Professional Documents
Culture Documents
Item
Description Warranty
No.
Page 1 of 4
Item
Description Warranty
No.
Page 2 of 4
Item
Description Warranty
No.
Common local control cabinet :- For type of
single-pole circuit breaker, the common local
control cabinet (combined from local control
cubicles of three single - pole circuit breaker)
must be equipped. The common local control
shall allow operating independently
38 -
closing/opening on each phase and operating
simultaneously closing/opening on three phases
of circuit breaker. Common control cabinet with
connecting cables for electrical coupling of
control cabinet with operating mechanism cubicle
on each phase
Aluminium; IP55
39 Control cubicle of Circuit Breaker
protection level
40 Insulating bushing Ceramic, brown
41 Rated capacitive breaking current
42 Number of spare auxiliary contact
Normally opened 12
Normally closed 12
43 Steel structure
Type Yes
Materials Yes
44 Rated times quantities of circuit breaker
Opening time (no-load) ≤36
Closing time (no-load) ≤72
Open-close time (no-load) ≤300
Reclosing time (no-load) ≤350
Close-open time (no-load) <70
45 SF6 gas
SF6 mass for one three-pole circuit breaker 9
Rated SF6 density 0.64Mpa(rel) at 20degC
First threshold of SF6 density 0.54Mpa(rel) at 20degC
Second threshold of SF6 density 0.51Mpa(rel) at 20degC
SF6 gas pressure density gauss Yes
Max. noise level at 3 meters distance due to
46 < 140 db
operation of circuit breaker
1200 daN both upwards and
47 Max. impact load due to circuit breaker operation
downwards
Terminals (Dimensions : Holes - No. , size and 200mm x125mm; 8 holes, 14mm
50
spacing) dia & 50mm spacing
HV Al.
51 Drawings of steel structure Yes
Page 4 of 4