ANNEX 01 - Technical specifications

1. 110kV Circuit Breaker:

Item
Description Warranty
No.

1 Manufacturer/Country of Origin GE T&D INDIA LTD/ INDIA


2 Ordering number GL312F1/4031P
3 Applicable standard IEC62271-100
Outdoor, three-pole
4 Type
operation
5 Number of quench bay per phase 1
6 Insulating medium SF6
7 Rated voltage 145 kV
8 Rated frequency 50 Hz
9 Rated current (In)
Type (Transformer bay) and OHL bay 3150 A
Rated three phase symmetrical short-circuit
10 40 kA rms
breaking current
Rated three phase symmetrical short circuit
11 100 kA peak
making current
12 Rated duration of short-circuits 3
13 Rated Operating Sequence O-0.3sec.-CO -3min -CO
Lightning impulse voltage (1.2/50µs) withstand
14 650 kV peak
to earth
One minute power frequency voltage withstand
15 275 kV rms
to earth 50 Hz
16 First-pole-to-clear factor 1.3

17 Minimum creepage distance >25 mm/kV

18 Operating mechanism Three-pole


19 Operating mechanism drive type Spring
20 Minimum clearance between phases 1391 mm
21 Minimum clearance from phase to earth 1230 mm
22 Operating times: (*)
-Maximum opening time ≤ 60 ms
-Maximum closing time ≤ 72 ms
23 Rated out-of phase breaking current 10 kA
24 Rated line charging breaking current 50 A
25 Rated cable charging breaking current 160 A

Page 1 of 4
Item
Description Warranty
No.

Rated transient recovery voltage for terminal


26 249 kVp
faults (T100)

Rate of rise of the transient recovery voltage at a


27 249 kVp
range of levels up to full fault level
28 Auxiliary power supply
- Voltage for heating and spring charged motor 220 Vac
- Control, tripping voltage 220Vdc ~ (70%-110%) *220Vdc

- Control, closing voltage 220Vdc ~ (85%-110%) *220Vdc


-Total burden of tripping and closing coils for
345 W per coil
three phase
29 Number of tripping coil 2
30 Number of closing coil 1
> 10,000 cycles (closing-
31 Mechanical operation duration(In- class M2)
opening)
Type test for Mechanical operation duration
32 (The contractor must provide type tests to Yes
demonstrate the parameters offered.)
Times tripping of 40kA short circuit current
33 15
without repair
Times tripping of 20kA short circuit current
34 60
without repair
Major inspection and maintenance (interrupter
35 and mechanism unit) shall not be required at less Yes
than 25-year intervals
36 SF6-loss-rate / year < 0,5%

Wiring in control cubicle including :


+Anti-pumping device
+ Local/remote control switch
+ SF6 density meter with alarm/trip contact
37 Yes
+ Auxiliary contact: 12NO & 12NC (minium)
+ Auxiliary contacts for charged spring signal
and motor control
+ Heating and lighting device

Page 2 of 4
Item
Description Warranty
No.
Common local control cabinet :- For type of
single-pole circuit breaker, the common local
control cabinet (combined from local control
cubicles of three single - pole circuit breaker)
must be equipped. The common local control
shall allow operating independently
38 -
closing/opening on each phase and operating
simultaneously closing/opening on three phases
of circuit breaker. Common control cabinet with
connecting cables for electrical coupling of
control cabinet with operating mechanism cubicle
on each phase
Aluminium; IP55
39 Control cubicle of Circuit Breaker
protection level
40 Insulating bushing Ceramic, brown
41 Rated capacitive breaking current
42 Number of spare auxiliary contact
Normally opened 12
Normally closed 12
43 Steel structure
Type Yes
Materials Yes
44 Rated times quantities of circuit breaker
Opening time (no-load) ≤36
Closing time (no-load) ≤72
Open-close time (no-load) ≤300
Reclosing time (no-load) ≤350
Close-open time (no-load) <70
45 SF6 gas
SF6 mass for one three-pole circuit breaker 9
Rated SF6 density 0.64Mpa(rel) at 20degC
First threshold of SF6 density 0.54Mpa(rel) at 20degC
Second threshold of SF6 density 0.51Mpa(rel) at 20degC
SF6 gas pressure density gauss Yes
Max. noise level at 3 meters distance due to
46 < 140 db
operation of circuit breaker
1200 daN both upwards and
47 Max. impact load due to circuit breaker operation
downwards

48 Rated mechanical terminal load kN Please refer OGA drg


49 Total weight of complete circuit breaker Approx 1100 kgs
Page 3 of 4
Item
Description Warranty
No.

Terminals (Dimensions : Holes - No. , size and 200mm x125mm; 8 holes, 14mm
50
spacing) dia & 50mm spacing
HV Al.
51 Drawings of steel structure Yes

Page 4 of 4