tion in the transformer iron increases, the reactance A summary of the above article on the capacitor
decreases and the impedance Ύt will increase. For a motor is as follows:
given voltage this results in a smaller current through 1. The motor has good performance in respect to
the capacitor phase and hence less torque. The power factor, efficiency, starting current, and torques.
general rule that the starting torque of an induction 2. The motor is simple in construction and has no
motor increases as the square of the voltage holds true objectionable commutator or brushes. The rotor can
on a capacitor motor only as long as the iron in the be wound either squirrel cage or polyphase with slip
transformer is not saturated. When the iron becomes rings.
highly saturated the torque may even decrease with 3. The field of appHcation for the capacitor motor is
increasing line voltage. broader and less limited than for any other type of single
[^The saturation of the transformer iron exists only at phase motor.
the starting connection because at the running con 4. The unit takes up more space on account of the
nection the primary winding turns are much greater. capacitor.
Generally the designing engineer is inclined to increase 5. Generally the total unit cost is higher than for
the flux density at starting to the highest possible any other type of single-phase motor. This is probably
limit; however in this case it is not wise to do so because the only factor which may react against its present day
the magnetizing volt-amperes directly reduce the use.
Abridgment of
Synopsis,—When overhead lines carry large short-circuit effects of a variation in each of the five principal variables, cable
currents, the resulting magnetic forces on the conductors are such as size, span length, spacing, tension and current are discussed. A
to cause the cables to be repelled to greater distances than the usual mathematical expression is derived by means of which the maximum
spacings. The elementary principles involved are stated. A movement of conductors in a horizontal plane can be determined
single-phase short circuit is shown to be the one producing the approximately. It has been found possible to set up a miniature
greatest movements. A theoretical calculation of the forces and test with small wire that very closely duplicates to a small scale the
actual experience showed the necessity of making tests to study the movements of a larger conductor. The results indicate that it is
problem. A description of the tests indicates how photographic necessary for moderately large systems to take account of these short-
records of the movements of relatively large cables were obtained. circuit forces in the design of their overhead systems. There is a
The results of over 330 tests are shown by pictures and curves. The large field for research on this subject and more work should be done.
28-112
Feb. 1 9 2 9 PETERSON AND McCRACKEN: OVERHEAD LINE CONDUCTORS 139
ment is more influenced by the average of these impulses mobile headlight bulb was fastened by means of an insu-
than by their instantaneous values. It can be shown lated clamp to the cables at the center of each span.
that the average value of force, in lb. per ft. of con The power for the light was supplied through flexible
ductor, is given, for a single-phase circuit, by the leads from a storage battery. The cameras used to
following formula:' record the movements of the lights were mounted as
0.045 Ρ nearly as possible on a horizontal line from the lights so
^ = ^ 0 ^ (2) no corrections for angularity would have to be made in
scaling distances from the pictures. In order to have a
where / is the effective value of current in each of the record of the time for the cable to reach any point a disk
conductors, D is the distance between conductors in with one or two holes in it was resolved in front of the
feet, and F is the force per ft. lens by means of a synchronous motor. Thus a dotted
The worst condition is a single-phase short circuit line record of the movements of the wire was obtained.
between adjacent conductors. The two currents are The wiring diagram. Fig. 3, shows the equipment
180 deg. out of phase, and the maximum repulsion and connections used for the test.
effect is obtained. The discussion will be limited to By means of the disconnect switches in this circuit,
the single-phase condition. the number of transformers could be varied and there-
For any given type of spacing we ñnd that the prob- fore a variation in .current could be obtained. The
lem contains six independent variables, namely: wire
size, span length, sag (or tension), spacing, current, and aQUCDUCT R?W5R FLANTd
LOS ANGELES Bureau of Po>ver & L/qhf
the length of time the current is flowing. The resulting
mathematical complexity of the problem made advis-
able full scale tests to determine the laws of action.
DESCRIPTION OF TESTS
7Mi. 110ffv. Trsnsm/ssion ^Mi. 110HI/. Transmission Line
The large number of variables made a complete Line
15000Kva^ / hsOOOKva.
experimental determination of values impossible.
1".,
Therefore a set of standard conditions was established ^'Λ^ '^'Ψ^
nrIPinηΓ[πη
8-1000 Kv3.
the variable, time, expressing duration of current, was 35000/2400 Volt
If Transformers
eliminated by leaving the current on long enough for
R Τ ίί
the cable to reach the end of its first throw. The
standard condition was 3/0 cable, 150 ft. span, 12,000 ,—^Ilil2£EL i 2000/5 c.T.
I E-a L
lb. per sq. in. tension, 4 ft. spacing and the highest value
F I G . 3 — W I R I N G DIAGRAM FOR T E S T
of current obtainable from the equipment available
for the test.
The cable sizes tested were No. 2, 3/0, 500,000 cir. circuit was closed through the solenoid operated oil
mils, and 4/0 weather-proof. The spans used were circuit breaker in the 2400-volt circuit and opened by a
150, 300, 450, and 600 ft. The stringing tensions used relay operating the 33-kv. breaker.
were 12,000, 18,000 and 24,000 lb. per sq. in., approxi- RESULTS OF TESTS
mately. The spacings were 2, 4, 8, and 12 ft. Currents Horizontal Spacing. In presenting the results, only
varied from 4000 to about 13,000 amperes. a few of the many pictures t h a t were taken can be
In making the tests two spans were set up and the shown. Complete date obtained from all the tests are
movements of each were measured simultaneously to given in Appendix Β of the complete paper.
save time. Two dead-end H-frame structures were Fig. 4 shows the movements of a 3/0 copper cable on
set up 750 ft. apart. At an intermediate point was a 600 ft. span for three different tests. These pictures
placed another similar structure. By moving this show the variation in the deflection for different values
latter pair of poles, the span lengths were varied. The of current. The distance between the large dots where
cable was dead-ended through suspension type insula- the cable started from is 4 ft. (1.22 m.), so there is an
tors and clamped to pin type insulators at the inter- indication that the cable moved 12.8 ft. (3.91 m.) from
mediate poles. At one end of the line the two cables its initial position with a current of only 7430 amperes.
were connected through an oil switch to the low-voltage The time to reach the point of maximum deflection in
side of the transformers supplying power for the test. Fig. 4 is approximately 1.2 sec. The current was inter
The far ends were short circuited. To obtain the rupted very close to the point of maximum deflection.
highest currents a jumper was placed across the cables This gives the worst condition for the tangling of the
at the end of the first span. cables on the return movement. In the lower picture,
The record of the movement of the wire was made the cable acquired a velocity of 18 ft. (5.49 m.) per sec.
photographically at night. In order to do this, an auto- near the center of its travel. At the end of the throw.
140 PETERSON AND McCRACKEN: OVERHEAD LINE CONDUCTORS J o u r n a l A. I. E. E.
the sag distance was increased to 19.4 ft. (5.91 m.), ical basis and fitting the data as closely as they do,
or nearly 6 ft. (1.83 m.) greater than the initial sag of gives one confidence in their use in extrapolating to
13.5 ft. (4.12 m.). high current values.
Approximately the same general characteristics of In order to reduce the large deflections noted in the
movement were observed for spans of 450, 300 ft. and foregoing curves the use of higher tensions suggests
150 ft. excepting that the maximum deflection and itself. Fig. 15, shows the variation in horizontal move
the time to reach that point was reduced. ment with tension for various span lengths. These
Due to the fact that in the great majority of cases curves indicate that the movement is varying approxi
mately inversely as the square root of the tension. The
movement is therefore not cut down as rapidly as the
sag, which is varying inversely as the tension. Very
high values of tension cannot be used because of other
loadings imposed on the cable by wind and ice in ad
dition to that produced by the magnetic forces.
The effect of spacing is shown in curve form in Fig. 18.
The curves are drawn for a current of 7000 amperes.
Although it can be observed that spacing reduces the
movement of the individual conductor, there is not a
12 \
\
o >
NJ
\ \ 60( 3 F t . S p a η
\
^10
FIG.
DIFFERENT
4—COMPARISON
CURRENTS
OF CONDUCTOR
WITH 3 / 0 C A B L E ,
MOVEMENTS
4 FT. HORIZONTAL
FOR
\ 0 Ft in
SPACING, 6 0 0 F T . S P A N , 1 2 , 8 0 0 L B . PER S Q . I N . T E N S I O N , 13.5
F T . SAG
0
4 8 12 16 20 24 28
28
TENSION IN T H O U S A N D S OF P O U N D S PER SQ. IN.
^>
/
/ Η great change in the total space occupied by the swinging
conductors.
Fig, 22 indicates how the use of heavy conductors will
/ •h
decrease the movements. Fig. 25 is also an example of
J a heavy conductor, b u t is also interesting because it is
representative of conditions on a feeder circuit.
λ Results with Vertical Spacing. In making tests on
^ 0 2 4 6 8 10 12 14 16 18
cables arranged above one another, it is found that the
EFFECTIVE VALUE OF CURRENT IN THOUSANDS OF AMPERES movements are primarily vertical, which leads to a
F I G . 9 — R E L A T I O N B E T W E E N M A X I M U M HORIZONTAL M O V E M E N T confusion of dots, so t h a t only the maximum points
OF CONDUCTORS AND C U R R E N T FOR VARIOUS SPANS
can be determined. The results are therefore best
3 / 0 copper cable, 4 ft. horizontal spacing, approximately 12,500Jb. per presented by means of curves. Only a limited in
sq, in. tension
0—Test points—calculated curve vestigation was made with respect to vertical construc
tion. A few miscellaneous results are shown in Fig. 29
and the sag of the conductors at this point. The and Fig. 31 where the zero ordinate is midway between
results of such calculations and the points obtained by the conductors.
test are shown in Fig. 9. See Appendix C for complete In general the movements for vertical construction
development of formula. The extension of the results are less than for horizontal, except at the higher current
by means of the curves, derived from a purely theoret- values.
Feb. 1929 PETERSON AND McCRACKEN: OVERHEAD LINE CONDUCTORS 141
\
en ζ
O —
\
χ
"A"
2
c
o 80 160 240 320 400 480
CABLE SIZE IN THOUSANDS OF CIRCULAR MILS
FiG. 22—RELATION BETWEEN MAXIMUM HORIZONTAL
M O V E M E N T OF CONDUCTORS AND W I R E SIZE
Four ft. horizontal spacing, approximately 12,500 lb. per sq. in. tension
A—7000 amperes, 600 ft. span. Β—4800 amperes, 600 ft.span. C—
7000 amperes, 150 ft. span
| 8
y 3
1
D
84
/ >
^2
=5
] 0
Β
2 4 6 8 10 12 14
EFFECTIVE VALUE OF CURRENT IN THOUSANDS
OF AMPERES
F I G . 3 1 — R E L A T I O N B E T W E E N M A X I M U M VERTICAL M O V E M E N T
OF CONDUCTORS AND C U R R E N T
would not be economical, as the. advantages due to 2. Present mathematical and experimental data on
diversity, etc., would be lost in excessive line cost. the movements of overhead conductors during short
This leads to the advocation of the idea that a central circuits are very incomplete. A large field exists for
station company should have its total system consist research on this problem.
of several nearly independent, relatively small capacity 3. It would seem t h a t the improvements in system
networks, practically complete in themselves; b u t and line design t h a t can come from a study of this
loosely coupled, that is, coupled through high reactance problem would justify various central station com
to each other for standby service. This reduces the panies in extending and making public the research
short-circuit currents to moderate values, and should on this subject.
lead to a lower cost system.
Acknowledgment is made to Messrs. M. 0 . Bolser,
CONCLUSIONS J. C. Albert, H. H. Cox, C. P. Carman, and R. Martin-
In closing, the following conclusions should be drawn dale, who, as members of the Los Angeles Bureau of
from the results described in the paper: Power and Light Technical Committee, made this in
1. I t is necessary to take account of short-circuit vestigation possible, and contributed many valuable
forces in designing overhead lines. suggestions.
Synopsis,—This paper outlines some important flow-measurement problems and points out the character of electrical apparatus
that may be used with other equipment for measuring flow.