DIABETES PLUS URGENT CARE CENTER

CLIENT LOGO

DR. SOLIMAN FAKEEH

HVAC CALCULATIONS
‫حسابات أعمال التكييف‬

J13-02100
ISSUED FOR CONSTRUCTION
TABLE OF CONTENTS

U DESCRIPTION U

1. General Data 01- 09

a. Design Weather Parameters.


b. Schedules Data.
c. Wall Construction Type.
d. Partition Wall Construction Type.
e. Roof Construction Type.
f. Window Constructions Type

2. AHU-01 10 – 40
-Air System Output Data
-Air System Input Data
-Space Description

3. AHU-02 41 - 67
-Air System Output Data
-Air System Input Data
-Space Description

4. AHU-03 68 - 89
-Air System Output Data
-Air System Input Data
-Space Description

5. AHU-04 90 - 111
-Air System Output Data
-Air System Input Data
-Space Description
6. AHU-05 112 - 149
-Air System Output Data
-Air System Input Data
-Space Description

7. AHU-06 150 - 183


-Air System Output Data
-Air System Input Data
-Space Description

8. AHU-07 184 - 204


-Air System Output Data
-Air System Input Data
-Space Description

9. AHU-08 205 - 253


-Air System Output Data
-Air System Input Data
-Space Description

10. FCU-(1-5) 254 - 291


-Air System Output Data
-Air System Input Data
-Space Description

11. FCU-06 292 - 302


-Air System Output Data
-Air System Input Data
-Space Description

11. FCU-07 303 - 307


-Air System Output Data
-Air System Input Data
-Space Description
11. Cooling Plant Sizing Summary 308

12. Ventilation Calculations 309 - 312

13. External Static Pressure Calculation 313 - 320

14. Air Balance 312- 328

15. Stairwell Pressurization 329- 330

16. SMOKE MANANGEMENT 331


Design Weather Parameters & MSHGs
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:34PM

Design Parameters:

City Name Jeddah


Location Saudi Arabia
Latitude 21.7 Deg.
Longitude -39.2 Deg.
Elevation 20.0 m
Summer Design Dry-Bulb 41.0 °C
Summer Coincident Wet-Bulb 23.5 °C
Summer Daily Range 10.2 °K
Winter Design Dry-Bulb 16.8 °C
Winter Design Wet-Bulb 9.7 °C
Atmospheric Clearness Number 1.00
Average Ground Reflectance 0.20
Soil Conductivity 1.385 W/(m-°K)
Local Time Zone (GMT +/- N hours) -3.0 hours
Consider Daylight Savings Time No
Simulation Weather Data noneN/A
Current Data is User Modified
Design Cooling Months January to December

Design Day Maximum Solar Heat Gains

(The MSHG values are expressed in W/m² )

Month N NNE NE ENE E ESE SE SSE S


January 88.2 88.2 146.1 420.3 614.9 765.6 797.6 745.7 693.7
February 97.7 97.7 274.3 534.2 698.5 777.0 759.4 653.0 573.1
March 107.7 147.9 406.4 624.3 742.7 746.2 661.0 500.4 393.1
April 119.2 290.4 506.1 661.7 717.9 665.1 512.3 309.6 202.7
May 143.2 383.5 565.6 674.3 683.0 590.1 406.1 189.0 135.0
June 182.5 409.7 587.1 675.2 663.3 553.6 356.0 152.6 133.6
July 148.5 377.4 566.6 668.1 670.6 573.6 388.7 182.0 136.9
August 125.1 282.9 500.7 645.0 693.5 637.6 492.3 296.0 198.4
September 110.9 145.1 376.6 587.3 707.8 720.7 630.7 485.3 385.9
October 99.7 99.7 265.5 504.9 684.1 758.2 726.5 627.4 555.7
November 88.8 88.8 139.2 411.6 627.2 742.7 786.1 732.2 682.2
December 83.5 83.5 96.3 374.0 587.3 742.0 802.2 769.7 727.7
Month SSW SW WSW W WNW NW NNW HOR Mult
January 745.7 800.0 759.2 626.7 423.2 138.5 88.2 708.3 1.00
February 650.4 757.1 775.7 709.6 532.6 257.0 97.7 810.8 1.00
March 499.7 660.2 748.0 743.2 623.5 404.2 149.0 885.4 1.00
April 309.0 517.2 657.6 717.8 668.3 517.9 277.0 899.3 1.00
May 189.1 402.9 584.5 684.9 682.4 577.4 382.9 890.5 1.00
June 153.9 351.1 551.4 664.4 679.0 592.3 416.4 879.8 1.00
July 182.3 387.8 573.2 670.6 668.5 567.3 378.4 877.3 1.00
August 296.5 496.5 632.8 692.2 646.9 505.4 277.8 878.8 1.00
September 490.4 639.2 714.1 693.1 590.7 396.6 134.0 854.6 1.00
October 632.7 728.5 760.2 674.7 497.9 273.9 99.7 790.1 1.00
November 731.0 774.8 756.7 622.8 391.5 152.3 88.8 699.3 1.00
December 768.2 794.4 749.8 588.2 365.2 106.2 83.5 660.6 1.00
Mult. = User-defined solar multiplier factor.

1 of 331

Hourly Analysis Program v4.60 Page 1 of 1


Schedule Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:36PM

EQUIPMENT 24/7 (Fractional)

Hourly Profiles:
1:Profile One
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

2:Profile Two
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

3:Profile Three
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

4:Profile Four
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

Assignments:
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Design 1 1 1 1 1 1 1 1 1 1 1 1
Monday 2 2 2 2 2 2 2 2 2 2 2 2
Tuesday 2 2 2 2 2 2 2 2 2 2 2 2
Wednesday 2 2 2 2 2 2 2 2 2 2 2 2
Thursday 2 2 2 2 2 2 2 2 2 2 2 2
Friday 2 2 2 2 2 2 2 2 2 2 2 2
Saturday 3 3 3 3 3 3 3 3 3 3 3 3
Sunday 4 4 4 4 4 4 4 4 4 4 4 4
Holiday 4 4 4 4 4 4 4 4 4 4 4 4

EQUIPMENT 24/7(1) (Fractional)

Hourly Profiles:
1:Profile One
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

2:Profile Two
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

3:Profile Three
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

4:Profile Four
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

Assignments:
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Design 1 1 1 1 1 1 1 1 1 1 1 1
Monday 2 2 2 2 2 2 2 2 2 2 2 2
Tuesday 2 2 2 2 2 2 2 2 2 2 2 2
Wednesday 2 2 2 2 2 2 2 2 2 2 2 2
Thursday 2 2 2 2 2 2 2 2 2 2 2 2
Friday 2 2 2 2 2 2 2 2 2 2 2 2
Saturday 3 3 3 3 3 3 3 3 3 3 3 3
Sunday 4 4 4 4 4 4 4 4 4 4 4 4
Holiday 4 4 4 4 4 4 4 4 4 4 4 4

2 of 331

Hourly Analysis Program v4.60 Page 1 of 5


Schedule Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:36PM

FAN THERMOSTAT 24/7 (Fan / Thermostat)

Hourly Profiles:
1:Profile One
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value O O O O O O O O O O O O O O O O O O O O O O O O

2:Profile Two
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value O O O O O O O O O O O O O O O O O O O O O O O O

3:Profile Three
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value O O O O O O O O O O O O O O O O O O O O O O O O

4:Profile Four
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value O O O O O O O O O O O O O O O O O O O O O O O O

O = Occupied; U = Unoccupied

Assignments:
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Design 1 1 1 1 1 1 1 1 1 1 1 1
Monday 2 2 2 2 2 2 2 2 2 2 2 2
Tuesday 2 2 2 2 2 2 2 2 2 2 2 2
Wednesday 2 2 2 2 2 2 2 2 2 2 2 2
Thursday 2 2 2 2 2 2 2 2 2 2 2 2
Friday 2 2 2 2 2 2 2 2 2 2 2 2
Saturday 3 3 3 3 3 3 3 3 3 3 3 3
Sunday 4 4 4 4 4 4 4 4 4 4 4 4
Holiday 4 4 4 4 4 4 4 4 4 4 4 4

FAN THERMOSTAT 24/7(1) (Fan / Thermostat)

Hourly Profiles:
1:Profile One
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value O O O O O O O O O O O O O O O O O O O O O O O O

2:Profile Two
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value O O O O O O O O O O O O O O O O O O O O O O O O

3:Profile Three
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value O O O O O O O O O O O O O O O O O O O O O O O O

4:Profile Four
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value O O O O O O O O O O O O O O O O O O O O O O O O

O = Occupied; U = Unoccupied

3 of 331

Hourly Analysis Program v4.60 Page 2 of 5


Schedule Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:36PM

Assignments:
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Design 1 1 1 1 1 1 1 1 1 1 1 1
Monday 2 2 2 2 2 2 2 2 2 2 2 2
Tuesday 2 2 2 2 2 2 2 2 2 2 2 2
Wednesday 2 2 2 2 2 2 2 2 2 2 2 2
Thursday 2 2 2 2 2 2 2 2 2 2 2 2
Friday 2 2 2 2 2 2 2 2 2 2 2 2
Saturday 3 3 3 3 3 3 3 3 3 3 3 3
Sunday 4 4 4 4 4 4 4 4 4 4 4 4
Holiday 4 4 4 4 4 4 4 4 4 4 4 4

LIGHTING 24/7 (Fractional)

Hourly Profiles:
1:Profile One
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

2:Profile Two
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

3:Profile Three
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

4:Profile Four
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

Assignments:
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Design 1 1 1 1 1 1 1 1 1 1 1 1
Monday 2 2 2 2 2 2 2 2 2 2 2 2
Tuesday 2 2 2 2 2 2 2 2 2 2 2 2
Wednesday 2 2 2 2 2 2 2 2 2 2 2 2
Thursday 2 2 2 2 2 2 2 2 2 2 2 2
Friday 2 2 2 2 2 2 2 2 2 2 2 2
Saturday 3 3 3 3 3 3 3 3 3 3 3 3
Sunday 4 4 4 4 4 4 4 4 4 4 4 4
Holiday 4 4 4 4 4 4 4 4 4 4 4 4

LIGHTING 24/7(1) (Fractional)

Hourly Profiles:
1:Profile One
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

2:Profile Two
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

3:Profile Three
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

4:Profile Four
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

4 of 331

Hourly Analysis Program v4.60 Page 3 of 5


Schedule Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:36PM

Assignments:
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Design 1 1 1 1 1 1 1 1 1 1 1 1
Monday 2 2 2 2 2 2 2 2 2 2 2 2
Tuesday 2 2 2 2 2 2 2 2 2 2 2 2
Wednesday 2 2 2 2 2 2 2 2 2 2 2 2
Thursday 2 2 2 2 2 2 2 2 2 2 2 2
Friday 2 2 2 2 2 2 2 2 2 2 2 2
Saturday 3 3 3 3 3 3 3 3 3 3 3 3
Sunday 4 4 4 4 4 4 4 4 4 4 4 4
Holiday 4 4 4 4 4 4 4 4 4 4 4 4

PEOPLE 24/7 (Fractional)

Hourly Profiles:
1:Profile One
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

2:Profile Two
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

3:Profile Three
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

4:Profile Four
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

Assignments:
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Design 1 1 1 1 1 1 1 1 1 1 1 1
Monday 2 2 2 2 2 2 2 2 2 2 2 2
Tuesday 2 2 2 2 2 2 2 2 2 2 2 2
Wednesday 2 2 2 2 2 2 2 2 2 2 2 2
Thursday 2 2 2 2 2 2 2 2 2 2 2 2
Friday 2 2 2 2 2 2 2 2 2 2 2 2
Saturday 3 3 3 3 3 3 3 3 3 3 3 3
Sunday 4 4 4 4 4 4 4 4 4 4 4 4
Holiday 4 4 4 4 4 4 4 4 4 4 4 4

PEOPLE 24/7(1) (Fractional)

Hourly Profiles:
1:Profile One
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

2:Profile Two
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

3:Profile Three
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

4:Profile Four
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

5 of 331

Hourly Analysis Program v4.60 Page 4 of 5


Schedule Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:36PM

Assignments:
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Design 1 1 1 1 1 1 1 1 1 1 1 1
Monday 2 2 2 2 2 2 2 2 2 2 2 2
Tuesday 2 2 2 2 2 2 2 2 2 2 2 2
Wednesday 2 2 2 2 2 2 2 2 2 2 2 2
Thursday 2 2 2 2 2 2 2 2 2 2 2 2
Friday 2 2 2 2 2 2 2 2 2 2 2 2
Saturday 3 3 3 3 3 3 3 3 3 3 3 3
Sunday 4 4 4 4 4 4 4 4 4 4 4 4
Holiday 4 4 4 4 4 4 4 4 4 4 4 4

6 of 331

Hourly Analysis Program v4.60 Page 5 of 5


Wall Constructions
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:37PM

EXTERIOR WALL

Wall Details
Outside Surface Color Medium
Absorptivity 0.675
Overall U-Value 0.300 W/(m²-°K)

Wall Layers Details (Inside to Outside)


Thickness Density Specific Ht. R-Value Weight
Layers mm kg/m³ kJ / (kg - °K) (m²-°K)/W kg/m²
Inside surface resistance 0.000 0.0 0.00 0.12000 0.0
3 mm gypsum plaster 3.000 720.8 1.34 0.01333 2.2
64 mm gypsum board 6.000 800.9 1.09 0.03728 4.8
Air space 0.000 0.0 0.00 0.16026 0.0
150 mm HW concrete 150.000 2242.6 0.84 0.08667 336.4
50 MM THICK INSULATION 50.000 32.0 0.92 2.69000 1.6
Air space 0.000 0.0 0.00 0.16026 0.0
30 mm STONE 30.000 977.1 0.84 0.02889 29.3
Outside surface resistance 0.000 0.0 0.00 0.04000 0.0
Totals 239.000 - 3.33669 374.3

INTERNAL WALL

Wall Details
Outside Surface Color Medium
Absorptivity 0.675
Overall U-Value 3.846 W/(m²-°K)

Wall Layers Details (Inside to Outside)


Thickness Density Specific Ht. R-Value Weight
Layers mm kg/m³ kJ / (kg - °K) (m²-°K)/W kg/m²
Inside surface resistance 0.000 0.0 0.00 0.12000 0.0
3 mm gypsum plaster 3.000 720.8 1.34 0.01333 2.2
150 mm HW concrete 150.000 2242.6 0.84 0.08667 336.4
Outside surface resistance 0.000 0.0 0.00 0.04000 0.0
Totals 153.000 - 0.26000 338.6

7 of 331

Hourly Analysis Program v4.60 Page 1 of 1


Roof Constructions
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:37PM

Floor

Roof Details
Outside Surface Color Medium
Absorptivity 0.675
Overall U-Value 3.087 W/(m²-°K)

Roof Layers Details (Inside to Outside)


Thickness Density Specific Ht. R-Value Weight
Layers mm kg/m³ kJ / (kg - °K) (m²-°K)/W kg/m²
Inside surface resistance 0.000 0.0 0.00 0.12000 0.0
300mm LW concrete 300.000 640.7 0.84 0.08667 192.2
50mm Concrete Screed 50.000 640.7 0.84 0.06928 32.0
15mm Concrete Water Proofing 15.000 1121.3 1.47 0.00110 16.8
10mm Thick Pea Gravel 10.000 4325.0 1.26 0.00694 43.3
Outside surface resistance 0.000 0.0 0.00 0.04000 0.0
Totals 375.000 - 0.32399 284.3

Roof

Roof Details
Outside Surface Color Medium
Absorptivity 0.675
Overall U-Value 0.300 W/(m²-°K)

Roof Layers Details (Inside to Outside)


Thickness Density Specific Ht. R-Value Weight
Layers mm kg/m³ kJ / (kg - °K) (m²-°K)/W kg/m²
Inside surface resistance 0.000 0.0 0.00 0.12000 0.0
300mm LW concrete 300.000 640.7 0.84 0.08667 192.2
50mm Concrete Screed 50.000 640.7 0.84 0.06928 32.0
15mm Concrete Water Proofing 15.000 1121.3 1.47 0.00110 16.8
80 MM TICK INSULATION 80.000 32.0 0.92 3.01000 2.6
10mm Thick Pea Gravel 10.000 4325.0 1.26 0.00694 43.3
Outside surface resistance 0.000 0.0 0.00 0.04000 0.0
Totals 455.000 - 3.33399 286.9

8 of 331

Hourly Analysis Program v4.60 Page 1 of 1


Window Constructions
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:37PM

Window Details:
Detailed Input No
Height 0.50 m
Width 1.00 m
Overall U-Value 1.400 W/(m²-°K)
Overall Shade Coefficient 0.300

9 of 331

Hourly Analysis Program v4.60 Page 1 of 1


Air System Sizing Summary for AHU-01
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:08PM

Air System Information


Air System Name AHU-01 Number of zones 10
Equipment Class CW AHU Floor Area 306.9 m²
Air System Type VAV Location Jeddah, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Central Cooling Coil Sizing Data


Total coil load 132.9 kW Load occurs at Jul 1500
Sensible coil load 123.1 kW OA DB / WB 41.0 / 23.5 °C
Coil L/s at Jul 1500 6289 L/s Entering DB / WB 29.0 / 18.3 °C
Max block L/s at Jul 1500 7395 L/s Leaving DB / WB 12.8 / 11.8 °C
Sum of peak zone L/s 7395 L/s Coil ADP 11.0 °C
Sensible heat ratio 0.926 Bypass Factor 0.100
m²/kW 2.3 Resulting RH 43 %
W/m² 433.1 Design supply temp. 12.8 °C
Water flow @ 6.0 °K rise 5.30 L/s Zone T-stat Check 10 of 10 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s at Jul 1500 7395 L/s Fan motor BHP 17.93 BHP
Standard L/s 7378 L/s Fan motor kW 14.22 kW
Actual max L/(s-m²) 24.10 L/(s-m²) Fan static 1250 Pa

Return Fan Sizing Data


Actual max L/s at Jul 1500 7395 L/s Fan motor BHP 8.61 BHP
Standard L/s 7378 L/s Fan motor kW 6.83 kW
Actual max L/(s-m²) 24.10 L/(s-m²) Fan static 600 Pa

Outdoor Ventilation Air Data


Design airflow L/s 1022 L/s L/s/person 39.32 L/s/person
L/(s-m²) 3.33 L/(s-m²)

10 of 331

Hourly Analysis Program v4.60 Page 1 of 4


Zone Sizing Summary for AHU-01
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:08PM

Air System Information


Air System Name AHU-01 Number of zones 10
Equipment Class CW AHU Floor Area 306.9 m²
Air System Type VAV Location Jeddah, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (kW) (L/s) (L/s) Load (kW) (m²) L/(s-m²)
Zone 1 33.1 2687 372 Jul 1500 0.8 61.7 43.52
Zone 2 24.0 1949 210 Jul 1500 0.6 44.9 43.43
Zone 3 6.3 508 98 Jul 1500 0.7 57.2 8.89
Zone 4 2.4 191 52 Jul 1500 0.4 34.0 5.63
Zone 5 7.4 604 115 Jul 1500 0.5 37.2 16.24
Zone 6 3.6 291 50 Jul 1500 0.3 23.1 12.58
Zone 7 4.3 353 9 Jul 1500 0.1 12.6 28.00
Zone 8 1.4 118 7 Jul 1500 0.1 8.1 14.54
Zone 9 4.3 350 55 Jul 1500 0.2 13.6 25.71
Zone 10 4.3 345 55 Jul 1500 0.2 14.5 23.76

Zone Terminal Sizing Data

Reheat Zone Zone


Reheat Coil Htg Htg Mixing
Coil Water Coil Water Box Fan
Load L/s Load L/s Airflow
Zone Name (kW) @ 11.0 °K (kW) @ 11.0 °K (L/s)
Zone 1 4.9 0.11 0.0 0.00 0
Zone 2 2.9 0.06 0.0 0.00 0
Zone 3 1.7 0.04 0.0 0.00 0
Zone 4 1.0 0.02 0.0 0.00 0
Zone 5 1.8 0.04 0.0 0.00 0
Zone 6 0.9 0.02 0.0 0.00 0
Zone 7 0.2 0.01 0.0 0.00 0
Zone 8 0.2 0.00 0.0 0.00 0
Zone 9 0.8 0.02 0.0 0.00 0
Zone 10 0.8 0.02 0.0 0.00 0

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
1-G-053 CONTROL (MRI) 1 2.5 Jul 1500 201 0.2 13.4 14.99
1-G-055 EQUIPMENT 1 23.5 Jul 1500 1912 0.2 13.9 137.17
1-G-056 MRI 1 7.1 Jul 1500 574 0.4 34.4 16.68
Zone 2
1-G-060 CONTROL (CT) 1 3.6 Jul 1500 289 0.1 4.9 59.25
1-G-062 CT SCAN 1 12.5 Jul 1500 1018 0.4 32.1 31.72
1-G-063 EQUIPMENT ROOM 1 7.7 Jul 1500 628 0.1 4.4 142.30
1-G-064 CHANGING 1 0.2 Jul 1500 15 0.0 3.5 4.23
Zone 3
1-G-061 RECEPTION 1 1.4 Jul 1500 116 0.1 9.2 12.60
11 of 331

Hourly Analysis Program v4.60 Page 2 of 4


Zone Sizing Summary for AHU-01
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:08PM

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
1-G-069 CORRIDOR 1 2.3 Jul 1500 187 0.4 38.1 4.90
1-G-072 CLEAN UTILITY 1 0.8 Jul 1500 62 0.0 3.1 19.75
1-G-077 PACS ROOM 1 1.6 Jul 1500 127 0.0 4.2 30.18
1-G-080 LOBBY 1 0.2 Jul 1500 17 0.0 2.6 6.73
Zone 4
1-G-058 PREP/RECOV. CUB 1 2.2 Jul 1500 178 0.4 30.8 5.77
1-G-059 CHANGING 1 0.2 Jul 1500 14 0.0 3.2 4.23
Zone 5
1-G-070 CONTROL (FLUOR.) 1 0.2 Jul 1500 20 0.0 3.2 6.27
1-G-071 FLUOROSCOPY 1 7.0 Jul 1500 569 0.5 30.4 18.70
1-G-065 CHANGING 1 0.2 Jul 1500 15 0.0 3.6 4.23
Zone 6
1-G-073 CONTROL (X-RAY) 1 0.3 Jul 1500 21 0.0 3.4 6.10
1-G-074 CHANGING 1 0.3 Jul 1500 22 0.0 3.2 6.94
1-G-075 GENERAL X-RAY 1 3.1 Jul 1500 248 0.2 16.5 15.02
Zone 7
1-G-067 VIEWING - REPORT 1 4.3 Jul 1500 353 0.1 12.6 28.00
Zone 8
1-G-068 RADIOLOGIST OFF. 1 1.4 Jul 1500 118 0.1 8.1 14.54
Zone 9
1-G-078 ULTRASOUND 1 4.3 Jul 1500 350 0.2 13.6 25.71
Zone 10
1-G-082 ULTRASOUND 1 4.3 Jul 1500 345 0.2 14.5 23.76

12 of 331

Hourly Analysis Program v4.60 Page 3 of 4


Air System Design Load Summary for AHU-01
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:08PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 41.0 °C / 23.5 °C HEATING OA DB / WB 16.8 °C / 9.7 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 544 - 12 m² - -
Wall Transmission 111 m² 531 - 111 m² 173 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 272 - 12 m² 87 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 307 m² 9928 - 307 m² 3192 -
Partitions 63 m² 1502 - 63 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 5368 W 5368 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 62760 W 62757 - 0 0 -
People 26 1867 1563 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 8277 156 10% 345 0
>> Total Zone Loads - 91045 1719 - 3798 0
Zone Conditioning - 89524 1719 - 2997 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 6289 L/s 4580 - 1022 L/s -556 -
Ventilation Load 1022 L/s 19451 8097 1022 L/s 5817 0
Supply Fan Load 6289 L/s 9541 - 1022 L/s -1159 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 123095 9815 - 7100 0
Central Cooling Coil - 123095 9821 - 0 0
Terminal Reheat Coils - 0 - - 7099 -
>> Total Conditioning - 123095 9821 - 7099 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

13 of 331

Hourly Analysis Program v4.60 Page 4 of 4


AHU-01 Input Data
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:17PM

1. General Details:
Air System Name AHU-01
Equipment Type Chilled Water AHU
Air System Type VAV
Number of zones 10

2. System Components:
Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Central Cooling Data:


Supply Air Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule * * MAMJJASON*
Capacity Control Constant Temperature - Fan On

Supply Fan Data:


Fan Type BI/AF with Variable Frequency Drive
Configuration Blow-thru
Fan Performance 1250 Pa
Overall Efficiency 65 %

% Airflow 100 90 80 70 60 50
% kW 100 77 57 42 30 21

% Airflow 40 30 20 10 0
% kW 15 13 10 7 5

Duct System Data:


Supply Duct Data:
Duct Heat Gain 0 %
Duct Leakage 0 %

Return Duct or Plenum Data:


Return Air Via Ducted Return

Return Fan Data:


Fan Type BI/AF with Variable Speed Drive
Fan Performance 600 Pa
Overall Efficiency 65 %

% Airflow 100 90 80 70 60 50
% kW 100 77 57 42 30 21

% Airflow 40 30 20 10 0
% kW 15 13 10 7 5

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
1-G-053 CONTROL (MRI) x1
1-G-055 EQUIPMENT x1
1-G-056 MRI x1
Zone 2: Zone 2
1-G-060 CONTROL (CT) x1
1-G-062 CT SCAN x1
1-G-063 EQUIPMENT ROOM x1
1-G-064 CHANGING x1
Zone 3: Zone 3
1-G-061 RECEPTION x1
14 of 331

Hourly Analysis Program v4.60 Page 1 of 3


AHU-01 Input Data
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:17PM

1-G-069 CORRIDOR x1
1-G-072 CLEAN UTILITY x1
1-G-077 PACS ROOM x1
1-G-080 LOBBY x1
Zone 4: Zone 4
1-G-058 PREP/RECOV. CUB x1
1-G-059 CHANGING x1
Zone 5: Zone 5
1-G-070 CONTROL (FLUOR.) x1
1-G-071 FLUOROSCOPY x1
1-G-065 CHANGING x1
Zone 6: Zone 6
1-G-073 CONTROL (X-RAY) x1
1-G-074 CHANGING x1
1-G-075 GENERAL X-RAY x1
Zone 7: Zone 7
1-G-067 VIEWING - REPORT x1
Zone 8: Zone 8
1-G-068 RADIOLOGIST OFF. x1
Zone 9: Zone 9
1-G-078 ULTRASOUND x1
Zone 10: Zone 10
1-G-082 ULTRASOUND x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 23.0 °C
Cooling T-stat: Unocc. 26.0 °C
Heating T-stat: Occ. 22.0 °C
Heating T-stat: Unocc. 18.0 °C
T-stat Throttling Range 2.00 °K
Diversity Factor 100 %
Direct Exhaust Airflow 0.0 L/s
Direct Exhaust Fan kW 0.0 kW

Thermostat Schedule FAN THERMOSTAT 24/7


Unoccupied Cooling is Available

Supply Terminals Data:


Zone All
Terminal Type VAV box with RH
Minimum Airflow 0.00 L/s/person

Reheat Coil Source Hot Water


Reheat Coil Schedule JFMAMJJASOND

Zone Heating Units:


Zone All
Zone Heating Unit Type None

Zone Unit Heat Source Hot Water


Zone Heating Unit Schedule JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature 12.8 °C
Supply Fan Airflow 7395.5 L/s
Ventilation Airflow 1022.3 L/s

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.0 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


15 of 331

Hourly Analysis Program v4.60 Page 2 of 3


AHU-01 Input Data
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:17PM

Zone Airflow Sizing Method Peak zone sensible load


Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) -
1 2686.6 - 4.9 -
2 1948.8 - 2.9 -
3 508.4 - 1.7 -
4 191.3 - 1.0 -
5 603.5 - 1.8 -
6 291.2 - 0.9 -
7 352.7 - 0.2 -
8 117.6 - 0.2 -
9 350.0 - 0.8
10 345.4 - 0.8

5. Equipment Data
No Equipment Data required for this system.

16 of 331

Hourly Analysis Program v4.60 Page 3 of 3


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

1-G-053 CONTROL (MRI)

1. General Details:
Floor Area 13.4 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15 % of supply air
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1470.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 13.4 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
(No partition data).

17 of 331

Hourly Analysis Program v4.60 Page 1 of 24


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

1-G-055 EQUIPMENT

1. General Details:
Floor Area 13.9 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15 % of supply air
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 20600.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 28.1 0 0 0

3.1. Construction Types for Exposure NE


Wall Type EXTERIOR WALL

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 13.9 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
(No partition data).

18 of 331

Hourly Analysis Program v4.60 Page 2 of 24


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

1-G-056 MRI

1. General Details:
Floor Area 34.4 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 55.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 4620.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 34.4 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
(No partition data).

19 of 331

Hourly Analysis Program v4.60 Page 3 of 24


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

1-G-058 PREP/RECOV. CUB

1. General Details:
Floor Area 30.8 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 50.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 90.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 30.8 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
(No partition data).

20 of 331

Hourly Analysis Program v4.60 Page 4 of 24


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

1-G-059 CHANGING

1. General Details:
Floor Area 3.2 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Storage room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 3.2 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
(No partition data).

21 of 331

Hourly Analysis Program v4.60 Page 5 of 24


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

1-G-060 CONTROL (CT)

1. General Details:
Floor Area 4.9 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15 % of supply air
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 2930.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 4.9 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
(No partition data).

22 of 331

Hourly Analysis Program v4.60 Page 6 of 24


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

1-G-061 RECEPTION

1. General Details:
Floor Area 9.2 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 20.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 790.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 9.2 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
(No partition data).

23 of 331

Hourly Analysis Program v4.60 Page 7 of 24


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

1-G-062 CT SCAN

1. General Details:
Floor Area 32.1 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 70.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 9675.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 24.6 0 0 0

3.1. Construction Types for Exposure NE


Wall Type EXTERIOR WALL

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 32.1 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
(No partition data).

24 of 331

Hourly Analysis Program v4.60 Page 8 of 24


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

1-G-063 EQUIPMENT ROOM

1. General Details:
Floor Area 4.4 m²
Avg. Ceiling Height 2.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15 % of supply air
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 6765.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 10.0 0 0 0

3.1. Construction Types for Exposure NE


Wall Type EXTERIOR WALL

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 4.4 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
(No partition data).

25 of 331

Hourly Analysis Program v4.60 Page 9 of 24


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

1-G-064 CHANGING

1. General Details:
Floor Area 3.5 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Storage room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 3.5 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
(No partition data).

26 of 331

Hourly Analysis Program v4.60 Page 10 of 24


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

1-G-065 CHANGING

1. General Details:
Floor Area 3.6 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Storage room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 3.6 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
(No partition data).

27 of 331

Hourly Analysis Program v4.60 Page 11 of 24


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

1-G-067 VIEWING - REPORT

1. General Details:
Floor Area 12.6 m²
Avg. Ceiling Height 2.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 3145.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 12.6 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
(No partition data).

28 of 331

Hourly Analysis Program v4.60 Page 12 of 24


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

1-G-068 RADIOLOGIST OFF.

1. General Details:
Floor Area 8.1 m²
Avg. Ceiling Height 2.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 790.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 8.1 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
(No partition data).

29 of 331

Hourly Analysis Program v4.60 Page 13 of 24


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

1-G-069 CORRIDOR

1. General Details:
Floor Area 38.1 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 60.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 38.1 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 3.0 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C

30 of 331

Hourly Analysis Program v4.60 Page 14 of 24


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

1-G-070 CONTROL (FLUOR.)

1. General Details:
Floor Area 3.2 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15 % of supply air
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 3.2 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
(No partition data).

31 of 331

Hourly Analysis Program v4.60 Page 15 of 24


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

1-G-071 FLUOROSCOPY

1. General Details:
Floor Area 30.4 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 110.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 3650.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 17.0 24 0 0
N 4.0 0 0 0

3.1. Construction Types for Exposure NE


Wall Type EXTERIOR WALL
1st Window Type W

3.2. Construction Types for Exposure N


Wall Type EXTERIOR WALL

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 30.4 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 8.0 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C

32 of 331

Hourly Analysis Program v4.60 Page 16 of 24


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

1-G-072 CLEAN UTILITY

1. General Details:
Floor Area 3.1 m²
Avg. Ceiling Height 2.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 470.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 3.1 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
(No partition data).

33 of 331

Hourly Analysis Program v4.60 Page 17 of 24


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

1-G-073 CONTROL (X-RAY)

1. General Details:
Floor Area 3.4 m²
Avg. Ceiling Height 2.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15 % of supply air
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 3.4 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
(No partition data).

34 of 331

Hourly Analysis Program v4.60 Page 18 of 24


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

1-G-074 CHANGING

1. General Details:
Floor Area 3.2 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Storage room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 7.4 0 0 0

3.1. Construction Types for Exposure N


Wall Type EXTERIOR WALL

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 3.2 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 2.7 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C

35 of 331

Hourly Analysis Program v4.60 Page 19 of 24


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

1-G-075 GENERAL X-RAY

1. General Details:
Floor Area 16.5 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 45.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1765.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 17.0 0 0 0

3.1. Construction Types for Exposure N


Wall Type EXTERIOR WALL

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 16.5 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
(No partition data).

36 of 331

Hourly Analysis Program v4.60 Page 20 of 24


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

1-G-077 PACS ROOM

1. General Details:
Floor Area 4.2 m²
Avg. Ceiling Height 3.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Storage room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1000.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 4.2 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 9.2 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C

37 of 331

Hourly Analysis Program v4.60 Page 21 of 24


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

1-G-078 ULTRASOUND

1. General Details:
Floor Area 13.6 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 55.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 2500.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 13.6 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 23.5 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C

38 of 331

Hourly Analysis Program v4.60 Page 22 of 24


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

1-G-080 LOBBY

1. General Details:
Floor Area 2.6 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 5.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 2.6 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
(No partition data).

39 of 331

Hourly Analysis Program v4.60 Page 23 of 24


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

1-G-082 ULTRASOUND

1. General Details:
Floor Area 14.5 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 55.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 2500.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 15.2 0 0 0

3.1. Construction Types for Exposure N


Wall Type EXTERIOR WALL

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 14.5 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 16.5 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C

40 of 331

Hourly Analysis Program v4.60 Page 24 of 24


Air System Sizing Summary for AHU-02
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:11PM

Air System Information


Air System Name AHU-02 Number of zones 12
Equipment Class CW AHU Floor Area 325.9 m²
Air System Type VAV Location Jeddah, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Central Cooling Coil Sizing Data


Total coil load 93.5 kW Load occurs at Aug 1500
Sensible coil load 81.5 kW OA DB / WB 41.0 / 23.5 °C
Coil L/s at Aug 1500 3793 L/s Entering DB / WB 30.6 / 19.2 °C
Max block L/s at Nov 1500 3975 L/s Leaving DB / WB 12.8 / 11.8 °C
Sum of peak zone L/s 4554 L/s Coil ADP 10.8 °C
Sensible heat ratio 0.872 Bypass Factor 0.100
m²/kW 3.5 Resulting RH 48 %
W/m² 286.8 Design supply temp. 12.8 °C
Water flow @ 6.0 °K rise 3.73 L/s Zone T-stat Check 12 of 12 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s at Nov 1500 3975 L/s Fan motor BHP 9.64 BHP
Standard L/s 3966 L/s Fan motor kW 7.64 kW
Actual max L/(s-m²) 12.20 L/(s-m²) Fan static 1250 Pa

Return Fan Sizing Data


Actual max L/s at Nov 1500 3975 L/s Fan motor BHP 4.63 BHP
Standard L/s 3966 L/s Fan motor kW 3.67 kW
Actual max L/(s-m²) 12.20 L/(s-m²) Fan static 600 Pa

Outdoor Ventilation Air Data


Design airflow L/s 1225 L/s L/s/person 27.85 L/s/person
L/(s-m²) 3.76 L/(s-m²)

41 of 331

Hourly Analysis Program v4.60 Page 1 of 3


Zone Sizing Summary for AHU-02
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:11PM

Air System Information


Air System Name AHU-02 Number of zones 12
Equipment Class CW AHU Floor Area 325.9 m²
Air System Type VAV Location Jeddah, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (kW) (L/s) (L/s) Load (kW) (m²) L/(s-m²)
Zone 1 12.6 1021 800 Aug 1600 1.3 107.9 9.46
Zone 2 2.0 163 107 Sep 1600 0.2 14.0 11.60
Zone 3 1.9 155 86 Sep 1600 0.2 11.3 13.76
Zone 4 4.4 355 191 Dec 1400 0.4 24.8 14.32
Zone 5 3.5 285 128 Dec 1400 0.3 16.5 17.20
Zone 6 3.8 305 126 Nov 1500 0.3 16.4 18.59
Zone 7 4.3 352 208 Dec 1400 0.4 20.6 17.09
Zone 8 3.3 414 414 Jul 1500 0.6 48.5 8.53
Zone 9 1.6 127 68 Jul 1500 0.1 8.8 14.39
Zone 10 8.2 741 290 Jul 1500 0.3 34.2 21.68
Zone 11 2.3 186 134 Jul 1500 0.2 17.5 10.68
Zone 12 0.3 450 450 Jul 1500 0.1 5.4 83.33

Zone Terminal Sizing Data

Reheat Zone Zone


Reheat Coil Htg Htg Mixing
Coil Water Coil Water Box Fan
Load L/s Load L/s Airflow
Zone Name (kW) @ 11.0 °K (kW) @ 11.0 °K (L/s)
Zone 1 10.2 0.22 0.0 0.00 0
Zone 2 1.4 0.03 0.0 0.00 0
Zone 3 1.2 0.03 0.0 0.00 0
Zone 4 2.6 0.06 0.0 0.00 0
Zone 5 1.7 0.04 0.0 0.00 0
Zone 6 1.7 0.04 0.0 0.00 0
Zone 7 2.7 0.06 0.0 0.00 0
Zone 8 5.2 0.11 0.0 0.00 0
Zone 9 0.9 0.02 0.0 0.00 0
Zone 10 3.2 0.07 0.0 0.00 0
Zone 11 1.7 0.04 0.0 0.00 0
Zone 12 5.1 0.11 0.0 0.00 0

Space Loads and Airflows

42 of 331

Hourly Analysis Program v4.60 Page 2 of 3


Air System Design Load Summary for AHU-02
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:11PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 41.0 °C / 23.5 °C HEATING OA DB / WB 16.8 °C / 9.7 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 96 m² 3929 - 96 m² - -
Wall Transmission 63 m² 284 - 63 m² 98 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 96 m² 2162 - 96 m² 695 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 326 m² 10599 - 326 m² 3321 -
Partitions 28 m² 654 - 28 m² 37 -
Ceiling 4 m² -1 - 4 m² 0 -
Overhead Lighting 5636 W 5636 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 13360 W 13359 - 0 0 -
People 44 3106 2346 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 3973 235 10% 415 0
>> Total Zone Loads - 43701 2580 - 4565 0
Zone Conditioning - 42387 2580 - 4239 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 2869 L/s 1661 - 2483 L/s -1210 -
Ventilation Load 1225 L/s 25875 9340 1225 L/s 7210 0
Supply Fan Load 3793 L/s 6841 - 3003 L/s -3846 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 76764 11920 - 6394 0
Central Cooling Coil - 81537 11925 - 0 0
Terminal Reheat Coils - -4774 - - 6379 -
>> Total Conditioning - 76764 11925 - 6379 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

43 of 331

Hourly Analysis Program v4.60 Page 3 of 3


AHU-02 Input Data
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:19PM

1. General Details:
Air System Name AHU-02
Equipment Type Chilled Water AHU
Air System Type VAV
Number of zones 12

2. System Components:
Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Central Cooling Data:


Supply Air Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule * * MAMJJASON*
Capacity Control Constant Temperature - Fan On

Supply Fan Data:


Fan Type BI/AF with Variable Frequency Drive
Configuration Blow-thru
Fan Performance 1250 Pa
Overall Efficiency 65 %

% Airflow 100 90 80 70 60 50
% kW 100 77 57 42 30 21

% Airflow 40 30 20 10 0
% kW 15 13 10 7 5

Duct System Data:


Supply Duct Data:
Duct Heat Gain 0 %
Duct Leakage 0 %

Return Duct or Plenum Data:


Return Air Via Ducted Return

Return Fan Data:


Fan Type BI/AF with Variable Speed Drive
Fan Performance 600 Pa
Overall Efficiency 65 %

% Airflow 100 90 80 70 60 50
% kW 100 77 57 42 30 21

% Airflow 40 30 20 10 0
% kW 15 13 10 7 5

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
2-G-014 RECEPTION x1
2-G-015 WAITING AREA x1
2-G-023 CORRIDOR x1
2-G-024 CLEAN UTILITY x1
2-G-027 PANTRY x1
Zone 2: Zone 2
2-G-019 ISOLATION CUBIC. x1
2-G-021 AIRLOCK x1
Zone 3: Zone 3
2-G-016 TRIAG x1
44 of 331

Hourly Analysis Program v4.60 Page 1 of 3


AHU-02 Input Data
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:19PM

Zone 4: Zone 4
2-G-030 CUBICLES x1
Zone 5: Zone 5
2-G-029 CUBICLES x1
Zone 6: Zone 6
2-G-022 RESUSCITATION RM x1
Zone 7: Zone 7
2-G-032 ELEC ROOM x1
Zone 8: Zone 8
2-G-031 CORRIDOR x1
2-G-039 STORE x1
Zone 9: Zone 9
2-G-026 PHYISICIANS OFF. x1
Zone 10: Zone 10
2-G-036 MINOR OP x1
2-G-037 SCRUB UP x1
2-G-088 STERILIZING ROOM x1
Zone 11: Zone 11
2-G-038 PLASTERING/CAST. x1
Zone 12: Zone 12
2-G-018 Soiled Work x1
2-FA x1

Thermostats and Zone Data:

T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)
1 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
2 23.0 26.0 22.0 18.0 2.00 100 145.0 0.0
3 23.0 26.0 22.0 18.0 2.00 100 155.0 0.0
4 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
5 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
6 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
7 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
8 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
9 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
10 22.0 26.0 21.0 18.0 2.00 100 740.0 0.0
11 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
12 24.0 26.0 22.0 18.0 2.00 100 35.0 0.0

Thermostat Schedule FAN THERMOSTAT 24/7


Unoccupied Cooling is Available

Supply Terminals Data:


Zone All
Terminal Type VAV box with RH
Minimum Airflow 10.00 ACH

Reheat Coil Source Hot Water


Reheat Coil Schedule JFMAMJJASOND

Zone Heating Units:


Zone All
Zone Heating Unit Type None

Zone Unit Heat Source Hot Water


Zone Heating Unit Schedule JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature 12.8 °C
45 of 331

Hourly Analysis Program v4.60 Page 2 of 3


AHU-02 Input Data
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:19PM

Supply Fan Airflow 3975.2 L/s


Ventilation Airflow 1225.3 L/s

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.0 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) -
1 1021.4 - 10.2 -
2 162.7 - 1.4 -
3 155.0 - 1.2 -
4 355.3 - 2.6 -
5 284.5 - 1.7 -
6 304.9 - 1.7 -
7 351.6 - 2.7 -
8 413.8 - 5.2 -
9 127.2 - 0.9 -
10 740.8 - 3.2 -
11 186.4 - 1.7
12 450.0 - 5.1

5. Equipment Data
No Equipment Data required for this system.

46 of 331

Hourly Analysis Program v4.60 Page 3 of 3


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

2-FA

1. General Details:
Floor Area 0.0 m²
Avg. Ceiling Height 2.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 440.0 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 0.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule None Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.00 W/m²
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

47 of 331

Hourly Analysis Program v4.60 Page 1 of 21


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

2-G-014 RECEPTION

1. General Details:
Floor Area 8.0 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 30.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1140.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 8.0 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
(No partition data).

48 of 331

Hourly Analysis Program v4.60 Page 2 of 21


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

2-G-015 WAITING AREA

1. General Details:
Floor Area 27.7 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 40.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 9.5 12 0 0

3.1. Construction Types for Exposure WSW


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 27.7 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
(No partition data).

49 of 331

Hourly Analysis Program v4.60 Page 3 of 21


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

2-G-016 TRIAG

1. General Details:
Floor Area 11.3 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 40.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 175.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 11.0 15 0 0

3.1. Construction Types for Exposure WSW


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 11.3 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
(No partition data).

50 of 331

Hourly Analysis Program v4.60 Page 4 of 21


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

2-G-018 Soiled Work

1. General Details:
Floor Area 5.4 m²
Avg. Ceiling Height 2.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 5.4 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition (No partition data).
Area 4.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 23.9 °C
Ambient at Space Max Temp 35.0 °C
Uncondit. Space Min Temp 23.9 °C
Ambient at Space Min Temp 12.8 °C

51 of 331

Hourly Analysis Program v4.60 Page 5 of 21


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

2-G-019 ISOLATION CUBIC.

1. General Details:
Floor Area 11.3 m²
Avg. Ceiling Height 2.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 40.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING 24/7 Latent 35.2 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 90.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 11.0 15 0 0

3.1. Construction Types for Exposure WSW


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 11.3 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
(No partition data).

52 of 331

Hourly Analysis Program v4.60 Page 6 of 21


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

2-G-021 AIRLOCK

1. General Details:
Floor Area 2.7 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 5.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 2.7 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
(No partition data).

53 of 331

Hourly Analysis Program v4.60 Page 7 of 21


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

2-G-022 RESUSCITATION RM

1. General Details:
Floor Area 16.4 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 75.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 705.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 11.1 15 0 0
S 11.2 15 0 0

3.1. Construction Types for Exposure WSW


Wall Type EXTERIOR WALL
1st Window Type W

3.2. Construction Types for Exposure S


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 16.4 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 7.0 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C

54 of 331

Hourly Analysis Program v4.60 Page 8 of 21


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

2-G-023 CORRIDOR

1. General Details:
Floor Area 61.7 m²
Avg. Ceiling Height 2.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 95.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 5.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1140.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 61.7 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
(No partition data).

55 of 331

Hourly Analysis Program v4.60 Page 9 of 21


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

2-G-024 CLEAN UTILITY

1. General Details:
Floor Area 7.1 m²
Avg. Ceiling Height 2.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 470.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 7.1 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
(No partition data).

56 of 331

Hourly Analysis Program v4.60 Page 10 of 21


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

2-G-026 PHYISICIANS OFF.

1. General Details:
Floor Area 8.8 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 790.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 8.8 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
(No partition data).

57 of 331

Hourly Analysis Program v4.60 Page 11 of 21


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

2-G-027 PANTRY

1. General Details:
Floor Area 3.4 m²
Avg. Ceiling Height 2.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 3.80 L/(s-m²)
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 2175.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 3.4 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
(No partition data).

58 of 331

Hourly Analysis Program v4.60 Page 12 of 21


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

2-G-029 CUBICLES

1. General Details:
Floor Area 16.5 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 70.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 20.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING 24/7 Latent 35.2 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 240.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 22.6 31 0 0

3.1. Construction Types for Exposure S


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 16.5 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
(No partition data).

59 of 331

Hourly Analysis Program v4.60 Page 13 of 21


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

2-G-030 CUBICLES

1. General Details:
Floor Area 24.8 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 85.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6.0 People
Wattage 20.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING 24/7 Latent 35.2 W/person
Schedule LIGHTING 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 360.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 24.9 34 0 0

3.1. Construction Types for Exposure S


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 24.8 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
(No partition data).

60 of 331

Hourly Analysis Program v4.60 Page 14 of 21


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

2-G-031 CORRIDOR

1. General Details:
Floor Area 38.5 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 60.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 38.5 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
(No partition data).

61 of 331

Hourly Analysis Program v4.60 Page 15 of 21


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

2-G-032 ELEC ROOM

1. General Details:
Floor Area 20.6 m²
Avg. Ceiling Height 3.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Electrical equipment room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 500.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 36.9 41 0 0
E 7.8 0 0 0

3.1. Construction Types for Exposure S


Wall Type EXTERIOR WALL
1st Window Type W

3.2. Construction Types for Exposure E


Wall Type EXTERIOR WALL

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 20.6 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
(No partition data).

62 of 331

Hourly Analysis Program v4.60 Page 16 of 21


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

2-G-036 MINOR OP

1. General Details:
Floor Area 25.9 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 155.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 25.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 3105.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 25.9 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
(No partition data).

63 of 331

Hourly Analysis Program v4.60 Page 17 of 21


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

2-G-037 SCRUB UP

1. General Details:
Floor Area 4.3 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 235.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 4.3 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
(No partition data).

64 of 331

Hourly Analysis Program v4.60 Page 18 of 21


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

2-G-038 PLASTERING/CAST.

1. General Details:
Floor Area 17.5 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 25.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 470.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 17.5 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 20.5 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 20.0 °C
Ambient at Space Min Temp 15.0 °C

65 of 331

Hourly Analysis Program v4.60 Page 19 of 21


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

2-G-039 STORE

1. General Details:
Floor Area 10.0 m²
Avg. Ceiling Height 4.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Storage room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 6.6 13 0 0
N 5.5 0 0 0

3.1. Construction Types for Exposure E


Wall Type EXTERIOR WALL
1st Window Type W

3.2. Construction Types for Exposure N


Wall Type EXTERIOR WALL

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 10.0 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
(No partition data).

66 of 331

Hourly Analysis Program v4.60 Page 20 of 21


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:25PM

2-G-088 STERILIZING ROOM

1. General Details:
Floor Area 4.0 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1765.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 4.0 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
(No partition data).

67 of 331

Hourly Analysis Program v4.60 Page 21 of 21


Air System Sizing Summary for AHU-03
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:11PM

Air System Information


Air System Name AHU-03 Number of zones 11
Equipment Class CW AHU Floor Area 255.2 m²
Air System Type VAV Location Jeddah, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Central Cooling Coil Sizing Data


Total coil load 184.3 kW Load occurs at Jul 1500
Sensible coil load 148.7 kW OA DB / WB 41.0 / 23.5 °C
Coil L/s at Jul 1500 4770 L/s Entering DB / WB 38.7 / 22.5 °C
Max block L/s at Jun 1500 4770 L/s Leaving DB / WB 12.8 / 11.4 °C
Sum of peak zone L/s 7577 L/s Coil ADP 9.9 °C
Sensible heat ratio 0.807 Bypass Factor 0.100
m²/kW 1.4 Resulting RH 52 %
W/m² 722.2 Design supply temp. 12.8 °C
Water flow @ 6.0 °K rise 7.35 L/s Zone T-stat Check 11 of 11 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s at Jun 1500 4770 L/s Fan motor BHP 11.56 BHP
Standard L/s 4759 L/s Fan motor kW 9.17 kW
Actual max L/(s-m²) 18.69 L/(s-m²) Fan static 1250 Pa

Return Fan Sizing Data


Actual max L/s at Jun 1500 4770 L/s Fan motor BHP 5.55 BHP
Standard L/s 4759 L/s Fan motor kW 4.40 kW
Actual max L/(s-m²) 18.69 L/(s-m²) Fan static 600 Pa

Outdoor Ventilation Air Data


Design airflow L/s 3810 L/s L/s/person 102.97 L/s/person
L/(s-m²) 14.93 L/(s-m²)

68 of 331

Hourly Analysis Program v4.60 Page 1 of 3


Zone Sizing Summary for AHU-03
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:11PM

Air System Information


Air System Name AHU-03 Number of zones 11
Equipment Class CW AHU Floor Area 255.2 m²
Air System Type VAV Location Jeddah, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (kW) (L/s) (L/s) Load (kW) (m²) L/(s-m²)
Zone 1 0.2 115 115 Jan 2300 0.0 5.3 21.58
Zone 2 5.4 770 175 Jun 0900 0.1 33.9 22.71
Zone 3 2.8 225 60 Jun 1700 0.1 18.0 12.48
Zone 4 1.0 83 30 Jan 2300 0.0 18.6 4.44
Zone 5 2.3 189 35 Jul 1500 0.0 23.1 8.17
Zone 6 2.9 480 455 Jan 2300 0.0 17.5 27.40
Zone 7 0.3 42 42 Jan 2300 0.0 9.8 4.33
Zone 8 15.4 1530 265 Jun 0900 0.2 89.2 17.16
Zone 9 9.9 935 110 Jun 0900 0.1 12.2 76.80
Zone 10 2.5 203 60 Jun 1700 0.1 13.6 14.99
Zone 11 3.3 3005 3005 Jun 1700 0.1 14.1 213.57

Zone Terminal Sizing Data

Reheat Zone Zone


Reheat Coil Htg Htg Mixing
Coil Water Coil Water Box Fan
Load L/s Load L/s Airflow
Zone Name (kW) @ 11.0 °K (kW) @ 11.0 °K (L/s)
Zone 1 1.1 0.02 0.0 0.00 0
Zone 2 1.8 0.04 0.0 0.00 0
Zone 3 0.8 0.02 0.0 0.00 0
Zone 4 0.3 0.01 0.0 0.00 0
Zone 5 0.4 0.01 0.0 0.00 0
Zone 6 4.5 0.10 0.0 0.00 0
Zone 7 0.4 0.01 0.0 0.00 0
Zone 8 2.9 0.06 0.0 0.00 0
Zone 9 1.1 0.02 0.0 0.00 0
Zone 10 0.7 0.02 0.0 0.00 0
Zone 11 33.5 0.73 0.0 0.00 0

Space Loads and Airflows

69 of 331

Hourly Analysis Program v4.60 Page 2 of 3


Air System Design Load Summary for AHU-03
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:11PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 41.0 °C / 23.5 °C HEATING OA DB / WB 16.8 °C / 9.7 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 93 m² 3619 - 93 m² - -
Wall Transmission 30 m² 152 - 30 m² 41 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 93 m² 2176 - 93 m² 592 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 21 m² 490 - 21 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4411 W 4411 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 27410 W 27409 - 0 0 -
People 37 2657 2224 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 4091 222 10% 63 0
>> Total Zone Loads - 45003 2446 - 697 0
Zone Conditioning - 44852 2446 - 585 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 2727 L/s 1209 - 3347 L/s -1861 -
Ventilation Load 3810 L/s 86236 33156 3810 L/s 21579 0
Supply Fan Load 4770 L/s 9173 - 4352 L/s -7327 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 141470 35602 - 12976 0
Central Cooling Coil - 148744 35603 - 0 0
Terminal Reheat Coils - -26874 - - 12972 -
>> Total Conditioning - 121870 35603 - 12972 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

70 of 331

Hourly Analysis Program v4.60 Page 3 of 3


AHU-03 Input Data
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:19PM

1. General Details:
Air System Name AHU-03
Equipment Type Chilled Water AHU
Air System Type VAV
Number of zones 11

2. System Components:
Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Central Cooling Data:


Supply Air Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule * * MAMJJASON*
Capacity Control Constant Temperature - Fan On

Supply Fan Data:


Fan Type BI/AF with Variable Frequency Drive
Configuration Blow-thru
Fan Performance 1250 Pa
Overall Efficiency 65 %

% Airflow 100 90 80 70 60 50
% kW 100 77 57 42 30 21

% Airflow 40 30 20 10 0
% kW 15 13 10 7 5

Duct System Data:


Supply Duct Data:
Duct Heat Gain 0 %
Duct Leakage 0 %

Return Duct or Plenum Data:


Return Air Via Ducted Return

Return Fan Data:


Fan Type BI/AF with Variable Speed Drive
Fan Performance 600 Pa
Overall Efficiency 65 %

% Airflow 100 90 80 70 60 50
% kW 100 77 57 42 30 21

% Airflow 40 30 20 10 0
% kW 15 13 10 7 5

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
3-M-25 AIR LOCK x1
Zone 2: Zone 2
3-M-26&69 SCOPE WASHROOM x1
3-M-53 PROCED. RM ENDOSC x1
Zone 3: Zone 3
3-M-54 VASCULAR CLINIC x1
Zone 4: Zone 4
3-M-36 PATIENT PREP/REC x1
3-M-37 PATIENT PREP/REC x1
Zone 5: Zone 5
71 of 331

Hourly Analysis Program v4.60 Page 1 of 3


AHU-03 Input Data
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:19PM

3-M-33 CLEAN WORKROOM x1


3-M-34 RECEPTION x1
Zone 6: Zone 6
3-M-38 MICROBIOLOGY x1
Zone 7: Zone 7
3-M-43 PHLEBOTOMY x1
3-M-45 PHLEBOTOMY x1
Zone 8: Zone 8
3-M-42 LABORATORY x1
Zone 9: Zone 9
3-M-39 MEDIA STERLIZ. x1
Zone 10: Zone 10
3-M-27 CASTRO CLINIC x1
Zone 11: Zone 11
3-M-28 GENERAL SURG. CLC x1
3-Balanced FA x1

Thermostats and Zone Data:

T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)
1 22.0 26.0 21.0 18.0 2.00 100 0.0 0.0
2 22.0 26.0 21.0 18.0 2.00 100 770.0 0.0
3 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
4 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
5 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
6 22.0 26.0 21.0 18.0 2.00 100 480.0 0.0
7 22.0 26.0 21.0 18.0 2.00 100 0.0 0.0
8 22.0 26.0 21.0 18.0 2.00 100 1530.0 0.0
9 22.0 26.0 21.0 18.0 2.00 100 935.0 0.0
10 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
11 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0

Thermostat Schedule FAN THERMOSTAT 24/7


Unoccupied Cooling is Available

Supply Terminals Data:

Fan Design Supply


Zone Terminal Type Min. Airflow Fan Performance Efficiency Temperature
1 VAV box with RH 115.0 L/s - - -
2 VAV box with RH 0.00 L/s/person - - -
3 VAV box with RH 0.00 L/s/person - - -
4 VAV box with RH 0.00 L/s/person - - -
5 VAV box with RH 0.00 L/s/person - - -
6 VAV box with RH 455.0 L/s - - -
7 VAV box with RH 6.00 ACH - - -
8 VAV box with RH 0.00 L/s/person - - -
9 VAV box with RH 0.00 L/s/person - - -
10 VAV box with RH 0.00 L/s/person - - -
11 VAV box with RH 0.00 L/s/person - - -

Reheat Coil Source Hot Water


Reheat Coil Schedule JFMAMJJASOND

Zone Heating Units:


Zone All
Zone Heating Unit Type None 72 of 331

Hourly Analysis Program v4.60 Page 2 of 3


AHU-03 Input Data
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:19PM

Zone Unit Heat Source Hot Water


Zone Heating Unit Schedule JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature 12.8 °C
Supply Fan Airflow 4769.9 L/s
Ventilation Airflow 3810.0 L/s

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.0 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) -
1 115.0 - 1.1 -
2 770.0 - 1.8 -
3 224.6 - 0.8 -
4 82.6 - 0.3 -
5 188.6 - 0.4 -
6 480.0 - 4.5 -
7 42.4 - 0.4 -
8 1530.0 - 2.9 -
9 935.0 - 1.1 -
10 203.4 - 0.7
11 3005.0 - 33.5

5. Equipment Data
No Equipment Data required for this system.

73 of 331

Hourly Analysis Program v4.60 Page 3 of 3


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

3-Balanced FA

1. General Details:
Floor Area 0.0 m²
Avg. Ceiling Height 2.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2940.0 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 0.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule None Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.00 W/m²
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

74 of 331

Hourly Analysis Program v4.60 Page 1 of 16


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

3-M-25 AIR LOCK

1. General Details:
Floor Area 5.3 m²
Avg. Ceiling Height 2.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

75 of 331

Hourly Analysis Program v4.60 Page 2 of 16


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

3-M-26&69 SCOPE WASHROOM

1. General Details:
Floor Area 7.8 m²
Avg. Ceiling Height 2.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 30.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 600.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 8.5 12 0 0

3.1. Construction Types for Exposure N


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

76 of 331

Hourly Analysis Program v4.60 Page 3 of 16


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

3-M-27 CASTRO CLINIC

1. General Details:
Floor Area 13.6 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 60.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1265.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 12.0 18 0 0

3.1. Construction Types for Exposure N


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

77 of 331

Hourly Analysis Program v4.60 Page 4 of 16


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

3-M-28 GENERAL SURG. CLC

1. General Details:
Floor Area 14.1 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 65.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1265.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 3.8 7 0 0
N 12.1 21 0 0

3.1. Construction Types for Exposure W


Wall Type EXTERIOR WALL
1st Window Type W

3.2. Construction Types for Exposure N


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 11.4 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C

78 of 331

Hourly Analysis Program v4.60 Page 5 of 16


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

3-M-33 CLEAN WORKROOM

1. General Details:
Floor Area 4.3 m²
Avg. Ceiling Height 2.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 5.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 120.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 9.1 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C

79 of 331

Hourly Analysis Program v4.60 Page 6 of 16


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

3-M-34 RECEPTION

1. General Details:
Floor Area 18.8 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 30.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1140.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

80 of 331

Hourly Analysis Program v4.60 Page 7 of 16


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

3-M-36 PATIENT PREP/REC

1. General Details:
Floor Area 8.8 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 175.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

81 of 331

Hourly Analysis Program v4.60 Page 8 of 16


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

3-M-37 PATIENT PREP/REC

1. General Details:
Floor Area 9.8 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 90.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

82 of 331

Hourly Analysis Program v4.60 Page 9 of 16


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

3-M-38 MICROBIOLOGY

1. General Details:
Floor Area 17.5 m²
Avg. Ceiling Height 2.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 50.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 2325.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

83 of 331

Hourly Analysis Program v4.60 Page 10 of 16


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

3-M-39 MEDIA STERLIZ.

1. General Details:
Floor Area 12.2 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 110.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 8095.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 9.4 15 0 0

3.1. Construction Types for Exposure NE


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

84 of 331

Hourly Analysis Program v4.60 Page 11 of 16


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

3-M-42 LABORATORY

1. General Details:
Floor Area 89.2 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 265.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 9.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 9130.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 46.8 68 0 0

3.1. Construction Types for Exposure NE


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

85 of 331

Hourly Analysis Program v4.60 Page 12 of 16


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

3-M-43 PHLEBOTOMY

1. General Details:
Floor Area 5.0 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 5.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

86 of 331

Hourly Analysis Program v4.60 Page 13 of 16


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

3-M-45 PHLEBOTOMY

1. General Details:
Floor Area 4.8 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 5.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

87 of 331

Hourly Analysis Program v4.60 Page 14 of 16


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

3-M-53 PROCED. RM ENDOSC

1. General Details:
Floor Area 26.1 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 145.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 5.0 People
Wattage 25.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1940.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 14.4 21 0 0

3.1. Construction Types for Exposure NE


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

88 of 331

Hourly Analysis Program v4.60 Page 15 of 16


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

3-M-54 VASCULAR CLINIC

1. General Details:
Floor Area 18.0 m²
Avg. Ceiling Height 2.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 60.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1265.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 16.0 23 0 0

3.1. Construction Types for Exposure N


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

89 of 331

Hourly Analysis Program v4.60 Page 16 of 16


Air System Sizing Summary for AHU-04
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:12PM

Air System Information


Air System Name AHU-04 Number of zones 14
Equipment Class CW AHU Floor Area 289.0 m²
Air System Type VAV Location Jeddah, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Central Cooling Coil Sizing Data


Total coil load 63.6 kW Load occurs at Aug 1500
Sensible coil load 53.2 kW OA DB / WB 41.0 / 23.5 °C
Coil L/s at Aug 1500 2285 L/s Entering DB / WB 32.1 / 20.0 °C
Max block L/s at Dec 1500 2853 L/s Leaving DB / WB 12.8 / 11.7 °C
Sum of peak zone L/s 2917 L/s Coil ADP 10.6 °C
Sensible heat ratio 0.836 Bypass Factor 0.100
m²/kW 4.5 Resulting RH 47 %
W/m² 220.2 Design supply temp. 12.8 °C
Water flow @ 6.0 °K rise 2.54 L/s Zone T-stat Check 14 of 14 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s at Dec 1500 2853 L/s Fan motor BHP 6.92 BHP
Standard L/s 2847 L/s Fan motor kW 5.49 kW
Actual max L/(s-m²) 9.87 L/(s-m²) Fan static 1250 Pa

Return Fan Sizing Data


Actual max L/s at Dec 1500 2853 L/s Fan motor BHP 3.32 BHP
Standard L/s 2847 L/s Fan motor kW 2.63 kW
Actual max L/(s-m²) 9.87 L/(s-m²) Fan static 600 Pa

Outdoor Ventilation Air Data


Design airflow L/s 875 L/s L/s/person 11.51 L/s/person
L/(s-m²) 3.03 L/(s-m²)

90 of 331

Hourly Analysis Program v4.60 Page 1 of 4


Zone Sizing Summary for AHU-04
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:12PM

Air System Information


Air System Name AHU-04 Number of zones 14
Equipment Class CW AHU Floor Area 289.0 m²
Air System Type VAV Location Jeddah, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (kW) (L/s) (L/s) Load (kW) (m²) L/(s-m²)
Zone 1 2.6 213 60 Sep 1600 0.1 18.2 11.72
Zone 2 3.0 240 65 Jan 1600 0.1 16.1 14.87
Zone 3 3.6 295 80 Dec 1500 0.1 20.1 14.68
Zone 4 2.8 227 55 Dec 1400 0.1 15.4 14.78
Zone 5 3.0 244 55 Dec 1400 0.1 16.9 14.41
Zone 6 3.0 243 55 Dec 1400 0.1 17.6 13.79
Zone 7 2.9 233 55 Dec 1400 0.1 15.4 15.10
Zone 8 2.2 180 40 Dec 1400 0.1 13.6 13.20
Zone 9 4.6 342 122 Nov 1400 0.2 29.0 11.80
Zone 10 0.3 40 40 Jan 2300 0.0 13.0 3.11
Zone 11 1.2 101 10 Jan 2300 0.0 8.4 12.07
Zone 12 3.9 286 122 Jul 0900 0.1 28.5 10.02
Zone 13 2.2 231 231 Jul 1500 0.0 67.4 3.43
Zone 14 0.5 41 15 Jan 2300 0.0 9.4 4.37

Zone Terminal Sizing Data

Reheat Zone Zone


Reheat Coil Htg Htg Mixing
Coil Water Coil Water Box Fan
Load L/s Load L/s Airflow
Zone Name (kW) @ 11.0 °K (kW) @ 11.0 °K (L/s)
Zone 1 0.8 0.02 0.0 0.00 0
Zone 2 0.8 0.02 0.0 0.00 0
Zone 3 1.0 0.02 0.0 0.00 0
Zone 4 0.7 0.01 0.0 0.00 0
Zone 5 0.7 0.01 0.0 0.00 0
Zone 6 0.7 0.01 0.0 0.00 0
Zone 7 0.7 0.01 0.0 0.00 0
Zone 8 0.5 0.01 0.0 0.00 0
Zone 9 1.6 0.03 0.0 0.00 0
Zone 10 0.4 0.01 0.0 0.00 0
Zone 11 0.1 0.00 0.0 0.00 0
Zone 12 1.5 0.03 0.0 0.00 0
Zone 13 2.6 0.06 0.0 0.00 0
Zone 14 0.2 0.00 0.0 0.00 0

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
4-M-01 PODIATRY CLINIC 1 2.6 Sep 1600 213 0.1 18.2 11.72
Zone 2
91 of 331

Hourly Analysis Program v4.60 Page 2 of 4


Zone Sizing Summary for AHU-04
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:12PM

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
4-M-02 PEDIATRIC DIABET. 1 3.0 Jan 1600 240 0.1 16.1 14.87
Zone 3
4-M-03 ADULT DIABET. CLC 1 3.6 Dec 1500 295 0.1 20.1 14.68
Zone 4
4-M-04 ADULT DIABET. CLC 1 2.8 Dec 1400 227 0.1 15.4 14.78
Zone 5
4-M-05 NEPHROLOGY CLC 1 3.0 Dec 1400 244 0.1 16.9 14.41
Zone 6
4-M-06 OPHTHALMIC CLC 1 3.0 Dec 1400 243 0.1 17.6 13.79
Zone 7
4-M-07 OPHTHALMIC CLINIC 1 2.9 Dec 1400 233 0.1 15.4 15.10
Zone 8
4-M-08 LASER CLINIC 1 2.2 Dec 1400 180 0.1 13.6 13.20
Zone 9
4-M-09 CLASS ROOM 1 4.6 Nov 1400 342 0.2 29.0 11.80
Zone 10
4-M-11 CORRIDOR 1 0.3 Jan 2300 40 0.0 13.0 3.11
Zone 11
4-M-14 OFFICE 1 1.2 Jan 2300 101 0.0 8.4 12.07
Zone 12
4-M-15 CLASS ROOM 1 3.9 Jul 0900 286 0.1 28.5 10.02
Zone 13
4-M-17 CLEAN UTILITY 1 0.9 Jul 1500 96 0.0 6.7 14.33
4-M-20 CORRIDOR 1 1.3 Jan 2300 212 0.0 60.7 3.50
Zone 14
4-M-65 ASESSMENT 1 0.5 Jan 2300 41 0.0 9.4 4.37

92 of 331

Hourly Analysis Program v4.60 Page 3 of 4


Air System Design Load Summary for AHU-04
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:12PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 41.0 °C / 23.5 °C HEATING OA DB / WB 16.8 °C / 9.7 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 101 m² 4309 - 101 m² - -
Wall Transmission 95 m² 429 - 95 m² 148 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 101 m² 2222 - 101 m² 732 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 6 m² 143 - 6 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 5003 W 5002 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 11030 W 11029 - 0 0 -
People 76 5457 4568 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 2859 457 10% 88 0
>> Total Zone Loads - 31451 5024 - 968 0
Zone Conditioning - 31033 5024 - 814 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 2285 L/s 1506 - 1006 L/s -370 -
Ventilation Load 875 L/s 17124 5428 875 L/s 4992 0
Supply Fan Load 2285 L/s 3138 - 1006 L/s -771 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 52801 10452 - 4664 0
Central Cooling Coil - 53186 10453 - 0 0
Terminal Reheat Coils - -385 - - 4664 -
>> Total Conditioning - 52801 10453 - 4664 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

93 of 331

Hourly Analysis Program v4.60 Page 4 of 4


AHU-04 Input Data
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:19PM

1. General Details:
Air System Name AHU-04
Equipment Type Chilled Water AHU
Air System Type VAV
Number of zones 14

2. System Components:
Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Central Cooling Data:


Supply Air Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule * * MAMJJASON*
Capacity Control Constant Temperature - Fan On

Supply Fan Data:


Fan Type BI/AF with Variable Frequency Drive
Configuration Blow-thru
Fan Performance 1250 Pa
Overall Efficiency 65 %

% Airflow 100 90 80 70 60 50
% kW 100 77 57 42 30 21

% Airflow 40 30 20 10 0
% kW 15 13 10 7 5

Duct System Data:


Supply Duct Data:
Duct Heat Gain 0 %
Duct Leakage 0 %

Return Duct or Plenum Data:


Return Air Via Ducted Return

Return Fan Data:


Fan Type BI/AF with Variable Speed Drive
Fan Performance 600 Pa
Overall Efficiency 65 %

% Airflow 100 90 80 70 60 50
% kW 100 77 57 42 30 21

% Airflow 40 30 20 10 0
% kW 15 13 10 7 5

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
4-M-01 PODIATRY CLINIC x1
Zone 2: Zone 2
4-M-02 PEDIATRIC DIABET. x1
Zone 3: Zone 3
4-M-03 ADULT DIABET. CLC x1
Zone 4: Zone 4
4-M-04 ADULT DIABET. CLC x1
Zone 5: Zone 5
4-M-05 NEPHROLOGY CLC x1
Zone 6: Zone 6
94 of 331

Hourly Analysis Program v4.60 Page 1 of 3


AHU-04 Input Data
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:19PM

4-M-06 OPHTHALMIC CLC x1


Zone 7: Zone 7
4-M-07 OPHTHALMIC CLINIC x1
Zone 8: Zone 8
4-M-08 LASER CLINIC x1
Zone 9: Zone 9
4-M-09 CLASS ROOM x1
Zone 10: Zone 10
4-M-11 CORRIDOR x1
Zone 11: Zone 11
4-M-14 OFFICE x1
Zone 12: Zone 12
4-M-15 CLASS ROOM x1
Zone 13: Zone 13
4-M-17 CLEAN UTILITY x1
4-M-20 CORRIDOR x1
Zone 14: Zone 14
4-M-65 ASESSMENT x1

Thermostats and Zone Data:

T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)
1 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
2 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
3 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
4 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
5 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
6 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
7 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
8 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
9 24.0 26.0 22.0 18.0 2.00 100 0.0 0.0
10 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
11 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
12 24.0 26.0 22.0 18.0 2.00 100 0.0 0.0
13 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
14 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0

Thermostat Schedule FAN THERMOSTAT 24/7


Unoccupied Cooling is Available

Supply Terminals Data:

Fan Design Supply


Zone Terminal Type Min. Airflow Fan Performance Efficiency Temperature
1 VAV box with RH 0.00 L/s/person - - -
2 VAV box with RH 0.00 L/s/person - - -
3 VAV box with RH 0.00 L/s/person - - -
4 VAV box with RH 0.00 L/s/person - - -
5 VAV box with RH 0.00 L/s/person - - -
6 VAV box with RH 0.00 L/s/person - - -
7 VAV box with RH 0.00 L/s/person - - -
8 VAV box with RH 0.00 L/s/person - - -
9 VAV box with RH 0.00 L/s/person - - -
10 VAV box with RH 4.00 ACH - - -
11 VAV box with RH 0.00 L/s/person - - -
95 of 331

Hourly Analysis Program v4.60 Page 2 of 3


AHU-04 Input Data
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:19PM

Fan Design Supply


Zone Terminal Type Min. Airflow Fan Performance Efficiency Temperature
12 VAV box with RH 0.00 L/s/person - - -
13 VAV box with RH 4.00 ACH - - -
14 VAV box with RH 0.00 L/s/person - - -

Reheat Coil Source Hot Water


Reheat Coil Schedule JFMAMJJASOND

Zone Heating Units:


Zone All
Zone Heating Unit Type None

Zone Unit Heat Source Hot Water


Zone Heating Unit Schedule JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature 12.8 °C
Supply Fan Airflow 2853.5 L/s
Ventilation Airflow 874.5 L/s

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.0 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) -
1 213.0 - 0.8 -
2 239.9 - 0.8 -
3 295.0 - 1.0 -
4 227.5 - 0.7 -
5 244.1 - 0.7 -
6 242.7 - 0.7 -
7 232.9 - 0.7 -
8 180.0 - 0.5 -
9 342.3 - 1.6 -
10 40.5 - 0.4 -
11 101.0 - 0.1 -
12 285.7 - 1.5 -
13 231.0 - 2.6
14 41.1 - 0.2

5. Equipment Data
No Equipment Data required for this system.

96 of 331

Hourly Analysis Program v4.60 Page 3 of 3


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

4-M-01 PODIATRY CLINIC

1. General Details:
Floor Area 18.2 m²
Avg. Ceiling Height 2.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 60.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 795.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 17.3 17 0 0
NW 9.5 0 0 0

3.1. Construction Types for Exposure WSW


Wall Type EXTERIOR WALL
1st Window Type W

3.2. Construction Types for Exposure NW


Wall Type EXTERIOR WALL

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

97 of 331

Hourly Analysis Program v4.60 Page 1 of 15


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

4-M-02 PEDIATRIC DIABET.

1. General Details:
Floor Area 16.1 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 65.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1175.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 16.2 16 0 0

3.1. Construction Types for Exposure SW


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

98 of 331

Hourly Analysis Program v4.60 Page 2 of 15


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

4-M-03 ADULT DIABET. CLC

1. General Details:
Floor Area 20.1 m²
Avg. Ceiling Height 2.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 80.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1175.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 13.0 13 0 0
WSW 13.0 13 0 0

3.1. Construction Types for Exposure S


Wall Type EXTERIOR WALL
1st Window Type W

3.2. Construction Types for Exposure WSW


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

99 of 331

Hourly Analysis Program v4.60 Page 3 of 15


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

4-M-04 ADULT DIABET. CLC

1. General Details:
Floor Area 15.4 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 55.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1175.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 13.0 13 0 0

3.1. Construction Types for Exposure S


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

100 of 331

Hourly Analysis Program v4.60 Page 4 of 15


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

4-M-05 NEPHROLOGY CLC

1. General Details:
Floor Area 16.9 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 55.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1265.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 13.9 14 0 0

3.1. Construction Types for Exposure S


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

101 of 331

Hourly Analysis Program v4.60 Page 5 of 15


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

4-M-06 OPHTHALMIC CLC

1. General Details:
Floor Area 17.6 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 55.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1235.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 14.4 14 0 0

3.1. Construction Types for Exposure S


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

102 of 331

Hourly Analysis Program v4.60 Page 6 of 15


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

4-M-07 OPHTHALMIC CLINIC

1. General Details:
Floor Area 15.4 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 55.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1235.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 13.0 13 0 0

3.1. Construction Types for Exposure S


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

103 of 331

Hourly Analysis Program v4.60 Page 7 of 15


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

4-M-08 LASER CLINIC

1. General Details:
Floor Area 13.6 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 40.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 880.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 11.2 11 0 0

3.1. Construction Types for Exposure S


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

104 of 331

Hourly Analysis Program v4.60 Page 8 of 15


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

4-M-09 CLASS ROOM

1. General Details:
Floor Area 29.0 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage EDUCATION: Classroom (age 9+)
OA Requirement 1 5.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 21.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 300.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 17.5 17 0 0
E 22.1 32 0 0

3.1. Construction Types for Exposure S


Wall Type EXTERIOR WALL
1st Window Type W

3.2. Construction Types for Exposure E


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

105 of 331

Hourly Analysis Program v4.60 Page 9 of 15


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

4-M-11 CORRIDOR

1. General Details:
Floor Area 13.0 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 20.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

106 of 331

Hourly Analysis Program v4.60 Page 10 of 15


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

4-M-14 OFFICE

1. General Details:
Floor Area 8.4 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 790.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

107 of 331

Hourly Analysis Program v4.60 Page 11 of 15


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

4-M-15 CLASS ROOM

1. General Details:
Floor Area 28.5 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage EDUCATION: Classroom (age 9+)
OA Requirement 1 5.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 21.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 300.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 21.5 28 0 0

3.1. Construction Types for Exposure E


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

108 of 331

Hourly Analysis Program v4.60 Page 12 of 15


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

4-M-17 CLEAN UTILITY

1. General Details:
Floor Area 6.7 m²
Avg. Ceiling Height 2.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 530.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 6.0 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C

109 of 331

Hourly Analysis Program v4.60 Page 13 of 15


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

4-M-20 CORRIDOR

1. General Details:
Floor Area 60.7 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 105.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

110 of 331

Hourly Analysis Program v4.60 Page 14 of 15


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

4-M-65 ASESSMENT

1. General Details:
Floor Area 9.4 m²
Avg. Ceiling Height 2.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 175.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

111 of 331

Hourly Analysis Program v4.60 Page 15 of 15


Air System Sizing Summary for AHU-05
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:12PM

Air System Information


Air System Name AHU-05 Number of zones 26
Equipment Class CW AHU Floor Area 442.5 m²
Air System Type VAV Location Jeddah, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Central Cooling Coil Sizing Data


Total coil load 103.5 kW Load occurs at Jun 1500
Sensible coil load 89.0 kW OA DB / WB 40.4 / 23.5 °C
Coil L/s at Jun 1500 4147 L/s Entering DB / WB 30.6 / 19.3 °C
Max block L/s at Jun 1600 4760 L/s Leaving DB / WB 12.8 / 11.8 °C
Sum of peak zone L/s 4889 L/s Coil ADP 10.8 °C
Sensible heat ratio 0.860 Bypass Factor 0.100
m²/kW 4.3 Resulting RH 46 %
W/m² 233.9 Design supply temp. 12.8 °C
Water flow @ 6.0 °K rise 4.13 L/s Zone T-stat Check 26 of 26 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s at Jun 1600 4760 L/s Fan motor BHP 11.54 BHP
Standard L/s 4749 L/s Fan motor kW 9.15 kW
Actual max L/(s-m²) 10.76 L/(s-m²) Fan static 1250 Pa

Return Fan Sizing Data


Actual max L/s at Jun 1600 4760 L/s Fan motor BHP 5.54 BHP
Standard L/s 4749 L/s Fan motor kW 4.39 kW
Actual max L/(s-m²) 10.76 L/(s-m²) Fan static 600 Pa

Outdoor Ventilation Air Data


Design airflow L/s 1225 L/s L/s/person 16.12 L/s/person
L/(s-m²) 2.77 L/(s-m²)

112 of 331

Hourly Analysis Program v4.60 Page 1 of 5


Zone Sizing Summary for AHU-05
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:12PM

Air System Information


Air System Name AHU-05 Number of zones 26
Equipment Class CW AHU Floor Area 442.5 m²
Air System Type VAV Location Jeddah, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (kW) (L/s) (L/s) Load (kW) (m²) L/(s-m²)
Zone 1 3.5 313 60 Jun 0900 0.1 10.8 28.96
Zone 2 3.0 246 80 Jun 0900 0.1 13.6 18.06
Zone 3 2.3 227 227 Jul 1900 0.1 62.9 3.61
Zone 4 2.3 189 55 Jun 0900 0.1 15.7 12.05
Zone 5 0.7 166 166 Jul 1900 0.0 11.6 14.30
Zone 6 1.6 132 45 Jun 0900 0.1 9.1 14.49
Zone 7 2.5 206 60 Jun 0900 0.1 14.2 14.47
Zone 8 2.6 208 65 Jun 0900 0.1 15.0 13.88
Zone 9 2.5 203 65 Jun 0900 0.1 15.2 13.36
Zone 10 0.5 38 15 Jan 2300 0.0 7.0 5.47
Zone 11 2.5 203 60 Jun 1400 0.0 14.6 13.94
Zone 12 1.7 135 40 Jan 2300 0.0 9.4 14.39
Zone 13 0.5 62 62 Jan 2300 0.0 19.9 3.11
Zone 14 2.4 195 75 Jun 1500 0.1 13.2 14.71
Zone 15 1.8 146 60 Jun 1700 0.1 13.6 10.74
Zone 16 2.3 189 30 Jun 1700 0.1 16.8 11.23
Zone 17 2.1 172 30 Jun 1700 0.1 17.9 9.64
Zone 18 1.9 158 30 Jun 1700 0.1 17.1 9.25
Zone 19 1.6 138 138 Jan 2300 0.0 44.9 3.08
Zone 20 2.2 199 2 Jan 2300 0.0 6.9 28.88
Zone 21 1.9 153 20 Aug 1500 0.0 15.4 9.92
Zone 22 3.0 242 35 Dec 1400 0.1 13.8 17.60
Zone 23 2.0 166 25 Jun 1700 0.1 17.8 9.35
Zone 24 3.2 258 40 Jul 1700 0.1 15.0 17.23
Zone 25 3.0 245 40 Jul 1700 0.1 13.0 18.76
Zone 26 3.7 299 45 Jul 1700 0.1 18.0 16.56

Zone Terminal Sizing Data

Reheat Zone Zone


Reheat Coil Htg Htg Mixing
Coil Water Coil Water Box Fan
Load L/s Load L/s Airflow
Zone Name (kW) @ 11.0 °K (kW) @ 11.0 °K (L/s)
Zone 1 0.6 0.01 0.0 0.00 0
Zone 2 1.0 0.02 0.0 0.00 0
Zone 3 2.6 0.06 0.0 0.00 0
Zone 4 0.7 0.02 0.0 0.00 0
Zone 5 1.9 0.04 0.0 0.00 0
Zone 6 0.6 0.01 0.0 0.00 0
Zone 7 0.8 0.02 0.0 0.00 0
Zone 8 0.8 0.02 0.0 0.00 0
Zone 9 0.8 0.02 0.0 0.00 0
Zone 10 0.2 0.00 0.0 0.00 0
113 of 331

Hourly Analysis Program v4.60 Page 2 of 5


Zone Sizing Summary for AHU-05
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:12PM

Reheat Zone Zone


Reheat Coil Htg Htg Mixing
Coil Water Coil Water Box Fan
Load L/s Load L/s Airflow
Zone Name (kW) @ 11.0 °K (kW) @ 11.0 °K (L/s)
Zone 11 0.7 0.02 0.0 0.00 0
Zone 12 0.4 0.01 0.0 0.00 0
Zone 13 0.7 0.01 0.0 0.00 0
Zone 14 0.9 0.02 0.0 0.00 0
Zone 15 0.7 0.02 0.0 0.00 0
Zone 16 0.4 0.01 0.0 0.00 0
Zone 17 0.4 0.01 0.0 0.00 0
Zone 18 0.4 0.01 0.0 0.00 0
Zone 19 1.5 0.03 0.0 0.00 0
Zone 20 0.0 0.00 0.0 0.00 0
Zone 21 0.2 0.00 0.0 0.00 0
Zone 22 0.5 0.01 0.0 0.00 0
Zone 23 0.3 0.01 0.0 0.00 0
Zone 24 0.5 0.01 0.0 0.00 0
Zone 25 0.5 0.01 0.0 0.00 0
Zone 26 0.6 0.01 0.0 0.00 0

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
5-F-068 ULTRA SOUND 1 3.5 Jun 0900 313 0.1 10.8 28.96
Zone 2
5-F-069 OB/GY CLINIC 1 3.0 Jun 0900 246 0.1 13.6 18.06
Zone 3
5-F-072 CLEAN UTILITY 1 0.8 Jan 2300 75 0.0 6.6 11.40
5-F-077 CORRIDOR 1 1.6 Jul 1900 209 0.1 56.3 3.72
Zone 4
5-F-076 OB/GY CLINIC 1 2.3 Jun 0900 189 0.1 15.7 12.05
Zone 5
5-F-078 PROCEDURE TRT 1 0.7 Jul 1900 166 0.0 11.6 14.30
Zone 6
5-F-082 IMMUNIZATION 1 1.6 Jun 0900 132 0.1 9.1 14.49
Zone 7
5-F-083 PEDIATRIC CLc 1 2.5 Jun 0900 206 0.1 14.2 14.47
Zone 8
5-F-086 PEDIATRIC CLINIC 1 2.6 Jun 0900 208 0.1 15.0 13.88
Zone 9
5-F-087 FAMILY MEDICINE 1 2.5 Jun 0900 203 0.1 15.2 13.36
Zone 10
5-F-088 VITAL SIGN 1 0.5 Jan 2300 38 0.0 7.0 5.47
Zone 11
5-F-091 FAMILY MEDICINE 1 2.5 Jun 1400 203 0.0 14.6 13.94
Zone 12
5-F-095 STRESS ECG ROOM 1 1.7 Jan 2300 135 0.0 9.4 14.39
Zone 13
5-F-096 CORRIDOR 1 0.5 Jan 2300 62 0.0 19.9 3.11
Zone 14
5-F-097 INTERNAL MEDIC. 1 2.4 Jun 1500 195 0.1 13.2 14.71
Zone 15
5-F-098 ECG 1 1.8 Jun 1700 146 0.1 13.6 10.74
Zone 16
5-F-099 CARDIOLOGY CLNC. 1 2.3 Jun 1700 189 0.1 16.8 11.23
Zone 17 114 of 331

Hourly Analysis Program v4.60 Page 3 of 5


Zone Sizing Summary for AHU-05
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:12PM

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
5-F-104 ENT CLINIC 1 2.1 Jun 1700 172 0.1 17.9 9.64
Zone 18
5-F-105 ENT CLINIC 1 1.9 Jun 1700 158 0.1 17.1 9.25
Zone 19
5-F-106 CORRIDOR 1 0.9 Jan 2300 130 0.0 41.9 3.11
5-F-110 CLEAN UTILITY 1 0.7 Jan 2300 60 0.0 3.0 19.95
Zone 20
5-F-107 DENTAL SERIALIZ. 1 2.2 Jan 2300 199 0.0 6.9 28.88
Zone 21
5-F-108 DENTAL CLINIC 1 1.9 Aug 1500 153 0.0 15.4 9.92
Zone 22
5-F-109 DENTAL CLINIC 1 3.0 Dec 1400 242 0.1 13.8 17.60
Zone 23
5-F-112 ENT CLINIC 1 2.0 Jun 1700 166 0.1 17.8 9.35
Zone 24
5-F-113 FLEXIBLE CLINIC 1 3.2 Jul 1700 258 0.1 15.0 17.23
Zone 25
5-F-115 FLEXIBLE CLINIC 1 3.0 Jul 1700 245 0.1 13.0 18.76
Zone 26
5-F-116 DENTAL CLINIC 1 3.7 Jul 1700 299 0.1 18.0 16.56

115 of 331

Hourly Analysis Program v4.60 Page 4 of 5


Air System Design Load Summary for AHU-05
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:12PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 40.4 °C / 23.5 °C HEATING OA DB / WB 16.8 °C / 9.7 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 132 m² 6227 - 132 m² - -
Wall Transmission 183 m² 842 - 183 m² 285 -
Roof Transmission 106 m² 617 - 106 m² 165 -
Window Transmission 132 m² 2886 - 132 m² 947 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 48 m² 1104 - 48 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 8088 W 8088 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 25195 W 25194 - 0 0 -
People 76 5457 4568 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 5041 457 10% 140 0
>> Total Zone Loads - 55454 5024 - 1536 0
Zone Conditioning - 54698 5024 - 1252 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 4147 L/s 3130 - 1570 L/s -598 -
Ventilation Load 1225 L/s 23341 9457 1225 L/s 7074 0
Supply Fan Load 4147 L/s 6521 - 1570 L/s -1245 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 87690 14482 - 6484 0
Central Cooling Coil - 89020 14482 - 0 0
Terminal Reheat Coils - -1330 - - 6481 -
>> Total Conditioning - 87690 14482 - 6481 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

116 of 331

Hourly Analysis Program v4.60 Page 5 of 5


AHU-05 Input Data
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:19PM

1. General Details:
Air System Name AHU-05
Equipment Type Chilled Water AHU
Air System Type VAV
Number of zones 26

2. System Components:
Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Central Cooling Data:


Supply Air Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule * * MAMJJASON*
Capacity Control Constant Temperature - Fan On

Supply Fan Data:


Fan Type BI/AF with Variable Frequency Drive
Configuration Blow-thru
Fan Performance 1250 Pa
Overall Efficiency 65 %

% Airflow 100 90 80 70 60 50
% kW 100 77 57 42 30 21

% Airflow 40 30 20 10 0
% kW 15 13 10 7 5

Duct System Data:


Supply Duct Data:
Duct Heat Gain 0 %
Duct Leakage 0 %

Return Duct or Plenum Data:


Return Air Via Ducted Return

Return Fan Data:


Fan Type BI/AF with Variable Speed Drive
Fan Performance 600 Pa
Overall Efficiency 65 %

% Airflow 100 90 80 70 60 50
% kW 100 77 57 42 30 21

% Airflow 40 30 20 10 0
% kW 15 13 10 7 5

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
5-F-068 ULTRA SOUND x1
Zone 2: Zone 2
5-F-069 OB/GY CLINIC x1
Zone 3: Zone 3
5-F-072 CLEAN UTILITY x1
5-F-077 CORRIDOR x1
Zone 4: Zone 4
5-F-076 OB/GY CLINIC x1
Zone 5: Zone 5
5-F-078 PROCEDURE TRT x1
117 of 331

Hourly Analysis Program v4.60 Page 1 of 5


AHU-05 Input Data
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:19PM

Zone 6: Zone 6
5-F-082 IMMUNIZATION x1
Zone 7: Zone 7
5-F-083 PEDIATRIC CLc x1
Zone 8: Zone 8
5-F-086 PEDIATRIC CLINIC x1
Zone 9: Zone 9
5-F-087 FAMILY MEDICINE x1
Zone 10: Zone 10
5-F-088 VITAL SIGN x1
Zone 11: Zone 11
5-F-091 FAMILY MEDICINE x1
Zone 12: Zone 12
5-F-095 STRESS ECG ROOM x1
Zone 13: Zone 13
5-F-096 CORRIDOR x1
Zone 14: Zone 14
5-F-097 INTERNAL MEDIC. x1
Zone 15: Zone 15
5-F-098 ECG x1
Zone 16: Zone 16
5-F-099 CARDIOLOGY CLNC. x1
Zone 17: Zone 17
5-F-104 ENT CLINIC x1
Zone 18: Zone 18
5-F-105 ENT CLINIC x1
Zone 19: Zone 19
5-F-106 CORRIDOR x1
5-F-110 CLEAN UTILITY x1
Zone 20: Zone 20
5-F-107 DENTAL SERIALIZ. x1
Zone 21: Zone 21
5-F-108 DENTAL CLINIC x1
Zone 22: Zone 22
5-F-109 DENTAL CLINIC x1
Zone 23: Zone 23
5-F-112 ENT CLINIC x1
Zone 24: Zone 24
5-F-113 FLEXIBLE CLINIC x1
Zone 25: Zone 25
5-F-115 FLEXIBLE CLINIC x1
Zone 26: Zone 26
5-F-116 DENTAL CLINIC x1

Thermostats and Zone Data:

T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)
1 22.0 26.0 21.0 18.0 2.00 100 0.0 0.0
2 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
3 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
4 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
5 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
6 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
7 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
8 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
9 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
118 of 331

Hourly Analysis Program v4.60 Page 2 of 5


AHU-05 Input Data
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:19PM

T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)
10 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
11 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
12 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
13 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
14 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
15 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
16 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
17 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
18 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
19 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
20 22.0 26.0 21.0 18.0 2.00 100 0.0 0.0
21 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
22 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
23 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
24 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
25 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
26 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0

Thermostat Schedule FAN THERMOSTAT 24/7


Unoccupied Cooling is Available

Supply Terminals Data:

Fan Design Supply


Zone Terminal Type Min. Airflow Fan Performance Efficiency Temperature
1 VAV box with RH 0.00 L/s/person - - -
2 VAV box with RH 0.00 L/s/person - - -
3 VAV box with RH 4.00 ACH - - -
4 VAV box with RH 0.00 L/s/person - - -
5 VAV box with RH 20.00 ACH - - -
6 VAV box with RH 0.00 L/s/person - - -
7 VAV box with RH 0.00 L/s/person - - -
8 VAV box with RH 0.00 L/s/person - - -
9 VAV box with RH 0.00 L/s/person - - -
10 VAV box with RH 0.00 L/s/person - - -
11 VAV box with RH 0.00 L/s/person - - -
12 VAV box with RH 0.00 L/s/person - - -
13 VAV box with RH 4.00 ACH - - -
14 VAV box with RH 0.00 L/s/person - - -
15 VAV box with RH 0.00 L/s/person - - -
16 VAV box with RH 0.00 L/s/person - - -
17 VAV box with RH 0.00 L/s/person - - -
18 VAV box with RH 0.00 L/s/person - - -
19 VAV box with RH 4.00 ACH - - -
20 VAV box with RH 0.00 L/s/person - - -
21 VAV box with RH 0.00 L/s/person - - -
22 VAV box with RH 0.00 L/s/person - - -
23 VAV box with RH 0.00 L/s/person - - -
24 VAV box with RH 0.00 L/s/person - - -
25 VAV box with RH 0.00 L/s/person - - -
119 of 331

Hourly Analysis Program v4.60 Page 3 of 5


AHU-05 Input Data
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:19PM

Fan Design Supply


Zone Terminal Type Min. Airflow Fan Performance Efficiency Temperature
26 VAV box with RH 0.00 L/s/person - - -

Reheat Coil Source Hot Water


Reheat Coil Schedule JFMAMJJASOND

Zone Heating Units:


Zone All
Zone Heating Unit Type None

Zone Unit Heat Source Hot Water


Zone Heating Unit Schedule JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature 12.8 °C
Supply Fan Airflow 4760.2 L/s
Ventilation Airflow 1225.0 L/s

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.0 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) -
1 312.6 - 0.6 -
2 245.6 - 1.0 -
3 226.9 - 2.6 -
4 189.4 - 0.7 -
5 166.2 - 1.9 -
6 132.4 - 0.6 -
7 206.1 - 0.8 -
8 208.0 - 0.8 -
9 203.0 - 0.8 -
10 38.3 - 0.2 -
11 203.5 - 0.7 -
12 135.0 - 0.4 -
13 61.9 - 0.7 -
14 194.8 - 0.9 -
15 145.7 - 0.7 -
16 189.2 - 0.4 -
17 172.3 - 0.4 -
18 158.0 - 0.4 -
19 138.4 - 1.5 -
20 199.3 - 0.0 -
21 152.6 - 0.2 -
22 242.0 - 0.5 -
23 166.3 - 0.3 -
24 258.0 - 0.5 -
25 244.9 - 0.5
120 of 331

Hourly Analysis Program v4.60 Page 4 of 5


AHU-05 Input Data
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:19PM

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) -
26 298.6 - 0.6

5. Equipment Data
No Equipment Data required for this system.

121 of 331

Hourly Analysis Program v4.60 Page 5 of 5


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

5-F-068 ULTRA SOUND

1. General Details:
Floor Area 10.8 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 60.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 2140.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 11.9 15 0 0

3.1. Construction Types for Exposure NE


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

122 of 331

Hourly Analysis Program v4.60 Page 1 of 28


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

5-F-069 OB/GY CLINIC

1. General Details:
Floor Area 13.6 m²
Avg. Ceiling Height 2.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 80.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1180.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 19.3 26 0 0

3.1. Construction Types for Exposure NE


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

123 of 331

Hourly Analysis Program v4.60 Page 2 of 28


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

5-F-072 CLEAN UTILITY

1. General Details:
Floor Area 6.6 m²
Avg. Ceiling Height 2.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 530.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

124 of 331

Hourly Analysis Program v4.60 Page 3 of 28


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

5-F-076 OB/GY CLINIC

1. General Details:
Floor Area 15.7 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 55.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1180.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 17.4 7 0 0

3.1. Construction Types for Exposure NE


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 15.7 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

125 of 331

Hourly Analysis Program v4.60 Page 4 of 28


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

5-F-077 CORRIDOR

1. General Details:
Floor Area 56.3 m²
Avg. Ceiling Height 3.3 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 105.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 40.0 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

126 of 331

Hourly Analysis Program v4.60 Page 5 of 28


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

5-F-078 PROCEDURE TRT

1. General Details:
Floor Area 11.6 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 35.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 90.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 11.6 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

127 of 331

Hourly Analysis Program v4.60 Page 6 of 28


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

5-F-082 IMMUNIZATION

1. General Details:
Floor Area 9.1 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 45.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 765.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 10.5 8 0 0

3.1. Construction Types for Exposure NE


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 9.1 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

128 of 331

Hourly Analysis Program v4.60 Page 7 of 28


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

5-F-083 PEDIATRIC CLc

1. General Details:
Floor Area 14.2 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 60.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1180.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 15.8 13 0 0

3.1. Construction Types for Exposure NE


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 14.2 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

129 of 331

Hourly Analysis Program v4.60 Page 8 of 28


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

5-F-086 PEDIATRIC CLINIC

1. General Details:
Floor Area 15.0 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 65.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1180.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 16.6 13 0 0

3.1. Construction Types for Exposure NE


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 15.0 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

130 of 331

Hourly Analysis Program v4.60 Page 9 of 28


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

5-F-087 FAMILY MEDICINE

1. General Details:
Floor Area 15.2 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 65.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1180.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 16.8 13 0 0

3.1. Construction Types for Exposure NE


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

131 of 331

Hourly Analysis Program v4.60 Page 10 of 28


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

5-F-088 VITAL SIGN

1. General Details:
Floor Area 7.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 180.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

132 of 331

Hourly Analysis Program v4.60 Page 11 of 28


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

5-F-091 FAMILY MEDICINE

1. General Details:
Floor Area 14.6 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 60.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1180.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 11.7 9 0 0

3.1. Construction Types for Exposure NE


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 10.3 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C

133 of 331

Hourly Analysis Program v4.60 Page 12 of 28


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

5-F-095 STRESS ECG ROOM

1. General Details:
Floor Area 9.4 m²
Avg. Ceiling Height 2.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 40.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1180.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

134 of 331

Hourly Analysis Program v4.60 Page 13 of 28


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

5-F-096 CORRIDOR

1. General Details:
Floor Area 19.9 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 30.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

135 of 331

Hourly Analysis Program v4.60 Page 14 of 28


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

5-F-097 INTERNAL MEDIC.

1. General Details:
Floor Area 13.2 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 75.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1180.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 10.5 8 0 0
N 8.5 7 0 0

3.1. Construction Types for Exposure NE


Wall Type EXTERIOR WALL
1st Window Type W

3.2. Construction Types for Exposure N


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

136 of 331

Hourly Analysis Program v4.60 Page 15 of 28


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

5-F-098 ECG

1. General Details:
Floor Area 13.6 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 60.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 825.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 12.7 10 0 0

3.1. Construction Types for Exposure N


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

137 of 331

Hourly Analysis Program v4.60 Page 16 of 28


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

5-F-099 CARDIOLOGY CLNC.

1. General Details:
Floor Area 16.8 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 30.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1180.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 15.8 12 0 0

3.1. Construction Types for Exposure N


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

138 of 331

Hourly Analysis Program v4.60 Page 17 of 28


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

5-F-104 ENT CLINIC

1. General Details:
Floor Area 17.9 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 30.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 795.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 17.2 13 0 0

3.1. Construction Types for Exposure N


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 6.3 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C

139 of 331

Hourly Analysis Program v4.60 Page 18 of 28


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

5-F-105 ENT CLINIC

1. General Details:
Floor Area 17.1 m²
Avg. Ceiling Height 2.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 30.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 795.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 16.8 13 0 0

3.1. Construction Types for Exposure N


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

140 of 331

Hourly Analysis Program v4.60 Page 19 of 28


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

5-F-106 CORRIDOR

1. General Details:
Floor Area 41.9 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 65.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

141 of 331

Hourly Analysis Program v4.60 Page 20 of 28


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

5-F-107 DENTAL SERIALIZ.

1. General Details:
Floor Area 6.9 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1765.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

142 of 331

Hourly Analysis Program v4.60 Page 21 of 28


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

5-F-108 DENTAL CLINIC

1. General Details:
Floor Area 15.4 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 20.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 855.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 3.4 0 0 0

3.1. Construction Types for Exposure S


Wall Type EXTERIOR WALL

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 13.2 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C

143 of 331

Hourly Analysis Program v4.60 Page 22 of 28


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

5-F-109 DENTAL CLINIC

1. General Details:
Floor Area 13.8 m²
Avg. Ceiling Height 2.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 35.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 855.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 15.8 19 0 0

3.1. Construction Types for Exposure S


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 7.8 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C

144 of 331

Hourly Analysis Program v4.60 Page 23 of 28


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

5-F-110 CLEAN UTILITY

1. General Details:
Floor Area 3.0 m²
Avg. Ceiling Height 2.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 5.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 530.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

145 of 331

Hourly Analysis Program v4.60 Page 24 of 28


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

5-F-112 ENT CLINIC

1. General Details:
Floor Area 17.8 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 25.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 795.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 16.8 13 0 0

3.1. Construction Types for Exposure N


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 3.5 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C

146 of 331

Hourly Analysis Program v4.60 Page 25 of 28


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

5-F-113 FLEXIBLE CLINIC

1. General Details:
Floor Area 15.0 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 40.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1180.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 14.0 18 0 0
N 14.4 0 0 0

3.1. Construction Types for Exposure W


Wall Type EXTERIOR WALL
1st Window Type W

3.2. Construction Types for Exposure N


Wall Type EXTERIOR WALL

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 6.4 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C

147 of 331

Hourly Analysis Program v4.60 Page 26 of 28


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

5-F-115 FLEXIBLE CLINIC

1. General Details:
Floor Area 13.0 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 40.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1180.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 15.0 20 0 0

3.1. Construction Types for Exposure W


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

148 of 331

Hourly Analysis Program v4.60 Page 27 of 28


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:26PM

5-F-116 DENTAL CLINIC

1. General Details:
Floor Area 18.0 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 45.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1295.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 19.7 26 0 0
S 14.4 0 0 0

3.1. Construction Types for Exposure W


Wall Type EXTERIOR WALL
1st Window Type W

3.2. Construction Types for Exposure S


Wall Type EXTERIOR WALL

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

149 of 331

Hourly Analysis Program v4.60 Page 28 of 28


Air System Sizing Summary for AHU-06
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:12PM

Air System Information


Air System Name AHU-06 Number of zones 18
Equipment Class CW AHU Floor Area 567.5 m²
Air System Type VAV Location Jeddah, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Central Cooling Coil Sizing Data


Total coil load 102.6 kW Load occurs at Aug 1600
Sensible coil load 88.8 kW OA DB / WB 40.7 / 23.4 °C
Coil L/s at Aug 1600 4052 L/s Entering DB / WB 31.0 / 19.4 °C
Max block L/s at Oct 1600 4674 L/s Leaving DB / WB 12.8 / 11.7 °C
Sum of peak zone L/s 4797 L/s Coil ADP 10.8 °C
Sensible heat ratio 0.865 Bypass Factor 0.100
m²/kW 5.5 Resulting RH 46 %
W/m² 180.8 Design supply temp. 12.8 °C
Water flow @ 6.0 °K rise 4.09 L/s Zone T-stat Check 18 of 18 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s at Oct 1600 4674 L/s Fan motor BHP 11.33 BHP
Standard L/s 4663 L/s Fan motor kW 8.99 kW
Actual max L/(s-m²) 8.24 L/(s-m²) Fan static 1250 Pa

Return Fan Sizing Data


Actual max L/s at Oct 1600 4674 L/s Fan motor BHP 5.44 BHP
Standard L/s 4663 L/s Fan motor kW 4.31 kW
Actual max L/(s-m²) 8.24 L/(s-m²) Fan static 600 Pa

Outdoor Ventilation Air Data


Design airflow L/s 1281 L/s L/s/person 14.89 L/s/person
L/(s-m²) 2.26 L/(s-m²)

150 of 331

Hourly Analysis Program v4.60 Page 1 of 4


Zone Sizing Summary for AHU-06
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:12PM

Air System Information


Air System Name AHU-06 Number of zones 18
Equipment Class CW AHU Floor Area 567.5 m²
Air System Type VAV Location Jeddah, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (kW) (L/s) (L/s) Load (kW) (m²) L/(s-m²)
Zone 1 1.3 107 105 Sep 1600 0.1 11.2 9.61
Zone 2 9.3 759 210 Sep 1600 0.4 62.7 12.10
Zone 3 18.6 1508 438 Jul 1800 0.5 277.2 5.44
Zone 4 1.4 111 40 Jan 2300 0.0 23.7 4.67
Zone 5 0.4 93 93 Jan 2300 0.0 9.6 9.67
Zone 6 0.5 95 95 Jul 1900 0.0 10.0 9.52
Zone 7 0.5 42 25 Jul 1900 0.0 8.0 5.26
Zone 8 1.3 109 13 Jan 2300 0.0 10.0 10.92
Zone 9 2.1 168 45 Jul 1900 0.0 14.6 11.47
Zone 10 9.7 788 180 Nov 1500 0.5 57.5 13.70
Zone 11 1.2 96 15 Jul 0900 0.1 9.4 10.24
Zone 12 0.5 83 83 Jul 1900 0.0 9.6 8.74
Zone 13 1.2 98 15 Jun 1000 0.1 8.0 12.24
Zone 14 1.6 133 30 Jul 1900 0.0 11.9 11.19
Zone 15 2.2 162 70 Dec 1500 0.1 12.2 13.25
Zone 16 2.3 185 45 Jul 1700 0.2 12.5 14.80
Zone 17 1.4 211 211 Jan 2300 0.0 14.8 14.23
Zone 18 0.2 50 50 Jul 1900 0.0 4.7 10.67

Zone Terminal Sizing Data

Reheat Zone Zone


Reheat Coil Htg Htg Mixing
Coil Water Coil Water Box Fan
Load L/s Load L/s Airflow
Zone Name (kW) @ 11.0 °K (kW) @ 11.0 °K (L/s)
Zone 1 1.2 0.03 0.0 0.00 0
Zone 2 2.7 0.06 0.0 0.00 0
Zone 3 5.3 0.12 0.0 0.00 0
Zone 4 0.4 0.01 0.0 0.00 0
Zone 5 1.0 0.02 0.0 0.00 0
Zone 6 1.1 0.02 0.0 0.00 0
Zone 7 0.3 0.01 0.0 0.00 0
Zone 8 0.1 0.00 0.0 0.00 0
Zone 9 0.5 0.01 0.0 0.00 0
Zone 10 2.5 0.05 0.0 0.00 0
Zone 11 0.2 0.01 0.0 0.00 0
Zone 12 0.9 0.02 0.0 0.00 0
Zone 13 0.3 0.01 0.0 0.00 0
Zone 14 0.4 0.01 0.0 0.00 0
Zone 15 0.9 0.02 0.0 0.00 0
Zone 16 0.7 0.02 0.0 0.00 0
Zone 17 2.1 0.05 0.0 0.00 0
Zone 18 0.6 0.01 0.0 0.00 0
151 of 331

Hourly Analysis Program v4.60 Page 2 of 4


Zone Sizing Summary for AHU-06
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:12PM

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
6-F-011 ISOLATION ROOM 1 1.3 Sep 1600 107 0.1 11.2 9.61
Zone 2
6-F-018&033 CUBIC. (1-8) 1 9.3 Sep 1600 759 0.4 62.7 12.10
Zone 3
6-F-024 CORRIDOR&NURSE 1 10.5 Jul 1900 854 0.3 227.0 3.76
6-F-025 CLEAN LINEN 1 0.2 Jan 2300 13 0.0 4.6 2.75
6-F-026 PANTRY 1 2.5 Jan 2300 207 0.0 4.7 44.23
6-F-021 CLEAN UTILITY 1 0.7 Jan 2300 61 0.0 5.3 11.55
6-F-037 STORE 1 0.1 Jan 2300 9 0.0 7.0 1.34
6-F-042 DIALYZER STORE 1 1.1 Jul 1700 88 0.2 9.5 9.24
6-F-044 PANTRY 1 2.5 Jan 2300 207 0.0 4.4 46.96
6-F-045CLEAN LINEN 1 0.1 Jan 2300 15 0.0 4.3 3.49
*6-F-047 DIRTY UTILITY 1 0.0 Jan 0000 0 0.0 5.2 0.00
6-F-048 CLEAN UTILITY 1 0.7 Jan 2300 61 0.0 5.3 11.49
Zone 4
6-F-020 CUBICLES (17-19) 1 1.4 Jan 2300 111 0.0 23.7 4.67
Zone 5
6-F-027 ISOLATION ROOM 1 0.4 Jan 2300 93 0.0 9.6 9.67
Zone 6
6-F-039 ISOLATION ROOM 1 0.5 Jul 1900 95 0.0 10.0 9.52
Zone 7
6-F-040 CUBICLE 1 0.5 Jul 1900 42 0.0 8.0 5.26
Zone 8
6-F-017 OFFICE 1 1.3 Jan 2300 109 0.0 10.0 10.92
Zone 9
6-F-046 NEPHROLOGY CLNC. 1 2.1 Jul 1900 168 0.0 14.6 11.47
Zone 10
6-F-043 CUBICLE(9-15) 1 9.7 Nov 1500 788 0.5 57.5 13.70
Zone 11
6-F-053 ISOLATION ROOM 1 1.2 Jul 0900 96 0.1 9.4 10.24
Zone 12
6-F-052 ISOLATION ROOM 1 0.5 Jul 1900 83 0.0 9.6 8.74
Zone 13
6-F-058 ISOLATION ROOM 1 1.2 Jun 1000 98 0.1 8.0 12.24
Zone 14
6-F-032 DIALYSIS WORK SH 1 1.6 Jul 1900 133 0.0 11.9 11.19
Zone 15
6-F-034 STAFF LOUNGE 1 2.2 Dec 1500 162 0.1 12.2 13.25
Zone 16
6-F-041 DIALYSIS TRAIN. 1 2.3 Jul 1700 185 0.2 12.5 14.80
Zone 17
6-F-014 PROCEDURE ROOM 1 1.4 Jan 2300 211 0.0 14.8 14.23
Zone 18
6-F-013 AIRLOCK 1 0.2 Jul 1900 50 0.0 4.7 10.67

152 of 331

Hourly Analysis Program v4.60 Page 3 of 4


Air System Design Load Summary for AHU-06
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:12PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 40.7 °C / 23.4 °C HEATING OA DB / WB 16.8 °C / 9.7 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 95 m² 5897 - 95 m² - -
Wall Transmission 136 m² 657 - 136 m² 212 -
Roof Transmission 428 m² 4440 - 428 m² 986 -
Window Transmission 95 m² 2113 - 95 m² 688 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 23 m² 535 - 23 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 9767 W 9766 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 19205 W 19204 - 0 0 -
People 86 6008 4222 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 4862 422 10% 189 0
>> Total Zone Loads - 53482 4645 - 2075 0
Zone Conditioning - 52338 4645 - 1704 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 4052 L/s 3037 - 1763 L/s -627 -
Ventilation Load 1281 L/s 24859 9204 1281 L/s 7293 0
Supply Fan Load 4052 L/s 6327 - 1763 L/s -1307 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 86561 13849 - 7061 0
Central Cooling Coil - 88763 13848 - 0 0
Terminal Reheat Coils - -2202 - - 7056 -
>> Total Conditioning - 86561 13848 - 7056 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

153 of 331

Hourly Analysis Program v4.60 Page 4 of 4


AHU-06 Input Data
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:20PM

1. General Details:
Air System Name AHU-06
Equipment Type Chilled Water AHU
Air System Type VAV
Number of zones 18

2. System Components:
Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Central Cooling Data:


Supply Air Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule * * MAMJJASON*
Capacity Control Constant Temperature - Fan On

Supply Fan Data:


Fan Type BI/AF with Variable Frequency Drive
Configuration Blow-thru
Fan Performance 1250 Pa
Overall Efficiency 65 %

% Airflow 100 90 80 70 60 50
% kW 100 77 57 42 30 21

% Airflow 40 30 20 10 0
% kW 15 13 10 7 5

Duct System Data:


Supply Duct Data:
Duct Heat Gain 0 %
Duct Leakage 0 %

Return Duct or Plenum Data:


Return Air Via Ducted Return

Return Fan Data:


Fan Type BI/AF with Variable Speed Drive
Fan Performance 600 Pa
Overall Efficiency 65 %

% Airflow 100 90 80 70 60 50
% kW 100 77 57 42 30 21

% Airflow 40 30 20 10 0
% kW 15 13 10 7 5

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
6-F-011 ISOLATION ROOM x1
Zone 2: Zone 2
6-F-018&033 CUBIC. (1-8) x1
Zone 3: Zone 3
6-F-024 CORRIDOR&NURSE x1
6-F-025 CLEAN LINEN x1
6-F-026 PANTRY x1
6-F-021 CLEAN UTILITY x1
6-F-037 STORE x1
6-F-042 DIALYZER STORE x1
154 of 331

Hourly Analysis Program v4.60 Page 1 of 4


AHU-06 Input Data
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:20PM

6-F-044 PANTRY x1
6-F-045CLEAN LINEN x1
*6-F-047 DIRTY UTILITY x1
6-F-048 CLEAN UTILITY x1
Zone 4: Zone 4
6-F-020 CUBICLES (17-19) x1
Zone 5: Zone 5
6-F-027 ISOLATION ROOM x1
Zone 6: Zone 6
6-F-039 ISOLATION ROOM x1
Zone 7: Zone 7
6-F-040 CUBICLE x1
Zone 8: Zone 8
6-F-017 OFFICE x1
Zone 9: Zone 9
6-F-046 NEPHROLOGY CLNC. x1
Zone 10: Zone 10
6-F-043 CUBICLE(9-15) x1
Zone 11: Zone 11
6-F-053 ISOLATION ROOM x1
Zone 12: Zone 12
6-F-052 ISOLATION ROOM x1
Zone 13: Zone 13
6-F-058 ISOLATION ROOM x1
Zone 14: Zone 14
6-F-032 DIALYSIS WORK SH x1
Zone 15: Zone 15
6-F-034 STAFF LOUNGE x1
Zone 16: Zone 16
6-F-041 DIALYSIS TRAIN. x1
Zone 17: Zone 17
6-F-014 PROCEDURE ROOM x1
Zone 18: Zone 18
6-F-013 AIRLOCK x1

Thermostats and Zone Data:

T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)
1 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
2 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
3 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
4 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
5 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
6 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
7 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
8 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
9 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
10 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
11 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
12 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
13 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
14 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
15 24.0 26.0 22.0 18.0 2.00 100 0.0 0.0
16 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
17 22.0 26.0 21.0 18.0 2.00 100 0.0 0.0
155 of 331

Hourly Analysis Program v4.60 Page 2 of 4


AHU-06 Input Data
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:20PM

T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)
18 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0

Thermostat Schedule FAN THERMOSTAT 24/7


Unoccupied Cooling is Available

Supply Terminals Data:

Fan Design Supply


Zone Terminal Type Min. Airflow Fan Performance Efficiency Temperature
1 VAV box with RH 12.00 ACH - - -
2 VAV box with RH 0.00 ACH - - -
3 VAV box with RH 0.00 ACH - - -
4 VAV box with RH 0.00 ACH - - -
5 VAV box with RH 12.00 ACH - - -
6 VAV box with RH 12.00 ACH - - -
7 VAV box with RH 0.00 ACH - - -
8 VAV box with RH 0.00 ACH - - -
9 VAV box with RH 0.00 ACH - - -
10 VAV box with RH 0.00 ACH - - -
11 VAV box with RH 0.00 ACH - - -
12 VAV box with RH 12.00 ACH - - -
13 VAV box with RH 0.00 ACH - - -
14 VAV box with RH 0.00 ACH - - -
15 VAV box with RH 0.00 ACH - - -
16 VAV box with RH 0.00 ACH - - -
17 VAV box with RH 20.00 ACH - - -
18 VAV box with RH 50.0 L/s - - -

Reheat Coil Source Hot Water


Reheat Coil Schedule JFMAMJJASOND

Zone Heating Units:


Zone All
Zone Heating Unit Type None

Zone Unit Heat Source Hot Water


Zone Heating Unit Schedule JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature 12.8 °C
Supply Fan Airflow 4674.3 L/s
Ventilation Airflow 1280.7 L/s

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.0 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) -
156 of 331

Hourly Analysis Program v4.60 Page 3 of 4


AHU-06 Input Data
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:20PM

1 107.3 - 1.2 -
2 758.8 - 2.7 -
3 1507.9 - 5.3 -
4 110.6 - 0.4 -
5 92.8 - 1.0 -
6 95.2 - 1.1 -
7 42.1 - 0.3 -
8 108.7 - 0.1 -
9 167.5 - 0.5 -
10 787.6 - 2.5 -
11 96.2 - 0.2 -
12 83.5 - 0.9 -
13 97.8 - 0.3 -
14 133.2 - 0.4 -
15 162.2 - 0.9 -
16 185.0 - 0.7 -
17 210.9 - 2.1
18 50.0 - 0.6

5. Equipment Data
No Equipment Data required for this system.

157 of 331

Hourly Analysis Program v4.60 Page 4 of 4


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:27PM

6-F-011 ISOLATION ROOM

1. General Details:
Floor Area 11.2 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 35.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 410.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 13.8 7 0 0

3.1. Construction Types for Exposure WSW


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 11.2 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

158 of 331

Hourly Analysis Program v4.60 Page 1 of 26


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:27PM

6-F-013 AIRLOCK

1. General Details:
Floor Area 4.7 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10.0 L/s/person
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule LIGHTING 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 4.7 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

159 of 331

Hourly Analysis Program v4.60 Page 2 of 26


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:27PM

6-F-014 PROCEDURE ROOM

1. General Details:
Floor Area 14.8 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 65.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 25.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 650.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

160 of 331

Hourly Analysis Program v4.60 Page 3 of 26


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:27PM

6-F-017 OFFICE

1. General Details:
Floor Area 10.0 m²
Avg. Ceiling Height 2.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 780.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

161 of 331

Hourly Analysis Program v4.60 Page 4 of 26


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:27PM

6-F-018&033 CUBIC. (1-8)

1. General Details:
Floor Area 62.7 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 210.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 16.0 People
Wattage 20.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING 24/7 Latent 35.2 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 3295.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 87.0 40 0 0

3.1. Construction Types for Exposure WSW


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 62.7 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

162 of 331

Hourly Analysis Program v4.60 Page 5 of 26


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:27PM

6-F-020 CUBICLES (17-19)

1. General Details:
Floor Area 23.7 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 40.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6.0 People
Wattage 20.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING 24/7 Latent 35.2 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 360.0 Watts
Schedule PEOPLE 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

163 of 331

Hourly Analysis Program v4.60 Page 6 of 26


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:27PM

6-F-021 CLEAN UTILITY

1. General Details:
Floor Area 5.3 m²
Avg. Ceiling Height 2.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 530.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

164 of 331

Hourly Analysis Program v4.60 Page 7 of 26


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:27PM

6-F-024 CORRIDOR&NURSE

1. General Details:
Floor Area 227.0 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 350.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 15.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 3770.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 186.0 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

165 of 331

Hourly Analysis Program v4.60 Page 8 of 26


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:27PM

6-F-025 CLEAN LINEN

1. General Details:
Floor Area 4.6 m²
Avg. Ceiling Height 2.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 5.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

166 of 331

Hourly Analysis Program v4.60 Page 9 of 26


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:27PM

6-F-026 PANTRY

1. General Details:
Floor Area 4.7 m²
Avg. Ceiling Height 2.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 3.80 L/(s-m²)
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 2175.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

167 of 331

Hourly Analysis Program v4.60 Page 10 of 26


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:27PM

6-F-027 ISOLATION ROOM

1. General Details:
Floor Area 9.6 m²
Avg. Ceiling Height 2.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 120.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

168 of 331

Hourly Analysis Program v4.60 Page 11 of 26


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:27PM

6-F-032 DIALYSIS WORK SH

1. General Details:
Floor Area 11.9 m²
Avg. Ceiling Height 2.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 30.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1085.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 11.9 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

169 of 331

Hourly Analysis Program v4.60 Page 12 of 26


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:27PM

6-F-034 STAFF LOUNGE

1. General Details:
Floor Area 12.2 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 70.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 5.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 120.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 7.2 9 0 0
S 16.2 13 0 0

3.1. Construction Types for Exposure WSW


Wall Type EXTERIOR WALL
1st Window Type W

3.2. Construction Types for Exposure S


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 12.2 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

170 of 331

Hourly Analysis Program v4.60 Page 13 of 26


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:27PM

6-F-037 STORE

1. General Details:
Floor Area 7.0 m²
Avg. Ceiling Height 3.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Storage room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

171 of 331

Hourly Analysis Program v4.60 Page 14 of 26


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:27PM

6-F-039 ISOLATION ROOM

1. General Details:
Floor Area 10.0 m²
Avg. Ceiling Height 2.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 120.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 10.0 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

172 of 331

Hourly Analysis Program v4.60 Page 15 of 26


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:27PM

6-F-040 CUBICLE

1. General Details:
Floor Area 8.0 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 25.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING 24/7 Latent 35.2 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 120.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 8.0 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

173 of 331

Hourly Analysis Program v4.60 Page 16 of 26


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:27PM

6-F-041 DIALYSIS TRAIN.

1. General Details:
Floor Area 12.5 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 45.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 500.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 12.5 0 0

4.1. Construction Types for Exposure H


Roof Type Floor

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

174 of 331

Hourly Analysis Program v4.60 Page 17 of 26


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:27PM

6-F-042 DIALYZER STORE

1. General Details:
Floor Area 9.5 m²
Avg. Ceiling Height 3.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Storage room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 9.5 0 0

4.1. Construction Types for Exposure H


Roof Type Floor

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

175 of 331

Hourly Analysis Program v4.60 Page 18 of 26


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:27PM

6-F-043 CUBICLE(9-15)

1. General Details:
Floor Area 57.5 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 180.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 14.0 People
Wattage 20.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING 24/7 Latent 35.2 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 840.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 77.5 87 0 0

3.1. Construction Types for Exposure SW


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 57.5 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 22.5 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C

176 of 331

Hourly Analysis Program v4.60 Page 19 of 26


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:27PM

6-F-044 PANTRY

1. General Details:
Floor Area 4.4 m²
Avg. Ceiling Height 2.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15.0 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 2175.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

177 of 331

Hourly Analysis Program v4.60 Page 20 of 26


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:27PM

6-F-045CLEAN LINEN

1. General Details:
Floor Area 4.3 m²
Avg. Ceiling Height 2.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

178 of 331

Hourly Analysis Program v4.60 Page 21 of 26


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:27PM

6-F-046 NEPHROLOGY CLNC.

1. General Details:
Floor Area 14.6 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 45.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1265.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 14.6 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

179 of 331

Hourly Analysis Program v4.60 Page 22 of 26


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:27PM

6-F-048 CLEAN UTILITY

1. General Details:
Floor Area 5.3 m²
Avg. Ceiling Height 2.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 530.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

180 of 331

Hourly Analysis Program v4.60 Page 23 of 26


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:27PM

6-F-052 ISOLATION ROOM

1. General Details:
Floor Area 9.6 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 120.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 9.6 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

181 of 331

Hourly Analysis Program v4.60 Page 24 of 26


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:27PM

6-F-053 ISOLATION ROOM

1. General Details:
Floor Area 9.4 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 120.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 12.7 14 0 0

3.1. Construction Types for Exposure E


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 9.4 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

182 of 331

Hourly Analysis Program v4.60 Page 25 of 26


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:27PM

6-F-058 ISOLATION ROOM

1. General Details:
Floor Area 8.0 m²
Avg. Ceiling Height 3.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 120.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 10.6 12 0 0
N 5.6 7 0 0

3.1. Construction Types for Exposure E


Wall Type EXTERIOR WALL
1st Window Type W

3.2. Construction Types for Exposure N


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 8.0 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

183 of 331

Hourly Analysis Program v4.60 Page 26 of 26


Air System Sizing Summary for AHU-07
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:12PM

Air System Information


Air System Name AHU-07 Number of zones 13
Equipment Class CW AHU Floor Area 305.6 m²
Air System Type VAV Location Jeddah, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Central Cooling Coil Sizing Data


Total coil load 69.3 kW Load occurs at Jun 1600
Sensible coil load 58.0 kW OA DB / WB 40.1 / 23.4 °C
Coil L/s at Jun 1600 3004 L/s Entering DB / WB 28.8 / 18.9 °C
Max block L/s at Jun 1700 3538 L/s Leaving DB / WB 12.8 / 11.9 °C
Sum of peak zone L/s 3624 L/s Coil ADP 11.0 °C
Sensible heat ratio 0.837 Bypass Factor 0.100
m²/kW 4.4 Resulting RH 47 %
W/m² 226.7 Design supply temp. 12.8 °C
Water flow @ 6.0 °K rise 2.76 L/s Zone T-stat Check 13 of 13 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s at Jun 1700 3538 L/s Fan motor BHP 5.15 BHP
Standard L/s 3530 L/s Fan motor kW 4.08 kW
Actual max L/(s-m²) 11.58 L/(s-m²) Fan static 750 Pa

Return Fan Sizing Data


Actual max L/s at Jun 1700 3538 L/s Fan motor BHP 2.74 BHP
Standard L/s 3530 L/s Fan motor kW 2.18 kW
Actual max L/(s-m²) 11.58 L/(s-m²) Fan static 400 Pa

Outdoor Ventilation Air Data


Design airflow L/s 560 L/s L/s/person 4.63 L/s/person
L/(s-m²) 1.83 L/(s-m²)

184 of 331

Hourly Analysis Program v4.60 Page 1 of 4


Zone Sizing Summary for AHU-07
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:12PM

Air System Information


Air System Name AHU-07 Number of zones 13
Equipment Class CW AHU Floor Area 305.6 m²
Air System Type VAV Location Jeddah, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (kW) (L/s) (L/s) Load (kW) (m²) L/(s-m²)
Zone 1 2.7 218 5 Jul 1700 0.0 17.8 12.22
Zone 2 4.5 336 48 Jul 1700 0.2 84.5 3.98
Zone 3 11.4 842 50 Jul 1600 0.3 48.0 17.55
Zone 4 1.9 158 25 Jun 1700 0.1 18.3 8.62
Zone 5 3.0 247 14 Jun 1700 0.1 14.4 17.13
Zone 6 3.0 245 11 Jun 1700 0.2 10.6 23.03
Zone 7 2.1 171 7 Jul 1700 0.1 8.0 21.29
Zone 8 1.6 132 5 Jul 1700 0.1 8.0 16.55
Zone 9 3.5 281 11 Dec 1500 0.2 11.2 25.12
Zone 10 2.9 237 16 Nov 1500 0.0 10.5 22.58
Zone 11 3.9 285 33 Jun 1700 0.2 25.0 11.41
Zone 12 0.7 54 10 Jul 1900 0.0 3.0 18.09
Zone 13 5.1 417 106 Jun 0900 0.3 46.2 9.03

Zone Terminal Sizing Data

Reheat Zone Zone


Reheat Coil Htg Htg Mixing
Coil Water Coil Water Box Fan
Load L/s Load L/s Airflow
Zone Name (kW) @ 11.0 °K (kW) @ 11.0 °K (L/s)
Zone 1 0.1 0.00 0.0 0.00 0
Zone 2 0.7 0.02 0.0 0.00 0
Zone 3 0.8 0.02 0.0 0.00 0
Zone 4 0.4 0.01 0.0 0.00 0
Zone 5 0.3 0.01 0.0 0.00 0
Zone 6 0.3 0.01 0.0 0.00 0
Zone 7 0.2 0.00 0.0 0.00 0
Zone 8 0.1 0.00 0.0 0.00 0
Zone 9 0.3 0.01 0.0 0.00 0
Zone 10 0.2 0.00 0.0 0.00 0
Zone 11 0.5 0.01 0.0 0.00 0
Zone 12 0.1 0.00 0.0 0.00 0
Zone 13 1.4 0.03 0.0 0.00 0

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
7-PH-39 CORRIDOR 1 2.7 Jul 1700 218 0.0 17.8 12.22
Zone 2
7-PH-40&41 DOCTORS LOUNG 1 4.5 Jul 1700 336 0.2 84.5 3.98
Zone 3
185 of 331

Hourly Analysis Program v4.60 Page 2 of 4


Zone Sizing Summary for AHU-07
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:12PM

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
7-PH-35 STAFF REST ROOM 1 11.4 Jul 1600 842 0.3 48.0 17.55
Zone 4
7-PH-48 MEETING ROOM 1 1.9 Jun 1700 158 0.1 18.3 8.62
Zone 5
7-PH-49 INSURANCE COMP 1 3.0 Jun 1700 247 0.1 14.4 17.13
Zone 6
7-PH-47 DIABET. DIR. OFF 1 3.0 Jun 1700 245 0.2 10.6 23.03
Zone 7
7-PH-46 DIALYSIS DIRECT. 1 2.1 Jul 1700 171 0.1 8.0 21.29
Zone 8
7-PH-45 URGENT CARE DIR. 1 1.6 Jul 1700 132 0.1 8.0 16.55
Zone 9
7-PH-44 NURSE DIR. OFF. 1 3.5 Dec 1500 281 0.2 11.2 25.12
Zone 10
7-PH-43 FINANCE - ADMINI 1 2.9 Nov 1500 237 0.0 10.5 22.58
Zone 11
7-PH-50 STAFF REST RM 1 3.9 Jun 1700 285 0.2 25.0 11.41
Zone 12
7-PH-36 CLEAN UTILITY 1 0.7 Jul 1900 54 0.0 3.0 18.09
Zone 13
7-PH-29 PRAYER HALL (M) 1 5.1 Jun 0900 417 0.3 46.2 9.03

186 of 331

Hourly Analysis Program v4.60 Page 3 of 4


Air System Design Load Summary for AHU-07
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:12PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 40.1 °C / 23.4 °C HEATING OA DB / WB 16.8 °C / 9.7 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 117 m² 5640 - 117 m² - -
Wall Transmission 108 m² 485 - 108 m² 168 -
Roof Transmission 306 m² 1860 - 306 m² 476 -
Window Transmission 117 m² 2490 - 117 m² 852 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 107 m² 2292 - 107 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4584 W 4584 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 15150 W 15149 - 0 0 -
People 121 8688 7272 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 4119 727 10% 150 0
>> Total Zone Loads - 45306 7999 - 1646 0
Zone Conditioning - 44204 7999 - 1172 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 2468 L/s 908 - 218 L/s -136 -
Ventilation Load 560 L/s 10129 3313 341 L/s 1882 0
Supply Fan Load 3004 L/s 2726 - 341 L/s -283 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 57968 11313 - 2635 0
Central Cooling Coil - 57968 11317 - 0 0
Terminal Reheat Coils - 0 - - 2635 -
>> Total Conditioning - 57968 11317 - 2635 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

187 of 331

Hourly Analysis Program v4.60 Page 4 of 4


AHU-07 Input Data
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:20PM

1. General Details:
Air System Name AHU-07
Equipment Type Chilled Water AHU
Air System Type VAV
Number of zones 13

2. System Components:
Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Central Cooling Data:


Supply Air Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule * * MAMJJASON*
Capacity Control Constant Temperature - Fan On

Supply Fan Data:


Fan Type BI/AF with Variable Frequency Drive
Configuration Blow-thru
Fan Performance 750 Pa
Overall Efficiency 65 %

% Airflow 100 90 80 70 60 50
% kW 100 77 57 42 30 21

% Airflow 40 30 20 10 0
% kW 15 13 10 7 5

Duct System Data:


Supply Duct Data:
Duct Heat Gain 0 %
Duct Leakage 0 %

Return Duct or Plenum Data:


Return Air Via Ducted Return

Return Fan Data:


Fan Type BI/AF with Variable Speed Drive
Fan Performance 400 Pa
Overall Efficiency 65 %

% Airflow 100 90 80 70 60 50
% kW 100 77 57 42 30 21

% Airflow 40 30 20 10 0
% kW 15 13 10 7 5

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
7-PH-39 CORRIDOR x1
Zone 2: Zone 2
7-PH-40&41 DOCTORS LOUNG x1
Zone 3: Zone 3
7-PH-35 STAFF REST ROOM x1
Zone 4: Zone 4
7-PH-48 MEETING ROOM x1
Zone 5: Zone 5
7-PH-49 INSURANCE COMP x1
Zone 6: Zone 6
188 of 331

Hourly Analysis Program v4.60 Page 1 of 3


AHU-07 Input Data
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:20PM

7-PH-47 DIABET. DIR. OFF x1


Zone 7: Zone 7
7-PH-46 DIALYSIS DIRECT. x1
Zone 8: Zone 8
7-PH-45 URGENT CARE DIR. x1
Zone 9: Zone 9
7-PH-44 NURSE DIR. OFF. x1
Zone 10: Zone 10
7-PH-43 FINANCE - ADMINI x1
Zone 11: Zone 11
7-PH-50 STAFF REST RM x1
Zone 12: Zone 12
7-PH-36 CLEAN UTILITY x1
Zone 13: Zone 13
7-PH-29 PRAYER HALL (M) x1

Thermostats and Zone Data:

T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)
1 23.0 26.0 22.0 18.0 2.00 100 185.0 0.0
2 24.0 26.0 22.0 18.0 2.00 100 305.0 0.0
3 24.0 26.0 22.0 18.0 2.00 100 0.0 0.0
4 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
5 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
6 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
7 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
8 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
9 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
10 23.0 26.0 22.0 18.0 2.00 100 0.0 0.0
11 24.0 26.0 22.0 18.0 2.00 100 0.0 0.0
12 24.0 26.0 22.0 18.0 2.00 100 0.0 0.0
13 23.0 26.0 22.0 18.0 2.00 100 70.0 0.0

Thermostat Schedule FAN THERMOSTAT 24/7


Unoccupied Cooling is Available

Supply Terminals Data:


Zone All
Terminal Type VAV box with RH
Minimum Airflow 0.00 L/s/person

Reheat Coil Source Hot Water


Reheat Coil Schedule JFMAMJJASOND

Zone Heating Units:


Zone All
Zone Heating Unit Type None

Zone Unit Heat Source Hot Water


Zone Heating Unit Schedule JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature 12.8 °C
Supply Fan Airflow 3538.2 L/s
Ventilation Airflow 560.0 L/s

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.0 °K
Hot Water Delta-T 11.0 °K

189 of 331

Hourly Analysis Program v4.60 Page 2 of 3


AHU-07 Input Data
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:20PM

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) -
1 217.6 - 0.1 -
2 336.1 - 0.7 -
3 842.3 - 0.8 -
4 157.8 - 0.4 -
5 246.7 - 0.3 -
6 244.7 - 0.3 -
7 171.3 - 0.2 -
8 132.4 - 0.1 -
9 281.3 - 0.3 -
10 237.5 - 0.2 -
11 285.2 - 0.5 -
12 54.3 - 0.1
13 417.3 - 1.4

5. Equipment Data
No Equipment Data required for this system.

190 of 331

Hourly Analysis Program v4.60 Page 3 of 3


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

7-PH-29 PRAYER HALL (M)

1. General Details:
Floor Area 46.2 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage PUBLIC ASSEMBLY: Religious worship
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 37.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 15.6 23 0 0
SE 43.3 0 0 0

3.1. Construction Types for Exposure NE


Wall Type EXTERIOR WALL
1st Window Type W

3.2. Construction Types for Exposure SE


Wall Type EXTERIOR WALL

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 46.2 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

191 of 331

Hourly Analysis Program v4.60 Page 1 of 14


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

7-PH-35 STAFF REST ROOM

1. General Details:
Floor Area 48.0 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 50.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 12.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 5300.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 15.2 22 0 0
N 15.0 21 0 0

3.1. Construction Types for Exposure NE


Wall Type EXTERIOR WALL
1st Window Type W

3.2. Construction Types for Exposure N


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 48.0 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 87.5 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
192 of 331

Hourly Analysis Program v4.60 Page 2 of 14


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

7-PH-36 CLEAN UTILITY

1. General Details:
Floor Area 3.0 m²
Avg. Ceiling Height 2.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 530.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 3.0 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

193 of 331

Hourly Analysis Program v4.60 Page 3 of 14


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

7-PH-39 CORRIDOR

1. General Details:
Floor Area 17.8 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Corridor
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 26.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 17.8 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 7.8 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C

194 of 331

Hourly Analysis Program v4.60 Page 4 of 14


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

7-PH-40&41 DOCTORS LOUNG

1. General Details:
Floor Area 84.5 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Reception area
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 9.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1140.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 7.8 10 0 0

3.1. Construction Types for Exposure W


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 84.5 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

195 of 331

Hourly Analysis Program v4.60 Page 5 of 14


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

7-PH-43 FINANCE - ADMINI

1. General Details:
Floor Area 10.5 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 5.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1580.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 3.4 5 0 0

3.1. Construction Types for Exposure S


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 10.5 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 11.3 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C

196 of 331

Hourly Analysis Program v4.60 Page 6 of 14


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

7-PH-44 NURSE DIR. OFF.

1. General Details:
Floor Area 11.2 m²
Avg. Ceiling Height 2.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 790.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 10.1 14 0 0
S 15.8 22 0 0

3.1. Construction Types for Exposure W


Wall Type EXTERIOR WALL
1st Window Type W

3.2. Construction Types for Exposure S


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 11.2 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

197 of 331

Hourly Analysis Program v4.60 Page 7 of 14


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

7-PH-45 URGENT CARE DIR.

1. General Details:
Floor Area 8.0 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 790.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 8.5 8 0 0

3.1. Construction Types for Exposure W


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 8.0 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

198 of 331

Hourly Analysis Program v4.60 Page 8 of 14


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

7-PH-46 DIALYSIS DIRECT.

1. General Details:
Floor Area 8.0 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 790.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 10.5 15 0 0

3.1. Construction Types for Exposure W


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 8.0 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

199 of 331

Hourly Analysis Program v4.60 Page 9 of 14


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

7-PH-47 DIABET. DIR. OFF

1. General Details:
Floor Area 10.6 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 790.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 10.5 15 0 0
W 13.3 20 0 0

3.1. Construction Types for Exposure N


Wall Type EXTERIOR WALL
1st Window Type W

3.2. Construction Types for Exposure W


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 10.6 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

200 of 331

Hourly Analysis Program v4.60 Page 10 of 14


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

7-PH-48 MEETING ROOM

1. General Details:
Floor Area 18.3 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 8.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 300.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 17.3 16 0 0

3.1. Construction Types for Exposure N


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 18.3 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

201 of 331

Hourly Analysis Program v4.60 Page 11 of 14


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

7-PH-49 INSURANCE COMP

1. General Details:
Floor Area 14.4 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1580.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 13.3 20 0 0

3.1. Construction Types for Exposure N


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 14.4 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

202 of 331

Hourly Analysis Program v4.60 Page 12 of 14


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

7-PH-50 STAFF REST RM

1. General Details:
Floor Area 25.0 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Break room
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 10.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1560.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 25.1 23 0 0

3.1. Construction Types for Exposure N


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 25.0 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

203 of 331

Hourly Analysis Program v4.60 Page 13 of 14


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

7-PH-Toilet Balance

1. General Details:
Floor Area 3.0 m²
Avg. Ceiling Height 2.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 0.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule None Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 3.0 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

204 of 331

Hourly Analysis Program v4.60 Page 14 of 14


Air System Sizing Summary for AHU-08
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:13PM

Air System Information


Air System Name AHU-08 Number of zones 1
Equipment Class CW AHU Floor Area 2666.5 m²
Air System Type SZCAV Location Jeddah, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s Sum of space airflow rates Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Central Cooling Coil Sizing Data


Total coil load 355.0 kW Load occurs at Aug 1500
Sensible coil load 314.0 kW OA DB / WB 41.0 / 23.5 °C
Coil L/s at Aug 1500 16603 L/s Entering DB / WB 29.7 / 19.3 °C
Max block L/s 16603 L/s Leaving DB / WB 14.0 / 13.0 °C
Sum of peak zone L/s 16603 L/s Coil ADP 12.2 °C
Sensible heat ratio 0.884 Bypass Factor 0.100
m²/kW 7.5 Resulting RH 46 %
W/m² 133.1 Design supply temp. 12.8 °C
Water flow @ 6.0 °K rise 14.16 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 16603 L/s Fan motor BHP 24.15 BHP
Standard L/s 16564 L/s Fan motor kW 19.16 kW
Actual max L/(s-m²) 6.23 L/(s-m²) Fan static 750 Pa

Return Fan Sizing Data


Actual max L/s 16603 L/s Fan motor BHP 16.10 BHP
Standard L/s 16564 L/s Fan motor kW 12.77 kW
Actual max L/(s-m²) 6.23 L/(s-m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 3995 L/s L/s/person 12.37 L/s/person
L/(s-m²) 1.50 L/(s-m²)

205 of 331

Hourly Analysis Program v4.60 Page 1 of 4


Zone Sizing Summary for AHU-08
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:13PM

Air System Information


Air System Name AHU-08 Number of zones 1
Equipment Class CW AHU Floor Area 2666.5 m²
Air System Type SZCAV Location Jeddah, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s Sum of space airflow rates Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (kW) (L/s) (L/s) Load (kW) (m²) L/(s-m²)
Zone 1 221.0 16603 16603 Jul 1500 17.2 2666.5 6.23

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
8-F-002 LOBBY (CORRIDOR) 1 10.2 Jul 1500 755 0.0 327.0 2.31
8-F-009 WATER TREATMENT 1 1.2 Jul 1700 87 0.1 34.9 2.50
8-F-010 COMM ROOM 1 1.7 Jul 1500 128 0.0 13.3 9.62
8-F-016 RECEP. (OFFICE) 1 1.1 Jan 2300 78 0.0 6.4 12.20
8-F-059 RECEPTION 1 3.0 Jul 1000 220 0.1 18.0 12.23
8-F-062 COMM ROOM 1 2.2 Jul 1500 163 0.0 11.0 14.75
8-F-074 ELEC ROOM 1 1.2 Jul 1500 87 0.0 8.4 10.36
8-F-079 PRAYER AREA (FM) 1 1.3 Jan 2300 95 0.0 15.5 6.14
8-F-081 KIDS PLAY ROOM 1 0.7 Jul 1900 52 0.0 9.5 5.47
8-F-084 RECEPTION 1 1.6 Jul 1900 121 0.0 9.2 13.10
8-F-085 LOBBY 1 2.2 Jul 1900 164 0.1 50.0 3.28
8-F-092 WAITING AREA 1 0.5 Jan 2300 38 0.0 7.1 5.35
8-F-093 WAITING AREA 1 1.8 Jan 2300 134 0.0 28.0 4.78
8-F-100 WAITING AREA 1 0.7 Jan 2300 54 0.0 10.7 5.05
8-F-101 WAITING AREA 1 0.7 Jan 2300 54 0.0 10.7 5.05
8-F-103 RECEPTION 1 1.6 Jan 2300 118 0.0 10.5 11.19
8-G-009 SERVER ROOM 1 4.5 Jul 1500 332 0.2 14.6 22.83
8-G-010 PHARMACY&OPTIC 1 9.8 Aug 1600 727 1.4 95.5 7.61
8-G-012 ENTRANCE LOBBY 1 8.3 Aug 1600 614 1.1 77.8 7.89
8-G-013&054 ALL CORRIDOR 1 42.9 Aug 1500 3181 7.3 630.0 5.05
8-G-045 COMM ROOM 1 2.5 Jul 1500 183 0.1 11.6 15.80
8-G-051 CAFE. DIET SHOP 1 11.0 Jun 1400 817 1.0 47.8 17.10
8-G-052 ELEC ROOM 1 1.5 Jul 1500 108 0.1 8.4 12.86
8-G-083 CALL CENTER 1 0.8 Jul 1500 62 0.1 8.5 7.25
8-G-084 ENTRANCE LOBBY 1 17.1 Oct 1500 1270 2.0 110.3 11.52
8-M-19 WAITING AREA (M) 1 0.6 Jan 2300 46 0.0 9.2 5.04
8-M-22 RECEPTION 1 1.2 Jan 2300 92 0.0 17.7 5.19
8-M-23 CHILD. PLAY AREA 1 0.5 Jul 1500 37 0.0 8.5 4.40
8-M-48 LOBBY 1 2.5 Jan 2300 186 0.0 41.7 4.45
8-M-49 RECEPTION 1 2.7 Jul 1500 201 0.0 36.2 5.56
8-M-50 COMM ROOM 1 2.1 Jul 1500 155 0.0 11.0 14.07
8-M-52 ELECTRIC ROOM 1 1.1 Jul 1500 83 0.0 8.4 9.87
8-M-59 CORRIDOR 1 14.7 Aug 1600 1091 0.2 456.0 2.39
8-PH-17 COMM ROOM 1 2.2 Jul 1600 163 0.1 11.0 14.83
206 of 331

Hourly Analysis Program v4.60 Page 2 of 4


Zone Sizing Summary for AHU-08
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:13PM

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
8-PH-24 COMM ROOM 1 2.0 Jun 0900 149 0.1 10.3 14.42
8-PH-26 ELEC ROOM 1 1.2 Jul 1600 89 0.0 8.4 10.55
8-PH-27 ALL CORRIDOR 1 25.5 Jun 1400 1890 1.2 220.0 8.59
8-SKY LEFT 1 16.7 Jun 1400 1239 0.8 121.3 10.21
8-SKY RIGHT 1 18.0 Jun 1400 1335 0.9 116.6 11.45
8-G-089 FireControl RM 1 2.8 Jul 1500 205 0.4 15.4 13.31

207 of 331

Hourly Analysis Program v4.60 Page 3 of 4


Air System Design Load Summary for AHU-08
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:13PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 41.0 °C / 23.5 °C HEATING OA DB / WB 16.8 °C / 9.7 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 545 m² 51655 - 545 m² - -
Wall Transmission 311 m² 1339 - 311 m² 485 -
Roof Transmission 261 m² 1452 - 261 m² 407 -
Window Transmission 235 m² 4981 - 235 m² 1707 -
Skylight Transmission 310 m² 6585 - 310 m² 2257 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 1020 m² 30950 - 1020 m² 10607 -
Partitions 849 m² 18717 - 849 m² 162 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 37384 W 37382 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 23230 W 23229 - 0 0 -
People 323 23685 20324 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 19998 2032 10% 1563 0
>> Total Zone Loads - 219974 22357 - 17188 0
Zone Conditioning - 210211 22357 - 9267 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 16603 L/s 12772 - 16603 L/s -12772 -
Ventilation Load 3995 L/s 71863 18652 3995 L/s 22503 0
Supply Fan Load 16603 L/s 19158 - 16603 L/s -19158 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 314004 41009 - -160 0
Central Cooling Coil - 314004 41026 - 0 0
>> Total Conditioning - 314004 41026 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

208 of 331

Hourly Analysis Program v4.60 Page 4 of 4


AHU-08 Input Data
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:20PM

1. General Details:
Air System Name AHU-08
Equipment Type Chilled Water AHU
Air System Type Single Zone CAV
Number of zones 1

2. System Components:
Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Central Cooling Data:


Supply Air Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND
Capacity Control Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type Backward Inclined or Airfoil (BI/AF)
Configuration Draw-thru
Fan Performance 750 Pa
Overall Efficiency 65 %

Duct System Data:


Supply Duct Data:
Duct Heat Gain 0 %
Duct Leakage 0 %

Return Duct or Plenum Data:


Return Air Via Ducted Return

Return Fan Data:


Fan Type Backward Inclined or Airfoil (BI/AF)
Fan Performance 500 Pa
Overall Efficiency 65 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
8-F-002 LOBBY (CORRIDOR) x1
8-F-009 WATER TREATMENT x1
8-F-010 COMM ROOM x1
8-F-016 RECEP. (OFFICE) x1
8-F-059 RECEPTION x1
8-F-062 COMM ROOM x1
8-F-074 ELEC ROOM x1
8-F-079 PRAYER AREA (FM) x1
8-F-081 KIDS PLAY ROOM x1
8-F-084 RECEPTION x1
8-F-085 LOBBY x1
8-F-092 WAITING AREA x1
8-F-093 WAITING AREA x1
8-F-100 WAITING AREA x1
8-F-101 WAITING AREA x1
8-F-103 RECEPTION x1
8-G-009 SERVER ROOM x1
8-G-010 PHARMACY&OPTIC x1
8-G-012 ENTRANCE LOBBY x1
8-G-013&054 ALL CORRIDOR x1
8-G-045 COMM ROOM x1
8-G-051 CAFE. DIET SHOP x1
8-G-052 ELEC ROOM x1
209 of 331

Hourly Analysis Program v4.60 Page 1 of 3


AHU-08 Input Data
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:20PM

8-G-083 CALL CENTER x1


8-G-084 ENTRANCE LOBBY x1
8-M-19 WAITING AREA (M) x1
8-M-22 RECEPTION x1
8-M-23 CHILD. PLAY AREA x1
8-M-48 LOBBY x1
8-M-49 RECEPTION x1
8-M-50 COMM ROOM x1
8-M-52 ELECTRIC ROOM x1
8-M-59 CORRIDOR x1
8-PH-17 COMM ROOM x1
8-PH-24 COMM ROOM x1
8-PH-26 ELEC ROOM x1
8-PH-27 ALL CORRIDOR x1
8-SKY LEFT x1
8-SKY RIGHT x1
8-G-089 FireControl RM x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 24.0 °C
Cooling T-stat: Unocc. 26.7 °C
Heating T-stat: Occ. 22.0 °C
Heating T-stat: Unocc. 18.3 °C
T-stat Throttling Range 2.00 °K
Diversity Factor 100 %
Direct Exhaust Airflow 0.0 L/s
Direct Exhaust Fan kW 0.0 kW

Thermostat Schedule FAN THERMOSTAT 24/7


Unoccupied Cooling is Available

Supply Terminals Data:


Zone All
Terminal Type Diffuser
Minimum Airflow 0.00 L/s/person

Zone Heating Units:


Zone All
Zone Heating Unit Type None

Zone Unit Heat Source Hot Water


Zone Heating Unit Schedule JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature 12.8 °C
Supply Fan Airflow 16603.0 L/s
Ventilation Airflow 3995.0 L/s

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.0 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) (L/s)
1 16603.0 - -

210 of 331

Hourly Analysis Program v4.60 Page 2 of 3


AHU-08 Input Data
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:20PM

5. Equipment Data
No Equipment Data required for this system.

211 of 331

Hourly Analysis Program v4.60 Page 3 of 3


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

8-F-002 LOBBY (CORRIDOR)

1. General Details:
Floor Area 327.0 m²
Avg. Ceiling Height 2.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 490.0 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 22.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 17.5 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 122.0 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C

212 of 331

Hourly Analysis Program v4.60 Page 1 of 42


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

8-F-009 WATER TREATMENT

1. General Details:
Floor Area 34.9 m²
Avg. Ceiling Height 3.3 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Storage room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 20.1 9 0 0

3.1. Construction Types for Exposure W


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

213 of 331

Hourly Analysis Program v4.60 Page 2 of 42


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

8-F-010 COMM ROOM

1. General Details:
Floor Area 13.3 m²
Avg. Ceiling Height 3.3 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Electrical equipment room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1000.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 16.8 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C

214 of 331

Hourly Analysis Program v4.60 Page 3 of 42


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

8-F-016 RECEP. (OFFICE)

1. General Details:
Floor Area 6.4 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 790.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

215 of 331

Hourly Analysis Program v4.60 Page 4 of 42


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

8-F-059 RECEPTION

1. General Details:
Floor Area 18.0 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 30.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1140.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 15.6 18 0 0

3.1. Construction Types for Exposure E


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 9.2 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 16.6 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C

216 of 331

Hourly Analysis Program v4.60 Page 5 of 42


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

8-F-062 COMM ROOM

1. General Details:
Floor Area 11.0 m²
Avg. Ceiling Height 3.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Electrical equipment room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1000.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 23.2 0 0 0

3.1. Construction Types for Exposure NE


Wall Type EXTERIOR WALL

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 33.0 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C

217 of 331

Hourly Analysis Program v4.60 Page 6 of 42


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

8-F-074 ELEC ROOM

1. General Details:
Floor Area 8.4 m²
Avg. Ceiling Height 3.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Electrical equipment room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 500.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 20.3 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C

218 of 331

Hourly Analysis Program v4.60 Page 7 of 42


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

8-F-079 PRAYER AREA (FM)

1. General Details:
Floor Area 15.5 m²
Avg. Ceiling Height 2.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage PUBLIC ASSEMBLY: Religious worship
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 13.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

219 of 331

Hourly Analysis Program v4.60 Page 8 of 42


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

8-F-081 KIDS PLAY ROOM

1. General Details:
Floor Area 9.5 m²
Avg. Ceiling Height 2.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage SPORTS: Sports arena (play area)
OA Requirement 1 0.0 L/s/person
OA Requirement 2 1.50 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 9.5 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

220 of 331

Hourly Analysis Program v4.60 Page 9 of 42


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

8-F-084 RECEPTION

1. General Details:
Floor Area 9.2 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1140.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 9.2 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

221 of 331

Hourly Analysis Program v4.60 Page 10 of 42


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

8-F-085 LOBBY

1. General Details:
Floor Area 50.0 m²
Avg. Ceiling Height 3.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 95.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 14.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 38.0 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

222 of 331

Hourly Analysis Program v4.60 Page 11 of 42


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

8-F-092 WAITING AREA

1. General Details:
Floor Area 7.1 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 5.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

223 of 331

Hourly Analysis Program v4.60 Page 12 of 42


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

8-F-093 WAITING AREA

1. General Details:
Floor Area 28.0 m²
Avg. Ceiling Height 2.6 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 40.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 790.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

224 of 331

Hourly Analysis Program v4.60 Page 13 of 42


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

8-F-100 WAITING AREA

1. General Details:
Floor Area 10.7 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 7.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

225 of 331

Hourly Analysis Program v4.60 Page 14 of 42


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

8-F-101 WAITING AREA

1. General Details:
Floor Area 10.7 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 7.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

226 of 331

Hourly Analysis Program v4.60 Page 15 of 42


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

8-F-103 RECEPTION

1. General Details:
Floor Area 10.5 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 20.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1140.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

227 of 331

Hourly Analysis Program v4.60 Page 16 of 42


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

8-G-009 SERVER ROOM

1. General Details:
Floor Area 14.6 m²
Avg. Ceiling Height 4.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Electrical equipment room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 3000.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 14.6 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 19.0 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C

228 of 331

Hourly Analysis Program v4.60 Page 17 of 42


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

8-G-010 PHARMACY&OPTIC

1. General Details:
Floor Area 95.5 m²
Avg. Ceiling Height 6.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Pharmacy (prep area)
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.90 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 12.0 People
Wattage 25.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 62.0 34 0 0
S 26.6 0 0 0

3.1. Construction Types for Exposure WSW


Wall Type EXTERIOR WALL
1st Window Type W

3.2. Construction Types for Exposure S


Wall Type EXTERIOR WALL

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 95.5 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 35.0 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C

229 of 331

Hourly Analysis Program v4.60 Page 18 of 42


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

8-G-012 ENTRANCE LOBBY

1. General Details:
Floor Area 77.8 m²
Avg. Ceiling Height 7.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 170.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 10.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1140.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 33.5 42 0 0

3.1. Construction Types for Exposure WSW


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 77.8 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
(No partition data).

230 of 331

Hourly Analysis Program v4.60 Page 19 of 42


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

8-G-013&054 ALL CORRIDOR

1. General Details:
Floor Area 630.0 m²
Avg. Ceiling Height 3.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 1300.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 72.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1580.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 5.9 11 0 0

3.1. Construction Types for Exposure W


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 630.0 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 145.0 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C

231 of 331

Hourly Analysis Program v4.60 Page 20 of 42


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

8-G-045 COMM ROOM

1. General Details:
Floor Area 11.6 m²
Avg. Ceiling Height 3.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Electrical equipment room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1000.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 11.6 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 32.9 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C

232 of 331

Hourly Analysis Program v4.60 Page 21 of 42


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

8-G-051 CAFE. DIET SHOP

1. General Details:
Floor Area 47.8 m²
Avg. Ceiling Height 6.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Coffee station
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 48.0 People
Wattage 15.00 W/m² Activity Level Sedentary Work
Ballast Multiplier 1.00 Sensible 82.1 W/person
Schedule LIGHTING 24/7 Latent 79.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 53.0 100 0 0

3.1. Construction Types for Exposure NE


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 47.8 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 24.2 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C

233 of 331

Hourly Analysis Program v4.60 Page 22 of 42


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

8-G-052 ELEC ROOM

1. General Details:
Floor Area 8.4 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Electrical equipment room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 500.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 8.4 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 20.4 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C

234 of 331

Hourly Analysis Program v4.60 Page 23 of 42


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

8-G-083 CALL CENTER

1. General Details:
Floor Area 8.5 m²
Avg. Ceiling Height 2.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 12.7 0 0 0

3.1. Construction Types for Exposure N


Wall Type EXTERIOR WALL

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 8.5 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 11.3 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C

235 of 331

Hourly Analysis Program v4.60 Page 24 of 42


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

8-G-084 ENTRANCE LOBBY

1. General Details:
Floor Area 110.3 m²
Avg. Ceiling Height 6.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Main entry lobby
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 15.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1140.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 57.0 0 0 0
W 57.5 88 0 0
S 37.0 71 0 0

3.1. Construction Types for Exposure N


Wall Type EXTERIOR WALL

3.2. Construction Types for Exposure W


Wall Type EXTERIOR WALL
1st Window Type W

3.3. Construction Types for Exposure S


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 110.3 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 60.5 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
236 of 331

Hourly Analysis Program v4.60 Page 25 of 42


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

Ambient at Space Max Temp 41.0 °C Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C

237 of 331

Hourly Analysis Program v4.60 Page 26 of 42


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

8-G-089 FireControl RM

1. General Details:
Floor Area 15.4 m²
Avg. Ceiling Height 3.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Electrical equipment room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1000.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 15.4 m²
Total Floor U-Value 2.000 W/(m²-°K)
Unconditioned Space Max Temp. 41.0 °C
Ambient at Space Max Temp. 41.0 °C
Unconditioned Space Min Temp. 16.8 °C
Ambient at Space Min Temp. 16.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition Partition Type Wall Partition
Area 15.6 m² Area 15.6 m²
U-Value 2.000 W/(m²-°K) U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.0 °C Ambient at Space Min Temp 16.8 °C

238 of 331

Hourly Analysis Program v4.60 Page 27 of 42


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

8-M-19 WAITING AREA (M)

1. General Details:
Floor Area 9.2 m²
Avg. Ceiling Height 3.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

239 of 331

Hourly Analysis Program v4.60 Page 28 of 42


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

8-M-22 RECEPTION

1. General Details:
Floor Area 17.7 m²
Avg. Ceiling Height 3.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 30.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 790.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

240 of 331

Hourly Analysis Program v4.60 Page 29 of 42


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

8-M-23 CHILD. PLAY AREA

1. General Details:
Floor Area 8.5 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage SPORTS: Sports arena (play area)
OA Requirement 1 0.0 L/s/person
OA Requirement 2 1.50 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 2.0 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C

241 of 331

Hourly Analysis Program v4.60 Page 30 of 42


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

8-M-48 LOBBY

1. General Details:
Floor Area 41.7 m²
Avg. Ceiling Height 2.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 60.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 12.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 790.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

242 of 331

Hourly Analysis Program v4.60 Page 31 of 42


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

8-M-49 RECEPTION

1. General Details:
Floor Area 36.2 m²
Avg. Ceiling Height 2.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 50.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 10.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 790.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 19.0 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C

243 of 331

Hourly Analysis Program v4.60 Page 32 of 42


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

8-M-50 COMM ROOM

1. General Details:
Floor Area 11.0 m²
Avg. Ceiling Height 3.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Electrical equipment room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1000.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 21.0 0 0 0

3.1. Construction Types for Exposure NE


Wall Type EXTERIOR WALL

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 29.0 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C

244 of 331

Hourly Analysis Program v4.60 Page 33 of 42


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

8-M-52 ELECTRIC ROOM

1. General Details:
Floor Area 8.4 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Electrical equipment room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 500.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 18.0 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C

245 of 331

Hourly Analysis Program v4.60 Page 34 of 42


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

8-M-59 CORRIDOR

1. General Details:
Floor Area 456.0 m²
Avg. Ceiling Height 3.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 810.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 30.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 13.7 24 0 0
WSW 33.0 19 0 0

3.1. Construction Types for Exposure E


Wall Type EXTERIOR WALL
1st Window Type W

3.2. Construction Types for Exposure WSW


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 114.0 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C

246 of 331

Hourly Analysis Program v4.60 Page 35 of 42


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

8-PH-17 COMM ROOM

1. General Details:
Floor Area 11.0 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Electrical equipment room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1000.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 22.1 0 0 0

3.1. Construction Types for Exposure NE


Wall Type EXTERIOR WALL

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 11.0 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 30.5 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C

247 of 331

Hourly Analysis Program v4.60 Page 36 of 42


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

8-PH-23 PUMP ROOM

1. General Details:
Floor Area 21.1 m²
Avg. Ceiling Height 3.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Electrical equipment room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1500.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 20.0 36 0 0

3.1. Construction Types for Exposure NE


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 21.1 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

248 of 331

Hourly Analysis Program v4.60 Page 37 of 42


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

8-PH-24 COMM ROOM

1. General Details:
Floor Area 10.3 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Electrical equipment room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1000.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 7.6 14 0 0
SE 19.4 0 0 0

3.1. Construction Types for Exposure NE


Wall Type EXTERIOR WALL
1st Window Type W

3.2. Construction Types for Exposure SE


Wall Type EXTERIOR WALL

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 10.3 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

249 of 331

Hourly Analysis Program v4.60 Page 38 of 42


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

8-PH-26 ELEC ROOM

1. General Details:
Floor Area 8.4 m²
Avg. Ceiling Height 3.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Electrical equipment room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 500.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 8.4 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 18.8 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C

250 of 331

Hourly Analysis Program v4.60 Page 39 of 42


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

8-PH-27 ALL CORRIDOR

1. General Details:
Floor Area 220.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 370.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 15.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 24.6 39 0 0

3.1. Construction Types for Exposure S


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 220.0 0 216

4.1. Construction Types for Exposure H


Roof Type Roof
Skylight Type W

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 29.7 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C

251 of 331

Hourly Analysis Program v4.60 Page 40 of 42


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

8-SKY LEFT

1. General Details:
Floor Area 121.3 m²
Avg. Ceiling Height 15.3 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 0.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule None Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 121.3 0 194

4.1. Construction Types for Exposure H


Roof Type Roof
Skylight Type W

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

252 of 331

Hourly Analysis Program v4.60 Page 41 of 42


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:28PM

8-SKY RIGHT

1. General Details:
Floor Area 116.6 m²
Avg. Ceiling Height 15.3 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 0.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule None Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 116.6 0 210

4.1. Construction Types for Exposure H


Roof Type Roof
Skylight Type W

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

253 of 331

Hourly Analysis Program v4.60 Page 42 of 42


Zone Sizing Summary for FCU (1-5)
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:13PM

Air System Information


Air System Name FCU (1-5) Number of zones 20
Equipment Class TERM Floor Area 820.0 m²
Air System Type 2P-FC Location Jeddah, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s Sum of space airflow rates Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (kW) (L/s) (L/s) Load (kW) (m²) L/(s-m²)
FCU-04 4.0 299 299 Jul 1500 0.0 16.5 18.10
FCU-04 4.6 341 341 Jul 1500 0.0 17.0 20.07
FCU-03 3.3 245 245 Jul 1500 0.0 18.5 13.25
FCU-03 3.5 260 260 Jul 1500 0.0 25.0 10.40
4*FCU-04 17.7 1314 1314 Jul 1500 0.2 217.0 6.06
2*FCU-04 9.2 682 682 Jul 1500 0.1 46.0 14.82
FCU-02 2.4 179 179 Jul 1500 0.0 20.0 8.95
FCU-03 3.5 258 258 Jul 1500 0.0 22.0 11.74
FCU-04 0.9 68 68 Jul 1500 0.0 11.0 6.23
FCU-04 4.3 320 320 Jul 1500 0.0 24.0 13.32
FCU-04 3.7 272 272 Jul 1500 0.0 19.5 13.94
FCU-04 4.1 301 301 Jul 1500 0.0 29.0 10.39
FCU-05 5.5 411 411 Jul 1500 0.0 64.0 6.42
FCU-03 3.4 250 250 Jul 1500 0.0 17.0 14.70
FCU-03 3.4 253 253 Jul 1500 0.0 19.0 13.34
FCU-03 3.3 242 242 Jul 1500 0.0 24.0 10.10
FCU-01 0.9 70 70 Jul 1500 0.0 9.5 7.38
2*FCU-04 9.2 682 682 Jul 1500 0.1 46.0 14.82
2*FCU-05 10.9 811 811 Jul 1500 0.1 152.0 5.34
FCU-04 4.3 316 316 Jul 1500 0.0 23.0 13.75

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 6.0 °K Peak
Zone Name (kW) (kW) (°C) (°C) (L/s) Load
FCU-04 4.0 3.9 26.3 / 18.6 15.3 / 14.6 0.16 Jul 1500
FCU-04 4.6 4.5 26.2 / 18.5 15.3 / 14.5 0.18 Jul 1500
FCU-03 3.3 3.2 26.1 / 18.4 15.1 / 14.4 0.13 Jul 1500
FCU-03 3.6 3.5 26.2 / 18.5 15.2 / 14.5 0.14 Jul 1500
4*FCU-04 20.7 19.3 27.3 / 18.9 15.1 / 14.3 0.83 Jul 1500
2*FCU-04 9.3 9.1 26.2 / 18.4 15.1 / 14.4 0.37 Jul 1600
FCU-02 2.7 2.5 26.7 / 18.6 15.0 / 14.2 0.11 Jul 1500
FCU-03 3.5 3.4 26.3 / 18.7 15.5 / 14.7 0.14 Jul 1500
FCU-04 1.0 0.9 26.5 / 18.8 15.4 / 14.7 0.04 Jun 1500
FCU-04 4.5 4.3 26.5 / 18.6 15.2 / 14.5 0.18 Jul 1400
FCU-04 3.9 3.8 26.5 / 18.5 15.0 / 14.3 0.16 Jul 1600
FCU-04 4.6 4.4 27.0 / 18.7 15.0 / 14.2 0.18 Jul 1500
FCU-05 6.5 6.0 27.3 / 18.8 15.0 / 14.3 0.26 Jul 1500
FCU-03 3.5 3.4 26.1 / 18.2 14.8 / 14.1 0.14 Jul 1600
FCU-03 3.5 3.3 26.1 / 18.4 15.1 / 14.4 0.14 Jul 1500
FCU-03 3.5 3.3 26.8 / 18.8 15.4 / 14.7 0.14 Jul 1500
FCU-01 1.1 1.0 27.1 / 18.7 14.9 / 14.1 0.04 Jul 1500
254 of 331

Hourly Analysis Program v4.60 Page 1 of 4


Zone Sizing Summary for FCU (1-5)
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:13PM

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 6.0 °K Peak
Zone Name (kW) (kW) (°C) (°C) (L/s) Load
2*FCU-04 9.3 9.1 26.2 / 18.4 15.1 / 14.4 0.37 Jul 1600
2*FCU-05 12.8 11.9 27.5 / 19.1 15.3 / 14.5 0.51 Jul 1400
FCU-04 4.3 4.2 26.1 / 18.4 15.1 / 14.4 0.17 Jul 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 °K AirFlow Motor Motor AirFlow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
FCU-04 0.0 -18.3 / -18.3 0.00 299 0.157 0.124 7
FCU-04 0.0 -18.3 / -18.3 0.00 341 0.179 0.142 5
FCU-03 0.0 -18.3 / -18.3 0.00 245 0.129 0.102 6
FCU-03 0.0 -18.3 / -18.3 0.00 260 0.137 0.108 8
4*FCU-04 0.0 -18.3 / -18.3 0.00 1314 0.690 0.548 130
2*FCU-04 0.0 -18.3 / -18.3 0.00 682 0.358 0.284 14
FCU-02 0.0 -18.3 / -18.3 0.00 179 0.094 0.075 11
FCU-03 0.0 -18.3 / -18.3 0.00 258 0.136 0.108 7
FCU-04 0.0 -18.3 / -18.3 0.00 68 0.036 0.029 3
FCU-04 0.0 -18.3 / -18.3 0.00 320 0.168 0.133 14
FCU-04 0.0 -18.3 / -18.3 0.00 272 0.143 0.113 13
FCU-04 0.0 -18.3 / -18.3 0.00 301 0.158 0.126 24
FCU-05 0.0 -18.3 / -18.3 0.00 411 0.216 0.171 38
FCU-03 0.0 -18.3 / -18.3 0.00 250 0.131 0.104 5
FCU-03 0.0 -18.3 / -18.3 0.00 253 0.133 0.106 6
FCU-03 0.0 -18.3 / -18.3 0.00 242 0.127 0.101 14
FCU-01 0.0 -18.3 / -18.3 0.00 70 0.037 0.029 6
2*FCU-04 0.0 -18.3 / -18.3 0.00 682 0.358 0.284 14
2*FCU-05 0.0 -18.3 / -18.3 0.00 811 0.426 0.338 91
FCU-04 0.0 -18.3 / -18.3 0.00 316 0.166 0.132 7

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
FCU-04
B1-02 SECURITY(1) 1 4.0 Jul 1500 299 0.0 16.5 18.10
FCU-04
B1-03 COMM(1) 1 4.6 Jul 1500 341 0.0 17.0 20.07
FCU-03
B1-04 LOBBY(1) 1 3.3 Jul 1500 245 0.0 18.5 13.25
FCU-03
B1-06 LOBBY 1 3.5 Jul 1500 260 0.0 25.0 10.40
4*FCU-04
B1-07 AHU 1 17.7 Jul 1500 1314 0.2 217.0 6.06
2*FCU-04
B1-08 MDP ROOM(1) 1 9.2 Jul 1500 682 0.1 46.0 14.82
FCU-02
B1-10 WASTE MANAGMENT 1 2.4 Jul 1500 179 0.0 20.0 8.95
FCU-03
B1-13 LOBBY(1) 1 3.5 Jul 1500 258 0.0 22.0 11.74
FCU-04
B1-15 LOBBY 1 0.9 Jul 1500 68 0.0 11.0 6.23
FCU-04
B1-16 BIO MED WORK SHOP 1 4.3 Jul 1500 320 0.0 24.0 13.32
255 of 331

Hourly Analysis Program v4.60 Page 2 of 4


Zone Sizing Summary for FCU (1-5)
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:13PM

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
FCU-04
B1-17 OFFICE(1) 1 3.7 Jul 1500 272 0.0 19.5 13.94
FCU-04
B1-19 DRIVER LOUNGE(1) 1 2.4 Jul 1500 178 0.0 22.0 8.09
B1-21 OFFICE(1) 1 1.7 Jul 1500 123 0.0 7.0 17.61
FCU-05
B1-14 WORK SHOP(1) 1 3.7 Jul 1500 277 0.0 32.0 8.65
B1-12 store 1 1.8 Jul 1500 134 0.0 32.0 4.19
FCU-03
B2-03 COMM 1 3.4 Jul 1500 250 0.0 17.0 14.70
FCU-03
B2-03 LOBBY 1 3.4 Jul 1500 253 0.0 19.0 13.34
FCU-03
B2-05 HOUSE KEEPING 1 3.3 Jul 1500 242 0.0 24.0 10.10
FCU-01
B2-06 HOUSE KEEPING 1 0.9 Jul 1500 70 0.0 9.5 7.38
2*FCU-04
B2-09 UPS ROOM 1 9.2 Jul 1500 682 0.1 46.0 14.82
2*FCU-05
B2-12 AHU 1 10.9 Jul 1500 811 0.1 152.0 5.34
FCU-04
B2-13 LOBBY 1 4.3 Jul 1500 316 0.0 23.0 13.75

256 of 331

Hourly Analysis Program v4.60 Page 3 of 4


Air System Design Load Summary for FCU (1-5)
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:13PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 41.0 °C / 23.5 °C HEATING OA DB / WB 16.8 °C / 9.7 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 1530 m² 65815 - 1530 m² 868 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 14558 W 14557 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 9800 W 9800 - 0 0 -
People 36 2717 2822 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 600 - 0 0
Safety Factor 10% / 10% 9289 342 10% 87 0
>> Total Zone Loads - 102177 3765 - 954 0
Zone Conditioning - 93883 3765 - 2756 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 423 L/s 0 - 423 L/s 0 -
Ventilation Load 423 L/s 7906 1038 423 L/s 295 0
Ventilation Fan Load 423 L/s 71 - 423 L/s -71 -
Space Fan Coil Fans - 3156 - - -3156 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 105016 4803 - -176 0
Terminal Unit Cooling - 105016 4890 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 105016 4890 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

257 of 331

Hourly Analysis Program v4.60 Page 4 of 4


FCU (1-5) Input Data
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:21PM

1. General Details:
Air System Name FCU (1-5)
Equipment Type Terminal Units
Air System Type 2-Pipe Fan Coil
Number of zones 20
Ventilation Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Open
Outdoor Air CO2 Level 400 ppm

Ventilation Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 100 Pa
Overall Efficiency 60 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: FCU-04
B1-02 SECURITY(1) x1
Zone 2: FCU-04
B1-03 COMM(1) x1
Zone 3: FCU-03
B1-04 LOBBY(1) x1
Zone 4: FCU-03
B1-06 LOBBY x1
Zone 5: 4*FCU-04
B1-07 AHU x1
Zone 6: 2*FCU-04
B1-08 MDP ROOM(1) x1
Zone 7: FCU-02
B1-10 WASTE MANAGMENT x1
Zone 8: FCU-03
B1-13 LOBBY(1) x1
Zone 9: FCU-04
B1-15 LOBBY x1
Zone 10: FCU-04
B1-16 BIO MED WORK SHOP x1
Zone 11: FCU-04
B1-17 OFFICE(1) x1
Zone 12: FCU-04
B1-19 DRIVER LOUNGE(1) x1
B1-21 OFFICE(1) x1
Zone 13: FCU-05
B1-14 WORK SHOP(1) x1
B1-12 store x1
Zone 14: FCU-03
B2-03 COMM x1
258 of 331

Hourly Analysis Program v4.60 Page 1 of 3


FCU (1-5) Input Data
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:21PM

Zone 15: FCU-03


B2-03 LOBBY x1
Zone 16: FCU-03
B2-05 HOUSE KEEPING x1
Zone 17: FCU-01
B2-06 HOUSE KEEPING x1
Zone 18: 2*FCU-04
B2-09 UPS ROOM x1
Zone 19: 2*FCU-05
B2-12 AHU x1
Zone 20: FCU-04
B2-13 LOBBY x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 24.0 °C
Cooling T-stat: Unocc. 26.0 °C
Heating T-stat: Occ. 17.0 °C
Heating T-stat: Unocc. 17.0 °C
T-stat Throttling Range 2.00 °K

Thermostat Schedule FAN THERMOSTAT 24/7(1)


Unoccupied Cooling is Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule * * MAMJJASON*

Fan Control Fan On

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 250 Pa
Fan Overall Efficiency 60 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature 12.8 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.0 °K
Hot Water Delta-T 11.1 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 298.7 - - 7.5
2 341.2 - - 5.1
3 245.1 - - 5.6
4 260.1 - - 7.5
5 1314.1 - - 130.2
6 681.7 - - 13.8
259 of 331

Hourly Analysis Program v4.60 Page 2 of 3


FCU (1-5) Input Data
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:21PM

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
7 179.0 - - 11.0
8 258.4 - - 6.6
9 68.5 - - 3.3
10 319.6 - - 14.4
11 271.9 - - 13.4
12 301.2 - - 23.7
13 410.7 - - 38.4
14 249.9 - - 5.1
15 253.5 - - 5.7
16 242.4 - - 14.4
17 70.1 - - 5.7
18 681.7 - - 13.8
19 811.1 - - 91.2
20 316.2 - - 6.9

5. Equipment Data
No Equipment Data required for this system.

260 of 331

Hourly Analysis Program v4.60 Page 3 of 3


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:32PM

B1-02 SECURITY

1. General Details:
Floor Area 16.5 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Free Hanging Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 500.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition (No partition data).
Area 66.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 23.9 °C
Ambient at Space Max Temp 35.0 °C
Uncondit. Space Min Temp 23.9 °C
Ambient at Space Min Temp 12.8 °C

261 of 331

Hourly Analysis Program v4.60 Page 1 of 31


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:32PM

B1-02 SECURITY(1)

1. General Details:
Floor Area 16.5 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Free Hanging Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7(1) Latent 60.1 W/person
Schedule PEOPLE 24/7(1)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 500.0 Watts
Schedule EQUIPMENT 24/7(1)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 66.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C

262 of 331

Hourly Analysis Program v4.60 Page 2 of 31


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:32PM

B1-03 COMM

1. General Details:
Floor Area 17.0 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Electrical equipment room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Free Hanging Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1000.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 22.1 0 0 0

3.1. Construction Types for Exposure NE


Wall Type EXTERIOR WALL

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 68.0 m² Area 30.5 m²
U-Value 2.839 W/(m²-°K) U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 23.9 °C Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 35.0 °C Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 23.9 °C Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 12.8 °C Ambient at Space Min Temp 16.8 °C

263 of 331

Hourly Analysis Program v4.60 Page 3 of 31


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:32PM

B1-03 COMM(1)

1. General Details:
Floor Area 17.0 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Electrical equipment room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Free Hanging Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7(1) Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1000.0 Watts
Schedule EQUIPMENT 24/7(1)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 68.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C

264 of 331

Hourly Analysis Program v4.60 Page 4 of 31


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:32PM

B1-04 LOBBY

1. General Details:
Floor Area 18.5 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Corridor
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 52.0 m² Area 8.3 m²
U-Value 2.839 W/(m²-°K) U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 23.9 °C Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 35.0 °C Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 23.9 °C Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 12.8 °C Ambient at Space Min Temp 16.8 °C

265 of 331

Hourly Analysis Program v4.60 Page 5 of 31


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:32PM

B1-04 LOBBY(1)

1. General Details:
Floor Area 18.5 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Corridor
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7(1) Latent 60.1 W/person
Schedule PEOPLE 24/7(1)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition Partition Type Wall Partition
Area 52.0 m² Area 8.3 m²
U-Value 2.839 W/(m²-°K) U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C Ambient at Space Min Temp 16.0 °C

266 of 331

Hourly Analysis Program v4.60 Page 6 of 31


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:32PM

B1-06 LOBBY

1. General Details:
Floor Area 25.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Corridor
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Free Hanging Occupancy 2.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7(1) Latent 60.1 W/person
Schedule PEOPLE 24/7(1)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 62.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C

267 of 331

Hourly Analysis Program v4.60 Page 7 of 31


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:32PM

B1-07 AHU

1. General Details:
Floor Area 217.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Storage room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Free Hanging Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7(1) Latent 60.1 W/person
Schedule PEOPLE 24/7(1)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 270.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C

268 of 331

Hourly Analysis Program v4.60 Page 8 of 31


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:32PM

B1-08 MDP ROOM

1. General Details:
Floor Area 46.0 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Electrical equipment room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Free Hanging Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 2500.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 22.1 0 0 0

3.1. Construction Types for Exposure NE


Wall Type EXTERIOR WALL

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 120.0 m² Area 30.5 m²
U-Value 2.839 W/(m²-°K) U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 23.9 °C Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 35.0 °C Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 23.9 °C Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 12.8 °C Ambient at Space Min Temp 16.8 °C

269 of 331

Hourly Analysis Program v4.60 Page 9 of 31


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:32PM

B1-08 MDP ROOM(1)

1. General Details:
Floor Area 46.0 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Electrical equipment room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Free Hanging Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7(1) Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 2500.0 Watts
Schedule EQUIPMENT 24/7(1)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 120.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C

270 of 331

Hourly Analysis Program v4.60 Page 10 of 31


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:32PM

B1-10 WASTE MANAGMENT

1. General Details:
Floor Area 20.0 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7(1) Latent 60.1 W/person
Schedule PEOPLE 24/7(1)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 200.0 Watts
Schedule EQUIPMENT 24/7(1)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 36.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C

271 of 331

Hourly Analysis Program v4.60 Page 11 of 31


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:32PM

B1-12 store

1. General Details:
Floor Area 32.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Storage room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Free Hanging Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule LIGHTING 24/7(1) Latent 133.3 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 27.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C

272 of 331

Hourly Analysis Program v4.60 Page 12 of 31


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:32PM

B1-13 LOBBY

1. General Details:
Floor Area 22.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Corridor
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 60.0 m² Area 8.3 m²
U-Value 2.839 W/(m²-°K) U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 23.9 °C Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 35.0 °C Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 23.9 °C Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 12.8 °C Ambient at Space Min Temp 16.8 °C

273 of 331

Hourly Analysis Program v4.60 Page 13 of 31


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:32PM

B1-13 LOBBY(1)

1. General Details:
Floor Area 22.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Corridor
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7(1) Latent 60.1 W/person
Schedule PEOPLE 24/7(1)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 60.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C

274 of 331

Hourly Analysis Program v4.60 Page 14 of 31


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:32PM

B1-14 WORK SHOP

1. General Details:
Floor Area 32.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Storage room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Free Hanging Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule LIGHTING 24/7 Latent 133.3 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 500.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 50.0 m² Area 8.3 m²
U-Value 2.839 W/(m²-°K) U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 23.9 °C Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 35.0 °C Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 23.9 °C Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 12.8 °C Ambient at Space Min Temp 16.8 °C

275 of 331

Hourly Analysis Program v4.60 Page 15 of 31


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:32PM

B1-14 WORK SHOP(1)

1. General Details:
Floor Area 32.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Storage room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Free Hanging Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule LIGHTING 24/7(1) Latent 133.3 W/person
Schedule PEOPLE 24/7(1)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 500.0 Watts
Schedule EQUIPMENT 24/7(1)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 50.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C

276 of 331

Hourly Analysis Program v4.60 Page 16 of 31


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:32PM

B1-15 LOBBY

1. General Details:
Floor Area 11.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Corridor
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7(1) Latent 60.1 W/person
Schedule PEOPLE 24/7(1)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 14.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C

277 of 331

Hourly Analysis Program v4.60 Page 17 of 31


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:32PM

B1-16 BIO MED WORK SHOP

1. General Details:
Floor Area 24.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Storage room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Free Hanging Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule LIGHTING 24/7(1) Latent 133.3 W/person
Schedule PEOPLE 24/7(1)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 500.0 Watts
Schedule EQUIPMENT 24/7(1)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 65.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C

278 of 331

Hourly Analysis Program v4.60 Page 18 of 31


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:32PM

B1-17 OFFICE

1. General Details:
Floor Area 19.5 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 500.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition (No partition data).
Area 54.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 23.9 °C
Ambient at Space Max Temp 35.0 °C
Uncondit. Space Min Temp 23.9 °C
Ambient at Space Min Temp 12.8 °C

279 of 331

Hourly Analysis Program v4.60 Page 19 of 31


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:32PM

B1-17 OFFICE(1)

1. General Details:
Floor Area 19.5 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7(1) Latent 60.1 W/person
Schedule PEOPLE 24/7(1)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 500.0 Watts
Schedule EQUIPMENT 24/7(1)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 54.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C

280 of 331

Hourly Analysis Program v4.60 Page 20 of 31


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:32PM

B1-19 DRIVER LOUNGE

1. General Details:
Floor Area 22.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage PUBLIC ASSEMBLY: Lobby
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Free Hanging Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 40.0 m² Area 8.3 m²
U-Value 2.839 W/(m²-°K) U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 23.9 °C Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 35.0 °C Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 23.9 °C Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 12.8 °C Ambient at Space Min Temp 16.8 °C

281 of 331

Hourly Analysis Program v4.60 Page 21 of 31


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:32PM

B1-19 DRIVER LOUNGE(1)

1. General Details:
Floor Area 22.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage PUBLIC ASSEMBLY: Lobby
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Free Hanging Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7(1) Latent 60.1 W/person
Schedule PEOPLE 24/7(1)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 38.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C

282 of 331

Hourly Analysis Program v4.60 Page 22 of 31


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:32PM

B1-21 OFFICE

1. General Details:
Floor Area 7.0 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 200.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition (No partition data).
Area 36.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 23.9 °C
Ambient at Space Max Temp 35.0 °C
Uncondit. Space Min Temp 23.9 °C
Ambient at Space Min Temp 12.8 °C

283 of 331

Hourly Analysis Program v4.60 Page 23 of 31


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:32PM

B1-21 OFFICE(1)

1. General Details:
Floor Area 7.0 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7(1) Latent 60.1 W/person
Schedule PEOPLE 24/7(1)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 200.0 Watts
Schedule EQUIPMENT 24/7(1)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 23.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C

284 of 331

Hourly Analysis Program v4.60 Page 24 of 31


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:32PM

B2-03 COMM

1. General Details:
Floor Area 17.0 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Electrical equipment room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Free Hanging Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7(1) Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1000.0 Watts
Schedule EQUIPMENT 24/7(1)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 42.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C

285 of 331

Hourly Analysis Program v4.60 Page 25 of 31


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:32PM

B2-03 LOBBY

1. General Details:
Floor Area 19.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Corridor
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7(1) Latent 60.1 W/person
Schedule PEOPLE 24/7(1)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 60.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C

286 of 331

Hourly Analysis Program v4.60 Page 26 of 31


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:32PM

B2-05 HOUSE KEEPING

1. General Details:
Floor Area 24.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Storage room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Free Hanging Occupancy 2.0 People
Wattage 15.00 W/m² Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule LIGHTING 24/7(1) Latent 133.3 W/person
Schedule PEOPLE 24/7(1)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 300 W
Schedule EQUIPMENT 24/7(1)
2.3. Electrical Equipment:
Wattage 200.0 Watts
Schedule EQUIPMENT 24/7(1)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 52.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C

287 of 331

Hourly Analysis Program v4.60 Page 27 of 31


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:32PM

B2-06 HOUSE KEEPING

1. General Details:
Floor Area 9.5 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Storage room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Free Hanging Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule LIGHTING 24/7(1) Latent 133.3 W/person
Schedule PEOPLE 24/7(1)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 300 W
Schedule EQUIPMENT 24/7(1)
2.3. Electrical Equipment:
Wattage 200.0 Watts
Schedule EQUIPMENT 24/7(1)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 10.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C

288 of 331

Hourly Analysis Program v4.60 Page 28 of 31


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:32PM

B2-09 UPS ROOM

1. General Details:
Floor Area 46.0 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Electrical equipment room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Free Hanging Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7(1) Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 2500.0 Watts
Schedule EQUIPMENT 24/7(1)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 120.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C

289 of 331

Hourly Analysis Program v4.60 Page 29 of 31


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:32PM

B2-12 AHU

1. General Details:
Floor Area 152.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Storage room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Free Hanging Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7(1) Latent 60.1 W/person
Schedule PEOPLE 24/7(1)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 157.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C

290 of 331

Hourly Analysis Program v4.60 Page 30 of 31


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:32PM

B2-13 LOBBY

1. General Details:
Floor Area 23.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Corridor
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7(1) Latent 60.1 W/person
Schedule PEOPLE 24/7(1)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 76.0 m²
U-Value 2.839 W/(m²-°K)
Uncondit. Space Max Temp 41.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 16.0 °C
Ambient at Space Min Temp 16.0 °C

291 of 331

Hourly Analysis Program v4.60 Page 31 of 31


Zone Sizing Summary for FCU-06
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:13PM

Air System Information


Air System Name FCU-06 Number of zones 1
Equipment Class TERM Floor Area 83.3 m²
Air System Type 2P-FC Location Jeddah, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s Sum of space airflow rates Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (kW) (L/s) (L/s) Load (kW) (m²) L/(s-m²)
Zone 1 9.2 700 700 Oct 1500 0.4 83.3 8.41

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 6.0 °K Peak
Zone Name (kW) (kW) (°C) (°C) (L/s) Load
Zone 1 12.8 11.6 28.6 / 19.2 14.8 / 13.9 0.51 Aug 1700

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 °K AirFlow Motor Motor AirFlow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -18.3 / -18.3 0.00 700 0.368 0.292 135

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
9-PH-04 ASSESSMENT 1 1.4 Jul 1900 102 0.0 11.5 8.87
9-PH-06 RECEPTION 1 1.4 Jul 1900 105 0.0 16.5 6.38
9-PH-08 CORRIDOR 1 1.6 Oct 1100 120 0.2 27.2 4.42
9-PH-10 CLN. UTILT.&STAF 1 1.1 Jul 1900 83 0.0 7.4 11.27
9-PH-13 TREATMENT 1 2.1 Nov 1500 158 0.1 8.9 17.69
9-PH-54 GSM 1 1.7 Aug 1600 122 0.1 8.2 14.93
9-PH-53 RO ROOM 1 0.1 Aug 1900 9 0.0 3.6 2.47

292 of 331

Hourly Analysis Program v4.60 Page 1 of 2


Air System Design Load Summary for FCU-06
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:13PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 40.0 °C / 23.2 °C HEATING OA DB / WB 16.8 °C / 9.7 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 13 m² 552 - 13 m² - -
Wall Transmission 26 m² 122 - 26 m² 48 -
Roof Transmission 83 m² 525 - 83 m² 155 -
Window Transmission 13 m² 268 - 13 m² 113 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 24 m² 519 - 24 m² 49 -
Ceiling 12 m² 256 - 12 m² 24 -
Overhead Lighting 1295 W 1294 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 4020 W 4020 - 0 0 -
People 10 718 601 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 827 60 10% 39 0
>> Total Zone Loads - 9101 661 - 428 0
Zone Conditioning - 8997 661 - -186 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 135 L/s 2358 448 135 L/s 498 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 292 - - -292 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 11647 1109 - 20 0
Terminal Unit Cooling - 11647 1111 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 11647 1111 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

293 of 331

Hourly Analysis Program v4.60 Page 2 of 2


FCU-06 Input Data
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:21PM

1. General Details:
Air System Name FCU-06
Equipment Type Terminal Units
Air System Type 2-Pipe Fan Coil
Number of zones 1
Ventilation Direct Ventilation

2. Ventilation System Components:


(Common Ventilation System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
9-PH-04 ASSESSMENT x1
9-PH-06 RECEPTION x1
9-PH-08 CORRIDOR x1
9-PH-10 CLN. UTILT.&STAF x1
9-PH-13 TREATMENT x1
9-PH-54 GSM x1
9-PH-53 RO ROOM x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 24.0 °C
Cooling T-stat: Unocc. 26.0 °C
Heating T-stat: Occ. 23.0 °C
Heating T-stat: Unocc. 17.0 °C
T-stat Throttling Range 2.00 °K

Thermostat Schedule FAN THERMOSTAT 24/7


Unoccupied Cooling is Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule * * MAMJJASON*

Fan Control Fan On


Ventilation Sizing Method Sum of Space OA Airflows

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 250 Pa
Fan Overall Efficiency 60 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature 12.8 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.0 °K
Hot Water Delta-T 11.1 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation 294 of 331

Hourly Analysis Program v4.60 Page 1 of 2


FCU-06 Input Data
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:21PM

(L/s) (kW) (kW) (L/s)


1 700.4 - - 134.6

5. Equipment Data
No Equipment Data required for this system.

295 of 331

Hourly Analysis Program v4.60 Page 2 of 2


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:31PM

9-PH-04 ASSESSMENT

1. General Details:
Floor Area 11.5 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 20.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 790.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 11.5 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

296 of 331

Hourly Analysis Program v4.60 Page 1 of 7


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:31PM

9-PH-06 RECEPTION

1. General Details:
Floor Area 16.5 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 25.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 790.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 16.5 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

297 of 331

Hourly Analysis Program v4.60 Page 2 of 7


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:31PM

9-PH-08 CORRIDOR

1. General Details:
Floor Area 27.2 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 40.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 7.7 12 0 0

3.1. Construction Types for Exposure SE


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 27.2 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 16.0 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C

298 of 331

Hourly Analysis Program v4.60 Page 3 of 7


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:31PM

9-PH-10 CLN. UTILT.&STAF

1. General Details:
Floor Area 7.4 m²
Avg. Ceiling Height 2.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 790.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 7.4 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

299 of 331

Hourly Analysis Program v4.60 Page 4 of 7


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:31PM

9-PH-13 TREATMENT

1. General Details:
Floor Area 8.9 m²
Avg. Ceiling Height 2.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 30.0 L/s
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 650.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 5.3 8 0 0
WSW 4.7 6 0 0

3.1. Construction Types for Exposure S


Wall Type EXTERIOR WALL
1st Window Type W

3.2. Construction Types for Exposure WSW


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 8.9 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 8.3 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
300 of 331

Hourly Analysis Program v4.60 Page 5 of 7


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:31PM

9-PH-53 RO ROOM

1. General Details:
Floor Area 3.6 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Storage room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 3.8 0 0 0
SE 3.0 0 0 0

3.1. Construction Types for Exposure SSE


Wall Type EXTERIOR WALL

3.2. Construction Types for Exposure SE


Wall Type EXTERIOR WALL

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 3.6 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

301 of 331

Hourly Analysis Program v4.60 Page 6 of 7


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:31PM

9-PH-54 GSM

1. General Details:
Floor Area 8.2 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Electrical equipment room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING 24/7 Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1000.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 6.8 0 0 0
SE 7.8 0 0 0

3.1. Construction Types for Exposure WSW


Wall Type EXTERIOR WALL

3.2. Construction Types for Exposure SE


Wall Type EXTERIOR WALL

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 8.2 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Ceiling Partition
Area 12.0 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C

302 of 331

Hourly Analysis Program v4.60 Page 7 of 7


Zone Sizing Summary for FCU-07
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:13PM

Air System Information


Air System Name FCU-07 Number of zones 1
Equipment Class TERM Floor Area 96.6 m²
Air System Type 2P-FC Location Jeddah, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s Sum of space airflow rates Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (kW) (L/s) (L/s) Load (kW) (m²) L/(s-m²)
Zone 1 21.8 1616 1616 Sep 1600 0.6 96.6 16.73

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 6.0 °K Peak
Zone Name (kW) (kW) (°C) (°C) (L/s) Load
Zone 1 31.8 24.8 27.0 / 19.3 14.3 / 13.6 1.27 Sep 1600

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 °K AirFlow Motor Motor AirFlow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -18.3 / -18.3 0.00 1616 0.849 0.674 145

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
9-PH-03 GYM 1 21.8 Sep 1600 1616 0.6 96.6 16.73

303 of 331

Hourly Analysis Program v4.60 Page 1 of 2


Air System Design Load Summary for FCU-07
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:13PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.6 °C / 22.9 °C HEATING OA DB / WB 16.8 °C / 9.7 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 40 m² 3524 - 40 m² - -
Wall Transmission 16 m² 70 - 16 m² 30 -
Roof Transmission 97 m² 528 - 97 m² 180 -
Window Transmission 40 m² 783 - 40 m² 347 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 9 m² 184 - 9 m² 18 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1450 W 1449 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 9120 W 9120 - 0 0 -
People 20 4162 6388 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1982 639 10% 57 0
>> Total Zone Loads - 21802 7027 - 632 0
Zone Conditioning - 21689 7027 - 140 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 145 L/s 2476 -112 145 L/s 482 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 673 - - -673 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 24839 6915 - -52 0
Terminal Unit Cooling - 24839 6923 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 24839 6923 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

304 of 331

Hourly Analysis Program v4.60 Page 2 of 2


FCU-07 Input Data
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:21PM

1. General Details:
Air System Name FCU-07
Equipment Type Terminal Units
Air System Type 2-Pipe Fan Coil
Number of zones 1
Ventilation Direct Ventilation

2. Ventilation System Components:


(Common Ventilation System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
9-PH-03 GYM x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 24.0 °C
Cooling T-stat: Unocc. 26.0 °C
Heating T-stat: Occ. 23.0 °C
Heating T-stat: Unocc. 17.0 °C
T-stat Throttling Range 2.00 °K

Thermostat Schedule FAN THERMOSTAT 24/7


Unoccupied Cooling is Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule * * MAMJJASON*

Fan Control Fan On


Ventilation Sizing Method Sum of Space OA Airflows

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 250 Pa
Fan Overall Efficiency 60 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature 12.8 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.0 °K
Hot Water Delta-T 11.1 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 1616.3 - - 145.0

5. Equipment Data
305 of 331

Hourly Analysis Program v4.60 Page 1 of 2


FCU-07 Input Data
Project Name: Fakeeh 9-9 09/10/2014
Prepared by: Zuhair Fayez Partnership 05:21PM

No Equipment Data required for this system.

306 of 331

Hourly Analysis Program v4.60 Page 2 of 2


Space Input Data
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:32PM

9-PH-03 GYM

1. General Details:
Floor Area 96.6 m²
Avg. Ceiling Height 2.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage SPORTS: Gym, stadium (play area)
OA Requirement 1 0.0 L/s/person
OA Requirement 2 1.50 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 20.0 People
Wattage 15.00 W/m² Activity Level Athletics
Ballast Multiplier 1.00 Sensible 208.1 W/person
Schedule LIGHTING 24/7 Latent 319.4 W/person
Schedule PEOPLE 24/7

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 9120.0 Watts
Schedule EQUIPMENT 24/7

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 51.0 73 0 0
W 5.0 7 0 0

3.1. Construction Types for Exposure WSW


Wall Type EXTERIOR WALL
1st Window Type W

3.2. Construction Types for Exposure W


Wall Type EXTERIOR WALL
1st Window Type W

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 96.6 0 0

4.1. Construction Types for Exposure H


Roof Type Roof

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 9.0 m²
U-Value 2.000 W/(m²-°K)
Uncondit. Space Max Temp 36.0 °C
Ambient at Space Max Temp 41.0 °C
Uncondit. Space Min Temp 22.0 °C
Ambient at Space Min Temp 16.8 °C
307 of 331

Hourly Analysis Program v4.60 Page 1 of 1


Cooling Plant Sizing Summary for Sample Plant
Fakeeh 9-9 09/10/2014
Zuhair Fayez Partnership 05:36PM

1. Plant Information:
Plant Name Sample Plant
Plant Type Generic Chilled Water
Design Weather Jeddah, Saudi Arabia

2. Cooling Plant Sizing Data:


Maximum Plant Load 1255.9 kW
Load occurs at Aug 1500
m²/kW 4.9 m²/kW
Floor area served by plant 6159.2 m²

3. Coincident Air System Cooling Loads for Aug 1500

System
Cooling
Coil Load
Air System Name Mult. ( kW )
AHU-01 1 132.8
AHU-02 1 93.5
AHU-03 1 184.3
AHU-04 1 63.6
AHU-05 1 102.6
AHU-06 1 102.3
AHU-07 1 68.3
AHU-08 1 355.0
FCU-07 1 31.1
FCU-06 1 12.4
FCU (1-5) 1 109.9

System loads are for coils whose cooling source is ' Chilled Water ' or ' Any ' .

308 of 331

Hourly Analysis Program v4.60 Page 1 of 1


Zuhair Fayez Partnership
Made by MFMM Date 9-2014 Project Diabetes Plus
Bldg. 0
Checked by MFMM Date 9-2014 Contract : Sheet No. 1 of 1
Revised by MFMM Date 9-2014 Section : HVAC Calc. No.
Checked by MMEH Date 9-2014 Job No. J13-02100 File
Subject : VENTILATION

Room Area And Volume Fan Selection Data


Space Name & No. AREA Height Volume No. of Air Air flow rate
CHANGING & SHOWERS P-55 13.50 2.4 32.4 12 108
TOILETS & WASHES P-5 14.50 2.4 34.8 12 116
JACCUZI P-07 8.50 2.4 20.4 12 68
DIRTY UTILITY P-09 4.80 2.4 11.5 12 38
330
340
EF-01 SAY 340 L/S

CHANGING & TOILETS P-38 22.20 2.4 53.3 12 178


STAFF TOILET (M) P-31 8.70 2.4 20.9 12 70
CLEAN UTILITY P-37 2.30 2.4 5.5 12 25
STAFF TOILET (F) P-34 10.00 2.4 24.0 12 80
ABLUTION P-30 8.60 2.4 20.6 12 69
DIRTY UTILITY P-32 3.10 2.4 7.4 12 25
DIRTY UTILITY P-33 2.20 2.4 5.3 12 25
TOILETS P-51 9.10 2.4 21.8 12 73
544
545
EF-02 SAY 545 L/S

TOILETS & WASHES(F) P-18 11.20 2.4 26.9 12 90


TOILETS & WASHES(M) P-22 10.50 2.4 25.2 12 84
JANITOR P-21 1.30 2.4 3.1 12 25
H.C. TOILET P-19 3.50 2.4 8.4 12 28
TOILETS & WASHES(F) F-063 11.20 2.4 26.9 12 90
TOILETS & WASHES(M) F-067 10.50 2.4 25.2 12 84
JANITOR F-066 1.30 2.4 3.1 12 25
H.C. TOILET F-064 3.50 2.4 8.4 12 28
DIRTY UTILITY F-073 6.20 2.4 14.9 12 50
PATIENT TOILET F-070 3.60 2.4 8.6 12 29
STAFF TOILET F-071 2.60 2.4 6.2 12 25
TOILETS & WASHES(F) MZ-60 11.20 2.4 26.9 12 90
TOILETS & WASHES(M) MZ-62 10.50 2.4 25.2 12 84
JANITOR MZ-64 1.30 2.4 3.1 12 25
H.C. TOILET MZ-63 3.50 2.4 8.4 12 28
SPECIMEN WC (F) MZ-47 3.20 2.4 7.7 12 26
SPECIMEN WC (M) MZ-46 2.60 2.4 6.2 12 25
TOILETS & WASHES(F) G-046 11.20 2.4 26.9 12 90
TOILETS & WASHES(M) G-050 10.50 2.4 25.2 12 84
JANITOR G-049 1.30 2.4 3.1 12 25
H.C. TOILET G-048 3.50 2.4 8.4 12 28
1060
1095
EF-03 SAY 1095 L/S

PATIENT TOILET(M) G-017 2.90 2.4 7.0 12 25


TOILET G-020 2.80 2.4 6.7 12 25
SOILED WORK ROOM G-018 5.40 2.8 15.1 12 50
PATIENT TOILET G-028 2.90 2.4 7.0 12 25
STAFF TOILET G-034 3.50 2.4 8.4 12 28
JANITOR MZ-24 4.00 2.4 9.6 12 32
PATIENT TOILET MZ-12 3.80 2.4 9.1 12 30
Dirty Utility DispsalHolding MZ-13 5.00 2.6 13.0 12 43
STAFF TOILET MZ-16 2.50 2.4 6.0 12 25
TOILET F-056 1.75 2.4 4.2 12 25
TOILET F-055 1.75 2.4 4.2 12 25
PATIENT TOILET F-054 3.90 2.4 9.4 12 31
PATIENT TOILET F-057 3.90 2.4 9.4 12 31
TOILET F-051 4.00 2.4 9.6 12 32
DIRTY UTILITY F-047 5.20 2.4 12.5 12 42
PATIENT TOILET F-036 4.00 2.4 9.6 12 32
TOILET F-028 3.30 2.4 7.9 12 26
TOILET F-030 2.60 2.4 6.2 12 25
STAFF TOILET (M) F-029 2.70 2.4 6.5 12 25
STAFF TOILET (M) F-031 2.40 2.4 5.8 12 25

309 of 331
Zuhair Fayez Partnership
Made by MFMM Date 9-2014 Project Diabetes Plus
Bldg. 0
Checked by MFMM Date 9-2014 Contract : Sheet No. 1 of 1
Revised by MFMM Date 9-2014 Section : HVAC Calc. No.
Checked by MMEH Date 9-2014 Job No. J13-02100 File
Subject : VENTILATION

PATIENT TOILET F-023 4.40 2.4 10.6 12 35


DIRTY UTILITY F-022 4.80 2.4 11.5 12 38
677
680
EF-04 SAY 680 L/S

TOILET F-012 2.75 2.4 6.6 12 25


TOILETS & WASHES(F) F-008 11.20 2.4 26.9 12 90
TOILETS & WASHES(M) F-005 11.10 2.4 26.6 12 89
H.C. TOILET F-006 3.50 2.4 8.4 12 28
JANITOR F-007 1.30 2.4 3.1 12 25
TOILETS & WASHES(F) G-008 11.20 2.4 26.9 12 90
TOILETS & WASHES(M) G-004 11.10 2.4 26.6 12 89
JANITOR G-007 1.30 2.4 3.1 12 25
H.C. TOILET G-005 3.50 2.4 8.4 12 28
488
490
EF-05 SAY 490 L/S

DIRTY UTILITY G-066 4.80 2.4 11.5 12 38


TOILET G-081 2.10 2.4 5.0 12 25
STORE G-087 2.90 3.7 10.7 12 36
TOILET G-079 3.00 2.4 7.2 12 25
DIRTY WORKROOM MZ-32 4.10 2.6 10.7 12 36
PATIENT TOILET /CHANGE MZ-35 3.60 2.4 8.6 12 29
JANITOR F-090 3.90 2.4 9.4 12 31
STAFF TOILET F-111 2.80 2.4 6.7 12 25
DIRTY UTILITY F-114 2.60 2.4 6.2 12 25
270
280
EF-06 SAY 280 L/S

AGS 5.60 3.2 17.9 12 60


60
60
EF-07 SAY 60 L/S

Medical Exuausted Spaces interlocked with AHU-02 1045


1045
1045
EF-08 SAY 1045 L/S

Medical Exuausted Spaces interlocked with AHU-03 3755


3755
3755
EF-09 SAY 3755 L/S

Medical Exuausted Spaces interlocked with AHU-05 355


355
355
EF-10 SAY 355 L/S

Medical Exuausted Spaces interlocked with AHU-06 270


270
270
EF-11 SAY 270 L/S

HOUSE KEEPING ROOM B2-06 9.40 4.0 37.6 12 125


125
125
EF-12 SAY 125 L/S

MEDICAL GAS G- 044 30.50 3.8 115.9 6 193


MEDICAL GAS G-045 24.00 3.8 91.2 6 152
345
345
EF-13 SAY 345 L/S

310 of 331
Zuhair Fayez Partnership
Made by MFMM Date 9-2014 Project Diabetes Plus
Bldg. 0
Checked by MFMM Date 9-2014 Contract : Sheet No. 1 of 1
Revised by MFMM Date 9-2014 Section : HVAC Calc. No.
Checked by MMEH Date 9-2014 Job No. J13-02100 File
Subject : VENTILATION

CLEANING GOODS STORE B2-07 14.60 4.0 58.4 12 195


195
200
EF-14 SAY 200 L/S

HOUSE KEEPING MAIN STORE B2-08 18.90 4.0 75.6 12 252


252
255
EF-15 SAY 255 L/S

DIESEL FUEL TANK B2-18 20.10 4.0 80.4 12 268


268
270
EF-16 SAY 270 L/S

TREATMENT ROOM 1 B2-14 23.80 4.0 95.2 6 159


159
160
EF-17 SAY 160 L/S

PUMP ROOM B2-17 38.00 4.0 152.0 6 253


253
255
EF-18 SAY 255 L/S

Toilet B1-20 6.00 4.0 24.0 12 80


80
40
EF-19 SAY 40 L/S

SECURE EQUIPMENT STORE B1-18 6.00 4.0 24.0 6 40


40
40
EF-20 SAY 40 L/S

Store B1-09 19.20 4.0 76.8 6 128


128
130
EF-21 SAY 130 L/S

COMM. ROOM P-17 11.00 3.4 37.4 8 83


COMM. ROOM F-062 11.00 3.4 37.4 8 83
COMM. ROOM MZ-50 11.00 3.2 35.2 8 78
COMM. ROOM G-045 11.60 3.7 42.9 8 95
95
95
CAEF-01 SAY 95 L/S

COMM. ROOM F-010 13.50 3.8 51.3 8 114


SERVER ROOM G-009 14.60 3.7 54.0 8 120
120
120
CAEF-02 SAY 120 L/S

ELEC. ROOM P-26 8.50 3.4 28.9 8 64


ELEC. ROOM F-074 8.50 3.4 28.9 8 64
ELEC. ROOM MZ-52 8.50 3.2 27.2 8 60
ELEC. ROOM G-052 8.50 3.7 31.5 8 70
70
70
CAEF-03 SAY 70 L/S

311 of 331
Zuhair Fayez Partnership
Made by MFMM Date 9-2014 Project Diabetes Plus
Bldg. 0
Checked by MFMM Date 9-2014 Contract : Sheet No. 1 of 1
Revised by MFMM Date 9-2014 Section : HVAC Calc. No.
Checked by MMEH Date 9-2014 Job No. J13-02100 File
Subject : VENTILATION

COMM. ROOM P-24 10.20 3.4 34.7 8 77

77
80
CAEF-04 SAY 80 L/S

MDP ROOM B1-08 69.00 4.0 276.0 8 613


613
615
CAEF-05 SAY 615 L/S

ELEC ROOM G-032 20.00 3.8 76.0 8 169


169
170
CAEF-06 SAY 170 L/S

GENERATOR ROOM G-040 39.50 3.8 150.1 8 334


334
335
CAEF-07 SAY 335 L/S

COMMUNICATION ROOM B1-03 18.50 4.0 74.0 6 123


123
115
CAEF-08 SAY 115 L/S

COMMUNICATION ROOM B2-02 16.80 4.0 67.2 8 149


149
150
CAEF-09 SAY 150 L/S

UPS ROOM B2-09 33.10 4.0 132.4 8 294


294
300
CAEF-10 SAY 300 L/S

GSM P-54 8.20 3.0 24.6 8 55


55
55
CAEF-11 SAY 55 L/S

Room Area And Volume Fan Selection Data


Space Name & No. AREA Height Volume No. of Air Air flow rate
PARKING B1 2416.00 3.7 8939.2 6 14899

PEF-01 (TWO SPEED FAN ) SAY 15000 L/S

Cyclone Fan No. of Fans Air flow rate


CEF-01 7.00 2128.38
2130
SAY 2130 L/S

PARKING B2 1990.00 3.7 7363.0 6 12272

PEF-02 (TWO SPEED FAN ) SAY 12300 L/S

Cyclone Fan No. of Fans Air flow rate


CEF-02 7.00 1753.10
1760
SAY 1760 L/S

312 of 331
Zuhair Fayez Partnership
Made by MFMM Date 9-2014
Project Diabetes Plus
Bldg. 0
Checked by MFMM Date 9-2014 Contract : Sheet No. 1 of 6
Revised by MFMM Date 9-2014 Section : HVAC Calc. No.
Checked by MMEH Date 9-2014 Job No. J13-02100 File
Subject : EXTERNAL STATIC LOSSES SUMMARY FOR AHU-01

EXTERNAL STATIC PRESSURE CALCULATION

Total equivalent supply length = Actual Length + Fitting Equivalent Length


= 95 + 48
= 142.5 M
Supply duct static losses = Total equ. length x Δ Pa/M
= 142.5 x 0.9
= 128.25 Pa
Additional Static Losses On Supply Air Duct :
1- Sound Attenuator 50 Pa
2- Volume Damper 25 Pa
3- Ceiling Diffuser 25 Pa
4- VAV Box 25 Pa
5- Fire Damper 25 Pa
6- Flexible Duct 25 Pa
7- HEAT PIPE INLET 0 Pa

Total Supply Duct Static Losses = 303 Pa

Total equivalent return length = Actual Length + Fitting Equivalent Length


= 77 + 39
= 115.5 M
Return Air duct static losses = Total equ. length x Δ Pa/M
115.5 x 0.8
92.4 Pa
Additional Static Losses On Return Air Duct :
1- Sound Attenuator 50 Pa
2- Volume Damper 25 Pa
3- Ceiling Diffuser 25 Pa
4- Fire Damper 25 Pa
5- VAV Box 25 Pa
6- HEAT PIPE OUTLET 0 Pa

Total Return Air Duct Static Losses = 242 Pa

Total external static losses = Total supply duct losses + Total Return air duct losses
Total external static losses = 545.65 Pa
Adding 10% factor of safety = 54.565 Pa
Total external static losses = 605 Pa
Say 605 Pa

313 of 331
Zuhair Fayez Partnership
Made by MFMM Date 9-2014
Project Diabetes Plus
Bldg. 0
Checked by MFMM Date 9-2014 Contract : Sheet No. 2 of 6
Revised by MFMM Date 9-2014 Section : HVAC Calc. No.
Checked by : Date 9-2014 Job No. J13-02100 File
Subject : EXTERNAL STATIC LOSSES SUMMARY FOR AHU-02

EXTERNAL STATIC PRESSURE CALCULATION

Total equivalent supply length = Actual Length + Fitting Equivalent Length


= 70 + 35
= 105 M
Supply duct static losses = Total equ. length x Δ Pa/M
= 105 x 0.9
= 94.5 Pa
Additional Static Losses On Supply Air Duct :
1- Sound Attenuator 50 Pa
2- Volume Damper 25 Pa
3- Ceiling Diffuser 25 Pa
4- VAV Box 25 Pa
5- Fire Damper 25 Pa
6- Flexible Duct 25 Pa
7- HEAT PIPE INLET 0 Pa

Total Supply Duct Static Losses = 270 Pa

Total equivalent return length = Actual Length + Fitting Equivalent Length


= 117 + 59
= 175.5 M
Return Air duct static losses = Total equ. length x Δ Pa/M
175.5 x 0.7
122.85 Pa
Additional Static Losses On Return Air Duct :
1- Sound Attenuator 50 Pa
2- Volume Damper 25 Pa
3- Ceiling Diffuser 25 Pa
4- Fire Damper 25 Pa
5- VAV Box 25 Pa
6- HEAT PIPE OUTLET 0 Pa

Total Return Air Duct Static Losses = 273 Pa

Total external static losses = Total supply duct losses + Total Return air duct losses
Total external static losses = 542.35 Pa
Adding 10% factor of safety = 54.235 Pa
Total external static losses = 600 Pa
Say 600 Pa

314 of 331
Zuhair Fayez Partnership
Made by MFMM Date 9-2014
Project Diabetes Plus
Bldg. 0
Checked by MFMM Date 9-2014 Contract : Sheet No. 3 of 6
Revised by MFMM Date 9-2014 Section : HVAC Calc. No.
Checked by : Date 9-2014 Job No. J13-02100 File
Subject : EXTERNAL STATIC LOSSES SUMMARY FOR AHU-03

EXTERNAL STATIC PRESSURE CALCULATION

Total equivalent supply length = Actual Length + Fitting Equivalent Length


= 115 + 58
= 172.5 M
Supply duct static losses = Total equ. length x Δ Pa/M
= 172.5 x 0.9
= 155.25 Pa
Additional Static Losses On Supply Air Duct :
1- Sound Attenuator 50 Pa
2- Volume Damper 25 Pa
3- Ceiling Diffuser 25 Pa
4- VAV Box 25 Pa
5- Fire Damper 25 Pa
6- Flexible Duct 25 Pa
7- HEAT PIPE INLET 0 Pa

Total Supply Duct Static Losses = 330 Pa

Total equivalent return length = Actual Length + Fitting Equivalent Length


= 127 + 64
= 190.5 M
Return Air duct static losses = Total equ. length x Δ Pa/M
190.5 x 0.8
152.4 Pa
Additional Static Losses On Return Air Duct :
1- Sound Attenuator 50 Pa
2- Volume Damper 25 Pa
3- Ceiling Diffuser 25 Pa
4- Fire Damper 25 Pa
5- VAV Box 25 Pa
6- HEAT PIPE OUTLET 0 Pa

Total Return Air Duct Static Losses = 302 Pa

Total external static losses = Total supply duct losses + Total Return air duct losses
Total external static losses = 632.65 Pa
Adding 10% factor of safety = 63.265 Pa
Total external static losses = 700 Pa
Say 700 Pa

315 of 331
Zuhair Fayez Partnership
Made by MFMM Date 9-2014
Project Diabetes Plus
Bldg. 0
Checked by MFMM Date 9-2014 Contract : Sheet No. 4 of 6
Revised by MFMM Date 9-2014 Section : HVAC Calc. No.
Checked by : Date 9-2014 Job No. J13-02100 File
Subject : EXTERNAL STATIC LOSSES SUMMARY FOR AHU-04

EXTERNAL STATIC PRESSURE CALCULATION

Total equivalent supply length = Actual Length + Fitting Equivalent Length


= 91 + 46
= 136.5 M
Supply duct static losses = Total equ. length x Δ Pa/M
= 136.5 x 0.9
= 122.85 Pa
Additional Static Losses On Supply Air Duct :
1- Sound Attenuator 50 Pa
2- Volume Damper 25 Pa
3- Ceiling Diffuser 25 Pa
4- VAV Box 25 Pa
5- Fire Damper 25 Pa
6- Flexible Duct 25 Pa
7- HEAT PIPE INLET 0 Pa

Total Supply Duct Static Losses = 298 Pa

Total equivalent return length = Actual Length + Fitting Equivalent Length


= 110 + 55
= 165 M
Return Air duct static losses = Total equ. length x Δ Pa/M
165 x 0.8
132 Pa
Additional Static Losses On Return Air Duct :
1- Sound Attenuator 50 Pa
2- Volume Damper 25 Pa
3- Ceiling Diffuser 25 Pa
4- Fire Damper 25 Pa
5- VAV Box 25 Pa
6- HEAT PIPE OUTLET 0 Pa

Total Return Air Duct Static Losses = 282 Pa

Total external static losses = Total supply duct losses + Total Return air duct losses
Total external static losses = 579.85 Pa
Adding 10% factor of safety = 57.985 Pa
Total external static losses = 640 Pa
Say 640 Pa

316 of 331
Zuhair Fayez Partnership
Made by MFMM Date 9-2014
Project Diabetes Plus
Bldg. 0
Checked by MFMM Date 9-2014 Contract : Sheet No. 5 of 6
Revised by MFMM Date 9-2014 Section : HVAC Calc. No.
Checked by : Date 9-2014 Job No. J13-02100 File
Subject : EXTERNAL STATIC LOSSES SUMMARY FOR AHU-05

EXTERNAL STATIC PRESSURE CALCULATION

Total equivalent supply length = Actual Length + Fitting Equivalent Length


= 90 + 45
= 135 M
Supply duct static losses = Total equ. length x Δ Pa/M
= 135 x 0.9
= 121.5 Pa
Additional Static Losses On Supply Air Duct :
1- Sound Attenuator 50 Pa
2- Volume Damper 25 Pa
3- Ceiling Diffuser 25 Pa
4- VAV Box 25 Pa
5- Fire Damper 25 Pa
6- Flexible Duct 25 Pa
7- HEAT PIPE INLET 0 Pa

Total Supply Duct Static Losses = 297 Pa

Total equivalent return length = Actual Length + Fitting Equivalent Length


= 210 + 105
= 315 M
Return Air duct static losses = Total equ. length x Δ Pa/M
315 x 0.8
252 Pa
Additional Static Losses On Return Air Duct :
1- Sound Attenuator 50 Pa
2- Volume Damper 25 Pa
3- Ceiling Diffuser 25 Pa
4- Fire Damper 25 Pa
5- VAV Box 25 Pa
6- HEAT PIPE OUTLET 0 Pa

Total Return Air Duct Static Losses = 402 Pa

Total external static losses = Total supply duct losses + Total Return air duct losses
Total external static losses = 698.5 Pa
Adding 10% factor of safety = 69.85 Pa
Total external static losses = 770 Pa
Say 770 Pa

317 of 331
Zuhair Fayez Partnership
Made by MFMM Date 9-2014
Project Diabetes Plus
Bldg. 0
Checked by MFMM Date 9-2014 Contract : Sheet No. 6 of 6
Revised by MFMM Date 9-2014 Section : HVAC Calc. No.
Checked by : Date 9-2014 Job No. J13-02100 File
Subject : EXTERNAL STATIC LOSSES SUMMARY FOR AHU-06

EXTERNAL STATIC PRESSURE CALCULATION

Total equivalent supply length = Actual Length + Fitting Equivalent Length


= 105 + 53
= 157.5 M
Supply duct static losses = Total equ. length x Δ Pa/M
= 157.5 x 0.9
= 141.75 Pa
Additional Static Losses On Supply Air Duct :
1- Sound Attenuator 50 Pa
2- Volume Damper 25 Pa
3- Ceiling Diffuser 25 Pa
4- VAV Box 25 Pa
5- Fire Damper 25 Pa
6- Flexible Duct 25 Pa
7- HEAT PIPE INLET 0 Pa

Total Supply Duct Static Losses = 317 Pa

Total equivalent return length = Actual Length + Fitting Equivalent Length


= 130 + 65
= 195 M
Return Air duct static losses = Total equ. length x Δ Pa/M
195 x 0.8
156 Pa
Additional Static Losses On Return Air Duct :
1- Sound Attenuator 50 Pa
2- Volume Damper 25 Pa
3- Ceiling Diffuser 25 Pa
4- Fire Damper 25 Pa
5- VAV Box 25 Pa
6- HEAT PIPE OUTLET 0 Pa

Total Return Air Duct Static Losses = 306 Pa

Total external static losses = Total supply duct losses + Total Return air duct losses
Total external static losses = 622.75 Pa
Adding 10% factor of safety = 62.275 Pa
Total external static losses = 690 Pa
Say 690 Pa

318 of 331
Zuhair Fayez Partnership
Made by MFMM Date 9-2014
Project Diabetes Plus
Bldg. 0
Checked by MFMM Date 9-2014 Contract : Sheet No. 6 of 6
Revised by MFMM Date 9-2014 Section : HVAC Calc. No.
Checked by : Date 9-2014 Job No. J13-02100 File
Subject : EXTERNAL STATIC LOSSES SUMMARY FOR AHU-07

EXTERNAL STATIC PRESSURE CALCULATION

Total equivalent supply length = Actual Length + Fitting Equivalent Length


= 40 + 20
= 60 M
Supply duct static losses = Total equ. length x Δ Pa/M
= 60 x 0.9
= 54 Pa
Additional Static Losses On Supply Air Duct :
1- Sound Attenuator 50 Pa
2- Volume Damper 25 Pa
3- Ceiling Diffuser 25 Pa
4- VAV Box 25 Pa
5- Fire Damper 25 Pa
6- Flexible Duct 25 Pa
7- HEAT PIPE INLET 0 Pa

Total Supply Duct Static Losses = 229 Pa

Total equivalent return length = Actual Length + Fitting Equivalent Length


= 37 + 19
= 55.5 M
Return Air duct static losses = Total equ. length x Δ Pa/M
55.5 x 0.8
44.4 Pa
Additional Static Losses On Return Air Duct :
1- Sound Attenuator 50 Pa
2- Volume Damper 25 Pa
3- Ceiling Diffuser 25 Pa
4- Fire Damper 25 Pa
5- Return Plenum & B.M.O. 25 Pa
6- HEAT PIPE OUTLET 0 Pa

Total Return Air Duct Static Losses = 194 Pa

Total external static losses = Total supply duct losses + Total Return air duct losses
Total external static losses = 423.4 Pa
Adding 10% factor of safety = 42.34 Pa
Total external static losses = 470 Pa
Say 470 Pa

319 of 331
Zuhair Fayez Partnership
Made by MFMM Date 9-2014
Project Diabetes Plus
Bldg. 0
Checked by MFMM Date 9-2014 Contract : Sheet No. 6 of 6
Revised by MFMM Date 9-2014 Section : HVAC Calc. No.
Checked by : Date 9-2014 Job No. J13-02100 File
Subject : EXTERNAL STATIC LOSSES SUMMARY FOR AHU-08

EXTERNAL STATIC PRESSURE CALCULATION

Total equivalent supply length = Actual Length + Fitting Equivalent Length


= 122 + 61
= 183 M
Supply duct static losses = Total equ. length x Δ Pa/M
= 183 x 0.9
= 164.7 Pa
Additional Static Losses On Supply Air Duct :
1- Sound Attenuator 50 Pa
2- Volume Damper 25 Pa
3- Ceiling Diffuser 25 Pa
4- VAV Box 25 Pa
5- Fire Damper 25 Pa
6- Flexible Duct 25 Pa
7- HEAT PIPE INLET 0 Pa

Total Supply Duct Static Losses = 340 Pa

Total equivalent return length = Actual Length + Fitting Equivalent Length


= 90 + 45
= 135 M
Return Air duct static losses = Total equ. length x Δ Pa/M
135 x 0.8
108 Pa
Additional Static Losses On Return Air Duct :
1- Sound Attenuator 50 Pa
2- Volume Damper 25 Pa
3- Ceiling Diffuser 25 Pa
4- Fire Damper 25 Pa
5- VAV Box 25 Pa
6- HEAT PIPE OUTLET 0 Pa

Total Return Air Duct Static Losses = 258 Pa

Total external static losses = Total supply duct losses + Total Return air duct losses
Total external static losses = 597.7 Pa
Adding 10% factor of safety = 59.77 Pa
Total external static losses = 660 Pa
Say 660 Pa

320 of 331
Zuhair Fayez Partnership
Made by MFMM Date 9-2014 Project Diabetes Plus
Bldg. 0
Checked by MFMM Date 9-2014 Contract : Sheet No. 1 OF 6
Revised by MFMM Date 9-2014 Section : HVAC Calc. No.
Checked by : Date 9-2014 Job No. J13-02100 File
Subject : Zone [Load/M3 , Air Pressurization & No. of Air Change/Hr.]

INPUT DATA :

ZONE NO. : 1
ZONE DESCRIPTION :
A/C UNIT : AHU-01
ZONE AREA 306.9 M2
ZONE HEIGHT 3 M
ZONE TOTAL COOLING LOAD = 132.9 kW
SUPPLY AIR FLOW RATE = 7395 L/S
FRESH AIR FLOW RATE = 1025 L/S
MIN. REQ. PRESS. PERCENTAGE = 10 %
ZONE EXHAUST AIR FLOW RATE = 125 L/S

Part EF-06 125

OUTPUT DATA :

ZONE VOLUME = 921 M3


TOTAL LOAD/UNIT VOLUME = 144 W/M3
ENERGY RECOVERY UNIT NOT APPLICABLE
VENT. RECLAM EXH. AIR FLOW RATE = 0 L/S
RETURN AIR = 6370 L/S
RETURN PERCENTAGE = 86.14 %
AIR CHANGE / HOUR = 29 NO.
FRESH AIR CHANGE / HOUR = 4 NO.
FRESH AIR / SUPPLY.AIR PERCENTAGE = 14 %
EXHAUST AIR / FRESH.AIR PERCENTAGE = 0 %

321 of 331
Zuhair Fayez Partnership
Made by MFMM Date 9-2014 Project Diabetes Plus
Bldg. 0
Checked by MFMM Date 9-2014 Contract : Sheet No. 2 OF 6
Revised by MFMM Date 9-2014 Section : HVAC Calc. No.
Checked by : Date 9-2014 Job No. J13-02100 File
Subject : Zone [Load/M3 , Air Pressurization & No. of Air Change/Hr.]

INPUT DATA :

ZONE NO. : 2
ZONE DESCRIPTION :
A/C UNIT : AHU-02
ZONE AREA 325.9 M2
ZONE HEIGHT 3 M
ZONE TOTAL COOLING LOAD = 93.5 kW
SUPPLY AIR FLOW RATE = 3975 L/S
FRESH AIR FLOW RATE = 1225 L/S
MIN. REQ. PRESS. PERCENTAGE = 10 %
ZONE EXHAUST AIR FLOW RATE = 1215 L/S

Part EF-04 , Part EF-08 1215

OUTPUT DATA :

ZONE VOLUME = 978 M3


TOTAL LOAD/UNIT VOLUME = 96 W/M3
ENERGY RECOVERY UNIT NOT APPLICABLE
VENT. RECLAM EXH. AIR FLOW RATE = 0 L/S
RETURN AIR = 2750 L/S
RETURN PERCENTAGE = 69.18 %
AIR CHANGE / HOUR = 15 NO.
FRESH AIR CHANGE / HOUR = 5 NO.
FRESH AIR / SUPPLY.AIR PERCENTAGE = 31 %
EXHAUST AIR / FRESH.AIR PERCENTAGE = 0 %

322 of 331
Zuhair Fayez Partnership
Made by MFMM Date 9-2014 Project Diabetes Plus
Bldg. 0
Checked by MFMM Date 9-2014 Contract : Sheet No. 3 OF 6
Revised by MFMM Date 9-2014 Section : HVAC Calc. No.
Checked by : Date 9-2014 Job No. J13-02100 File
Subject : Zone [Load/M3 , Air Pressurization & No. of Air Change/Hr.]

INPUT DATA :

ZONE NO. : 3
ZONE DESCRIPTION :
A/C UNIT : AHU-03
ZONE AREA 255.2 M2
ZONE HEIGHT 3 M
ZONE TOTAL COOLING LOAD = 184.3 kW
SUPPLY AIR FLOW RATE = 4770 L/S
FRESH AIR FLOW RATE = 3810 L/S
MIN. REQ. PRESS. PERCENTAGE = 10 %
ZONE EXHAUST AIR FLOW RATE = 3875 L/S

Part EF-06 , EF-09 , Part EF-03 3875

OUTPUT DATA :

ZONE VOLUME = 766 M3


TOTAL LOAD/UNIT VOLUME = 241 W/M3
ENERGY RECOVERY UNIT NOT APPLICABLE
VENT. RECLAM EXH. AIR FLOW RATE = 0 L/S
RETURN AIR = 960 L/S
RETURN PERCENTAGE = 20.13 %
AIR CHANGE / HOUR = 22 NO.
FRESH AIR CHANGE / HOUR = 18 NO.
FRESH AIR / SUPPLY.AIR PERCENTAGE = 80 %
EXHAUST AIR / FRESH.AIR PERCENTAGE = 0 %

323 of 331
Zuhair Fayez Partnership
Made by MFMM Date 9-2014 Project Diabetes Plus
Bldg. 0
Checked by MFMM Date 9-2014 Contract : Sheet No. 4 OF 6
Revised by MFMM Date 9-2014 Section : HVAC Calc. No.
Checked by : Date 9-2014 Job No. J13-02100 File
Subject : Zone [Load/M3 , Air Pressurization & No. of Air Change/Hr.]

INPUT DATA :

ZONE NO. : 4
ZONE DESCRIPTION :
A/C UNIT : AHU-04
ZONE AREA 289.0 M2
ZONE HEIGHT 3 M
ZONE TOTAL COOLING LOAD = 63.6 kW
SUPPLY AIR FLOW RATE = 2855 L/S
FRESH AIR FLOW RATE = 875 L/S
MIN. REQ. PRESS. PERCENTAGE = 10 %
ZONE EXHAUST AIR FLOW RATE = 135 L/S

Part EF-04 135

OUTPUT DATA :

ZONE VOLUME = 867 M3


TOTAL LOAD/UNIT VOLUME = 73 W/M3
ENERGY RECOVERY UNIT NOT APPLICABLE
VENT. RECLAM EXH. AIR FLOW RATE = 0 L/S
RETURN AIR = 1980 L/S
RETURN PERCENTAGE = 69.35 %
AIR CHANGE / HOUR = 12 NO.
FRESH AIR CHANGE / HOUR = 4 NO.
FRESH AIR / SUPPLY.AIR PERCENTAGE = 31 %
EXHAUST AIR / FRESH.AIR PERCENTAGE = 0 %

324 of 331
Zuhair Fayez Partnership
Made by MFMM Date 9-2014 Project Diabetes Plus
Bldg. 0
Checked by MFMM Date 9-2014 Contract : Sheet No. 5 OF 6
Revised by MFMM Date 9-2014 Section : HVAC Calc. No.
Checked by : Date 9-2014 Job No. J13-02100 File
Subject : Zone [Load/M3 , Air Pressurization & No. of Air Change/Hr.]

INPUT DATA :

ZONE NO. : 5
ZONE DESCRIPTION :
A/C UNIT : AHU-05
ZONE AREA 442.5 M2
ZONE HEIGHT 3 M
ZONE TOTAL COOLING LOAD = 103.5 kW
SUPPLY AIR FLOW RATE = 4760 L/S
FRESH AIR FLOW RATE = 1225 L/S
MIN. REQ. PRESS. PERCENTAGE = 10 %
ZONE EXHAUST AIR FLOW RATE = 545 L/S

Part EF-06 , EF-10 , Part EF-03 545

OUTPUT DATA :

ZONE VOLUME = 1328 M3


TOTAL LOAD/UNIT VOLUME = 78 W/M3
ENERGY RECOVERY UNIT NOT APPLICABLE
VENT. RECLAM EXH. AIR FLOW RATE = 0 L/S
RETURN AIR = 3535 L/S
RETURN PERCENTAGE = 74.26 %
AIR CHANGE / HOUR = 13 NO.
FRESH AIR CHANGE / HOUR = 3 NO.
FRESH AIR / SUPPLY.AIR PERCENTAGE = 26 %
EXHAUST AIR / FRESH.AIR PERCENTAGE = 0 %

325 of 331
Zuhair Fayez Partnership
Made by MFMM Date 9-2014 Project Diabetes Plus
Bldg. 0
Checked by MFMM Date 9-2014 Contract : Sheet No. 6 OF 6
Revised by MFMM Date 9-2014 Section : HVAC Calc. No.
Checked by : Date 9-2014 Job No. J13-02100 File
Subject : Zone [Load/M3 , Air Pressurization & No. of Air Change/Hr.]

INPUT DATA :

ZONE NO. : 6
ZONE DESCRIPTION :
A/C UNIT : AHU-06
ZONE AREA 567.5 M2
ZONE HEIGHT 3 M
ZONE TOTAL COOLING LOAD = 102.6 kW
SUPPLY AIR FLOW RATE = 4675 L/S
FRESH AIR FLOW RATE = 1280 L/S
MIN. REQ. PRESS. PERCENTAGE = 10 %
ZONE EXHAUST AIR FLOW RATE = 690 L/S

EF-11 , Part EF-05 , Part EF-04 690

OUTPUT DATA :

ZONE VOLUME = 1703 M3


TOTAL LOAD/UNIT VOLUME = 60 W/M3
ENERGY RECOVERY UNIT NOT APPLICABLE
VENT. RECLAM EXH. AIR FLOW RATE = 0 L/S
RETURN AIR = 3395 L/S
RETURN PERCENTAGE = 72.62 %
AIR CHANGE / HOUR = 10 NO.
FRESH AIR CHANGE / HOUR = 3 NO.
FRESH AIR / SUPPLY.AIR PERCENTAGE = 27 %
EXHAUST AIR / FRESH.AIR PERCENTAGE = 0 %

326 of 331
Zuhair Fayez Partnership
Made by MFMM Date 9-2014 Project Diabetes Plus
Bldg. 0
Checked by MFMM Date 9-2014 Contract : Sheet No. 7 OF 6
Revised by MFMM Date 9-2014 Section : HVAC Calc. No.
Checked by : Date 9-2014 Job No. J13-02100 File
Subject : Zone [Load/M3 , Air Pressurization & No. of Air Change/Hr.]

INPUT DATA :

ZONE NO. : 7
ZONE DESCRIPTION :
A/C UNIT : AHU-07
ZONE AREA 305.6 M2
ZONE HEIGHT 3 M
ZONE TOTAL COOLING LOAD = 69.3 kW
SUPPLY AIR FLOW RATE = 3540 L/S
FRESH AIR FLOW RATE = 560 L/S
MIN. REQ. PRESS. PERCENTAGE = 10 %
ZONE EXHAUST AIR FLOW RATE = 545 L/S

EF-02 545

OUTPUT DATA :

ZONE VOLUME = 917 M3


TOTAL LOAD/UNIT VOLUME = 76 W/M3
ENERGY RECOVERY UNIT NOT APPLICABLE
VENT. RECLAM EXH. AIR FLOW RATE = 0 L/S
RETURN AIR = 2980 L/S
RETURN PERCENTAGE = 84.18 %
AIR CHANGE / HOUR = 14 NO.
FRESH AIR CHANGE / HOUR = 2 NO.
FRESH AIR / SUPPLY.AIR PERCENTAGE = 16 %
EXHAUST AIR / FRESH.AIR PERCENTAGE = 0 %

327 of 331
Zuhair Fayez Partnership
Made by MFMM Date 9-2014 Project Diabetes Plus
Bldg. 0
Checked by MFMM Date 9-2014 Contract : Sheet No. 8 OF 6
Revised by MFMM Date 9-2014 Section : HVAC Calc. No.
Checked by : Date 9-2014 Job No. J13-02100 File
Subject : Zone [Load/M3 , Air Pressurization & No. of Air Change/Hr.]

INPUT DATA :

ZONE NO. : 8
ZONE DESCRIPTION :
A/C UNIT : AHU-08
ZONE AREA 1333.3 M2
ZONE HEIGHT 3 M
ZONE TOTAL COOLING LOAD = 177.5 kW
SUPPLY AIR FLOW RATE = 8300 L/S
FRESH AIR FLOW RATE = 2000 L/S
MIN. REQ. PRESS. PERCENTAGE = 10 %
ZONE EXHAUST AIR FLOW RATE = 805 L/S

Part EF-05 , Part EF-03 805

OUTPUT DATA :

ZONE VOLUME = 4000 M3


TOTAL LOAD/UNIT VOLUME = 44 W/M3
ENERGY RECOVERY UNIT NOT APPLICABLE
VENT. RECLAM EXH. AIR FLOW RATE = 0 L/S
RETURN AIR = 6300 L/S
RETURN PERCENTAGE = 75.90 %
AIR CHANGE / HOUR = 7 NO.
FRESH AIR CHANGE / HOUR = 2 NO.
FRESH AIR / SUPPLY.AIR PERCENTAGE = 24 %
EXHAUST AIR / FRESH.AIR PERCENTAGE = 0 %

328 of 331
Zuhair Fayez Partnership
Made by MFMM Date Sep-14 Project DIABATES PLUS
Bldg. 0
Checked MFMM Date Sep-14 Contract : Sheet No. 1 of 2
Revised MFMM Date Sep-14 Section : HVAC Calc. No. Calc. No.
Checked MMEH Date Sep-14 Job No. J13-2100 File
Subject : Stairwell Pressurization

closed door section (Q1)


Q = volumetric flow rate, (m³/s )
N1 = number of floors
∆Psbt =pressure difference between stairwell and building at stairwell top, ( pa )

∆Psbb =pressure difference between stairwell and building at stairwell bottom, ( pa )


As=The stairwell wall area is per floor, ( m² )
Abs=flow area between stairwell and building (per floor), m² SYMBOL value
Ao=The exterior of the building wall area per floorm, ( m² ) N1 (no) 6
Abo=flow area between building and outside (per floor), ( m² ) AO ( m²) 420
B = 3460(1/To - 1/Ts) at sea level standard pressure As ( m²) 72.15
y = distance above stairwell bottom, ( m ) Y1 (m) 23.4
Asb = flow area between stairwell and building (per floor), ( m² ) To (C°) 45
Abo = flow area between building and outside (per floor), ( m² ) Ts (C°) 21
To = temperature of outside air, ( C° ) ∆Psbb(pa) 13
Ts = temperature of stairwell air, ( C° )
AE = area of the gap around each stairwell door to the building is 0.024 ( m² )

notes maximum design pressure


differences when all stairwell doors are closed is 87 pa; the minimum allowable pressure difference is 13 pa. so
∆Psbt should be ≤ maximum design pressure ( for Sprinklered bulding)

Ts To
B = 3460(1/T0 - 1/Ts) 294 318 = 0.888204338

Ab(m2)
Abo=Ab(0.21 * 10-3) 420 = 0.0882

As (m2)
Asb=As(0.11 * 10-3) +AE 72.15 = 0.0319365

Y
∆Psbt =∆Psbb+BY/[1 +( Asb/ Abo)2] 23.4 = 31.37484627

N ∆Psbb
Q SYMBOL 13 = 0.75123122 m³/s
751.23122 L/S

Q1 = 755 L/S

Opened Door Section (Q2)


Q2 = V' = volumetric flow rate from the section, (m/s)
G = the flow factor, fpm (m/s)
Ae = effective flow area per floor from stairwell, (m2)
N2 = number of floors in section (number of open door)
Asb = 1/2 door area
∆Psob = pressure difference at elevation y SYMBOL value
Y b = distance from bottom to lowest open door Asb ( m²) 1
Y t = distance from bottom to highest open door N2 (no) 1
Y t (m) 15.3
Y b (m) 8
Ae = Asb x Abo / [(Asb)2 + (Abo)2] 1/2 0.08785892

∆Psob =∆Psbb X [1 +( Asb/ Abo)2] = 14.70443648


∆Pb =∆Psob +B x Yb = 21.81007118
∆Pt =∆Psob +B x Yt = 28.29396285

329 of 331
G= 4.19392

Q2 = G x N x Ae 368.473444
Q2 = 370 L/S

Exterior Stairwell Door (Q3)

Q = volumetric airflow rate, m3/s


∆P = pressure difference across flow path, Pa
A = flow area (leakage area), m2 = 1/2 door area
Y2 = 1/2 ground floor hight
SYMBOL value
A ( m²) 1
Y2 (m) 2

= 16.4808452

Q3 = 3406.05534
Q3 = 3410

Q tot = Q1 + Q2 + Q 3 = L/S

4535 L/S

330 of 331
Zuhair Fayez Partnership
Made by MFMM Date Sep-14 Project DIABATES PLUS
Bldg. 0
Checked by MFMM Date Sep-14 Contract : Sheet No. 1 of 1
Revised by MFMM Date Sep-14 Section : HVAC Calc. No.
Checked by : Date Sep-14 Job No. :J13-2100 File
Subject : SMOKE MANANGEMENT

Flame Height

Zf 3.01

Mass Flow Rate of Plume

Z 12.3
qc 1400 KW

m. 54.58 kg/s

Q 45.48 m3/s

331 of 331