Professional Documents
Culture Documents
Firing up Boiler
Manual Operation: Open air operated valve on deck via hand wheel
till desired temperature through heater is reached. Do in
increments to let system have time to settle out. Check heater
temperatures on the panel in cargo office. In manual mode you can
close in on bypass till open 1 turn. ‘DO NOT SHUT OFF
COMPLETELY’
Automatic Operation: Open air valve on pneumatic temperature control unit. Set
the controller to the desired temperature by moving the red set needle (never set
above 105C). The black needle gives wash water temperature and should rise to
80-85C. This will take up to 1/2 hour. Make sure the pneumatic valve is
modulating correctly. Boiler setting 125-135C for tank wash gives 80-85C for one
fixed machine & 140-160 gives 75-80C for portable machine. If not then switch to
manual control or oil flow problems will occur tripping the boiler burners out.
OR
Manual Operation: Open air valve on pneumatic temperature control unit. Set
the controller red set needle to maximum 100-105C to keep the pneumatic valve in
the open position and protect the tank wash heater from being overheated should
the temperature rise too high it will still trip out the boiler. Boiler setting 125-135C
for tank wash gives 80-85C for one fixed machine & 140-160 gives 75-80C for
portable machine. The black needle gives wash water temperature and should rise
to 80-95C. This will take up to 1 hour. All Deck personnel are to be aware that any
change in the number of machines open/closed will change the boiler and water
heater settings. E/R personnel are to be informed before any changes in the flow
are done so the system can be monitored.
NOTE : A flow of water must be maintained at all times through the tank
wash heater or it will be damaged. Always have at least one machine and/or
the bleeder open one turn.
Shutting Down Hot Tank Washing
-Make sure to flush all lines and tank wash machines through with fresh
water from the tank wash tank if have been using sea water before
shutting down.
-Open thermal oil bypass valve on deck full before shutting
down heater
-Bring set point down to about 25C on thermal oil boiler control panel
-Switch burner to ‘OFF’
-Close fuel valve on burner
-Keep water running through the heater to cool down the heater.
-Put heating controller red set point needle to zero and wait for black
temperature indication needle to come down to <40C
-Bleed off and shut the air to the controller (3 way valve)
-Open the warm through valve on the heater and shut the outlet and inlet
thermal oil valves to the heater
-After cooling down 10-15 minutes shut off the warming through valve
-Finish shutting down the thermal oil boiler according to the instructions
-Allow thermal oil to circulate till cooled down to about 100C
-Shut down pumps
-Switch off panel