LIFT WELL PRESSURIZATION CALCULATION FOR ,48 ACRE NORTH TOWN CHENNAI EKANTA TOWER

TOWER C - (G+17)

Q = 0.839 x A x (ΔP)1/2

Q = Volumetric Flow Rate in M3/Sec.

A = Flow Area in Sq. Mtr.

Pressure Difference Maintained Across the Lift Door in Pascal


ΔP = ( 50 Pascal to be maintained as per NBC-2005)

0.83 = Coefficient

Leakage Area Per Lift Door = 0.065 Sq. Mtr. (As per ASHRAE Handbook of Application)

No. of Floors = Level- Ground Floor to 17th Floor = 17

Total Leakage Area = 0.065x18

= 1.17 Sq.Mtr.

Total Leakage Air Flow (Q) = 0.839 x 1.17 x (50)1/2

= 6.95 M3/Sec.

= 14609 CFM

Say = 15000 CFM / Lift Well

2NOS. Selected Fan Capacity for two Lift Well = 30000 CFM

Fan Static Pressure = 40 MMWG

Calculated Power Consumption (BHP) = 10.53

Calculated Power Consumption (IHP) = 12.11

Selected Motor = 15 HP

Selected Fan Capacity for one Lift Well = 15000 CFM

Fan Static Pressure = 40 MMWG

Calculated Power Consumption (BHP) = 10.53

Calculated Power Consumption (IHP) = 12.11

Selected Motor = 15 HP
LIFT WELL PRESSURIZATION CALCULATION FOR ONE LIT WELL

TOWER-1 to 9 IN ANANDA- (G+15)

Q =

Q =

A =

ΔP =

0.83 =

Leakage Area Per Lift Door =

No. of Floors =

Total Leakage Area =

Total Leakage Air Fow (Q) =

Say =

Selected Fan Capacity for Two Lift Well =

Fan Static Pressure =

Calculated Power Consumption (BHP) =

Selected Motor =
ESSURIZATION CALCULATION FOR ONE LIT WELL

TOWER-1 to 9 IN ANANDA- (G+15)

0.839 x A x (ΔP)1/2

Volumetric Flow Rate in M3/Sec.

Flow Area in Sq. Mtr.

Pressure Difference Maintained Across the Lift Door in Pascal


( 50 Pascal to be maintained as per NBC-2005)

Coefficient

0.051 Sq. Mtr. (As per ASHRAE Handbook of Application)

Level- Ground Floor to 15th Floor = 16

0.051x16

0.816 Sq.Mtr.

0.839 x 0.816 x (50)1/2

4.84 M3/Sec.

10248 CFM

10500 CFM / Lift Well

21000 CFM

40 MMWG

11.05

12.5 HP