Professional Documents
Culture Documents
1) Dotaciones a Considerar
Departamentos
a)
Cantidad Nº Dot. Máx. Consumo
Depto Tipo Nº Hab Q inst.
Depto Tipo Dormitorios Diaria Máx. Día
[Nº] [Nº] [Nº] [lt/min] [lt/hab/día] [m3/día]
A 75 1 2 60 150 22.5
SubTotal 22.5
SubTotal 0.45
d) Sala de Basura:
Dot. Máx. Consumo
Superf. de
Diaria Máx. Día
Limpieza
[lt/m2/día] [m3/día]
[m2]
15 20 0.30
Total Consumo Maximo Diario: (a+b+c+d) = 25.25 [m3/día]
Bombas-1 1500 268.52 63.00 1.0 0.0 2.2 0.0 1.2 0.0 4.5 3.0 0.3
1-2 1500 268.52 63.00 1.0 2.0 2.2 1.0 1.2 0.0 4.5 0.0 0.3
2-3 1500 268.52 63.00 1.0 1.0 2.2 0.0 1.2 0.0 4.5 0.0 0.3
3-4 1500 268.52 63.00 1.0 1.0 2.2 0.0 1.2 0.0 4.5 1.0 0.3
4-5 1500 268.52 63.00 26.4 2.2 1.0 1.2 4.5 0.3
5-6 1200 230.24 50.00 2.55 1.7 1.0 1.0 3.6 0.3
6-7 900 188.84 50.00 2.55 1.7 1.0 1.0 3.6 0.3
7-8 600 142.81 50.00 2.55 1.7 1.0 1.0 3.6 0.28
8-9 300 88.57 50.00 2.55 1.0 1.7 1.0 3.6 0.3
9-10 300 88.57 50.00 1.0 1.0 1.7 0.0 1.0 0.0 3.6 0.0 0.3
10-11 300 88.57 50.00 0.75 0.0 1.7 0.0 1.0 1.0 3.6 0.0 0.3
11-Rem 60 29.22 19.00 0.8 1.0 0.6 0.0 0.3 0.0 1.1 1.0 0.1
Rem-12 60 29.22 19.00 0.8 1.0 0.6 0.0 0.3 0.0 1.1 1.0 0.1
12-13 60 29.22 19.00 20.6 1.0 0.6 0.0 0.3 0.0 1.1 0.0 0.1
13-14 60 29.22 19.00 2.68 0.0 0.6 0.0 0.3 1.0 1.1 1.0 0.1
14-15 33 25.00 19.00 0.2 0.0 0.6 1.0 0.3 0.0 1.1 1.0 0.1
15-16 25 25.00 19.00 0.6 0.0 0.6 1.0 0.3 0.0 1.1 0.0 0.1
16-17 15 15.00 13.00 2.8 4.0 0.4 0.0 0.2 0.0 0.8 1.0 0.1
Cálculo de la Impulsión
Características Técnicas
(diferencial entre 6 y 12 mca)
Pa (Presion de Conexión o Partida) 69 m.c.a
Pb (Presión de desconección) 79 m.c.a.
Potencia T Potencia T
HP min HP min
7,5 - 15
1-3 1.2 3
15 - 30
3-5 1.5 4
Sobre 30
5-7,5 2 6
Vr = (Qm x T) / 4 = 50 lts
,
Piso 11 a Piso 15 (2 Bombas + 1 de Reserva)
Bombas-1 1500 268.52 63.00 1.0 0.0 2.2 0.0 1.2 0.0 4.5 3.0 0.3
1-2 1500 268.52 63.00 1.0 2.0 2.2 1.0 1.2 0.0 4.5 0.0 0.3
2-3 1500 268.52 63.00 1.0 1.0 2.2 0.0 1.2 0.0 4.5 0.0 0.3
3-4 1500 268.52 63.00 1.0 1.0 2.2 0.0 1.2 0.0 4.5 1.0 0.3
4-5 1500 268.52 63.00 13.7 2.2 1.0 1.2 4.5 0.3
5-6 1200 230.24 50.00 2.55 1.7 1.0 1.0 3.6 0.3
6-7 900 188.84 50.00 2.55 1.7 1.0 1.0 3.6 0.3
7-8 600 142.81 50.00 2.55 1.7 1.0 1.0 3.6 0.28
8-9 300 88.57 50.00 2.55 1.0 1.7 1.0 3.6 0.3
9-10 300 88.57 50.00 1.0 1.0 1.7 0.0 1.0 0.0 3.6 0.0 0.3
10-11 300 88.57 50.00 0.75 0.0 1.7 0.0 1.0 1.0 3.6 0.0 0.3
11-Rem 60 29.22 19.00 0.8 1.0 0.6 0.0 0.3 0.0 1.1 1.0 0.1
Rem-12 60 29.22 19.00 0.8 1.0 0.6 0.0 0.3 0.0 1.1 1.0 0.1
12-13 60 29.22 19.00 20.6 1.0 0.6 0.0 0.3 0.0 1.1 0.0 0.1
13-14 60 29.22 19.00 2.68 0.0 0.6 0.0 0.3 1.0 1.1 1.0 0.1
14-15 33 25.00 19.00 0.2 0.0 0.6 1.0 0.3 0.0 1.1 1.0 0.1
15-16 25 25.00 19.00 0.6 0.0 0.6 1.0 0.3 0.0 1.1 0.0 0.1
16-17 15 15.00 13.00 2.8 4.0 0.4 0.0 0.2 0.0 0.8 1.0 0.1
Cálculo de la Impulsión
Características Técnicas
(diferencial entre 6 y 12 mca)
Pa (Presion de Conexión o Partida) 55 m.c.a
Pb (Presión de desconección) 65 m.c.a.
Potencia T Potencia T
HP min HP min
1-3 1.2 7,5 - 15 3
3-5 1.5 15 - 30 4
5-7,5 2 Sobre 30 6
,
6 a Piso 10 (2 Bombas + 1 de Reserva)
Bombas-1 1598 280.48 63.00 1.0 0.0 2.2 0.0 1.2 0.0 4.5 3.0 0.3
1-2 1598 280.48 63.00 1.0 2.0 2.2 1.0 1.2 0.0 4.5 0.0 0.3
2-3 1598 280.48 63.00 1.0 1.0 2.2 0.0 1.2 0.0 4.5 0.0 0.3
3-4 1598 280.48 63.00 1.0 1.0 2.2 0.0 1.2 0.0 4.5 1.0 0.3
4-5 1598 280.48 63.00 0.9 2.2 1.0 1.2 4.5 0.3
5-6 1200 230.24 50.00 2.55 1.7 1.0 1.0 3.6 0.3
6-7 900 188.84 50.00 2.55 1.7 1.0 1.0 3.6 0.3
7-8 600 142.81 50.00 2.55 1.7 1.0 1.0 3.6 0.28
8-9 300 88.57 50.00 2.55 1.0 1.7 1.0 3.6 0.3
9-10 300 88.57 50.00 1.0 1.0 1.7 0.0 1.0 0.0 3.6 0.0 0.3
10-11 300 88.57 50.00 0.75 0.0 1.7 0.0 1.0 1.0 3.6 0.0 0.3
11-Rem 60 29.22 19.00 0.8 1.0 0.6 0.0 0.3 0.0 1.1 1.0 0.1
Rem-12 60 29.22 19.00 0.8 1.0 0.6 0.0 0.3 0.0 1.1 1.0 0.1
12-13 60 29.22 19.00 20.6 1.0 0.6 0.0 0.3 0.0 1.1 0.0 0.1
13-14 60 29.22 19.00 2.68 0.0 0.6 0.0 0.3 1.0 1.1 1.0 0.1
14-15 33 25.00 19.00 0.2 0.0 0.6 1.0 0.3 0.0 1.1 1.0 0.1
15-16 25 25.00 19.00 0.6 0.0 0.6 1.0 0.3 0.0 1.1 0.0 0.1
16-17 15 15.00 13.00 2.8 4.0 0.4 0.0 0.2 0.0 0.8 1.0 0.1
Cálculo de la Impulsión
Características Técnicas
(diferencial entre 6 y 12 mca)
Pa (Presion de Conexión o Partida) 36 m.c.a
Pb (Presión de desconección) 46 m.c.a.
Potencia T Potencia T
HP min HP min
1-3 1.2 7,5 - 15 3
3-5 1.5 15 - 30 4
5-7,5 2 Sobre 30 6
,
raneo a Piso 5 (2 Bombas + 1 de Reserva)