You are on page 1of 6

2014 International Conference on Power System Technology (POWERCON 2014) Chengdu, 20-22 Oct.

2014

Application of Model Current Predictive


Control in Low Voltage Ride Through of
Photovoltaic Station
JIA Lihu, ZHU Yongqiang, GUO Wenrui, WANG Yinshun

 the orders, which can not only reduce the other reactive
Abstract—As the large amount of new energy accessed to the equipment investment, but also improve the transient stability of
power system, the transient cut off of the new energy from the the power system. According to the study in this paper, the
grid will have an inevitable influence on the power system, at the proposed method has been proved effective.
same time, various faults of the power system will have bad
impact on the new energy system. This paper makes the Index Terms—Cost function, grid-connected inverters, low
photovoltaic generation system as the research object, and the voltage ride through, model current predictive control,
research mainly focused on the low voltage ride through ability of photovoltaic plants.
photovoltaic station when the grid occurs three-phase short
circuit fault and heavy load disturbance, which means the
grid-connected inverters can not only keep on operation I. INTRODUCTION
uninterrupted, but also injects the reactive current into the system,
which can provide voltage support for the power system during
the period of grid fault. Based on the foundation of traditional
control strategy of low voltage ride-through of photovoltaic power
D riven by the pressure of solving energy shortage crisis and
protecting the environment, a consensus has been reached
by researchers and policy makers around the world that new
station, a new control strategy of low voltage ride-through of energy resources mainly represented by solar power and wind
photovoltaic inverter based on model current predictive control power should be developed and exploited vigorously. The
(MPC) is proposed in this paper. The discrete-time model of the
inverter, filter, and load are used to predict the future behavior of
larger the scale of new energy connected to the grid, the heavier
the output currents for each of the eight possible switching states. the influence is exerted on the power grid. The connection and
This control method used the cost function to choose a switching disconnection of photovoltaic power station with a large energy
state that minimizes the error between the output currents and volume will exert a great influence on the stability of the power
their references. This control strategy has some advantages, such system, and on the other side power electronic devices broadly
as, control system design is relatively simple, output currents can implemented in new energy power stations are vulnerable
follow their references order quickly, so it has a good dynamic
characteristic. Finally, three-phase short circuit fault and heavy
during power system faults[1], [2]. As a consequence,
load disturbance simulations have been carried out on the photovoltaic power station with a large energy volume is
PSCAD/EMTDC platform, the simulation results show that required of being capable to conduct low voltage ride-through
during the low voltage of the system, the PV plant can support the according to the latest grid connection standard released by the
voltage by providing reactive power. During the heavy load access State Grid Corporation of China.
into the system suddenly, grid-inverters can control the PV inverter is the key equipment for photovoltaic power
photovoltaic station inject certain reactive current into the power
system and provide power for the heavy load nearby according to
station to realise low voltage ride-through. An LVRT control
strategy implemented on a single-stage non-isolated PV
inverter achieving LVRT by coordinating active power and
reactive power is proposed [3], but the aforementioned control
This work was supported in part by the Fundamental research funds for the
strategy adopts the traditional double closed-loop control
Central Universities and State Key Laboratory of Alternate Electrical Power strategy, the control circuit contains multiple PI controller,
System with Renewable Energy Sources open fund project. therefore, regulating parameters is difficult in practical
JIA Lihu, was with North China Electric Power University, Beijing 102206, engineering.
China. e-mail: jialihu@ncepuedu.cn.
ZHU Yongqiang, was with North China Electric Power University, Beijing In the reference [4], it presents a new LVRT SPLL
102206, China. e-mail: zyq@ncepu.edu.cn. (software phase locked loop) technique which is simpler and
GUO Wenrui, was with North China Electric Power University, Beijing faster, and designs a grid-connected PV (photovoltaic) inverter
102206, China. e-mail: guofrank@163.com.
WANG Yinshun, was with North China Electric Power University, Beijing based on the SPLL technique and relative control strategy.
102206, China. e-mail: yswang@ncepu.edu.cn. Without giving consideration to circumstances of voltage sag

POWERCON 2014 Paper No CP2529 Page 1/6 2846 Session 6


2014 International Conference on Power System Technology (POWERCON 2014) Chengdu, 20-22 Oct. 2014

over 20%, stability and reliability of the control algorithm inductor, and circuit element labeled with R is the equivalent
under serious fault cannot be guaranteed. resistor.
On the basis of [5-9], this paper adopts model current g1 g3 g5
predictive control strategy (MPC) on the control of PV inverter
for grid connection, which improves the traditional LVRT ia R eA
U dc
a ~
method remarkably, and gains desirable dynamic responses ib R eB
that distributes active power and reactive power according to b eC
~
c ic R
the situation of grid voltage sag rapidly and supports the ~
g4 g6 g2
voltage of the grid-connection point. What’s more, linear
current controller and PWM modulation module is abandoned
in the aforementioned control strategy, so the control algorithm
is simple, realised with digital signal processing(DSP) and Fig. 2 Structure of Grid-connected inverter
conducted in engineering practice are easy. According to the Kirchhoff’s voltage law, dynamic current
equation of the inverter can be described as follows:
II. LVRT REQUIREMENTS OF PV POWER STATION dik
L ukN  Rik  ek  unN (1)
Technical Requirement for grid connection of PV power dt
station mentions: PV power station should satisfy requirements where k=a, b, c. ik represents the output current of inverter for
of LVRT as shown in Fig.1. a) When voltage of grid connection; ukN represents output voltage of inverter for
grid-connection point of PV station drops to 0, PV power grid-connection; unN represents voltage between neutral point
station should be able to stay online and in continuous of grid voltage and the negative electrode of the DC ; ek
operation for 0.15s; b) when voltage of grid-connection point of represents the three phase grid voltage . Assuming that the grid
PV station drops below curve 1, PV power station can be voltage is symmetrical, then we get the equation ea+eb+ec=0.
switched out from the grid [10]. Now we analyze relationship between output voltage
vectors and switch status of the three phase inverter for
grid-connection [15]. Every set of bridge has two switch status
including case that upper leg of the bridge switches on and the
case that the lower leg of the bridge switches on, so that the
inverter has 23=8 switch status, which can be described using
single polar two-value logic switch function

­1, if S1 on and S 4 off


ga ® (2a)
¯0, if S1 off and S 4 on
­1, if S3 on and S6 off
Fig. 1. LVRT capacity requirements of photovoltaic plants gb ® (2b)
¯0, if S3 off and S6 on
III. SYSTEM MODEL AND PREDICTIVE CURRENT CONTROL ­1, if S5 on and S 2 off
STRATEGY gc ® (2c)
Model current predictive control strategy is based on the fact ¯0, if S5 off and S 2 on
that only a finite number of possible switching states can be Output voltage of inverter˖
generated. In addition, system model can predict the behaviors u U dc ( g a  ag b  a 2 g c ) (3)
of limited control variables under various switch status [11-15]. 2
For the selection of the appropriate switching state to be applied, j S
In equation (3), a e . 3
a selection criteria must be defined. This selection criteria is
expressed as a cost function that will be evaluated for the Converted from three phase static axis abc to two phase
predicted values of the variables to be con-trolled. Prediction of static axis DE , we get,
the future value of these variables is calculated for each ­ 2 1 1
possible switching state. The switching state that minimizes the °uD ( g a  gb  g c ) ˜ U dc
quality function is selected in the next period.
° 3 2 2 (4)
®
Fig.2 shows the main circuit of the PV inverter for grid ° 2
connection. The circuit element labeled with L is the filtering °̄uE 2 b
( g  g c ) ˜ U dc

POWERCON 2014 Paper No CP2529 Page 2/6 2847 Session 6


2014 International Conference on Power System Technology (POWERCON 2014) Chengdu, 20-22 Oct. 2014

The relationship between switch status and output voltage of and reactive power Q are respectively:
the inverter is shown in Fig.3. 3 3
E P ed id , Q  ed iq (8)
2 2
V3 V2 It can be concluded that the instantaneous active power and
the instantaneous reactive power of the inverter is only
g (0

determined by components of output current of inverter on axes


)
10
10

g (1

V0 d and q which are represented by idǃiq respectively, which


)

V4 g ( 00
0) V1
g (011) g (100) makes it possible to achieve decoupling control of active power
g (1
11) D and reactive power of inverter by controlling idǃiq.
01)

V7 After transformation of coordinates dq / DE , reference of


g (1
g (0

01)

*
V5 active current and reactive current id* ǃ iq that needed to be
V6
* *
Fig. 3 Relationship between switch states and output voltage
poured into the grid can be converted to reference iD ǃ iE in

Performing abc / DE conversion on equation (1), we get two phase static coordinates DE .
­ diD § iD* · § cosM  sinM · § id* ·
°° L dt uD  eD  RiD ¨ *¸ ¨ ¨ ¸
¨ i ¸ © sinM cosM ¸¹ ¨ i* ¸
(9)
(5)
® ©E¹ © q¹
° L diE uE  eE  RiE Value function is chosen as follows:
°̄ dt
c [iD*  iD ( k 1) ]2  [iD*  iE ( k 1) ]2 (10)
In the equation, uD ǃuE are components of output voltage of
where iD (k 1) ǃ iE (k 1) in the function are predictions of the
the inverter projected on axis D and E ; iD ǃ iE are
next sampling period.
components of output current of the inverter projected on axis
D and E ; eD ǃ eE are components of voltage of IV. CONTROL STRATEGY OF LVRT OF PV INVERTER
grid-connection point of the inverter projected on axis When grid voltage fluctuates between 0.9 p.u. and 1.1 p.u,
D and E ˗ the power system stays in normal operation; when grid voltage
drops below 0.9 p.u., the control model of the PV inverter
During the time period( tk , tk 1 ), perform discretization on switches to LVRT control from the normal control when the
(5), we get fault occurs. The reference of predictive current in normal
control is based on outer loop voltage, whereas the reference of
­ iD (k  1)  iD (k ) LVRT control is set by customer directly.
°L TS
uD (k )  eD (k )  RiD (k ) According to requirements of LVRT of PV power station
° (6) [10], dynamic reactive current Iq poured into the power system
®
i
°L E ( k  1)  iE (k ) by PV power station should trace the voltage variation of grid
uE (k )  eE (k )  RiE (k )
°¯ TS connection point in real time, and should meet the following
conditions,
where TS tk 1  tk is the sampling period. ­ Iq t 1.5 u (0.9  U G ) I N (0.2 d U G d 0.9)
It can be deduced from equation (6), ° (11)
® Iq t 1.05 I N (U G  0.2)
­ § RTS · TS ° Iq 0 (U G  0.9)
°iD (k 1) ¨1 L ¸ iD (k)  L > (uD (k)  eD (k))@ ¯
° © ¹ ˄7˅ where UG is the per unit value of the voltage of the grid
®
°i (k 1) §1 RTS · i (k)  TS ª(u (k)  e (k))º connection point of the PV power station; IN = rated installed
¨ ¸E
°¯ E L¬ ¼
E E
© L ¹
capacity of the PV power station / ( 3 u rated voltage of the
Under condition of balanced three phase voltage, applying grid connection point).
orientation control with grid voltage vectors, we orient axis d of The reactive current poured into the grid can be calculated
synchronously rotating coordinates dq to the direction of vector based on voltages of grid connection point, and both the active
Es which is synthesized by grid voltage, then we get the current and the reactive current should not exceed 1.1 times of
following equations: ed=|E|,eq=0. According to the the rated current, which can be described by the following
instantaneous power theory, the instantaneous active power P

POWERCON 2014 Paper No CP2529 Page 3/6 2848 Session 6


2014 International Conference on Power System Technology (POWERCON 2014) Chengdu, 20-22 Oct. 2014

inequality: connection point of PV power station is carried out on the


2 2 PSCAD/EMTDC platform, and feasibility and validity of the
i  i d 1.1I N
d q (12) proposed LVRT control strategy based on model current
LVRT control strategy based on model current prediction prediction is also verified. The capacity of the PV station is
* 1MW, the output voltage of the converter is 0.4kV, then it
manipulates id* ǃ iq mainly according to the voltage sag of the
connected to the grid through a 1000kVA/10kV transformer.
grid connection point. To avoid current increase, we apply LGJ-240/40 is chosen for the overhead line, and the length is
limiting amplitude control [16-18]. The block diagram of 10km.
LVRT control based on model current prediction is described in k (3)
Fig.4,
S
*
i
d
iq* predictive current control
iD* ga
dq / DE gb cost 
iE* predictive Grid
function g Fig. 6 Structure diagram of PV grid-connected system
c
T iD , E ( k )
model iD , E ( k  1)
B. Three phase short circuit fault
Three phase short circuit fault occurs on 10kv bus at 0.5s, and
lasts for 0.1s. the relay protection devices clears the fault at 0.6s,
and the system recovers. Before the fault occurs, the PV power
Fig. 4 Diagram of photovoltaic inverter control station operates with rated power output, and the power factor
is 1.
Fig.5 presents the control flow diagram of model current
predictive control, in which the programming in simulation is
completed using interface of language C in PSCAD/EMTDC.

uDˈE f ( S a , Sb , S c , Vdc )
(a) Instantaneous voltage and current
( k  2) ( k +1) ( k +1) ( k +1)
at grid connection point
iD ˈE f (iDˈE , uDˈE , eDˈE )

iDˈE * f (id * , iq * , M )

c (iD*  iD ( k  2) ) 2  (iE*  iE ( k  2) ) 2

if c (i ) d gop

(b) Comparison of active power at grid connection point

Fig. 5 Control flow of model current predictive control

V. IMPLEMENTATION OF THE CONTROL STRATEGY


A. Parameters in the simulation
In this paper, as shown in Fig.6, simulation cases of both
three-phase grounding fault and large load disturbance of grid

POWERCON 2014 Paper No CP2529 Page 4/6 2849 Session 6


2014 International Conference on Power System Technology (POWERCON 2014) Chengdu, 20-22 Oct. 2014

C. Grid connection point voltage with heavy load


At 0.5s, the active load at the terminal of the 10kV bus
doubles abruptly, and keeps that volume without further change.
Before the change of the load volume, the PV power station
operates at the rated power capacity with unity power factor.
After LVRT control strategy was carried out, comparison of the
waveforms of the voltage and power is shown as Fig.8.

(c) Comparison of reactive power at grid connection point


Voltage(p.u)
.

(a) Comparison of active power at grid connection point

(d) Comparison of voltage at grid connection point


Fig. 7 Comparison of parameters
before & after LVRT control

Due to the limiting amplitude effect of the inverter, the


output current of the inverter stays basically unchanged in
comparison to the value before the voltage sag occurs, whereas,
the phase between voltage and current changes remarkably, as
shown in Fig.7(a), because of the reactive power poured into (b) Comparison of reactive power at grid connection point
the grid through the control of LVRT to sustain the grid
voltage.

The capacity of the PV power station in the simulation


model is 1MW, of which the compensating capacity is 1MVAR.
To clearly explain the effect of voltage support of the PV power
station to the grid, the active current reference is set by id* 0 ,
and the reactive current reference is set by iq*  1 following
(c) Comparison of voltage at grid connection point
the priority of reactive power, which means the active current Fig. 8 Comparison of parameters before & after
value is zero. It can be seen from Fig.7(b)(c), after the LVRT control
application of LVRT control strategy, the volume of reactive After load variation, the output of active power will reduce
power improves from 0MVAR to 0.65 MVAR, and active and the output of reactive power will increase if the LVRT
power reduces from 0.9MW to 0MW. In the meantime, the PV control of active and reactive power is applied, as shown in
power station offers no active power to the grid, and becomes Fig.8(a),(b), and both the active power and the reactive power
reactive power compensating device completely. Furthermore, of the inverter will trace the reference value.
active power and reactive power will recover rapidly and be As shown in Fig.8(c), after load is put into operation, the
back the steady-state value as soon as the fault is excluded. voltage of the 10kV bus will drop below 0.91p.u. if LVRT
control strategy of power is not applied; in contrary, the bus
As shown in Fig.7(d), after the application of the LVRT voltage can be raised to 0.937p.u. ,and voltage support will be
control strategy, inverter can regulate the power rapidly offer to the grid by PV power station if the LVRT control
according to the current reference given, which offers voltage strategy is applied. It can be seen from the simulation example,
support to the grid and improves the voltage of the grid during the voltage sag period, the PV power station can offer
connection point from 0.683p.u. to 0.703p.u.. reactive power to the grid in a very short time, which functions
as voltage support to the grid. Because of the limited volume of

POWERCON 2014 Paper No CP2529 Page 5/6 2850 Session 6


2014 International Conference on Power System Technology (POWERCON 2014) Chengdu, 20-22 Oct. 2014

the PV power station, reactive power offered to the grid is also [7] AN Zhilong. Reaserch on the integration control strategy and low voltage
ride through technology of grid-connected PV system[D]. North China
limited. However, during grid disturbance or fault period, Electric Power University, 2012.
regardless of the output characteristics of the reactive power, [8] ZHANG Yajing, ZHENG Qionglin, MA Liang, LU Yuanhong. LVRT of
PV power stations offers voltage support to the grid in some Photovoltaic Grid-Connected Inverter Adopting Dual-Loop Control[J].
Transactions of China Electrotechnical Society, 2013,12:136-141.
degree, which improves the transient stability of the power [9] YANG Yong, ZHAO Fangping, RUAN Yi, ZHAO Chunjiang. Model
system. current predictive control for the three-phase grid-connected inverters[J].
Transactions of China Electrotechnical Society, 2011, 06:153-159ˊ
VI. CONCLUSION [10] GB/T 19964-2012 Technical regulations of the photovoltaic powerstation
connected to the power system[S]ˊBeijing: State Grid Corporation of
A predictive current control strategy and its practical China,2012ˊ
implementation in LVRT of grid-connected PV station has [11] Kouro S, Cortes P, Vargas R, et al. Model predictive control—a simple
been presented. It has been shown that the proposed method and powerful method to control power converters[J]. IEEE Transactions
on Industrial Electronics, 2009, 56(6): 1826-1838ˊ
control were very effective, and it can also offers desirable [12] Patricio C, Gabriel Otriz, Juan I, et al. Model Predictive Control of an
dynamic responses that will contributes to fast control of Inverter With Output LC Filter for UPS Applications[J]. IEEE
inverter for grid connection. Three phase short circuit fault and Transactions on Industrial Electronics, 2009, 56(6): 1875-1883ˊ
heavy load disturbance have been carried out on the [13] José Rodríguez, Jorge Pontt, César A. Silva, et al. Predictive Current
Control of a Voltage Source Inverter[J]. IEEE Transactions on Industrial
PSCAD/EMTDC platform, from the simulation result, it can be Electronics , 2007, 54(1):495-5033.
seen that by applying the control strategy during the fault [14] Patricio Cortés, Marian P. Kazmierkowski Ralph M. Kennel, et al.
period, the PV power station can improve its LVRT ability and Predictive Control in Power Electronics and Drives[J]. IEEE Transactions
on Industrial Electronics, 2008, 55(12): 4312-4323ˊ
offer the grid with some reactive power, which supports voltage
[15] Ali M. Almaktoof, A. K. Raji, and M. T. E. Kahn. Modeling and
in local field and cuts the volume of devices of traditional Simulation of Three-Phase Voltage Source Inverter Using a Model
reactive compensation. What’s more, by using such control Predictive Current Control[J]. International Journal of Innovation,
strategy, system will recover and be back to the normal Management and Techo -logy, 2014, 5(1):9-13ˊ
[16] WANG Wei, SUN Mingdong, ZHU Xiaodong. Analysis on the Low
operation rapidly, and the transient stability of the PV power Voltage Ride Through Technology of DFIG[J]. Automation of Power
station will be improved, which has vital practical significance. System, 2007, 23:84-89.
[17] ZHANG Yajing, Trillion Q. Zheng, LU Yuanhong, Ma Liang.
Optimization and Design of LVRT Strategy of Grid-Connected PV
System[J]. ACTA Energy Solaris Sinica, 2013,06:984-990.
[18] ZHANG Fei, ZHANG Junjun, DING Mingchang. Low Voltage
Ride-through Modeling and Control Strategy for Photovoltaic Generation
System Based on RTDS[J]. Automation of Power System, 2012,
22:19-24.

REFERENCES
[1] ZHAO Zhengming, LEI Yi, HE Fanbo, LU Zongxiang, TIAN Qi.
Overview of Large-scale Grid-connected Photovoltaic Power Plants[J].
Automation of Power System, 2011, 12: 101-107.
[2] GAO Mingjie, HUI Dong, LEI Weimin, et al. Presentation of National
Wind/Photovoltaic/Energy Storage and Transmission Demonstration
Project and Analysis of Typical Opration Modes[J]. Automation of Power
System, 2013, 01: 59-64.
[3] YUAN Xiaoling, SONG Pengfei, FAN Fajing, CHEN Yu. Low voltage
ride through control strategy for PV inverters[J]. Power Electronics, 2013,
03:67-69.
[4] WANG Nan, CHEN Yifeng, WU Hengliang. Reaserch on the technology
of low voltage ride through for the grid-connected photovoltaic
inverter[J]. High Power Converter Technology, 2013, 01:38-42+60.
[5] S. Alepuz, S. Busquets-Monge, J. Bordonau, et al. Predictive Current
Control of Grid-Connected Neutral-Point-Clamped Converters to Meet
Low Voltage Ride-Through Requirements[C]. Power Electronics
Specialists Conference, 2008, 2423-2428.
[6] ZHOU Jinghua, LIU Jingdong, CHEN Yaai, LI Jin. Low voltage ride
through control of high power inverter for grid –connection of
photovoltaic generation[J]. Power System Technology, 2013,
07:1799-1807.

POWERCON 2014 Paper No CP2529 Page 6/6 2851 Session 6

You might also like