Professional Documents
Culture Documents
Series C MDL-Frame
400-800A, 240-600V
Contents
Description Page
Catalog Number Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Note:
Time/Current characteristic curves for Series C M-frame circuit breakers--voltages shown in curve headings are
maximum at which the breaker may be applied. Interrupting capacity of inidvidual breaker is tabulated on each curve.
Note:
The following curves are UL489 Listed for use in North America.
The following circuit breakers are derived from Eaton, Westinghouse, or Cutler-Hammer history.
Time Current Curves are engineering reference documents for application and coordination purposes only.
For field testing molded case circuit breakers, refer to NEMA AB 4 guidelines.
Time Current Curves TD012036EN Series C
Effective December 2015 M-Frame
Notee: Unless noted below, all curves remain unchanged from their prior revision .
2 EATON www.eaton.com
Series C Time Current Curves TD012036EN
M-Frame Effective December 2015
MT 3 800 T
MDL 3 800 F
Circuit Breaker/
Frame Type Number of Poles
MDL, MDLB 2 = Two-pole Circuit Breaker/Frame Suffix
HMDL, HMDLB 3 = Three-pole Ampere Rating
F = Frame only
300 1 K = High magnetic molded case switch
350 1 V = 500C (thermal-magnetic trip units only)
400 W = Without terminals
450 X = Load side terminals only
500 Y = Line side terminals only
600
700
800
Note
1 Thermal-magnetic only.
EATON www.eaton.com 3
Time Current Curves TD012036EN Series C
Effective December 2015 M-Frame
Terminals
Performance at 480 Vac
Poles W = No terminals
MDLB = 50 kAIC
HMDLB = 65 kAIC 3 = Three
Amperes
CMDLB = 50 kAIC
100% rated 800 Features
CHMDLB = 65 kAIC Blank = No feature
100% rated Frame B20 = High load alarm
Designation B21 = Ground fault
F alarm, with trip
B22 = Ground fault
Trip Unit alarm, no trip
ZG = Zone selective
T33 = 310+ Electronic LS interlocking
T32 = 310+ Electronic LSI
T35 = 310+ Electronic LSG
T36 = 310+ Electronic LSIG
T38 = 310+ Electronic LSI with Maintenance Mode
T39 = 310+ Electronic LSIG with Maintenance Mode
Trip
Unit Type Poles
MES 3 = Three Amperes Features
800 Blank = No feature
B20 = High load alarm
B21 = Ground fault
alarm, with trip
Trip Unit B22 = Ground fault
alarm, no trip
LS = 310+ Electronic LS
ZG = Zone selective
LSI = 310+ Electronic LSI
interlocking
LSG = 310+ Electronic LSG
LSIG = 310+ Electronic LSIG
ALSI = 310+ Electronic LSI with
Maintenance Mode
ALSIG = 310+ Electronic LSIG with
Maintenance Mode
MDL 3 800 F
Note
1 Maintenance Mode and ZSI are only available with LSI and LSIG trip units.
2 B21 and B22 features available only with LSG, LSIG and ALSIG trip units.
3 B2x suffixes cannot be combined with other B2x suffixes.
4 EATON www.eaton.com
Series C Time Current Curves TD012036EN
M-Frame Effective December 2015
LSIG
LSG
LSI
LS
EATON www.eaton.com 5
Time Current Curves TD012036EN Series C
Effective December 2015 M-Frame
9000
8000
7000
6000
5000 1.15 Digitrip 310+ Circuit Breaker Time/Current Curves (Phase Current)
1 H our
80
70 2*, 4*, 7*, 10, 12, 15*, 20, 24* Notes:
60 *Shown below at 6x
50 1 Curve accuracy applies from –20°C to +55°C ambient . For possible continuous ampere
40 derating for ambient above 40°C, refer to Eaton . Temperatures above +88°C cause an
over-temperature protection trip.
30
.
24
2
Application frequency is 50/60 Hertz.
3 There is a memory effect that can act to shorten the long delay. The memory effect comes
20
. into play if a current above the long delay pickup value exists for a time and then is cleared
by the tripping of a downstream device or the circuit breaker itself. A subsequent overload
Time in Seconds
will cause the circuit breaker to trip in shorter time than normal. The amount of time
15 .
Minimum Total reduction is inverse to the amount of time that has elapsed since the previous overload.
10 Clearing Time Approximately five minutes is required between overloads to completely reset the memory.
9
8 4
The right portion of the curve is determined by the interrupting rating of the circuit breaker.
7 5
The left portion of the curve is shown as a multiple of the Long Delay Setting.
6 7 .
(Long Delay Pickup = 115% of Ir). Range is 110%–120%.
5
4 .
4
6
Total clearing times shown include the response times of the trip unit, the breaker opening,
and the interruption of the current.
3 7
The Short Delay Pick Up has 7 settings/positions, 2–8 Ir
2 3 .
2
Short Delay I2T band has a tolerance of ±15%.
8
Breakpoint back to FLAT response occurs at 8x IR for upper line of the I2T curve.
9
10 For high fault current levels, an additional fixed instantaneous hardware override is provided
at 6800A (Tolerance ±15%).
2 4
1
0.9
0.8
0.7 5
0.6
0.5
0.4 7
0.3 0.3
8 Available Short Delay
0.2 Pickup Settings 0.2
6
I 2t Short Delay 2–8 x I r ±5%
(See Note 8) (See Notes 7 and 10)
0.1 0.1
.
0.09 0.09
0.08 0.08
0.07 Instantaneous Application 0.07
0.06 Override Determines 0.06
67 ms
Time in Seconds
0.03 0.03
See Note 9
0.02 0.02
0.01 0.01
0.5 0.7 1 2 3 4 5 7 10 12 20 30 40 50 70 100 2 3 4 5 7 10 20 30 40 50 70 100
Current in Multiples of (Ir) Current in Multiples of (In)
I 2t Trip Style (LS and LSG)
Figure 2. Digitrip 310+ Trip Units (800A), Long Delay Response and Short Delay with I2T Response Curve and Override
(LS, LSG) - TD012051EN, October 2014
6 EATON www.eaton.com
Series C Time Current Curves TD012036EN
M-Frame Effective December 2015
9000
8000
7000
6000
5000 Digitrip 310+ Circuit Breaker Time/Current Curves (Phase Current)
1.15
1 H our
80 Notes:
70 2*, 4*, 7*, 10, 12, 15*, 20, 24*
60 *Shown below at 6x
50 1 Curve accuracy applies from –20°C to +55°C ambient . For possible continuous ampere
derating for ambient above 40°C, refer to Eaton . Temperatures above +88°C cause an
40 over-temperature protection trip.
30 2
Application frequency is 50/60 Hertz.
. 3 There is a memory effect that can act to shorten the long delay. The memory effect comes
20 24 into play if a current above the long delay pickup value exists for a time and then is cleared
by the tripping of a downstream device or the circuit breaker itself. A subsequent overload
Time in Seconds
. will cause the circuit breaker to trip in shorter time than normal. The amount of time
reduction is inverse to the amount of time that has elapsed since the previous overload.
MinimumTotal 15
Approximately five minutes is required between overloads to completely reset the memory.
10 ClearingTime
9 4
The right portion of the curve is determined by the interrupting rating of the circuit breaker.
8
7 . 5
The left portion of the curve is shown as a multiple of the Long Delay Setting .
6 7 (Long Delay). Range is 110%–120%.
5 6 Total clearing times shown include the response times of the trip unit, the breaker
. Pickup = 115% of Ir opening, and the interruption of the current.
4
4 7
The Short Delay Pick Up has 7 settings/positions, 2–8 IR
3
8
For high fault current levels, an additional fixed instantaneous hardware override is provided
at 5620A (Tolerance ±15%).
2 .
2
Available Short
2 4
Delay Pickup
1 Settings 2–8,
0.9 6
0.8 x I r ±5% 3
0.7 (See Note 7) 8
0.6 5
0.5
0.4 0.4
0.3 300 ms 0.3
(P, Q, R)
Instantaneous
Time in Seconds
0.02 0.02
0.01 0.01
0.5 0.7 1 2 3 4 5 7 10 12 20 30 40 50 70 100 2 3 4 5 7 10 20 30 40 50 70 100
Current in Multiples of (Ir) Current in Multiples of (In)
Adjustable Flat Trip Style (LSI, LSIG, ALSI, ALSIG)
Figure 3. Digitrip 310+ Trip Units (800A), Long Delay Response and Short Delay with Flat Response Curve and Override
(LSI, LSIG, ALSI, ALSIG) - TD012052EN, October 2014
EATON www.eaton.com 7
Time Current Curves TD012036EN Series C
Effective December 2015 M-Frame
Curve accuracy applies from –20°C to +55°C ambient. For possible continuous ampere derating
for ambient above 40°C, refer to Eaton.
1000
900 Digitrip RMS 310 trip units are suitable for functional field testing with test kit Cat. No. STK2.
800 For field testing using primary injection methods, follow NEMA publications
700
600
500
400
300
200
100
90
80
1 Minute
70
60
50
40
30
20
Time in Seconds
10
9
8
7
6 Ground Fault Pickup Settings
5 (Tolerance ±10%)
4
0.4X
0.2X 0.6X 1X
1
0.9 0.3X
0.8
0.7
0.6 0.8X
0.5
0.4
0.3 300 ms
(L, O, R)
0.2
120 ms
0.1 (K, N, Q)
0.09
0.08
0.07
0.06
Inst.
0.05
(J, M, P)
0.04
0.03
0.02
0.01
0.1 0.2 0.3 0.4 0.5 0.7 1 2
Ground Current in Multiple of (In)
Figure 4. Ground Fault Delay Response Curve (LSG, LSIG, ALSIG) - Curve Number TD012053EN
8 EATON www.eaton.com
Series C Time Current Curves TD012036EN
M-Frame Effective December 2015
Notes:
Digitrip 310+ Circuit Breaker Time/Current Curves
Maintenance Mode Setting 1
The Maintenance Mode feature must be ENABLED via application of
24 Vdc for these curves to apply. The blue LED is lit when in Maintenance Mode.
Trip Unit Types: 38 (ALSI) and 39 (ALSIG)
2
The end of the curve is determined by the interrupting rating of the circuit breaker.
Series C M-Frame Trip Unit Nameplates
3 Total clearing times shown include the response times of the trip unit,
the breaker opening, and the interruption of the current.
4
Nominal Values (Pickup) (Tolerance is ±15%) 2.5 x In.
5
The total clearing times shown are conservative and consider the maximum response
time of the trip unit, the circuit breaker opening, and the interruption of the current in
the worst case conditions such as: maximum rated voltages, single-phase interruption,
and minimum power factor. Faster clearing times are possible depending on the specific
ALSI system conditions.
Contact Eaton for additional information.
.
NO
C
Black Yellow
Ir = Continuous Current Setting or Rating Plug Value, Is = Current Sensor Frame Rating, 24 Vdc
In = Rating Plug Value, Ig = Ground Current Pickup Multiplier, Ii = Instantaneous Override Pickup. Relay Wiring
Blue
Red
1
.9
.8
.7
.6 2.5
.5
.4
TIME IN SECONDS
.3
.2
.1
.09
.08
.07
.06 Application
.05 determines
end of curve
.04
.03
.02
.01
1
20
40
50
6
30
10
.8
.9
.6
4
.7
3
.5
7
8
9
Figure 5. Maintenance Mode Setting (ALSI, ALSIG) - Curver Number - TD012054EN, October 2014
EATON www.eaton.com 9
Time Current Curves TD012036EN Series C
Effective December 2015 M-Frame
Types MDL, HMDL, CMDL, and CHMDL Equipped with Type MES Digitrip RMS 310 Trip Units, Types MES3800LS and MES3800LSG
1.15 with Circuit Breaker Types MDL, HMDL, CMDL and CHMDL 3 Poles.
3,000
Fixed Short Delay Time Typical Trip Unit Nameplate
Digitrip RMS 310 Rating Plug Test
2,000 Cat.
Short Delay
Pickup x I n
Standard Fixed In
Push to Trip
4
5
6 Digitrip RMS 310
Rating Plug Engaged
3
2 8
7 Trip Unit
40o C Ambient
Remove
1,000
Digitrip RMS 310 trip units are suitable for functional field testing with test kit Cat. No. STK2.
For field testing using primary injection methods, follow NEMA AB4 publications.
3
Calibration response in short delay pick-up range is same for 1, 2 or 3 poles in series.
5X
2 There is a memory effect that can act to shorten the long delay. The memory effect comes
8X
into play if a current above the long delay pick-up value exists for a time and then is cleared
TIME IN SECONDS
by the tripping of a downstream device or the circuit breaker itself. A subsequent overload
will cause the circuit breaker to trip in shorter time than normal. The amount of time delay
1 reduction is inverse to the amount of time that has elapsed since the previous overload.
6X
Approximately five minutes is required between overloads to completely reset the memory.
1 Curve accuracy applies from –20°C to +55°C ambient. For possible continuous ampere
.5 derating for ambient above 40°C, refer to Eaton.
2 For high fault current levels a fixed instantaneous override is provided at 6800A.
.3 (Tolerance ±15%).
7X
3 The end of the curve is determined by the interrupting rating of the circuit breaker.
.2 See above tabulation.
.1 .1
.05 .05
Fixed Instantaneous
.04 Override ➁
.03 .03
Interrupting
.02 .02
Rating
Determines
End of
SECONDS
Curve ➂
.01 .01
.005
.003
.002
.001 .001
.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 910 20
1000
2000
3000
4000
5000
10,000
20,000
30,000
40,000
50,000
100,000
Figure 6. MDL, HMDL, CMDL, and CHMDL, types MES3800LS and MES3800LSG - Curve Number SC-7204-99, June 2007
10 EATON www.eaton.com
Series C Time Current Curves TD012036EN
M-Frame Effective December 2015
Types MDL, HMDL, CMDL, and CHMDL Equipped with Type MES Digitrip RMS 310 Trip Units, Types MES3800LSI and MES3800LSIG
Remove
5,000
Available Rating Plugs
1 HOUR
10
Calibration response in short delay pick-up range is same for 1, 2 or 3 poles in series.
There is a memory effect that can act to shorten the long delay. The memory effect comes
into play if a current above the long delay pick-up value exists for a time and then is cleared
4X
5 by the tripping of a downstream device or the circuit breaker itself. A subsequent overload
will cause the circuit breaker to trip in shorter time than normal. The amount of time delay
reduction is inverse to the amount of time that has elapsed since the previous overload.
Approximately five minutes is required between overloads to completely reset the memory.
6X
2
1 Curve accuracy applies from –20°C to +55°C ambient. For possible continuous ampere
derating for ambient above 40°C, refer to Eaton.
8X
TIME IN SECONDS
2 For high fault current levels a fixed instantaneous override is provided at 6800A.
(Tolerance ±15%).
7X
3 The end of the curve is determined by the interrupting rating of the circuit breaker.
See above tabulation.
.5
4 Long delay pickup is 115% of In, +/- 5%.
3X
5X
300 ms
.3
200 ms
.2
100 ms
.1 .1
I
.05 .05
Fixed Instantaneous
.04 Override ➁
.03 .03
.01 .01
Curve ➂
.005
.003
.002
.001 .001
.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20
1000
2000
3000
4000
5000
10,000
20,000
30,000
40,000
50,000
100,000
Figure 7. MDL, HMDL, CMDL, and CHMDL, types MES3800LSI and MES3800LSIG – Curve Number - SC-6913-98, June 2007
EATON www.eaton.com 11
Time Current Curves TD012036EN Series C
Effective December 2015 M-Frame
Types MDL, HMDL, CMDL, and CHMDL Equipped with Type MES Digitrip RMS 310 Trip Units, Ground Fault Protection
GROUND CURRENT-AMPERES
16000
1120
1280
1440
1600
160
320
480
640
800
960
10,000
2 HOURS
1,000
Fixed Short Delay Time Typical Trip Unit Nameplate
Digitrip RMS 310 Rating Plug Test
Short Delay Ground Fault Time
Cat. Pickup x I n Pickup x I g MIsec
Push to Trip 5 4 500
In 4 6 3 5 300 Digitrip RMS 310
7 3 2 150 Trip Unit
I 40o C Ambient
Engaged 1 I g = 160A
500 2 8
Remove
Remove
100
Notes:
1 MINUTE
Curve accuracy applies from –20°C to +55°C ambient. For possible continuous ampere derating
for ambient above 40°C, refer to Eaton.
50
Digitrip RMS 310 trip units are suitable for functional field testing with test kit Cat. No. STK2. For
field testing using primary injection methods, follow NEMA publication (AB4).
30
20
1xI G
10
3xI G
4xI G
2 Except + 20% on
1xI G Setting)
TIME IN SECONDS
5xI G
500 ms
.5
300 ms
.3
.2
150 ms
.1
I
.05
.03
.02
.01
.005
.003
.002
.001
1 2 3 4 5 6 7 8 910 100
Figure 8. MDL, HMDL, CMDL, and CHMD Ground Fault Protection - Curve Number SC-6914-98, June 2007
12 EATON www.eaton.com
Series C Time Current Curves TD012036EN
M-Frame Effective December 2015
Types MDL, HMDL, MDLB, and HMDLB Equipped with Type MT Thermal-Magnetic Trip Unit, 300 to 600 Amperes
10,000
1000
2000
3000
4000
5000
6000
7000
8000
9000
100
200
300
400
500
600
700
800
900
50
60
70
80
90
10,000 Series C M-Frame Circuit Breakers 10,000
2 HOURS
2 HOURS
1 HOUR
1 HOUR
start. Connected with four (4) feet of rated wire (75°C) per terminal. Tested in open air with
3,000 current in all poles. Instantaneous calibration based on single-pole3,000
tests.
2,000
Maximum Voltage: 600V, AC (50/60 Hz) 250V, DC 2,000
Breaker Rating
Rated Instantaneous Trip Amperes
1,000 1,000
Amperes (In) (See Figure Below)
300 - 600 500 to 1000% of trip unit rating (DC values are approximately 40% higher)
500 500
Interrupting Rating
UL/CSA rms Sym. kA, 50/60 Hz kA, DC
Maximum Single
300 Pole Trip Times Breaker Type 240V 480V 600V 250V
300
at 25 o C 1
MDL, MDLB 65 50 25 22
200 200
HMDL, HMDLB 100 65 35 25
Minimum
IEC 60947-2 rms Sym. kA, 50/60 Hz kA, DC
Maximum
100
Breaker Type 240V 380V 415V 250V 100
Icu Ics Icu Ics Icu Ics
1 MINUTE
1 MINUTE
MDL, MDLB 65 65 50 50 20 10 20 10
HMDL, HMDLB 100 100 70 50 25 13 20 10
50 50
Utilization Category A
UIMP = 8 kV
30
Notes:
30
1 Single pole data at 25°C based on NEMA Procedures (AB 4) for verifying performance of
molded case circuit breakers.
10 Typical 10
Trip Unit
Nameplate
7.5 7.5 7.5
C Thermal Push to Trip
5 Magnetic 5
Trip Unit
10 5 10 5 10 5
2 2
Individual Pole
TIME IN SECONDS
Adjustments
TIME IN SECONDS
+20% +10%
10X
5X
1 1
.5 .5
Adjustable Magnetic Trip
.3 .3
.2 .2
.1 .1
.05 .05
.03
Maximum Interrupting Time .03
.02 .02
.01 .01
Interrupting Rating
Determines End of
.005 .005
Curve
.003 .003
.002 .002
.001 .001
100,000
20,000
30,000
40,000
50,000
60,000
70,000
80,000
90,000
10,000
60
50
70
80
500
90
700
7000
200
300
400
600
800
900
100
1000
2000
3000
4000
5000
6000
8000
9000
Figure 9. MDL, HMDL, MDLB, and HMDLB, 300-600A - Curve Number SC-6911-98, June 2007
EATON www.eaton.com 13
Time Current Curves TD012036EN Series C
Effective December 2015 M-Frame
Types MDL, HMDL, MDLB, and HMDLB Equipped with Type MT Thermal-Magnetic Trip Unit, 700 and 800 Amperes
10,000
1000
2000
3000
4000
5000
6000
7000
8000
9000
100
200
300
400
500
600
700
800
900
50
60
70
80
90
10,000 10,000
2 HOURS
2 HOURS
1 HOUR
1 HOUR
2,000
For application and coordination purposes only. Thermal calibration based on 40°C ambient, cold
2,000
start. Connected with four (4) feet of rated wire (75°C) per terminal. Tested in open air with
current in all poles. Instantaneous calibration based on single-pole tests.
Breaker Rating
Rated Instantaneous Trip Amperes
500 500
Amperes (In) (See Figure Below)
Maximum Single 700 - 800 400 to 800% of trip unit rating (DC values are approximately 40% higher)
300 Pole Trip Times 300
at 25 o C 1
Interrupting Rating
200 200
UL/CSA rms Sym. kA, 50/60 Hz kA, DC
Breaker Type 240V 480V 600V 250V
Minimum Maximum
100 MDL, MDLB 65 50 25 100 22
HMDL, HMDLB 100 65 35 25
1 MINUTE
1 MINUTE
1 Single pole data at 25°C based on NEMA Procedures (AB 4) for verifying performance of
molded case circuit breakers.
5 5
6 6 6
3 Thermal 3
Magnetic Push to Trip
Trip Unit
8 4 8 4 8 4
2 2
Magnetic Amps o
C Cat.
(I n)
TIME IN SECONDS
8X
1 1
Individual Pole
Adjustments
.5 .5
Adjustable Magnetic Trip
.3 .3
.2 .2
.1 .1
.05 .05
.03 .03
Maximum Interrupting Time
.02 .02
.01 .01
Interrupting Rating
Determines End of
.005 .005
Curve
.003 .003
.002 .002
.001 .001
100,000
20,000
30,000
40,000
50,000
60,000
70,000
80,000
90,000
10,000
60
50
70
80
500
90
700
7000
200
300
400
600
800
900
100
1000
2000
3000
4000
5000
6000
8000
9000
Figure 10. MDL, HMDL, MDLB, and HMDLB, 700-800A - Curve Number SC-6912-98, June 2007
14 EATON www.eaton.com
Series C Time Current Curves TD012036EN
M-Frame Effective December 2015
EATON www.eaton.com 15
Time Current Curves TD012036EN Series C
Effective December 2015 M-Frame
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
© 2014 Eaton
All Rights Reserved Eaton is a registered trademark.
Printed in USA
Publication No. TD012036EN / KDC All other trademarks are property
April 2014 of their respective owners.