You are on page 1of 18

gasprocessingnews.com/features/201408/simplify-bog-recondenser-design-and-operation—part-2.

aspx

Gas Processing & LNG is Produced by Gulf Publishing Holdings LLC

Simplify BOG recondenser design and operation—Part 2


S. P. B. Lemmers, Vopak LNG Holding BV, Rotterdam, The Netherlands

An LNG receiving and regasification terminal connects the intermittent process of LNG
carrier unloading and/or loading with the mostly continuous process of LNG vaporization
and gas transmission into a sendout pipeline system.

In addition to these LNG carrier operations, truck/train loading operations can take place
simultaneously. During all operational modes of the LNG terminal, boil-off gas (BOG) is
produced, which requires processing to avoid flaring or venting (under normal operating
conditions) and to minimize the environmental impact of the facility.

Part 1 of this article discussed optimal designs for BOG recondensers used in LNG
terminals. Here, operational aspects of BOG recondensers, based on the designs selected,
are examined.

For the two BOG recondenser designs commonly used in the industry, there are several
operational and process control elements to consider with respect to pressure and level
control.

Annular space type

In Fig. 1, an annular space type of BOG recondenser is shown. This type is used in many
LNG terminals, both older and newer. There are a number of advantages and
disadvantages to this design.

1/18
Fig. 1. Operation of an annular space BOG recondenser.

The LNG and BOG enter the packed section. This type of BOG recondenser works by
adjusting the amount of packed-section area available for condensing, by means of partial
flooding of the packed bed. To achieve partial flooding while ensuring a constant level and
net positive section head (NPSH) for the high-pressure (HP) pumps, a physical separation
between the two packed sections and the annular space is required.

The level and pressure in the annular section are kept constant. The level and pressure in
the packed section can be distinct from those in the annular section. Both the pressure and
level in the packed section self-adjust in response to varying BOG/LNG ratios.

At high BOG/LNG ratios, the liquid level in the packed-bed section decreases automatically,
through pushing of liquid to the annular space, as the pressure in this section increases.
2/18
This process exposes more of the packed bed, increasing the heat transfer/condensation
area to create equilibrium conditions—commonly referred to as the “auto-regulating” effect.

Likewise, a lower BOG/LNG ratio tends to reduce pressure in the packed section, which
then results in a level increase in the packed section. In other words, this type of
recondenser tends to adjust itself. Both the level and pressure in the two sections are
different.

Pressure control. For stable operation of the BOG recondenser, the BOG compressor
discharge pressure and annulus pressure must be controlled. Also, the annulus level and
the BOG recondenser outlet temperature must be guarded to ensure sufficient NPSH for
the HP pumps. The following examples of pressure control have been proven in the
industry.

Example 1. The BOG compressors compress the BOG into the BOG recondenser. The BOG
entering at the top of the BOG recondenser is condensed by contacting the BOG with
subcooled LNG from the discharge of the low-pressure (LP) pumps over a packed bed in
the BOG recondenser.

The pressure (and, therefore, the level) in the packed bed of the BOG recondenser varies
with the ratio of LNG vs. supplied BOG. When the BOG/LNG ratio increases, the pressure in
the packed section will rise, and the level in this section (which differs from the level in the
annular section, as does the pressure) will decrease. This results in an increase of the
available area for recondensation, thereby establishing a new equilibrium where all
incoming BOG is fully recondensed.

The discharge pressure of the BOG compressors is controlled via pressure controller PC 1,
and the pressure in the annulus is controlled via pressure controller PC2:

PC1 is a split-range controller that maintains the pressure in the discharge of the BOG
compressors via the control valve, which regulates the flow of BOG to the packed-
bed section. If the BOG compressors’ discharge pressure becomes too low to
guarantee sufficient NPSHrequired for the HP pumps, then PC 1 will introduce padding
gas from the HP natural gas system or fuel gas system.
PC2 is a split-range controller that maintains the pressure in the annulus of the BOG
recondenser. Even in the annular space, there will be some recondensation of BOG
into the LNG at the interface. Therefore, to maintain pressure, some BOG must be fed
into the annular space. On the other hand, ambient heat in-leak generates BOG,
counteracting the above process. There is a need for split-range pressure control
(i.e., bringing in BOG or venting to the BOG compressor suction head, as required).
When the pressure rises, this controller will first close the control valve on the
incoming BOG that bypasses the packed bed. Then, when the pressure rises further,
PC2 will open the control valve to the LP BOG head upstream of the BOG
compressors.

The control characteristics of both pressure controllers are depicted in Fig. 2.

3/18
Fig. 2. Pressure control characteristics.

Example 2. To maintain both the correct pressure control (Fig. 3) of the annulus pressure
and the NPSHrequired for the HP pumps, transmitters connected to the annular space
provide an input to three pressure controllers to deal with low (PC1), medium (PC 2) and high
(PC3) pressure conditions:

Under normal conditions, the pressure in the annulus will be maintained by gas from
the BOG compressors by means of the PC2 pressure controller, which controls BOG
flow into the annular space.
If there is less BOG available, then the pressure in the annulus will tend to fall, and
the pressure controller will introduce padding gas. Under normal conditions, the
padding gas control valve will be closed.
If the pressure in the annulus becomes too high, then the PC 3 pressure controller will
allow BOG to pass through the vent to the LP BOG head upstream of the BOG
compressors. Similar to the padding gas control valve, this control valve will be
closed under normal conditions.
A differential pressure control valve will be provided in the line from the BOG
compressors downstream of the split to the recondenser annulus and center section,
to maintain positive BOG pressure upstream of the BOG recondenser.

4/18
Fig. 3. BOG recondenser pressure control.

Level and total volume control. To ensure constant HP pump conditions, the LNG level in
the annular space of the BOG recondenser is controlled via manipulating the LNG inlet
valve to the packed-bed section of the BOG recondenser. The level controller must be
tuned so that moderate fluctuations in the BOG recondenser level are allowed to prevent
unacceptable disturbances to the LP pump operation. The control valve should have a high
turndown ratio and high resolution.

As discussed previously, the level in the packed-bed section is not directly regulated; it will
vary as a result of the BOG/LNG ratio. The higher the BOG/LNG injection ratio, the less
contacting area is required for recondensation, and the higher the level will reach. When
there is less contacting area, the pressure will rise and the level will decrease due to the
increased pressure.
5/18
Conversely, when the BOG/LNG ratio is high, the pressure in the packed section will rise
and the level will drop. This results in an increase of the available area for recondensation;
the pressure will fall, and the level will rise again.

A practical result of this floating packed-section level is the following inverse-response


phenomenon. If the BOG/LNG ratio increases, then the level in the packed bed will
decrease, and the level in the annulus will initially increase because the pressure in the
central section increases (pushing LNG from the packed section into the annular space),
which forces the level controller (LC) to close the LNG inlet valve. This reduces the level in
the packed-bed section even further.

To avoid this inverse response of the level control system, an LNG total volume control,
based on both the level in the packed section and the level in the annulus, has been
developed and implemented. This response, which is potentially caused by uncontrolled
introduction of padding gas, may displace liquid from the packed-bed section to the
annulus and vice versa, making the simple annulus level an unstable parameter for
controlling the flow of LNG into the recondenser.

For total volume control, liquid levels in both the BOG recondenser annulus and the BOG
recondenser packed bed will be measured and used for calculation of total LNG volume in
the BOG recondenser. The calculated total LNG volume, rather than the level in the annular
space, is controlled by regulating the flow of LNG to the packed bed. By using total volume
control, any transient conditions are ignored and the inverse response is eliminated.

The total volume of LNG in the BOG recondenser is calculated as shown in Eq. 1:

LNG volume = Vf × π × Rb 2 × Lb + (π Rv 2 − πRb 2) × La(1)

where:

Vf=Volume of fractional voids

La=Annulus level

Lb=Core section level

Rb=Packed-bed radius

Rv=Vessel radius.

Application of total volume control is depicted in Fig. 4.

6/18
Fig. 4. Total volume control applied to the BOG recondenser.

Bottom level and ratio control. All process control examples described so far include LNG
flow through the BOG recondenser packed section. At high LNG terminal sendout rates, this
can result in a continuous recycle of padding gas from downstream of the LNG vaporizers
to maintain pressure in the BOG recondenser, since the LNG sendout rate is significantly
higher than that required to recondense all generated BOG.

This operation is not energy efficient; therefore, some annular space type designs have
introduced an LNG inlet into the holdup section. This reduces the BOG/LNG ratio in the
packed-bed section and minimizes the requirement for padding gas. The downside is that
it influences the effectiveness of the auto-regulating effect (when level is maintained
predominantly below the packed bed), compared to a BOG recondenser without a bottom
inlet.

Some of these annular space BOG recondenser designs have introduced ratio control for
the ratio of LNG to the packed bed and BOG. The balance of the LNG goes directly into the
holdup section of the BOG recondenser. Since BOG and LNG compositions and
temperatures can change, the pressure in the BOG recondenser packed section is a result
of the setpoint of the BOG/LNG ratio controller.
7/18
Fig. 5 shows the described level and ratio control scheme. The installation of a bottom LNG
inlet that is controlled by level can influence the effectiveness of the auto-regulating effect,
which is the main feature of the annular space type design. The selection of an annular
space BOG recondenser should, therefore, be reconsidered.

Fig. 5. Introduction of level bottom inlet and BOG/LNG ratio control.

Ratio control and pressure override. When the BOG/LNG ratio controller is not
programmed and/or configured correctly, there is a possibility that either padding gas will
need to be introduced by PC1 (when the LNG-to-packed bed/BOG ratio is too high), or BOG
will need to be directed to the BOG suction head by PC3 (when the ratio is too low). Either
scenario results in a loss of operational energy efficiency.

To resolve this issue, overrides from PC 2 can be configured to control the BOG recondenser
pressure when the bypass valve around the pressure differential controller (i.e., the bypass
of BOG to the annular space) is already closed. This scenario is depicted in Fig. 6.

8/18
Fig. 6. Level bottom inlet control with pressure override.

Top packed-bed section type

A typical top packed-bed section type of the BOG recondenser is depicted in Figs. 7 and
10. The pressure and level control for this type are depicted in Figs. 2 and 5 of Part 1.
Similar to the annular space type, this BOG recondenser receives BOG from the BOG
compressors for recondensation, and it also provides holdup and NPSHrequired for the HP
pumps.

For the top packed-bed section BOG recondensers, the liquid level is normally below the
bottom of the packed bed. As such, the heat transfer area constantly allows for a simple
and proven pressure control scheme. To control the BOG recondenser pressure, only some
of the LNG is routed to the packed bed, with the balance of the incoming LNG being routed
directly to the bottom holdup section. This type of BOG recondenser requires two LNG
inlets.

Pressure control. The main objective of the pressure control is achieved by the flowrate of
the subcooled LNG from the bottom LNG inlet line to the packed section, to keep the BOG
9/18
recondenser at a pre-set operational pressure. This control enables stable HP pump and
BOG compressor operation. Output from the pressure controller is cascaded as setpoint to
the LNG quench (LNG to packed bed) flow controller.

If the pressure increases, then more LNG is routed to the packed bed, reducing the
pressure and preventing the opening of the connection to the BOG compressor suction
head. If the pressure decreases, then the pressure controller will increase the LNG flowrate
via the quench flow controller, to prevent the opening of the padding gas supply. With this
type of BOG recondenser, it is easy to adjust the operating pressure of the BOG
recondenser (typically between 6 barg and 10 barg) in LNG operations.

When no quench flow controller or flow measurement is provided, the pressure controller
can directly act on the quench flow valve. A cascade configuration provides more stability
with respect to change in flow, which will be picked up directly by the flow controller before
it affects BOG recondenser pressure.

Level control. The LNG liquid level in the BOG recondenser is controlled by manipulating
the bottom LNG inlet valve to the BOG recondenser. The level controller can be loosely
controlled, since neither operation nor the process requires tight level control in the BOG
recondenser.

Process control examples and lessons learned

Process control scenarios can be applied to both types of BOG recondensers, showing
control schemes that work, as well as schemes that have failed to work, in practice.

Ratio control with pressure prediction. For both BOG recondenser designs, the BOG/LNG
ratio control between the LNG quench flow to the packed bed and the incoming BOG has
been applied. Fig. 7 depicts this control scheme for a top packed-bed section type.

10/18
Fig. 7. BOG/LNG ratio control with the objective to predict operating pressure.

The objective of this control scheme is to establish a pressure setpoint that is converted
into a flow setpoint to the quench flow controller. The scheme in Fig. 7 is a simplification;
an implemented control scheme uses a ratio of mass-flow of LNG to BOG, corrected for
BOG and LNG quench temperature and BOG recondenser operating pressure. The final
volumetric quench flow setpoint is based on actual LNG quench flow density calculations,
shown in Eqs. 2–4:

LNGtoBOGmassratio = UncorrectedRatio ×
BOGTCorrection × LNGTCorrection(2)

ActualVolLNGtoBOGmassratio =
LNGtoBOGmassratio / ρLNG(3)

ActualVolFlowLNG = ActualVolLNGtoBOG
massratio × BOGmassflow(4)

The control scheme’s objective is to predict the pressure in the BOG recondenser on the
basis of Eqs. 2–4. However, multi-process variable control resulted in an offset between the
desired pressure in the BOG recondenser and the actual pressure. This result proved that,
even by creating a rigorous mathematical model of the involved thermodynamics, the
pressure in the BOG recondenser could not be predicted.

LNG operations then changed the input to the model (i.e., the desired pressure in the BOG
recondenser) so that the desired pressure was reached. This resulted in manual feedback
control by the operator. For instance, if 6 barg was the desired pressure, the operator keyed
6.32 barg into the distributed control system. However, when the composition changed, the
resulting value was 6.65 barg. LNG operations used trial-and-error to achieve the desired
setpoint pressure.

Pressure override on ratio control. Some designs for both types of BOG recondensers
have a pressure override controller on the BOG/LNG ratio control. When the pressure
reaches the HP setting, this pressure controller will take over from the BOG/LNG ratio
controller.

As an alternative to this pressure override controller, a pressure controller with a gap could
be considered; this controller acts only on the quench on HP to avoid opening the control
valve to the suction of the LP compressors. On LP, it acts on the quench to avoid the
unnecessary supply of padding gas.

Some fundamental questions to ask are, “If the pressure must be controlled, can a pressure
controller be installed on the quench?” and “What are the real advantages and benefits of
BOG/LNG ratio control and a floating pressure?” This argument is especially true for the
top packed-bed type of BOG recondenser. Furthermore, the original annular space type
without a bottom LNG inlet requires a floating pressure for the auto-regulating effect.

11/18
By installing the override from PC 2, it has become obvious that BOG recondenser control
based on ratio control is not essential. Also, the main pressure control is better located on
the bypass, and the quench LNG flow should be located at the top (Fig. 8).

Fig. 8. Pressure override and padding gas stability.

Padding gas stability. For stable padding gas control of the BOG recondenser pressure, the
padding gas control valves should be installed at a certain distance to the BOG
recondenser to provide adequate control time for the control loop to stabilize. Typically, a
few seconds are required for the padding gas control loop to stabilize. An unstable padding
gas control loop results in violent opening and closing of the valve. In one example, LNG
operations decoupled the padding gas control loop due to valve issues.

Full operational bypass without pumps holdup. A BOG recondenser with full operational
bypass directly to the HP pump suction is depicted in Fig. 9. In this configuration, the
majority of the LNG completely bypasses the BOG recondenser and is fed directly into the
suction of the HP pumps, while the balance of the LNG is fed to the packed bed, as required
to control the pressure in the BOG recondenser.

12/18
Fig. 9. Full operational bypass without holdup for HP pumps with operational
bypass.

Successful application of this system has demonstrated that there is no need for
substantial liquid holdup in the BOG recondenser. The one potential operational
disadvantage of this control scheme is that the LNG in the BOG recondenser can be at
bubble-point conditions (rather than subcooled, as is the pumped LNG from the LP pumps),
and a sudden inflow of warm LNG (resulting from the interruption of colder LNG flowing
directly from the LP pumps) can upset HP pump operations. This upset would happen at a

13/18
high level in the aforementioned example, where the valve supplying subcooled LNG from
the LP pumps is closed, and only relatively warm LNG from the BOG recondenser is fed into
the HP pump suction cans.

Control of recondenser bottom pressure. One design that uses bottom pressure control in
an attempt to maintain stable suction conditions to the HP pumps is shown in Fig. 10. At a
fixed BOG recondenser pressure, the HP pump suction pressure is a direct function of the
LNG level, so the PC4 effectively replaces the normal level controller, manipulating the
control valve to the holdup section. However, this pressure control scheme is not advised,
since 0.5 bar of pressure in the suction needs to be compensated with approximately 10
meters of LNG, which will result in unstable level and pressure control of the BOG
recondenser.

Fig. 10. Control of BOG recondenser bottom pressure.

Compressor type and pressure control. The type of compressor chosen—centrifugal or


reciprocating—sets requirements on the BOG recondenser pressure control. The more
commonly used reciprocal compressors are reasonably insensitive to fluctuations in BOG
recondenser discharge pressure.

Conversely, the less commonly used centrifugal compressors can easily move between the
surge area (at high BOG recondenser pressure) to the stonewall area (at low BOG
recondenser pressure) as a result of discharge pressure fluctuations (Fig. 11). Therefore,
when using centrifugal BOG compressors, the BOG recondenser pressure must be tightly
controlled.

14/18
Fig. 11. Typical variable centrifugal BOG compressor curves (either by inlet guide
vanes or speed).

Operation and process control takeaway

Several conclusions can be drawn with respect to the information presented on operation
and process control of both types of BOG recondensers. For the annular space type of BOG
recondenser:

Various pressure control schemes have been successfully implemented in the


industry, and are functional
An annular space design having an LNG inlet only to the top packed-bed section can
suffer from an inverse response when configured to operate on level control only;
therefore, total volume control is required for stable operation
The aforementioned type can also introduce the requirement of continuous recycle of
padding gas from the gas sendout system (in the case of high BOG/LNG ratio), at the
expense of overall energy efficiency
To avoid continuous recycle of padding gas to the BOG recondenser, an LNG bottom
inlet controlled by level can be introduced at the cost of reducing the effectiveness of
the auto-regulating effect
Selecting a top packed-bed type of BOG recondenser should be considered when a
bottom LNG inlet is installed in combination with an annular space type of BOG
recondenser, since its main feature, the auto-regulating effect, will not work when
the level remains predominantly controlled below the packed bed.
15/18
For the top packed-bed section type:

Trying to predict the resulting operating pressure on the basis of BOG/LNG ratio has
proven not to be feasible in practice
When the operating pressure must be controlled, a simple pressure control loop (see
Figs. 2 and 5, Part 1) has proven its effectiveness
BOG/LNG ratio control is feasible, but pressure remains a fluctuating process
variable
Controlling the BOG recondenser bottom LNG outlet pressure by controlling level has
proven to be unstable in practice, since a small change in pressure results in a large
change in BOG recondenser level.

For both types:

For BOG recondenser types with a bottom LNG inlet, BOG/LNG ratio control can be
used when a fluctuating pressure in the BOG recondenser is acceptable
When installing BOG/LNG ratio control and pressure overrides, the designer should
consider installing pressure control with a gap, or just a simple pressure control
For stable padding gas control, the padding gas control valves should be installed at
a certain distance to the BOG recondenser to provide adequate time for the control
loop to stabilize
In top packed-bed section type BOG recondensers that have operational bypass
directly into the HP pump suction cans, a sudden inflow of warm LNG from the BOG
recondenser can disturb HP pump operations
When a centrifugal BOG compressor is applied, stable pressure control is required to
ensure stable BOG compressor operation. The top packed-bed section type with
pressure control on the LNG quench is more suitable for this process than is the
annular space type.

Less is more. An overview of the most commonly used process control and operational
tactics of BOG recondensers reveals the advantages and disadvantages in BOG
recondenser operation. BOG recondensers of both types—annular space type and packed-
bed type—have been installed and operated successfully.

As a general recommendation, BOG recondenser designers are advised to consider simple


designs and operational process control mechanisms.

End of series. Part 1, May/June 2014. GP

Acknowledgment

The author thanks Michiel Baerends from Fluor BV and his colleagues at Vopak LNG
Holding BV (part of Koninklijke Vopak NV), as well as Gate terminal BV,
for reviewing the article prior to publication.

SANDER P. B. LEMMERS has more than 17 years of experience in both the technical and
business facets of the global engineering, procurement and construction industry. He holds
a BSc degree and an MSc degree in industrial engineering and management, and an MSc
degree in chemical engineering, from Twente University for Technical and Social Sciences

16/18
in Enschede, The Netherlands. At present, Mr. Lemmers is involved in the development of
LNG and other liquefied gas terminals in Southeast Asia, Scandinavia, France, and The
Netherlands.

Commodity Last Change

Crude Oil WTI 67.59s +0.26

Natural Gas (Henry 3.185s -0.017


Hub)

Copyright © 2018. All market data is provided


by Barchart Solutions. Futures: at least a 10
minute delay. Information is provided 'as is'
and solely for informational purposes, not for
trading purposes or advice. To see all
exchange delays and terms of use, please see disclaimer.

FEATURED COLUMNS
GasPro 2.0: A Webcast Symposium

Register Now

The global LNG industry is becoming increasingly interconnected as grassroots export


projects get off the ground. Another technology route for processing gas into fuels—GTL—
is attracting renewed attention due to improving economics. Small-scale solutions for both
LNG and GTL are at the forefront of new technological developments, while major projects
using more conventional technologies continue to start up around the world.

During this webcast, we will focus on LNG, GTL, gas processing technology developments
and deployments, operations, small-scale solutions, transportation, trading, distribution,
safety, regulatory affairs, business analysis and more.

October 25, 2018 08:30 AM CDT

Register Now

Please read our Term and Conditions, Cookies Policy, and Privacy Policy before using the
site. All material subject to strictly enforced copyright laws.
© 2018 Gulf Publishing Holdings LLC.

17/18
18/18

You might also like