You are on page 1of 20

Source: HANDBOOK OF MECHANICAL ENGINEERING CALCULATIONS

P • A • R • T 1

POWER GENERATION

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)


Copyright © 2006 The McGraw-Hill Companies. All rights reserved.
Any use is subject to the Terms of Use as given at the website.
POWER GENERATION

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)


Copyright © 2006 The McGraw-Hill Companies. All rights reserved.
Any use is subject to the Terms of Use as given at the website.
Source: HANDBOOK OF MECHANICAL ENGINEERING CALCULATIONS

SECTION 1
MODERN POWER-PLANT
CYCLES AND EQUIPMENT
CYCLE ANALYSES 1.4 Steam-Turbine Regenerative-Cycle
Choosing Best Options for Boosting Performance 1.71
Combined-Cycle Plant Output 1.4 Reheat-Regenerative Steam-Turbine
Selecting Gas-Turbine Heat-Recovery Heat Rates 1.74
Boilers 1.10 Steam Turbine-Gas Turbine Cycle
Gas-Turbine Cycle Efficiency Analysis Analysis 1.76
and Output Determination 1.13 Gas Turbine Combustion Chamber
Determining Best-Relative-Value of Inlet Air Temperature 1.81
Industrial Gas Turbines Using a Life- Regenerative-Cycle Gas-Turbine
Cycle Cost Model 1.18 Analysis 1.83
Tube Bundle Vibration and Noise Extraction Turbine kW Output 1.86
Determination in HRSGs 1.22 STEAM PROPERTIES AND PROCESSES
Determining Oxygen and Fuel Input in 1.87
Gas-Turbine Plants 1.25 Steam Mollier Diagram and Steam
Heat-Recovery Steam Generator Table Use 1.87
(HRSG) Simulation 1.28 Interpolation of Steam Table Values
Predicting Heat-Recovery Steam 1.90
Generator (HRSG) Temperature Constant-Pressure Steam Process
Profiles 1.33 1.93
Steam Turbogenerator Efficiency and Constant-Volume Steam Process
Steam Rate 1.36 1.95
Turbogenerator Reheat-Regenerative Constant-Temperature Steam Process
Cycle Alternatives Analysis 1.37 1.97
Turbine Exhaust Steam Enthalpy and Constant-Entropy Steam Process
Moisture Content 1.42 1.99
Steam Turbine No-Load and Partial- Irreversible Adiabatic Expansion of
Load Steam Flow 1.43 Steam 1.101
Power Plant Performance Based on Irreversible Adiabatic Steam
Test Data 1.45 Compression 1.103
Determining Turbogenerator Steam Throttling Processes for Steam and
Rate at Various Loads 1.47 Water 1.105
Analysis of Reheating-Regenerative Reversible Heating Process for Steam
Turbine Cycle 1.48 1.107
Steam Rate for Reheat-Regenerative Determining Steam Enthalpy and
Cycle 1.49 Quality Using the Steam Tables
Binary Cycle Plant Efficiency Analysis 1.109
1.51 Maximizing Cogeneration Electric-
CONVENTIONAL STEAM CYCLES 1.53 Power and Process-Steam Output
Finding Cogeneration System 1.110
Efficiency vs a Conventional Steam ECONOMIC ANALYSES OF
Cycle 1.53 ALTERNATIVE ENERGY SOURCES
Bleed-Steam Regenerative Cycle 1.112
Layout and T-S Plot 1.55 Choice of Most Economic Energy
Bleed Regenerative Steam Cycle Source Using the Total-Annual-Cost
Analysis 1.59 Method 1.112
Reheat-Steam Cycle Performance Seven Comparison Methods for
1.62 Energy Source Choice 1.115
Mechanical-Drive Steam-Turbine Selection of Prime Mover Based on
Power-Output Analysis 1.67 Annual Cost Analyses 1.120
Condensing Steam-Turbine Power- Determining If a Prime Mover Should
Output Analysis 1.69 Be Overhauled 1.122

1.3
Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
Copyright © 2006 The McGraw-Hill Companies. All rights reserved.
Any use is subject to the Terms of Use as given at the website.
MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.4 POWER GENERATION

Cycle Analyses

CHOOSING BEST OPTION FOR BOOSTING


COMBINED-CYCLE PLANT OUTPUT

Select the best option to boost the output of a 230-MW facility based on a 155-
MW natural-gas-fired gas turbine (GT) featuring a dry low NOx combustor (Fig.
1). The plant has a heat-recovery steam generator (HRSG) which is a triple-pressure
design with an integral deaerator. A reheat condensing steam turbine (ST) is used
and it is coupled to a cooling-tower / surface-condenser heat sink turbine inlet. Steam
conditions are 1450-lb / in2 (gage) / 1000F (9991-kPa / 538C). Unit ratings are for
operation at International Standard Organization (ISO) conditions. Evaluate the var-
ious technologies considered for summer peaking conditions with a dry bulb (DB)
temperature of 95F and 60 percent RH (relative humidity) (35C and 60 percent
RH). The plant heat sink is a four-cell, counterflow, mechanical-draft cooling tower
optimized to achieve a steam-turbine exhaust pressure of 3.75 inHg absolute (9.5
cmHg) for all alternatives considered in this evaluation. Base circulating-water sys-
tem includes a surface condenser and two 50 percent-capacity pumps. Water-
treatment, consumption, and disposal-related O&M (operating & maintenance)

H-p I-p turbine L-p turbine


turbine
Cooling tower
Generator

H-p steam

L-p
Cold steam
reheat
steam Makeup water
Hot reheat I-p steam Feedwater Condensate
pumps pumps
Deaerator
Reheater
Fuel
suprerheater

suprerheater
economizer

economizer

economizer
evaporator

evaporator

evaporator

Generator
H-p

H-p

L-p

L-p
I-p

I-p

I-p

I-p

Gas turbine
H-p superheater
Air Blowdown Blowdown

I-p pump

I-p pump

FIGURE 1 155-MW natural-gas-fired gas turbine featuring a dry low NOx combustor (Power).

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)


Copyright © 2006 The McGraw-Hill Companies. All rights reserved.
Any use is subject to the Terms of Use as given at the website.
MODERN POWER-PLANT CYCLES AND EQUIPMENT

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.5

costs for the zero-discharge facility are assumed to be $3 / 1000 gal ($3 / 3.8 m3) of
raw water, $6 / 1000 gal ($6 / 3.8 m3) of treated demineralized water, and $5 / 1000
gal ($5 / 3.8 m3) of water disposal. The plant is configured to burn liquid distillate
as a backup fuel.

Calculation Procedure:
1. List the options available for boosting output
Seven options can be developed for boosting the output of this theoretical reference
plant. Although plant-specific issues will have a significant effect on selecting an
option, comparing performance based on a reference plant, Fig. 1, can be helpful.
Table 1 shows the various options available in this study for boosting output. The
comparisons shown in this procedure illustrate the characteristics, advantages, and
disadvantages of the major power augmentation technologies now in use.
Amidst the many advantages of gas turbine (GT) combined cycles (CC) popular
today from various standpoints (lower investment than for new greenfield plants,
reduced environmental impact, and faster installation and startup), one drawback is
that the achievable output decreases significantly as the ambient inlet air tempera-
ture increases. The lower density of warm air reduces mass flow through the GT.
And, unfortunately, hot weather typically corresponds to peak power loads in many
areas. So the need to meet peak-load and power-sales contract requirements causes
many power engineers and developers to compensate for ambient-temperature-
output loss.
The three most common methods of increasing output include: (1) injecting
water or steam into the GT, (2) precooling GT inlet air, and / or (3) supplementary
firing of the heat-recovery steam generator (HRSG). All three options require sig-
nificant capital outlays and affect other performance parameters. Further, the options

TABLE 1 Performance Summary for Enhanced-Output Options

Case 61 Case 72
Case 1 Case 2 Case 3 Case 4 Case 5 Supp.- Supp.-
Measured change from Evap. Mech. Absorp. Steam Water fired fired
base case cooler chiller chiller injection injection HRSG HRSG
GT output, MW 5.8 20.2 20.2 21.8 15.5 0 0
ST output, MW 0.9 2.4 ⫺2.1 ⫺13 3.7 8 35
Plant aux. load, MW 0.05 4.5 0.7 400 0.2 0.4 1
Net plant output, MW 6.65 18.1 17.4 8.4 19 7.6 34
Net heat rate, Btu / kWh3 15 55 70 270 435 90 320
Incremental costs
Change in total water
cost, $ / h 15 35 35 115 85 35 155
Change in wastewater
cost, $ / h 1 17 17 2 1 1 30
Change in capital cost /
net output, $ / kW 180 165 230 75 15 70 450
1
Partial supplementary firing.
2
Full supplementary firing.
3
Based on lower heating value of fuel.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)


Copyright © 2006 The McGraw-Hill Companies. All rights reserved.
Any use is subject to the Terms of Use as given at the website.
MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.6 POWER GENERATION

may uniquely impact the operation and / or selection of other components, including
boiler feedwater and condensate pumps, valves, steam turbine / generators, con-
densers, cooling towers, and emissions-control systems.

2. Evaluate and analyze inlet-air precooling


Evaporative cooling, Case 1, Table 1, boosts GT output by increasing the density
and mass flow of the air entering the unit. Water sprayed into the inlet-air stream
cools the air to a point near the ambient wet-bulb temperature. At reference con-
ditions of 95F (35C) DB and 60 percent RH, an 85 percent effective evaporative
cooler can alter the inlet-air temperature and moisture content to 85F (29C) and
92 percent RH, respectively, using conventional humidity chart calculations, page
16.79. This boosts the output of both the GT and—because of energy added to the
GT exhaust—the steam turbine / generator. Overall, plant output for Case 1 is in-
creased by 5.8 MW GT output ⫹ 0.9 MW ST output—plant auxiliary load of 0.9
MW ⫽ 6.65 MW, or 3.3 percent. The CC heat rate is improved 0.2 percent, or 15
Btu / kWh (14.2 kJ / kWh). The total installed cost for the evaporative cooling sys-
tem, based on estimates provided by contractors and staff, is $1.2-million. The
incremental cost is $1,200,000 / 6650 kW ⫽ $180.45 / kW for this ambient condition.
The effectiveness of the same system operating in less-humid conditions—say
95F DB (35C) and 40 percent RH—is much greater. In this case, the same evap-
orative cooler can reduce inlet-air temperature to 75F DB (23.9C) by increasing
RH to 88 percent. Here, CC output is increased by 7 percent, heat rate is improved
(reduced) by 1.9 percent, and the incremental installed cost is $85 / kW, computed
as above. As you can clearly see, the effectiveness of evaporative cooling is directly
related to reduced RH.
Water-treatment requirements must also be recognized for this Case, No. 1. Be-
cause demineralized water degrades the integrity of evaporative-cooler film media,
manufacturers may suggest that only raw or filtered water be used for cooling
purposes. However, both GT and evaporative-cooler suppliers specify limits for
turbidity, pH, hardness, and sodium (Na) and potassium (K) concentrations in the
injected water. Thus, a nominal increase in water-treatment costs can be expected.
In particular, the cooling water requires periodic blowdown to limit solids buildup
and system scaling. Overall, the evaporation process can significantly increase a
plant’s makeup-water feed rate, treatment, and blowdown requirements. Compared
to the base case, water supply costs increase by $15 / h of operation for the first
approach, and $20 / h for the second, lower RH mode. Disposal of evaporative-
cooler blowdown costs $1 / h in the first mode, $2 / h in the second. Evaporative
cooling has little or no effect on the design of the steam turbine.

3. Evaluate the economics of inlet-air chilling


The effectiveness of evaporative cooling is limited by the RH of the ambient air.
Further, the inlet air cannot be cooled below the wet-bulb (WB) temperature of the
inlet air. Thus, chillers may be used for further cooling of the inlet air below the
wet-bulb temperature. To achieve this goal, industrial-grade mechanical or absorp-
tion air-conditioning systems are used, Fig. 2. Both consist of a cooling medium
(water or a refrigerant), an energy source to drive the chiller, a heat exchanger for
extracting heat from the inlet air, and a heat-rejection system.
A mechanical chilling system, Case 2, Table 1, is based on a compressor-driven
unit. The compressor is the most expensive part of the system and consumes a
significant amount of energy. In general, chillers rated above 12-million Btu / h (3.5
MW) (1000 tons of refrigeration) (3500 kW) employ centrifugal compressors. Units
smaller than this may use either screw-type or reciprocating compressors. Overall,

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)


Copyright © 2006 The McGraw-Hill Companies. All rights reserved.
Any use is subject to the Terms of Use as given at the website.
MODERN POWER-PLANT CYCLES AND EQUIPMENT

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.7

Ambient air
Circulating (95F, 60% RH)
water pump
Chilled-
water coils

Chilled Chilled air


water (60F, 100% RH)

HRSG

Gas turbine/
generator
Cooling
Electric- tower
driven Cooling
centrifugal water
chiller

Chilled-water loop
25-psia Cooling tower
steam
from
HRSG 2-stage
lithium
Condensate bromide
return adsorption
chiller

FIGURE 2 Inlet-air chilling using either centrifugal or absorption-type chillers, boosts the
achieveable mass flow and power output during warm weather (Power).

compressor-based chillers are highly reliable and can handle rapid load changes
without difficulty.
A centrifugal-compressor-based chiller can easily reduce the temperature of the
GT inlet air from 95F (35C) to 60F (15.6C) DB—a level that is generally ac-
cepted as a safe lower limit for preventing icing on compressor inlet blades—and
achieve 100 percent RH. This increases plant output by 20.2 MW for GT ⫹ 2.4
MW for ST ⫺ 4.5 MW plant auxiliary load ⫽ 18.1 MW, or 8.9 percent. But it
degrades the net CC heat rate by 0.8 percent and results in a 1.5-in-(3.8-cm)-H2O
inlet-air pressure drop because of heat-exchanger equipment located in the inlet-air
stream.
Cooling requirements of the chilling system increase the plant’s required cir-
culating water flow by 12,500 gal / min (47.3 m3 / min). Combined with the need for
increased steam condensing capacity, use of a chiller may necessitate a heat sink
25 percent larger than the base case. The total installed cost for the mechanical
chilling system for Case 2 is $3-million, or about $3,000,000 / 18,100 kW ⫽
$165.75 / kW of added output. Again, costs come from contractor and staff studies.
Raw-water consumption increase the plant’s overall O&M costs by $35 / h when
the chiller is operating. Disposal of additional cooling-tower blowdown costs $17 /
h. The compressor used in Case 2 consumes about 4 MW of auxiliary power to
handle the plant’s 68-million Btu / h (19.9 MW) cooling load.

4. Analyze an absorption chilling system


Absorption chilling systems are somewhat more complex than mechanical chillers.
They use steam or hot water as the cooling motive force. To achieve the same inlet-
air conditions as the mechanical chiller (60F DB, 100 percent RH) (15.6C, 100

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)


Copyright © 2006 The McGraw-Hill Companies. All rights reserved.
Any use is subject to the Terms of Use as given at the website.
MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.8 POWER GENERATION

percent RH), an absorption chiller requires about 111,400 lb / h (50,576 kg / h) of


10.3-lb / in2 (gage) (70.9-kPa) saturated steam, or 6830 gal / min (25.9 m3 / min) of
370F (188C) hot water.
Cost-effective supply of this steam or hot water requires a redesign of the ref-
erence plant. Steam is extracted from the low-pressure (l-p) steam turbine at 20.3
lb / in2 (gage) (139.9 kPa) and attemperated until it is saturated. In this case, the
absorption chiller increases plant output by 8.7 percent or 17.4 MW but degrades
the plant’s heat rate by 1 percent.
Although the capacity of the absorption cooling system’s cooling-water loop
must be twice that of the mechanical chiller’s, the size of the plant’s overall heat
sink is identical—25 percent larger than the base case—because the steam extracted
from the l-p turbine reduces the required cooling capacity. Note that this also re-
duces steam-turbine output by 2 MW compared to the mechanical chiller, but has
less effect on overall plant output.
Cost estimates summarized in Table 1 show that the absorption chilling system
required here costs about $4-million, or about $230 / kW of added output. Compared
to the base case, raw-water consumption increases O&M costs by $35 / h when the
chiller is operating. Disposal of additional cooling-water blowdown adds $17 / h.
Compared to mechanical chillers, absorption units may not handle load changes
as well; therefore they may not be acceptable for cycling or load-following oper-
ation. When forced to operate below their rated capacity, absorption chillers suffer
a loss in efficiency and reportedly require more operator attention than mechanical
systems.
Refrigerant issues affect the comparison between mechanical and absorption
chilling. Mechanical chillers use either halogenated or nonhalogenated fluorocar-
bons at this time. Halogenated fluorocarbons, preferred by industry because they
reduce the compressor load compared to nonhalogenated materials, will be phased
out by the end of the decade because of environmental considerations (destruction
of the ozone layer). Use of nonhalogenated refrigerants is expected to increase both
the cost and parasitic power consumption for mechanical systems, at least in the
near term. However, absorption chillers using either ammonia or lithium bromide
will be unaffected by the new environmental regulations.
Off-peak thermal storage is one way to mitigate the impact of inlet-air chilling’s
major drawback: high parasitic power consumption. A portion of the plant’s elec-
trical or thermal output is used to make ice or cool water during off-peak hours.
During peak hours, the chilling system is turned off and the stored ice and / or cold
water is used to chill the turbine inlet air. A major advantage is that plants can
maximize their output during periods of peak demand when capacity payments are
at the highest level. Thermal storage and its equipment requirements are analyzed
elsewhere in this handbook—namely at page 18.70.

5. Compare steam and water injection alternatives


Injecting steam or water into a GT’s combustor can significantly increase power
output, but either approach also degrades overall CC efficiency. With steam injec-
tion, steam extracted from the bottoming cycle is typically injected directly into the
GT’s combustor, Fig. 3. For advanced GTs, the steam source may be extracted from
either the high-pressure (h-p) turbine exhaust, an h-p extraction, or the heat recovery
steam generator’s (HRSG) h-p section.
Cycle economics and plant-specific considerations determine the steam extrac-
tion point. For example, advanced, large-frame GTs require steam pressures of 410
to 435 lb / in2 (gage) (2825 to 2997 kPa). This is typically higher than the econom-
ically optimal range of h-p steam turbine exhaust pressures of 285 to 395 lb / in2

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)


Copyright © 2006 The McGraw-Hill Companies. All rights reserved.
Any use is subject to the Terms of Use as given at the website.
MODERN POWER-PLANT CYCLES AND EQUIPMENT

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.9

Demin. Water-injection
storage power sugmentation Steam-injection
power sugmentation
Attemperating
Water station
injection
skid

HRSG

Gas turbine/ High-pressure


generator superheater
FIGURE 3 Water or steam injection can be used for both power augmentation and NOx control
(Power).

(gage) (1964 to 2722 kPa). Thus, steam must be supplied from either the HRSG
or an h-p turbine extraction ahead of the reheat section.
Based on installed-cost considerations alone, extracting steam from the HRSG
is favored for peaking service and may be accomplished without altering the reheat
steam turbine. But if a plant operates in the steam-injection mode for extended
periods, extracting steam from the turbine or increasing the h-p turbine exhaust
pressure becomes more cost-effective.
Injecting steam from the HRSG superheat section into the GT increases unit
output by 21.8 MS, Case 4 Table 1, but decreases the steam turbine / generator’s
output by about 12.8 MW. Net gain to the CC is 8.4 MW. But CC plant heat rate
also suffers by 4 percent, or 270 Btu / kWh (256.5 kJ / kWh).
Because the steam-injection system requires makeup water as pure as boiler
feedwater, some means to treat up to 350 gal / min (22.1 L / s) of additional water
is necessary. A dual-train demineralizer this size could cost up to $1.5-million.
However, treated water could also be bought from a third party and stored. Or
portable treatment equipment could be rented during peak periods to reduce capital
costs. For the latter case, the average expected cost for raw and treated water is
about $130 / h of operation.
This analysis assumes that steam- or water-injection equipment is already in
place for NOx control during distillate-fuel firing. Thus, no additional capital cost
is incurred.
When water injection is used for power augmentation or NOx control, the rec-
ommended water quality may be no more than filtered raw water in some cases,
provided the source meets pH, turbidity, and hardness requirements. Thus, water-
treatment costs may be negligible. Water injection, Case 5 Table 1, can increase
the GT output by 15.5 MW.
In Case 5, the bottoming cycle benefits from increased GT-exhaust mass flow,
increasing steam turbine / generator output by about 3.7 MW. Overall, the CC output
increases by 9.4 percent or 19 MW, but the net plant heat rate suffers by 6.4 percent,
or 435 Btu / kWh (413.3 kJ / kWh). Given the higher increase in the net plant heat
rate and lower operating expenses, water injection is preferred over steam injection
in this case.

6. Evaluate supplementary-fired HRSG for this plant


The amount of excess O2 in a GT exhaust gas generally permits the efficient firing
of gaseous and liquid fuels upstream of the HRSG, thereby increasing the output

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)


Copyright © 2006 The McGraw-Hill Companies. All rights reserved.
Any use is subject to the Terms of Use as given at the website.
MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.10 POWER GENERATION

from the steam bottoming cycle. For this study, two types of supplementary firing
are considered—(1) partial supplementary firing, Case 6 Table 1, and (2) full sup-
plementary firing, Case 7 Table 1.
There are three main drawbacks to supplementary firing for peak power en-
hancement, including 910 lower cycle efficiency, (2) higher NOx and CO emissions,
(3) higher costs for the larger plant equipment required.
For this plant, each 100-million Btu / h (29.3 MW) of added supplementary firing
capacity increases the net plant output by 5.5 percent, but increases the heat rate
by 2 percent. The installed cost for supplementary firing can be significant because
all the following equipment is affected: (1) boiler feed pumps, (2) condensate
pumps, (3) steam turbine / generator, (4) steam and water piping and valves, and (5)
selective-catalytic reduction (SCR) system. Thus, a plant designed for supplemen-
tary firing to meet peak-load requirements will operate in an inefficient, off-design
condition for most of the year.

7. Compare the options studied and evaluate results


Comparing the results in Table 1 shows that mechanical chilling, Case 2, gives the
largest increase in plant output for the least penalty on plant heat rate—i.e., 18.1
MW output for a net heat rate increase of 55 Btu / kWh (52.3 kJ / kWh). However,
this option has the highest estimated installed cost ($3-million), and has a relatively
high incremental installed cost.
Water injection, Case 5 Table 1, has the dual advantage of high added net output
and low installed cost for plants already equipped with water-injection skids for
NOx control during distillate-fuel firing. Steam injection, Case 4 Table 1, has a
significantly higher installed cost because of water-treatment requirements.
Supplementary firing, Cases 6 and 7 Table 1, proves to be more acceptable for
plants requiring extended periods of increased output, not just seasonal peaking.
This calculation procedure is the work of M. Boswell, R. Tawney, and R. Narula,
all of Bechtel Corporation, as reported in Power magazine, where it was edited by
Steven Collins. SI values were added by the editor of this handbook.
Related Calculations. Use of gas turbines for expanding plant capacity or for
repowering older stations is a popular option today. GT capacity can be installed
quickly and economically, compared to conventional steam turbines and boilers.
Further, the GT is environmentally acceptable in most areas. So long as there is a
supply of combustible gas, the GT is a viable alternative that should be considered
in all plant expansion and repowering today, and especially where environmental
conditions are critical.

SELECTING GAS-TURBINE HEAT-RECOVERY


BOILERS

Choose a suitable heat-recovery boiler equipped with an evaporator and economizer


to serve a gas turbine in a manufacturing plant where the gas flow rate is 150,000
lb / h (68,040 kg / h) at 950F (510C) and which will generate steam at 205 lb / in2
(gage) (1413.5 kPa). Feedwater enters the boiler at 227F (108.3C). Determine if
supplementary firing of the exhaust is required to generate the needed steam. Use
an approach temperature of 20F (36C) between the feedwater and the water leav-
ing the economizer.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)


Copyright © 2006 The McGraw-Hill Companies. All rights reserved.
Any use is subject to the Terms of Use as given at the website.
MODERN POWER-PLANT CYCLES AND EQUIPMENT

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.11

Calculation Procedure:
1. Determine the critical gas inlet-temperature
Turbine exhaust gas (TEG) typically leaves a gas turbine at 900–1000F
(482–538C) and has about 13 to 16 percent free oxygen. If steam is injected into
the gas turbine for NOx control, the oxygen content will decrease by 2 to 5 percent
by volume. To evaluate whether supplementary firing of the exhaust is required to
generate needed steam, a knowledge of the temperature profiles in the boiler is
needed.
Prepare a gas / steam profile for this heat-recovery boiler as shown in Fig. 4.
TEG enters on the left at 950F (510C). Steam generated in the boiler at 205 lb /
in2 (gage) (1413.5 kPa) has a temperature of 390F (198.9C), from steam tables.
For steam to be generated in the boiler, two conditions must be met: (1) The ‘‘pinch
point’’ temperature must be greater than the saturated steam temperature of 390F
(198.9C), and (2) the temperature of the saturated steam leaving the boiler econ-
omizer must be greater than that of the feedwater. The pinch point occurs some-
where along the TEG temperature line, Fig. 4, which starts at the inlet temperature
of 950F (510C) and ends at the boiler gas outlet temperature, which is to be
determined by calculation. A pinch-point temperature will be assumed during the
calculation and its suitability determined.
To determine the critical gas inlet-temperature, T1, get from the steam tables the
properties of the steam generated by this boiler: ts ⫽ 390F (198.9C); hl, heat of
saturated liquid ⫽ 364 Btu / lb (846.7 kJ / kg); hs, total heat of saturated vapor ⫽
1199.6 Btu / lb (2790.3 kJ / kg; hw, heat of saturated liquid of feedwater leaving the
economizer at 370F (187.8C) ⫽ 342 Btu / lb (795.5 kJ / kg); and hƒ, heat of satu-
rated liquid of the feedwater at 227F (108.3C) ⫽ 196.3 Btu / lb (456.6 kJ / kg).

Top Numbers: Example 1


T1
Bottom Numbers: Example 2
950
1,550
T2 Pinch point
415
440 T3
317
Tl 296

390
390
Tw
370 Tt
Approach point 325 227
227

950˚F (510˚C) 1550˚F (843˚C) 390˚F (199˚C) 390˚F (199˚C)


415˚F (213˚C) 440˚F (227˚C) 370˚F (188˚C) 325˚F (163˚C)
317˚F (158˚C) 296˚F (147˚C) 227˚F (108˚C) 227˚F (108˚C)
FIGURE 4 Gas / steam profile and data (Chemical Engineering).

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)


Copyright © 2006 The McGraw-Hill Companies. All rights reserved.
Any use is subject to the Terms of Use as given at the website.
MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.12 POWER GENERATION

Writing an energy balance across the evaporator neglecting heat and blowdown
losses, we get: (T1 ⫺ T2) / (T1 ⫺ T3) ⫽ (hs ⫺ hw ) / (hs ⫺ hƒ) ⫽ X, where T1 ⫽ gas
temperature in boiler, F (C); T2 ⫽ pinch-point gas temperature, F (C); T3 ⫽
outlet gas temperature for TEG, F (C); enthalpy, h, values as listed above; X ⫽
ratio of temperature or enthalpy differences. Substituting, X ⫽ (1199.6 ⫺ 342) /
(1199.9 ⫺ 196.3) ⫽ 0.855, using enthalpy values as given above.
The critical gas inlet-temperature, T1c ⫽ (ts ⫺ Xtƒ) / (1 ⫺ X ), where ts ⫽ tem-
perature of saturated steam, F (C); tƒ ⫽ temperature of feedwater, F (C); other
symbols as before. Using the values determined above, T1c ⫽ [390 ⫺
(0.855)(227)] / (1 ⫺ 0.855) ⫽ 1351F (732.8C).

2. Determine the system pinch point and gas / steam profile


Up to a gas inlet temperature of approximately 1351F (732.8C), the pinch point
can be arbitrarily selected. Beyond this, the feedwater inlet temperature limits the
temperature profile. Let’s then select a pinch point of 25F (13.9C), Fig. 4. Then,
T2, the gas-turbine gas temperature at the pinch point, F (C) ⫽ tƒ ⫹ pinch-point
temperature difference, or 390F ⫹ 25F ⫽ 415F (212.8C).
Setting up an energy balance across the evaporator, assuming a heat loss of 2
percent and a blowdown of 3 percent, leads to: Qevap ⫽ We (1 ⫺ heat loss)(TEG
heat capacity, Btu / F) (T1 ⫺ T2), where We ⫽ TEG flow, lb / h; heat capacity of
TEG ⫽ 0.27 Btu / F; T1 ⫽ TEG inlet temperature, F (C). Substituting, Qevap ⫽
150,000(0.98)(0.27)(950 ⫺ 415) ⫽ 21.23 ⫻ 106 Btu / h (6.22 MW).
The rate of steam generation, Ws ⫽ Qevap / [(hs ⫺ hw ) ⫹ blowdown percent ⫻
(hl ⫺ hw )], where the symbols are as given earlier. Substituting, Ws ⫽ 21.23 ⫻
106 / [(1199.6 ⫺ 342) ⫹ 0.03 ⫻ (364 ⫺ 342)] ⫽ 24,736 lb / h (11,230 kg / h).
Determine the boiler economizer duty from Qecon ⫽ (1 ⫹ blowdown)(Ws )
(hw ⫺ hƒ), where symbols are as before. Substituting, Qecon ⫽ 1.03(24,736)(342 ⫺
196.3) ⫽ 3.71 ⫻ 106 Btu / h (1.09 MW).
The gas exit-temperature, T3 ⫽ T2 ⫺ Qecon / TEG gas flow, lb / h)(1 ⫺ heat
loss)(heat capacity, Btu / lb F). Since all values are known, T3 ⫽ 415 ⫺ 3.71 ⫻
106 / (150,000 ⫻ 0.98 ⫻ 0.27) ⫽ 317F (158C). Figure 4 shows the temperature
profile for this installation.
Related Calculations. Use this procedure for heat-recovery boilers fired by
gas-turbine exhaust in any industry or utility application. Such boilers may be un-
fired, supplementary fired, or exhaust fired, depending on steam requirements.
Typically, the gas pressure drop across the boiler system ranges from 6 to 12 in
(15.2 to 30.5 cm) of water. There is an important tradeoff: a lower pressure drop
means the gas-turbine power output will be higher, while the boiler surface and the
capital cost will be higher, and vice versa. Generally, a lower gas pressure drop
offers a quick payback time.
If Pe is the additional gas pressure in the system, the power, kW, consumed in
overcoming this loss can be shown approximately from P ⫽ 5 ⫻ 10⫺8 (We Pe T
/ E, where E ⫽ efficiency of compression).
To show the application of this equation and the related payback period, assume
We ⫽ 150,000 lb / g (68,100 kg / h), T ⫽ 1000R (average gas temperature in the
boiler, Pe ⫽ 4 in water (10.2 cm), and E ⫽ 0.7. Then P ⫽ 5 ⫻ 10⫺8 (150,000 ⫻
4 ⫻ 1000 / 0.7) ⫽ 42 kW.
If the gas turbine output is 4000 kW, nearly 1 percent of the power is lost due
to the 4-in (10.2-cm) pressure drop. If electricity costs 7 cent / kWh, and the gas
turbine runs 8000 h / yr, the annual loss will be 8000 ⫻ 0.07 ⫻ 42 ⫽ $23,520. If
the incremental cost of a boiler having a 4-in (10.2-cm) lower pressure drop is, say
$22,000, the payback period is about one year.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)


Copyright © 2006 The McGraw-Hill Companies. All rights reserved.
Any use is subject to the Terms of Use as given at the website.
MODERN POWER-PLANT CYCLES AND EQUIPMENT

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.13

Fuel

F, Wf

We, T1´ (We  Wf),T1´


Burner

TEG

(Weh1´  LHV  Wt)  (We  Wf)h1

FIGURE 5 Gas / steam profile for fired mode (Chemical Engineering).

If steam requirements are not stated for a particular gas inlet condition, and
maximum steaming rate is desired, a boiler can be designed with a low pinch point,
a large evaporator, and an economizer. Check the economizer for steaming. Such
a choice results in a low gas exit temperature and a high steam flow.
Then, the incremental boiler cost must be evaluated against the additional steam
flow and gas-pressure drop. For example, Boiler A generates 24,000 lb / h (10,896
kg / h), while Boiler B provides 25,000 lb / h (11,350 kg / h) for the same gas pres-
sure-drop but costs $30,000 more. Is Boiler B worth the extra expense?
To answer this question, look at the annual differential gain in steam flow. As-
suming steam costs $3.50 / 1000 lb (3.50 / 454 kg), the annual differential gain in
steam flow ⫽ 1000 ⫻ 3.5 ⫻ 8000 / 1000 ⫽ $28,000. Thus, the simple payback is
about a year ($30,000 vs $28,000), which is attractive. You must, however, be
certain you assess payback time against the actual amount of time the boiler will
operate. If the boiler is likely to be used for only half this period, then the payback
time is actually two years.
The general procedure presented here can be used for any type industry using
gas-turbine heat-recovery boilers—chemical, petroleum, power, textile, food, etc.
This procedure is the work of V. Ganapathy, Heat-Transfer Specialist, ABCO In-
dustries, Inc., and was presented in Chemical Engineering magazine.
When supplementary fuel is added to the turbine exhaust gas before it enters
the boiler, or between boiler surfaces, to increase steam production, one has to
perform an energy balance around the burner, Fig. 5, to evaluate accurately the gas
temperature increase that can be obtained.
V. Ganapathy, cited above, has a computer program he developed to speed this
calculation.

GAS-TURBINE CYCLE EFFICIENCY ANALYSIS


AND OUTPUT DETERMINATION

A gas turbine consisting of a compressor, combustor, and an expander has air


entering at 60F (15.6C) and 14.0 lb / in2 (abs) (96.5 kPa). Inlet air is compressed

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)


Copyright © 2006 The McGraw-Hill Companies. All rights reserved.
Any use is subject to the Terms of Use as given at the website.
MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.14 POWER GENERATION

to 56 lb / in2 (abs) (385.8 kPa); the isentropic efficiency of the compressor is 82


percent. Sufficient fuel is injected to give the mixture of fuel vapor and air a heating
value of 200 Btu / lb (466 kJ / kg). Assume complete combustion of the fuel. The
expander reduces the flow pressure to 14.9 lb / in2 (abs), with an engine efficiency
of 85 percent. Assuming that the combustion products have the same thermody-
namic properties as air, cp ⫽ 0.24, and is constant. The isentropic exponent may
be taken as 1.4. (a) Find the temperature after compression, after combustion, and
at the exhaust. (b) Determine the Btu / lb (kJ / kg) of air supplied, the work delivered
by the expander, the net work produced by the gas turbine, and its thermal effi-
ciency.

Calculation Procedure:
1. Plot the ideal and actual cycles
Draw the ideal cycle as 1-2-3-4-1, Figs. 6 and 7. Actual compression takes place
along 1-2. Actual heat added lies along 2-3. The ideal expansion process path is
3-4. Ideal work ⫽ cp (ideal temperature difference). Actual work ⫽ cp (actual
temperature difference).

2. Find the temperature after compression


Use the relation (T2 / T1) ⫽ (P2 / P1)(k⫺1) / k, where T1 ⫽ entering air temperature, R;
T2 ⫽ temperature after adiabatic compression, R; P1 ⫽ entering air pressure, in
units given above; P2 ⫽ pressure after compression, in units given above; k ⫽
isentropic exponent ⫽ 1.4. With an entering air temperature, T1 of 60F (15.6C),
or 60 ⫹ 460 ⫽ 520R, and using the data given, T2 ⫽ 520[(56 / 14)](1.4⫺1) / 1.4 ⫽
772.7R, or 772.7 ⫺ 520 ⫽ 252.7F (122.6C).
(a) Here we have isentropic compression in the compressor with an effi-
ciency of 85 percent. Using the equation, Efficiency, isentropic ⫽ (cp )(T2 ⫺ T1) /
(cp )(T2 ⫺ T1), and solve for T2, the temperature after isentropic compression. Solv-
ing, T2 ⫽ 0.82 ⫽ 0.24(772.7 ⫺ 520) / 0.24(T2 ⫺ 520) ⫽ 828.4R, or 368F. This
is the temperature after compression.

3. Determine the temperature after combustion


To find the temperature after combustion, use the relation Heating value of fuel ⫽
Q ⫽ cp (T3 ⫺ T2), where T3 ⫽ temperature after combustion, R. Substituting,
200 ⫽ 0.24(T3 ⫺ 828). Solving, T3 ⫽ 1661.3R; 1201.3F (649.6C).

FIGURE 6 Ideal gas-turbine cycle, 1-2-3-4-1. Actual compression takes place along 1-2; actual
heat added 2-3; ideal expansion 3-4.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)


Copyright © 2006 The McGraw-Hill Companies. All rights reserved.
Any use is subject to the Terms of Use as given at the website.
MODERN POWER-PLANT CYCLES AND EQUIPMENT

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.15

FIGURE 7 Ideal gas-turbine cycle T-S diagram with the same processes as in Fig. 6; complete-
cycle gas turbine shown below the T-S diagram.

4. Find the temperature at the exhaust of the gas turbine


Using an approach similar to that above, determine T4 from (T4 / T3) ⫽
[(P4 / P3)]k⫺1 / k. Substituting and solving for T4 ⫽ 1661[(14.9 / 56)](1.4⫺1) / 1.4 ⫽
1137.9R, or 677.8F (358.8C).
Now use the equation for gas-turbine efficiency, namely, Turbine efficiency ⫽
cp (T3 ⫺ T4ⴖ)/ cp (T3 ⫺ T4) ⫽ 0.85, and solve for T4ⴖ, the temperature after expan-
sion, at the exhaust. Substituting as earlier, T4ⴖ ⫽ 1218.2R, 758.2F (403.4C). This
is the temperature after expansion, i.e., at the exhaust of the gas turbine.

5. Determine the work of compression, expander work, and thermal efficiency


(b) The work of compression ⫽ cp(T2 ⫺ T1) ⫽ 0.24(828 ⫺ 520) ⫽ 74.16 Btu (78.23
J).
The work delivered by the expander ⫽ cp(T2 ⫺ T1) ⫽ 0.24 (1661 ⫺ 1218) ⫽
106.32 Btu (112.16 J).
The net work ⫽ 106.3 ⫺ 74.2 ⫽ 32.1 Btu (33.86 J). Then, the thermal
efficiency ⫽ net work / heat supplied ⫽ 32.1 / 200 ⫽ 0.1605, 16.6 percent thermal
efficiency.
Related Calculations. With the widespread use today of gas turbines in a va-
riety of cycles in industrial and central-station plants, it is important that an engineer
be able to analyze this important prime mover. Because gas turbines can be quickly
installed and easily hooked to heat-recovery steam generators (HRSG), they are
more popular than ever before in history.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)


Copyright © 2006 The McGraw-Hill Companies. All rights reserved.
Any use is subject to the Terms of Use as given at the website.
MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.16 POWER GENERATION

Further, as aircraft engines become larger—such as those for the Boeing 777
and the Airbus 340—the power output of aeroderivative machines increases at little
cost to the power industry. The result is further application of gas turbines for
topping, expansion, cogeneration and a variety of other key services throughout the
world of power generation and energy conservation.
With further refinement in gas-turbine cycles, specific fuel consumption, Fig. 8,
declines. Thus, the complete cycle gas turbine has the lowest specific fuel con-
sumption, with the regenerative cycle a close second in the 6-to-1 compression-
ratio range.
Two recent developments in gas-turbine plants promise much for the future. The
first of these developments is the single-shaft combined-cycle gas and steam turbine,
Fig. 9. In this cycle, the gas turbine exhausts into a heat-recovery steam generator
(HRSG) that supplies steam to the turbine. This cycle is the most significant electric
generating system available today. Further, its capital costs are significantly lower
than competing nuclear, fossil-fired steam, and renewable-energy stations. Other
advantages include low air emissions, low water consumption, smaller space re-
quirements, and a reduced physical profile, Fig. 10. All these advantages are im-
portant in today’s strict permitting and siting processes.

FIGURE 8 With further gas-turbine cycle refinement, the specific fuel consumption declines.
These curves are based on assumed efficiencies with T3 ⫽ 1400 F (760 C).

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)


Copyright © 2006 The McGraw-Hill Companies. All rights reserved.
Any use is subject to the Terms of Use as given at the website.
MODERN POWER-PLANT CYCLES AND EQUIPMENT

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.17

Stack

Inlet air
Generator Gas turbine
H-p I-p L-p

L-p I-p H-p Synchronous HRSG


Steam turbine clutch
Fuel
FIGURE 9 Single-shaft combined-cycle technology can reduce costs and increase thermal effi-
ciency over multi-shaft arrangements. This concept is popular in Europe (Power).

68.5 ft (20.9 m)

(51.9 m)
170.6 ft

29.5 ft 95 ft
152 ft
(8.99 m) (46.33 m) (28.95 m)
FIGURE 10 Steam turbine, electric generator, and gas turbine fit into one compact building when
all three machines are arranged on a single shaft. Net result: Reduced site footprint and civil-
engineering work (Power).

Having the gas turbine, steam turbine, and generator all on one shaft simplifies
plant design and operation, and may lower first costs. When used for large reheat
cycles, as shown here, separate high-pressure (h-p), intermediate-pressure (i-p), and
low-pressure (l-p) turbine elements are all on the same shaft as the gas turbine and
generator. Modern high-technology combined-cycle single-shaft units deliver a
simple-cycle net efficiency of 38.5 percent for a combine-cycle net efficiency of
58 percent on a lower heating value (LHV) basis.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)


Copyright © 2006 The McGraw-Hill Companies. All rights reserved.
Any use is subject to the Terms of Use as given at the website.
MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.18 POWER GENERATION

The second important gas-turbine development worth noting is the dual-fueled


turbine located at the intersection of both gas and oil pipelines. Being able to use
either fuel gives the gas turbine greater opportunity to increase its economy by
switching to the lowest-cost fuel whenever necessary. Further developments along
these lines is expected in the future.
The data in the last three paragraphs and the two illustrations are from Power
magazine.

DETERMINING BEST-RELATIVE-VALUE OF
INDUSTRIAL GAS TURBINES USING A
LIFE-CYCLE COST MODEL

An industrial application requires a 21-MW continuous electrical output year-round.


Five different gas turbines are under consideration. Determine which of these five
turbines is the best choice, using a suitable life-cycle cost analysis.

Calculation Procedure:
1. Assemble the cost data for each gas turbine being considered
Assemble the cost data as shown below for each of the five gas turbines identified
by the letters A through E. Contact the gas-turbine manufacturers for the initial
cost, $ / kW, thermal efficiency, availability, fuel consumption, generator efficiency,
and maintenance cost, $ / kWh. List these data as shown below.
The loan period, years, will be the same for all the gas turbines being considered,
and is based on an equipment life-expectancy of 20 years. Interest rate on the capital
investment for each turbine will vary, depending on the amount invested and the
way in which the loan must be repaid and will be provided by the accounting
department of the firm considering gas-turbine purchase.
Equipment Attributes for Typical Candidates*

Gas-turbine candidates
Parameter A B C D E
Initial cost, $ / kW 205 320 275 320 200
Thermal efficiency, % 32.5 35.5 34.0 36.5 30.0
Loan period, yr 20 20 20 20 20
Availability 0.96 0.94 0.95 0.94 0.96
Fuel cost, $ / million Btu 4 4 4 4 4
Interes, % 6.5 8.0 7.0 8.5 7.5
Generator efficiency, % 98.0 98.5 98.5 98.0 98.5
Maintenance cost, $ / kWh 0.004 0.005 0.005 0.005 0.004
*Assuming an equipment life of 20 years, an output of 21 MW.

2. Select a life-cycle cost model for the gas turbines being considered
A popular and widely used life-cycle cost model for gas turbines has three parts:
(1) the annual investment cost, Cp ; (2) annual fuel cost, Cƒ; (3) annual maintenance
cost, Cm. Summing these three annual costs, all of which are expressed in mils /
kWh, gives CT , the life-cycle cost model. The equations for each of the three
components are given below, along with the life-cycle working model, CT :

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)


Copyright © 2006 The McGraw-Hill Companies. All rights reserved.
Any use is subject to the Terms of Use as given at the website.
MODERN POWER-PLANT CYCLES AND EQUIPMENT

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.19

The life-cycle cost model (CT ) consists of annual investment cost (Cp ) ⫹ annual
fuel cost (Cƒ) ⫹ annual maintenance cost (Cm ). Equations for these values are:
l {i / [1 ⫺ (1 ⫺ i )⫺n ]}
Cp ⫽
(A )(kW)(8760)(G )
where l ⫽ initial capital cost of equipment, dollars
i ⫽ interest rate
n ⫽ number of payment periods
A ⫽ availability (expressed as decimal)
kW ⫽ kilowatts of electricity produced
8760 ⫽ total hours in year
G ⫽ efficiency of electric generator
Cƒ ⫽ E(293)
where E ⫽ thermal efficiency of gas turbine
293 ⫽ conversion of Btu to kWh
Cm ⫽ M / kW
where M ⫽ maintenance cost, dollars per operating (fired) hour.
Thus, the life-cycle working model can be expressed as
l {i / [1 ⫺ (1 ⫺ i )⫺n ]}
CT ⫽ ⫹ F / E(293) ⫹ M / kW
(A )(kW)(8760)(G )
where F ⫽ fuel cost, dollars per million Btu (higher heating value)
To evaluate the comparative capital cost of a gas-turbine electrical generating
package the above model uses the capital-recovery factor technique. This approach
spreads the initial investment and interest costs for the repayment period into an
equal annual expense using the time value of money. The approach also allows for
the comparison of other periodic expenses, like fuel and maintenance costs.

3. Perform the computation for each of the gas turbines being considered
Using the compiled data shown above, compute the values for Cp, Cƒ, and Cm, and
sum the results. List for each of the units as shown below.

Results from Cost Model

Unit Mils / kWh produced


A 48.3
B 47.5
C 48.3
D 46.6
E 51.9

4. Analyze the findings of the life-cycle model


Note that the initial investment cost for the turbines being considered ranges be-
tween $200 and $320 / kW. On a $ / kW basis, only unit E at the $200 level, would
be considered. However, the life-cycle cost model, above, shows the cost per kWh

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)


Copyright © 2006 The McGraw-Hill Companies. All rights reserved.
Any use is subject to the Terms of Use as given at the website.
MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.20 POWER GENERATION

produced for each of the gas-turbine units being considered. This gives a much
different perspective of the units.
From a life-cycle standpoint, the choice of unit E over unit D would result in
an added expenditure of about $975,000 annually during the life span of the equip-
ment, found from [(51.9 ⫺ 46.6) / 1000](8760 hr / yr)(21,000 kW) ⫽ $974,988; this
was rounded to $975,000. Since the difference in the initial cost between units D
and E is $6,720,000 ⫺ $4,200,000 ⫽ $2,520,000, this cost difference will be re-
covered in $2,520,000 / 974,988 ⫽ 2.58 years, or about one-eighth of the 20-year
life span of the equipment.
Also, note that the 20-year differential in cost / kWh produced between units D
and E is equivalent to over 4.6 times the initial equipment cost of unit E. When
considering the values output of a life-cycle model, remember that such values are
only as valid as the data input. So take precautions to input both reasonable and
accurate data to the life-cycle cost model. Be careful in attempting to distinguish
model outputs that vary less than 0.5 mil from one another.
Since the predictions of this life-cycle cost model cannot be compared to actual
measurements at this time, a potential shortcoming of the model lies with the va-
lidity of the data and assumptions used for input. For this reason, the model is best
applied to establish comparisons to differentiate between several pieces of com-
peting equipment.
Related Calculations. The first gas turbines to enter industrial service in the
early 1950s represented a blend of steam-turbine and aerothermodynamic design.
In the late 1950s / early-1960s, lightweight industrial gas turbines derived directly
from aircraft engines were introduced into electric power generation, pipeline com-
pression, industrial power generation, and a variety of other applications. These
machines had performance characteristics similar to their steam-turbine counter-
parts, namely pressure ratios of about 12⬊1, firing temperatures of 1200–1500F
(649–816C), and thermal efficiencies in the 23–27 percent range.
In the 1970s, a new breed of aeroderivative gas turbines entered industrial ser-
vice. These units, with simple-cycle thermal efficiencies in the 32–37 percent
bracket, represented a new technological approach to aerothermodynamic design.
Today, these second-generation units are joined by hybrid designs that incor-
porate some of the aeroderivative design advances but still maintain the basic struc-
tural concepts of the heavy-frame machines. These hybrid units are not approaching
the simple-cycle thermal-efficiency levels reached by some of the early second-
generation aeroderivative units first earmarked for industrial use.
Traditionally, the major focus has been on first cost of industrial gas-turbine
units, not on operating cost. Experience with higher-technology equipment, how-
ever, reveals that a low first cost does not mean a lower total cost during the
expected life of the equipment. Conversely, reliable, high-quality equipment with
demonstrated availability will be remembered long after the emotional distress as-
sociated with high initial cost is forgotten.
The life-cycle cost model presented here uses 10 independent variables. A sin-
gle-point solution can easily be obtained, but multiple solutions require repeated
calculations. Although curves depicting simultaneous variations in all variables
would be difficult to interpret, simplified diagrams can be constructed to illustrate
the relative importance of different variables.
Thus, the simplified diagrams shown in Fig. 11, all plot production cost, mils /
kWh, versus investment cost. All the plots are based on continuous operation of
8760 h / yr at 21-MW capacity with an equipment life expectancy of 20 years.
The curves shown depict the variation in production cost of electricity as a
function of initial investment cost for various levels of thermal efficiency, loan

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)


Copyright © 2006 The McGraw-Hill Companies. All rights reserved.
Any use is subject to the Terms of Use as given at the website.

You might also like