You are on page 1of 72

EDMY041427

Split Type Air Conditioners


- Cooling Only -

FTKC-N Series
EDMY041427

Split Type
Air Conditioners
FTKC-N Series
FTKC25NVMM RKC25NVM
FTKC35NVMM RKC35NVM
Cooling Only
FTKC50NVMM RKC50NVM
FTKC60NVMM RKC60NVM
1. Power Supply ..........................................................................................2
2. Functions.................................................................................................3
3. Specifications ..........................................................................................4
4. Dimensions .............................................................................................6
4.1 Indoor Unit................................................................................................6
4.2 Outdoor Unit .............................................................................................7
5. Wiring Diagrams......................................................................................8
5.1 Indoor Unit................................................................................................8
5.2 Outdoor Unit .............................................................................................9
6. Piping Diagrams....................................................................................10
6.1 Indoor Unit..............................................................................................10
6.2 Outdoor Unit ...........................................................................................11
7. Capacity Tables ....................................................................................13
7.1 Cooling Only...........................................................................................13
7.2 Capacity Correction Factor by the Length of Refrigerant Piping
(Reference) ............................................................................................15
8. Operation Limit......................................................................................16
9. Sound Level ..........................................................................................17
9.1 Measuring Location ................................................................................17
9.2 Indoor Unit..............................................................................................17
9.3 Outdoor Unit ...........................................................................................18
10.Electric Characteristics..........................................................................19
11.Installation Manual ................................................................................20
11.1 25/35 Class ............................................................................................20
11.2 50/60 Class ............................................................................................30
12.Operation Manual..................................................................................40
13.Optional Accessories ............................................................................65
13.1 Option List ..............................................................................................65
13.2 <KPW937B4> Air Direction Adjustment Grille........................................66
13.3 <KPW945A4> Air Direction Adjustment Grille........................................67

Split Type Air Conditioners FTKC-N Series 1


Power Supply EDMY041427

1. Power Supply
Indoor Unit Outdoor Unit Power Supply
FTKC25NVMM RKC25NVM
FTKC35NVMM RKC35NVM 1 phase, 220 - 230 - 240 V, 50 Hz
FTKC50NVMM RKC50NVM 1 phase, 220 - 230 V, 60 Hz
FTKC60NVMM RKC60NVM

Note: Power Supply Intake ; Outdoor Unit

2 Split Type Air Conditioners FTKC-N Series


EDMY041427 Functions

2. Functions

FTKC25/35NVMM

FTKC50/60NVMM

FTKC25/35NVMM

FTKC50/60NVMM
RKC25/35NVM

RKC50/60NVM

RKC25/35NVM

RKC50/60NVM
Category Functions Category Functions

Basic Inverter (with inverter power control) z z Health & Air-purifying filter — —
Function Clean
19.4 19.4 Photocatalytic deodorising filter — —
Operation limit for cooling (°CDB) ~ 46 ~ 46
Air-purifying filter with photocatalytic
— —
Operation limit for heating (°CWB) — — deodorising function
PAM control z z Titanium apatite photocatalytic
z z
Standby electricity saving — z air-purifying filter
Compressor Oval scroll compressor — — Air filter (prefilter) z z
Swing compressor z z Wipe-clean flat panel z z
Rotary compressor — — Washable grille — —
Reluctance DC motor z z MOULD PROOF operation — —
Comfortable Power-airflow flap z — Heating dry operation — —
Airflow
Power-airflow dual flaps — z Good-sleep cooling operation — —
Power-airflow diffuser — — Timer WEEKLY TIMER operation — —
Wide-angle louvres z z 24-hour ON/OFF TIMER z z
Auto-swing (up and down) z z NIGHT SET mode z z
Auto-swing (right and left) — — Worry Free Auto-restart (after power failure) z z
(Reliability &
3-D airflow — — Durability) Self-diagnosis (digital, LED) display z z
COMFORT AIRFLOW operation z — Wiring error check function — —
Comfort Auto fan speed z z Anti-corrosion treatment of outdoor heat
Control z z
Indoor unit quiet operation z z exchanger
NIGHT QUIET mode (automatic) — — Flexibility Multi-split / split type compatible indoor
— —
unit
OUTDOOR UNIT QUIET operation — z
(manual) Flexible power supply correspondence z z
INTELLIGENT EYE operation — — Chargeless 10 m 10 m
Quick warming function — — Either side drain (right or left) z z
Hot-start function — — Power selection — —
Automatic defrosting — — Remote 5-room centralised controller (option) — —
Control
Operation Automatic operation — — Remote control adaptor (normal open
— —
Programme dry operation z z pulse contact) (option)
Fan only z z Remote control adaptor
— —
(normal open contact) (option)
Lifestyle New POWERFUL operation — —
Convenience (non-inverter) DIII-NET compatible (adaptor) (option) — —
Inverter POWERFUL operation z z Remote Wireless z z
Controller
Priority-room setting — — Wired — —
COOL / HEAT mode lock — —
HOME LEAVE operation — —
ECONO operation z z
Indoor unit ON/OFF button z z
Signal receiving sign z z
R/C with back light — —
Temperature display — —
Note: z : Available
— : Not available

Split Type Air Conditioners FTKC-N Series 3


Specifications EDMY041427

3. Specifications
50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V
Indoor Unit FTKC25NVMM FTKC35NVMM
Model
Outdoor Unit RKC25NVM RKC35NVM
kW 2.5 (1.2 ~ 3.4) 3.5 (1.3 ~ 4.1)
Capacity Btu/h 8,500 (4,100 ~ 11,600) 11,900 (4,400 ~ 14,000)
Rated (Min. ~ Max.)
kcal/h 2,150 (1,030 ~ 2,920) 3,010 (1,120 ~ 3,530)
Moisture Removal L/h 1.2 1.9
Running Current (Rated) A 3.4 - 3.3 - 3.1 / 3.4 - 3.3 4.6 - 4.4 - 4.2 / 4.6 - 4.4
Power Consumption (Rated) W 700 990
Power Factor (Rated) % 93.6 - 92.3 - 94.1 / 93.6 - 92.3 97.8 - 97.8 - 98.2 / 97.8 - 97.8
COP (Rated) W/W 3.57 3.54
Liquid mm φ 6.4 φ 6.4
Piping φ 9.5 φ 9.5
Connections Gas mm
Drain mm φ 16.0 φ 16.0
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Max. Interunit Piping Length m 15 15
Max. Interunit Height Difference m 12 12
Chargeless m 10 10
Amount of Additional Charge of g/m 20 20
Refrigerant
Indoor Unit FTKC25NVMM FTKC35NVMM
Front Panel Colour Shiny Pure White Shiny Pure White
H 9.0 (318) 9.2 (324)
M m³/min 6.7 (237) 6.9 (244)
Airflow Rate (cfm)
L 4.4 (155) 4.6 (162)
SL 3.5 (124) 3.6 (127)
Type Cross Flow Fan Cross Flow Fan
Fan Motor Output W 16 16
Speed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto
Air Direction Control Right, Left, Horizontal, Downwards Right, Left, Horizontal, Downwards
Air Filter Removable / Washable / Mildew Proof Removable / Washable / Mildew Proof
Running Current (Rated) A 0.19 - 0.18 - 0.17 / 0.19 - 0.18 0.27 - 0.26 - 0.24 / 0.27 - 0.26
Power Consumption (Rated) W 39 57
Power Factor (Rated) % 93.3 - 94.2 - 95.6 / 93.3 - 94.2 96.0 - 95.3 - 99.0 / 96.0 - 95.3
Temperature Control Microcomputer Control Microcomputer Control
Dimensions (H × W × D) mm 283 × 770 × 203 283 × 770 × 203
Packaged Dimensions (H × W × D) mm 263 × 840 × 344 263 × 840 × 344
Weight (Mass) kg 8 8
Gross Weight (Gross Mass) kg 10 10
Sound
Pressure H / M / L / SL dB(A) 38 / 33 / 25 / 22 39 / 34 / 26 / 23
Level
Outdoor Unit RKC25NVM RKC35NVM
Casing Colour Ivory White Ivory White
Type Hermetically Sealed Swing Type Hermetically Sealed Swing Type
Compressor Model 1YC25BXD 1YC25BXD
Motor Output W 860 860
Refrigerant Type FW68DA FW68DA
Oil Charge L 0.350 0.350
Type R-32 R-32
Refrigerant
Charge kg 0.5 0.7
Airflow Rate H m³/min 27.1 (957) 27.1 (957)
(cfm)
Type Propeller Propeller
Fan
Motor Output W 20 20
Running Current (Rated) A 3.21 - 3.12 - 2.93 / 3.21 - 3.12 4.33 - 4.14 - 3.96 / 4.33 - 4.14
Power Consumption (Rated) W 661 933
Power Factor (Rated) % 93.6 - 92.1 - 94.0 / 93.6 - 92.1 97.9 - 98.0 - 98.2 / 97.9 - 98.0
Starting Current A 2.5 2.5
Dimensions (H × W × D) mm 550 × 658 × 275 550 × 658 × 275
Packaged Dimensions (H × W × D) mm 616 × 788 × 359 616 × 788 × 359
Weight (Mass) kg 28 32
Gross Weight (Gross Mass) kg 32 34
Sound
Pressure H dB(A) 47 - 48 - 48 / 49 - 50 49 - 49 - 50 / 49 - 50
Level
Drawing No. 3D089134A 3D089135A

Note: „ The data are based on the conditions shown in the table below.
Cooling Piping Length Conversion Formulae

Indoor ; 27°CDB / 19°CWB kcal/h = kW × 860


Outdoor ; 35°CDB / 24°CWB 7.5 m Btu/h = kW × 3412
cfm = m³/min × 35.3

4 Split Type Air Conditioners FTKC-N Series


EDMY041427 Specifications

50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V


Indoor Unit FTKC50NVMM FTKC60NVMM
Model
Outdoor Unit RKC50NVM RKC60NVM
kW 5.2 (1.6 ~ 5.9) 6.0 (1.8 ~ 6.9)
Capacity Btu/h 17,700 (5,500 ~ 20,100) 20,500 (6,100 ~ 23,500)
Rated (Min. ~ Max.)
kcal/h 4,470 (1,380 ~ 5,070) 5,160 (1,550 ~ 5,930)
Moisture Removal L/h 2.9 3.9
Running Current (Rated) A 6.7 - 6.4 - 6.1 / 6.7 - 6.4 8.0 - 7.7 - 7.3 / 8.0 - 7.7
Power Consumption (Rated) W 1,445 1,740
Power Factor (Rated) % 98.0 - 98.2 - 98.7 / 98.0 - 98.2 98.9 - 98.2 - 99.3 / 98.9 - 98.2
COP (Rated) W/W 3.60 3.45
Liquid mm φ 6.4 φ 6.4
Piping φ 12.7 φ 12.7
Connections Gas mm
Drain mm φ 18.0 φ 18.0
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Max. Interunit Piping Length m 30 30
Max. Interunit Height Difference m 20 20
Chargeless m 10 10
Amount of Additional Charge of g/m 20 20
Refrigerant
Indoor Unit FTKC50NVMM FTKC60NVMM
Front Panel Colour Shiny Pure White Shiny Pure White
H 14.3 (504) 15.4 (544)
M m³/min 12.4 (437) 13.5 (478)
Airflow Rate (cfm)
L 10.1 (356) 11.4 (402)
SL 9.0 (317) 9.9 (350)
Type Cross Flow Fan Cross Flow Fan
Fan Motor Output W 43 43
Speed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto
Air Direction Control Right, Left, Horizontal, Downwards Right, Left, Horizontal, Downwards
Air Filter Removable / Washable / Mildew Proof Removable / Washable / Mildew Proof
Running Current (Rated) A 0.19 - 0.18 - 0.18 / 0.19 - 0.18 0.21 - 0.20 - 0.19 / 0.21 - 0.20
Power Consumption (Rated) W 34 40
Power Factor (Rated) % 81.3 - 82.1 - 78.7 / 81.3 - 82.1 86.6 - 87.0 - 87.7 / 86.6 - 87.0
Temperature Control Microcomputer Control Microcomputer Control
Dimensions (H × W × D) mm 290 × 1,050 × 237 290 × 1,050 × 237
Packaged Dimensions (H × W × D) mm 361 × 1,145 × 364 361 × 1,145 × 364
Weight (Mass) kg 12 12
Gross Weight (Gross Mass) kg 17 17
Sound
Pressure H / M / L / SL dB(A) 42 / 37 / 32 / 29 44 / 39 / 34 / 31
Level
Outdoor Unit RKC50NVM RKC60NVM
Casing Colour Ivory White Ivory White
Type Hermetically Sealed Swing Type Hermetically Sealed Swing Type
Compressor Model 2YC40BXD 2YC40BXD
Motor Output W 1,300 1,300
Refrigerant Type FW68DA FW68DA
Oil Charge L 0.650 0.650
Type R-32 R-32
Refrigerant
Charge kg 1.2 1.2
H m³/min 49.5 (1,748) 53.4 (1,886)
Airflow Rate (cfm)
SL 45.8 (1,617) 45.8 (1,617)
Type Propeller Propeller
Fan
Motor Output W 53 53
Running Current (Rated) A 6.51 - 6.22 - 5.92 / 6.51 - 6.22 7.80 - 7.50 - 7.11 / 7.80 - 7.50
Power Consumption (Rated) W 1,411 1,700
Power Factor (Rated) % 98.5 - 98.6 - 99.3 / 98.5 - 98.6 99.2 - 98.6 - 99.6 / 99.2 - 98.6
Starting Current A 3.5 3.5
Dimensions (H × W × D) mm 735 × 825 × 300 735 × 825 × 300
Packaged Dimensions (H × W × D) mm 784 × 960 × 390 784 × 960 × 390
Weight (Mass) kg 43 43
Gross Weight (Gross Mass) kg 48 48
Sound
Pressure H / SL dB(A) 48 / 44 52 / 46
Level
Drawing No. 3D089136 3D089137

Note: „ The data are based on the conditions shown in the table below.
Cooling Piping Length Conversion Formulae

Indoor ; 27°CDB / 19°CWB kcal/h = kW × 860


Outdoor ; 35°CDB / 24°CWB 7.5 m Btu/h = kW × 3412
cfm = m³/min × 35.3

Split Type Air Conditioners FTKC-N Series 5


Dimensions EDMY041427

4. Dimensions
4.1 Indoor Unit

FTKC25/35NVMM

AIR FLOW (INDOOR)


THE MARK (→) SHOWS PIPING DIRECTION

PERFORMANCE)
REAR

(SPACE FOR
770

30MIN.
LEFT RIGHT

INCLUDING
MOUNTING PLATE

205 50MIN. 50MIN.


(SPACE FOR (SPACE FOR
203 REQUIRED SPACE
FRONT PANEL FIXING SCREWS MAINTENANCE) MAINTENANCE)
(INSIDE)
MANUFACTURER' S
LABEL

283
SIGNAL RECEIVER
TERMINAL BLOCK
OPERATION LAMP
WITH EARTH
TIMER LAMP TERMINAL
INDOOR UNIT ON/OFF SWITCH (INSIDE)
BOTTOM FLAPS
GAS PIPE φ9.5 CuT DRAIN HOSE
ROOM TEMP. THERMISTOR (THE LENGTH OF PIPE OUTSIDE
(INSIDE) (CONNECTING PART
THE UNIT : ABOUT 350) I.D. φ14
LIQUID PIPE φ6.4 CuT O.D. φ16
(THE LENGTH OF PIPE OUTSIDE THE HOSE LENGTH OF OUTSIDE
THE UNIT : ABOUT 400) THE UNIT IS ABOUT 450)

SIGNAL TRANSMITTER MODEL NAME 770


549 101

16
PLATE

6
58 18 BLADE ANGLE
UP/DOWN (AUTOMATIC)

172
DAIKIN

283
41.3
COOLING DRY

5˚ 5˚
163

45˚ 45˚ 54.5 54

41.3
FAN WALL HOLE FOR EMBEDDED PIPING
RIGHT/LEFT (MANUAL)
φ65 HOLE
WALL HOLE

STANDARD LOCATIONS OF WALL HOLES φ65 HOLE
WIRELESS REMOTE CONTROLLER 45˚
45˚ 45˚ 3D089148
(ARC433A88)

FTKC50/60NVMM

THE MARK (→) SHOWS PIPING DIRECTION AIR FLOW (INDOOR)


1050 (FOR PERFORMANCE AND MAINTENANCE)

PERFORMANCE)
REAR REAR
LEFT RIGHT

(SPACE FOR
MIN.30

( INSTALLATION
INCLUDING
PLATE )
239
237
MIN.50 MIN.50
MODEL NAME (SPACE FOR (SPACE FOR
PLATE MAINTENANCE) REQUIRED SPACE MAINTENANCE)
290

TERMINAL BLOCK WITH


EARTH TERMINAL
(INSIDE)

BOTTOM FRONT GRILLE FIXING SCREWS


(INSIDE)
SIGNAL RECEIVER
OPERATION LAMP
TIMER LAMP

GAS PIPE φ12.7 CuT DRAIN HOSE FOR VP13


INDOOR UNIT ON/OFF SWITCH (THE LENGTH OF PIPE OUTSIDE (CONNECTING PART
THE UNIT : ABOUT 430) I.D. 14.0, O.D. 18.0)
ROOM TEMP. THERMISTOR (INSIDE) (THE HOSE LENGTH OF
FLAPS MODEL NAME PLATE LIQUID PIPE φ6.4 CuT OUTSIDE THE UNIT :
SIGNAL (THE LENGTH OF PIPE OUTSIDE
ABOUT 530)
TRANSMITTER THE UNIT : ABOUT 480)
(58) (18) HORIZONTAL BLADE BLADE ANGLES 1050
(AUTOMATIC)
893.5 52.5
30

COOLING DRY
14.5

155.5

10˚ 5˚
290
(163)

52

40˚ 10˚ 5˚
35˚
40˚ 35˚
FAN
VERTICAL BLADE (MANUAL)
52

60 99.5 WALL HOLE


5˚ φ80 HOLE
WALL HOLE FOR STANDARD LOCATIONS OF WALL HOLES
50˚
WIRELESS REMOTE CONTROLLER
5˚ 50˚ EMBEDDED PIPING
55˚
55˚ φ80 HOLE 3D089150
(ARC433A105)

6 Split Type Air Conditioners FTKC-N Series


EDMY041427 Dimensions

4.2 Outdoor Unit

RKC25/35NVM

DRAIN OUTLET WALL HEIGHT ON AIR OUTLET SIDE


MINIMUM SPACE FOR AIR PASSAGE
(I.Dφ15.9 HOSE FOR CONNECTION =LESS THAN 1200

150
4-HOLES FOR ANCHOR BOLTS
WITH DRAIN JOINT) (M8 OR M10)

470 96
379

11

100

150
40

50 50

300
50

297

50

100
HANDLE BRAND NAME LABEL MANUFACTURE'S LABEL
275 13.5 12 658 50 8 OUTDOOR AIR THERMISTOR

LIQUID
STOP VALVE
WIRING (φ6.4 CuT)
INLET
550

SERVICE
PORT

168
108
155
GAS STOP VALVE
(φ9.5 CuT)
INDICATION LABEL (INDONESIA)
FOR INDONESIA MODEL ONLY IN CASE OF REMOVING
STOP VALVE COVER

3D089153

RKC50/60NVM

DRAIN OUTLET MINIMUM SPACE FOR AIR PASSAGE WALL HEIGHT ON AIR OUTLET SIDE

100
(I.D.φ15.9 HOSE FOR CONNECTION) =LESS THAN 1200

825 78
325
100

124 580
350

2
36

50 50
50
350
350

330

300

100

350

IN CASE OF REMOVING
STOP VALVE COVER
10

25

OUTDOOR AIR TEMPERATURE


NAME PLATE THERMISTOR
4-HOLES FOR ANCHOR BOLTS TERMINAL STRIP
(M8 OR M10) BRAND NAME PLATE WIRING INLET WITH EARTH TERMINAL
735

89 64

LIQUID STOP VALVE 155 18


(φ6.4 CuT) 160 30
GAS STOP VALVE
SERVICE PORT (φ12.7 CuT)

3D083536B

Split Type Air Conditioners FTKC-N Series 7


Wiring Diagrams EDMY041427

5. Wiring Diagrams
5.1 Indoor Unit

FTKC25/35NVMM

PCB2 PCB1
S27 S26
1 BLK 9 FIELD WIRING.
BLK
LED1 H1P BLK TRANSMISSION GRN/YLW
BLK CIRCUIT
LED2 H2P BLK FG 3
BLK GRN
BLK 2
BLK RECTIFIER H3
+ RED 3 OUTDOOR
9 BLK 1 V1 MR10 1
H2
WHT 2
H1
S1W BLK 1 CAUTION
F1U NOTE THAT OPERATION WILL
t˚ 3.15A X1M RESTART AUTOMATICALLY IF
+ THE MAIN POWER SUPPLY IS
R1T TURNED OFF AND THEN BACK
SIGNAL IPM200 ON AGAIN.
RECEIVER
1 2 1 5 1 6 9 12 1 S403 10
S32 S6 S200
BLK INDOOR
BLK
BLK
BLK
BLK
BLK
BLK

BLK
YLW

BLK BLK
WHT

BLK BLK
ORG

RED
BLU

BLK

WIRELESS BLK BLK BLK


REMOTE
CONTROLLER FG : FRAME GROUND
6 1 4 1
S602 S601 F1U : FUSE
M M H1~H3 : HARNESS
t˚ M1S H1P~H2P : PILOT LAMP
M1F M1F : FAN MOTOR
R2T M1S : SWING MOTOR
PCB1~PCB3 : PRINTED CIRCUIT BOARD
R1T, R2T : THERMISTOR
S6~S602 : CONNECTOR
S1W : OPERATION SWITCH
NOTE) S21 X1M : TERMINAL STRIP
1. PCB3 IS SHOWS THE CASE OF : PROTECTIVE EARTH
OPTION CONNECTION.
PCB3
OPTION
3D058454D

FTKC50/60NVMM

1
PCB3 PCB1
S49 S46 FU1 X1M 2
1 BLK 1 F1U H1
LED1 BLK 1
BLK 3 OUTDOOR
H1P 3.15A
BLK ~ WHT 2
BLK C102 V1
LED2 RED 3
BLK MR10 H2
H2P GRN
BLK
BLK FIELD WIRING.
LED3
H3P BLK C101 GRN/YLW
TRANSMISSION H3
9 BLK 9
CIRCUIT CAUTION
SW1 FG NOTE THAT OPERATION WILL RESTART
S21 AUTOMATICALLY IF THE MAIN POWER SUPPLY
t˚ IS TURNED OFF AND THEN BACK ON AGAIN.
HA S1 BZ : BUZZER
BZ RTH1 7 RED C101, C102 : CAPACITOR
R1T FG : FRAME GROUND
F1U : FUSE
4 BLU H1P~H3P : PILOT LAMP
BRN MR10 : MAGNETIC RELAY
MS
ORG
M1F : FAN MOTOR
M1S : SWING MOTOR
1 WHT
PCB1~PCB3 : PRINTED CIRCUIT BOARD
S47 S32 S41 M1F R1T, R2T : THERMISTOR
1 3 1 2 15 13 11 9 7 S1~S49 : CONNECTOR
SW1 : OPERATION SWITCH
V1 : VARISTOR
BLK
BLK
BLK
BLK

BLK

X1M : TERMINAL STRIP


ORG
RED

YLW
PNK
BLU

: PROTECTIVE EARTH
PCB2 S48
WIRELESS 1 3 t˚
REMOTE INDOOR
R2T M
CONTROLLER SIGNAL
RECEIVER
M1S
3D088910

8 Split Type Air Conditioners FTKC-N Series


EDMY041427 Wiring Diagrams

5.2 Outdoor Unit

RKC25/35NVM

3D088772A

RKC50/60NVM

Split Type Air Conditioners FTKC-N Series 9


Piping Diagrams EDMY041427

6. Piping Diagrams
6.1 Indoor Unit
FTKC25/35NVMM FTKC50/60NVMM

INDOOR UNIT

INDOOR UNIT
HEAT EXCHANGER
7.0 CuT

4.8 CuT
(7.9 CuT)
7.0 CuT

THERMISTOR 7.0 CuT


ON HEAT EXCH.
7.0 CuT HEAT EXCHANGER

THERMISTOR
CROSS FLOW FAN ON HEAT EXCH.
FIELD PIPING
(6.4 CuT)
M FIELD PIPING
CROSS FLOW FAN

FAN MOTOR (6.4 CuT)


M
FIELD PIPING 9.5 CuT FAN MOTOR
(9.5 CuT) FIELD PIPING
(12.7 CuT) (12.7 CuT)

REFRIGERANT FLOW
COOLING REFRIGERANT FLOW
COOLING

4D075755A 4D083425C

10 Split Type Air Conditioners FTKC-N Series


EDMY041427 Piping Diagrams

6.2 Outdoor Unit

RKC25NVM

OUTDOOR UNIT
OUTDOOR TEMPERATURE
6.4 CuT HEAT EXCHANGER THERMISTOR
6.4 CuT

7.0 CuT
HEAT EXCHANGER

MOTOR OPERATED
THERMISTOR

VALVE
6.4 CuT 6.4 CuT 6.4 CuT

FAN MUFFLER

6.4 CuT
M MOTOR WITH
FILTER

PROPELLER FAN

STRAINER
4.8 CuT
6.4 CuT

9.5 CuT

FIELD PIPING
LIQUID STOP (6.4 CuT)
VALVE
REFRIGERANT FLOW
DISCHARGE PIPE 9.5 CuT FIELD PIPING
COMPRESSOR COOLING
THERMISTOR (9.5 CuT)
MUFFLER MUFFLER GAS STOP
ACCUMULATOR VALVE

3D089192A

RKC35NVM

OUTDOOR UNIT

HEAT EXCHANGER OUTDOOR TEMPERATURE


7.0 CuT THERMISTOR
9.5 CuT

7.0 CuT
HEAT EXCHANGER

MOTOR OPERATED
THERMISTOR

VALVE
6.4 CuT6.4 CuT 6.4 CuT

MUFFLER
FAN
M WITH
6.4 CuT

MOTOR
FILTER

PROPELLER FAN
STRAINER
4.8 CuT
7.9 CuT

9.5 CuT

FIELD PIPING
REFRIGERANT FLOW
(6.4 CuT)
LIQUID STOP
COOLING
VALVE
9.5 CuT FIELD PIPING
DISCHARGE PIPE COMPRESSOR
THERMISTOR (9.5 CuT)
MUFFLER MUFFLER GAS STOP
ACCUMULATOR VALVE

3D089185A

Split Type Air Conditioners FTKC-N Series 11


Piping Diagrams EDMY041427

RKC50/60NVM

OUTDOOR UNIT

HEAT EXCHANGER
7.0 CuT OUTDOOR TEMPERATURE
THERMISTOR
7.0 CuT

HEAT MUFFLER MOTOR MUFFLER


EXCHANGER WITH OPERATED WITH
THERMISTOR FILTER VALVE FILTER
6.4 CuT
FILTER

M
7.9 CuT

6.4 CuT
PROPELLER FAN

FIELD PIPING
MUFFLER (6.4 CuT)
LIQUID STOP
DISCHARGE PIPE VALVE
THERMISTOR 12.7 CuT
COMPRESSOR FIELD PIPING
ACCUMULATOR 12.7 CuT (12.7 CuT)
GAS STOP
VALVE
REFRIGERANT FLOW
COOLING

3D090240

12 Split Type Air Conditioners FTKC-N Series


EDMY041427 Capacity Tables

7. Capacity Tables
7.1 Cooling Only

FTKC25NVMM + RKC25NVM (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)
AFR 9
BF 0.10

INDOOR OUTDOOR TEMPERATURE (°CDB)


EWB EDB 20 25 30 32 35 40
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.0 20 2.46 2.03 0.54 2.35 1.98 0.59 2.23 1.93 0.64 2.28 1.95 0.66 2.21 1.92 0.69 2.10 1.86 0.74
16.0 22 2.57 2.00 0.54 2.46 1.95 0.60 2.34 1.90 0.65 2.40 1.92 0.66 2.33 1.89 0.70 2.21 1.84 0.75
18.0 25 2.68 2.12 0.55 2.57 2.08 0.60 2.46 2.03 0.65 2.51 2.05 0.67 2.44 2.03 0.70 2.33 1.98 0.75
19.0 27 2.73 2.27 0.55 2.62 2.22 0.60 2.51 2.18 0.65 2.57 2.20 0.67 2.50 2.17 0.70 2.38 2.13 0.75
22.0 30 2.90 2.20 0.55 2.79 2.16 0.60 2.68 2.12 0.66 2.74 2.14 0.67 2.67 2.12 0.70 2.56 2.08 0.76
24.0 32 3.01 2.15 0.56 2.90 2.11 0.61 2.79 2.08 0.66 2.86 2.10 0.68 2.79 2.08 0.71 2.67 2.04 0.76

Symbols: Notes:
AFR : Airflow rate (m³/min.) 1. shows nominal (rated) capacities and power input.
2. TC, PI and SHC must be calculated by interpolation using the figures in
BF : Bypass factor the above tables.
EWB : Entering wet bulb temp. (°C) (Figures out of the tables should not be used for calculation.)
3. Capacities are based on the following conditions.
EDB : Entering dry bulb temp. (°C) Corresponding refrigerant piping length : 7.5 m
TC : Total capacity (kW) Level difference : 0 m
SHC : Sensible heat capacity (kW)
PI : Power input (kW)

3D089843

FTKC35NVMM + RKC35NVM (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)
AFR 9.2
BF 0.12

INDOOR OUTDOOR TEMPERATURE (°CDB)


EWB EDB 20 25 30 32 35 40
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.0 20 3.16 2.37 0.72 3.16 2.37 0.82 3.13 2.36 0.91 3.16 2.37 0.93 3.10 2.34 0.98 2.93 2.26 1.05
16.0 22 3.60 2.47 0.77 3.44 2.39 0.84 3.28 2.32 0.92 3.36 2.36 0.94 3.26 2.31 0.98 3.10 2.23 1.06
18.0 25 3.75 2.58 0.77 3.59 2.51 0.85 3.44 2.44 0.92 3.52 2.48 0.94 3.42 2.43 0.99 3.26 2.36 1.06
19.0 27 3.83 2.72 0.77 3.67 2.65 0.85 3.51 2.58 0.92 3.60 2.62 0.95 3.50 2.58 0.99 3.34 2.51 1.06
22.0 30 4.06 2.62 0.78 3.90 2.56 0.85 3.75 2.50 0.93 3.84 2.53 0.95 3.74 2.50 1.00 3.58 2.44 1.07
24.0 32 4.21 2.55 0.79 4.06 2.49 0.86 3.90 2.44 0.93 4.00 2.47 0.96 3.90 2.44 1.00 3.74 2.38 1.07

Symbols: Notes:
AFR : Airflow rate (m³/min.) 1. shows nominal (rated) capacities and power input.
2. TC, PI and SHC must be calculated by interpolation using the figures in
BF : Bypass factor the above tables.
EWB : Entering wet bulb temp. (°C) (Figures out of the tables should not be used for calculation.)
3. Capacities are based on the following conditions.
EDB : Entering dry bulb temp. (°C) Corresponding refrigerant piping length : 7.5 m
TC : Total capacity (kW) Level difference : 0 m
SHC : Sensible heat capacity (kW)
PI : Power input (kW)

3D089844

Split Type Air Conditioners FTKC-N Series 13


Capacity Tables EDMY041427

FTKC50NVMM + RKC50NVM (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)
AFR 14.3
BF 0.07

INDOOR OUTDOOR TEMPERATURE (°CDB)


EWB EDB 20 25 30 32 35 40
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.0 20 5.11 3.86 1.11 4.88 3.74 1.22 4.65 3.63 1.33 4.75 3.68 1.36 4.60 3.61 1.43 4.36 3.49 1.54
16.0 22 5.34 3.79 1.12 5.11 3.68 1.23 4.88 3.58 1.34 4.99 3.62 1.37 4.84 3.56 1.44 4.60 3.45 1.54
18.0 25 5.57 3.98 1.13 5.34 3.88 1.24 5.11 3.78 1.34 5.23 3.83 1.38 5.08 3.77 1.44 4.84 3.67 1.55
19.0 27 5.69 4.21 1.13 5.45 4.11 1.24 5.22 4.01 1.35 5.35 4.06 1.38 5.20 4.00 1.45 4.96 3.91 1.55
22.0 30 6.03 4.06 1.14 5.80 3.97 1.25 5.57 3.89 1.36 5.70 3.94 1.39 5.56 3.89 1.45 5.32 3.80 1.56
24.0 32 6.26 3.95 1.15 6.03 3.88 1.25 5.80 3.80 1.36 5.94 3.85 1.40 5.80 3.80 1.46 5.56 3.72 1.57

Symbols: Notes:
AFR : Airflow rate (m³/min.) 1. shows nominal (rated) capacities and power input.
2. TC, PI and SHC must be calculated by interpolation using the
BF : Bypass factor figures in the above tables.
EWB : Entering wet bulb temp. (°C) (Figures out of the tables should not be used for calculation.)
3. Capacities are based on the following conditions.
EDB : Entering dry bulb temp. (°C) Corresponding refrigerant piping length : 7.5 m
TC : Total capacity (kW) Level difference : 0 m
SHC : Sensible heat capacity (kW)
PI : Power input (kW)

3D089845

FTKC60NVMM + RKC60NVM (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)
AFR 15.4
BF 0.08

INDOOR OUTDOOR TEMPERATURE (°CDB)


EWB EDB 20 25 30 32 35 40
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.0 20 5.90 4.34 1.34 5.63 4.20 1.47 5.36 4.07 1.60 5.48 4.12 1.64 5.31 4.04 1.72 5.03 3.90 1.85
16.0 22 6.16 4.26 1.35 5.90 4.13 1.48 5.63 4.01 1.61 5.75 4.07 1.65 5.59 3.99 1.73 5.31 3.86 1.86
18.0 25 6.43 4.46 1.36 6.16 4.34 1.49 5.89 4.22 1.62 6.03 4.28 1.66 5.86 4.21 1.74 5.58 4.09 1.86
19.0 27 6.56 4.69 1.36 6.29 4.58 1.49 6.03 4.47 1.62 6.17 4.53 1.66 6.00 4.46 1.74 5.72 4.34 1.87
22.0 30 6.96 4.52 1.37 6.69 4.42 1.50 6.42 4.32 1.63 6.58 4.38 1.67 6.41 4.32 1.75 6.14 4.22 1.88
24.0 32 7.23 4.40 1.38 6.96 4.31 1.51 6.69 4.22 1.64 6.86 4.28 1.68 6.69 4.22 1.76 6.41 4.13 1.89

Symbols: Notes:
AFR : Airflow rate (m³/min.) 1. shows nominal (rated) capacities and power input.
2. TC, PI and SHC must be calculated by interpolation using the
BF : Bypass factor figures in the above tables.
EWB : Entering wet bulb temp. (°C) (Figures out of the tables should not be used for calculation.)
3. Capacities are based on the following conditions.
EDB : Entering dry bulb temp. (°C) Corresponding refrigerant piping length : 7.5 m
TC : Total capacity (kW) Level difference : 0 m
SHC : Sensible heat capacity (kW)
PI : Power input (kW)

3D089846

14 Split Type Air Conditioners FTKC-N Series


EDMY041427 Capacity Tables

7.2 Capacity Correction Factor by the Length of Refrigerant Piping (Reference)


The cooling capacity of the unit has to be corrected in accordance with the length of refrigerant piping —
the distance between the indoor unit and the outdoor unit.

7.2.1 25/35 Class

Cooling (R-32)
(%)
100
Capacity correction factor

90

Range of the
refrigerant
80
additional
charge

5 10 15 (m)

Piping length
(R20651)

7.2.2 50/60 Class

Cooling (R-32)
(%)
100
Capacity correction factor

90

80
Range of the refrigerant additional charge

5 10 15 20 25 30 (m)

Piping length
(R20375)

Note: The graphs show the factor when additional refrigerant of the proper quantity is charged.

Split Type Air Conditioners FTKC-N Series 15


Operation Limit EDMY041427

8. Operation Limit
RKC25/35NVM

50

46

40

Outdoor temp. (˚CDB)

Continuous operation

Pull-down period
30

20
19.4

Notes : 10 14 20 23 28 30
The graph is based Indoor temp. (˚CWB)
on the following conditions.
· Equivalent piping length 7.5m
· Level difference 0m
· Air flow rate High

4D073983E

RKC50/60NVM

50

46

40
Outdoor temp. (˚CDB)

Continuous operation

Pull-down period

30

20
19.4

Notes : 10 14 20 23 28 30
The graph is based Indoor temp. (˚CWB)
on the following conditions.
• Equivalent piping length 7.5m
• Level difference 0m
• Air flow rate High
4D083533A

16 Split Type Air Conditioners FTKC-N Series


EDMY041427 Sound Level

9. Sound Level
9.1 Measuring Location

Indoor Unit Outdoor Unit

1m 1m

0.8 m
MICROPHONE

MICROPHONE

Notes: 1. Operation sound is measured in an anechoic chamber.


2. The data are based on the conditions shown in the table below.

Cooling Piping Length


Indoor ; 27°CDB / 19°CWB 5m
Outdoor ; 35°CDB / 24°CWB

9.2 Indoor Unit


FTKC25NVMM FTKC35NVMM

70 OVER ALL (dB) 70 OVER ALL (dB)


NC-70 NC-70
50/60Hz 50/60Hz 50/60Hz 50/60Hz
SCALE 220-240/220-230V 220-240/220-230V SCALE 220-240/220-230V 220-240/220-230V
OCTAVE BAND SOUND PRESSURE LEVEL
OCTAVE BAND SOUND PRESSURE LEVEL

(H) (L) (H) (L)


60 60
NC-60 A 38 25 NC-60 A 39 26

(B.G.N IS ALREADY RECTIFIED) (B.G.N IS ALREADY RECTIFIED)


dB (0dB=0.0002µ bar)
dB (0dB=0.0002µ bar)

50 50
NC-50 OPERATING CONDITIONS NC-50 OPERATING CONDITIONS
POWER SOURCE 220-240/220-230V 50/60Hz POWER SOURCE 220-240/220-230V 50/60 Hz

40 JIS STANDARD 40 JIS STANDARD


NC-40 220-240/220-230V 50/60Hz (H) NC-40 220-240/220-230V 50/60 Hz (H)
220-240/220-230V 50/60Hz (L) 220-240/220-230V 50/60 Hz (L)
30 Cooling 30 Cooling
NC-30 NC-30

20 20
APPROXIMATE APPROXIMATE NC-20
NC-20
THRESHOLD HEARING THRESHOLD HEARING
FOR CONTINUOUS FOR CONTINUOUS
NOISE NOISE
63 125 250 500 1000 2000 4000 8000 4D089376 63 125 250 500 1000 2000 4000 8000 4D089379
OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz)

FTKC50NVMM FTKC60NVMM

70 OVER ALL (dB) 70 OVER ALL (dB)


NC-70 NC-70
50/60Hz 50/60Hz 50/60Hz 50/60Hz
SCALE 220-240/220-230V 220-240/220-230V SCALE 220-240/220-230V 220-240/220-230V
OCTAVE BAND SOUND PRESSURE LEVEL
OCTAVE BAND SOUND PRESSURE LEVEL

60 (H) (L) 60 (H) (L)


NC-60 A 42 32 NC-60 A 44 34

(B.G.N IS ALREADY RECTIFIED) (B.G.N IS ALREADY RECTIFIED)


dB (0dB=0.0002µ bar)
dB (0dB=0.0002µ bar)

50 50
NC-50 OPERATING CONDITIONS NC-50 OPERATING CONDITIONS
POWER SOURCE 220-240/220-230V 50/60Hz POWER SOURCE 220-240/220-230V 50/60Hz
JIS STANDARD JIS STANDARD
40 40
NC-40 220-240/220-230V 50/60Hz (H) NC-40 220-240/220-230V 50/60Hz (H)
220-240/220-230V 50/60Hz (L) 220-240/220-230V 50/60Hz (L)
30 Cooling 30 Cooling
NC-30 NC-30

20 20
APPROXIMATE APPROXIMATE
THRESHOLD HEARING THRESHOLD HEARING
FOR CONTINUOUS NC-20 FOR CONTINUOUS NC-20
NOISE NOISE
63 125 250 500 1000 2000 4000 8000 4D089508 63 125 250 500 1000 2000 4000 8000 4D089509
OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz)

Split Type Air Conditioners FTKC-N Series 17


Sound Level EDMY041427

9.3 Outdoor Unit


RKC25NVM RKC35NVM

COOLING COOLING
70 OVER ALL (dB) 70 OVER ALL (dB)
NC-70 NC-70
50Hz 60Hz 50Hz 60Hz
SCALE SCALE
220-230-240V 220-230V

OCTAVE BAND SOUND PRESSURE LEVEL


220-230-240V 220-230V
OCTAVE BAND SOUND PRESSURE LEVEL

60 60
NC-60 A 47-48-48 49-50 NC-60 A 49-49-50 49-50

(B.G.N IS ALREADY RECTIFIED) (B.G.N IS ALREADY RECTIFIED)

dB (0dB=0.0002µ bar)
50 50
dB (0dB=0.0002µ bar)

NC-50 OPERATING CONDITIONS NC-50 OPERATING CONDITIONS


POWER SOURCE 220-240/220-230V 50/60Hz (H) POWER SOURCE 220-240/220-230V 50/60Hz (H)
JIS STANDARD (JIS9612) 40 JIS STANDARD (JIS9612)
40
NC-40 220-240/220-230V 50/60Hz (H) NC-40 220-240/220-230V 50/60Hz (H)

30 30
NC-30 NC-30

20 20
APPROXIMATE APPROXIMATE
THRESHOLD HEARING THRESHOLD HEARING NC-20
NC-20 FOR CONTINUOUS
FOR CONTINUOUS
NOISE NOISE
63 125 250 500 1000 2000 4000 8000 4D089535A 63 125 250 500 1000 2000 4000 8000 4D089392A
OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz)

RKC50NVM RKC60NVM

70 OVER ALL (dB) 70 OVER ALL (dB)


NC-70 NC-70
50/60Hz 50/60Hz
OCTAVE BAND SOUND PRESSURE LEVEL

SCALE SCALE
OCTAVE BAND SOUND PRESSURE LEVEL

220-240/220-230V (H) 220-240/220-230V (H)


60 60
NC-60 A 48 NC-60 A 52

(B.G.N IS ALREADY RECTIFIED) (B.G.N IS ALREADY RECTIFIED)


dB (0dB=0.0002µ bar)

dB (0dB=0.0002µ bar)

50 50
NC-50 OPERATING CONDITIONS NC-50 OPERATING CONDITIONS
POWER SOURCE 220-240/220-230V 50/60Hz (H) POWER SOURCE 220-240/220-230V 50/60Hz (H)
40 JIS STANDARD 40 JIS STANDARD
NC-40 NC-40
220-240/220-230V 50/60Hz (H) 220-240/220-230V 50/60Hz (H)

30 30
NC-30
NC-30

20 20
APPROXIMATE APPROXIMATE
THRESHOLD HEARING NC-20 THRESHOLD HEARING
FOR CONTINUOUS NC-20
FOR CONTINUOUS
NOISE NOISE
63 125 250 500 1000 2000 4000 8000 4D088836A 63 125 250 500 1000 2000 4000 8000 4D088837A
OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz)

18 Split Type Air Conditioners FTKC-N Series


EDMY041427 Electric Characteristics

10. Electric Characteristics

Power supply Compressor OFM IFM


Indoor Unit Outdoor Unit
Hz - Volts Voltage range MCA MFA RHz RLA W FLA W FLA
50 - 220 3.0 0.22 0.19
50 - 230 Max. 50 Hz, 264 V 2.9 0.21 0.18
Min. 50 Hz, 198 V
FTKC25NVMM RKC25NVM 50 - 240 8.50 10 46 2.7 20 0.20 16 0.17
60 - 220 Max. 60 Hz, 253 V 3.0 0.22 0.19
60 - 230 Min. 60 Hz, 198 V 2.9 0.21 0.18
50 - 220 4.1 0.22 0.27
Max. 50 Hz, 264 V
50 - 230 3.9 0.21 0.26
Min. 50 Hz, 198 V
FTKC35NVMM RKC35NVM 50 - 240 9.25 10 66 3.7 20 0.20 16 0.24
60 - 220 Max. 60 Hz, 253 V 4.1 0.22 0.27
60 - 230 Min. 60 Hz, 198 V 3.9 0.21 0.26
50 - 220 6.3 0.19 0.19
Max. 50 Hz, 264 V
50 - 230 Min. 50 Hz, 198 V 6.0 0.18 0.18
FTKC50NVMM RKC50NVM 50 - 240 13.50 15 58 5.8 53 0.17 43 0.18
60 - 220 Max. 60 Hz, 253 V 6.3 0.19 0.19
60 - 230 Min. 60 Hz, 198 V 6.0 0.18 0.18
50 - 220 7.6 0.20 0.21
50 - 230 Max. 50 Hz, 264 V 7.3 0.19 0.20
Min. 50 Hz, 198 V
FTKC60NVMM RKC60NVM 50 - 240 13.50 15 69 6.9 53 0.18 43 0.19
60 - 220 Max. 60 Hz, 253 V 7.6 0.20 0.21
60 - 230 Min. 60 Hz, 198 V 7.3 0.19 0.20

Symbols: Notes:
MCA : Min. circuit amps (A) 1. RLA is based on the following conditions.
Indoor temp. 27°CDB / 19°CWB
MFA : Max. fuse amps (A) Outdoor temp. 35°CDB
RHz : Rated operating frequency (Hz) 2. Maximum allowable voltage variation between phases is 2%.
3. Select wire size based on the larger value of MCA.
RLA : Rated load amps (A) 4. Instead of fuse, use circuit breaker.
OFM : Outdoor fan motor 5. Be sure to install an earth leak detector.
(This unit uses an inverter, which means that an earth leak
IFM : Indoor fan motor detector capable of handling high harmonics must be used in
W : Fan motor rated output (W) order to prevent malfunctioning of the earth leak detector.)
FLA : Full load amps (A)

3D089021

Split Type Air Conditioners FTKC-N Series 19


Installation Manual EDMY041427

11. Installation Manual


11.1 25/35 Class

20 Split Type Air Conditioners FTKC-N Series


EDMY041427 Installation Manual

Split Type Air Conditioners FTKC-N Series 21


Installation Manual EDMY041427

22 Split Type Air Conditioners FTKC-N Series


EDMY041427 Installation Manual

Split Type Air Conditioners FTKC-N Series 23


Installation Manual EDMY041427

24 Split Type Air Conditioners FTKC-N Series


EDMY041427 Installation Manual

Split Type Air Conditioners FTKC-N Series 25


Installation Manual EDMY041427

26 Split Type Air Conditioners FTKC-N Series


EDMY041427 Installation Manual

Split Type Air Conditioners FTKC-N Series 27


Installation Manual EDMY041427

28 Split Type Air Conditioners FTKC-N Series


EDMY041427 Installation Manual

3P363835-16C

Split Type Air Conditioners FTKC-N Series 29


Installation Manual EDMY041427

11.2 50/60 Class

30 Split Type Air Conditioners FTKC-N Series


EDMY041427 Installation Manual

Split Type Air Conditioners FTKC-N Series 31


Installation Manual EDMY041427

32 Split Type Air Conditioners FTKC-N Series


EDMY041427 Installation Manual

Split Type Air Conditioners FTKC-N Series 33


Installation Manual EDMY041427

34 Split Type Air Conditioners FTKC-N Series


EDMY041427 Installation Manual

Split Type Air Conditioners FTKC-N Series 35


Installation Manual EDMY041427

36 Split Type Air Conditioners FTKC-N Series


EDMY041427 Installation Manual

Split Type Air Conditioners FTKC-N Series 37


Installation Manual EDMY041427

38 Split Type Air Conditioners FTKC-N Series


EDMY041427 Installation Manual

3P363835-17C

Split Type Air Conditioners FTKC-N Series 39


Operation Manual EDMY041427

12. Operation Manual

40 Split Type Air Conditioners FTKC-N Series


EDMY041427 Operation Manual

Split Type Air Conditioners FTKC-N Series 41


Operation Manual EDMY041427

42 Split Type Air Conditioners FTKC-N Series


EDMY041427 Operation Manual

Split Type Air Conditioners FTKC-N Series 43


Operation Manual EDMY041427

44 Split Type Air Conditioners FTKC-N Series


EDMY041427 Operation Manual

Split Type Air Conditioners FTKC-N Series 45


Operation Manual EDMY041427

46 Split Type Air Conditioners FTKC-N Series


EDMY041427 Operation Manual

Split Type Air Conditioners FTKC-N Series 47


Operation Manual EDMY041427

48 Split Type Air Conditioners FTKC-N Series


EDMY041427 Operation Manual

Split Type Air Conditioners FTKC-N Series 49


Operation Manual EDMY041427

50 Split Type Air Conditioners FTKC-N Series


EDMY041427 Operation Manual

Split Type Air Conditioners FTKC-N Series 51


Operation Manual EDMY041427

52 Split Type Air Conditioners FTKC-N Series


EDMY041427 Operation Manual

Split Type Air Conditioners FTKC-N Series 53


Operation Manual EDMY041427

54 Split Type Air Conditioners FTKC-N Series


EDMY041427 Operation Manual

Split Type Air Conditioners FTKC-N Series 55


Operation Manual EDMY041427

56 Split Type Air Conditioners FTKC-N Series


EDMY041427 Operation Manual

Split Type Air Conditioners FTKC-N Series 57


Operation Manual EDMY041427

58 Split Type Air Conditioners FTKC-N Series


EDMY041427 Operation Manual

Split Type Air Conditioners FTKC-N Series 59


Operation Manual EDMY041427

60 Split Type Air Conditioners FTKC-N Series


EDMY041427 Operation Manual

Split Type Air Conditioners FTKC-N Series 61


Operation Manual EDMY041427

62 Split Type Air Conditioners FTKC-N Series


EDMY041427 Operation Manual

Split Type Air Conditioners FTKC-N Series 63


Operation Manual EDMY041427

3P363834-9B

64 Split Type Air Conditioners FTKC-N Series


EDMY041427 Optional Accessories

13. Optional Accessories


13.1 Option List
13.1.1 Indoor Unit

Option Name 25/35/50/60 Class


1 Titanium apatite photocatalytic air-purifying filter (without frame) ★ KAF970A46
2 Remote controller loss prevention with chain KKF917A4

Note: ★ Standard accessory

13.1.2 Outdoor Unit

Option Name 25/35 Class 50/60 Class


1 Air direction adjustment grille KPW937B4 KPW945A4
2 Drain plug KKP937A4

Split Type Air Conditioners FTKC-N Series 65


Optional Accessories EDMY041427

13.2 <KPW937B4> Air Direction Adjustment Grille

4P202735-1

66 Split Type Air Conditioners FTKC-N Series


EDMY041427 Optional Accessories

13.3 <KPW945A4> Air Direction Adjustment Grille

3P089958-2C

Split Type Air Conditioners FTKC-N Series 67


Warning Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the user's manual carefully before using this product. The user's manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.

Cautions on product corrosion


1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install
the outdoor unit close to the sea shore, contact your local distributor.

Specifications, designs and other content appearing in this brochure are current as of August 2014 but subject to change without notice.

c All rights reserved

AK