TECHNICAL SUPPORT REPORT

COMBUSTION SYSTEM DATA


Part 2. Burner Conversion Surve
DISCLAIMER

This report was prepared as an account of work sponsored by an


agency of the United States Government. Neither the United States
Government nor any agency Thereof, nor any of their employees,
makes any warranty, express or implied, or assumes any legal
liability or responsibility for the accuracy, completeness, or
usefulness of any information, apparatus, product, or process
disclosed, or represents that its use would not infringe privately
owned rights. Reference herein to any specific commercial product,
process, or service by trade name, trademark, manufacturer, or
otherwise does not necessarily constitute or imply its endorsement,
recommendation, or favoring by the United States Government or any
agency thereof. The views and opinions of authors expressed herein
do not necessarily state or reflect those of the United States
Government or any agency thereof.
DISCLAIMER

Portions of this document may be illegible in


electronic image products. Images are produced
from the best available original document.
INDUSTRIAL MEDIUM-Btu FUEL GAS
DEMONSTRATION-PLANT PROGRAM

TECHNICAL SUPPORT REPORT: -


CQMBUSTIOM SYSTEM DATA .
Part 2. Burner Conversion Survey

Prepared for the

UNITED STATES DEPARTMENT OF ENERGY

Under Contract No. ET-77-C-01-2582

Submitted by
MEMPHIS LIGHT, GAS AND WATER DIVISION
P.O. Box 4 3 0
Memphis, Tennessee 38101

Prepared by
l nstitute of Gas Technology
IIT Center, 3 4 2 4 S. State Street
Chicago, Illinois 6 0 6 1 6

Date Published - ~ o v e m b e r1.979


- -
DISCLAIMER

,,

1
MEflPHIS INDUSTRIAL FUEL GAS
DEMONSTRATION PIANT PROJECT

TECHNICAL SUPPORT REPORT - PART 2


( ~ e l i v e r a b l e#46 )

NOTICE

!his r e p o r t was prepared as a a account o f work


sponsored by an agency o f t h e United S t a t e s
Government'. Neither t h e United S t a t e s nor any
agency t h e r e o f , nor any of t h e i r employees, makes
any warranty, expressed o r implied, o r assumes
any l e g a l l i a b i l i t y o r r e s p o n s i b i l i t y f o r any'
t h i r d p a r t y ' s use o r the. r e s u l t s o f such use o f
any information, apparatus, product o r process
disclosed i n t h i s r e p o r t , o r r e p r e s e n t s t h a t
i t s use by such t h i r d p a r t y would not i n f r i n g e
p r i v a t e l y owned r i g h t s . ...

MEMPHIS LIGHT, GAS & WATER DIVISION


P.O. Box 430
MEMPHIS , TENNESSEE38101

PREPARED FOR THE - .

U. S DEPARTMENT OF ENERGY , . .
TABLE O F CONTENTS
Page
I . INTRODUCTIO N 1

DISCUSSION

CONCLUSIONS

APPENDIX A. B u r n e r Inf o r m a t i o n

A P P E N D I X B. Survey Letter

APPENDIX C . Manufacturers ' R e p 1 i e s

iii

I N S T I T U T E 0 F G A S T E C H N O L O G Y
THIS PAGE
WAS INTENTIONALLY
LEFT BLANK
L I S T OF TABLES
T a b l e No.. Page
1 P r e l i m i n a r y L i s t of P r o s p e c t i v e Customers

2 Sample of Burner I n f o r m a t i o n Obtained From Survey

3 Burner M a n u f a c t u r e r s
I~TRODUCTION
The purpose of t h i s s u r v e y w a s t o - d e t e r m i n e t h e f e a s i b i l i t y of c o n v e r t i n g
t h e e x i s t i n g n a t u r a l g a s b u r n e r s of t h e proposed i n d u s t r i a l f u e l gas: (IFG)
customers t o u s e IFG. To do t h i s , a d d i t i o n a l d e t a i l e d i n f o r m a t i o n was
o b t a i n e d f o r e a c h , b u r n e r i n s t a l l a t i o n , and l e t t e r s were s e n t t o t h e manufac-
t u r e r s g i v i n g t h e p r o p e r t i e s of t h e IFG a n d ' r e q u e s t i n g t h e m a n u f a c t u r e r s '
recommendations r e g a r d i n g t h e , f e a s i b i l i t y of f i r i n g IFG and any m o d i f i c a t i o n s
necessary.

I N S T I T U T E 0 F G A S T E C H N O L O G Y
DISCUSSION

E i g h t - s i x . b u r n e r i n s t a l l a t i o n s were i d e n t i f i e d among t h e 22 customers


surveyed. Table 1 i s a l i s t .of t h e 24 p r o s p e c t i v e customers. A s noted,
D e l t a R e f i n i n g and Buckeye Ce:llulose were n o t i n c l u d e d because D e l t a h a s been
d i r e c t l y i n c o n t a c t w i t h t h e i r . b u r n e r m a n u f a c t u r e r s and Buckeye h a s been
t h e s u b j e c t of a s e p a r a t e p r e v i o u s s t u d y . .

Combustion Energy S e r v i c e s , I n c . , (CES) of Memphis, Tennessee; was sub'-


c0ntracte.d t o conduct t h e d e t a i l e d , o n - s i t e survey because t h e y were v e r y
f a m i l i a r w i t h many of t h e i n s t a l l a t i o n s . Table 2 i s a sample of t h e i n f o r -
mation o b t a i n e d f o r one of t h e b u r n e r i n s t a l l a t i o n s . Appendix A l i s t s a l l
of t h e i n f o r m a t i o n o b t a i n e d .

The 86 burner i n s t a l l a t i o n s i d e n t i f i e d were r e p r e s e n t e d by 19 manufac-


turers. These m a n u f a c t u r e r s a r e l i s t e d i n Table 3 . The m a n u f a c t u r e r s were
s e n t a l e t t e r d e s c r i b i n g t h e combustion p r o p e r t i e s of t h e IFG and r e q u e s t i n g
t h e i r recommendations. A copy of t h e l e t t e r s e n t t o t h e m a n u f a c t u r e r s
i s i n c l u d e d a s Appendix B.

Twelve of t h e m a n u f a c t u r e r s responded t o t h e l e t t e r . Those companies


r e s p o n d i n g corresponded t o 7 9 of t h e 86 i n s t a l l a t i o n s , o r b e t t e r t h a n 90%
response. The l e t t e r s of r e s p o n s e a r e i n c 1 u d c d . a ~Appendix C. Those n o t
r e s p o n d i n g have been asked t o send draw5ngs of t h e b u r n e r s t o s e e i f t h e i r
d e s i g n s a r e s i m i l a r t o t h o s e of companies t h a t have responded o r s i m i l a r t o
t h o s e s t u d i e d i n - o t h e r I n s t i t u t e of Gas Technology (IGT) t e s t s .

Of t h o s e responding, most of t h e m a n u f a c t u r e r s recommended t h a t e i t h e r


t h e b u r n e r s could a t p r e s e n t be f i r e d w i t h 'IFG o r o n l y minor m o d i f i c a t i o n s
would b e r e q u i r e d t o u s e IFG. I n . a l l c a s e s , t h e m o d i f i c a t i o n s involved
e n l a r g i n g t h e f u e l o r i f i c e s t o a l l o w f o r t h e i n c r e a s e d volumes of f u e l
required.

Two l a r g e b o i l e r m a n u f a c t u r e r s , Combustion E n g i n e e r i n g , I n c . , and Babcock


and Wilcox, I n c ., (B&W) would n o t , comment w i t h o u t conducting a n e n g i n e e r i n g
study. Such a s t u d y was done by B&W a t Memphis L i g h t , Gas and Water's (MLGW'S)
r e q u e s t f o r one of t h e b o i l e r s a t Buckeye C e l l u l o s e . The r e s u l t s of t h i s
s t u d y recommended t h a t t h e b o i l e r would o p e r a t e ~ a ~ t i s f a c t o r i b
l yu t t h a t
b u r n e r m o d i f i c a t i o n s would have t o b e made. During t h e same p e r i o d a s t h e ,
-

I N S ' T I T U T E 0 F G A S T E C H N O L O G Y
e n g i n e e r i n g s t u d y , B&W cooperated w i t h IGT by designed a s u b s c a l e n a t u r a l
g a s b u r n e r and a modified burner f o r IGT. Combustion t r i a l s w i t h t h i s equip-
ment, r e p o r t e d i n P a r t I. Combustion T r i a l s of t h i s r e p o r t , ' s h o w e d %lie
d i f f e r e n c e s and s i n i i l a r i t i e s . 'of t h e two f u e l s . h he t r i a l s a l s o ' g a t e i n £ orma-
t i o n needed f o r f u e l i n j e c t o r m o d i f i c a t i o n s f o r t h e IFG.

Baker-Perkins, Maxon, and North American Manufacturing f e l t t h a t some of


t h e i r b u r n e r s i n s t a l l e d i n t h e companies i n c l u d e d i n t h e survey could n o t b e
converted t o burn t h e IFG. Each of t h e s e companies f e l t t h a t t h e y , , c o u l d .
recommend a l t e r n a t i v e equipment t h a t could b e s u c c e s s f u l l y u t i l i z e d . North.
American Manufacturing a l s o i n d i c a t e d t h a t .some combustion t r i a l s would b e
required.
. .
'&.
. . . .

I N S T I T U T E 0 F. G A S T E C e H N O L O G Y

- -- - --
CONCLUSIONS

T h i s s t u d y was l i m i t e d t o a n a n a l y s i s o f t h e f e a s i b i l i t y o f b u r n i n g t h e
IFG , i n t h e e x i s t i n g b u r n e r s a n d combustion chambers among a g r o u p of p r o s p e c t i v e
IFG c u s t o m e r s . The r e s u l t s of t h i s s t u d y i n d i c a t e t h a t t h e g r e a t m a j o r i t y . o f
b u r n e r and equipment m a n u f a c t u r e r s recommend t h a t t h e IPG c a n b e u t i l i z e d w i t h
t h e i r equipment. ' T h i s i s e s p e c i a l l y t r u e w i t h t h e b o i l e r s which make up t h e
l a r g e s t p a r t of t h e l o a d 'among t h e p o t e n t i a l u s e r s of t h e ' IFG. A s m a l l .number
of b u r n e r s . r e p r e s e n t i n g a s m a l l p a r t ' o f t h e t o t a l p o t e n t i a l l o a d . w i l l p r o b a b l y
have t o b e r e p l a c e d .

T h i s s t u d y d i d n o t a d d r e s s t h e c h a n g e s t h a t would b e r e q u i r e d w i t h r e s p e c t
t o t h e f u e l d i s t r i b u t i o n p i p i n g w i t h i n each f a c i l i t y . At a minimum t h e
e x i s t i n g r e g u l a t o r s , flow meters,and c o n t r o l v a l v e s designed f o r t h e n a t u r a l
g a s f l o w r a t e s would h a v e t o b e r e p l a c e d t o accommodate t h e h i g h e r f u e l f l o w
r a t e s r e q u i r e d w i t h t h e IFG. I n many f a c i l i t i e s , t h e f u e l d i s t r i b u t i o n p i p i n g
would h a v e t o b e r e p l a c e d . No c h a n g e s , however, a r e r e q u i r e d f o r t h e
combustion a i r f a n s o r f l u e s and s t a c k s .

0 F\ G A, S ' T E C H N O L O G Y
Table 1. PRELIMINARY.LIST OF PROSPECTIVE CUSTOMERS

Memphis, Tenn.,
Street Address

1. Cargill, Inc., 1877 Channel

Nat Buring Packing Company 1837 Harbor

Humble-Exxon 454 .W. Wisconsin

Kroger 1029. Florida


c

Delta Refining Company 2255 Fisher

Refined Metal 304 W. Industrial

Conley Frog & Switch Company -362 E. Bodley

Wesson Foods 1351 Williams

Methodist Hospital 1265 Union

Sealtest Dairy 175 Walnut

Baptist Hospital 899 Madison

John Gaston Hospital 860 Madison

City of Memphis Hospital 951 Court

U. T. Hospital 842 Jefferson

LeBonheur Children's Hospital 848 Adams .

Veterans' Hospital 1030 Jefferson'

St. Joseph Hospital 254 Jackson

St. Jude Hospital 332 North Lauderdale

Buckman Lab 1256 N. McLean

Velsicol Chemical 1199 Warford

Humko Chemical . . 1231 Pope

Buckeye Cellulose 2782 Chelsea

Humko Chemical . 1238 Pope

Quaker Oats 3324 Chelsea

I N S T ' I T U T ' E 0 F. .G A S T E C H N O L O G Y
Table 2. SAMPLE OF'BURNER INFORMATION
OBTAINED FROM SURVEY

COMF'AhT Humko LOCATION 1231 Pope S t r e e t

DATE 7-10-79

BURNERS' ARE ON Dow Therm V a p o r i z e r (!I5 S t i l l ) . .

MANUFACTURER Eclipse

S I Z E OF UKIT BURfU'ER(S) ARE FIRING IK 5,009,000 Btu Output

HOW M Y BUIUI'ERS One

BURNER TYPE Spud

CAPACITY 6,000,000 Btu

MODEL AX-60

BURNER MANUFACTURER Ace E n g i n e e r i n g ~ o m ~ a n ~

SERIAL NUMBER 34337

FLA?IE SAFETY MAXUFACTURER H o n e y w e l l R4 140L101.4

TYPE OF COKTROL Manual - Positioning

COKTROL MASUFACTURER Hone\rwell

GAS PRESSLTE TO VALVE TRAIS lo." V.C.

GAS PRESSURE AT BURNER 6 . " W.C.

VALVE TRAIN MANUFACTLRER Honeywell

I N S T I T U T E 0 F G A S T E C H N O L O G Y
T a b l e 3. BURNER MANUFACTURERS

1. Baker-Perkins

2. Cleaver Brooks

3. Ace E n g i n e e r i n g

4. Barker ~ a n u f a c t u r i n gCo. , Inc.

5. Babcock and Wilcox, I n c .

6. The C. M. Kemp Manufacturing Co.

7. Coen Company

8. Combustion E n g i n e e r i n g , I n c . , ( I n c l u d e s Wickes)

9. Oswego Package B o i l e r Co., I n c .

10. E c l i p s e Combustion

11. I n d u s t r i a l Combustion, I n c .

12. John Zink Company

13. Maxon C o r p o r a t i o n

14. North American Manufacturing

15. Peabody Gordon-Piatt, Inc.

16. Ransome Gas I n d u s t r i e s , I n c .

17. Ray Burner Company

18. Webster Engineering .

19. B o i l e r E n g i n e e r i n g and Supply

I N S T I T U T E 0 F G A S T E C H N O L O G Y
APPENDIX A. Burner Information

I N S T I T U T E T E C H N O L O G Y
THIS PAGE
WAS INTENTIONALLY
LEFT BLANK
11/79

COMPANY Humko LOCATION 1231 Pope S t r e e t

DATE 7-10-79

BURNERS ARE ON Dow T h e m Vaporizer (/I5 Stil.1.)

MANUFACTURER Ec.lipse %

A
SIZE OF UNIT BURNER(S) ARE FIRING I N 5,000,000 Btu Output

HOW MANY BURNERS , One . .

BURNER TYPE - Spud

CAPACITY 6,000,000 Btu

MODEL AX-60

BURNER MANUFACTURER Ace E n g i n e e r i n g Company

SERIAL NUMBER 34337

FLAME SAFETY MANUFACTURER Honeywell R4140L1014

TYPE OF CONTROL Manual - Positioning

CONTROL MANUFACTURER Honeywell

GAS PRESSURE TO VALVE TRAIN 10." W.C.

GAS PRESSURE AT BURNER 6." W.C.

VALVE TRAIN MANUFACTURER Honeywell ., .

VALVE TRAIN SIZE 2"

A-3

I N S T I T U T E 0.F G A. S . T E C H N O L O G Y

- -~
COMPANY Kroger Bakery LOCATION 1029 F l o r i d a

DATE 8-16-79

BURNERS ARE ON Bread Oven DATE 1953 .

MANUFACTURER P e t e r s o n {IATO-434

SIZE OF UNIT BURNER(S) ARE FIRING I N --

.
HOW MANY BURNERS Three ,

BURNER TYPE Inspirator - Atmospheric -

CAPACITY 500,000 B t u Each

MODEL /I . .
--

BURNER MANUFACTURER Baker ; P e r k i n s I n c .

SERIAL NUMBER --

FLAME SAFETY MANUFACTURER B a r b e r Colman 1490-1

TYPE OF CONTROL E l e c t . Hi-Lo, Temp. C o n t r o l l e d

CONTROL MANUFACTURER Honeywell

GAS PRESSURE TO VALVE TRAIN 4'5 OZ'

GAS PRESSURE AT BURNER 4.0 02.

VALVE TRAIN MANUFACTURER


Maxon - Honeywell

2-112"
VALVE TRAIN S I Z E .

A-4 \

I N S T I T U T E O F : G A S T E C H N O L O G Y
COMPANY Krbger Bakery LOCATION 1029 Florida

f,
DATE 8-16-79

BURNERS ARE ON Bread Oven DATE 1953

MANUFACTURER Peterson

S I Z E OF U N I T BURNER(S) ARE F I. R. I N G IN-"-- --

HOW MANY BURNERS One

BURNER TYPE Atmos. Inspirator

CAPACITY 500,000 B t u

MODEL --

BURNER MANUFACTURER B a k e r P e r k i n s , Inc.

S E R I A L NUMBER --

FLAME SAFETY MANUFACTURER B a r b e r Colman

TYPE OF CONTROL E l e c t r i c Hi-Lo, Temp. O p e r a t e d

CONTROL MANUFACTURER Honeywell

GAS PRESSURE TO VALVE T R A I N 4. 02.

VALVE TRAIN MANUFACTURER E c l i p s e Gen. C o n t r o l s

VALVE T R A I N S I Z E 1-1/4"

A-5
I N S T 1 . T - U T E 0 F G A S T E C H N O L O G Y
COMPANY Methodist H o s p i t a l LOCATION 1265. Union

DATE 7-9-79 i

BURNERS ARE ON Incinerator . .


b

MANUFACTURER Pliblico
*-

S1ZE.W UNIT BURNER(S) ARE FIRING I N 2,650,000 O u ~ p u t .- A

HOW MANY BURNERS Three

BUKNER TYPE Gun


E
CAPACITY 3,450,000 I n p u t (Btu)
J.

MODEL # 1 each 1500 C 1


BURNER MANUFACTURER Barber Manufacturing Company

SERIAL NUMBER Not A v a i l a b l e

*-
&
FLAME SAFETY MANUFACTURER F i r e y e TFMID

TYPE OF CONTROL Manual I

CONTROL MANUFACTURER General C o n t r o l

GAS PRESSURE TO VALVE TRAIN 30" W.C.

I
GAS PRESSURE AT BURNER . 9 02. -.

J
VALVE TRAINMANUFACTURER General C o n t r o l

II
VALVETRAIN SIZE .- 1-1/4"

T E C H N O L O G Y
4
COMPANY Quaker O a t s LOCATION 2782,Chelsea

DATE 7-9-79

BURNERS ARE ON Steam Boiler

MANUFACTURER B&W

HOW MANY BURNERS One . .

BURNER TYPE Spud

CAPACITY 60,000,000 Btu

MODEL FM 1 7 8 5

. . BURNER. MANUFACTURER B&W .

S E R I A L NUMBER Not Available

FLAME SAFETY MANUFACTURER Fireye 26RJ8 6 0 0 9

TYPE OF CONTROL Auto - Metering

CONTROL MANUFACTURER Bailey

GAS PRESSURE TO VALVE TRAIN 8 lbs.

GAS PRESSURE AT BURNER 6 lbs.

VALVE -TRAIN MANUFACTURER Maxon

VALVE T R A I N S I Z E - 4"

I N S T I T U T E T E C H N O L O G Y
COMPANY N a t B u r i n g Packing LOCATION 1837 Harbor

DATE 8-16-7 9

BURNERS ARE ON Steam B o i l e r DATE 1976

MANUFACTURER Cleaver Brooks

SJZE OF U N I T BURNEK(S) ARE F I R I N G I N 250 H.F.

HOW MANY BURNERS One

BUKNER TYPE R jng

CAPACITY 10,461,000 Btu

MODEL CB-250 H P

BURNER MANUFACTURER Cleaver Brooks

S E R I A L NUMBER L-60087

FLAME SAFETY MANUFACTURER H o n e y w e l l R4140L1022-CB40

TYPE OF CONTROL Electric Positioning

CONTROL MANUFACTURER Honeywell

GAS PRESSURE TO VALVE TRAIN 10. 02.

GAS PRESSURE AT BURNER 4." W.C.

VALVE T R A I N MANUFACTURER Honeywell

VALVE TRAIN S I Z E 3"

A-8

I N S T I T U T E 0. F G A S T E C H N O L O G Y
11/79

COMPANY B a p t i s t . H o s p i t a l LOCATION 899 Madison

DATE 7-24-79

BURNERS ARE ON Steam B o i l e r (#4) DATE 1965

MANUFACTURER C l e a v e r Brooks

SIZE OF UNIT BURNER(S) ARE FIRING I N " 600. HP

HOW MANY BURNERS One

BURNER TYPE Ring

CAPACITY 25,106,000 Btu

MODEL CB-266-600

BURNER MANUFACTURER C l e a v e r Brooks

SERIAL NUMBER L-37951

FLAME SAFETY MANUFACTURER F i r e y e 2 6 ~ CB-1


~ 8

TYPE OF CONTROL Electric, Positioning

CONTROL MANUFACTURER Honeywell

GAS PRESSURE TO VALVE TRAIN , ,. 14. oz.

GAS.PRESSURE AT BURNER 2.00.z.

VALVE TRAIN MANUFACTURER General Controls

VALVE TRAIN SIZE 4"

I N S T I T U T E T E C H N O L O G Y
11/79

COMPANY Humko-Sheffield LOCATION 1 2 3 1 Pope S t r e e t .

DATE 7-io-79

BURNERS ARE ON 800# Steam B o i l e r - S a t . Stm. ( # 3 )

MANUFACTURER C l e a v e r Brooks

SIZE OF UNIT BURNER(S) ARE FIRING I N 12,000 P . P . B . A

HOW MANY BURNERS One

BURNER 'TYPE Ring

CAPACITY 16,630,000 Btu

MODEL WT 400X-8-3

BURNER MANUFACTURER C l e a v e r Brooks

SERIAL NUMBER WL-2188

FLAME SAFETY MANUFACTURER F i r e y e 26RJ8-6080

TYPE OF CONTROL Positioning - O7 Compensated, Auto

CONTROL MANUFACTURER Bailey

GAS PRESSURE TO VALVE TRAIN 30." W.C.

GAS PRESSURE AT BURNER 8." W.C.

VALVE TRAIN MANUFACTURER General C o n t r o l s

VALVE TRAIN SIZE 4"

I N S T I T U T E T E C H N O L O G Y
COMPANY John Gaston Hospital LOCATION 860 Madison.

DATE 7-24-79

BURNERS ARE ON Steam Boiler ( # 4 ) DATE 1963 .

MANUFACTURER Cleaver Brooks

SIZE OF UNIT BURNER(S) ARE FIRING IN'-"' 600 HP

HOW MANY BURNERS One

.BURNER TYPE Ring

CAPACITY 25,106,000 Btu

MODEL # CB-266-600

BURNER MANUFACTURER Cleaver Brooks

SERIAL NUMBER L-31459

FLAME SAFETY MANUFACTURER Fireye 26RJ8 CB-1

TYPE OF CONTROL Electric Positioning

CONTROL MANUFACTURER Honeywell

GAS PRESSURE TO VALVE TRAIN 16. oz.

GAS PRESSURE AT BURNER 2. 02.'

VALVE TRAIN MANUFACTURER General Controls

VALVE TRAIN SIZE 4"

I N S T I T U T E 0 F G A S T E C H N O L O G Y
COMPANY Lebonheur H o s p i t a l LOCATION 848 Adams

DATE 8-21-79

BURNERS ARE O N Steam B o i l e r

MANUFACTURER C l e a v e r Brooks

SIZE OF UNIT BURNER(S) ARE FIRING I N 1 5 U HP

HOW MANY BURNERS One

BURNER TYPE Ring

CAPACITY ---- 6,000,000 Btu

MODEL /I M4HP

BURNER MANUFACTURER C l e a v e r Brooks

SERIAL NUMBER --

FLAME. SAFETY MANUFACTURER Honeywell

TYPE OF CONTROL Auto. E l e c t r i c P o s i t i o n i n g

CONTROL MANUFACTURER Honeywell

GAS PRESSURE TO VALVE TRAIN 1 2 . " W.C.

GAS PRESSURE AT.BURNER 4." W.C.

VALVE TRAIN MANUFACTURER Honeywell

' /
VALVE TRAIN S I Z E 3"

(On o r d e r - d e l i v e r y November, 1979)


A

I N S T I T U T E 0 F G A S T E C H N O L O G Y
COMPANY Lebonheur Hospital LOCATION 848 A d a m s

DATE 8-21-79

BURNERS ARE ON S t e a m B o i l e r (ill) DATE 1972

MANUFACTURER Cleaver Brooks

S I Z E OF U N I T BURNER(S1 ARE F I R I N G I N 2 0 0 HP

>
HOW MANY BURNERS One

BURNER TYPE Ring

CAPACITY 8,369,000 Btu

MODEL CB-200-200

BURNER MANUFACTURER Cleaver Brooks

. ' S E R I A L NUMBER L-54312

FLAME SAFETY MANUFACTURER

TYPE OF CONTROL A u t o . E l e c t r i c Positioning

CONTROL MANUFACTURER Honeywell

GAS PRESSURE TO VALVE TRAIN 11." W.C.

GAS PRESSURE AT BURNER 3." W.C.

VALVE TRAIN MANUFACTURER General Controls

VALVE TRAIN S I Z E \> 3"

I N S T I T U T E 0 F G A S T E C H N O L O G Y
11/79
COMPANY Lebonheur H o s p i t a l LOCATION 8 4 8 Adams

DATE 8-21-79

BURNERS ARE ON S t e a m B o i l e r (#2) DATE 1972

MANUFACTURER Cleaver ,Brooks

HOW MANY BURNERS One

BURNER 'I'YP E Ring

CAPACITY 8,369,000 B t u

MODEL , CB 2 0 0 - 2 0 0

BURNER MANUFACTURER Cleaver Brooks

S E R I A L NUMBER L-54311

FLAME SAFETY MANUFACTURER H o n e y w e l l R4140L

TYPE OF CONTROL Auto. E l e c t r i c P o s i t i o n i n g

CONTROL MANUFACTURER Honeywell

GAS PRESSURE TO VALVE TRAIN 11." W.C.

GAS PRESSURE AT BURNER 3 . " W.C.

VALVE TRAIN MANUFACTURER General Controls

VALVE TRAIN S I Z E 3"

A-1 4

I N S T I T U T E 0 F G A S T E C H N O L O G Y
COMPANY Methodist H o s p i t a l LOCATION . 1265 Union

DATE 7-9-79

BURNERS ARE ON Steam B o i l e r (,115)

MANUFACTURER C l e a v e r Brooks

SIZE OF UNIT BURNER(S) ARE FIRING IN".-* -49,500 P.P.H.

HOW MANY BURNERS One

BURNER TYPE Ring

CAPACITY , 63,810,000 Btu

MODEL WL-2326

BURNER MANUFACTURER C l e a v e r Brooks

SERIAL NUMBER WT400X-CN3

FLAME SAFETY MANUFACTURER F i r e y e 26RJ8 CB3

TYPE OF CONTROL Auto - Positioning

CONTROL MANUFACTURER Hays

GAS PRESSURE TO VALVE TRAIN 2-1/2#

GAS PRESSURE AT BURNER 1{I

VALVE TRAIN MANUFACTURER Maxon

VALVE TRAIN SIZE 4"

0 F G A S T E C H N O L O G Y
.:
COMPANY S t . Jude H o s p i t a l ' LOCATION 3 3 2 N. L a u d e r d a l e

DATE 8-21-7 9

BURNERS ARE ON S t e a m B o i l e r (#2) DATE 1973

MANUFACTURER Cleaver 'Brooks

S I Z E OF l M I T BURNER(S) ARE F I R I N G I N 500 HP

HOW MANY BURNERS One

BURNEK TYPE Ring

CAPACITY 20,922,000 Btu

MODEL I CB-200-500

BURNER MANUFACTURER Cleaver Brooks

S E R I A L NUMBER L-56405

FLAME SAFETY MANUFACTURER H o n e y w e l l R 4 1 4 0 L CB40


.
TYPE OF CONTROL E l e c t r i c Auto. P o s i t i o n i n g

CONTROL MANUFACTURER Honeywell

GAS PRESSURE TO VALVE TRAIN 22." W.C.

GAS PRESSURE AT BURNER 3.5" W.C.

VALVE TRAIN MANUFACTURER General Controls

VALVE TRAIN S I Z E 4"

I N S T I T U T E O F . G A S T E C H N O L O G Y
11/79

COMPANY St. Jude Hospital LOCATION 332 N. L a u d e r d a l e

DATE 8-21-79

BURNERS ARE ON S t e a m B o i l e r (ill) DATE 1,973,

MANUFACTURER Cleaver Brooks

S I Z E OF UNIT BURNER(S) ARE FIRING IN---.- 5 0 0 HP . . .

HOW MANY BURNERS - One

BURNER TYPE Ring

CAPACITY 20,922,000 Btu

MODEL CB-200-500

BURNER MANUFACTURER Cleaver Brooks

SERIAL NUMBER L-56404

FLAME SAFETY MANUFACTURER H o n e y w e l l R4140L CB40

TYPE OF CONTROL E l e c t r i c P o s i t i o n i n g Auto.

CONTROL MANUFACTURER Honeywell

GAS PRESSURE TO VALVE TRAIN 22." W.C.

GAS PRESSURE AT BURNER 4 . " W.C.

VALVE TRAIN MANUFACTURER General Controls

VALVE TRAIN S I Z E 4"

I N S T I T U T E
COMPANY HumkO LOCATION 1 2 3 1 Pope S t r e e t

DATE 7-10-79

BURNERS ARE ON Nitrogen Generator

MANUFACTURER CM Kemp

S I Z E OF U N I T RURNER(S) ARE F I R I N G I N - ,
50,008 CFH - Nitrogen

HOW MANY BURNERS One - Inert G a s - Nitrogen

BURNER TYPE - Premix

CAPACITY 5,860,000 B t u

MODEL PH-50

BURNER MANUFACTURER CM Kemp

S E R I A L NUMBER 2-1.399-1

FLAME SAFETY MANUFACTURER Honeywell

TYPE OF CONTROL Auto - P r e m i x , C o n t r o l l e d by Press.

CONTROL MANUFACTURER North American

GAS PRESSURE TO VALVE TRAIN 2.25#

GAS PRESSURE AT BURNER 54." W.C.

VALVE TRAIN MANUFACTURER Eclipse

VALVETRAIN S I Z E . 3"

I N S T I T U T E T E C H N O L O G Y
11/79

COMPANY Buckman Lab LOCATION 1256 N. McLean

DATE 7-26-79

BURNERS ARE ON Steam Boiler DATE 1968

MANUFACTURER Fost er-Wheeler

SIZE OF UNIT BURNER(S1 ARE FIRING IN 50,000 P.P.H. Sat.

HOW MANY BURNERS One

BURNER TYPE Ring

CAPACITY 65,000,000 Btu

MODEL # DAZ-25

BURNER MANUFACTURER Coen

SERIAL NUMBER D-3123

n A M E SAFETY MANUFACTURER Honeywell

TYPE OF CONTROL Electric Positioning

CONTROL MANUFACTURER Honeywell

GAS PRESSURE TO VALVE TRAIN 10. Psig

GAS PRESSURE AT BURNER 4 .O Psig

VALVE TRAIN MANUFACTURER General Controls

VALVE TRAIN SIZE 3"

I N. S T I T U T ' E
COMPANY Buckman Lab LOCATION 1256 N. McLean

DATE 7-26-79

BURNERS ARE ON Steam Boiler DATE 1975

MANUFACTURER Comb. Eng.

SIZE OF UNIT BURNER(S) ARE FIRING IN 50,800 P.P.H. Sat.

HOW MANY BURNERS One

BUKNER TYPE Ring

CAPACITY 65,000,000 Btu

MODEL DAZ-25

BURNER MANUFACTURER Coen

SERIAL NUMBER D-6462

F'LAME SAFETY MANUFACTURER Honeywell

TYPE OF CONTROL Electric Positioning

CONTROL MANUFACTURER Honeywell

GAS PRESSURE TO VALVE TRAIN 15. Psig

GAS PRESSURE AT BURNER 3.6 Psig

VALVE TRAIN MANUFACTURER Maxon

VALVE TRAIN SIZE 3"


11/79

COMPANY Cargill, Inc. LOCATION 1877 Channel

DATE 7-10-79

BURNERS ARE ON Steam B o i l e r

MANUFACTURER Murray I r o n Works

SIZE UNIT BURNER (S) ARE FIRING : 110.000 P.P.H.

HOW MANY BURNERS One .

BURNER TYPE Ring

CAPACITY 135,000,000 Btu

MODEL /I DA-Z

BURNER MANUFACTURER Coen

SERIAL NUMBER D4345

SAFETY MANUFACTURER Fireve

TYPE OF CONTROL Auto. P o s i t i o n i n g

CONTROL MANUFACTURER Bailey

GAS PRESSURE TO VALVE TRAIN , . .7 /I

GAS PRESSURE AT BURNER 5#

VALVE TRAIN MANUFACTURER Eclipse


A>

VALVE TRAIN SIZE 6"

I N S T I T U T E
COMPANY Humko-Sheffield LOCATION 1231 Pope S t r e e t

DATE ' 7-10-79

BURNERS ARE ON S t e a m B o i l e r (ii6)

MANUFACTURER Union I r o n Works

S I Z E OF UNIT BURNER(S) ARE FIRING I N 1 2 5 , 0 0 0 P.P.H. Sat. Steam

HOW MANY BURNERS One

BURNER TYPE. Ring

CAPACITY 150,000,000 Btu

MODEL DA-Z

BURNER MANUFACTURER Coen

SERIAL NUMBER D-3436

FLAME SAFETY MANUFACTURER Fireye

TYPE OF CONTROL Metering

CONTROL MANUFACTURER Bailey

GAS PRESSURE TO VALVE TRAIN 15i/

GAS PRESSURE AT BURNER 5/I

VALVE TRAIN MANUFACTURER Maxon

VALVE TRAIN S I Z E 4"

I N S T I T U T E 0 F G A S T E C H N O L O G Y
COMPANY Humko-Sheffield LOCATION 1231 Pope Street

DATE 7-10-79

. BURNERS ARE ON Steam Boiler (#6)

MANUFACTURER Union Iron Works

SIZE OF UNIT BURNER(S) ARE FIRING IN - 125,000 P.P.H..Sat. Steam

HOW MANY BURNERS One

BURNER TYPE Ring

CAPACITY 150,000,000 Btu

MODEL W DA-Z

BURNER MANUFACTURER Coen

SERIAL NUMBER D-3436

FL,@lESAFETY MANUFACTURER Fireye

TYPE OF CONTROL Metering

CONTROL MANUFACTURER Bailey .

GAS PRESSURE TO VALVE TRATN l5#

GAS PRESSURE AT BURNER 5

VALVE TRAIN MANUFACTURER . Maxon

VALVE TRAIN SIZE 4"


COMPANY U. T. H o s p i t a l LOCATION 842 J e f f e r s o n

DATE 8-20-79
,

BURNERS ARE ON Steam B o i l e r DATE 1962

MANUFACTURER Wickes
*

S I Z E OF UNIT RIJRNER(S) ARE FIRING I N -- 15,000 l b s . p e r hr.

HOW MANY BURNERS One

BURNER TYPE -. Ring

CAPACITY 18,700,000

MODEL d BF 1 6 . 5

BURNER MANUFACTURER Coen I


SERIAL NUMBER --

FLAME SAFETY MANUFACTURER E d i s o n Model 4 2 1

TYPE OF CONTROL Auto Metering

CONTROL MANUFACTURER Hays

GAS PRESSURE TO VALVE TRAIN 7 lbs.

GAS PRESSURE AT BURNER 4 lbs.

VALVE TRAIN MANUFACTURER General Control

VALVE TRAIN S I Z E 2"

A-24

I N S T I T U T E 0 F G A S T E C H N O L O G Y
COMPANY U. T. H o s p i t a l LOCATION 842 J e f f e r s o n

DATE 8-20-79

BURNERS ARE ON - Steam B o i l e r DATE 1.962

MANUFACTURER Wickes .

SIZE OF UNIT BURNER(S)ARE FIRING IN 15,000 l b s . p e r h r .

HOW MANY BURNERS One

BURNER TYPE Ring

CAPACITY 18,700,000

MODEL // BF 1 6 . 5

BURNER MANUFACTURER Co e n

SERIAL NUMBER --

nAME SAFETY MANUFACTURER E d i s o n Model 421

TYPE OF CONTROL Auto M e t e r i n g

CONTROL MANUFACTURER Hays . .

GAS PRESSURE TO VALVE TRAIN 7 lbs.

GAS PRESSURE AT BURNER 4 lbs.

VALVE TRAIN MANUFACTURER General Controls

VALVE TRAIN SIZE 2"

. ,

T E C H N O L O G Y
11/79

COMPANY Quaker Oats LOCATION 2782 C h e l s e a

DATE 7-9-79

BURNERS ARE ON Steam B o i l e r

MANUFACTURER CE W-50

SIZE OF ITNIT BURNER(S) ARE FIRING I N I5U,UUU r . r . d . Sup. H L ~ .

HOW MANY BURNERS Four

BURNER TYPE Gun

CAPACITY 59,250,000 Btu Each

MODEL RO

BURNER MANUFACTURER Combustion E n g i n e e r i n g , .

SERIAL NUMBER None

FLAME SAFETY MANUFACTURER None on Gas

TYPE OF CONTROL M e t e r i n g Auto

CONTROL MANUFACTURER Republic

GAS PRESSURE TO VALVE TRAIN . 34 P s i g

GAS PRESSURE AT BURNER 10 Psig

VALVE TRAIN MANUFACTURER. --

VALVE TRAIN SIZE , 6"


( B u r n e r s a r e d e s i g n e d f o r 40% extra c a p a c i t y f o r d r y i n g p u r p o s e s . )

I N S T I T U T E T E ' C H ' N O L O G Y
11/ 7 9

COMPANY V e l s i c o l Chemical LOCATION 1199 Warford

DATE. 7-11-79

BURNERS ARE ON Steam B o i l e r (.1/5)

MANUFACTURER Combustion E n g i n e e r i n g

SIZE OF UNIT BURNER(S) ARE FIRING I N 75,000 P.P.H. Sup. Htd.

HOW MANY BURNERS One

BURNER TYPE Spud

CAPACITY 101,500,000 B t u
. .

D
MODEL d WDOG-26/24-1/2

BURNER MANUFACTURER Combustion E n g i n e e r i n g

SERIAL NUMBER
--

FLAME SAFETY MANUFACTURER Fireye

TYPE OF CONTROL '


Auto. M e t e r i n g

CONTROL MANUFACTURER Bailey

GAS PRESSURE TO VALVE TRAIN 30. P s i g

GAS PRESSURE AT BURNER 7. Psig

VALVE TRAIN MANUFACTURER Maxon

VALVE TRAIN SIZE 4"

A-27

I N S T I T U T E 0 F G A S T E C H N O L O G Y
11/ 7 9

COMPANY Sealtest-Kraft, Inc. LOCATION 1 7 5 Walnut

DATE 8-21-79

BURNERS ARE ON S t e a m B o i l e r (#I) DATE 1952

MANUFACTURER Cyclotherm

S I Z E OF U N I T BURNER(S1 ARE F I R I N G I N 6,90U Y.P.H. Sat.

HOW MANY BURNERS One

BURNER TYPE N o z z l e Mix --


CAPACITY 8,970,000 Btu

MODEL --

BURNER MANUFACTURER Cyclotherm

S E R I A L NUMBER C-7000

FLAME SAFETY MANUFACTURER Honeywell

TYPE OF CONTROL Auto. E l e c t r i c P o s i t i o n i n g

CONTROL MANUFACTURER Honeywell

GAS PRESSURE TO VALVE TRAIN 1 4 . " W.C.

GAS PRESSURE AT BURNER 3." W.C.

VALVE TRAIN MANUFACTURER Honeywell - General Controls

VALVE TRAIN S I Z E 3"

I N S T I T U T E T E C H N O L O G Y
COMPANY Sealtest-Kraft, Inc. LOCATION 175 Walnut

DATE 8-21-79

BURNERS ARE ON Steam Boiler (#2) DATE 1952

MANUFACTURER Cyclotherm

SIZE OF UNIT BURNER(S) ARE FIRING IN 6,900 P.P.H. Sat.

HOW MANY BURNERS One

BURNER TYPE Nozzle Mix

CAPACITY a 8,970,000 Btu

MODEL // C-7000

BURNER MANUFACTURER Cyclotherm

SERIAL NUMBER --

FLAME SAFETY MANUFACTURER Honeywell

TYPE OF CONTROL Auto. Electric Positioning

CONTROL MANUFACTURER Honeywell

GAS PRESSURE TO VALVE TRAIN 21." W.C.

GAS PRESSURE AT BURNER 4." W.C.

VALVE TRAIN MANUFACTURER General Controls

VALVE .TRAIN SIZE . 311

A-29
I N S T I T U T E 0 F G A S T E C H N O L O G Y
COMPANY Conley-Frog & SW LOCATION ..362E. Bodley

DATE 8-17-79

BURNERS ARE ON Forge Furnace (ill) DATE 1975

MANUFACTURER --

STZE OF UNIT BURNER(S) ARE FIRING IN -- 3'x~'xti'-

HOW MANY BURNERS Four

BURNER TYPE Nozzle Mix

CAPACITY 2,000,000 Btu Eac:h

MODEL /! 126 HCFG

BURNER MANUFACTURER Eclipse

SERIAL NUMBER -- 3'X3'X6'

FLAME SAFETY MANUFACTURER None

TYPE OF CONTROL Auto. Temp. Operated, Proportioning

CONTROL MANUFACTURER Barber Colman

-
GAS PRESSURE TO VALVE TRAIN 1.OPsig .

GAS PRESSURE AT BURNER 2." W.C.

VALVE TRAIN MANUFACTURER Eclipse

. VALVE TRAIN SIZE 3"

A-30
I N S T I T U T E 0 F. G A S
11/79

COMPANY Conley Grog & SW LOCATION 362 E. Bodley

DATE 8-17-79

BURNERS ARE ON Forge Furnace (#2) DATE 1975

MANUFACTURER --

SIZE OF UNIT BURNER(S) ARE FIRING IN 3 O"X4 O"X7 2"

HOW MANY BURNERS Four

BURNER TYPE Nozzle Mix

CAPAC173' 2,230,000 Btu Each

MODEL 126HCFG

a BURNER MANUFACTURER Eclipse

SERIAL NUMBER --

FLAME SAFETY MANUFACTURER None

U
TYPE OF CONTROL Electric, Proportioning, Temp. Auto.

CONTROL MANUFACTURER Barber Colman

GAS PRESSURE TO VALVE TRAIN 12. oz.

GAS PRESSURE AT BURNER 2." W.C.

VALVE TRAIN MANUFACTURER --

VALVE TRAIN SIZE 3"

T E C H N O L O G Y

-
COMPANY Conley Frog & SW LOCATION 362 E. Bodley .

DATE 8-17-79

BURNERS ARE ON Forge Furnace (#3) DATE 1975

MANUFACTURER --

SIZE 'IT BURNER (S) ARE FIRING

HOW MANY BURNERS Four

BUKNEK TYPE Nozzle Mix

CAPAC 1 , 0 0 0 , 0 0 0 Btu Each

MODEL /i 1 2 6 HCFG

BURNER MANUFACTURER

SERIAL NUMBER --

nAME SAFETY MANUFACTURER None

TYPE OF CONTROL E l e c t r i c , Auto., Temp. Op. P r o p o r t i o n i n g

CONTROL MANUFACTURER B a r b e r Colman

GAS PRESSURE TO VALVE TRAIN 12. 02.

GAS PRESSURE AT BURNER 2." W.C.

VALVE TRAIN MANUFACTURER --

VALVE TRAIN SIZE 3"

T E - C H N O L O G Y
COMPANY Conley F r o g & SW LOCATION 362 E. Bodley

f DATE 8-17-79

BURNERS ARE ON Forge Furnace (#4) DATE 1975

MANUFACTURER --

SIZE OF UNIT BURNER(S) ARE FIRING I N --

HOW MANY BURNERS Two

BURNER TYPE Nozzle Mix

CAPAC I TY 1.400.000 Btu Each

MODEL /I 126 HCFG

BURNER MANUFACTURER Eclipse

SERIAL NUMBER --

n A M E SAFETY MANUFACTURER None

TYPE OF CONTROL A u t o . , Temp. Opr. E l e c t r i c P r o p o r t i o n i n g

CONTROL MANUFACTURER B a r b e r Colman

GAS PRESSURE TO VALVE TRAIN 12. -o z. .

GAS PRESSURE AT BURNER 2." W.C.

VALVE TRAIN MANUFACTURER --

VALVE TRAIN SIZE 3"

I N S T I T U T E O F G A S T E C H N O L O G Y
. . .
11/79

COMPANY Conley Frog & SW LOCATION ' 3 6 2 E. Bodley

DATE 8-17-79

BURNERS ARE ON F o r g e F u r n a c e (#6) DATE 1975

MANUFACTURER --

SIZE OF UNIT BURNER(S)ARE FIRING IN --

HOW MANY BURNERS Four

BURNER TYPE Nozzle Mix

CAPACITY 1 , 0 0 0 , 0 0 0 Btu Each

MODEL 1 2 6 HCFG

BURNER MANUFACTURER Eclipse

SERIAL NUMBER --

FLAME SAFETY MANUFACTURER None

TYPE OF CONTROL Auto. E l e c t r i c Temp. Opr. P r o p o r t i o n i n g

CONTROL MANUFACTURER B a r b e r Colman

GAS PRESSURE TO VALVE TRAIN 12. 02.

GAS PRESSURE AT BURNER 2." W.C.

VALVE TRAIN MANUFACTURER --

VALVE TRAIN SIZE 3"

I N S T I T U T E T E C H N O L O G Y
11/79

COMPANY Conley Frog & SW LOCATION 362 E. Bodley

DATE 8-17-79

BURNERS ARE ON Forge Furnace (#5) DATE 1975 . .

--.
MANUFACTURER

SIZE OF UNIT BURNER(S) ARE FIRING IN . --

HOW MANY BURNERS Four

BURNER TYPE . Nozzle Mix

CAPACITY 1,000,000 Btu Each

MODEL # 126 HCFG

BURNER MANUFACTURER Eclipse

SERIAL'NUMBER --

FLAME SAFETY MANUFACTURER None

TYPE OF CONTROL . Auto. Temp. Opr. Electric Proportioning


. .

CONTROL MANUFACTURER Barber Colman

GAS PRESSURE TO VALVE TRAIN 12. oz.

GAS PRESSURE AT BURNER 2." W.C.

VALVE TRAIN MANUFACTURER --

VALVE TRAIN SIZE 3"

0 F G A S T E C H N O L O G Y

- 1 - -
COMPANY C o n l e y F r o g & SW LOCATION 362 E. B o d l e y

DATE . 8-17-79

BURNERS ARE ON R a i l ( F o r g e ) F u r n a c e DATE 1950

MANUFACTURER --

S I Z E OF UNIT BURNER(S) ARE FIRING IN 2'XZ1X6'

HOW MANY BURNERS Two

BUKNER TYPE N o z z l e Mjx

CAPACITY 875,000 Btu Each

MODEL TA

BURNER MANUFACTURER ' Eclipse

SERIAL NUMBER --

FLAME SAFETY MANUFACTURER None

TYPE OF CONTROL Manual P r o p o r t i o n i n g

CONTROL IQlNUFACTURER --

GAS PRESSURE TO VALVE TRAIN 8. 02.

GAS PRESSURE AT BURNER 3 . l ' W.C.

VALVE TRAIN MANUFACTURER --

VALVE TRAIN S I Z E 3 I'

A-36

I N S T I T U T E O F G A S T E C H N O L O G Y
11/79

COMPANY Conley Frog & SW LOCATION 362 E. Bodley

DATE 8-17-7 9

DATE 1974
BURNERS ARE ON . . F o r g e .Furnace ("Blacksmith Furnace")

MANUFACTURER --

SIZE OFUNIT BURNER(S) ARE FIRING I N 2'X4'X6' . .

HOW MANY BURNERS Four

BURNER TYPE Nozzle Mix .

CAPACITY 850,000 Btu Each

MODEL 1 2 6 HCFG
. .

BURNE Eclipse

SERIAL NUMBER --
. .

FLAME SAFETY MANUFACTURER None

TYPE OF CONTROL . .. Manual P r o p o r t i o n i n g

CONTROL MANUFACTURER --

. GAS PRESSURE TO VALVE TRAIN 24." W.C.

GAS PRESSURE AT BURNER 2." W.C.

VALVE TRAIN MANUFACTURER --


. .

VALVE TRAIN SIZE 2"

T E C H N O L O G Y
11/79

COMPANY Conley Frog & SW LOCATION 362' E. Bodley

. DATE 8-17-79

DATE 1959
BURNERS ARE ON S l o t (Forge) Furnace (!I3 S l o t Furnace)

MANUFACTURER --

SIZE OF UNIT BURNER(S) ARE FIRING I N 2'X2'X4'

HOW MANY BURNERS Two

BURNER TYFE Nozzle Mix

CAPACITY 850,000 Btu Each

MODEL !I TA

BURNER MANUFACTURER Eclipse

SER1A.L.NUMBER --

FLAME SAFETY MANUFACTURER None

TYPE OF CONTROL Manual P r o p o r t i o n i n g

CONTROL MANUFACTURER --

GAS PRESSURE TO VALVE TRAIN 16. .oz.

GAS PRESSURE AT BURNER . 7." W.C.

VALVE TRAIN MANUFACTURER .


--

VALVE TRAIN SIZE 3"

A-38

I N S T I T U T E 0 F' G A S T ' E C H N O L O G Y
COmANY Conley Frog 6 SW , LOCATION 362 E* Bodley

DATE 8-17-79

DATE 1960
BURNERS ARE ON S l o t (Forge) F u r n a c e (!I2 S l o t Furnace)

MANUFACTURER --

SIZE UNIT BURNER (S) ARE FIRING

HOW MANY BURNERS Two

BURNER TYPE Nozzle Mix

CAPACITY 1 , 0 0 0 , 0 0 0 Btu Each

MODEL TA

BURNER MANUFACTURER Eclipse

SERIAL NUMBER --

FLAME SAFETY MANUFACTURER None

TYPE OF CONTROL Manual - Proportioning

CONTROL MANUFACTURER --

GAS PRESSWE TO VALVE TRAIN 10. 02.

GAS PRESSURE AT BURNER 4." W.C. , .

. .

VALVE TRAIN MANUFACTURER


--

VALVE TRAIN SIZE . . 4"

A-39

0 F G A S
COMPANY C o n l e y F r o g & SW , LOCATION 3 6 2 E. B o d l e y

DATE 8-17-79

DATE 1 9 6 0
BURNERS ARE ON S l o t ( F o r g e ) F u r n a c e (/I1S l o t F--u-r n a c e )

MANUFACTURER --

S I Z E OF UNIT BURNER(S) ARE FIRING I N 2'X2'X4' .--

HOW MANY BURNERS Two

BURNER TYPE __- N o z z l e Mix

CAPACITY 1,000,000 Btu Each

MODEL /I TA

BURNER MANUFACTURER Eclipse

SERIAL NUMBER -- . .-

FLAME SAFETY MANUFACTURER None

TYPE OF CONTROL Manual - P r o p o r t i o n i n g

CONTROL MANUFACTURER --

GAS PRESSURE TO VALVE TRAIN 10. 02.

GAS PRESSURE AT BURNER 5." W.C.

VALVE TRAIN MANUFACTURER .


--

VALVE. TRAIN S I Z E 4"

I N S T I T U T E T E C H N O L O G Y
COMPANY Con1 p y Frog Q GW LOCATION 362 E. Bodley

DATE 8-17-79 '

BURNERS ARE ON Forge Furnace (#9) DATE 1975

MANUFACTURER Plibrico ..

SIZE OF UNIT BURNER(S) ARE FIRING I N 3'X6'X6'

HOW MANY BURNERS Four

BURNER TYPE Nozzle Mix

CAPACITY 1 , 9 0 0 , 0 0 0 Btu Each

MODEL 126 HCFG

BURNER MANUFACTURER Eclipse

SERIAL NUMBER --

FLAME SAFETY MANUFACTURER None

TYPE OF CONTROL Auto. E l e c t r i c Temp. Cont. P r o p o r t i o n i n g

CONTROL MANUFACTURER B a r b e r Colman

GAS PRESSURE TO VALVE TRAIN 20." W.C.

GAS PRESSURE AT BURNER 2." W.C.

VALVE TRAIN MANUFACTURER --

VALVE TRAIN SIZE 3"

A-4 1

. I N S T I T U T E O'F G A S T E C H N O L O G Y
11/79

COMPANY Conley Frog & SW LOCATION 362 E. Bodley

DATE + 8-17-79

BURNERS ARE ON Forge' F u r n a c e (il8) DATE 1975

MANUFACTURER Plibrico

SIZE OF UNIT RIJRNER(S) AKE FIRING I N --

HOW MANY BURNERS Two. . -.

BURNER TYPE Nozzlc Mix

CAPACITY 1 , 4 0 0 , 0 0 0 Btu Each

MODEL 126 HCFG

BURNER MANUFACTURER Eclipse

SERIAL NUMBER --

FLAME SAFETY MANUFACTURER None

TYPE OF CONTROL Auto. E l e c t r i c Temp. Cont. P r o p o r t i o n i n g

CONTROL MANUFACTURER B a r b e r Colman

GAS PRESSURE TO VALVE TRAIN 16." W.C.

GAS PRESSURE AT BURNER 2." W.C.

VALVE TRAIN MANUFACTURER --

VALVE TRAIN SIZE 3"

A-42

I N S T I T U T E 0 F G A S T E C H N O L O G Y

- - - - - -- - ---
COMPANY Conley Frog & SW LOCATION 362 E* Bodley

DATE 8-1.7-79

BURNERS ARE ON 1 Forge urnac ace (#7) CATE 1975

MANUFACTURER --,

SIZE OF UNIT BURNER(S) ARE FIRING IN --

HOW MANY BURNERS Four

BURNER TYPE Nozzle Mix

CAPACITY 1,900,000 Btu Each

MODEL !/ 126 HCFG -

BURNER MANUFACTURER Eclipse - .

SERIAL NUMBER --

FLAME SAFETY MANUFACTURER None

TYPE OF CONTROL Auto. Temp. Opr. Electric Proportioning ,

CONTROL MANUFACTURER Barber Colman

GAS PRESSURE TO VALVE TRAIN 16." W.C.

.GAS PRESSURE AT .BURNER 2." W.C..

VALVE TRAIN MANUFACTURER --

%
-..
VALVE TRAIN SIZE 3"

A-4 3

I N S T I T U T E ' 0. F G A S T E C H N O L O G Y

- - -
COMPANY kmko LOCATION 1231' Pope S t r e e t

DATE 7-10-79

Therminol H e a t e r - Liquid Phase


BURNERS ARE ON (600-700 S t i l l )

MANUFACTURER Eclipse

SIZE OF UNIT RURNER(S)ARE FIRING IN 4 , 2 0 0 , 0 0 0 Btu Output

HOW MANY BURNERS One

BURNER TYPE King

CAPACITY 6,216,000 Btu

MODEL d PR-B

BURNER MANUFACTURER . Eclipse

SERIAL NUMBER 700

FLAME SAFETY MANUFACTURER Honeywell

TYPE OF CONTROL P o s i t i o n i n g , Manual


C

CONTROL MANUFACTURER Honeywell

GAS PRESSURE TO VALVE TRAIN 2.511

GAS PRESSURE AT BURNER 6." W.C.

VALVE TRAIN MANUFACTURER Honeywell

VALVE TRAIN SIZE . . 2"

A-4 4

I N S T I T U T E 0 F G A S T E C H N O L O G Y
. 11/79
COMPANY Humko-Sheffield LOCATION 1231 Pope Street

DATE 7-10-79

BURNERS ARE ON . Dow Therm Vapor (/I6 Still)

MANUFACTURER Eclipse . .

SIZE OF UNIT BURNER(S) ARE FIRING IN 7,000,000.Bt.u Output

HOW MANY BURNERS One

BURNER TYPE Ring

CAPACITY 10,000,000

MODEL /I PR-C

BURNER MANUFACTURER Eclipse

SERIAL NUMBER 396

F U M E SAFETY MANUFACTURER. Honeywell R4126A1073

TYPE OF CONTROL Positioning - Manual

CONTROL MANUFACTURER Honeywell

GAS PRESSURE TO VALVE TRAIN 16 02.

GAS,PRESSUREAT BURNER 2." W.C.

VALVE TRAIN MANUFACTURER Eclipse

VALVE TRAIN SIZE 3"

I N S T I T U T E T E C H N O L O G Y
COMPANY John Gaston Hospital LOCATION 860 Madison

DATE 7-24-79

BURNERS ARE' ON Steam Boiler (#2) DATE 1978

MANUFACTURER Titusville

SIZE OF UNIT BURNER(S) ARE FIRING IN 20,000 P.P.H. Sat

HOW MANY BURNERS One

BURNER TYPE --. Ring

CAPACITY 25,200,000 Btu

MODEL /I DLG-252s

BURNER MANUFACTURER Industrial Combustion

SERIAL NUMBER L-6993

FLAME SAFETY MANUFACTURER Fireye 26CF6

TYPE OF CONTROL Electric Positioning

CONTROL MANUFACTURER Honeywell

GAS PRESSURE TO VALVE TRAIN 17.0 Psig

GAS PRESSURE AT BURNER 2.0 Psig

VALVE TRAIN MANUFACTURER Honeywell

VALVE TRAIN SIZE 3"

I N S T I T U T E T E C H N O L O G Y
COMPANY J o h n Gaston H o s p i t a l LOCATION ' 860 M a d i s u l ~ .

DATE 7-24-79

BURNERS ARE ON Steam B o i l e r (#1) DATE 1978

MANLJFACTURER Titusville

SIZE UNIT BURNER ARE FIRING 20,000 P.P.H. Sat .

HOW MANY BURNERS One

BURNER TYPE Ring

CAPACITY 25,200,000 Btu

MODEL DLG-252s

BURNER MANUFACTURER I n d u s t r i a l Combustion

SERIAL NUMBER L-6991

nAME SAFETY MANUFACTURER F i r e y e 26CF6

TYPE OF CONTROL Electric Positioning

CONTROL MANUFACTURER Honeywell

GAS PRESSURE TO VALVE TRAIN 17.0 Psig

GAS PRESSURE AT BURNER 2.0 P s i g

VALVE TRAIN MANUFACTURER Honeywell

VALVE TRAIN SIZE 3"

A-4 7

I N S T I T U T E 0 F G A S T E C H - N O L O G Y
COMPANY John Gaston H o s p i t a l . . LOCATION 860 Madison

DATE 7-24-79

BURNERS ARE ON Steam B o i l e r (#3) DATE 1978

MANUFACTURER Titusville

SIZE OF UNIT BURNER(S) ARE FIRING I N 20,000 P.P.H. Sat

HOW MANY BURNERS One

BURNER TYPE Ring

CAPACITY 25,200,000 Btu

MODEL DLG-252s

BURNER MANUFACTURER I n d u s t r i a l Combustion

SERIAL NUMBER L-6992

FLAME SAFETY MANUFACTURER F i r e y e 26CF6 . .

TYPE OF CONTROL Electric Positioning

CONTROL MANUFACTURER Honeywell

GAS,PRESSURE TO VALVE TRAIN 17.O P s i g .

GAS, PRESSURE AT BURNER 2 . 0 Psi'g

VALVE TRAIN MANUFACTURER Honeywell

VALVE TRAIN SIZE 3"

I N S T ILT U T ' E
COMPANY . Cargill, Inc. LOCATION 1877 Chanr~el

DATE 7-10-79

BURNERS ARE ON Grain Dryer

MANUFACTURER Hart-Carter

SIZE UNIT BURNER (S) ARE FIRING IN 3000 Bushel Per Hr

HOW MANY BURNERS Lino Flame Assy

BURNER TYPE Atmospheric, Inspirator

CAPACITY 22,000,000 Btu Total

MODEL VFH

BURNER MANUFACTURER Maxon

SERIAL NUMBER --

FLAME SAFETY MANUFACTURER Honeywell R47951016

TYPE OF CONTROL Auto, Temp. Operated

CONTROL MANUFACTURER Partlow

GAS PRESSURE VALVE TRAIN 13. Psig

GAS PRESSURE AT BURNER ,6. Psig . .

VALVE TRAIN MANUFACTURER Maxon

A-4 9

I N S T I T U T E 0 F G A S T E C H N O L O G Y
COMPANY Buclanan L a b LOCATION 1 2 5 6 N. M c L e a n

DATE 7-26-79

BURNERS ARE ON Air Heater DATE 1957

MANUFACTURER --

S I Z E OF U N I T BURNER(S) ARE F I R I N G I N 4 'XI2 Horizorital

HOW MANY BURNERS One

BURNER TYPE V e n t u r i Injector

CAPACITY 6,000,000 B t u

MODEL --

BURNER MANUFACTURER North American

S E R I A L NUMBER --

FLAME SAFETY MANUFACTURER B a r b e r Colman

TYPE OF CONTROL E l e c t r i c Positioning

CONTROL MANUFACTURER B a r b e r Colman

GAS PRESSURE TO VALVE T R A I N 20. Psig

GAS PRESSURE AT BURNER 15. P s i g

VALVE TRAIN MANUFACTURER Maxon

VALVE T R A I N S I Z E 2"

A-50

I N S T I T U T E 0 F G A S T E C H N O L O G Y
COMPANY Buckman L a b LOCATION 1256 N. M c L e a n

DATE 7-26-79

BURNERS ARE ON Rotary Kiln DATE 1979

MANUFACTURER V u l c a n Iron Works

S I Z E OF U N I T BURNER(S) ARE F I R I N G I N 6'X70t Ho$iizontal

HOW MANY BURNERS One

BURNER TYPE Spud

CAPACITY 7.000.000 Btu

MODEL 214-8B

BURNER MANUFACTURER North American

S E R I A L NUMBER --

F'LAME SAFETY MANUFACTURER B a r b e r Colman

TYPE OF CONTROL Metering - Electronic

CONTROL MANUFACTURER North American

GAS PRESSURE TO VALVE TRAIN 1.0 P s i g

GAS PRESSURE AT BURNER 8. 02.

VALVE TRAIN MANUFACTURER North American

VALVE TRAIN S I Z E 2"

I N S T I T U T E O F ' G A S T E C H N O L O G Y

-
COMPANY Humble-Exxon LOCATION 454 W. Wisconsin

DATE 7-26-79

BURNERS ARE ON . Asphalt Heater DATE 1979

MANUFACTURER Struthers-Wells

SIZE OF UNIT BURNER(S) ARE FIRING IN Vertical Unit - No Data

HOW MANY BURNERS Three

BURNER TYPE Spud

CAPACITY 8,150,000 Btu Each

MODEL // 6514-8B

BURNER MANUFACTURER North American

SEKlAL NUMBER UF/8302

FLAME SAFETY MANUFACTURER Barber Colman

TYPE OF CONTROL Proportioning Fuel/Air

CONTROL MANUFACTURER . . North American

GAS PRESSURE TO VALVE TRAIN 3.0 Psig

GAS PRESSURE AT BURNER 1.0 Psig

VALVE TRAIN MANUFACTURER Maxon ..

VALVE TRAIN SIZE 3"

I N S T I T U T E , T E C H N O L O G Y
COMPANY Humble-EXXO~ LOCATION 454 W. Wisconsin

. .
DATE 7-26-79

BURNERS AFUI ON As,phaltHeater DATE 1954


I

MANUFACTURER Struthers-Wells

SIZE OF UNIT BURNER(S) ARE FIRING IN Vertical Unit. No Data

HOW MANY BURNERS Three

BURNER TYPE Spud

CAPACITY 8,150,000 Btu Each

MODEL 214-8B

BURNER MANUFACTURER North American

SERIAL NUMBER -- -1.


.
'
A

n A M E SAFETY MANUFACTURER Barber Colman

TYPE OF CONTROL Proportioning Fuel/Air

CONTROL MANUFACTURER North American

GAS PRESSURE TO VALVE TRAIN 4.0 Psig

GAS PRESSURE AT BURNER 14.0 02.

VALVE TRAIN MANUFACTURER North American


. .

VALVE TRAIN SIZE. 13" Header, 2" Valves

I N .S T I T U T ,~ELz.
-. *
2 . '
, ' 0 F G A S
COMPANY Quaker Oats LOCATION 2782Chelsea

DATE 7-9-79

BURNERS ARE ON Therminol Vapor. .*

MANUFACTURER American Hydro

SIZE OF UNIT BURNER(S) ARE FIRING IN 5,500,000 Btu

HOW MANY BURNERS One

BURNER TYPE Spud . -

CAPACITY 6,600,000 Btu

MODEL DE-6970 .

BUKNER MANUFACTURER North American

SERIAL NUMBER 6795-9 SPL

FLAME SAFETY MANUFACTURER Fireye 26RJ8 6018

TYPE OF CONTROL North American Metering "Auto"

CONTROL MANUFACTURER North American

GAS PRESSURE TO VALVE TRAIN 1 lb.

GAS PRESSURE AT BURNER 8 02.

VALVE TRAIN MANUFACTURER . Eclipse

VALVE TRAIN SIZE 4"

I N S T I T U T E T E C H N ' O L O G Y
11/79

COMPANY Quaker Oats LOCATION 2782 Chelsea

DATE 7-9-79

BURNERS ARE ON Scrubber (Air)

MANUFACTURER Quaker O a t s Design

S I Z E ' O F U N I T BURNER(S) ARE F I R I N G I N 9 0 , 0 0 0 C.F.H.. Air

HOW MANY BURNERS One

BURNER TYPE Spud

CAPACITY 9,000,000 Btu

MODEL 4988-9000

BURNER MANUFACTURER North American

S E R I A L NUMBER CK6-427AZ
-
FLAME SAFETY MANUFACTURER H o n e y w e l l RA890G

TYPE OF CONTROL A u t o . Temp. O p e r a t e d Poisitioning

CONTROL MANUFACTURER North American

GAS PRESSURE TO VALVE TRAIN 10 l b .

GAS PRESSURE AT BURNER 8 02.

VALVE TRAIN MANUFACTURER Maxon

VALVE T R A I N S I Z E 2-1 12"

T E C H N O L O G Y

--
COMPANY Humko LOCATION 1 2 3 1 Pope S t r e e t

DATE 7-10-79

BURNERS ARE ON Steam B o i l e r ( # 7 ) --..-

MANUFACTURER E r i e C i t y - Zurn I n d u s t r i e s

SIZE OF UNIT BURNER(S) ARE FIRING IN 150,000 P.P.H. Sat

HOW MANY BURNERS One

BURNER TYPE - Spud

CAPACITY 150,000,000 Btu

MODEL APR 27

BURNER MANUFACTURER Peabody

SERIAL NUMBER Not A v a i l a b l e


.

FLAME SAFETY MANUFACTURER Fireye

TYPE OF CONTROL Metering

CONTROL MANUFACTURER Bailey

GAS PRESSURE TO VALVE TRAIN 20 l b .

GAS PRESSURE AT BURNER 10 l b .

VALVE TRAIN MANUFACTURER Maxon

VALVE TRAIN SIZE . . 4"

T E C H N O L O G Y
COMPANY V.A. Hospital LOCATION 1030 J e f f e r s o n

DATE 8-20-79

BURNERS ARE ON S t e a m B o i l e r (#3) DATE 1965

MANUFACTURER Murray

S I Z E OF U N I T BURNER(S) ARE F I R I N G I N ' 2 0 , 0 0 0 lbs. per hr.

HOW MANY BURNERS One

BURNER TYPE Ring

CAPACITY 27,000,000

MODEL /I M 15

BURNER Peabody

S E R I A L NUMBER Peabody D r a w i n g {IGSR-MN

SAFETY MANUFACTURER Fieye 255U5 4 0 1 1 . .

TYPE CONTROL Auto Metering

CONTROL MANUFACTURER Hays

GAS PRESSURE TO VALVE T,RAIN 10 lbs.

GAS PRESSURE AT BURNER 3 lbs. ,

VALVE TRAIN MANUFACTURER Maxon

VALVE T R A I N S I Z E 2"

I N S T I T U T E
COMPANY V.A. Hospital LOCATION 1030 J e f f e r s o n

DATE 8-20-79

BURNERS ARE ON S t e a m B o i l e r (#1) DATE 1965

MANUFACTURER Murray

S I Z E OF UNIT BURNER(S) ARE F I R I N G I N 38,000 l b s . p e r h r .

HOW MANY BURNERS One

BURNER TYPE -- Ring

CAPACITY 51,000,000

MODEL // M2 0

BURNER MANUFACTURER Peabody

S E R I A L NUMBER P e a b o d y D r a w i n g #GSR-MN

FLAME SAFETY MANUFACTURER Fireye 255U5 4 0 1 1

TYPE OF CONTROL Auto Metering

CONTROL MANUFACTURER Hays

GAS PRESSURE TO VALVE TRAIN 10 l b s .

GAS PRESSURE AT BURNER 3 lbs.

VALVE TRAIN MANUFACTURER Maxon

VALVE TRAIN S I Z E 2-1/2"

I N S T I T U T E 0 F G A S T E C H N O L O G Y
COMPANY V.A. Hospital -
=-
LOCATION 1030 Jefferson

DATE 8-20-79

BURNERS ARE ON Steam Boiler (#2) DATE 1965

MANUFACTURER ' Murray

SIZE OF UNIT BURNER(S) ARE FIRING IN 38,000 lbs. per hr.

HOW MANY BURNERS One

BURNER TYPE Ring

CAPACITY 51,000,000

MODEL # M 20

BURNER MANUFACTURER Peabody

SERIAL NUMBER Peabody Drawing #GSR-MN

FLAME SAFETY MANUFACTURER Fireye 255U5 4011

TYPE OF CONTROL Auto Metering

CONTROL MANUFACTURER Hays

GAS PRESSURE TO VALVE TRAIN 10 Ibs.

GAS 'PRESSURE AT BURNER 3 lbs. . .

VALVE TRAIN MANUFACTURER . Maxon

VALVE TRAIN SIZE 2-1 12"

AL5 9
0 F G A S
COMPANY Velsicol Chemical ' . LOCATION 1199 Warford

DATE 7-11-79

BURNERS ARE ON Steam Bailer (#3) .-

MANUFACTURER Edgemoor

SIZE OF UNIT BURNER(S) ARE FIRING IN 30,000 P.P.H.

HOW MANY BURNERS Two

BURNER TYPE -- - Ring

CAPACITY 19,000,000 Btu Each

MODEL fl M i8

BURNER MANUFACTURER Peabody

SERIAL NUMBER --

FLAME SAFETY MANUFACTURER None

TYPE OF CONTROL Auto, Positioning

. CONTROL MqNUFACTURER A.W. Cash

GAS PRESSURE VALVE TRAIN 30. Psig

GAS PRESSURE AT BURNER 6. Psig

VALVE TRAIN MANUFACTURER Manual Valves

VALVE TRAIN SIZE 4"

A-60

I N S T I T U T ' E 0 F. G A S T E C H N O L O G Y
COMPANY V e l s i c o l Chemical LOCATION 1199 Warford

DATE 7-11-79

BURNERS ARE ON S t e a m B o i l e r (#2)

MANUFACTURER Edgemoor

S I Z E OF UNIT BURNER(S) ARE FIRING I N 30,000 P.P.H.

HOW MANY BURNERS Two

BURNER TYPE Ring

CAPACITY 19,000,000 Btu Each

MODEL I/ M 18

BURNER MANUFACTURER Peabody

SERIAL NUMBER --

FLAME SAFETY MANUFACTURER. None

TYPE OF CONTROL Auto, P o s i t i o n i n g

CONTROL MANUFACTURER A.W. Cash


01

GAS PRESSURE TO VALVE TRAIN 30. P s i g

GAS PRESSURE AT BURNER 6. P s i g

VALVE TRAIN MANUFACTURER Manual Valves

VALVE TRAIN S I Z E 4"


COMPANY V e l s i c o l Chemical LOCATION 1199 Warford

DATE 7-11-79

BURNERS ARE OK Steam B o i l e r ( # I )

MANUFACTURER Edgemoor

SIZE OF UNIT BURNER(S) ARE FIRING IN, .. 30,000 P.P.H.

HOW MANY BURNERS Two

BURNER TYPE Ring

CAPACITY 19,000,000 Btu Each

MODEL # M 18

BURNER MANUFACTURER Peabody

SERIAL NUMBER --

FLAME SAFETY MANUFACTURER None

TYPE OF CONTROL Auto, P o s i t i o n i n g

CONTROL MANUFACTURER A.W. Cash

GAS PRESSURE TO VALVE TRAIN 30. P s i g

GAS PRESSURE AT BURNER 6. Psig

VALVE TRAIN MANUFACTURER 'Manual Valves

VALVE TRAIN SIZE 4"

A-62
I N S T I T U T E 0 F G A S T E C H N O L O G Y

- - --- - -
COMPANY C a r g i l l Inc. LOCATION 1877 Channel Ave;

DATE 7-10-79

BURNERS G r a i n Dryer

MANUFACTURER Shanzer

SIZE OF UNIT BURNER(S) ARE FIRING I N - 1800 B u s h e l P e r 'Hr.

HOW MANY BURNERS Two

BURNER TYPE Ring

CAPACITY 10,000,000 Btu Each

MODEL # --

BURNER MANUFACTURER Ransome

SERIAL NUMBER ' --

FLAME SAFETY MANUFACTURER Fireye

TYPE OF CONTROL Auto. Temp. P a r t l o w

CONTROL MANUFACTURER P a r t low

GAS PRESSURE TO VALVE TRAIN 8 lb.

GAS PRESSURE AT BURNER 6.5 l b . '

VALVE TRAIN MANUFACTURER . . Maxon

VALVE TRAIN SIZE 2-1/2"

A-63

I N S T . I T U T.E. G A S T E C H N O L O G Y ,
COMPANY Bap t i s t LOCATION 899 Madison

DATE 7-24-79

BURNERS ARE ON Steam B o i l e r (111) DATE 1953

MANUFACTURER Erie City

SIZE OF UNIT BURNER(S) ARE FIRING I N 1 9 , 5 0 0 P.P.H. Sat

HOW MANY BURNERS Two

BURNER TYPE Gun


-.--
.

CAPACITY 24,000,000 Btu T o t a l

MODEL RD-3 0

BURNER MANUFACTURER Webs t e r E n g i n e e r i n g

SERIAL NUMBER --

F'LAME SAFETY MANUFACTURER Honeywell R4138A1004

TYPE OF CONTROL Metering - Electric

CONTROL MANUFACTURER Hays

GAS PRESSURE TO VALVE TRAIN 15.0 Psig

GAS PRESSURE AT BURNER 7.0 P s i g

VALVE TRAIN MANUFACTURER Honeywell and Maxon

VALVE TRAIN SIZE 3"

A-64

0 F G A S T E C H N O L O G Y

- -
COMPANY Baptist Hospital LOCATION 899 Madison

DATE 7-24-79

BURNERS ARE ON Steam B o i l e r ( # 2 ) DATE 1953

MANUFACTURER Erie City

SIZE OF UNIT BURNER(S) ARE FIRING I N 1 9 , 5 0 0 P.P.H. Sat

HOW MANY BURNERS Two

BURNER TYPE Gun

CAPACITY 24,000,000 Btu T o t a l

MODEL RD 30

BURNER MANUFACTURER Webster E n g i n e e r i n g

SERIAL NUMBER --

FLAME SAFETY MANUFACTURER Honeywell R4138A 1004

TYPE OF CONTROL Metering, E l e c t r i c

CONTROL MANUFACTURER' Hays . .

GAS PRESSURE TO VALVE TRAIN 1 5 .O P s i g

GAS PRESSURE AT BURNER 7.. 0 P s i g

VALVE TRAIN MANUFACTURER Honeywell & Maxon


b
VALVE TRAIN SIZE 3"
COMPANY Baptist Hospital LOCATION 899 Madison

DATE 7-24-79

BURNERS ARE ON Steam Boiler (#3) DATE 1940


I

MANUFACTURER Erie City

SIZE OF UNIT BUIU?ER(S) ARE FIRING IN 19,500 P.P.H. Sat

HOW MANY BURNERS Two

BURNER TYPE Gun

CAPACITY 24,000,000 Btu Total

MODEL /\ . RD 30

BURNER MANUFACTURER Webster Engineering

SERIAL NUMBER --

FLAME SAFETY MANUFACTURER Honeywell R4138A 1004

TYPE OF CONTROL Hays, Metering Electric

CONTROL MANUFACTURER Havs

GAS PRESSURE TO VALVE TRAIN 15.0 Psig

GAS PRESSURE AT BURNER 7 .O Psig

VALVE TRAIN MANUFACTURER Honeywell and Maxon

VALVE TRAIN SIZE 3"

A-66

I N S T I ' T U . T E 0 F G A ' S T E C H N O L O G Y
COMPANY Humko . . LOCATION. 1 2 3 1 Pope S t r e e t

DATE 7-10-79.

BURNERS ARE ON Dowtherm V a p o r i z e r (/I3 S t i l l )

MANUFACTURER Eclipse .

SIZE OF UNIT BURNER(S)ARE FIRING


. . IN 3,000,000 Btu Output

HOW MANY BURNERS One

BURNER TYPE -- Ring

CAPACITY 4,500,000 Btu

MODEL HCL-115

BURNE R MANUFACTURER Webster E n g i n e e r i n g

SERIAL NUMBER W1985

FLAME SAFETY MANUFACTURER F i r e y e 26RJ8 6018

TYPE OF CONTROL Manual - Positioning

CONTROL MANUFACTURER Honeywell

GAS PRESSURE TO VALVE TRAIN 10." W.C.


\

GAS PRESSURE AT BURNER 6.." W.C.

VALVE TRAIN MANUFACTURER : Gen,eral C o n t r o l s

VALVE TRAIN SIZE 2"

I N S T I T U T E . 0 F. G A..S .
COMPANY Humko S h e f f i e l d LOCATION 1 2 3 1 Pope S t r e e t .

DATE 7-10-79

BURNERS ARE ON Dowtherm V a p o r i z e r (/I4 S t i l l )

MANUFACTURER Eclipse

SIZE OF UNIT BURNER(S) ARE FIRING I N 2,500,000 Btu Output

HOW MANY BURNERS One

BURNER TYPE Ring

CAPACITY 3,575,000

MODEL /I HCL- 9 5

BURNER MANUFACTURER Webster

SERIAL NUMBER 2163

FLAME SAFETY MANUFACTURER Fireye

TYPE OF CONTROL Positioning - Manual

CONTROL MANUFACTURER Honeywell

GAS PRESSURE TO VALVE TRAIN 10." W.C.

GAS PRESSURE AT BURNER 6." W.C.

VALVE TRAIN MANUFACTURER General Control

VALVE TRAIN SIZE 2"

I N S T I T U T E O F . G A S
COMPANY Methodist Hospital LOCATION 1265 Union

DATE 7-9-79

BURNERS ARE ON Steam Bo-iler ( # 4 )

MANUFACTURER B&W

SIZE OF UNIT BURNER(S) ARE FIRING IN 33,000 P.P.H.

HOW MANY BURNERS Two


. .

BURNER TYPE Gun . .

CAPACITY 20,625,000 each

MODEL RD-28

BURNER MANUFACTURER Webster

SERIAL NUMBER Not Available

FLAME SAFETY MANUFACTURER Honeywell RA890F .. .

TYPE CONTROL Auto - Metering

CONTROL MANUFACTURER Hays

GAS PRESSURE TO VALVE TRAIN 10 lbs.

GAS PRESSURE AT BURNER 7 lbs.

VALVE TRAIN MANUFACTURER Maxon . ,

VALVE TRAIN SIZE 2-112''

I N S T I T U T E 0 F G A S T E C H N O L O G Y
COMPANY ~ethodistHospital LOCATION 1265 Union

DATE 7-9,-79

BURNERS ARE ON steam ~diler(#3)

MANUFACTURER B&W

SIZE OF UNIT BURNER(S) ARE FIRING IN --------."--.- -


10,000 P.P.H. .- -a-m=-.- -

HOW MANY BURNERS One

BURNER TYPE Gun

CAPACITY 14,500,000 Btu

MODEL RD-23WGOS

BURNER MANUFACTURER Webster

SERIAL NUMBER 13192

FLAME SAFETY MANUFACTURER Honevwell RA890F

TYPE OF CONTROL Auto - Metering

CONTROL MANUFACTURER . Hays

GAS PRESSURE TO VALVE TRAIN 8 lbs.

GAS PRESSURE AT BURNER 6 lbs.

VALVE TRAIN MANUFACTURER . Maxon

VALVE TRAIN SIZE . : 2-1/2"

A-70

I N - S T I T U T ' E 0 F G A S T E C H N O L O G Y
11/79

COMPANY Methodist Hospital LOCATION 1265 Union

DATE 7-9-79

BURNERS ARE ON Steam Boiler ( # 2 )

MANUFACTURER B&W

SIZE OF UNIT BURNER(S) ARE FIRING IN ' 10,000 P.P.H. . .

HOW MANY BURNERS One

BURNER TYPE Gun

CAPACITY 14,500,000 Btu

MODEL // RD-23WGOS

BURNER MANUFACTURER Webster

SERIAL NUMBER 13192

FLAME SAFETY MANUFACTURER Honeywell ~A890F

TYPE OF CONTROL Auto - Metering

CONTROL MANUFACTURER Hays

GAS PRESSURE TO VALVE TRAIN 8 lbs'.

GAS PRESSURE AT BURNER 6 lbs.

VALVE TRAIN MANUFACTURER Maxon

VALVE TRAIN SIZE 2-1/2"

I N S T I T U T E 0 F G A S T E C H N , O L O G Y
11/79

COMPANY Methodist Hospital LOCATION' 1265 Union

DATE 7-9-79 :-

BURNHRS ARE ON S t e a m B o i l e r (#I)

MANUFACTURER B&W

S I Z E OF U N I T BURNER(S) ARE F I R I N G I N 10,000 P . P . H .

HOW MANY BURNERS One

BURNER TYPE . Gun

CAPACITY 14,500,000 B t u

MODEL fl RD-23WGOS

BURNER MANUFACTURER Webster

S E R I A L NUMBER 13192

FLAME SAFETY MANUFACTURER H o n e y w e l l RA890F

TYPE OF CONTROL Auto - Metering

CONTROL MANUFACTURER Hays

GAS PRESSURE TO VALVE TRAIN 8 lbs.

GAS PRESSURE AT BURNER 6 lbs.

VALVE T R A I N MANUFACTURER Maxon

VALVE TRAIN SIZE 2-1/2"

T E C H N ' O L O G Y
COMPANY S t . Joseph Hospital L ~ , 254.
- J a c k~s o n ~
~ ~ ~

DATE 8-20-79

BURNERS ARE ON Steam B o i l e r (ill) DATE 1 9 4 9

MANUFACTURER B&W

SIZE OF UNIT BURNER(S) ARE FIRING I N 1 4 , 6 0 0 P.P.H. Sat. .

HOW MANY BURNERS Two

BURNER TYPE. Gun

CAPACITY 1 0 , 0 0 0 , 0 0 0 B t u Each

MODEL /I Rb

BURNER MANUFACTURER Webster Engineering

SERIAL NUMBER --

FUME SAFETY MANUFACTURER Honeywell

TYPE CONTROL E l e c t r i c Metering


3 .

CONTROL MANUFACTURER Hays .

GAS PRESSURE TO
.
VALVE
.
TRAIN 7 . P s i--g - .. - .

GAS PRESSURE AT BURNER 4. P s i g

VALVE TRAIN MANUFACTURER Pyronics

VALVE TRAIN SIZE 2-112"

I N S T I T U ' T E,
11/79

COMPANY . St. .Joseph Hospital LOCATION 254 J a c k s o n

BURNERS ARE ON Steam B o i l e r (#2) DATE 1 9 4 9

MANUFACTURER B&W

SIZE OF UNIT BURNER(S) ARE FIRING I N ' 1 4 , 6 0 0 P.P.H. Sat.

HOW MANY BURNERS Two

BURNER TYPE Gun

CAPAC ITY i 0 , 0 0 0 , 0 0 0 ~ t Eua c h

MODEL RD

BURNER MANUFACTURER Webs t e r E n g i n e e r i n g

SERIAL NUMBER --
.-.

FLAME SAFETY MANUFACTURER Honeywell

-.
TYPE OF CONTROL E l e c t r i c Metering

CONTROL MANUFACTURER Hays

GAS PRESSURE TO VALVE TRAIN 7. P s i g

GAS PRESSURE AT BURNER 4. P s i g

VALVE TRAIN MANUFACTURER . Pyronics

VALVE TRAIN SIZE . , 2-1/2"

A-74

O F .' G A S
COMPANY St. Joseph Hospital LOCATION 254 Jackson..
. .

DATE 8-20-79

BURNERS ARE ON Steam Boiler ( # 3 ) DATE 1960

MANUFACTURER B&W

SIZE OF UNIT BURNER(S) ARE FIRING IN , 14,600 P.P.H. Sat.

HOW MANY BURNERS . TWO

BURNER TYPE Gun

CAPACITY 10,000,000 Btu Each

MODEL /I RD

BURNER MANUFACTURER Webster

SERIAL NUMBER --

FLAME SAFETY MANUFACTURER Honeywell . .

TYPE OF CONTROL Electric Metering

CONTROL MANUFACTURER Hays

GAS PRESSURE TO VALVE TRAIN 7. Psig

GAS PRESSURE
. . AT. .BURNER
.
4. Psig

VALVE TRAIN MANUFACTURER . Pyronics

. .
VALVE ,TRAIN SIZE 2-112"
. . .

, A-75

' I N S T I T U T E O F . G A S T E C H N O L O G Y
,COMPANY Hunko S h e f f i e l d LOCATION . 1 2 3 1 Pope S t r e e t

DATE 7-10-79

. .
BURNERS ARE ON , Steam B o i l e r (ill)

MANUFACTURER International

SIZE OF UNIT BUrnTER(S) ARE FIRING I N 20,000 P.P.H. S a t . Stm.

HOW MANY BURNERS. One

BURNER TYPE Gun

CAPACITY 30,000,000 Btu

MODEL 11 . YE

B U M R MANUFACTURER John Zink

SERIAL NUMBER --

FLAME SAFETY MANUFACTURER F i r e y e 26RJ86018

. -
TYPE OF CONTROL Manual - Pneumatic P o s i t i o n i n g
I

CONTROL MANUFACTURER Foxboro

GAS PRESSURE TO VALVE TRAIN 8 lbs.

GAS PRESSURE AT BURNER 5 lbs.

VALVE TRAIN MANUFACTURER General C o n t r o l s

VALVE TRAIN. SIZE . 3" . ,

T E C H N O L O G Y
COMPANY Humko Sheffield LOCATION 1231 Pope Street '

DATE 7-10-79

BURNERS ARE ON Steam Boiler (#2)


i

MANUFACTURER . International

SIZE OF UNIT BURNER(S) ARE FIRING I N ' '20,000 P.P.H. Sat. Steam

HOW MANY BURNERS One


/

BURNER TYPE -- Gun

CAPACITY 30,000,000 Btu

MODEL d YE

BURNER MANUFACTURER John Zink

SERIAL NUMBER Not Available


I

' FLAME SAFETY MANUFACTURER Fireye 26RJ8 6018 .

TYPE OF CONTROL Manual - Pneumatic Positioning

CONTROL MANUFACTURER Foxboro

GAS PRESSURE TO VALVE TRAIN 8 lbs.

GAS PRESSURE AT BURNER 5 lbs.

VALVE TRAIN MANUFACTURER General Controls .

VALVE TRAIN SIZE 3"

A-7 7

I N S T I T U T E 0. F G A S T E C H N O L O G Y
COMPANY . -Humko LOCATION T231 Pope S t r e e t

DATE 7-10-79
A

BURNERS ARE ON L i q u i d P h a s e T h e n n i n o l H e a t e r (Dimer)

MANUFACTURER Struthers-Wells Corporation

SIZE OF UNIT BURNERCS) AKE FIRING I N ' 8,000,000 Btu Output

HOW MANY BURNERS One

BURNER TYPE Spud

CAPACITY 1 1 , 5 8 0 , 6 6 0 Btu

MODEL DBA

BURNER MANUFACTURER J o h n Zink

SERIAL NUMBER Not A v a i l a b l e

nAME SAFETY MANUFACTURER B a r b e r Colman

TYPE OF CONTROL P o s i t i o n i n g , Auto

CONTROL MANUFACTURER Bailey

GAS PRESSURE TO VALVE TRAIN 25 l b s .

GAS PRESSURE AT BURNER 10 l b s .

VALVE TRAIN MANUFACTURER . * Maxon

A-7 8

I N S T I T U T E 0 F G A S T E C H N O L O G Y
COMPANY Quaker Oats LOCATION 2782 Chelsea

DATE 7-9-79

BURNERS ARE ON Hydrogen Generator I

MANUFACTURER Girdler

SIZE OF UNIT BURNER(S) ARE FIRING IN -- . .

HOW MANY . BURNERS


. .
12

BURNER TYPE Atmospheric, Injector

CAPACITY 550,000 Btu Each

MODEL PMSR2-3

' BURNER MANUFACTURER John Zink

SERI4L NUMBER Not Available

FLAME SAFETY MANUFACTURER Honeywell

TYPE OF CONTROL Manual

CONTROLMANUFACTURER --

GAS PRESSURE TO VALVE TRAIN 34 1 . b .

GAS PRESSURE AT BURNER 30 lbs. , .

VALVE TRAIN MANUFACTURER Maxon

VALVE TRAIN SIZE 1-112"

A-7 9

I N S T I T U T E 0 F, G A . S . T E C H N O L O G Y
11/79

COMPANY Velsicol Chemical .LOCATION 1199 W a r f o r d

DATE 7-11-79
I
i
BURNERS ARE ON . S t e a m B o i l e r (#4_;)_

MANUFACTURER B&W F F - 2 7 7 1

1
SIZE OF UNIT BURNER(S) ARE FIRING IN 50,000 P . P . H . Sup. Htd. 1

HOW MANY BURNERS Three

BURNER TYPE - Gun

I
CAPACITY 20,000,000 Btu Each
1

MODEL YB-18-F

BURNER MANUFACTURER John Z i n k

S E R I A L NUMBER --

FLAME SAFETY MANUFACTURER Honewell

T Y P E O F CONTROL Auto.. Metering

CONTROL MANUFACTURER Havs - Re~ublic

GAS P R E S S U R E TO VALVE T R A I N 30. P s i n

GAS P R E S S U R E AT BURNER 1 2 . Psig

VALVE T R A I N MANUFACTURER Eclipse

VALVE T R A I N S I Z E 2-112"

A-8 3

I N S T I T U T E O F G A S T E C H N O L O G Y
COMPANY Velsicol Chemical LOCATION 1199 Warford

DATE 7-11-79. . ..

BURNERS ARE ON Dowtherm.Vaporizer

MANUFACTURER Struthers-Wells Corporation


. .

SIZE OF UNIT BURNER(S) ARE FIRING IN 4,500,000.Btu Output


. .

HOW
. . MANY BURNERS One

BURNER TYPE Gun . .

CAPACITY 8,600,000.Btu

MODEL /I WR-24

BURNER MANUFACTURER John Zink

SERIAL NUMBER 034448

FLAME SAFETY. . MANUFACTURER Wheelco (B.C.) /I1470 I .

TYPE OF CONTROL Auto., Positioning

CONTROL MANUFACTURER Honeywell

GAS PRESSURE TO VALVE TRAIN 20. psi^

GAS PRESSURE AT BURNER 10. Psig

VALVE TRAIN MANUFACTURER General Controls

VALVE TRAIN SIZE . " ,


1-112"

I N S T I T U T E
COMPANY Wesson F o o d s LOCATION 1315 Williams

DATE 11-9-79 .

BURNERS ARE ON Dow Therm V a p o r i z e r DATE 1 9 7 7

MANUFACTURER F o s t e r Wheeler

SIZE OF UNIT BUKNER(S)ARE FIRING IN 1295 6q. fc. heating surface

HOW MANY BURNERS 1

BURNER TYPE Spud

CAPACITY 7,323,000 Btu

MODEL AECR-144

BURNER MANUFACTURER Ray B u r n e r Company

SERIAL NUMBER 298672

FLAME SAFETY MANUFACTURER Honeywell ,

TYPE OF CONTROL E l e c . P o s i t . Temp. O p e r a t e d

CONTROL MANUFACTURER Honeywel.1 '

GAS PRESSURE TO VALVE TRAIN 10" W.C.

GAS PRESSURE AT BURNER 4" W.C.

VALVE TRAIN MANUFACTURER General Controls

VALVE TRAIN SIZE 3"


C

I N S T I T U T E T E C H N O L O G Y
11/79

COMPANY Wesson Foods LOCATION 1315 Williams

DATE 11-9-79 . .

BURNERS ARE ON 1, 2 & 3 Steam Boiler DATE 1970

MANUFACTURER Walsh Weidner

SIZE OF UNIT BURNER(S) ARE FIRING IN 33,000 lbs. Steamlhr

HOW MANY BURNERS 3

BURNER TYPE Ring

CAPACITY 44,800,000 Btu Each

MODEL DAZ 22

BURNER MANUFACTURER Coen

SERIAL NUMBER D-4313 A, B & C

FLAME SAFETY MANUFACTURER Fireye

TYPE OF CONTROL Elec. Pos.

CONTROL MANUFACTURER Coen

GAS PRESSURE TO VALVE TRAIN 12 lbs.

GAS PRESSURE AT BURNER 3-112 Ibs.

VALVE TRAIN MANUFACTURER Maxon

VALVE TRAIN SIZE 2-112" . .


. .
Note - These will be replaced by 2 new boilers with 80 or 90,000 lbs. per hr
steam (service 1980 - Coen burners)

A-8 3
1 N S T I T U T . E 0, F G A S T E C H N O L . O G Y
COMPANY Refined Metals LOCATION 2 5 7 W. M a l l o r y

DATE 11-8-79

BURNERS ARE ON L e a d P o t (#4) DATE 1 9 7 0

S I Z E OF UNIT BURNER(S) ARE FIRING I N 50 t o n

HOW MANY BURNERS 1

BURNER TYPE Atmospheric I n je c t o r - Low P r e s s u-r-


e-

CAPACITY 750,000 Btu

MODEL /I --

BURNER MANUFACTURER Eclipse

SERIAL NUMBER --

FLAME SAFETY MANUFACTURER --

TYPE OF CONTROL Manual

CONTROL MANUFACTURER --

GAS PRESSURE AT BURNER 4" W.C.

VALVE TRAIN MANUFACTURER --

VALVE TRAIN S I Z E 1-112"

A-8 4

I N S T I T U T E ' 0 F G A S T E C H N O L O G Y
11/79

COMPANY Refined Metals ... . LOCATION 2,57W. Mallory


..

DATE 11-8-79.

BURNERS ARE ON Lead Pot (#1,2&3) DATE 1970

MANUFACTURER -- . .

SIZE OF UNIT BURNER(S). ARE FIRING IN 50 tons

HOW MANY BURNERS 3 . .

BURNER
. .
TYPE Atmospheric Injector - Low Pressure

CAPACITY 600.000 Btu

MODEL /I --

BURNER MANUFACTURER Eclipse

SERIAL NUMBER --

FLAME SAFETY MANUFACTURER

TYPE OF CONTROL Manual

CONTROL MANUFACTURER --

GAS PRESSURE TO VALVE TRAIN 1 Ih.

GAS PRESSURE AT BURNER 6" W.C.

VALVE TRAIN MANUFACTURER --

VALVE TRAIN SIZE 1"

I N S T I T U T E 0 F G A S T E C H N O L O G Y

-
COMPANY R e f i n e d Metals LOCATION 257 W. M a l l o r y

DATE 11-8-79

BURNERS ARE ON Air Scrubber DATE 1 9 7 5

MANUFACTURER --

SIZE OF UNIT BURNER(S) ARE FIRING I N Chamber - No S i z e

HOW MANY BURNERS 1

BURNER TYPE N o z z l e Mix

CAPACITY 4,375,000 Btu

MODEL I 1 6 8 HCF-G

BURNER MANUFACTURER Eclipse

SERIAL NUMBER --

FLAME SAFETY MANUFACTURER Protection Control

TYPE OF CONTROL E l e c . P r o p . Temp. O p e r .

CONTROL MANUFACTURER B a r b e r Colman

GAS PRESSURE TO VALVE TRAIN 10" W.C.


. I

GAS PRESSURE AT BURNER 2" W.C.

VALVE TRAIN MANUFACTURER Eclipse

VALVE TRAIN SIZE 3 I'

A-8 6

I N S T ' I T U T E 0 F G A S T E C H N O L O G Y
11/79

COMPANY Refined Metals LOCATION 257 W. M a l l o r y

DATE 11-8-79

BURNERS ARE ON R e v e r b e r a t i n g Furnace DATE 1 9 7 0 .

MANUFACTURER --
. .

S I Z E OF U N I T BURNER(S) ARE F I R I N G I N ' --

HOW MANY BURNERS 2 . .

BURNER TYPE Nozzle Mix

CAPACITY 7,500,000 B t u E a c h . .

MODEL Multi-Fier 6"

BURNER MANUFACTURER Maxon

S E R I A L NUMBER --

FLAME SAFETY MANUFACTURER

TYPE OF CONTROL Manual . . .

CONTROL MANUFACTURER --

GAS PRESSURE TO VALVE T R A I N 23" W.C.

GAS PRESSURE AT BURNER 10" W.C.

VALVE T R A I N MANUFACTURER Maxon

VALVE T R A I N S I Z E 3"

A-87

I N S T I T U T E 0 F G A S T E C H N O L O G Y
COMPANY . ~ e i nf e d M e t a l s LOCATION 2 5 7 W. M a l l o r y

DATE 11-8-79

BURNERS ARE ON L i d M e l t i n n P o t (/I51 DATE 1 9 7 5

MANUFACTURER --

S I Z E OF UNIT RURNER(S) ARE FIRING I N - 1 0 0 t o n s

HOW MANY BURNERS 1

BURNER TYPE N o z z l e Mix

CAPACITY 4,375,000 Btu

MODEL # 1 6 8 HCF-G

BURNER MANUFACTURER Eclipse ~

SERIAL NUMBER --

FLAME SAFETY MANUFACTURER Protection Controls

TYPE OF CONTROL E l e c . P r o p . Temp. O p e r .

CONTROL MANUFACTURER B a r b e r Colman

GAS PRESSURE TO VALVE TRAIN 10'' W.C.

GAS PRESSURE AT BURNER 3" W.C.

VALVE .TRAIN MANUFACTURER Eclipse

VALVE TRAIN S I Z E .. . 2'l

0 F G A S T E C H N O L O G Y

- - -
11/79

COMPANY R e f i n e d Metals LOCATION 257 W. M a l l o r y

DATE .\., 11-8-79

BURNERS ARE ON Lid Meltina P o t (#6) DATE 1 9 7 5

MANUFACTURER --

S I Z E OF UNIT BURNER(S) ARE FIRING I N - 100 t o n s

HOW MANY BURNERS 1

BURNER TYPE .--- N o z a Mix

CAPACITY 4,375.000 Btu

MODEL 1 6 8 HCF-G

BURNER MANUFACTURER E c ~ ~ D s ~

SERIAL NUMBER --

FLAME SAFETY MANUFACTURER Protection Controls

TYPE OF CONTROL E l e c . P r o p . Temp. O p e r .

CONTROL MANUFACTURER B a r b e r Colman

GAS PRESSURE TO VALVE TRAIN 10" W.C.

GAS PRESSURE AT BURNER 2" W.C.

VALVE TRAIN MANUFACTURER Eclipse

VALVE TRAIN S I Z E 2"

I N S T I T U T E T E C H N O L O G Y
APPENDIX B. Survey Letter

B-1

I N S T I T U T E 0 F G A S T E C H N O L O G Y
THIS PAGE
WAS INTENTIONALLY
LEFT BLANK
I *
STITUTE OF OAS TECHNOLOOY 3424 SOUTH STATE STREET IIT CENTER CHICAGO, ILLINOIS 6 0 6 1 6

GENERAL PHONE 31 2/567-3650


TELEX 25-61 89
DIRECT DIAL 31 2/567-' 5748

The Department of Energy (DOE) and t h e Memphis L i g h t , Gas and Water


Company (MLGW) a r e p l a n n i n g t o b u i l d and o p e r a t e a n i n d u s t r i a l f u e l g a s
(IFG) p l a n t n e a r Memphis. The p l a n t would p r o d u c e a medium h e a t i n g v a l u e
g a s ( ~ 2 7 5B t u / c u . f t . ) t o r e p l a c e n a t u r a l g a s p r e s e n t l y b e i n g s u p p l i e d by
MLGW.

IFG a n d / o r o t h e r medium h e a t i n g v a l u e g a s e s have b e e n t e s t e d by t h e


I n s t i t u t e of Gas Technology on a b o u t t e n d i f f e r e n t i n d u s t r i a l n a t u r a l g a s
b u r n e r s . I n most c a s e s no m o d i f i c a t i o n s were n e c e s s a r y " t o s u c c e s s f u l l y
b u r n t h e s e g a s e s a t t h e r a t e d c a p a c i t y of t h e b u r n e r . A l s o , we found no
s i g n i f i c a n t c h a n g e s i n t h e t h e r m a l e f f i c i e n c y of t h e equipment.

Some MLGW c u s t o m e r s have b u r n e r s and o t h e r equipment b u i l t by your


company. A s t h e s e were d e s i g n e d f o r n a t u r a l g a s , we would g r e a t l y a p p r e -
c i a t e your h e l p i n recommending b u r n e r m o d i f i c a t i o n s , i f a n y , r e q u i r e d t o
s u c c e s s f u l l y b u r n IFG.

The l o c a t i o n s , t y p e s , c a p a c i t i e s , and t h e y e a r of i n s t a l l a t i o n of t h e
b u r n e r s and t h e p r o p e r t i e s of IFG a r e a t t a c h e d .

Sincerely yours,

Hamid A. A b b a s i
Chemical E n g i n e e r

AFFILIATED WITH ILLINOIS INSTITUTE OF TECHNOLOQY


T a b l e 1. INDUSTRIAL FUEL GAS COMPOSITION (Mol %)

Hydrogen
Carbon Monoxide
Methane
Carbon D i o x i d e
Nitrogen

T a b l e 2. COMPARISON OF INDUSTRIAL FUEL GAS AND NATURAL GAS PROPERTIES

Typical
-
I FG N a t u r a l Gas

Speclf i c Gravity 0.69 0.59


H i g h e r H e a t i n g V a l u e , BtuISCF 275 1020
Lower H e a t i n g v a l u e , Btu/SCF 251 920
SCF Fue1/1000 Btu 3.6 1.0
SCF A i r / 1 0 0 0 Btu 7.6 9.4
SCF P r o d u c t s / 1 0 0 0 Btu 9.8 10.4
A d i a b a t i c Flame T e m p e r a t u r e ( S t o i c h i o m e t r i c ) , O F 3500 3530

B -4

I N S T I T U T E 0 F G A S T E C H N O L O G Y
APPENDIX C. Manufacturers ' R e p l i e s

I N S T I T U T E T E C H N O L O G Y

--
THIS PAGE
WASi INTENTIONALLY
.

'I

LEFT BLANK
i4
. .

--
Babcock&Wilcox ,... .. .. .. - .....: .. .
Power Generation Group
.... - ... -.------..--------.---.,--.
1367 The Illuminating Building, Clevelarid. Ohio 441 13
Telephone: (216)781-9212

October 12, 1979


Institute of Gas Technology
3424 South State Street
IIT Center
Chicago, Illinois 60616,
Attention:Mr.Hamid A.Abbasi,
Chemical Engineer

Gentlemen:
We have your letter originally addressed to' our Mr.S.D.Potterton.
We would like to advise that in any project requiring the.deter-
'mination of modifications to an existing boiler unit, by virtue
of using a fuel for which the unit was not designed, our practice
is to,first conduct.an Engineering Study..
Your letter to Mr.Potterton of'september 24, 1979 suggests to us
that a study would be .required to develop the specifics of
burner and,possibly,control modifications, which would be
necessary in order to burn the industrial fuel gas for which you
provided an analysis.
Our Engineering Studies range in price from several thousand dollars
.upwards. If you desire'us to make such a study, please contact me
in this office and we will prepare a quotation for the study.

Yours very truly,

RTK: CNW Manager, Energy .Services Sales


Cleveland

The Babcock & Wilcox Company I Established 1867

(2-3

I N S T I T U . T E 0 . 'F' G A S T E C H N O L , O G Y
~ a k e 'qerkins
r Inc
Saginaw
Michigan 48601

Telgphone 1517) 752.4121


rsml 227459
llrr 810.265-9064
Telegrams &,fins SGW

October 5 , 1979

Mr. Hamid A . Abbasi


I n s r i t u t e of Gas Technology
3424 South S t a t e S t r e e t
ITT C e n t e r
Chicago, I l l i n o i s 60616
Dear Mr. Abbas i :
.Subject: K r o g e r , Memphis, Tennessee
Ovens Nos. AT0434 & ASU4045

Regarding your l e t t e r of September 24, 1979, on t h e b u r n e r


o p e r a t i o n w i t h a change frorr. n a t u r a l gas t o a low BTU g a s
a s proposed by t h e Memphis L i g h t , Gas and Water Company,
we b e l i e v e you w i l l have probdems m k i n g t h e s e b u r n e r s
operate properly.
These ovens have a r e c i r c u l a t i n g h e a t i n ? system, where t h e
D a i r f o r combustion i s provided by a n e g a t i v e p r e s s u r e i n t h e
f i r e box. This n e g a t i v e p r e s s u r e i s c o n s t a n t on h i g h o r
low f i r e . The h i g h hydrogen c o n t e n t of t h i s proposcd low
BTU g a s w i l l r e s u l t i n a v e r y s h o r t E l a a e due t o t h e m c h
'higher'ignition rate.
The c o n s t a n t q u a n t i t y of combustion a i r and t h e s h o r t flame
w i l l make t h e low f i r e s e t t i n g ' v e r y c r i t i c a l .
I t would b e our recommendation t h e s e b u r n e r s b e r e p l a c e d w i t h
a m o d u l a t i n g b u r n e r and c o n t r o l s , i f t h i s proposed change i n
gas t a k e s p l a c e . '
Your d a t a s h e e t on t h e s e b u r n e r s i s i n c o r r e c t a s t h e c a p a c i t y
i s 1 , 5 0 0 , 0 0 0 BTUIhour n o t 500,000 a s shown.
Sincerely,
BAKER PERKJPIIS I N C

- I
B . E. P e t r v
Manager, ~ k s i ~ Engineering
n - ovens - . .
Food E n g i n e e r i n g D i v i s i o n

Baker Perkins lnc./ 1000 Hess sl./saginaw Mich. 48601

I N S T I T U T E o F G A. i T E C H N O L O G Y
cleaver ~rooks" 4
DIVISION O F AQUA-CHEM, INC.

P.O. BOX 421. MILWAUKEE. WISCONSIN 53201 111-962-0100 CABLE: CLEBRO

October 1 , 19.79

Mr. Hamid A. Abbasi


Chemical Engineer
Institute of G a s Technology
3 4 2 4 South State Street
C h i c a g o , IL 60616

i
! Gentlemen:

Your l e t t e r of September 2 4 , 1979, questions t h e need for modifications to


I
the burner, for the u s e of 275 BTU/Cu.Ft. fuel g a s .

We a r e relatively confident that the burner s y s t e m s a s supplied with the ' '

Cleaver-Brooks boilers listed on your attachment, will perform satisfactorily


with this IFG. It should be pointed out that the burner system includes a g a s . . .
ring containing a s e r i e s of drilled orifices to c a u s e uniform distribution of the
g a s around i t s periphery. These orifices r e s u l t in a pressure drop in the g a s
flow stream. The g a s stream a l s o flows through a piping and.contro1 manifold
which a l s o c a u s e s a head l o s s during g a s flow.

Since the g a s which is intended to be used h a s a lower heating content than


natural g a s , greater g a s flow will be required to achieve the required h e a t
input t o the boiler. Increased g a s flows will require substantially higher g a s
p r e s s u r e s , which c a n be calculated on the b a s i s of standard formulae. w h e n
s o , d o i n g , it must be remembered that the g a s burner pressure i s a composite
of furnace pressure plus orifice pressure drop. It is not expected that the fur-
n a c e pressure would r i s e a n appreciable amount a s a r e s u l t of the u s e of the
lower BTU content f u e l . Therefore, the burner pressure l i s t e d in your data
cannot be used a s is for your c a l c u l a t i o n s .

Very truly yours,

Glenn D. k r a i g , Manager
Product ~ n ~ i n e e r i n g

I
!
ORIGINATOR AND LARGEST PRODUCER OF PACKAGED BOILER SYSTEMS

I N S T I T U T E 0 F G A S T E C H N O L O G Y
COMPANY me.
Combrtsrion Engineers and Manufacrurers Since 1912
1 5 1 0 R O L L I N S ROAD, BURLINGA-ME. C A L I F O R N I A 94010. T E L E P H O N E : 4 1 5 . 6 9 7 . 0 4 4 0
TELEX: 03.4337 'CABLE: C O E N B U R N E R

October 10, 1979

I n s t i t u t e o f Gas Technology
3424 South S t a t e S t r e e t
11T Center
Chicago, I l l i n o i s 60616

Attention: Hamid A. Abbasi

Subject: IFG Gas f o r Memphis

Dear Mr. Abbasi:

Mr. Hendricks has asked me t o answer your l e t t e r o f September 24. Coen


Company i s w e l l aware o f t h e DOEIMLGW i n t e r e s t i n t h e U-gas process and
have been i n discussion w i t h IGT & MLGW concerning t h e conversion work
recommended f o r t h e e x i s t i n g p l a n t s t o u t i l i z e IFG.

Our r e p r e s e n t a t i v e s i n Memphis, Combustion & C o n t r o l s Company, d i d a study


f o r MLGW w i t h recommended approaches t o using IFG i n .Coen combustion equip-
ment. Copies o f these r e p o r t s and meeting minutes o f May 18, w i t h MLGW
and IGT personnel, summarize rriodi f i c a t i o n s we recomend f o r IFG.

Since n a t u r a l gas l i n e s e x i s t t o present MLGW customers, and IFG fuel


l i n e s and p i p i n g t r a i n s t o t h e b o i l e r s w i l l most l i k e l y be added, we
b e l i e v e IFG should be added t o e x i s t i n g equipment t o a l l o w b u r n i n g n a t u r a l
gas, o i l o r IFG as t h e s i t u a t i o n (and f u e l c o s t ) d i c t a t e s .

Yours very t r u l y ,

COEN COMPANY INCORPORATED

es H. White, Manager
b u s t i o n Systems

A t t : 3 Letters
. ..
"Coen Company a t Your Service" brochure
LG 78

cc: Combustion & Controls, A t t n : Ed Cook


Schoonhoven & Olson, Chicago, A t t n : S. Van Peski
C-6
I N S T I T U T E 0' F G A S T E C H N D L 0 , G Y
C-E Power Systsnle
Combustion Engineering, Inc.
2100 Clearwater Drive
Oak Brook, Illinois 60521

POWER
6-E'SYSTEMS
October 15, 1979

Institute of Gas Technology


3424 South State Street
IIT Center
Chicago, Illinois 60616
Attention: . M r . Hamid A. Abbasi
Re: Your Letter of 9/24/79 to D. Frey
IFG
Dear Sir:
While your experience indicates modifications were required in most cases,
we can only make recommendations based on a study of the fuel and of each
unit you are considering.
This study would cost $10,000.00
Respectfully subnitted,
COMBUSTION ENGINEERING, INC.

Sr. Sales Engineer


EFO:jks

C-7

I N S . T I T U T E 0 F G A S T E C H N O L O G Y
FCI I P S E BURNERS

M'R Engelhardt Cu.


w C H I C A G O , ILLINOIS 60646
G A S ENERGY SYSTEMS, EQUIPMENT AND CONTROLS P H O N E '775-4800,

O c t o b e r 1 0 , 1979

I n s t i t u t e o f Gas Technology
3424 S. S t a t e S t .
I I T Center
C h i c a g o , 11. 60616
A t t n : M r . Hamid A. Abbasi

Subject: Memphis L i g h t , Gas & Water Co.


Your L e t t e r o f 9/24/79

Dear Mr. Abbasi : f-

A p r e l i m i n a r y e v a l u a t i o n o f t h i s g a s shows t h a t i t
c a n p r o b a b l y b e u s e d i n t h e b u r n e r s l i s t e d on y o u r
equipment f i l e .
One t h i n g t h a t w i l l have t o b e done:
E n g i n e e r i n g f e e l s t h a t t h e gas p r e s s u r e , a t each
b u r n e r , would h a v e t o b e 1 2 . 7 t i m e s t h e p r e s e n t
g a s p r e s s u r e a t e a c h b u r n e r t o o b t a i n t h e same
i n p u t a t each burner.

The p e r i f e r y equipment would h a v e t o b e e v a l u a t e d


t o see i f i t c o u l d o p e r a t e a t t h i s i n c r e a s e d p r e s s u r e .
I f we c a n b e o f f u r t h e r s e r v i c e , p l e a s e f e e l f r e e t o
c o n t a c t o u r o f f i c e a t any t i m e .

Sincerely,

A. A. ENGELHARDT CO.

M. W . Finnegan ..,
. l' . ,..

MWF :gm
cc: J. Baker

I N S T I T U T E . o F G A S T E C H N O L O G Y
industrial

INDUSTRIAL AND COMMERCIAL BOILERS AND BURNERS

Octobeh 2 , 1979

I n b t i t u t e 0 6 Gab T e c h n o l o g y
3424 S o u t h S t a t e S t h e e t I T T C e n t e h
Chicago, I t t i n o i d 606 1 6

Att: Hamid A. A b b a b i - Chemical Engineeh

Gentlemen:

Mh. Hanna i b away dhom ' h i d o d d i c e and hub h e q u e b t e d me t o


bend i n d o h m a t i o n h e q u e b t e d i n youh l e t t e h 0 6 Septembeh 26, 1979.

I t Lh d i d d i c u l t t o p h e d i c t w i t h a n y deghee 0 6 aCCUhaCy
m o d i 6 i c a t i o n b t o t h e I C DLG-252s now i n d t a l l e d i n t h e C i t y 06
Memphib H o d p i t a l doh c o n v e h b i o n dhom n a t u + a l gab t o youh
IFG g a b .

T h e DLG- 2 52 buhneh i s d e b i g n e d doh o p t i m u m h e b u l t b b u h n i n g


n a t u h a l gab a l t e h n a t e l y w i t h d u e l o i l w i t h ebb e n t i a l l y
d u p l i c a t e pehdohmance w i t h e i t h e h d u e l . T h e ~ cbuhnehb w i l l
d i k e d u e l gab h a n g i n g dhom 500 8 . t . u . manu6actuhed gab t o
2600 8 . t . u . LPG w i t h o n l y m i n o h pehdohmance c h a n g e and w i t h
e b b e n t i a l l y t h e dame pehdohmance w i t h c h a n g e i n gab p o h t b i z e .

We t h i n k t h a t y o u h I F G w i l l buhn domewhat l i k e w a b t e ' h y d h o g e n


w h i c h hub been b ~ c c e b b d ~ l lbuhned y i n t h i b model. T h e mobt
b e v e h e phobtem we a n t i c i p a t e i b e x z k e m e l y b h o h t dlame
h e b u t t i n g i n h i g h combubtoh t e m p e h a t u h e . Some changeb ' i n
c o n b t h u c t i o n m a t e h i a l b a h e ubed w i t h h y d h o g e n b u h n i n g u n i t 4
t o h e b i b t t h e h i g h e h tempehatuheb.

S p e c i d i c a l l y we e x p e c t i t w o u l d be d e b i h e a b l e t o i n c h c a b e
t h e gab p o h t b i z e b doh youh 275 8 . t . u . gab doh d e c h e a d c d
t u h b u l e n c e i n t h e g a b l a i h m i x i n g z o n e and t o h e p l a c e t h e
b t a n d a h d d l a m e h o l d i n g d i d dub eh w i t h h i g heh t e m p e h a t u h e
matehial. I t may be dound necebbahy t o h e p l a c e t h e dlame
cone hedhactohy (dhy oven) w i t h h i g h e h tempehatute he6hactoky.

To keep t h e gas b e h v i c e phebbuhe dhom becoming e x c e b b i v e ,


you may d i n d i t necebbahy t o h e p l a c e t h e e x i b t i n g 3" v a l v e t h a i n
w i t h 4" componenx2 h a t e d doh t h e a c t u a l gab phebbuhe. The 3"

351 - 21st STREET MONROE. WISCONSIN 53566 608-325-3141 TWX: 910-280-2870

C-9

I N S T I T U T E 0 F G A S T E C H N O L O G Y
Page 2
ffamid A. A b b a b i
O c t o b e h 2 , 1979
IE industrial
:,oeustlon,

V5055 v a l v e i b h a t e d d o h 5 PSI maximum. W i t h 2 7 5 - 8 . t . u . gab


Rhe V p w o u l d e x c e e d t h a t . I t w o u l d a l b o be d e b i h e a b l e t o
h e p l a c e t h e 4" R.P. t h h o t t l e v a l u e w i t h u 4" d u l l p o h t va.eve.

E n l a h g i n g t h e 6 i x e d d i a m e t e h gab p o h t b t o a c c o m o d a t e 275
B . t . u . gab w o u l d h a v e a d e t h i m e n t a l e 6 6 e c t u p o n t h e a b i l i t y
t o d i k e n a t u t a l gad ad a n a l t e h n a t e . Foh t h a t h e a d o n you
m i g h t 6 i n d i t d e b i h e a b l e t o d e b i g n doh a comphomide b h o u l d
you w i b h t o m a i n t a i n n a t u h a l gab .d.tandby c a p a b i l i t y .

Babed u p o n e x p e h i e n c e w i t h h y d i o g e n d u e l and h e c e n t e x p e h i e n c e b
w i t h 1 b 0 / 2 0 0 B . 2 . u . wood buded phoduce-k gab we b e l i e v e youh
gab w i l l buhn b u c c e b b 6 u l l y , b u t t h e phoblemb w i l l be i n
d e l i v e h i n g t h e IFG gab t o t h e b o i l e k and p h a c t i c a t c o n b i d e h a t i o n
06 accomodating a l t e h n a t c duels. An e n c l o b ed t e p h . i n t bhowb
t h e d c h e m a t i c ahhangement 0 6 t h e buhneh.

We h o p e you w i l l k e e p ub indohmed 06 youh p h o j e c t and w i l l


l e t us know how w e m i g h t h e l p y o u .

Vehy t h u t y y o u h b ,

Richahd C . W h i g h t
C0nb u l t i n g E n g i n e e h

cc: T . Hanna; I. Fletcheh; Poweh E q u i p m e n t

Enclobuhe

C-10

0 F G A S T E C H N O L O G Y
CORPORATION M AAO N@

w- MUNCIE,
TEL.(317)
INDIANA
284-3304 .
47302
TELEX 1 7 - 3 9 2
Industrial Combustion Equipment bnd Valves

October 10, 1979

institute of Gas Technology


3424 South State Street
IIT Center
Chicago, Illinois 60616

Attn: Harnid A. Abbasi


Chemical Engineer
I
SUBJECT: MLGW PROJECT/MAXON BURNERS

Dear Mr. Abbasi:

Your letter of September 24th requested our recommendation regarding possible


modifications to burners that were originally designed f o r use with natural gas,
and would now be using an industrial fuel gas.

The Maxon VFH Burner installed at Cargill Inc. , 1877 Channel Ave. , would - not
be recomm.ended f o r use with the industrial fuel gas shown in Table I of your
specification sheet. The high hydrogen and carbon monoxide content of the gas
would cause i t to burn very rapidly and thereby tend to overheat the face of the
VFH Burner. We would recommend the VFH ~ u r h e be r replaced by our Series
"66" AL5 Burner which allows a slower combustion of the gas to take place.
The "6611 Burner is not a 100% premix type burner, such a s the VFH; rather i t
uses a progressive aeration pattern which allows a slower burning of the fuel.
Catalog literature on the SERIES lt661t~ u r n e is
r enclosed for your review.

If we can be of further assistance in this matter, please give u s a call.

Yours truly,

MAXON CORPORATION

Manager of ~ a r kting
e l/ i/

cc: D. E. Waid

Enclosures: Catalog Page 2413, Bulletin 2400 & Bulletin 5100


C-11

I N S T I T U T E 0 F G A S T . E C H N O L O ' G Y
NORTH AMERICAN M FG. C O .
1216) 2 7 1 - ~ 0 0 0
TELEX .98-5510
'

4455 E A S T 7
1
' STREET CLEVELAND, O H 44105 USA CABLE NORTHAMCO '

October 15, 1979

Mr. Hamid A. Abbasi


chemical Engineer
Institute of Gas Technology
3424 South State Street . .
Chicago, IL 60616

Dear Mr. Abbasi:

This is inAregard to your September 24 letter about the DOE


experiment with Industrial Fuel'Gas at Memphis Light, Gas, and Water
Company. I am sorry that it has taken so long to get back to you
.on Lhis project. Attached is a photocopy of'a memo from our Mr. Ralph
Niemira, evaluating the chances of success with IFG to existing burners
at 5 installations in the Memphis area,

The answers are:


The 6795 burner at Quaker Oats will burn the IFG,
The 4988 at Quaker Oats will not burn the IFG.
All,others are questionable.

Concerning the 214-8B and 6514-8B burners at Beckman Lab and Humble-
Exxon, you will certainly want to remove the oil atomizers from the gas
tubes when burning IFG. Further, you need to determine if the 8, 14, and
16 osi gas pressures at the burners are really measured at the burner
inlet or upstream of the limiting'orifice valves. Also,are these gas
pressures the pressures the present pressures or the ones you anticipate
with the new fuel? I feel that you have people that can evaluate the
pressure losses through the regulators and gas train to answer the above
questions and that from Ralph ~iemira's explanation you can decide whether
a burner modification will be necessary.

I hope that with the above information relative to our evaluation


of the gas interchangeability on our burners, your IGT gas engineers can
make the rest of the necessary determinations.

Enclosed is a printout from our STOIC computer program, which provides


quite a bit of usG2ul information relative to the proposed Memphis IFG.
Good Luck on this project.
Sincerely,
. .

Richard J. Reed
Techni.ca1 Director
Enclosures
cc: Don Moreland, Ralph Niemira, Greg Wendzicki

I N S T I T U T E 0 F G A S T E C H N O L O G Y
Peabody Engineering Corp.
39 Maple Tree'Avenue!Stamford.'Connecticut 06906

October 1 5 , 1.979

Mr. Hamid A. Abbasi


I n s t i t u t e o f Gas Technology
3424 South S t a t e S t r e e t
I.I.T. Center
Chicago, I L 60616

I, .
I

Peab'Tdy Engineering
Dear M r . Abbasi:
We.have your l e t t e r d a t e d September' 2 4 , 1979, , t r a n s m i t t e d
t o u s by M r . Black o f Pea'body G o r d o n - P i a t t .
W e have reviewed your d a t a c o v e r i n g i n d u s t r i a l f u e l g a s
h a v i n g a p p r o x i m a t e l y 2 7 5 BTU/cf. and f i n d t h a t t h i s g a s
c a n be u s e d w i t h Peabody g a s b u r n e r ' s . I t w i l l b e
n e c e s s a r y t h a t t h e . d r i l l i n g a r e a b e ' I n c r e a s e d and a s k e d
t h a t t h e g a s be c l e a n a n d ' d r y t o p r e v e n ' t p l u. g g i n g o f t h e
.

gas o r i f i c e s .
When t h i s g a s becomes a v a i l a b l e a t t h e s p e c i f i c i n s t a l l a - .
t i o n , w e w i l l be g l a d t o a s s i s t you w i t h i n f o r m a t i o n r e l -
a t i v e t o revised drilling.
If w e c a n be o f a n y f u r t h e r a s s i s t a n c e , p l e a s e . f e e 1 f r e e
t o contact the w r i t e r .

Yours v e r y t r u l y ,

C-13
I N S T I T U T E 0 F G A S T E C H N O L O G Y
. ,
I m m
.
610 INDUSTRIAL ROAD
ENGINEERING 81 MANUFACTURING CO., INC.
DRAWER 748 W WINFIELD, KANSAS 67156 W PHONE (316) 221-7464

O c t o b e r 1 7 , 1979

I n s t i t u t e of Gas Technology
3424 South S t a t e S t r e e t
I I T Center
C h i c a g o , I l l i n o i s 60616

Attention: Hamid A . A b b a s i , Chemical E n g i n e e r

Subject: I n d u s t r i a l F u e l Gas A p p l i c a t i o n

Reference: Your l e t t e r d a t e d September 2 4 , 1979

Gentlemen:

We h a v e reviewed t h e p r o p e r t i e s of t h e i n d u s t r i a l f u e l g a s and t h e
a p p l i c a t i o n of t h a t g a s t o t h e b u r n e r s m a n u f a c t u r e d by u s mentioned i n
y o u r above r e f e r e n c e d l e t t e r . We do f e e l t h a t t h e IFG g a s c a n b e u s e d
on t h e e x i s t i n g b u r n e r s w i t h some m o d i f i c a t i o n s . The B a p t i s t H o s p i t a l ,
M e t h o d i s t H o s p i t a l , and St.. J o s e p h H o s p i t a l a l l h a v e "RD" t y p e b u r n e r s ,
which a r e a h i g h p r e s s u r e g a s gun t y p e of b u r n e r . To u s e t h e s e b u r n e r s
w i t h o u t m o d i f i c a t i o n t h e e x i s t i n g o p e r a t i n g g a s gun p r e s s u r e f o r n a t u r a l
g a s would h a v e t o b e m u l t i p l i e d by a p p r o x i m a t e l y 1 1 . 2 , i n o r d e r t o o b t a i n
t h e e q u i v a l e n t BTU f l o w r a t e of n a t u r a l g a s . For o p e r a t i n g r e a s o n s , we do
n o t recommend i n c r e a s i n g t h e o r i f i c e p r e s s u r e by t h a t l a r g e of a m u l t i p l i e r .
I n l i e u of t h e a b o v e , we would recommend t h a t t h e g a s gun t i p s b e r e p l a c e d
w i t h new t i p s w i t h o r i f i c e s s i z e d t o o b t a i n t h e same e q u i v a l e n t BTU f l o w
r a t e a t a p p r o x i m a t e l y t h e same p r e s s u r e o r i g i n a l l y used f o r n a t u r a l g a s .
I n a d d i t i o n t o t h e above, t h e r e a r e p o s s i b i l i t i e s t h a t t h e e x i s t i n g c o n t r o l
t r a i n s i z e s may need t o b e examined f o r e x c e s s i v e p r e s s u r e l o s s w i t h t h e
i n c r e a s e i n f l o w volume.

The j o b l o c a t i o n d e s c r i b e d a s Humko S h e f f i e l d h a s HCL model b u r n e r s . T h i s


s t y l e and model of b u r n e r s a r e no l o n g e r m a n u f a c t u r e d and a r e o b s o l e t e . Since
p a r t s a r e no l o n g e r a v a i l a b l e f o r t h i s l i n e of b u r n e r s , we would h i g h l y recommend
t h a t t h i s equipment b e r e p l a c e d w i t h modern up-to-date equipment s i z e d and
d e s i g n e d t o f i r e . t h e IFG. However, a s on t h e RD b u r n e r s , t h e o r i f i c e p r e s s u r e s
would have t o b e i n c r e a s e d by a m u l t i p l i e r o f 11.2 o r t h e e x i s t i n g o r i f i c e
arrangement r e s i z e d t o o b t a i n t h e BTU f l o w r a t e a t a l o w e r p r e s s u r e . A l s o , t h e
g a s c o n t r o l t r a i n s would need t o b e examined f o r e x c e s s i v e p r e s s u r e l o s s .

We t r u s t t h e above i n f o r m a t i o n i s h e l p f u l and i f we c a n b e o f any f u r t h e r s e r v i c e ,


p l e a s e do n o t h e s i t a t e t o c o n t a c t u s .

a+ Sincerely,

L. E. Wolfe
S a l e s Manager

I N S T I T U T E 0 F G A S T E C H N O L O G Y
C/
October 4 , 1979

I n s t i t u t e o f G a s Technology
3424 S o u t h S t a t e S t r e e t
IIT Center
C h i c a g o , I L 60616

Attention: Mr. Hamid A. A b b a s i

Reference: C o n v e r s i o n from N a t u r a l Gas t o IFG


Your L e t t e r o f 9-24-79

Gentlemen:

W e h a v e r e v i e w e d t h e IFG s p e c i f i c a t i o n s a n d b u r n e r s you r e f e r e n c e d .

F o r a l l b u r n e r s you r e f e r e n c e d , % w i t h o n e e x c e p t i o n , t h e b u r n e r s w i l l
accommodate t h e IFG i f t h e c u s t o m e r w i l l r e p l a c e g a s t i p s w i t h new
t i p s d r i l l e d f o r IFG.

The o n e ' e x c e p t i o n i s o n Quaker O a t s G i r d l e r hydrogen u n i t . T h e s e


b u r n e r s w i l l r e q u i r e new g a s l i m i t i n g o r i f i c e s t o h a n d l e t h e IFG.

From o u r c a l c u l a t i o n s and t e s t f i r i n g o n s i m i l a r f u e l s , we f i n d
t h e f u e l p r e s s u r e r e q u i r e d o n IFG i s a p p r o x i m a t e l y 1 5 t i m e s t h e re-
q u i r e d n a t u r a l g a s f u e l p r e s s u r e f o r comparable h e a t r e l e a s e on
burners d r i l l e d f o r natural gas.

Such h i g h p r e s s u r e s would c a u s e s e v e r a l p r o b l e m s i n f i r i n g . The


most l i k e l y problems a r e burner i n s t a b i l i t y and extreme n o i s e
generation.

Such p r o b l e m s w i l l b e e l i m i n a t e d by r e p l a c i n g t h e g a s t i p s o n
burners.

W e a p p r e c i a t e t h e o p p o r t u n i t y t o h e l p you a n d t h e g a s c u s t o m e r s o n
projects l i k e these. I n t h i s way, we c a n e q u i p t h e b u r n e r ' s w i t h
s u i t a b l e p a r t s t o avoid problems i n o p e r a t i o n .

P l e a s e a d v i s e i f we c a n h e l p f u r t h e r .

Very t r u l y y o u r s ,

JOHN ZINK COMPANY

LRM:bjb