Professional Documents
Culture Documents
a
b
c
I
Distribution Fault
Substation
I
Wire
Generally, short circuits cause very high magnitude system current (larger than the
normal load currents).
Constant Current
I T
Equilibrium
T Te
Ti
dW
= I 2R
dt t
T(t)=( Ti - Te )e-t/t + Te
Any current (large or not) passing through a wire in free space causes a
temperature rise in the wire. The energy comes from the current, for which the
change over time (power) can be expressed with the following equation:
dW
= I2R
dt
In the former equation, “I” represents the rms value of the current.
Part of this energy heats up the conductor; convection transmits another part of
this energy to ambient. During normal load conditions, if we assume the current
has constant rms (steady state), the wire temperature reaches an equilibrium. This
means that the wire temperature T remains constant and all the energy the current
provides is transmitted to the surrounding medium.
For this simple system, the wire temperature as a function of time can be
expressed as follows:
T( t ) = ( Ti - Te )e - t / t + Te
Current Wire
Magnitude Material
Properties
I
Ambient
d
Temperature
and Other
Wire Size
Environmental
Factors
For a given material and a given set of constant environmental parameters, the
temperature change of the wire depends almost exclusively on the wire size and
the current magnitude (the rms value).
The values Te, Ti and t strongly depend on the rms value of the current I.
Ti
td
t
If the current is large enough, the wire temperature could exceed the limit. The
time td needed for the temperature to reach the limit is called damage time.
I
t
T
I = I3 > I2
T
I = I2 > I1 Damage
I = I1 Curve
t1
Td I = Imd t2
t3
Ti
t3 t2 t1
t
Imd I1 I2 I3 I
• There is a current (Imd) that causes the equilibrium to equal the insulation damage
temperature. Equivalently, the damage time for this current is “infinite.”
The curve obtained by plotting the damage time vs. the applied current is called the damage
curve.
Damage
Curve
In Imd I
Rating
The damage curve is also known as the thermal capacity curve, or the short-time
thermal damage curve.
Notice that the cable rating (rated current) is not the same as the minimum current
Imd. The nominal current In (rating) is the current that causes the wire to reach the
rated temperature of the cable in the steady state (equilibrium). This temperature,
in steady state, is the value at which the manufacturer guarantees the useful life of
the cable.
l Copper Conductors,
Thermoplastic
Insulation
l Damage
Temperature: 150° C
For relatively large currents (larger than three times the cable rating) it is possible
to approximate the damage curve with the following equation:
CA 2 [seconds]
td = 2
I
I2 t = K [A 2 s]
l Stranded Aluminum
Conductors (Without
Insulation)
l Damage Time
Needed for
Annealing
In the case of conductors without insulation (as in overhead distribution lines), the
damage temperature is given by the annealing temperature.
Transformer
Impedance: Z = 4%
I / In = 1 I / In = 2 I / In = 20
Many factors affect the shape of transformer damage curves. We will study these
curves later in this course.
Experiment
Expensive Cable T
Melting
Inexpensive
Wire Tm
T2 Damage
Td
I
T1
T1
tm td t
T2 tm < t d
Fuse Melting
t
I = I3 > I2
T
I = I2 > I1
I = I1
Melting Melting
Tm Curve
I = Imm
t1
t2
Ti t3
t3 t2 t1 t
In Imm I1 I2 I3 I
Fuse Rating
As we did with damage time, we can show (experimentally and analytically) the following:
• There is a current (Imm) that causes the equilibrium to equal the fuse melting
temperature. Equivalently, the melting time for this current is “infinite.” It is
difficult to experimentally determine an accurate value for this current.
The curve obtained by plotting the damage time vs. the applied current is called the
minimum melting time curve.
Notice that the fuse rating (nominal current) is not the same as the minimum melting
current Imm.
Protected t
Equipment
Fuse
Protected
td Equipment
I Damage curve
tm
Fuse
l First Approach to Basic Melting
Protection Principle: Curve
SPEED
In Imm Ix I
Fuse Rating
The result of the experiment described on the previous page can be represented in
a time vs. current plot.
As a first approach, we can say that, for every current value, the fuse must melt
before the protected equipment suffers damage.
Fault Clearing
T
tarc
Vaporization i
Melting Tm Fuse
T
Ti
tm tc t
i
i
t
Melting Clearing
The melting time the former pages of this section describe refers to the time
before the fuse reaches melting temperature. The current does not become zero
immediately. The fuse goes through a series of different stages that terminate with
the development of an arc. The current disappears when this arc is completely
extinguished. At that moment, we say that the fault has been cleared.
The time period between the fault occurrence and the fault clearing is called the
total clearing time.
Fuse Curves
t
Total
Clearing
Time
tc
Curve
tm
Minimum
Melting
Time
In Imm Ix I Curve
Fuse Rating
As we did with melting time, we can draw a curve to represent the total clearing
time as a function of the current.
• The fuse rating (nominal current) which should not be confused with the
minimum melting current.
t l A Better Approach:
Consider the Total
Protected
Equipment
Clearing Time
td
Damage curve
tc Protected
Equipment
Fuse
Fuse
Curves
I
In Imm Ix I
To improve the first approach for overcurrent protection, we could say that the
total clearing time for the fuse should be less than the damage time for the
protected equipment.
Other Damage
l Mechanical Damage
l Voltage Sags
l Transient Stability
Mechanical Damage
l Very Destructive in Bus Bars, Isolators,
Supports, Transformers and Machines
l Damage is “Instantaneous”
Mechanical
Forces
f1 f2
i1
i2
Voltage Sags
Unacceptable Voltage Variation
VOLTAGE (%)
100
ELECTRONIC DRIVER
90
80 COMPUTER
70
60
CONTACTOR
50
40
30
20
10
0
0 10 20 30 40 50 60 70 80 90 100
TIME (Cycles)
Voltage Sags
=Loads
I
S/E
Vs
V
Vs 1 p.u.
UVVR limit
(sensitive loads)
Clearing Time
t
Transient Stability
1 2
System
EÐ0 Fault EÐd
Generator
d Unstable d Stable
For synchronization of generators and utility systems after a fault, the clearing
time must be very short.
The upper permissible limit for this clearing time is traditionally known as the
critical clearing time.
For the simple case shown, the clearing time (tclear) of Circuit Breakers 1 and 2
must be less than machine characteristics and the critical clearing time (tcrit) the
system imposes.
Summary
l Thermal Damage
l Mechanical Damage
l Voltage Sags
l Transient Stability
PROTECTION SPEED