PIPE SUPPORTS
PART 1 GENERAL
1.01 SUMMARY
A. Section Includes: Supports for pipe, duct, fittings, valves, and appurtenances.
C. Related Sections:
1. Section 01612 - Seismic Design Requirements.
2. Section 05120 - Structural Steel.
3. Section 09960 - High Performance Coatings.
4. Section 15052 - Basic Piping Materials and Methods.
5. Section 15053 - Seismic Restraints for Piping.
6. Section 15054 - Expansion Control for Piping.
7. Section 15062 - Preformed Channel Pipe Support System.
8. Section 15063 - Non-Metallic Pipe Support System.
D. Inclusion of a specific manufacturer’s name in the Specifications does not mean that
the specific manufacturer’s standard product will be acceptable. Specified
manufacturer’s or other manufacturer’s standard product shall be modified as
required to meet the Specifications.
1.03 DESIGN
A. The CONTRACTOR shall cause the design of the pipe and duct hanger and
support system to be developed in conjunction with preparation of the design of the
seismic restraints and expansion control systems by the design professional
selected in accordance with the provisions of Section 15052.
B. The pipe and duct system drawings specified in Section 15052, shall show the
hanger and support locations as well as the details of the seismic restraints and
expansion control systems.
C. The pipe and duct hanger and support design drawings and calculations shall be
prepared and signed by the design professional and shall bear the design
professional's registration seal.
1.04 SUBMITTALS
A. Shop Drawings: Include schedule, indicating where supports will be installed, where
seismic bracing will be installed, and drawings of pipe and duct support system
components and seismic bracing.
PART 2 PRODUCTS
A. Concrete Inserts for Pipes under 30-Inch Diameter: ANSI/MSS SP-69 Type 18.
Minimum 1,140 pounds capacity with 5/8-inch diameter rod.
1. Manufacturers: One of the following or equal:
a. Anvil, Figure 282.
b. Carpenter and Paterson, Figure CP-109.
B. Concrete Inserts for Pipe 30 Inch Diameter and Larger: Hot-dip galvanized steel
body with 3/4 inch diameter National Coarse zinc plated square nut, anchor insert to
steel concrete reinforcement.
1. Manufacturers: One of the following or equal:
a. Connection Specialties, Inc., Model 6MD350.
J. Brackets: ANSI/MSS SP-69 Type 32 with back plate; rated for 1,500 pounds.
1. Manufacturers: One of the following or equal:
a. Anvil, Figure 195.
b. B-Line Systems, Inc., Figure B3066.
K. Brackets, Heavy Duty: ANSI/MSS SP 69 Type 33 with back plate; rated for
3,000 pounds.
1. Manufacturers: One of the following or equal:
a. Anvil, Figure 199.
b. B-Line Systems, Inc., Figure B3067.
Q. Floor Stand or Stanchion Saddles: ANSI/MSS SP-69 Type 37. Provided with U-bolt
hold down yokes.
1. Manufacturers: One of the following or equal:
a. Anvil, Figure 259.
b. Bergen-Paterson, Part 6652.
c. B-Line Systems, Inc., Figure B3090.
R. Spring Supports:
1. Manufacturers: One of the following or equal:
a. Bergen-Paterson, Part 3200.
b. Anvil, Figure B-268.
Z. Anchor Bolts, Flush Shells, Powder Actuated Fasteners, and Concrete Anchors: As
specified in Section 05120.
2.02 MATERIALS
B. Fasteners:
1. As specified in Section 05120.
PART 3 EXECUTION
3.01 INSTALLATION
A. Properly support, suspend or anchor exposed pipe, duct, fittings, valves, and
appurtenances to prevent sagging, overstressing, or movement of piping and
ducting; and to prevent thrusts or loads on or against connected pumps, blowers,
and other equipment. Not all supports are shown on the Drawings. Provide supports
shown in addition to the requirements herein.
B. Pipe and duct supports shown on the Drawings do not show required seismic
bracing. Provide seismic bracing as required.
F. Do not use stud type powder actuated fasteners for securing metallic conduit or
steel pipe larger than 1 inch to concrete, masonry, or wood.
G. Suspend pipe or duct hangers from hanger rods. Secured with double nuts.
H. Install continuously threaded hanger rods only where indicated on the Drawings.
I. Use adjustable ring hangers; or adjustable clevis hangers, for 6-inch and smaller
diameter pipe.
J. Use adjustable clevis hangers for pipe larger than 6 inches in diameter.
K. Secure pipes with galvanized double nutted U-bolts or suspend pipes from hanger
rods and hangers.
L. Support Spacing:
1. Support 2-inch and smaller piping on horizontal and vertical runs at maximum
5 feet on center, unless otherwise specified.
2. Support larger than 2-inch piping and ducting on horizontal and vertical runs at
maximum 10 feet on center, unless otherwise specified.
3. Support exposed polyvinyl chloride and other plastic pipes at maximum 5 feet
on center, regardless of size.
4. Support tubing, copper pipe and tubing, fiber-reinforced plastic pipe or duct,
and rubber hose and tubing at intervals close enough to prevent sagging
greater than 1/4 inch between supports.
N. Securely anchor plastic pipe, valves, and headers to prevent movement during
operation of valves.
O. Anchor plastic pipe between expansion loops and direction changes to prevent axial
movement through anchors.
P. Provide ductile iron elbows or tees supported from floors with base fittings where
indicated on the Drawings.
Q. Support base fittings with metal supports or when indicated on the Drawings,
concrete piers.
S. Do not use chains, plumbers' straps, wire, or similar devices for permanently
suspending, supporting, or restraining pipes.
T. Support plumbing drainage and vents in accordance with Uniform Plumbing Code.
W. Install insulation shield in accordance with ANSI/MSS SP 69, Type 40. Shield shall
be galvanized steel unless specified elsewhere.
X. Install riser clamps at floor penetrations and where indicated on the Drawings.
3.02 INSTALLATION
B. The design professional shall inspect the completed pipe and duct hanger and
support system before the DISTRICT assumes beneficial occupancy and provide
written certification that the installation conforms to the engineer's design.
C. The certification shall bear the design professional's registration seal and original
signature.
END OF SECTION