21
9 CubicleBUS
3VA-line 3VA-line
10 8
2
1 1 1 11
12
NSE0_01105
3
Siemens · 04/2018 5
© Siemens AG 2018
Introduction
11
6 7 8 10
3VA-line 3VA-line
9
5
3
1 1 1 2 4
I201_19162
1 3VA molded case circuit breakers 7 COM100 breaker data server
2 3WL air circuit breaker 8 7KM PAC4200 measuring device
3 COM16 MODBUS module 9 7KM PAC3100 measuring device
4 3VL molded case circuit breaker 10 7KM PAC3200 measuring device
5 COM21 MODBUS module 11 Powerconfig commissioning and service software V2.3 and higher
6 COM800 breaker data server
Characteristics
• Coordinated communication concept using the PROFIBUS Communication:
DP or MODBUS, ranging from 16 A to 6300 A with 3VL molded • For air circuit breakers with optional communication function
case circuit breakers and 3WL air circuit breakers (ETU45B or ETU76B Electronic Trip Units), see Catalog LV 10.
• The high level of modularity of circuit breakers and accesso- • For accessories, see Catalog LV 10.
ries allows easy retrofitting of all communication components
• For more information, see also Catalog LV 10, chapters
• Significant additional benefits for the switchboard due to the "Measuring Devices and Power Monitoring" and "Software".
possibility of linking up external input and output modules to
the circuit breaker-internal CubicleBUS of the 3WL air circuit
breaker
• Innovative software products for parameterization, operation,
monitoring, and diagnostics of circuit breakers, both locally or
via PROFIBUS DP, MODBUS or Ethernet/Intranet/Internet
• Complete integration of the circuit breakers into the Totally
Integrated Power and Totally Integrated Automation solutions
6 Siemens · 04/2018
© Siemens AG 2018
■ Benefits • Measured values are the basis for efficient load management,
for drawing up power demand profiles and for allocating
Low space requirements energy to cost centers
• Preventive maintenance reduces the risk of expensive plant
The 3WL air circuit breakers require very little space. Size I downtimes
devices (up to 2000 A) fit into a 400 mm wide switchboard panel.
• Metering function with a very wide range of measured values,
Size III devices (up to 6300 A) are the smallest of their kind and
such as current, voltage, energy, power, etc.
with their construction width of 704 mm fit into an 800 mm wide
switchboard panel. • Can be used in 690 V networks
Size I II
Type Up to 3WL11 12 3WL11 16 3WL11 20 3WL12 08 3WL12 10 3WL12 12 3WL12 16 3WL12 20
3WL11 10
Permissible load • Up to 55 C A 1000 1250 1600 2000 800 1000 1250 1600 2000
for withdrawable (Cu bare) A 1000 1250 1600 1930 800 1000 1250 1600 2000
versions • Up to 60 C A 1000 1210 14902) 1780 800 1000 1250 1600 2000
at rear horizontal (Cu bare)1)
main circuit • Up to 70 C
connections (Cu painted black)1)
Main conductor • Copper bars, Unit(s) 1 × 2× 2× 3× 1× 1× 2× 2× 3×
minimum bare mm2 60 × 10 40 × 10 50 × 10 50 × 10 50 × 10 60 × 10 40 × 10 50 × 10 50 × 10
cross-sections Unit(s) 1 × 2× 2× 3× 1× 1× 2× 2× 3×
• Copper bars,
painted black mm2 60 × 10 40 × 10 50 × 10 50 × 10 50 × 10 60 × 10 40 × 10 50 × 10 50 × 10
Size II III
Type 3WL12 25 3WL12 32 3WL12 403) 3WL13 40 3WL13 50 3WL13 633)
Permissible load • Up to 55 C A 2500 3200 39504) 4000 5000 5920
for withdrawable (Cu bare) A 2500 3020 3810 4000 5000 5810
versions • Up to 60 C A 2280 2870 3600 4000 5000 5500
at rear horizontal (Cu bare)1)
main circuit • Up to 70 C
connections (Cu painted black)1)
Main conductor • Copper bars, Unit(s) 2 × 3× 4× 4x 6x 6x
minimum bare mm2 100 × 10 100 × 10 120 × 10 100 x 10 100 x 10 120 x 10
cross-sections • Copper bars, Unit(s) 2 × 3× 4× 4× 6× 6×
painted black mm2 100 × 10 100 × 10 100 × 105) 100 × 10 100 × 10 120 × 10
1) ETU76B with graphics display can be used up to max. 55 C. 5) Minimum main conductor cross-sections for 4-pole withdrawable circuit
2) At breaking capacity H: 1600 A up to 70 C breakers: 4 × 120 mm × 10 mm
3) With rear vertical connections
4) Size II, 3-pole, in fixed-mounted version
Siemens · 04/2018 7
© Siemens AG 2018
■ Design
Circuit breaker Breaking capacity Dimensions
rated current n max (A) With-
cu at 500 V AC (kA) or Fixed-mounted, drawable
cc at 300 V DC (kA) 3-/4-pole 3-/4-pole
4000
2500
Size II
2000
434 / 434 460 / 460 Height
1600 DC N S H
1250 30 66 80 100
800
1250
H 434 / 434 460 / 460 Height
DC N S
1000
800
20 55 66 85
630
291 / 291 385 / 385 Depth
The dimension for the depth of the circuit breaker is from the circuit breaker rear to the inner surface of the closed switchgear door. NSE0_00887q
8 Siemens · 04/2018
© Siemens AG 2018
NSE0_00969b
NSE0_00967b
NSE0_00979a
Other safety features include:
• Infeed from above or below, as required
Horizontal Front connection with Vertical
• Locking of the guide frame with the circuit breaker removed,
connection single hole or double hole connection as standard
• Locking of the withdrawable circuit breaker against
Withdrawable circuit breaker, withdrawable guide frame movement, as standard
• High degree of protection with cover IP55
• Mechanical reclosing lockout after overload or short-circuit
tripping as standard
NSE0_00971b
NSE0_00970b
NSE0_00973b
• The circuit breaker is always equipped with the required
NSE0_00972b
NSE0_00967b
Siemens · 04/2018 9
© Siemens AG 2018
In addition, the withdrawable unit can be adapted to various Motor cutout switch
rated currents of one size. Selector switch for switching off the motorized operating
Withdrawable short-circuit and grounding unit mechanism (automatic charging).
The withdrawable short-circuit and grounding unit consists of a Operating cycles counter
breaker enclosure with blade contacts which are connected with The motorized operating mechanism can be supplied with a
the short-circuiting link. 5-digit operating cycles counter. The display is incremented
Depending on the version, the short-circuiting links are arranged by "1" as soon as the spring energy store is fully charged.
at the top or bottom. The grounding and short-circuit Resetting of the manual tripped signal
connections are established when the device is inserted.
When the circuit breaker has tripped, this is indicated by the
It must be ensured that the side to be short-circuited and protruding red mechanical tripped indicator on the ETU. When
grounded is not live. For this reason it is recommended that the the mechanical tripped indicator is activated, the tripping
withdrawable unit is only cranked in when the door is closed. solenoid and tripped signal are reset. If this manual display is to
be reset remotely, the reset button can be equipped with a reset
Withdrawable bridging unit solenoid.
The withdrawable bridging unit consists of a breaker enclosure This option allows the circuit breaker to be reset both manually
in which all disconnection components and the operating and electrically.
mechanism have been replaced with simple connections
between the upper and lower contacts. Automatic resetting of reclosing lockout
Auxiliary releases When the ETU is tripped, reclosing of the circuit breaker is
prevented until the trip unit is either electrically or manually reset.
Up to two auxiliary releases can be installed at the same time. If the "Automatic resetting of reclosing lockout" option is used,
The following are available for selection: the pre-tensioned circuit breaker is ready to close immediately
1 shunt release after tripping. Resetting the manual "tripped" indicator is not
or 1 undervoltage release included in this option.
or 2 shunt releases Tripped signaling switch
or 1 shunt release
+ 1 undervoltage release If the circuit breaker has tripped due to an overload, short-
circuit, ground fault or extended protection function, the tripped
Signaling switches for auxiliary releases signaling switch can indicate this. This signaling switch is
One signaling contact is used for each auxiliary release to available as an option. If the circuit breaker is used for
determine the positions of the auxiliary releases. communication, this option is supplied as standard.
When the operational voltage is connected to the shunt release, The 3WL circuit breakers are equipped with an optical ready-to-
the circuit breaker is opened immediately. The shunt release is close indicator as standard. In addition, the ready-to-close
available in the versions 5% OP for overexcitation and 100% OP status can be transmitted by means of a signaling switch as an
for permanent excitation. This means that it is also possible to option. If the switch is used for communication, this signaling
block the circuit breaker against being jogged into closing. switch is supplied as standard.
10 Siemens · 04/2018
© Siemens AG 2018
28 1 1 Arc chute
2 Carrying handle
2 3 Labeling plates
27 4 Motor cutout switch (option) or
"Electrical ON" (option)
26 3 5 Type plate for circuit breaker
4 6 Spring charge indicator
25 7 "Mechanical ON" button
5 8 Rated current indication
9 Positioning pictogram
24 10 Operating cycles counter (option)
6
23 11 Hand-operated lever
12 Crank handle
22 7 13 Withdrawable unit drive shaft
14 Equipment plate
21
15 Grounding connection
8 16 Position indicator
17 Table for ground-fault protection
20 9
18 Safety lock for crank handle (option)
19 Mechanical unlocking of crank handle
10
19 (option)
11 20 Electronic trip unit
18 21 Rating plug
22 "Mechanical OFF" button or
17 12 "EMERGENCY-STOP"
13 mushroom pushbutton (option)
16 23 Ready-to-close indicator
14
24 Contact position indicator
15
NSE0_00965b 25 "Tripped" indicator (reset button)
26 "Secure OFF" locking device (option)
27 Operator panel
28 Male connector for auxiliary connections
Guide frames
12
9
11
NSE0_00966b
10
Siemens · 04/2018 11
© Siemens AG 2018
If the circuit breaker is replaced, closing is no longer prevented The locking set contains covering caps which can be sealed.
unless the new circuit breaker is also protected against Sealing device for Electronic Trip Units
unauthorized closing.
The transparent cover can be sealed. The parameter setting
To activate the locking device, the circuit breaker must be sections are covered to prevent unauthorized access. Openings
opened. The locking device is disabled when the circuit breaker allow access to the query and test button.
is closed. The lock is only activated when the key is removed.
The safety key can be removed only in the "OFF" position. Locking mechanisms
Locking device for "Electrical ON" Locking mechanism against movement for withdrawable circuit
(see graphic "Circuit breakers") breakers when the control cabinet door is open
This prevents unauthorized electrical closing from the operator The crank handle is blocked when the control cabinet door is
panel. Mechanical closing and remote closing remain possible. open and cannot be removed. The withdrawable circuit breaker
The lock is only activated when the key is removed. cannot be moved. The lock only affects the inserted crank
handle.
Locking device for "Mechanical ON"
(see graphic "Circuit breakers") Locking of the control cabinet door
This prevents unauthorized mechanical closing. The mechanical The control cabinet door cannot be opened if
ON button can only be activated if the key is inserted (key • the fixed-mounted circuit breaker is closed (the blocking
operation). Closing with the "Electrical ON" button and remote signal is transmitted via the Bowden cable) or
closing remain possible. The lock is only activated when the key • the withdrawable circuit breaker is in the connected position
is removed.
Blocking mechanism using "Mechanical ON" and "OFF" button
"Safe OFF" circuit breaker-independent locking device against
unauthorized closing The "Mechanical ON" and "OFF" buttons are covered with a cap
which only allows actuation with a tool. These cover caps are
This special breaker-independent function for withdrawable part of the interlocking set.
circuit breakers prevents closing and fulfills the requirements for
main control switches to EN 60204 (VDE 0113) – supply discon- Optional equipment for guide frames
necting device. Unauthorized closing remains impossible even
after the circuit breaker has been replaced. Shutters
To activate the lock, the circuit breaker must be opened. The The sealing strips of the shutter seal the laminated contacts of
locking device is disabled when the circuit breaker is closed. the guide frame when the withdrawable circuit breaker is
The lock is only activated when the key is removed. The safety removed and therefore implement touch protection.
key can be removed only in the "OFF" position. The sealing strips can be manually opened using the strip
Locking device for crank handle levers.
Prevents removal of the crank. The circuit breaker is protected The position of the sealing strips can be locked in various
against movement. The lock is only activated when the key is positions using padlocks for securing against tampering.
removed.
Locking device for "Mechanical OFF"
Prevents unauthorized mechanical opening from the operator
panel. The "Mechanical OFF button" can only be activated if the
key is inserted (key operation). Remote opening remains
possible. The lock is only activated when the key is removed.
Locking device for hand-operated lever
The hand-operated lever can be locked with a padlock. The
spring energy store cannot be charged manually.
Locking device against resetting the "tripped" indicator
A lockable cover prevents manual resetting of the "tripped"
indicator after tripping due to overcurrent. This locking device is
supplied together with the transparent cover option for
Electronic Trip Units.
12 Siemens · 04/2018
© Siemens AG 2018
4
4 Withdrawable circuit breaker
right-hand side; left-hand side similar
5 5 Coding pin on guide frame
Rated current coding unit between circuit breaker and guide frame
4
DISCON
NSE0_01033a
NSE0_01037
1 Auxiliary circuit
2 Main circuit
4 Shutter
Disconnected position CONNECT
Disconnected Disconnected Closed Closed
3
TEST
DISCON
NSE0_01034a
NSE0_01038
3 Control cabinet
door
Test position CONNECT
Disconnected Connected Closed Closed
TEST
DISCON
NSE0_01035a
NSE0_01039
TEST
DISCON
NSE0_01036a
NSE0_01040
Siemens · 04/2018 13
© Siemens AG 2018
■ Function
NSE0_00882b
NSE0_00881b
NSE0_00880b
R
R
s d
s d
J s d
J s d
g
J g
NSE0_00950c N S E 0 _ 0 0 9 5 1 b N S E 0 _ 0 0 9 5 2 b
Additional functions
Neutral conductor protection (can be switched on/off) -- -- ✔
N-conductor protection adjustable -- -- --
Short-time delay short-circuit protection (can be switched on/off) -- -- --
Instantaneous short-circuit protection (can be switched on/off) -- -- --
Thermal memory can be switched on/off -- -- --
Load monitoring -- -- --
Short-time delay short-circuit protection switchable to I2t -- -- --
Instantaneous short-circuit protection adjustable ✔ -- --
Overload protection switchable to I4t -- -- --
Overload protection can be switched on/off -- -- --
Selectable parameter sets -- -- --
Metering function
Metering function Plus -- -- --
Communication
CubicleBUS -- -- --
Communication through PROFIBUS DP -- -- --
Communication through MODBUS -- -- --
Communication via Ethernet -- -- --
✔ Standard -- Not available ❑ Optional
Note
Detailed information about the functions of the Electronic Trip Units is given in the following.
14 Siemens · 04/2018
© Siemens AG 2018
ETU76B
Rating Plug
=
12
NSE0_00883b
NSE0_00886c
IR IR
tR tR
Isd Isd
t sd t sd
Ig Ig
Ii Ii
tg tg
ETU45B ETU76B
✔ ✔
✔ ✔
✔ ✔
✔ ✔
❑ ❑
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
-- ✔
-- ✔
✔ --
-- ✔
-- ✔
❑ ❑
❑ --
-- ✔
❑ ❑
✔ ✔
❑ ❑
❑ ❑
❑ ❑
Siemens · 04/2018 15
© Siemens AG 2018
• Metering function
• Display Selectable parameters
• Rating plug In the case of quick changes of power supply conditions,
This allows quick adaptation to new local power supply e.g. for switchover from transformer to generator operation or if
conditions. In addition, innovative functions have been included a section of the supply is disconnected when the shift changes,
in the ETUs. 3WL circuit breakers allow the relevant protection parameters to
be quickly adapted to the new conditions.
Rating plug The ETU76B contains two independent tripping characteristics
The rating plug is an exchangeable module which allows the (parameter sets). The switchover is completed within 200 ms
user to reduce the rated device current so as to adapt it and is performed with the help of an external signal.
optimally to the plant; e.g. if a new plant section is put into
operation. The rating plug must be selected to correspond to the
rated current of the plant.
16 Siemens · 04/2018
© Siemens AG 2018
Test socket
Siemens · 04/2018 17
© Siemens AG 2018
NSE0_00956c
The same as ETU25B but also
• Connectable neutral conductor protection
Indicator: overcurrent
ETU27B N-conductor protection • Permanently integrated ground-fault protection.
release activated
on/off Calculation of the ground-fault current through vectorial
Indicator: overload alarm OFF ON
Query pushbutton
Test pushbutton Clear pushbutton
Test socket
18 Siemens · 04/2018
© Siemens AG 2018
Ground-fault protection Ground-fault releases "G" sense fault currents that flow to ground
and that can cause a fire in the plant. Multiple circuit breakers
Selector for Indicators: Ground-fault connected in series can have their delay times adjusted so as to
ground-fault alarm provide graduated discrimination.
detection
Ground-fault
tripped When setting the parameters for the Electronic Trip Unit it is
Rotary switch possible to choose between "alarm" and "trip" in the event that
for setting
value, the set current value is exceeded. The reason for tripping is
ground-fault indicated by means of an LED when the query button is
protection activated.
Rotary switch
for setting
Rotary switch NSE0_00962 value, ground- The ETU45B and ETU76B Electronic Trip Unit versions can be
for setting value fault protection retrofitted with a ground-fault protection module. This ground-
ground-fault alarm delay tg/ 2 tg fault protection function is integrated in ETU27B Electronic Trip
GFM AT 45B ground-fault module
Units.
Siemens · 04/2018 19
© Siemens AG 2018
A standard current transformer with the following data With the exception of the ETU27B Electronic Trip Unit, all
is used for measurement of the ground-fault current: versions of the ground-fault modules are supplied with
1200 A/1 A, Class 1 (the internal load of the 3WL circuit breaker an I2t characteristic curve which can be activated.
is 0.11 ). The current transformer can be installed directly in the Selection criteria for 3WL circuit breakers
grounded neutral point of a transformer.
Basic criteria for selecting circuit breakers are:
• Max. short-circuit current at place of installation of circuit
breaker Ik max .
L1 This value determines the short-circuit breaking capacity or
L2 short-circuit current carrying capacity of the circuit breaker.
L3
N • It is compared with the value Icu, Ics, Icw of the circuit breaker
T5 PE and essentially determines the size of the circuit breaker.
NSE0_00946a
See Figure "Overview of 3WL circuit breakers/non-automatic
air circuit breakers".
• Rated current In that is to flow through the branch circuit. This
3-pole circuit breakers, current transformers in the N-conductor value must not be higher than the maximum rated current for
the circuit breaker.
L1 The rated current for the 3WL circuit breaker is set with the
L2 rating plug. See Figure "Overview of 3WL circuit breakers/
L3 non-automatic air circuit breakers" under "Design".
N • Ambient temperature for the circuit breaker.
This is usually the control cabinet's internal temperature.
T6
PE • Design of the circuit breaker
T6: 1200 A/1 A NSE0_00947
• Minimum short-circuit current which flows through the
switching device. The trip unit must still detect this value as a
3-pole circuit breakers, current transformers in the grounded neutral short-circuit and must respond by tripping.
point of the transformer
Protection functions of the circuit breaker.
These are defined by selection of the corresponding Electronic
L1
Trip Unit; see table "Functions of the Electronic Trip Units" under
L2
L3
"Functions".
N
T6
PE
NSE0_00948
T6: 1200 A/1 A
20 Siemens · 04/2018
© Siemens AG 2018
■ Configuration
Mutual mechanical circuit breaker interlocks • The bending radii of the Bowden cable must be > 500 mm
The module for mutual mechanical interlocking can be used for • The total bending angle across the length of the Bowden
two or three 3WL circuit breakers and can be adapted easily to cable must not exceed 640°
the corresponding versions. The fixed-mounted and • If the circuit breakers to be interlocked are arranged vertically,
withdrawable circuit breaker versions are fully compatible and the interlock mechanisms must be aligned
can therefore be used in a mixed configuration in an installation. • Circuit breakers to be interlocked must be arranged so that
This also applies to 3WN6 circuit breakers. Bowden cables can be optimally installed in compliance with
The circuit breakers can be mounted adjacent to each other or the conditions mentioned in the above points
one above the other, whereby the distance of the circuit breakers • The installed Bowden cable must be fixed (with cable ties or
is determined solely by the length of the Bowden cable the like) before the interlock is adjusted
(lengths: 2 m/3 m/4.5 m). Interlock signals are looped through
using the Bowden cables. Interlocking is only effective in the • Select the width of switchboard cubicle to allow enough
connected position in the case of withdrawable circuit breakers. freedom of movement for adjusting the interlock!
The mechanical endurance of the Bowden cables is • Openings and cutout sections in system elements must be
10000 operating cycles. designed in such a way that the direction of the Bowden
cables is not changed and that the wires are not obstructed
To ensure that the interlock functions properly, the following when they are routed
minimum switchboard requirements must be fulfilled:
• Bowden cables must be laid so that they are as straight as
possible
Mutual mechanical interlocking of circuit breakers – examples
Mutual interlocking of two Interlocking of three circuit Mutual interlocking of three Interlocking of three circuit
circuit breakers breakers circuit breakers breakers, two of them mutual
S1 S2 S1 S3 S1 S3
S1 S2 S3
S2 S2
S1 S2 S3
Siemens · 04/2018 21
© Siemens AG 2018
20
Ethernet
18
19
PROFIBUS
PROFINET
13 14 15 16 17 7
4 5 6 21
9 CubicleBUS
3VA-line 3VA-line
10 8
2
1 1 1 11
12
NSE0_01105
3
22 Siemens · 04/2018
© Siemens AG 2018
11
6 7 8 10
3VA-line 3VA-line
9
5
3
1 1 1 2 4
I201_19162
1 3VA molded case circuit breakers 7 COM100 breaker data server
2 3WL air circuit breaker 8 7KM PAC4200 measuring device
3 COM16 MODBUS module 9 7KM PAC3100 measuring device
4 3VL molded case circuit breaker 10 7KM PAC3200 measuring device
5 COM21 MODBUS module 11 Powerconfig commissioning and service software V2.3 and higher
6 COM800 breaker data server
The requirements for power distribution in terms of communica- The high modularity of the system allows retrofitting of communi-
tion capability, data transparency, flexibility and integration are cation functions (e.g. metering function) at any time. Similarly, a
constantly increasing. An integrated and modular communica- non-communication-capable 3WL circuit breaker can be
tion architecture was designed for the 3WL circuit breaker to upgraded (e.g. changeover from ETU25B to ETU45B with
ensure that it can satisfy these requirements. CubicleBUS) easily on site in the plant. All modules connected
to the CubicleBUS can directly access the existing source data
The core component of this architecture is the CubicleBUS, of the circuit breaker, which guarantees the quickest possible
which links together all of the intelligent components within the access to information and response to events.
3WL circuit breaker and enables the easy and safe connection
of other additional external components to the circuit breaker. Furthermore, additional external modules (including digital
The CubicleBUS is already incorporated and connected in all inputs and outputs, analog outputs) can be connected to the
complete circuit breakers with ETU45B and ETU76B trip units. CubicleBUS to provide cost-effective solutions for the
automation of additional devices in the switchboard.
Siemens · 04/2018 23
© Siemens AG 2018
24 Siemens · 04/2018
© Siemens AG 2018
Siemens · 04/2018 25
© Siemens AG 2018
26 Siemens · 04/2018
© Siemens AG 2018
■ Technical specifications
Size I II
Type ... 3WL11 10 3WL11 12 3WL11 16 3WL11 20 3WL12 08 3WL12 10 3WL12 12 3WL12 16
Number of poles 3-pole, 4-pole
Rated current In at 40 °C, at 50/60 Hz
Main conductor A ... 1000 1250 1600 2000 800 1000 1250 1600
N-conductor (only on 4-pole versions) A ... 1000 1250 1600 2000 800 1000 1250 1600
Rated operational voltage Ue at 50/60 Hz V AC ... ... ... ... ... ... ... ...
(1000 V version, see Catalog LV 10 "Options") 690/1000 690/1000 690/1000 690/1000 690/1000 690/1000 690/1000 690/1000
Rated insulation voltage Ui V AC 1000 1000 1000 1000 1000 1000 1000 1000
Rated impulse withstand voltage Uimp
• Main conducting paths kV 12 12 12 12 12 12 12 12
• Auxiliary circuits kV 4 4 4 4 4 4 4 4
• Control circuits9) kV 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5
Isolating function acc. to EN 60947-2 Yes Yes Yes Yes Yes Yes Yes Yes
Utilization category B
Permissible ambient temperature
• During operation (in operation with LCD max. 55 °C)1) C –25/+70 –25/+70 –25/+70 –25/+70 –25/+70 –25/+70 –25/+70 –25/+70
• Storage C –40/+70 –40/+70 –40/+70 –40/+70 –40/+70 –40/+70 –40/+70 –40/+70
Permissible load for • Up to 55 C (Cu bare) A 1000 1250 1600 2000 800 1000 1250 1600
withdrawable versions • Up to 60 C (Cu bare)2) A 1000 1250 1600 1930 800 1000 1250 1600
at rear horizontal main circuit • Up to 70 C A 1000 1210 14903) 1780 800 1000 1250 1600
connections (Cu painted black)2)
Rated rotor operational voltage Uer V 2000 2000 2000 2000 2000 2000 2000 2000
Power loss at In
With 3-phase symmetrical load
• Fixed-mounted circuit breakers W 100 105 150 240 40 45 80 85
• Withdrawable circuit breakers W 195 205 350 440 85 95 165 175
Switching times
• Make time ms 35 35 35 35 35 35 35 35
• Opening time ms 38 38 38 38 34 34 34 34
• Electrical make time (through closing coil)4) ms 80 80 80 80 100 100 100 100
• Electrical opening time (through shunt release) ms 73 73 73 73 73 73 73 73
• Electrical opening time (instantaneous undervoltage ms 73 73 73 73 73 73 73 73
release)
• Opening time due to ETU, instantaneous short-circuit ms 50 50 50 50 50 50 50 50
release
Service life: Breaking capacity N and S, 3-/4-pole
• Mechanical (without maintenance) Operating cycles 10 000 10 000 10 000 10 000 10 000 10 000 10 000 10 000
• Mechanical (with maintenance)5) Operating cycles 20 000 20 000 20 000 15 000 15 000 15 000 15 000 15 000
• Electrical (without maintenance) Operating cycles 10 000 10 000 10 000 7500 7500 7500 7500 7500
• 1000 V version, electrical (without maintenance) Oper. cycles -- -- -- -- -- -- -- --
• 1150 V version, electrical (without maintenance) Oper. cycles -- -- -- -- -- -- -- --
• Electrical (with maintenance)5) Operating cycles 20 000 20 000 20 000 15 000 15 000 15 000 15 000 15 000
Service life: Breaking capacity H, 3-pole
• Mechanical (without maintenance) Operating cycles 10 000 10 000 10 000 10 000 10 000 10 000 10 000 10 000
• Mechanical (with maintenance)5) Operating cycles 15 000 15 000 15 000 15 000 15 000 15 000 15 000 15 000
• Electrical (without maintenance) Operating cycles 7 500 7 500 7 500 7500 7500 7500 7500 7500
• 1000 V version, electrical (without maintenance) Oper. cycles 1000 1000 1000 1000 1000 1000 1000 1000
• 1150 V version, electrical (without maintenance) Oper. cycles -- -- -- -- 500 500 500 500
• Electrical (with maintenance)5)6) Operating cycles 15 000 15 000 15 000 15 000 15 000 15 000 15 000 15 000
Service life: Breaking capacity H, 4-pole
• Mechanical (without maintenance) Operating cycles 10 000 10 000 10 000 10 000 10 000 10 000 10 000 10 000
• Mechanical (with maintenance)5) Operating cycles 15 000 15 000 15 000 15 000 15 000 15 000 15 000 15 000
• Electrical (without maintenance) Operating cycles 7 500 7 500 7 500 7500 7500 7500 7500 7500
• 1000 V version, electrical (without maintenance) Oper. cycles 1000 1000 1000 1000 1000 1000 1000 1000
• 1150 V version, electrical (without maintenance) Oper. cycles -- -- -- -- 500 500 500 500
• Electrical (with maintenance)5)6) Operating cycles 10 000 10 000 10 000 10 000 15 000 15 000 15 000 15 000
Service life: Breaking capacity C
• Mechanical (without maintenance) Operating cycles -- -- -- -- 5 000 5 000 5 000 5 000
• Mechanical (with maintenance)5) Operating cycles -- -- -- -- 10 000 10 000 10 000 10 000
• Electrical (without maintenance) Operating cycles -- -- -- -- 5 000 5 000 5 000 5 000
• Electrical (with maintenance)5) Operating cycles -- -- -- -- 10 000 10 000 10 000 10 000
Switching frequency7)
• 690 V version 1/h 608) 608) 608) 60 608) 608) 608) 608)
• 1000 V version 1/h -- -- -- 20 20 20 20 20
• 1150 V version 1/h -- -- -- -- 20 20 20 20
Minimum interval between tripping operation by ms 80 80 80 80 80 80 80 80
Electronic Trip Unit and next making operation of the
circuit breaker (only with automatic mechanical resetting
of the lockout device).
Minimum interval between On-Off or Off-On switching
operations.
1) 6)
Use of trip units from –20 °C Replacement of the main contact elements of circuit breakers size I with
2)
ETU76B with graphics display can be used up to max. 55 °C. breaking capacity H is only possible at the factory.
3) 7)
At breaking capacity H: 1600 A to 70 °C. Minimum interval time between 2 tripping operations.
4) 8)
Make time through closing coil for synchronization purposes 3-pole switching with breaking capacity N and S: 45/h.
9)
(short-time excited) 50 ms. Motorized operating mechanisms Uimp = 1.2 kV
5)
Maintenance means: Replace main contact elements and arc chutes
(see Operating Manual).
Siemens · 04/2018 27
© Siemens AG 2018
Size I II
Type ... 3WL11 10 3WL11 12 3WL11 16 3WL11 20 3WL12 08 3WL12 10 3WL12 12 3WL12 16
Mounting position 30° 30°
Dhmax.
= 1 mm
30° 30°
and/or
Degree of protection IP20 without cabinet door, IP41 with door sealing frame, IP55 with cover
Main conductor • Copper bars, 1×
Unit(s) 2× 2× 3× 1× 1× 2× 2×
minimum bare mm2 60 × 10 40 × 10 50 × 10 50 × 10 50 × 10 60 × 10 40 × 10 50 × 10
cross-sections • Copper bars, Unit(s)
1× 2× 2× 3× 1× 1× 2× 2×
painted black mm2 60 × 10 40 × 10 50 × 10 50 × 10 50 × 10 60 × 10 40 × 10 50 × 10
Auxiliary conductors (Cu) Standard connection =
Max. number strain-relief clamp
Auxiliary conductors × • Without end sleeve 2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16); 1 × 2.5 mm2 (AWG 14)
cross-section • With end sleeve acc. to 1 × 0.5 mm2 (AWG 20) ... 1 × 1.5 mm2 (AWG 16)
(solid/stranded) DIN 46228 Part 2
• With twin end sleeve 2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16)
Optional connection =
tension spring
• Without end sleeve 2 × 0.5 mm2 (AWG 20) ... 2 × 2.5 mm2 (AWG 14)
• With end sleeve acc. to 2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16)
DIN 46228 Part 2
Position signaling switches Tension spring terminals 1 × 0.5 mm2 (AWG 20) ... 1 × 2.5 mm2 (AWG 14)
Weights 3-pole • Fixed-mounted circuit kg 43 43 43 43 56 56 56 56
breakers
• Withdrawable circuit kg 45 45 45 45 60 60 60 60
breakers
• Guide frames kg 25 25 25 25 31 31 31 31
4-pole • Fixed-mounted circuit kg 50 50 50 50 67 67 67 67
breakers
• Withdrawable circuit kg 54 54 54 54 72 72 72 72
breakers
• Guide frames kg 30 30 30 30 37 37 37 37
Dimensions W mm 320/410 460/590
3-/4-pole Fixed-mounted H mm 434 434
W D D mm 291 291
Withdrawable H mm 465.5 465.5
H
D mm 471 471
NSS0_00535
28 Siemens · 04/2018
© Siemens AG 2018
Size II III
Type 3WL12 20 3WL12 25 3WL12 32 3WL12 40 3WL13 40 3WL13 50 3WL13 63
Number of poles 3-pole, 4-pole
Rated current In at 40 °C, at 50/60 Hz
Main conductor A 2000 2500 3200 4000 4000 5000 6300
N-conductor (only on 4-pole versions) A 2000 2500 3200 4000 4000 5000 6300
Rated operational voltage Ue at 50/60 Hz V AC ... ... ... ... 690 ... ... ...
(1000 V version, see Catalog LV 10 "Options") 690/1000 690/1000 690/1000 690/1000 690/1000 690/1000
Rated insulation voltage Ui V AC 1000 1000 1000 1000 1000 1000 1000
Rated impulse withstand voltage Uimp
• Main conducting paths kV 12 12 12 12 12 12 12
• Auxiliary circuits kV 4 4 4 4 4 4 4
• Control circuits10) kV 2.5 2.5 2.5 2.5 2.5 2.5 2.5
Isolating function acc. to EN 60947-2 Yes Yes Yes Yes Yes Yes Yes
Utilization category B
Permissible ambient temperature
• During operation (in operation with LCD max. 55 °C)1) C –25/+70 –25/+70 –25/+70 –25/+70 –25/+70 –25/+70 –25/+70
• Storage C –40/+70 –40/+70 –40/+70 –40/+70 –40/+70 –40/+70 –40/+70
Permissible load for with- • Up to 55 C (Cu bare) A 2000 2500 3200 39503) 4000 5000 5920
drawable versions2) • Up to 60 C (Cu bare)4) A 2000 2500 3020 3810 4000 5000 5810
• Up to 70 C (Cu painted black)4) A 2000 2280 2870 3600 4000 5000 5500
Rated rotor operational voltage Uer V 2000 2000 2000 2000 2000 2000 2000
Power loss at In
With 3-phase symmetrical load
• Fixed-mounted circuit breakers W 180 270 410 750 520 630 900
• Withdrawable circuit breakers W 320 520 710 925 810 1050 1600
Switching times
• Make time ms 35 35 35 35 35 35 35
• Opening time ms 34 34 34 34 34 34 34
• Electrical make time (through closing coil)5) ms 100 100 100 100 100 100 100
• Electrical opening time (through shunt release) ms 73 73 73 73 73 73 73
• Electrical opening time (instantaneous undervoltage release) ms 73 73 73 73 73 73 73
• Opening time due to ETU, instantaneous short-circuit release ms 50 50 50 50 50 50 50
Service life: Breaking capacity N, S and H11)
• Mechanical (without maintenance) Operating cycles 10000 10000 10000 10000 5000 5000 5000
• Mechanical (with maintenance)6) Operating cycles 15000 15000 15000 15000 10000 10000 10000
• Electrical (without maintenance) up to 690 V Operating cycles 7500 7500 4000 2000 2000 2000 2000
• 1000 V version, electrical (without maintenance) Operating cycles 1000 1000 1000 1000 1000 1000 1000
• 1150 V version, electrical7) (without maintenance) Operating cycles 500 500 500 500 500 500 500
• Electrical (with maintenance)6) Operating cycles 15000 15000 15000 15000 10000 10000 10000
Service life: Breaking capacity C
• Mechanical (without maintenance) Operating cycles 5000 5000 5000 -- 5000 5000 5000
• Mechanical (with maintenance)6) Operating cycles 10000 10000 10000 -- 10000 10000 10000
• Electrical (without maintenance) up to 690 V Operating cycles 5000 5000 4000 -- 1000 1000 1000
• Electrical (without maintenance) up to 1150 V Operating cycles -- -- -- -- 500 500 500
• Electrical (with maintenance) up to 690 V6) Operating cycles 10000 10000 8000 -- -- -- --
Switching frequency8)
• 690 V version 1/h 609) 609) 609) 609) 60 60 60
• 1000 V version 1/h 20 20 20 20 20 20 20
• 1150 V version7) 1/h 20 20 20 20 20 20 20
Minimum interval between tripping operation by Electronic Trip ms 80 80 80 80 80 80 80
Unit and next making operation of the circuit breaker (only with
automatic mechanical resetting of the lockout device).
Minimum interval between On-Off or Off-On switching operations.
1) 6)
Use of trip units from –20 °C Maintenance means: Replace main contact elements and arc chutes
2)
4000 A, size II in fixed-mounted version, 3-pole. (see Operating Manual).
7)
3)
Derating factors for fixed mounting of 3WL12 40. Size II with order code "A15" and size III:
4)
data for very high breaking capacity.
ETU76B with graphics display can be used up to max. 55 °C. 8)
5)
Minimum interval time between 2 tripping operations.
Make time through closing coil for synchronization purposes (short-time 9)
excited) 50 ms. 3-pole switching with breaking capacity N and S: 45/h.
10)
Motorized operating mechanisms Uimp = 1.2 kV
11)
1000 V and 1150 V versions only in the case of H breaking capacity
Siemens · 04/2018 29
© Siemens AG 2018
Size II III
Type 3WL12 20 3WL12 25 3WL12 32 3WL12 40 3WL13 40 3WL13 50 3WL13 63
Dhmax.
= 1 mm
Mounting position 30° 30° 30° 30°
and/or
Degree of protection IP20 without cabinet door, IP41 with door sealing frame, IP55 with cover
Main conductor • Copper bars, Unit(s) 3 × 2× 3× 4× 4x 6x 6x
minimum bare mm2 50 × 10 100 × 10 100 × 10 120 × 10 100 x 10 100 x 10 120 x 10
cross-sections • Copper bars, Unit(s) 3 × 2× 3× 4× 4× 6× 6×
painted black mm2 50 × 10 100 × 10 100 × 10 100 × 101) 100 × 10 100 × 10 120 × 10
Auxiliary conductors Standard connection = strain-relief clamp
(Cu) • Without end sleeve 2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16); 1 × 2.5 mm2 (AWG 14)
Max. number of • With end sleeve acc. to 1 × 0.5 mm2 (AWG 20) ... 1 × 1.5 mm2 (AWG 16)
auxiliary conductors × DIN 46228 Part 2
cross-section • With twin end sleeve 2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16)
(solid/stranded) Optional connection = tension spring
• Without end sleeve 2 × 0.5 mm2 (AWG 20) ... 2 × 2.5 mm2 (AWG 14)
• With end sleeve acc. to DIN 46228 Part 2 2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16)
Position signaling Tension spring terminals 1 × 0.5 mm2 (AWG 20) ... 1 × 2.5 mm2 (AWG 14)
switches
Weights 3-pole • Fixed-mounted circuit breakers kg 56 59 64 85 82 82 90
• Withdrawable circuit breakers kg 60 63 68 121 88 88 96
• Guide frames kg 31 39 45 52 60 60 70
4-pole • Fixed-mounted circuit breakers kg 67 71 77 103 99 99 108
• Withdrawable circuit breakers kg 72 76 82 146 106 106 108
• Guide frames kg 37 47 54 62 84 84 119
Dimensions W mm 460/590 704/914
3-/4-pole Fixed-mounted H mm 434 434
W D D mm 291 291
Withdrawable H mm 465.5 465.5
H
D mm 471 471
NSS0_00535
CubicleBUS module Number of modules Max. continuous current Max. startup current
per CubicleBUS per module from the per module from the
CubicleBUS CubicleBUS
ETU45B Electronic Trip Unit 1 120 mA 2000 mA
ETU76B Electronic Trip Unit 1 170 mA 2000 mA
Metering function PLUS 1 120 mA 120 mA
Breaker Status Sensor BSS 1 40 mA 110 mA
COM15 PROFIBUS communication module 1 125 mA 280 mA
ZSI module 1 50 mA 125 mA
Digital output modules with rotary coding switch, 1-2 180 mA 125 mA
relay outputs
Digital output modules, configurable, 1 180 mA 125 mA
relay outputs
Analog output modules 1-2 110 mA 800 mA
Digital input modules 1-2 30 mA 125 mA
BDA PLUS 1 250 mA 350 mA
30 Siemens · 04/2018
© Siemens AG 2018
Size I to III
Type 3WL1
Manual operating mechanism with mechanical closing
Switching on/charging Max. force required to operate the hand lever N 230
the energy store Required number of strokes on the hand lever 9
Manual operating mechanism with mechanical and electrical closing
Charging the energy store
Closing coil (CC) • Primary operating range 0.85 ... 1.1 × Us
• Extended operating range for battery operation At 24 V DC, 48 V DC 0.7 ... 1.26 × Us
60 V DC, 110 V DC
220 V DC
• Rated control supply voltage Us 50/60 Hz AC V 110 ... 127; 208 ... 240
DC V 24; 30; 48; 60; 110 ... 125; 220 ... 250
• Power consumption AC/DC VA/ 15/15
W
• Min. command duration at Us for the closing coil ms 60
• Short-circuit protection 1 A TDz (slow)/1 A
Smallest permissible DIAZED fuse (operational class gL)/
automatic circuit breaker with C characteristic
Manual/motorized operating mechanism with mechanical and electrical closing
Manual operating mechanism For data, see above.
Motor • Primary operating range 0.85 ... 1.1 × Us
• Extended operating range for battery operation At 24 V DC, 48 V DC 0.7 ... 1.26 × Us
60 V DC, 110 V DC
220 V DC
• Power consumption of motor AC/DC VA/ 135/135
W
• Time required to charge the spring energy store at 1 × Us s 10
Closing coil For data, see above.
For motor and • Short-circuit protection 6 A TDz (slow)/2 A
closing coil Smallest permissible DIAZED fuse (operational class gL)/
automatic circuit breaker with C characteristic;
Motor and closing coil for same rated control supply voltages
• Smallest permissible DIAZED fuse (operational class gL)/ At Us = 24 ... 30 V 6A
automatic circuit breaker with C characteristic (for different At Us = 48 ... 60 V 6A
rated control supply voltages) At Us = 110 ... 125 V DC/ 2A
110 ... 127 V AC
At Us = 220 ... 250 V DC/ 2A
208 ... 240 V AC
Signals of the Electronic Trip Unit
Measuring accuracy of the Electronic Trip Unit Protection functions acc. to EN 60947;
Current indication 10%;
Metering function for base quantities
1%;
Metering function for
derived quantities 4%
Auxiliary releases
Undervoltage releases • Response values Pickup 0.85 × Us
UVR (F3) and (circuit breaker can be closed)
UVR-td (F4) Dropout 0.35 ... 0.7× Us
(circuit breaker is opened)
• Primary operating range 0.85 ... 1.1
• Extended operating range for battery operation At 24 V DC, 30 V DC, 0.85 ... 1.26
48 V DC, 110 V DC,
220 V DC
• Rated control supply voltage Us Instantaneous
50/60 Hz AC V 110 ... 127/208 ... 240/380 ... 415
DC V 24/30/48/60/110 ... 125/220 ... 2501)
Delayed
50/60 Hz AC V 110 ... 127; 208 ... 240; 380 ... 415
DC V 48; 110 ... 125; 220 ... 250
• Power consumption (pickup/uninterrupted duty) AC VA 20/5
DC W 20/5
• Opening time of the circuit breaker at Us = 0 ms 200
- Version UVR (F3)
Without delay ms 80
With delay ms 200
- Version UVR-td (F8)
With delay, td = 0.2 to 3.2 s s 0.2 ... 3.2
Reset through additional NC contact – direct tripping ms 100
• Short-circuit protection 1 A TDz (slow)/1 A
Smallest permissible DIAZED fuse (operational class gL)/
automatic circuit breaker with C characteristic
1) 24 V and 30 V only with undervoltage release UVR (F3).
Siemens · 04/2018 31
© Siemens AG 2018
Size I to III
Type 3WL1
Auxiliary releases
Shunt releases (ST) • For continuous command - Response value Pickup > 0.7 × Us
(F1, F2) (100% OP), locks out on (circuit breaker is tripped)
momentary-contact - Primary operating range 0.85 ... 1.1 × Us
commands
- Extended operating range At 24 V DC, 48 V DC 0.7 ... 1.26 × Us
for battery operation 60 V DC, 110 V DC
220 V DC
- Rated control supply voltage Us 50/60 Hz AC V 110 ... 127; 208 ... 240
DC V 24; 30; 48; 60; 110 ... 125;
220 ... 250
- Power consumption AC/DC VA/W 15/15
- Min. command duration at Us ms 60
- Opening time of circuit breaker At AC/DC ms 80
at Us = 100%
- Short-circuit protection 1 A TDz (slow)/1 A
Smallest permissible DIAZED fuse (operational
class gL)/ automatic circuit breaker with
C characteristic
5% OP - Response value Pickup > 0.7 × Us
(circuit breaker is tripped)
- Primary operating range 0.85 ... 1.1 × Us
- Extended operating range At 24 V DC, 48 V DC 0.7 ... 1.26 × Us
for battery operation 60 V DC, 110 V DC
220 V DC
- Rated control supply voltage Us 50/60 Hz AC V 110 ... 127; 208 ... 240
DC V 24; 48; 110 ... 125; 220 ... 250
- Power consumption AC/DC VA/W 15/15
- Min. command duration at Us ms 25
- Opening time of circuit breaker At AC/DC ms 50
at Us = 100%
- Short-circuit protection 1 A TDz (slow)/1 A
Smallest permissible DIAZED fuse (operational
class gL)/ automatic circuit breaker with
C characteristic
• With spring energy store - Rated control supply voltage Us 50/60 Hz AC V 110; 230
consisting of shunt DC V 110; 220
release and capacitor - Primary operating range 0.85 ... 1.1 × Us
storage device
- Power consumption AC/DC VA/W 1/1
- Storage time at Us/ max. 5 min/min. 5 s
Recharging time at Us
- Opening time of the circuit breaker, As with "for continuous
short-circuit protection command"
Remote reset solenoid for mechanical tripped indicator (F7)
Remote reset solenoid for - Primary operating range 0.85 ... 1.1 × Us
mechanical tripped - Extended operating range At 24 V DC, 48 V DC 0.7 ... 1.26 × Us
indicator (F7) for battery operation 110 V DC
220 V DC
- Power consumption AC/DC VA/W 50/50
- Min. command duration at Us for the remote reset ms 60
solenoid
- Short-circuit protection
Smallest permissible DIAZED fuse (operational class gL)/ 2 A TDz (slow)/1 A at 24 V DC
automatic circuit breaker with C characteristic and 48 V DC,
1 A TDz (slow)/1 A at 110 V and
208 ... 250 V
Contact position-driven auxiliary switches (S1, S2, S3, S4, S7, S8)
Rated insulation voltage Ui V 500
AC/DC
Rated operational voltage Ue V 500
AC/DC
Rated impulse withstand voltage Uimp kV 4
Breaking capacity • Alternating current - Rated operational voltage Ue V 24 ... 230 380/400
50/60 Hz - Rated operational current
Ie/AC-12 A 10 10
Ie/AC-15 A 4 3
• Direct current - Rated operational voltage Ue V 24 48 110 220
- Rated operational current
Ie/DC-12 A 10 8 3.5 1
Ie/DC-13 A 8 4 1.2 0.4
Short-circuit protection • Largest permissible DIAZED fuse (operational class gL) 10 A TDz, 10 A Dz
• Largest permissible miniature circuit breaker with C characteristic 10 A
32 Siemens · 04/2018
© Siemens AG 2018
Size I to III
Type 3WL1
Ready-to-close signaling switches (S20) (acc. to DIN VDE 0630)
Breaking capacity • Alternating current - Rated operational voltage Ue V 250
- Rated operational current Ie A 8
• Direct current - Rated operational voltage Ue V 125 250
- Rated operational current Ie A 0.4 0.2
Short-circuit protection Largest permissible DIAZED fuse (operational class gL) 2 A Dz (quick)
Tripped signaling switches (S24) and signaling switches for auxiliary releases (S22, S23)
(acc. to DIN VDE 0630)
Breaking capacity • Alternating current - Rated operational voltage Ue V 250
- Rated operational current Ie/AC-12 A 8
• Direct current - Rated operational voltage Ue V 24 125 250
- Rated operational current Ie/DC-12 A 6 0.4 0.2
Short-circuit protection Largest permissible DIAZED fuse (operational class gL) 6 A Dz (quick)
Tripped signaling switch Signal duration after tripping Until manual or
electrical remote reset (option)
Position signaling switch on guide frame
Type of contact • Signal: - "Circuit breaker in connected position" 3 CO 1 CO
- "Circuit breaker in test position" 2 CO or 1 CO
- "Circuit breaker in disconnected position" 1 CO 1 CO
Rated insulation voltage Ui 50/60 Hz AC V 440
DC V 250
Rated operational voltage Ue V 250
Rated impulse withstand voltage Uimp kV 4
Breaking capacity • Rated operational - Ie/AC-12 24 V 10 A, 110/127 V 10 A,
current Ie 220/240 V 10 A, 320/440 V 10 A
- Ie/AC-15 220/240 V 4 A,
320/440 V 3 A,
- Ie/DC-12 24 V 10 A, 48 V 2.5 A,
220/240 V 0.2 A,
- Ie/DC-13 24 V 3.0 A, 220/240 V 0.1 A
Siemens · 04/2018 33
© Siemens AG 2018
34 Siemens · 04/2018
© Siemens AG 2018
Setting range of the response current Ig Increment size when settings are made for the ETU76B using the menu For the legend, see
Size I and size II Size III From ... to Increment size From ... to Increment size page 34.
A 100 A 400 A 0 ... 1 0.1 1000 ... 1600 50
B 300 A 600 A 1 ... 100 1 1600 ... 10000 100
C 600 A 800 A 100 ... 500 5 10000 ... max 1000
D 900 A 1000 A 500 ... 1000 10
E 1200 A 1200 A
Siemens · 04/2018 35
© Siemens AG 2018
■ Characteristic curves2)
Every Electronic Trip Unit type and every setting has its own
characteristic curve. Only a selection is shown in the following. 10000
NSE0_01527
The characteristic curves each show the largest and smallest R min R max
[s]
setting range of 3WL circuit breakers with 1000 A rated current 1000 0,5 ... 1,0 x n
at 500 V rated voltage with various trip units. In order to obtain a
Opening time
complete tripping characteristic curve, the relevant parts of the
characteristic curves have to be combined. The characteristic 100
curves show the behavior of the Electronic Trip Unit when it is
activated by a current that is already flowing before the tripping 10
operation. If the overcurrent tripping occurs immediately after
closing and the Electronic Trip Unit is therefore not yet activated,
1 i min i max
the opening time is extended, depending on the level of the
2 ... 8 x n
overcurrent by up to 15 ms. To determine the break-times of the
circuit breakers, approximately 15 ms must be added to the 0,1
opening times shown for the arcing time.
For tolerances, see legend below.
0,01
The characteristic curves shown apply to ambient temperatures 0,1 1 10 100
at the circuit breaker between –5 and +55 °C. The trip unit can / n
be operated at ambient temperatures of –20 to +70 °C. An ex-
tended tolerance band can apply at these temperatures. 3WL circuit breaker with ETU15B Electronic Trip Unit
10000
NSE0_01520
10000
NSE0_01519
R min R max
R min R max
Opening time [s]
100
100
10
10
1 sd min sd max
sd min sd max
1,25 ... 12 x n 1
sd max 1,25 ... 12 x n sd max
0 ... 0,4 s sd min
0,1 0 ... 0,4 s sd min
i i > 20 x n 0,1
max. 50 kA i i > 20 x n
max. 50 kA
0,01
0,01
0,1 1 10 100
/ 0,1 1 10 100
n
/ n
3WL circuit breaker with ETU25B Electronic Trip Unit, 3WL circuit breaker with ETU27B Electronic Trip Unit,
LSI characteristic curve LSIN characteristic curve
10000
NSE0_01521
10000
NSE0_01523a
Opening time [s]
[s]
1000
1000 sd
Opening time
1,25 ... 12 x n
100
100
2 = const
sd
g min g max
10
10
100 ... 1200 A 1)
1
1 2
sd = const
g max
0,1 ... 0,5 s
sd = const 0,1 ... 0,4 s
0,1 g min
0,1
0,02 ... 0,4 s
0,01
0,01
100 1000 10000 100000
0,1 1 10 100
A / n
36 Siemens · 04/2018
© Siemens AG 2018
NSE0_01525a
The characteristic curves each show the largest and smallest
NSE0_01526a
Opening time [s]
10000
NSE0_01522a
4 1000
R = const sd
[s]
2
= const
100 10
R
10 2
2 ... 30s for 2
4
1 sd = const
1 ... 5s for
sd = const
0,1 ... 0,4 s
1 0,1 0,02 ... 4 s
0,1
0,01
0,1 1 10 1
/ n / cw
0,01
0,1 1 10 100
/ n 3WL circuit breaker with ETU76B Electronic Trip Unit, S characteristic
curve
3WL circuit breaker with ETU45B and ETU76B Electronic Trip Unit,
L characteristic curve
10000 Further characteristic curves are shown in the manual and the
NSE0_01524a
0,01
0,1 1 10 1
/ n / cs
3WL circuit breaker with ETU45B and ETU76B Electronic Trip Unit,
I characteristic curve
1)
Sizes I and II: 100 ... 1200 A
Size III: 400 ... 1200 A.
Siemens · 04/2018 37
© Siemens AG 2018
■ Dimensional drawings
Voltage transformers for 3WL air circuit breakers External current transformers for N-conductor without copper
connection pieces
+
S 11
11 12 13 14
Size I, 3WL9111-0AA21-0AA0
60
125 ±1
16
8
NSE0_01103
8,9
R 13,1
96,8
NSE0_01375
51 52 55 58 61 62 65 68 71 72 75 78
40 22
81
260 ±3 87 ±2 R 22
18 51
36
Current transformers for overload protection in the 70
N-conductor 83
External current transformers for N-conductor with copper Size II, 3WL9111-0AA22-0AA0
connection pieces
Size I, 3WL9111-0AA31-0AA0 R 27
131
115
54
NSE0_01376
15
83
65,5
41
55
Ø 13,5
88 51
51 44
95
170
113 3
130
68
24
91
107
123
R 15
45
NSE0_01377
Size II, 3WL9111-0AA32-0AA0
31
3
30 30 3×10
50,5 160 51
Ø 13,5 184
51 44
91
295
NSE0_00607b
90 131
340
113
Door cutout for operator panel using the door sealing frame
130
170
24
91
68
R5 R5
185
140
2
Ø5,5
350
140
180
175
40 120
1) Mounting surface
2) Center 3WL circuit breaker operator panel
11,5
12
3) 8 mounting holes for door sealing frame 1 21 4
40
4) 3 mounting holes for door sealing frame
Dimensions for option with door interlocking
38 Siemens · 04/2018
© Siemens AG 2018
70 86 81,9 38
45,5 19
47,5
94
NSE0_02085
153
6
NSE0_02086
30
400
NSE0_01029c
395
NSE0_01030b
4 x R5
4 x 5,5
340-350
°
85
72
295-300
72
435
68
70
Siemens · 04/2018 39
© Siemens AG 2018
21 20
8
NSE0_00611i 14
9
275
19
a
3
327,5
17
4 5 3
18
a
123,5
15
275
NSE0_00620a
150
270 15 5,5
76
300
390 NSE0_00614i 45 60 90 90 90
210 6
230 127
90 90 90 60
Ø13 55
h
3 7
150
110
20
40
NSE0_00617k
139 58
320
410
Vertical connection
h b
Ø13,5
60
3
30
267,5
NSE0_00618i
NSE0_00619a
127,5
113,5
M8 60 90 90 90
128,5
Ø13,5
NSE0_00612i
421
3
e
6
h
NSE0_00613c
d
26
c 82 M8 60 90 90 90
47 55 55 55 55
Ø13,5
40
m
NSE0_00615i
421
3
g
NSE0_00616c
6
f
40
m
14
M8 60 90 90 90
c 82
40 Siemens · 04/2018
© Siemens AG 2018
Connection dimensions in mm
Safety clearances in mm
SZ I, fixed-mounted version ... from grounded or non-conductive parts ... from live parts IT system
Above 71) At side At rear Above 7 At side 8 At rear 9 Above 7
Operational voltage, breaking capacity Standard arc chutes – 401 mm
500 V AC, N/S 460 0 0 615 20 20 550
500 V AC, H 460 0 0 715 20 20 550
690 V AC, N/S 460 0 0 765 50 125 --
690 V AC, H 460 0 0 965 75 140 --
Operational voltage, breaking capacity High arc chutes – 451 mm (A05, A16 or DC)
690 V AC 515 0 0 965 75 140 5503)
690 V AC + 20% H 515 0 0 1015 100 140 --
1000 V AC, H 515 0 0 1015 100 140 --
1000 V DC 550 0 0 2) 2) 2) --
1) Values for struts, grids and perforated sheets. When using plates with
conductive surfaces: values on request.
2) With insulating shield; for clearance, see "non-conductive parts"
3) Ue = 1000 V with breaking capacity H and Z option Z = A05
Siemens · 04/2018 41
© Siemens AG 2018
21 382,5
367,5 20
NSE0_00624h
327 350
320 14 260
NSE0_00630i
270
12
NSE0_00621k
3
19
287
275
16
327,5
4 15
5 3
a
275 4
Ø1
69
123,5
150
76
10 10 55 90 90 90 10
13 30 15
40
27
31
10 220 45
210 55 42
300 6
11
12
13
,5
55 55 55 55 13
Ø
j
NSE0_00627
139 68
270 25
320
410
350
260 350
260
14 j b
55 55 55 55
NSE0_00629i
NSE0_00628i
NSE0_00631i
M
NSE0_00632i
12
60
33
127,5 30
l
267,5
287
287
142,5 26
282,5
3 3
l
69
150
69
121 10 165 10 15 90 90 90
15 90 90 90 Ø13,5
NSE0_00625h
m
NSE0_00623b
40
6 6
373
493
403
373
287
287
3
NSE0_00626h
69
34
69
m
15 90 90 90
h
26
11
c 169,5 10 10
14
40
c 169,5
15 90 90 90
42 Siemens · 04/2018
© Siemens AG 2018
Connection dimensions in mm
Safety clearances in mm
SZ I, withdrawable versions ... from grounded or non-conductive parts ... from live parts IT system
Above 7 At side At rear Above 7 At side 8 At rear 9 Above 7
Arc chute covers Without1) / with Without/with Without/with Without/with Without/with Without/with Without
Operational voltage, breaking capacity Standard arc chutes – 4 = 460 mm
500 V AC, N/S 460 / 460 0 / 402) 0/0 615 / 480 20 / 100 20 / 14 550
500 V AC, H 460 / 460 0 / 402) 0/0 715 / 480 50 / 50 20 / 14 550
690 V AC, N/S 460 / 460 0 / 402) 0/0 765 / 480 50 / 100 125 / 14 --
690 V AC, H 460 / 460 0 / 402) 0/0 965 / 480 75 / 225 140 / 14 --
Operational voltage, breaking capacity High arc chutes – 4 = 510 mm (A05, A16 or DC)
690 V AC, H 510 / -- 0 / -- 0 / -- 965 / -- 75 / -- 140 / -- 5503)
690 V AC + 20% H 510 / -- 0 / -- 0 / -- 1015 / -- 100 / -- 140 / -- --
1000 V AC 510 / -- 0 / -- 0 / -- 1015 / -- 100 / -- 140 / -- --
1) Values for struts, grids and perforated sheets. When using plates with
conductive surfaces: values on request.
2) Value for plates that cover the lateral openings in the guide frame,
0 mm for struts and grids
3) Ue = 1000 V with breaking capacity H and Z option Z = A05
Siemens · 04/2018 43
© Siemens AG 2018
14
20
NSE0_00633b
19 NSE0_00642
a
17
327,5
275 18 3
a
15 3
275
4 5
150
5,5
76
123,5
NSE0_00636f 45
150
6
270 85 10 210
440 230 127
570
21 90 130 130 130
90 30 30
,5
3 7
150
110
3 7
40
20
NSE0_00639k
139 128
460
590
Vertical connection 3200 A AC and 4000 A DC Vertical connection 4000 A AC (terminal face length k = 40 mm)
Ø13,5 b
30
30
NSE0_00640c
85 Nm
NSE0_00641b
30
98 30
3 Ø 13,5
345,5
290
79,5
NSE0_01868a
134,5
100
h
10
113 k
128 M8 90 130 130 130 20
142 M8
200 130 200
162
Front connection (single)
Ø1 90 90 90 90
3,5
40
h
47
NSE0_00634e
NSE0_00635e
6
421
3
e
c 82 M8
d
m
NSE0_00637e
NSE0_00638d
421
3
g
6
f
40
M8
14
44 Siemens · 04/2018
© Siemens AG 2018
Connection dimensions in mm
Safety clearances in mm
SZ II, fixed-mounted version ... from grounded or non-conductive parts ... from live parts IT system
Above1) 7 At side At rear Above 7 At side 8 At rear 9 Above 7
Operational voltage Standard arc chutes – 401 mm
500 V AC 460 0 0 715 50 20 550
690 V AC 460 0 0 1065 100 140 --
300 V DC 495 0 0 2) 2) 2) --
2) 2) 2)
600 V DC 650 0 0 --
Operational voltage, breaking capacity High arc chutes – 451 mm (A05, A16 or DC)
690 V AC, H 510 0 0 1015 100 140 6003)
690 V AC, C 510 0 0 775 100 125 --
690 V AC + 20% H 620 0 0 1015 100 125 --
1000 V AC, H 620 0 0 1015 100 125 --
2) 2) 2)
1150 V AC 620 0 0 --
2) 2) 2)
1000 V DC 615 0 0 --
3WL52 Double high arc chutes – 501 mm (A17)
1)
Values for struts, grids and perforated sheets. When using plates with
conductive surfaces: values on request.
2)
With insulating shield; for clearance, see "non-conductive parts"
3)
Ue = 1000 V with breaking capacity H and Z option Z = A05
4)
Does not apply to 3WL5: 3WL5 see dimensions 3200 A AC
Siemens · 04/2018 45
© Siemens AG 2018
NSE0_00652c
9
a
327,5
275
287
4 5 3
275
a
150
Ø14
76
123,5
69
31
40
27 220 45
40 42 10 5545 130 130 130 10
10
10 270
350 55
480 21
Ø13,5 30 30
j
NSE0_00649b
139 138
270 95
460
590
Vertical connection 3200 A AC and 4000 A DC Vertical connection 4000 A AC (terminal face length k = 40 mm)
530
30
400
b
NSE0_00650c
100
j
30
30
315,5
NSE0_01869
100 30
3
287
109,5
290
NSE0_00651b
135
k 4,6 10
10
20
69
177
157 55 45
10 197
172 5545 130 130 130
200 130 200
400
90 90 90 90 90 90 90 90
62,5 40 40 62,5
40
40 40
NSE0_00644c
13,5
NSE0_00647c
m
h
3 3
NSE0_00648d
NSE0_00645d
6 6
373
373
287
287
g
e
26
14
69
69
h
m
f
c 45,1 c 10
40
d
90 40
NSE0_00653a
M
12
33
59
26
287
282,5
3
59
142,5
69
46 Siemens · 04/2018
© Siemens AG 2018
Connection dimensions in mm
Safety clearances in mm
SZ II, withdrawable version ... from grounded or non-conductive parts ... from live parts IT system
Above 7 At side At rear Above 7 At side 8 At rear 9 Above 7
Arc chute covers Without1) / with Without/with Without/with Without/with Without/with Without/with Without
Operational voltage Standard arc chutes – 4 = 460 mm
500 V AC 460 / 460 0 / 702) 0/0 715 / 480 50 / 50 14 / 14 550
690 V AC 460 / 460 0 / 702) 0/0 1065 / 480 100 / 225 30 / 14 --
3) 3) 3)
300 V DC 495 / -- 0 / -- 0 / -- --
3) 3) 3)
600 V DC 650 / -- 0 / -- 0 / -- --
Operational voltage, breaking capacity High arc chutes – 4 = 510 mm (A05, A16 or DC)
690 V AC, H 510 / -- 0 / -- 0 / -- 1015 / -- 105 / -- 30 / -- 6004)
690 V AC, C 510 / -- 0 / -- 0 / -- 775 / -- 100 / -- 30 / --
690 V AC + 20% H 620 / -- 0 / -- 0 / -- 1015 / -- 100 / -- 140 / -- --
1000 V AC, H 620 / -- 0 / -- 0 / -- 1015 / -- 100 / -- 140 / -- --
3) 3) 3)
1150 V AC 620 / -- 0 / -- 0 / -- --
1000 V DC 615 / -- 0 / -- 0 / -- 3) 3) 3) --
1) Values for struts, grids and perforated sheets. When using plates with
conductive surfaces: values on request.
2) Value for plates that cover the lateral openings in the guide frame,
0 mm for struts and grids
3) With insulating shield; for clearance, see "non-conductive parts"
4) Ue = 1000 V with breaking capacity H and Z option Z = A05
Siemens · 04/2018 47
© Siemens AG 2018
21
NSE0_00655c 14 20
30
275
19
327,5
4 5 17
18 3
15
30
3
275
123,5
150
NSE00664a
76
270 205 12
680 NSE0_00658h 5,5
890 35 150 45
130 210 210 210 130
210 6
230 127
Ø13,5
7 3 7 110 (150)
4x Ø11
20
4x M10
NSE0_00661j
139 248
704
914
NSE0_00662c
15
3
k
330,5
NSE0_00663a
120
94,5
Ø1
3,5 160 160 160 160
47 5050
NSE0_00656d
h
NSE0_00657d
451
421
6 3
h
11
m
NSE0_00659e
NSE0_00660d
541
3
421
6
34
40
m
14
48 Siemens · 04/2018
© Siemens AG 2018
Connection dimensions in mm
Safety clearances in mm
SZ III, fixed-mounted version ... from grounded or non-conductive parts ... from live parts IT system
Above1) 7 At side At rear Above 7 At side 8 At rear 9 Above 7
Operational voltage Standard arc chutes – 401 mm
500 V AC 460 0 0 515 20 20 450
690 V AC 460 0 0 965 100 125 --
Operational voltage High arc chutes – 451 mm (> 690 V AC, A05 or C)
690 V AC 510 0 0 965 100 125 5002)
690 V AC + 10% H 615 0 0 865 100 125 --
690 V AC + 20% H 615 0 0 865 100 125 --
1000 V AC 615 0 0 865 100 125 --
1150 V AC 615 0 0 3) 3) 3) --
1) Values for struts, grids and perforated sheets. When using plates with
conductive surfaces: values on request.
2) Ue = 1000 V with breaking capacity H and Z option Z = A05 or breaking
capacity C
3) With insulating shield; for clearance, see "non-conductive parts"
Siemens · 04/2018 49
© Siemens AG 2018
NSE0_00674h
30
327,5
275
465,5
468,5
30
287
275
150
Ø14
76
123,5
69
31
40
27 220 45
10 10 270 160 10 42 57 85 210 210 210
590
800 57
21
30
Ø13
30 30
,5
j
139 260
NSE0_00671h
270 217
704
914
840 840
630 630
10 704
M
NSE0_00676c
20
12
j
NSE0_00672c
NSE0_00675b
Ø14
33
30
l
287
142,5 26
330,5
282,5
NSE0_00673h
124,5
l
94,5
69
24 57 a b b 210 5 30
10 10 121 10 57 85 210 210 210
177 590
197 800 590
704 800
914 914
840 840
NSE0_00670d
NSE0_00667d
630 630
Ø13,5
50 50 50 50 50 50 50 50
40
62,5
62,5
NSE0_00669c
NSE0_00666c
m
h
287
373
493
6
287
373
6
403
14
34
69
m
69
h
40
20 590 590
169,5
11
50 Siemens · 04/2018
© Siemens AG 2018
Connection dimensions in mm
Safety clearances in mm
SZ III, withdrawable version ... from grounded or non-conductive parts ... from live parts IT system
Above 7 At side At rear Above 7 At side 8 At rear 9 Above 7
Arc chute covers Without1) / with Without/with Without/with Without/with Without/with Without/with Without
Operational voltage Standard arc chutes – 4 = 460 mm
500 V AC 460 / 460 0 / 402) 0/0 510 / 480 20 / 50 14 / 14 460
690 V AC 460 / 460 0 / 402) 0/0 965 / 480 100 / 200 14 / 14 --
Operational voltage, breaking capacity High arc chutes – 4 = 510 mm (> 690 V AC, A05, A16 or C)
690 V AC 510 / -- 0 / -- 0 / -- 965 / -- 100 / -- 14 / -- 5103)
1000 V AC, H 615 / -- 0 / -- 0 / -- 865 / -- 100 / -- 14 / -- --
1000 V AC, C 615 / -- 0 / -- 0 / -- 865 / -- 100 / -- 14 / -- --
4) 4) 4)
1150 V AC 615 / -- 0 / -- 0 / -- --
1)
Values for struts, grids and perforated sheets. When using plates with
conductive surfaces: values on request.
2)
Value for plates that cover the lateral openings in the guide frame,
0 mm for struts and grids
3)
Ue = 1000 V with breaking capacity H and Z option Z = A05 or breaking
capacity C
4)
With insulating shield; for clearance, see "non-conductive parts"
Siemens · 04/2018 51
© Siemens AG 2018
■ Circuit diagrams
Terminal assignment diagram
F1, 2
COM15/COM16 module is at position "-X7".
– + OUT
13 COM15/COM16
1 2 3 4 5 6 7 8 9
Open
12 (Option F02/F12)
Y1
Stored energy status indication S21 11
Close
– +
10
Electrical ON button S10 9
Free
L / L+ Us/Uc
– +
8
2nd tripped signaling switch S25 1NO
DPWrite Free
7
Enable
4
Signaling switch on 3
2nd auxiliary release S23 2
1
14 L / L+
1st auxiliary release F1 "ST" Uc
13 N / L–
12
S1 "NO"
11
10
S1 "NC"
9
Closing coil 8 N / L–
Uc
7 L / L+
6
5
"Ready to close" signal S20
4
S2 "NO"
3
2
S2 "NC"
1
52 Siemens · 04/2018
© Siemens AG 2018
L1 L1
(L+) release (L+)
OFF
contact
ON
-X5.10
-X7.14
-X7.12
-X6.10
-X5.12
-X6.14
-X6.12
-X6.2
-X6.6
-X5.8
-X5.4
-X6.4
-X5.2
-X5.6
-X6.7
-X7.9
5
1
3
-A1 ETU
version L
-S10
S
RESET
electr.
TRIP
I
ON
N N
G
R
-S11 -F5
-S20
-S24
-Y1 -T2
mech.
ON
-T3
NSE0_01558b
mech. -S12
-F1
OFF
-X5.9
6
2
4
-X6.1
-X5.7
-X5.3
-X6.9
-X6.13
-X6.3
-X5.5
-X6.11
-X7.13
-X5.11
-X8.9
-X5.1
-X8.10
-X6.8
-X6.5
N N
(L-) (L-)
* Short terminals, if no N transformer
Siemens · 04/2018 53
© Siemens AG 2018
module
module
4 4 4
ZSI
ZSI
ZSI
5 5 5
6 6 6 SENTRON 3WL SENTRON 3WL
3 3
module
module
5
6
1
2
3
4
4 4
ZSI
ZSI
5 ZSI module 5
6 6
SENTRON 3WL SENTRON 3WL
3 3
module
module
4 4
ZSI
ZSI
5 5 NSE0_01898
6 6
SENTRON 3WL
SENTRON 3VL SENTRON 3WL Circuit diagram for a Zone Selective Interlocking function with multiple
3 infeed and several outgoing units with 3WL circuit breakers
module
4
ZSI
NSE0_01897
5
6
module
5
6
1
2
3
4
4 4
ZSI
ZSI
5 ZSI module 5
6 6
NSE0_01899
SENTRON 3WL
module
4 4
ZSI
ZSI
5 5
6 6
■ More information
Up-to-date information on the Internet at:
http://www.siemens.com/sentron
54 Siemens · 04/2018
© Siemens AG 2018
■ Technical specifications
Size I II
Type 3WL11 20 3WL12 10 3WL12 20 3WL12 40
Rated current In at 40 °C
Main conductor A 2000 ... 1000 2000 4000
Rated operational voltage Ue V DC 1000 ... 600/1000 ... 600/1000 ... 600/1000
(1000 V version, see Catalog LV 10, order code "A05")
Rated insulation voltage Ui V DC 1000 1000 1000 1000
Rated impulse withstand voltage Uimp
• Main conducting paths kV 12 12 12 12
• Auxiliary circuits kV 4 4 4 4
• Control circuits kV 2.5 2.5 2.5 2.5
Isolating function acc. to EN 60947-2 Yes Yes Yes Yes
Utilization category B
Permissible ambient temperature
• Operation C –25/+70 –25/+70 –25/+70 –25/+70
• Storage C –40/+70 –40/+70 –40/+70 –40/+70
Permissible load Up to 40 C A 2000 1000 2000 4000
At rear horizontal main circuit Up to 55 C A 1910 1000 2000 3640
connections Up to 60 C A 1850 1000 2000 3500
(Cu painted black) Up to 70 C A 1710 1000 1950 3250
Power loss at In for symmetrical loads
Withdrawable circuit breakers W 150 280 770 1640
Switching times
• Make time ms 35 35 35 35
• Opening time ms 38 34 34 34
• Electrical make time (through activation solenoid)1) ms 100 100 100 100
• Electrical opening time (through shunt release) ms 73 73 73 73
• Electrical opening time (instantaneous undervoltage release) ms 73 73 73 73
Endurance3)
• Mechanical (without maintenance) Operating cycles 10 000 10000 10000 10000
• Mechanical (with maintenance)2) Operating cycles 15 000 15000 15000 15000
• Electrical (without maintenance) Operating cycles 1000 6000 6000 4000
• 1000 V version Operating cycles 1000 1000 1000 1000
• Electrical (with maintenance)2) Operating cycles 2000 15000 15000 15000
Switching frequency
• 600 V version 1/h -- 60 60 60
• 1000 V version 1/h 20 20 20 20
30° 30° 30° 30°
Dhmax.
= 1 mm
Mounting position
and/or
Degree of protection IP20 without cabinet door, IP41 with door sealing frame, IP55 with cover
Auxiliary conductors (Cu) Standard connection = strain-relief clamp
Max. number • Without end sleeve 2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16); 1 × 2.5 mm2 (AWG 14)
Auxiliary conductors × • With end sleeve acc. to DIN 46228 Part 2 1 × 0.5 mm2 (AWG 20) ... 1 × 1.5 mm2 (AWG 16)
cross-section • With twin end sleeve 2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16)
(solid/stranded)
Optional connection = tension spring
• Without end sleeve 2 × 0.5 mm2 (AWG 20) ... 2 × 2.5 mm2 (AWG 14)
• With end sleeve acc. to DIN 46228 Part 2 2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16)
Weights 3-pole • Fixed-mounted circuit breakers kg 43 56 56 64
• Withdrawable circuit breakers kg -- 60 60 68
• Guide frames kg -- 31 31 45
4-pole • Fixed-mounted circuit breakers kg 50 67 67 77
• Withdrawable circuit breakers kg -- 72 72 82
• Guide frames kg -- 37 37 54
1) Make time through activation solenoid for synchronization purposes 2) Maintenance means: Replace main contact elements and arc chutes (see
(short-time excited) 50 ms. Operating Manual).
3)
Further technical specifications on request.
Size I II
Type 3WL11 3WL12
Breaking capacity DC DC
Rated short-circuit breaking capacity
Up to 220 V DC Icc kA 20 35
Up to 300 V DC Icc kA 20 30
Up to 600 V DC Icc kA 20 25
Up to 1000 V DC Icc kA 20 20
Rated short-time withstand current Icw
0.5 s kA -- --
1s kA 20 351)/302)/253)/204)
2s kA -- --
3s kA -- --
1) 3)
At Ue = 220 V DC At Ue = 600 V DC
2) At Ue = 300 V DC 4) At Ue = 1000 V DC
Siemens · 04/2018 55
© Siemens AG 2018
■ Characteristic curves
10000
R= 0.4 ... 1.0 n
R= 2 ... 10 s at 6 R
[s]
R= 10 s [B]
100 B
2 s [A]
B
A
A
10
1
MIN MAX
I= 1.5
I=
4 n
R
I=1.25 R
0,1
NSE0_01578
0,01
0,1 1 10
/ n
■ Dimensional drawings
DIGmat S100
Note:
For dimensional drawings for non-automatic circuit breakers
up to 4000 A (DC), see page 38 to 47.
56 Siemens · 04/2018
© Siemens AG 2018
■ Circuit diagrams
L1
AC230
+
N
PE -
DC24
AC230
+ - + - + - + -
12
14
-K1 11 -Q01 1 3 5
Excitation / Alarm
Automatic / Reset
-X6.14 -X5.12
12 14
SENTRON
3WL
-K2 11 -F1 -F3
NSE0_01577a
-X6.13 -X5.11
-Q01 2 4 6
Circuit diagrams of the DIGmat S100 and the 3WL non-automatic air circuit breaker
NSS0_00539
The connection to the circuit breakers is not dependent on of 1 m from the connecting bars, the circuit breaker can be used
direction and polarity; the circuit diagrams can be adapted at full operational current load.
accordingly.
] Grounded system
If the parallel or series connections are made directly to the
connecting bars, for thermal reasons the continuous load on the Load
circuit breakers must only be 80% of the permissible operational
current. If the parallel or series connection is made at a distance
Siemens · 04/2018 57
© Siemens AG 2018
Load Load
*B,B;;B
■ More information
Up-to-date information on the Internet at:
www.siemens.com/sentron
58 Siemens · 04/2018
© Siemens AG 2018
© Siemens AG 2018
Siemens AG Subject to change without prior notice The information provided in this brochure contains merely general
Energy Management PDF (3ZW1012-3WL11-0AC1) descriptions or characteristics of performance which in case of actual
use do not always apply as described or which may change as a result
Low Voltage & Products PH 0718 60 En
of further development of the products. An obligation to provide the
Postfach 10 09 53 Produced in Germany respective characteristics shall only exist if expressly agreed in the
93009 REGENSBURG © Siemens AG 2018 terms of contract. Availability and technical specifications are subject
GERMANY to change without notice.
All product designations may be trademarks or product names of
Siemens AG or supplier companies whose use by third parties for their
own purposes could violate the rights of the owners.
www.siemens.com/lowvoltage