Professional Documents
Culture Documents
Data Values
Methodology
The pipeline wall thickness should be calculated for the maximum local pressure difference at all points
on the pipeline or pipeline section.
In many cases the the maximum pressure is defined at a reference location (and elevation).
The reference location might be a relief valve, pump/compressor station, wellhead, etc.
The local pressure must be calculated from the reference pressure, fluid density, and relative elevation.
The wall thickness should be calculated for the maximum pressure difference.
Use the calculate local pressure option.
For offshore platforms external pressure is ignored.
The maximum local pressure occurs at the lowest dry point on the pipeline or pipeline section.
For subsea pipelines with internal fluid lighter than the external fluid (eg oil).
The maximum local pressure difference occurs at the highest submerged point on the pipeline or pipeline
section.
For risers the highest submerged point and the lowest dry point is at the water line.
Valves and other fittings should also be specified according for the maximum local pressure difference.
In other cases a fluid flow / fluid pressure analysis has been performed to determine the maximum internal
pressure in the pipeline or pipeline section.
A design pressure can be defined which is >= the maximum pressure in the section.
The wall thickness is designed for the design pressure (minus the external pressure).
Use the user defined local pressure option.
Set the user defined local pressure equal to the design pressure.
Valves and other fittings are also specified according to the design pressure (minus the external pressure).
Calculate Wall Thickness From Pipeline Reference Pressure
Calculate local internal pressure from reference pressure, internal fluid density and local elevation.
Calculate external pressure from internal fluid density and local elevation relative tot he surface.
For wall thickness calculations the lowest surface elevation should be used.
Typically LAT (lowest astronomical tide) minus storm surge.
Variations in fluid density should be accounted for.
Select : Internal Pressure Type = [1] Calculate Local Internal Pressure From Reference Pressure
Input : User Defined Reference Internal Pressure = 11.7e6 [Pa]
Input : Internal Fluid Density = 730 [kg/m^3]
Input : Reference Elevation = 25.4 [m]
Input : Local Elevation = 121.3 [m]
−3
ρf := 730 ⋅ kg ⋅ m Internal Fluid Density
−3
ρe := 1027 ⋅ kg ⋅ m External Fluid Density
∆P ⋅ OD −3
t := t = 6.794405 × 10 m Pressure Design Wall Thickness
2 ⋅ Sd + ∆P
−3
tn := t + tc tn = 9.794405 × 10 m Nominal Wall Thickness
−1
ID := OD − 2tn ID = 3.0421119 × 10 m Nominal Inside Diameter
OD 1
dot := dot = 4.765686 × 10 Diameter Over Pressure Thickness
t
∆P ⋅ ( OD − t) 8
Sh := Sh = 2.7 × 10 Pa Hoop Stress
2⋅ t
Sh 0
sos := sos = 1 × 10 Hoop Stress Ratio
Sd
Select : Hoop Stress Type = [2] Barlow's Equation From Dm Mid Wall Diameter
Select : Pipe Wall Thickness Type = [16] 12 NPS 12.7 mm Wall XS
Select : Wall Thickness Calculation Type = [2] Wall Thickness Specified
−3
t := tn − tc t = 9.7 × 10 m Pressure Design Wall Thickness
OD 1
dot := dot = 2.549606 × 10 Diameter Over Nominal Thickness
tn
∆P ⋅ ( OD − t) 8
Sh := Sh = 1.873892 × 10 Pa Hoop Stress
2⋅ t
Sh −1
sos := sos = 6.940339 × 10 Hoop Stress Ratio
Sd
Calculate Wall Thickness From Inside Diameter : Barlows Equation OD
Select : Hoop Stress Type = [1] Barlow's Equation From OD Outside Diameter
Select : Line Pipe Schedule Type = [1] User Defined Pipe Diameter And Wall Thickness
Select : Line Pipe Diameter Type = [2] User Defined Inside Diameter
Input : User Defined Inside Diameter =0.2905 [m]
Select : Wall Thickness Type = [1] Calculate Wall Thickness
∆P ⋅ ( ID + 2 ⋅ tc) −3
t := t = 6.6395176 × 10 m Pressure Design Wall Thickness
2 ⋅ (Sd − ∆P)
−3
tn := t + tc tn = 9.639518 × 10 m Nominal Wall Thickness
OD 1
dot := dot = 4.665686 × 10 Diameter Over Pressure Thickness
t
∆P ⋅ OD 8
Sh := Sh = 2.7 × 10 Pa Hoop Stress
2⋅ t
Sh −1
sos := sos = 10 × 10 Hoop Stress Ratio
Sd