CLIENT LOGO
HVAC CALCULATIONS
حسابات أعمال التكييف
J13-02100
ISSUED FOR CONSTRUCTION
TABLE OF CONTENTS
U DESCRIPTION U
2. AHU-01 10 – 40
-Air System Output Data
-Air System Input Data
-Space Description
3. AHU-02 41 - 67
-Air System Output Data
-Air System Input Data
-Space Description
4. AHU-03 68 - 89
-Air System Output Data
-Air System Input Data
-Space Description
5. AHU-04 90 - 111
-Air System Output Data
-Air System Input Data
-Space Description
6. AHU-05 112 - 149
-Air System Output Data
-Air System Input Data
-Space Description
Design Parameters:
1 of 331
Hourly Profiles:
1:Profile One
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
2:Profile Two
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
3:Profile Three
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
4:Profile Four
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Assignments:
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Design 1 1 1 1 1 1 1 1 1 1 1 1
Monday 2 2 2 2 2 2 2 2 2 2 2 2
Tuesday 2 2 2 2 2 2 2 2 2 2 2 2
Wednesday 2 2 2 2 2 2 2 2 2 2 2 2
Thursday 2 2 2 2 2 2 2 2 2 2 2 2
Friday 2 2 2 2 2 2 2 2 2 2 2 2
Saturday 3 3 3 3 3 3 3 3 3 3 3 3
Sunday 4 4 4 4 4 4 4 4 4 4 4 4
Holiday 4 4 4 4 4 4 4 4 4 4 4 4
Hourly Profiles:
1:Profile One
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
2:Profile Two
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
3:Profile Three
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
4:Profile Four
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Assignments:
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Design 1 1 1 1 1 1 1 1 1 1 1 1
Monday 2 2 2 2 2 2 2 2 2 2 2 2
Tuesday 2 2 2 2 2 2 2 2 2 2 2 2
Wednesday 2 2 2 2 2 2 2 2 2 2 2 2
Thursday 2 2 2 2 2 2 2 2 2 2 2 2
Friday 2 2 2 2 2 2 2 2 2 2 2 2
Saturday 3 3 3 3 3 3 3 3 3 3 3 3
Sunday 4 4 4 4 4 4 4 4 4 4 4 4
Holiday 4 4 4 4 4 4 4 4 4 4 4 4
2 of 331
Hourly Profiles:
1:Profile One
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value O O O O O O O O O O O O O O O O O O O O O O O O
2:Profile Two
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value O O O O O O O O O O O O O O O O O O O O O O O O
3:Profile Three
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value O O O O O O O O O O O O O O O O O O O O O O O O
4:Profile Four
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value O O O O O O O O O O O O O O O O O O O O O O O O
O = Occupied; U = Unoccupied
Assignments:
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Design 1 1 1 1 1 1 1 1 1 1 1 1
Monday 2 2 2 2 2 2 2 2 2 2 2 2
Tuesday 2 2 2 2 2 2 2 2 2 2 2 2
Wednesday 2 2 2 2 2 2 2 2 2 2 2 2
Thursday 2 2 2 2 2 2 2 2 2 2 2 2
Friday 2 2 2 2 2 2 2 2 2 2 2 2
Saturday 3 3 3 3 3 3 3 3 3 3 3 3
Sunday 4 4 4 4 4 4 4 4 4 4 4 4
Holiday 4 4 4 4 4 4 4 4 4 4 4 4
Hourly Profiles:
1:Profile One
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value O O O O O O O O O O O O O O O O O O O O O O O O
2:Profile Two
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value O O O O O O O O O O O O O O O O O O O O O O O O
3:Profile Three
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value O O O O O O O O O O O O O O O O O O O O O O O O
4:Profile Four
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value O O O O O O O O O O O O O O O O O O O O O O O O
O = Occupied; U = Unoccupied
3 of 331
Assignments:
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Design 1 1 1 1 1 1 1 1 1 1 1 1
Monday 2 2 2 2 2 2 2 2 2 2 2 2
Tuesday 2 2 2 2 2 2 2 2 2 2 2 2
Wednesday 2 2 2 2 2 2 2 2 2 2 2 2
Thursday 2 2 2 2 2 2 2 2 2 2 2 2
Friday 2 2 2 2 2 2 2 2 2 2 2 2
Saturday 3 3 3 3 3 3 3 3 3 3 3 3
Sunday 4 4 4 4 4 4 4 4 4 4 4 4
Holiday 4 4 4 4 4 4 4 4 4 4 4 4
Hourly Profiles:
1:Profile One
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
2:Profile Two
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
3:Profile Three
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
4:Profile Four
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Assignments:
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Design 1 1 1 1 1 1 1 1 1 1 1 1
Monday 2 2 2 2 2 2 2 2 2 2 2 2
Tuesday 2 2 2 2 2 2 2 2 2 2 2 2
Wednesday 2 2 2 2 2 2 2 2 2 2 2 2
Thursday 2 2 2 2 2 2 2 2 2 2 2 2
Friday 2 2 2 2 2 2 2 2 2 2 2 2
Saturday 3 3 3 3 3 3 3 3 3 3 3 3
Sunday 4 4 4 4 4 4 4 4 4 4 4 4
Holiday 4 4 4 4 4 4 4 4 4 4 4 4
Hourly Profiles:
1:Profile One
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
2:Profile Two
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
3:Profile Three
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
4:Profile Four
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
4 of 331
Assignments:
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Design 1 1 1 1 1 1 1 1 1 1 1 1
Monday 2 2 2 2 2 2 2 2 2 2 2 2
Tuesday 2 2 2 2 2 2 2 2 2 2 2 2
Wednesday 2 2 2 2 2 2 2 2 2 2 2 2
Thursday 2 2 2 2 2 2 2 2 2 2 2 2
Friday 2 2 2 2 2 2 2 2 2 2 2 2
Saturday 3 3 3 3 3 3 3 3 3 3 3 3
Sunday 4 4 4 4 4 4 4 4 4 4 4 4
Holiday 4 4 4 4 4 4 4 4 4 4 4 4
Hourly Profiles:
1:Profile One
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
2:Profile Two
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
3:Profile Three
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
4:Profile Four
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Assignments:
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Design 1 1 1 1 1 1 1 1 1 1 1 1
Monday 2 2 2 2 2 2 2 2 2 2 2 2
Tuesday 2 2 2 2 2 2 2 2 2 2 2 2
Wednesday 2 2 2 2 2 2 2 2 2 2 2 2
Thursday 2 2 2 2 2 2 2 2 2 2 2 2
Friday 2 2 2 2 2 2 2 2 2 2 2 2
Saturday 3 3 3 3 3 3 3 3 3 3 3 3
Sunday 4 4 4 4 4 4 4 4 4 4 4 4
Holiday 4 4 4 4 4 4 4 4 4 4 4 4
Hourly Profiles:
1:Profile One
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
2:Profile Two
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
3:Profile Three
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
4:Profile Four
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
5 of 331
Assignments:
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Design 1 1 1 1 1 1 1 1 1 1 1 1
Monday 2 2 2 2 2 2 2 2 2 2 2 2
Tuesday 2 2 2 2 2 2 2 2 2 2 2 2
Wednesday 2 2 2 2 2 2 2 2 2 2 2 2
Thursday 2 2 2 2 2 2 2 2 2 2 2 2
Friday 2 2 2 2 2 2 2 2 2 2 2 2
Saturday 3 3 3 3 3 3 3 3 3 3 3 3
Sunday 4 4 4 4 4 4 4 4 4 4 4 4
Holiday 4 4 4 4 4 4 4 4 4 4 4 4
6 of 331
EXTERIOR WALL
Wall Details
Outside Surface Color Medium
Absorptivity 0.675
Overall U-Value 0.300 W/(m²-°K)
INTERNAL WALL
Wall Details
Outside Surface Color Medium
Absorptivity 0.675
Overall U-Value 3.846 W/(m²-°K)
7 of 331
Floor
Roof Details
Outside Surface Color Medium
Absorptivity 0.675
Overall U-Value 3.087 W/(m²-°K)
Roof
Roof Details
Outside Surface Color Medium
Absorptivity 0.675
Overall U-Value 0.300 W/(m²-°K)
8 of 331
Window Details:
Detailed Input No
Height 0.50 m
Width 1.00 m
Overall U-Value 1.400 W/(m²-°K)
Overall Shade Coefficient 0.300
9 of 331
10 of 331
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated
12 of 331
13 of 331
1. General Details:
Air System Name AHU-01
Equipment Type Chilled Water AHU
Air System Type VAV
Number of zones 10
2. System Components:
Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm
% Airflow 100 90 80 70 60 50
% kW 100 77 57 42 30 21
% Airflow 40 30 20 10 0
% kW 15 13 10 7 5
% Airflow 100 90 80 70 60 50
% kW 100 77 57 42 30 21
% Airflow 40 30 20 10 0
% kW 15 13 10 7 5
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
1-G-053 CONTROL (MRI) x1
1-G-055 EQUIPMENT x1
1-G-056 MRI x1
Zone 2: Zone 2
1-G-060 CONTROL (CT) x1
1-G-062 CT SCAN x1
1-G-063 EQUIPMENT ROOM x1
1-G-064 CHANGING x1
Zone 3: Zone 3
1-G-061 RECEPTION x1
14 of 331
1-G-069 CORRIDOR x1
1-G-072 CLEAN UTILITY x1
1-G-077 PACS ROOM x1
1-G-080 LOBBY x1
Zone 4: Zone 4
1-G-058 PREP/RECOV. CUB x1
1-G-059 CHANGING x1
Zone 5: Zone 5
1-G-070 CONTROL (FLUOR.) x1
1-G-071 FLUOROSCOPY x1
1-G-065 CHANGING x1
Zone 6: Zone 6
1-G-073 CONTROL (X-RAY) x1
1-G-074 CHANGING x1
1-G-075 GENERAL X-RAY x1
Zone 7: Zone 7
1-G-067 VIEWING - REPORT x1
Zone 8: Zone 8
1-G-068 RADIOLOGIST OFF. x1
Zone 9: Zone 9
1-G-078 ULTRASOUND x1
Zone 10: Zone 10
1-G-082 ULTRASOUND x1
Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %
5. Equipment Data
No Equipment Data required for this system.
16 of 331
1. General Details:
Floor Area 13.4 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15 % of supply air
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 13.4 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
(No partition data).
17 of 331
1-G-055 EQUIPMENT
1. General Details:
Floor Area 13.9 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15 % of supply air
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 28.1 0 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 13.9 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
(No partition data).
18 of 331
1-G-056 MRI
1. General Details:
Floor Area 34.4 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 55.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 34.4 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
(No partition data).
19 of 331
1. General Details:
Floor Area 30.8 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 50.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 30.8 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
(No partition data).
20 of 331
1-G-059 CHANGING
1. General Details:
Floor Area 3.2 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Storage room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 3.2 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
(No partition data).
21 of 331
1. General Details:
Floor Area 4.9 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15 % of supply air
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 4.9 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
(No partition data).
22 of 331
1-G-061 RECEPTION
1. General Details:
Floor Area 9.2 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 20.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 9.2 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
(No partition data).
23 of 331
1-G-062 CT SCAN
1. General Details:
Floor Area 32.1 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 70.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 24.6 0 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 32.1 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
(No partition data).
24 of 331
1. General Details:
Floor Area 4.4 m²
Avg. Ceiling Height 2.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15 % of supply air
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 10.0 0 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 4.4 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
(No partition data).
25 of 331
1-G-064 CHANGING
1. General Details:
Floor Area 3.5 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Storage room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 3.5 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
(No partition data).
26 of 331
1-G-065 CHANGING
1. General Details:
Floor Area 3.6 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Storage room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 3.6 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
(No partition data).
27 of 331
1. General Details:
Floor Area 12.6 m²
Avg. Ceiling Height 2.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 12.6 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
(No partition data).
28 of 331
1. General Details:
Floor Area 8.1 m²
Avg. Ceiling Height 2.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 8.1 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
(No partition data).
29 of 331
1-G-069 CORRIDOR
1. General Details:
Floor Area 38.1 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 60.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 38.1 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 3.0 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
30 of 331
1. General Details:
Floor Area 3.2 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15 % of supply air
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 3.2 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
(No partition data).
31 of 331
1-G-071 FLUOROSCOPY
1. General Details:
Floor Area 30.4 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 110.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 17.0 24 0 0
N 4.0 0 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 30.4 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 8.0 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
32 of 331
1. General Details:
Floor Area 3.1 m²
Avg. Ceiling Height 2.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 3.1 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
(No partition data).
33 of 331
1. General Details:
Floor Area 3.4 m²
Avg. Ceiling Height 2.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15 % of supply air
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 3.4 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
(No partition data).
34 of 331
1-G-074 CHANGING
1. General Details:
Floor Area 3.2 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Storage room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 7.4 0 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 3.2 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 2.7 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
35 of 331
1. General Details:
Floor Area 16.5 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 45.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 17.0 0 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 16.5 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
(No partition data).
36 of 331
1. General Details:
Floor Area 4.2 m²
Avg. Ceiling Height 3.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Storage room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 4.2 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 9.2 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
37 of 331
1-G-078 ULTRASOUND
1. General Details:
Floor Area 13.6 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 55.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 13.6 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 23.5 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
38 of 331
1-G-080 LOBBY
1. General Details:
Floor Area 2.6 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 5.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 2.6 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
(No partition data).
39 of 331
1-G-082 ULTRASOUND
1. General Details:
Floor Area 14.5 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 55.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 15.2 0 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 14.5 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 16.5 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
40 of 331
41 of 331
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated
42 of 331
43 of 331
1. General Details:
Air System Name AHU-02
Equipment Type Chilled Water AHU
Air System Type VAV
Number of zones 12
2. System Components:
Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm
% Airflow 100 90 80 70 60 50
% kW 100 77 57 42 30 21
% Airflow 40 30 20 10 0
% kW 15 13 10 7 5
% Airflow 100 90 80 70 60 50
% kW 100 77 57 42 30 21
% Airflow 40 30 20 10 0
% kW 15 13 10 7 5
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
2-G-014 RECEPTION x1
2-G-015 WAITING AREA x1
2-G-023 CORRIDOR x1
2-G-024 CLEAN UTILITY x1
2-G-027 PANTRY x1
Zone 2: Zone 2
2-G-019 ISOLATION CUBIC. x1
2-G-021 AIRLOCK x1
Zone 3: Zone 3
2-G-016 TRIAG x1
44 of 331
Zone 4: Zone 4
2-G-030 CUBICLES x1
Zone 5: Zone 5
2-G-029 CUBICLES x1
Zone 6: Zone 6
2-G-022 RESUSCITATION RM x1
Zone 7: Zone 7
2-G-032 ELEC ROOM x1
Zone 8: Zone 8
2-G-031 CORRIDOR x1
2-G-039 STORE x1
Zone 9: Zone 9
2-G-026 PHYISICIANS OFF. x1
Zone 10: Zone 10
2-G-036 MINOR OP x1
2-G-037 SCRUB UP x1
2-G-088 STERILIZING ROOM x1
Zone 11: Zone 11
2-G-038 PLASTERING/CAST. x1
Zone 12: Zone 12
2-G-018 Soiled Work x1
2-FA x1
T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)
1 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
2 23.0 26.0 22.0 18.0 2.00 100 145.0 0.0
3 23.0 26.0 22.0 18.0 2.00 100 155.0 0.0
4 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
5 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
6 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
7 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
8 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
9 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
10 22.0 26.0 21.0 18.0 2.00 100 740.0 0.0
11 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
12 24.0 26.0 22.0 18.0 2.00 100 35.0 0.0
Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %
5. Equipment Data
No Equipment Data required for this system.
46 of 331
2-FA
1. General Details:
Floor Area 0.0 m²
Avg. Ceiling Height 2.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 440.0 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 0.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule None Latent 60.1 W/person
Schedule None
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
47 of 331
2-G-014 RECEPTION
1. General Details:
Floor Area 8.0 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 30.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 8.0 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
(No partition data).
48 of 331
1. General Details:
Floor Area 27.7 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 40.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 9.5 12 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 27.7 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
(No partition data).
49 of 331
2-G-016 TRIAG
1. General Details:
Floor Area 11.3 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 40.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 11.0 15 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 11.3 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
(No partition data).
50 of 331
1. General Details:
Floor Area 5.4 m²
Avg. Ceiling Height 2.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 5.4 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition (No partition data).
Area 4.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 23.9 °C
Ambient at Space Max Temp 35.0 °C
Uncondit. Space Min Temp 23.9 °C
Ambient at Space Min Temp 12.8 °C
51 of 331
1. General Details:
Floor Area 11.3 m²
Avg. Ceiling Height 2.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 40.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING 24/7 Latent 35.2 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 11.0 15 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 11.3 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
(No partition data).
52 of 331
2-G-021 AIRLOCK
1. General Details:
Floor Area 2.7 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 5.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 2.7 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
(No partition data).
53 of 331
2-G-022 RESUSCITATION RM
1. General Details:
Floor Area 16.4 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 75.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 11.1 15 0 0
S 11.2 15 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 16.4 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 7.0 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
54 of 331
2-G-023 CORRIDOR
1. General Details:
Floor Area 61.7 m²
Avg. Ceiling Height 2.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 95.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 5.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 61.7 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
(No partition data).
55 of 331
1. General Details:
Floor Area 7.1 m²
Avg. Ceiling Height 2.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 7.1 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
(No partition data).
56 of 331
1. General Details:
Floor Area 8.8 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 8.8 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
(No partition data).
57 of 331
2-G-027 PANTRY
1. General Details:
Floor Area 3.4 m²
Avg. Ceiling Height 2.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 3.80 L/(s-m²)
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 3.4 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
(No partition data).
58 of 331
2-G-029 CUBICLES
1. General Details:
Floor Area 16.5 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 70.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 20.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING 24/7 Latent 35.2 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 22.6 31 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 16.5 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
(No partition data).
59 of 331
2-G-030 CUBICLES
1. General Details:
Floor Area 24.8 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 85.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6.0 People
Wattage 20.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING 24/7 Latent 35.2 W/person
Schedule LIGHTING 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 24.9 34 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 24.8 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
(No partition data).
60 of 331
2-G-031 CORRIDOR
1. General Details:
Floor Area 38.5 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 60.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 38.5 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
(No partition data).
61 of 331
1. General Details:
Floor Area 20.6 m²
Avg. Ceiling Height 3.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Electrical equipment room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 36.9 41 0 0
E 7.8 0 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 20.6 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
(No partition data).
62 of 331
2-G-036 MINOR OP
1. General Details:
Floor Area 25.9 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 155.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 25.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 25.9 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
(No partition data).
63 of 331
2-G-037 SCRUB UP
1. General Details:
Floor Area 4.3 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 4.3 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
(No partition data).
64 of 331
2-G-038 PLASTERING/CAST.
1. General Details:
Floor Area 17.5 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 25.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 17.5 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 20.5 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 20.0 °C
Ambient at Space Min Temp 15.0 °C
65 of 331
2-G-039 STORE
1. General Details:
Floor Area 10.0 m²
Avg. Ceiling Height 4.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Storage room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 6.6 13 0 0
N 5.5 0 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 10.0 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
(No partition data).
66 of 331
1. General Details:
Floor Area 4.0 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 4.0 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
(No partition data).
67 of 331
68 of 331
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated
69 of 331
70 of 331
1. General Details:
Air System Name AHU-03
Equipment Type Chilled Water AHU
Air System Type VAV
Number of zones 11
2. System Components:
Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm
% Airflow 100 90 80 70 60 50
% kW 100 77 57 42 30 21
% Airflow 40 30 20 10 0
% kW 15 13 10 7 5
% Airflow 100 90 80 70 60 50
% kW 100 77 57 42 30 21
% Airflow 40 30 20 10 0
% kW 15 13 10 7 5
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
3-M-25 AIR LOCK x1
Zone 2: Zone 2
3-M-26&69 SCOPE WASHROOM x1
3-M-53 PROCED. RM ENDOSC x1
Zone 3: Zone 3
3-M-54 VASCULAR CLINIC x1
Zone 4: Zone 4
3-M-36 PATIENT PREP/REC x1
3-M-37 PATIENT PREP/REC x1
Zone 5: Zone 5
71 of 331
T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)
1 22.0 26.0 21.0 18.0 2.00 100 0.0 0.0
2 22.0 26.0 21.0 18.0 2.00 100 770.0 0.0
3 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
4 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
5 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
6 22.0 26.0 21.0 18.0 2.00 100 480.0 0.0
7 22.0 26.0 21.0 18.0 2.00 100 0.0 0.0
8 22.0 26.0 21.0 18.0 2.00 100 1530.0 0.0
9 22.0 26.0 21.0 18.0 2.00 100 935.0 0.0
10 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
11 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %
5. Equipment Data
No Equipment Data required for this system.
73 of 331
3-Balanced FA
1. General Details:
Floor Area 0.0 m²
Avg. Ceiling Height 2.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2940.0 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 0.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule None Latent 60.1 W/person
Schedule None
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
74 of 331
1. General Details:
Floor Area 5.3 m²
Avg. Ceiling Height 2.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
75 of 331
1. General Details:
Floor Area 7.8 m²
Avg. Ceiling Height 2.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 30.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 8.5 12 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
76 of 331
1. General Details:
Floor Area 13.6 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 60.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 12.0 18 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
77 of 331
1. General Details:
Floor Area 14.1 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 65.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 3.8 7 0 0
N 12.1 21 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 11.4 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
78 of 331
1. General Details:
Floor Area 4.3 m²
Avg. Ceiling Height 2.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 5.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 9.1 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
79 of 331
3-M-34 RECEPTION
1. General Details:
Floor Area 18.8 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 30.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
80 of 331
1. General Details:
Floor Area 8.8 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
81 of 331
1. General Details:
Floor Area 9.8 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
82 of 331
3-M-38 MICROBIOLOGY
1. General Details:
Floor Area 17.5 m²
Avg. Ceiling Height 2.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 50.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
83 of 331
1. General Details:
Floor Area 12.2 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 110.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 9.4 15 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
84 of 331
3-M-42 LABORATORY
1. General Details:
Floor Area 89.2 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 265.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 9.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 46.8 68 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
85 of 331
3-M-43 PHLEBOTOMY
1. General Details:
Floor Area 5.0 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 5.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
86 of 331
3-M-45 PHLEBOTOMY
1. General Details:
Floor Area 4.8 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 5.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
87 of 331
1. General Details:
Floor Area 26.1 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 145.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 5.0 People
Wattage 25.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 14.4 21 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
88 of 331
1. General Details:
Floor Area 18.0 m²
Avg. Ceiling Height 2.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 60.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 16.0 23 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
89 of 331
90 of 331
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated
92 of 331
93 of 331
1. General Details:
Air System Name AHU-04
Equipment Type Chilled Water AHU
Air System Type VAV
Number of zones 14
2. System Components:
Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm
% Airflow 100 90 80 70 60 50
% kW 100 77 57 42 30 21
% Airflow 40 30 20 10 0
% kW 15 13 10 7 5
% Airflow 100 90 80 70 60 50
% kW 100 77 57 42 30 21
% Airflow 40 30 20 10 0
% kW 15 13 10 7 5
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
4-M-01 PODIATRY CLINIC x1
Zone 2: Zone 2
4-M-02 PEDIATRIC DIABET. x1
Zone 3: Zone 3
4-M-03 ADULT DIABET. CLC x1
Zone 4: Zone 4
4-M-04 ADULT DIABET. CLC x1
Zone 5: Zone 5
4-M-05 NEPHROLOGY CLC x1
Zone 6: Zone 6
94 of 331
T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)
1 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
2 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
3 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
4 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
5 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
6 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
7 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
8 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
9 24.0 26.0 22.0 18.0 2.00 100 0.0 0.0
10 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
11 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
12 24.0 26.0 22.0 18.0 2.00 100 0.0 0.0
13 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
14 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %
5. Equipment Data
No Equipment Data required for this system.
96 of 331
1. General Details:
Floor Area 18.2 m²
Avg. Ceiling Height 2.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 60.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 17.3 17 0 0
NW 9.5 0 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
97 of 331
1. General Details:
Floor Area 16.1 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 65.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 16.2 16 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
98 of 331
1. General Details:
Floor Area 20.1 m²
Avg. Ceiling Height 2.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 80.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 13.0 13 0 0
WSW 13.0 13 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
99 of 331
1. General Details:
Floor Area 15.4 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 55.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 13.0 13 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
100 of 331
1. General Details:
Floor Area 16.9 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 55.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 13.9 14 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
101 of 331
1. General Details:
Floor Area 17.6 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 55.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 14.4 14 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
102 of 331
1. General Details:
Floor Area 15.4 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 55.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 13.0 13 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
103 of 331
1. General Details:
Floor Area 13.6 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 40.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 11.2 11 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
104 of 331
1. General Details:
Floor Area 29.0 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage EDUCATION: Classroom (age 9+)
OA Requirement 1 5.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 21.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 17.5 17 0 0
E 22.1 32 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
105 of 331
4-M-11 CORRIDOR
1. General Details:
Floor Area 13.0 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 20.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
106 of 331
4-M-14 OFFICE
1. General Details:
Floor Area 8.4 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
107 of 331
1. General Details:
Floor Area 28.5 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage EDUCATION: Classroom (age 9+)
OA Requirement 1 5.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 21.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 21.5 28 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
108 of 331
1. General Details:
Floor Area 6.7 m²
Avg. Ceiling Height 2.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 6.0 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
109 of 331
4-M-20 CORRIDOR
1. General Details:
Floor Area 60.7 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 105.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
110 of 331
4-M-65 ASESSMENT
1. General Details:
Floor Area 9.4 m²
Avg. Ceiling Height 2.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
111 of 331
112 of 331
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated
115 of 331
116 of 331
1. General Details:
Air System Name AHU-05
Equipment Type Chilled Water AHU
Air System Type VAV
Number of zones 26
2. System Components:
Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm
% Airflow 100 90 80 70 60 50
% kW 100 77 57 42 30 21
% Airflow 40 30 20 10 0
% kW 15 13 10 7 5
% Airflow 100 90 80 70 60 50
% kW 100 77 57 42 30 21
% Airflow 40 30 20 10 0
% kW 15 13 10 7 5
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
5-F-068 ULTRA SOUND x1
Zone 2: Zone 2
5-F-069 OB/GY CLINIC x1
Zone 3: Zone 3
5-F-072 CLEAN UTILITY x1
5-F-077 CORRIDOR x1
Zone 4: Zone 4
5-F-076 OB/GY CLINIC x1
Zone 5: Zone 5
5-F-078 PROCEDURE TRT x1
117 of 331
Zone 6: Zone 6
5-F-082 IMMUNIZATION x1
Zone 7: Zone 7
5-F-083 PEDIATRIC CLc x1
Zone 8: Zone 8
5-F-086 PEDIATRIC CLINIC x1
Zone 9: Zone 9
5-F-087 FAMILY MEDICINE x1
Zone 10: Zone 10
5-F-088 VITAL SIGN x1
Zone 11: Zone 11
5-F-091 FAMILY MEDICINE x1
Zone 12: Zone 12
5-F-095 STRESS ECG ROOM x1
Zone 13: Zone 13
5-F-096 CORRIDOR x1
Zone 14: Zone 14
5-F-097 INTERNAL MEDIC. x1
Zone 15: Zone 15
5-F-098 ECG x1
Zone 16: Zone 16
5-F-099 CARDIOLOGY CLNC. x1
Zone 17: Zone 17
5-F-104 ENT CLINIC x1
Zone 18: Zone 18
5-F-105 ENT CLINIC x1
Zone 19: Zone 19
5-F-106 CORRIDOR x1
5-F-110 CLEAN UTILITY x1
Zone 20: Zone 20
5-F-107 DENTAL SERIALIZ. x1
Zone 21: Zone 21
5-F-108 DENTAL CLINIC x1
Zone 22: Zone 22
5-F-109 DENTAL CLINIC x1
Zone 23: Zone 23
5-F-112 ENT CLINIC x1
Zone 24: Zone 24
5-F-113 FLEXIBLE CLINIC x1
Zone 25: Zone 25
5-F-115 FLEXIBLE CLINIC x1
Zone 26: Zone 26
5-F-116 DENTAL CLINIC x1
T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)
1 22.0 26.0 21.0 18.0 2.00 100 0.0 0.0
2 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
3 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
4 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
5 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
6 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
7 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
8 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
9 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
118 of 331
T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)
10 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
11 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
12 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
13 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
14 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
15 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
16 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
17 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
18 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
19 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
20 22.0 26.0 21.0 18.0 2.00 100 0.0 0.0
21 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
22 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
23 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
24 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
25 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
26 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %
5. Equipment Data
No Equipment Data required for this system.
121 of 331
1. General Details:
Floor Area 10.8 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 60.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 11.9 15 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
122 of 331
1. General Details:
Floor Area 13.6 m²
Avg. Ceiling Height 2.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 80.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 19.3 26 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
123 of 331
1. General Details:
Floor Area 6.6 m²
Avg. Ceiling Height 2.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
124 of 331
1. General Details:
Floor Area 15.7 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 55.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 17.4 7 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 15.7 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
125 of 331
5-F-077 CORRIDOR
1. General Details:
Floor Area 56.3 m²
Avg. Ceiling Height 3.3 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 105.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 40.0 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
126 of 331
1. General Details:
Floor Area 11.6 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 35.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 11.6 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
127 of 331
5-F-082 IMMUNIZATION
1. General Details:
Floor Area 9.1 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 45.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 10.5 8 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 9.1 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
128 of 331
1. General Details:
Floor Area 14.2 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 60.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 15.8 13 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 14.2 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
129 of 331
1. General Details:
Floor Area 15.0 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 65.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 16.6 13 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 15.0 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
130 of 331
1. General Details:
Floor Area 15.2 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 65.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 16.8 13 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
131 of 331
1. General Details:
Floor Area 7.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
132 of 331
1. General Details:
Floor Area 14.6 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 60.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 11.7 9 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 10.3 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
133 of 331
1. General Details:
Floor Area 9.4 m²
Avg. Ceiling Height 2.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 40.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
134 of 331
5-F-096 CORRIDOR
1. General Details:
Floor Area 19.9 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 30.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
135 of 331
1. General Details:
Floor Area 13.2 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 75.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 10.5 8 0 0
N 8.5 7 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
136 of 331
5-F-098 ECG
1. General Details:
Floor Area 13.6 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 60.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 12.7 10 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
137 of 331
1. General Details:
Floor Area 16.8 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 30.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 15.8 12 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
138 of 331
1. General Details:
Floor Area 17.9 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 30.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 17.2 13 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 6.3 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
139 of 331
1. General Details:
Floor Area 17.1 m²
Avg. Ceiling Height 2.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 30.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 16.8 13 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
140 of 331
5-F-106 CORRIDOR
1. General Details:
Floor Area 41.9 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 65.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
141 of 331
1. General Details:
Floor Area 6.9 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
142 of 331
1. General Details:
Floor Area 15.4 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 20.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 3.4 0 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 13.2 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
143 of 331
1. General Details:
Floor Area 13.8 m²
Avg. Ceiling Height 2.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 35.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 15.8 19 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 7.8 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
144 of 331
1. General Details:
Floor Area 3.0 m²
Avg. Ceiling Height 2.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 5.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
145 of 331
1. General Details:
Floor Area 17.8 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 25.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 16.8 13 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 3.5 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
146 of 331
1. General Details:
Floor Area 15.0 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 40.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 14.0 18 0 0
N 14.4 0 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 6.4 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
147 of 331
1. General Details:
Floor Area 13.0 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 40.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 15.0 20 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
148 of 331
1. General Details:
Floor Area 18.0 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 45.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 19.7 26 0 0
S 14.4 0 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
149 of 331
150 of 331
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated
152 of 331
153 of 331
1. General Details:
Air System Name AHU-06
Equipment Type Chilled Water AHU
Air System Type VAV
Number of zones 18
2. System Components:
Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm
% Airflow 100 90 80 70 60 50
% kW 100 77 57 42 30 21
% Airflow 40 30 20 10 0
% kW 15 13 10 7 5
% Airflow 100 90 80 70 60 50
% kW 100 77 57 42 30 21
% Airflow 40 30 20 10 0
% kW 15 13 10 7 5
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
6-F-011 ISOLATION ROOM x1
Zone 2: Zone 2
6-F-018&033 CUBIC. (1-8) x1
Zone 3: Zone 3
6-F-024 CORRIDOR&NURSE x1
6-F-025 CLEAN LINEN x1
6-F-026 PANTRY x1
6-F-021 CLEAN UTILITY x1
6-F-037 STORE x1
6-F-042 DIALYZER STORE x1
154 of 331
6-F-044 PANTRY x1
6-F-045CLEAN LINEN x1
*6-F-047 DIRTY UTILITY x1
6-F-048 CLEAN UTILITY x1
Zone 4: Zone 4
6-F-020 CUBICLES (17-19) x1
Zone 5: Zone 5
6-F-027 ISOLATION ROOM x1
Zone 6: Zone 6
6-F-039 ISOLATION ROOM x1
Zone 7: Zone 7
6-F-040 CUBICLE x1
Zone 8: Zone 8
6-F-017 OFFICE x1
Zone 9: Zone 9
6-F-046 NEPHROLOGY CLNC. x1
Zone 10: Zone 10
6-F-043 CUBICLE(9-15) x1
Zone 11: Zone 11
6-F-053 ISOLATION ROOM x1
Zone 12: Zone 12
6-F-052 ISOLATION ROOM x1
Zone 13: Zone 13
6-F-058 ISOLATION ROOM x1
Zone 14: Zone 14
6-F-032 DIALYSIS WORK SH x1
Zone 15: Zone 15
6-F-034 STAFF LOUNGE x1
Zone 16: Zone 16
6-F-041 DIALYSIS TRAIN. x1
Zone 17: Zone 17
6-F-014 PROCEDURE ROOM x1
Zone 18: Zone 18
6-F-013 AIRLOCK x1
T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)
1 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
2 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
3 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
4 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
5 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
6 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
7 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
8 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
9 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
10 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
11 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
12 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
13 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
14 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
15 24.0 26.0 22.0 18.0 2.00 100 0.0 0.0
16 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
17 22.0 26.0 21.0 18.0 2.00 100 0.0 0.0
155 of 331
T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)
18 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %
1 107.3 - 1.2 -
2 758.8 - 2.7 -
3 1507.9 - 5.3 -
4 110.6 - 0.4 -
5 92.8 - 1.0 -
6 95.2 - 1.1 -
7 42.1 - 0.3 -
8 108.7 - 0.1 -
9 167.5 - 0.5 -
10 787.6 - 2.5 -
11 96.2 - 0.2 -
12 83.5 - 0.9 -
13 97.8 - 0.3 -
14 133.2 - 0.4 -
15 162.2 - 0.9 -
16 185.0 - 0.7 -
17 210.9 - 2.1
18 50.0 - 0.6
5. Equipment Data
No Equipment Data required for this system.
157 of 331
1. General Details:
Floor Area 11.2 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 35.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 13.8 7 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 11.2 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
158 of 331
6-F-013 AIRLOCK
1. General Details:
Floor Area 4.7 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10.0 L/s/person
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule LIGHTING 24/7
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 4.7 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
159 of 331
1. General Details:
Floor Area 14.8 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 65.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 25.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
160 of 331
6-F-017 OFFICE
1. General Details:
Floor Area 10.0 m²
Avg. Ceiling Height 2.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
161 of 331
1. General Details:
Floor Area 62.7 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 210.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 16.0 People
Wattage 20.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING 24/7 Latent 35.2 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 87.0 40 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 62.7 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
162 of 331
1. General Details:
Floor Area 23.7 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 40.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6.0 People
Wattage 20.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING 24/7 Latent 35.2 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
163 of 331
1. General Details:
Floor Area 5.3 m²
Avg. Ceiling Height 2.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
164 of 331
6-F-024 CORRIDOR&NURSE
1. General Details:
Floor Area 227.0 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 350.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 15.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 186.0 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
165 of 331
1. General Details:
Floor Area 4.6 m²
Avg. Ceiling Height 2.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 5.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
166 of 331
6-F-026 PANTRY
1. General Details:
Floor Area 4.7 m²
Avg. Ceiling Height 2.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 3.80 L/(s-m²)
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
167 of 331
1. General Details:
Floor Area 9.6 m²
Avg. Ceiling Height 2.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
168 of 331
1. General Details:
Floor Area 11.9 m²
Avg. Ceiling Height 2.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 30.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 11.9 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
169 of 331
1. General Details:
Floor Area 12.2 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 70.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 5.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 7.2 9 0 0
S 16.2 13 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 12.2 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
170 of 331
6-F-037 STORE
1. General Details:
Floor Area 7.0 m²
Avg. Ceiling Height 3.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Storage room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
171 of 331
1. General Details:
Floor Area 10.0 m²
Avg. Ceiling Height 2.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 10.0 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
172 of 331
6-F-040 CUBICLE
1. General Details:
Floor Area 8.0 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 25.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING 24/7 Latent 35.2 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 8.0 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
173 of 331
1. General Details:
Floor Area 12.5 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 45.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 12.5 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
174 of 331
1. General Details:
Floor Area 9.5 m²
Avg. Ceiling Height 3.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Storage room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 9.5 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
175 of 331
6-F-043 CUBICLE(9-15)
1. General Details:
Floor Area 57.5 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 180.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 14.0 People
Wattage 20.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING 24/7 Latent 35.2 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 77.5 87 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 57.5 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 22.5 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
176 of 331
6-F-044 PANTRY
1. General Details:
Floor Area 4.4 m²
Avg. Ceiling Height 2.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15.0 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
177 of 331
6-F-045CLEAN LINEN
1. General Details:
Floor Area 4.3 m²
Avg. Ceiling Height 2.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
178 of 331
1. General Details:
Floor Area 14.6 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 45.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 14.6 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
179 of 331
1. General Details:
Floor Area 5.3 m²
Avg. Ceiling Height 2.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
180 of 331
1. General Details:
Floor Area 9.6 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 9.6 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
181 of 331
1. General Details:
Floor Area 9.4 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 12.7 14 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 9.4 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
182 of 331
1. General Details:
Floor Area 8.0 m²
Avg. Ceiling Height 3.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 10.6 12 0 0
N 5.6 7 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 8.0 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
183 of 331
184 of 331
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated
186 of 331
187 of 331
1. General Details:
Air System Name AHU-07
Equipment Type Chilled Water AHU
Air System Type VAV
Number of zones 13
2. System Components:
Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm
% Airflow 100 90 80 70 60 50
% kW 100 77 57 42 30 21
% Airflow 40 30 20 10 0
% kW 15 13 10 7 5
% Airflow 100 90 80 70 60 50
% kW 100 77 57 42 30 21
% Airflow 40 30 20 10 0
% kW 15 13 10 7 5
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
7-PH-39 CORRIDOR x1
Zone 2: Zone 2
7-PH-40&41 DOCTORS LOUNG x1
Zone 3: Zone 3
7-PH-35 STAFF REST ROOM x1
Zone 4: Zone 4
7-PH-48 MEETING ROOM x1
Zone 5: Zone 5
7-PH-49 INSURANCE COMP x1
Zone 6: Zone 6
188 of 331
T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)
1 23.0 26.0 22.0 18.0 2.00 100 185.0 0.0
2 24.0 26.0 22.0 18.0 2.00 100 305.0 0.0
3 24.0 26.0 22.0 18.0 2.00 100 0.0 0.0
4 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
5 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
6 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
7 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
8 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
9 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
10 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
11 24.0 26.0 22.0 18.0 2.00 100 0.0 0.0
12 24.0 26.0 22.0 18.0 2.00 100 0.0 0.0
13 23.0 26.0 22.0 18.0 2.00 100 70.0 0.0
189 of 331
Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %
5. Equipment Data
No Equipment Data required for this system.
190 of 331
1. General Details:
Floor Area 46.2 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage PUBLIC ASSEMBLY: Religious worship
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 37.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 15.6 23 0 0
SE 43.3 0 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 46.2 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
191 of 331
1. General Details:
Floor Area 48.0 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 50.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 12.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 15.2 22 0 0
N 15.0 21 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 48.0 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 87.5 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
192 of 331
1. General Details:
Floor Area 3.0 m²
Avg. Ceiling Height 2.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 3.0 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
193 of 331
7-PH-39 CORRIDOR
1. General Details:
Floor Area 17.8 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Corridor
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 26.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 17.8 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 7.8 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
194 of 331
1. General Details:
Floor Area 84.5 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Reception area
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 9.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 7.8 10 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 84.5 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
195 of 331
1. General Details:
Floor Area 10.5 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 5.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 3.4 5 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 10.5 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 11.3 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
196 of 331
1. General Details:
Floor Area 11.2 m²
Avg. Ceiling Height 2.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 10.1 14 0 0
S 15.8 22 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 11.2 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
197 of 331
1. General Details:
Floor Area 8.0 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 8.5 8 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 8.0 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
198 of 331
1. General Details:
Floor Area 8.0 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 10.5 15 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 8.0 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
199 of 331
1. General Details:
Floor Area 10.6 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 10.5 15 0 0
W 13.3 20 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 10.6 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
200 of 331
1. General Details:
Floor Area 18.3 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 8.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 17.3 16 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 18.3 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
201 of 331
1. General Details:
Floor Area 14.4 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 13.3 20 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 14.4 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
202 of 331
1. General Details:
Floor Area 25.0 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Break room
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 10.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 25.1 23 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 25.0 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
203 of 331
7-PH-Toilet Balance
1. General Details:
Floor Area 3.0 m²
Avg. Ceiling Height 2.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 0.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule None Latent 60.1 W/person
Schedule None
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 3.0 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
204 of 331
205 of 331
Zone L/s Sum of space airflow rates Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated
207 of 331
208 of 331
1. General Details:
Air System Name AHU-08
Equipment Type Chilled Water AHU
Air System Type Single Zone CAV
Number of zones 1
2. System Components:
Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
8-F-002 LOBBY (CORRIDOR) x1
8-F-009 WATER TREATMENT x1
8-F-010 COMM ROOM x1
8-F-016 RECEP. (OFFICE) x1
8-F-059 RECEPTION x1
8-F-062 COMM ROOM x1
8-F-074 ELEC ROOM x1
8-F-079 PRAYER AREA (FM) x1
8-F-081 KIDS PLAY ROOM x1
8-F-084 RECEPTION x1
8-F-085 LOBBY x1
8-F-092 WAITING AREA x1
8-F-093 WAITING AREA x1
8-F-100 WAITING AREA x1
8-F-101 WAITING AREA x1
8-F-103 RECEPTION x1
8-G-009 SERVER ROOM x1
8-G-010 PHARMACY&OPTIC x1
8-G-012 ENTRANCE LOBBY x1
8-G-013&054 ALL CORRIDOR x1
8-G-045 COMM ROOM x1
8-G-051 CAFE. DIET SHOP x1
8-G-052 ELEC ROOM x1
209 of 331
Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %
210 of 331
5. Equipment Data
No Equipment Data required for this system.
211 of 331
1. General Details:
Floor Area 327.0 m²
Avg. Ceiling Height 2.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 490.0 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 22.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 17.5 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 122.0 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
212 of 331
1. General Details:
Floor Area 34.9 m²
Avg. Ceiling Height 3.3 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Storage room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 20.1 9 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
213 of 331
1. General Details:
Floor Area 13.3 m²
Avg. Ceiling Height 3.3 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Electrical equipment room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 16.8 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
214 of 331
1. General Details:
Floor Area 6.4 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
215 of 331
8-F-059 RECEPTION
1. General Details:
Floor Area 18.0 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 30.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 15.6 18 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 9.2 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 16.6 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
216 of 331
1. General Details:
Floor Area 11.0 m²
Avg. Ceiling Height 3.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Electrical equipment room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 23.2 0 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 33.0 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
217 of 331
1. General Details:
Floor Area 8.4 m²
Avg. Ceiling Height 3.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Electrical equipment room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 20.3 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
218 of 331
1. General Details:
Floor Area 15.5 m²
Avg. Ceiling Height 2.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage PUBLIC ASSEMBLY: Religious worship
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 13.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
219 of 331
1. General Details:
Floor Area 9.5 m²
Avg. Ceiling Height 2.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage SPORTS: Sports arena (play area)
OA Requirement 1 0.0 L/s/person
OA Requirement 2 1.50 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 9.5 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
220 of 331
8-F-084 RECEPTION
1. General Details:
Floor Area 9.2 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 9.2 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
221 of 331
8-F-085 LOBBY
1. General Details:
Floor Area 50.0 m²
Avg. Ceiling Height 3.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 95.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 14.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 38.0 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
222 of 331
1. General Details:
Floor Area 7.1 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 5.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
223 of 331
1. General Details:
Floor Area 28.0 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 40.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
224 of 331
1. General Details:
Floor Area 10.7 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 7.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
225 of 331
1. General Details:
Floor Area 10.7 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 7.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
226 of 331
8-F-103 RECEPTION
1. General Details:
Floor Area 10.5 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 20.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
227 of 331
1. General Details:
Floor Area 14.6 m²
Avg. Ceiling Height 4.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Electrical equipment room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 14.6 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 19.0 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
228 of 331
8-G-010 PHARMACY&OPTIC
1. General Details:
Floor Area 95.5 m²
Avg. Ceiling Height 6.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Pharmacy (prep area)
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.90 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 12.0 People
Wattage 25.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 62.0 34 0 0
S 26.6 0 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 95.5 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 35.0 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
229 of 331
1. General Details:
Floor Area 77.8 m²
Avg. Ceiling Height 7.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 170.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 10.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 33.5 42 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 77.8 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
(No partition data).
230 of 331
1. General Details:
Floor Area 630.0 m²
Avg. Ceiling Height 3.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 1300.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 72.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 5.9 11 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 630.0 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 145.0 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
231 of 331
1. General Details:
Floor Area 11.6 m²
Avg. Ceiling Height 3.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Electrical equipment room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 11.6 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 32.9 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
232 of 331
1. General Details:
Floor Area 47.8 m²
Avg. Ceiling Height 6.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Coffee station
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 48.0 People
Wattage 15.00 W/m² Activity Level Sedentary Work
Ballast Multiplier 1.00 Sensible 82.1 W/person
Schedule LIGHTING 24/7 Latent 79.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 53.0 100 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 47.8 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 24.2 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
233 of 331
1. General Details:
Floor Area 8.4 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Electrical equipment room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 8.4 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 20.4 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
234 of 331
1. General Details:
Floor Area 8.5 m²
Avg. Ceiling Height 2.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 12.7 0 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 8.5 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 11.3 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
235 of 331
1. General Details:
Floor Area 110.3 m²
Avg. Ceiling Height 6.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Main entry lobby
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 15.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 57.0 0 0 0
W 57.5 88 0 0
S 37.0 71 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 110.3 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 60.5 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
236 of 331
Ambient at Space Max Temp 41.0 °C Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
237 of 331
8-G-089 FireControl RM
1. General Details:
Floor Area 15.4 m²
Avg. Ceiling Height 3.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Electrical equipment room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 15.4 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition Partition Type Wall Partition
Area 15.6 m² Area 15.6 m²
U-Value 2.000 W/(m²-°K) U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.0 °C Ambient at Space Min Temp 16.8 °C
238 of 331
1. General Details:
Floor Area 9.2 m²
Avg. Ceiling Height 3.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
239 of 331
8-M-22 RECEPTION
1. General Details:
Floor Area 17.7 m²
Avg. Ceiling Height 3.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 30.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
240 of 331
1. General Details:
Floor Area 8.5 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage SPORTS: Sports arena (play area)
OA Requirement 1 0.0 L/s/person
OA Requirement 2 1.50 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 2.0 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
241 of 331
8-M-48 LOBBY
1. General Details:
Floor Area 41.7 m²
Avg. Ceiling Height 2.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 60.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 12.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
242 of 331
8-M-49 RECEPTION
1. General Details:
Floor Area 36.2 m²
Avg. Ceiling Height 2.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 50.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 10.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 19.0 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
243 of 331
1. General Details:
Floor Area 11.0 m²
Avg. Ceiling Height 3.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Electrical equipment room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 21.0 0 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 29.0 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
244 of 331
1. General Details:
Floor Area 8.4 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Electrical equipment room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 18.0 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
245 of 331
8-M-59 CORRIDOR
1. General Details:
Floor Area 456.0 m²
Avg. Ceiling Height 3.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 810.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 30.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 13.7 24 0 0
WSW 33.0 19 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 114.0 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
246 of 331
1. General Details:
Floor Area 11.0 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Electrical equipment room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 22.1 0 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 11.0 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 30.5 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
247 of 331
1. General Details:
Floor Area 21.1 m²
Avg. Ceiling Height 3.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Electrical equipment room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 20.0 36 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 21.1 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
248 of 331
1. General Details:
Floor Area 10.3 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Electrical equipment room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 7.6 14 0 0
SE 19.4 0 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 10.3 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
249 of 331
1. General Details:
Floor Area 8.4 m²
Avg. Ceiling Height 3.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Electrical equipment room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 8.4 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 18.8 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
250 of 331
1. General Details:
Floor Area 220.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 370.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 15.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 24.6 39 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 220.0 0 216
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 29.7 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
251 of 331
8-SKY LEFT
1. General Details:
Floor Area 121.3 m²
Avg. Ceiling Height 15.3 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 0.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule None Latent 60.1 W/person
Schedule None
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 121.3 0 194
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
252 of 331
8-SKY RIGHT
1. General Details:
Floor Area 116.6 m²
Avg. Ceiling Height 15.3 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 0.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule None Latent 60.1 W/person
Schedule None
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 116.6 0 210
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
253 of 331
Zone L/s Sum of space airflow rates Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated
256 of 331
257 of 331
1. General Details:
Air System Name FCU (1-5)
Equipment Type Terminal Units
Air System Type 2-Pipe Fan Coil
Number of zones 20
Ventilation Common Ventilation System
% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54
% Airflow 40 30 20 10 0
% kW 46 40 33 27 21
3. Zone Components:
Space Assignments:
Zone 1: FCU-04
B1-02 SECURITY(1) x1
Zone 2: FCU-04
B1-03 COMM(1) x1
Zone 3: FCU-03
B1-04 LOBBY(1) x1
Zone 4: FCU-03
B1-06 LOBBY x1
Zone 5: 4*FCU-04
B1-07 AHU x1
Zone 6: 2*FCU-04
B1-08 MDP ROOM(1) x1
Zone 7: FCU-02
B1-10 WASTE MANAGMENT x1
Zone 8: FCU-03
B1-13 LOBBY(1) x1
Zone 9: FCU-04
B1-15 LOBBY x1
Zone 10: FCU-04
B1-16 BIO MED WORK SHOP x1
Zone 11: FCU-04
B1-17 OFFICE(1) x1
Zone 12: FCU-04
B1-19 DRIVER LOUNGE(1) x1
B1-21 OFFICE(1) x1
Zone 13: FCU-05
B1-14 WORK SHOP(1) x1
B1-12 store x1
Zone 14: FCU-03
B2-03 COMM x1
258 of 331
Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %
5. Equipment Data
No Equipment Data required for this system.
260 of 331
B1-02 SECURITY
1. General Details:
Floor Area 16.5 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Free Hanging Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition (No partition data).
Area 66.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 23.9 °C
Ambient at Space Max Temp 35.0 °C
Uncondit. Space Min Temp 23.9 °C
Ambient at Space Min Temp 12.8 °C
261 of 331
B1-02 SECURITY(1)
1. General Details:
Floor Area 16.5 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Free Hanging Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7(1) Latent 60.1 W/person
Schedule PEOPLE 24/7(1)
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 66.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C
262 of 331
B1-03 COMM
1. General Details:
Floor Area 17.0 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Electrical equipment room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Free Hanging Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 22.1 0 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 68.0 m² Area 30.5 m²
U-Value 2.839 W/(m²-°K) U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 23.9 °C Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 35.0 °C Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 23.9 °C Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 12.8 °C Ambient at Space Min Temp 16.8 °C
263 of 331
B1-03 COMM(1)
1. General Details:
Floor Area 17.0 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Electrical equipment room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Free Hanging Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7(1) Latent 60.1 W/person
Schedule None
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 68.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C
264 of 331
B1-04 LOBBY
1. General Details:
Floor Area 18.5 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Corridor
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 52.0 m² Area 8.3 m²
U-Value 2.839 W/(m²-°K) U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 23.9 °C Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 35.0 °C Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 23.9 °C Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 12.8 °C Ambient at Space Min Temp 16.8 °C
265 of 331
B1-04 LOBBY(1)
1. General Details:
Floor Area 18.5 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Corridor
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7(1) Latent 60.1 W/person
Schedule PEOPLE 24/7(1)
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition Partition Type Wall Partition
Area 52.0 m² Area 8.3 m²
U-Value 2.839 W/(m²-°K) U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C Ambient at Space Min Temp 16.0 °C
266 of 331
B1-06 LOBBY
1. General Details:
Floor Area 25.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Corridor
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Free Hanging Occupancy 2.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7(1) Latent 60.1 W/person
Schedule PEOPLE 24/7(1)
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 62.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C
267 of 331
B1-07 AHU
1. General Details:
Floor Area 217.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Storage room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Free Hanging Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7(1) Latent 60.1 W/person
Schedule PEOPLE 24/7(1)
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 270.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C
268 of 331
1. General Details:
Floor Area 46.0 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Electrical equipment room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Free Hanging Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 22.1 0 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 120.0 m² Area 30.5 m²
U-Value 2.839 W/(m²-°K) U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 23.9 °C Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 35.0 °C Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 23.9 °C Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 12.8 °C Ambient at Space Min Temp 16.8 °C
269 of 331
1. General Details:
Floor Area 46.0 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Electrical equipment room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Free Hanging Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7(1) Latent 60.1 W/person
Schedule None
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 120.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C
270 of 331
1. General Details:
Floor Area 20.0 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7(1) Latent 60.1 W/person
Schedule PEOPLE 24/7(1)
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 36.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C
271 of 331
B1-12 store
1. General Details:
Floor Area 32.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Storage room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Free Hanging Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule LIGHTING 24/7(1) Latent 133.3 W/person
Schedule None
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 27.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C
272 of 331
B1-13 LOBBY
1. General Details:
Floor Area 22.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Corridor
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 60.0 m² Area 8.3 m²
U-Value 2.839 W/(m²-°K) U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 23.9 °C Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 35.0 °C Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 23.9 °C Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 12.8 °C Ambient at Space Min Temp 16.8 °C
273 of 331
B1-13 LOBBY(1)
1. General Details:
Floor Area 22.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Corridor
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7(1) Latent 60.1 W/person
Schedule PEOPLE 24/7(1)
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 60.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C
274 of 331
1. General Details:
Floor Area 32.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Storage room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Free Hanging Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule LIGHTING 24/7 Latent 133.3 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 50.0 m² Area 8.3 m²
U-Value 2.839 W/(m²-°K) U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 23.9 °C Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 35.0 °C Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 23.9 °C Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 12.8 °C Ambient at Space Min Temp 16.8 °C
275 of 331
1. General Details:
Floor Area 32.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Storage room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Free Hanging Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule LIGHTING 24/7(1) Latent 133.3 W/person
Schedule PEOPLE 24/7(1)
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 50.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C
276 of 331
B1-15 LOBBY
1. General Details:
Floor Area 11.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Corridor
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7(1) Latent 60.1 W/person
Schedule PEOPLE 24/7(1)
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 14.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C
277 of 331
1. General Details:
Floor Area 24.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Storage room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Free Hanging Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule LIGHTING 24/7(1) Latent 133.3 W/person
Schedule PEOPLE 24/7(1)
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 65.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C
278 of 331
B1-17 OFFICE
1. General Details:
Floor Area 19.5 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition (No partition data).
Area 54.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 23.9 °C
Ambient at Space Max Temp 35.0 °C
Uncondit. Space Min Temp 23.9 °C
Ambient at Space Min Temp 12.8 °C
279 of 331
B1-17 OFFICE(1)
1. General Details:
Floor Area 19.5 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7(1) Latent 60.1 W/person
Schedule PEOPLE 24/7(1)
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 54.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C
280 of 331
1. General Details:
Floor Area 22.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage PUBLIC ASSEMBLY: Lobby
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Free Hanging Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 40.0 m² Area 8.3 m²
U-Value 2.839 W/(m²-°K) U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 23.9 °C Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 35.0 °C Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 23.9 °C Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 12.8 °C Ambient at Space Min Temp 16.8 °C
281 of 331
1. General Details:
Floor Area 22.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage PUBLIC ASSEMBLY: Lobby
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Free Hanging Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7(1) Latent 60.1 W/person
Schedule PEOPLE 24/7(1)
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 38.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C
282 of 331
B1-21 OFFICE
1. General Details:
Floor Area 7.0 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition (No partition data).
Area 36.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 23.9 °C
Ambient at Space Max Temp 35.0 °C
Uncondit. Space Min Temp 23.9 °C
Ambient at Space Min Temp 12.8 °C
283 of 331
B1-21 OFFICE(1)
1. General Details:
Floor Area 7.0 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7(1) Latent 60.1 W/person
Schedule PEOPLE 24/7(1)
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 23.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C
284 of 331
B2-03 COMM
1. General Details:
Floor Area 17.0 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Electrical equipment room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Free Hanging Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7(1) Latent 60.1 W/person
Schedule None
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 42.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C
285 of 331
B2-03 LOBBY
1. General Details:
Floor Area 19.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Corridor
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7(1) Latent 60.1 W/person
Schedule PEOPLE 24/7(1)
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 60.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C
286 of 331
1. General Details:
Floor Area 24.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Storage room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Free Hanging Occupancy 2.0 People
Wattage 15.00 W/m² Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule LIGHTING 24/7(1) Latent 133.3 W/person
Schedule PEOPLE 24/7(1)
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 52.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C
287 of 331
1. General Details:
Floor Area 9.5 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Storage room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Free Hanging Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule LIGHTING 24/7(1) Latent 133.3 W/person
Schedule PEOPLE 24/7(1)
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 10.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C
288 of 331
1. General Details:
Floor Area 46.0 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Electrical equipment room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Free Hanging Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7(1) Latent 60.1 W/person
Schedule None
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 120.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C
289 of 331
B2-12 AHU
1. General Details:
Floor Area 152.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Storage room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Free Hanging Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7(1) Latent 60.1 W/person
Schedule PEOPLE 24/7(1)
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 157.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C
290 of 331
B2-13 LOBBY
1. General Details:
Floor Area 23.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Corridor
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7(1) Latent 60.1 W/person
Schedule PEOPLE 24/7(1)
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 76.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C
291 of 331
Zone L/s Sum of space airflow rates Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated
292 of 331
293 of 331
1. General Details:
Air System Name FCU-06
Equipment Type Terminal Units
Air System Type 2-Pipe Fan Coil
Number of zones 1
Ventilation Direct Ventilation
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
9-PH-04 ASSESSMENT x1
9-PH-06 RECEPTION x1
9-PH-08 CORRIDOR x1
9-PH-10 CLN. UTILT.&STAF x1
9-PH-13 TREATMENT x1
9-PH-54 GSM x1
9-PH-53 RO ROOM x1
Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %
Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation 294 of 331
5. Equipment Data
No Equipment Data required for this system.
295 of 331
9-PH-04 ASSESSMENT
1. General Details:
Floor Area 11.5 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 20.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 11.5 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
296 of 331
9-PH-06 RECEPTION
1. General Details:
Floor Area 16.5 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 25.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 16.5 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
297 of 331
9-PH-08 CORRIDOR
1. General Details:
Floor Area 27.2 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 40.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 7.7 12 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 27.2 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 16.0 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
298 of 331
1. General Details:
Floor Area 7.4 m²
Avg. Ceiling Height 2.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 7.4 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
299 of 331
9-PH-13 TREATMENT
1. General Details:
Floor Area 8.9 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 30.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 5.3 8 0 0
WSW 4.7 6 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 8.9 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 8.3 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
300 of 331
9-PH-53 RO ROOM
1. General Details:
Floor Area 3.6 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Storage room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 3.8 0 0 0
SE 3.0 0 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 3.6 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
301 of 331
9-PH-54 GSM
1. General Details:
Floor Area 8.2 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Electrical equipment room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 6.8 0 0 0
SE 7.8 0 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 8.2 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Ceiling Partition
Area 12.0 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
302 of 331
Zone L/s Sum of space airflow rates Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated
303 of 331
304 of 331
1. General Details:
Air System Name FCU-07
Equipment Type Terminal Units
Air System Type 2-Pipe Fan Coil
Number of zones 1
Ventilation Direct Ventilation
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
9-PH-03 GYM x1
Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %
5. Equipment Data
305 of 331
306 of 331
9-PH-03 GYM
1. General Details:
Floor Area 96.6 m²
Avg. Ceiling Height 2.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage SPORTS: Gym, stadium (play area)
OA Requirement 1 0.0 L/s/person
OA Requirement 2 1.50 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 20.0 People
Wattage 15.00 W/m² Activity Level Athletics
Ballast Multiplier 1.00 Sensible 208.1 W/person
Schedule LIGHTING 24/7 Latent 319.4 W/person
Schedule PEOPLE 24/7
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 51.0 73 0 0
W 5.0 7 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 96.6 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 9.0 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
307 of 331
1. Plant Information:
Plant Name Sample Plant
Plant Type Generic Chilled Water
Design Weather Jeddah, Saudi Arabia
System
Cooling
Coil Load
Air System Name Mult. ( kW )
AHU-01 1 132.8
AHU-02 1 93.5
AHU-03 1 184.3
AHU-04 1 63.6
AHU-05 1 102.6
AHU-06 1 102.3
AHU-07 1 68.3
AHU-08 1 355.0
FCU-07 1 31.1
FCU-06 1 12.4
FCU (1-5) 1 109.9
System loads are for coils whose cooling source is ' Chilled Water ' or ' Any ' .
308 of 331
309 of 331
Zuhair Fayez Partnership
Made by MFMM Date 9-2014 Project Diabetes Plus
Bldg. 0
Checked by MFMM Date 9-2014 Contract : Sheet No. 1 of 1
Revised by MFMM Date 9-2014 Section : HVAC Calc. No.
Checked by MMEH Date 9-2014 Job No. J13-02100 File
Subject : VENTILATION
310 of 331
Zuhair Fayez Partnership
Made by MFMM Date 9-2014 Project Diabetes Plus
Bldg. 0
Checked by MFMM Date 9-2014 Contract : Sheet No. 1 of 1
Revised by MFMM Date 9-2014 Section : HVAC Calc. No.
Checked by MMEH Date 9-2014 Job No. J13-02100 File
Subject : VENTILATION
311 of 331
Zuhair Fayez Partnership
Made by MFMM Date 9-2014 Project Diabetes Plus
Bldg. 0
Checked by MFMM Date 9-2014 Contract : Sheet No. 1 of 1
Revised by MFMM Date 9-2014 Section : HVAC Calc. No.
Checked by MMEH Date 9-2014 Job No. J13-02100 File
Subject : VENTILATION
77
80
CAEF-04 SAY 80 L/S
312 of 331
Zuhair Fayez Partnership
Made by MFMM Date 9-2014
Project Diabetes Plus
Bldg. 0
Checked by MFMM Date 9-2014 Contract : Sheet No. 1 of 6
Revised by MFMM Date 9-2014 Section : HVAC Calc. No.
Checked by MMEH Date 9-2014 Job No. J13-02100 File
Subject : EXTERNAL STATIC LOSSES SUMMARY FOR AHU-01
Total external static losses = Total supply duct losses + Total Return air duct losses
Total external static losses = 545.65 Pa
Adding 10% factor of safety = 54.565 Pa
Total external static losses = 605 Pa
Say 605 Pa
313 of 331
Zuhair Fayez Partnership
Made by MFMM Date 9-2014
Project Diabetes Plus
Bldg. 0
Checked by MFMM Date 9-2014 Contract : Sheet No. 2 of 6
Revised by MFMM Date 9-2014 Section : HVAC Calc. No.
Checked by : Date 9-2014 Job No. J13-02100 File
Subject : EXTERNAL STATIC LOSSES SUMMARY FOR AHU-02
Total external static losses = Total supply duct losses + Total Return air duct losses
Total external static losses = 542.35 Pa
Adding 10% factor of safety = 54.235 Pa
Total external static losses = 600 Pa
Say 600 Pa
314 of 331
Zuhair Fayez Partnership
Made by MFMM Date 9-2014
Project Diabetes Plus
Bldg. 0
Checked by MFMM Date 9-2014 Contract : Sheet No. 3 of 6
Revised by MFMM Date 9-2014 Section : HVAC Calc. No.
Checked by : Date 9-2014 Job No. J13-02100 File
Subject : EXTERNAL STATIC LOSSES SUMMARY FOR AHU-03
Total external static losses = Total supply duct losses + Total Return air duct losses
Total external static losses = 632.65 Pa
Adding 10% factor of safety = 63.265 Pa
Total external static losses = 700 Pa
Say 700 Pa
315 of 331
Zuhair Fayez Partnership
Made by MFMM Date 9-2014
Project Diabetes Plus
Bldg. 0
Checked by MFMM Date 9-2014 Contract : Sheet No. 4 of 6
Revised by MFMM Date 9-2014 Section : HVAC Calc. No.
Checked by : Date 9-2014 Job No. J13-02100 File
Subject : EXTERNAL STATIC LOSSES SUMMARY FOR AHU-04
Total external static losses = Total supply duct losses + Total Return air duct losses
Total external static losses = 579.85 Pa
Adding 10% factor of safety = 57.985 Pa
Total external static losses = 640 Pa
Say 640 Pa
316 of 331
Zuhair Fayez Partnership
Made by MFMM Date 9-2014
Project Diabetes Plus
Bldg. 0
Checked by MFMM Date 9-2014 Contract : Sheet No. 5 of 6
Revised by MFMM Date 9-2014 Section : HVAC Calc. No.
Checked by : Date 9-2014 Job No. J13-02100 File
Subject : EXTERNAL STATIC LOSSES SUMMARY FOR AHU-05
Total external static losses = Total supply duct losses + Total Return air duct losses
Total external static losses = 698.5 Pa
Adding 10% factor of safety = 69.85 Pa
Total external static losses = 770 Pa
Say 770 Pa
317 of 331
Zuhair Fayez Partnership
Made by MFMM Date 9-2014
Project Diabetes Plus
Bldg. 0
Checked by MFMM Date 9-2014 Contract : Sheet No. 6 of 6
Revised by MFMM Date 9-2014 Section : HVAC Calc. No.
Checked by : Date 9-2014 Job No. J13-02100 File
Subject : EXTERNAL STATIC LOSSES SUMMARY FOR AHU-06
Total external static losses = Total supply duct losses + Total Return air duct losses
Total external static losses = 622.75 Pa
Adding 10% factor of safety = 62.275 Pa
Total external static losses = 690 Pa
Say 690 Pa
318 of 331
Zuhair Fayez Partnership
Made by MFMM Date 9-2014
Project Diabetes Plus
Bldg. 0
Checked by MFMM Date 9-2014 Contract : Sheet No. 6 of 6
Revised by MFMM Date 9-2014 Section : HVAC Calc. No.
Checked by : Date 9-2014 Job No. J13-02100 File
Subject : EXTERNAL STATIC LOSSES SUMMARY FOR AHU-07
Total external static losses = Total supply duct losses + Total Return air duct losses
Total external static losses = 423.4 Pa
Adding 10% factor of safety = 42.34 Pa
Total external static losses = 470 Pa
Say 470 Pa
319 of 331
Zuhair Fayez Partnership
Made by MFMM Date 9-2014
Project Diabetes Plus
Bldg. 0
Checked by MFMM Date 9-2014 Contract : Sheet No. 6 of 6
Revised by MFMM Date 9-2014 Section : HVAC Calc. No.
Checked by : Date 9-2014 Job No. J13-02100 File
Subject : EXTERNAL STATIC LOSSES SUMMARY FOR AHU-08
Total external static losses = Total supply duct losses + Total Return air duct losses
Total external static losses = 597.7 Pa
Adding 10% factor of safety = 59.77 Pa
Total external static losses = 660 Pa
Say 660 Pa
320 of 331
Zuhair Fayez Partnership
Made by MFMM Date 9-2014 Project Diabetes Plus
Bldg. 0
Checked by MFMM Date 9-2014 Contract : Sheet No. 1 OF 6
Revised by MFMM Date 9-2014 Section : HVAC Calc. No.
Checked by : Date 9-2014 Job No. J13-02100 File
Subject : Zone [Load/M3 , Air Pressurization & No. of Air Change/Hr.]
INPUT DATA :
ZONE NO. : 1
ZONE DESCRIPTION :
A/C UNIT : AHU-01
ZONE AREA 306.9 M2
ZONE HEIGHT 3 M
ZONE TOTAL COOLING LOAD = 132.9 kW
SUPPLY AIR FLOW RATE = 7395 L/S
FRESH AIR FLOW RATE = 1025 L/S
MIN. REQ. PRESS. PERCENTAGE = 10 %
ZONE EXHAUST AIR FLOW RATE = 125 L/S
OUTPUT DATA :
321 of 331
Zuhair Fayez Partnership
Made by MFMM Date 9-2014 Project Diabetes Plus
Bldg. 0
Checked by MFMM Date 9-2014 Contract : Sheet No. 2 OF 6
Revised by MFMM Date 9-2014 Section : HVAC Calc. No.
Checked by : Date 9-2014 Job No. J13-02100 File
Subject : Zone [Load/M3 , Air Pressurization & No. of Air Change/Hr.]
INPUT DATA :
ZONE NO. : 2
ZONE DESCRIPTION :
A/C UNIT : AHU-02
ZONE AREA 325.9 M2
ZONE HEIGHT 3 M
ZONE TOTAL COOLING LOAD = 93.5 kW
SUPPLY AIR FLOW RATE = 3975 L/S
FRESH AIR FLOW RATE = 1225 L/S
MIN. REQ. PRESS. PERCENTAGE = 10 %
ZONE EXHAUST AIR FLOW RATE = 1215 L/S
OUTPUT DATA :
322 of 331
Zuhair Fayez Partnership
Made by MFMM Date 9-2014 Project Diabetes Plus
Bldg. 0
Checked by MFMM Date 9-2014 Contract : Sheet No. 3 OF 6
Revised by MFMM Date 9-2014 Section : HVAC Calc. No.
Checked by : Date 9-2014 Job No. J13-02100 File
Subject : Zone [Load/M3 , Air Pressurization & No. of Air Change/Hr.]
INPUT DATA :
ZONE NO. : 3
ZONE DESCRIPTION :
A/C UNIT : AHU-03
ZONE AREA 255.2 M2
ZONE HEIGHT 3 M
ZONE TOTAL COOLING LOAD = 184.3 kW
SUPPLY AIR FLOW RATE = 4770 L/S
FRESH AIR FLOW RATE = 3810 L/S
MIN. REQ. PRESS. PERCENTAGE = 10 %
ZONE EXHAUST AIR FLOW RATE = 3875 L/S
OUTPUT DATA :
323 of 331
Zuhair Fayez Partnership
Made by MFMM Date 9-2014 Project Diabetes Plus
Bldg. 0
Checked by MFMM Date 9-2014 Contract : Sheet No. 4 OF 6
Revised by MFMM Date 9-2014 Section : HVAC Calc. No.
Checked by : Date 9-2014 Job No. J13-02100 File
Subject : Zone [Load/M3 , Air Pressurization & No. of Air Change/Hr.]
INPUT DATA :
ZONE NO. : 4
ZONE DESCRIPTION :
A/C UNIT : AHU-04
ZONE AREA 289.0 M2
ZONE HEIGHT 3 M
ZONE TOTAL COOLING LOAD = 63.6 kW
SUPPLY AIR FLOW RATE = 2855 L/S
FRESH AIR FLOW RATE = 875 L/S
MIN. REQ. PRESS. PERCENTAGE = 10 %
ZONE EXHAUST AIR FLOW RATE = 135 L/S
OUTPUT DATA :
324 of 331
Zuhair Fayez Partnership
Made by MFMM Date 9-2014 Project Diabetes Plus
Bldg. 0
Checked by MFMM Date 9-2014 Contract : Sheet No. 5 OF 6
Revised by MFMM Date 9-2014 Section : HVAC Calc. No.
Checked by : Date 9-2014 Job No. J13-02100 File
Subject : Zone [Load/M3 , Air Pressurization & No. of Air Change/Hr.]
INPUT DATA :
ZONE NO. : 5
ZONE DESCRIPTION :
A/C UNIT : AHU-05
ZONE AREA 442.5 M2
ZONE HEIGHT 3 M
ZONE TOTAL COOLING LOAD = 103.5 kW
SUPPLY AIR FLOW RATE = 4760 L/S
FRESH AIR FLOW RATE = 1225 L/S
MIN. REQ. PRESS. PERCENTAGE = 10 %
ZONE EXHAUST AIR FLOW RATE = 545 L/S
OUTPUT DATA :
325 of 331
Zuhair Fayez Partnership
Made by MFMM Date 9-2014 Project Diabetes Plus
Bldg. 0
Checked by MFMM Date 9-2014 Contract : Sheet No. 6 OF 6
Revised by MFMM Date 9-2014 Section : HVAC Calc. No.
Checked by : Date 9-2014 Job No. J13-02100 File
Subject : Zone [Load/M3 , Air Pressurization & No. of Air Change/Hr.]
INPUT DATA :
ZONE NO. : 6
ZONE DESCRIPTION :
A/C UNIT : AHU-06
ZONE AREA 567.5 M2
ZONE HEIGHT 3 M
ZONE TOTAL COOLING LOAD = 102.6 kW
SUPPLY AIR FLOW RATE = 4675 L/S
FRESH AIR FLOW RATE = 1280 L/S
MIN. REQ. PRESS. PERCENTAGE = 10 %
ZONE EXHAUST AIR FLOW RATE = 690 L/S
OUTPUT DATA :
326 of 331
Zuhair Fayez Partnership
Made by MFMM Date 9-2014 Project Diabetes Plus
Bldg. 0
Checked by MFMM Date 9-2014 Contract : Sheet No. 7 OF 6
Revised by MFMM Date 9-2014 Section : HVAC Calc. No.
Checked by : Date 9-2014 Job No. J13-02100 File
Subject : Zone [Load/M3 , Air Pressurization & No. of Air Change/Hr.]
INPUT DATA :
ZONE NO. : 7
ZONE DESCRIPTION :
A/C UNIT : AHU-07
ZONE AREA 305.6 M2
ZONE HEIGHT 3 M
ZONE TOTAL COOLING LOAD = 69.3 kW
SUPPLY AIR FLOW RATE = 3540 L/S
FRESH AIR FLOW RATE = 560 L/S
MIN. REQ. PRESS. PERCENTAGE = 10 %
ZONE EXHAUST AIR FLOW RATE = 545 L/S
EF-02 545
OUTPUT DATA :
327 of 331
Zuhair Fayez Partnership
Made by MFMM Date 9-2014 Project Diabetes Plus
Bldg. 0
Checked by MFMM Date 9-2014 Contract : Sheet No. 8 OF 6
Revised by MFMM Date 9-2014 Section : HVAC Calc. No.
Checked by : Date 9-2014 Job No. J13-02100 File
Subject : Zone [Load/M3 , Air Pressurization & No. of Air Change/Hr.]
INPUT DATA :
ZONE NO. : 8
ZONE DESCRIPTION :
A/C UNIT : AHU-08
ZONE AREA 1333.3 M2
ZONE HEIGHT 3 M
ZONE TOTAL COOLING LOAD = 177.5 kW
SUPPLY AIR FLOW RATE = 8300 L/S
FRESH AIR FLOW RATE = 2000 L/S
MIN. REQ. PRESS. PERCENTAGE = 10 %
ZONE EXHAUST AIR FLOW RATE = 805 L/S
OUTPUT DATA :
328 of 331
Zuhair Fayez Partnership
Made by MFMM Date Sep-14 Project DIABATES PLUS
Bldg. 0
Checked MFMM Date Sep-14 Contract : Sheet No. 1 of 2
Revised MFMM Date Sep-14 Section : HVAC Calc. No. Calc. No.
Checked MMEH Date Sep-14 Job No. J13-2100 File
Subject : Stairwell Pressurization
Ts To
B = 3460(1/T0 - 1/Ts) 294 318 = 0.888204338
Ab(m2)
Abo=Ab(0.21 * 10-3) 420 = 0.0882
As (m2)
Asb=As(0.11 * 10-3) +AE 72.15 = 0.0319365
Y
∆Psbt =∆Psbb+BY/[1 +( Asb/ Abo)2] 23.4 = 31.37484627
N ∆Psbb
Q SYMBOL 13 = 0.75123122 m³/s
751.23122 L/S
Q1 = 755 L/S
329 of 331
G= 4.19392
Q2 = G x N x Ae 368.473444
Q2 = 370 L/S
= 16.4808452
Q3 = 3406.05534
Q3 = 3410
Q tot = Q1 + Q2 + Q 3 = L/S
4535 L/S
330 of 331
Zuhair Fayez Partnership
Made by MFMM Date Sep-14 Project DIABATES PLUS
Bldg. 0
Checked by MFMM Date Sep-14 Contract : Sheet No. 1 of 1
Revised by MFMM Date Sep-14 Section : HVAC Calc. No.
Checked by : Date Sep-14 Job No. :J13-2100 File
Subject : SMOKE MANANGEMENT
Flame Height
Zf 3.01
Z 12.3
qc 1400 KW
m. 54.58 kg/s
Q 45.48 m3/s
331 of 331