EXISTING
2S1 I021 1 RD RD 1 I021 X12 1 NEW
CABLE
2S2 I022 2 YL 4C-4mm² YL 2 I022 X12 2 CONDUIT
TRENCH
CT SECONDARY BOX TO
62 2S3 I023 3 BL 344CBN-I02 I 02 BL 3 I023 X12 3 CT MARSHALLING BOX
10
2S4 I024 4 GN GN 4 I024 X12 4
CT05 CT05 EXISTING
NEW
(5LI2CBN-BTA)CBN (5LI1CBN-CEL)CBN CONDUIT
CABLE
3S1 I031 1 RD RD 1 I031 X13 1 TRENCH
3S2 I032 2 YL 4C-4mm² YL 2 I032 X13 2
CT SECONDARY BOX TO
63 3S3 I033 3 BL 344CBN-I03 I 03 BL 3 I033 X13 3 CT MARSHALLING BOX
10
EXISTING
3S4 I034 4 GN GN 4 I034 X13 4 NEW
CABLE
CONDUIT
TRENCH
4S1 I041 1 RD RD 1 I041 X14 1
4S2 I042 2 YL 4C-4mm² YL 2 I042 X14 2
EXISTING CT SECONDARY BOX TO
64 4S3 I043 3 BL 344CBN-I04 I 04 BL 3 I043 X14 3 NEW
CT MARSHALLING BOX
10
CABLE
4S4 I044 4 GN GN 4 I044 X14 4 CONDUIT
TRENCH
PHASE A MARSHALLING BOX
1S1 I051 1 RD RD 1 I051 X11 6
EXISTING
1S2 I052 2 WH 4C-4mm² WH 2 I052 X11 7 NEW
CABLE CT SECONDARY BOX TO
65 1S3 I053 3 BK 344CBN-I05 I 05 BK 3 I053 X11 8 CONDUIT
TRENCH CT MARSHALLING BOX
10
1S4 I054 4 GN GN 4 I054 X11 9
EXISTING
2S1 I061 1 RD RD 1 I061 X12 6 NEW
CABLE
2S2 I062 2 YL 4C-4mm² YL 2 I062 X12 7 CONDUIT
TRENCH
CT SECONDARY BOX TO
66 2S3 I063 3 BL 344CBN-I06 I 06 BL 3 I063 X12 8 CT MARSHALLING BOX
10
2S4 I064 4 GN GN 4 I064 X12 9
CT05 CT05 EXISTING
NEW
(5LI2CBN-BTA)CBN (5LI1CBN-CEL)CBN CONDUIT
CABLE
3S1 I071 1 RD RD 1 I071 X13 6 TRENCH
3S2 I072 2 YL 4C-4mm² YL 2 I072 X13 7
CT SECONDARY BOX TO
67 3S3 I073 3 BL 344CBN-I07 I 07 BL 3 I073 X13 8 CT MARSHALLING BOX
10
EXISTING
3S4 I074 4 GN GN 4 I074 X13 9 NEW
CABLE
CONDUIT
TRENCH
4S1 I081 1 RD RD 1 I081 X14 6
4S2 I082 2 YL 4C-4mm² YL 2 I082 X14 7
EXISTING CT SECONDARY BOX TO
68 4S3 I083 3 BL 344CBN-I08 I 08 BL 3 I083 X14 8 NEW
CT MARSHALLING BOX
10
CABLE
4S4 I084 4 GN GN 4 I084 X14 9 CONDUIT
TRENCH
PHASE B MARSHALLING BOX
1S1 I091 1 RD RD 1 I091 X11 11
EXISTING
1S2 I092 2 WH 4C-4mm² WH 2 I092 X11 12 NEW
CABLE CT SECONDARY BOX TO
69 1S3 I093 3 BK 344CBN-I09 I 09 BK 3 I093 X11 13 CONDUIT
TRENCH CT MARSHALLING BOX
10
1S4 I094 4 GN GN 4 I094 X11 14
EXISTING
2S1 I101 1 RD RD 1 I101 X12 11 NEW
CABLE
2S2 I102 2 YL 4C-4mm² YL 2 I102 X12 12 CONDUIT
TRENCH
CT SECONDARY BOX TO
70 2S3 I103 3 BL 344CBN-I10 I 10 BL 3 I103 X12 13 CT MARSHALLING BOX
10
2S4 I104 4 GN GN 4 I104 X12 14
CT05 CT05 EXISTING
NEW
(5LI2CBN-BTA)CBN (5LI1CBN-CEL)CBN CONDUIT
CABLE
3S1 I111 1 RD RD 1 I111 X13 11 TRENCH
3S2 I112 2 YL 4C-4mm² YL 2 I112 X13 12
CT SECONDARY BOX TO
71 3S3 I113 3 BL 344CBN-I11 I 11 BL 3 I113 X13 13 CT MARSHALLING BOX
10
EXISTING
3S4 I114 4 GN GN 4 I114 X13 14 NEW
CABLE
5 CONDUIT
TRENCH
4S1 I121 1 RD RD 1 I121 X14 11
4S2 I122 2 YL 4C-4mm² YL 2 I122 X14 12
EXISTING CT SECONDARY BOX TO
72 4S3 I123 3 BL 344CBN-I12 I 12 BL 3 I123 X14 13 NEW
CT MARSHALLING BOX
10
CABLE
4S4 I124 4 GN GN 4 I124 X14 14 CONDUIT
TRENCH
PHASE C MARSHALLING BOX
4 GN GN 4 FRP-3
+COMMON
-XR1 1 R061 1 1 R061 -XB1 8
50/51 OVERCURRENT TRIP
-XR1 10 R062 2 2 R062 -XB1 37 50/51N OVERCURRENT TRIP
-XR1 11 R063 3 3 R063 -XB1 38 UNDERFREQUENCY TRIP
-XR1 12 R064 4 4 R064 -XB1 39 AUTORECLOSE NOT READY
69KV FEEDER -XR1 14 R065 5 12C-2.5mm² 5 R065 -XB1 40 FAULT RECORDER NEW AUTORECLOSE SUCCESSFUL
138 PROTECTION -XR1 15 R066 6 344CBN-R06 R 06 6 R066 -XB1 41 PANEL-3 CABLE AUTORECLOSE BLOCK 10
TRENCH
-XR1 16 R067 7 7 R067 -XB1 42 VT FAIL
-XR1 13 R068 8 8 R068 -XB1 43 RELAY FAIL
-XR1 6 R069 9 9 R069 -XB1 44 DC FAIL
-XR1 17 R0610 10 10 R0610 -XB1 45 AC FAIL
-XR1 18 R0611 11 11 R0611 -XB1 46
FRP-3
-XR1 1 R071 1 RD RD 1 R071 -XB1 3 +COMMON
-XR1 10 R072 2 YL YL 2 R072 -XB1 49 BREAKER FAIL START
-XR1 11 R073 3 BL BL 3 R073 -XB1 50 BREAKER FAIL TRIP
BREAKER FAIL -XR1 12 R074 4 GN 8C-2.5mm² GN 4 R074 -XB1 51 AR SUCCESSFUL
FAULT RECORDER NEW
-XR1 13 R075 5 WH 344CBN-R07 WH 5 R075 -XB1 52 AR NOT READY
139 PROTECTION R 07 PANEL-3 CABLE 10
-XR1 14 R076 6 BK BK 6 R076 -XB1 53 TRENCH DEFINITIVE TRIP
BFR(8XC02CBN)
RELAY FAILURE
-XR1 16 R077 7 BR BR 7 R077 -XB1 54
8 OR OR 8 FRP-3
7 BR BR 7
CELCOR-L2 8 OR OR 8 DS05 (5LI2CBN-CEL)
EXISTING TBK 9 C451 1 RD RD 1 C451 TBK1 7 +VE COMMON
8XC02CBN EXISTING
MCSB PANEL TBK 10 C452 2 YL 4C-2.5mm² YL 2 C452 TBK1 8 REM (BCU) CB CLOSING CMD
184 C 45 MCSB CABLE 10
(MODIFIED) TBK 11 C453 3 BL 344CBN-C45 BL 3 C453 TBK1 9 TRENCH REM (BCU) CB OPENING CMD
CELCOR-L2 C454 4 GN GN 4 C454 NEW MCSB
TBK 18 C461 1 RD RD 1 C461 TBK1 10 +VE COMMON
TBK 19 C462 2 YL YL 2 C462 TBK1 11 DS03 REMOTE CLOSING CMD FRM RTU
EXISTING TBK 20 C463 3 BL BL 3 C463 TBK1 12 DS03 REMOTE OPENING CMD FRM RTU
8XC02CBN EXISTING
MCSB PANEL TBK 27 C464 4 GN 8C-2.5mm² GN 4 C464 TBK1 13 +VE COMMON
185 C 46 MCSB CABLE 10
(MODIFIED) TBK 28 C465 5 WH 344CBN-C46 WH 5 C465 TBK1 14 TRENCH DS05 REMOTE CLOSING CMD FRM RTU
TBK 29 C466 6 BK BK 6 C466 TBK1 15 DS05 REMOTE OPENING CMD FRM RTU
7 BR BR 7
CELCOR-L2 8 OR OR 8 NEW MCSB
69kV BUS-1 C471 1 RD RD 1 C471 XC5 6 BUS BAR PROT TRIP FOR TC1 & BLOCK AR
69KV FEEDER NEW EXISTING
PROTECTION C472 2 YL 4C-2.5mm² YL 2 C472 XC5 74C BUS BAR PROT TRIP FOR TC1 & BLOCK AR
186 C 47 PROTECTION CABLE CABLE 25
C473 3 BL 344CBN-C47 BL 3 C473 XC1 4 TRENCH TRENCH TO BUS BAR INITIATE BFP
EXISTING SEL 487B C474 4 GN GN 4 C474 XC1 6 CELCOR-L2 TO BUS BAR INITIATE BFP
69kV BUS-1 C481 1 RD RD 1 C481 XC5 11 BUS BAR PROT TRIP FOR TC2 & BLOCK AR
69KV FEEDER NEW EXISTING
PROTECTION C482 2 YL 4C-2.5mm² YL 2 C482 XC5 75C BUS BAR PROT TRIP FOR TC2 & BLOCK AR
187 C 48 PROTECTION CABLE CABLE 25
C483 3 BL 344CBN-C48 BL 3 C483 XC4 4 TRENCH TRENCH TO BUS BAR INITIATE BFP
EXISTING SEL 487B C484 4 GN GN 4 C484 XC4 6 CELCOR-L2 TO BUS BAR INITIATE BFP
C554 4 4 C554
DS OPEN FOR CB INTERLOCK
EXISTING C555 5 12C-2.5mm² 5 C555
EXISTING
C556 6 344CBN-C55 6 C556 69KV DS NEW
194 MCSB C 55 CONDUIT
CABLE DS CLOSE FOR CB INTERLOCK 170
C557 7 7 C557 TRENCH
C558 8 8 C558
C559 9 9 C559
C5510 10 10 C5510 DS ALARMS
to check if existing cables
C5511 11 11 C5511
are sufficient in length
69kV TR02 C5512 12 12 C5512 5DS03 (8XF02CBN)
C561 1 RD RD 1 C211 X1 4A +VE COMMON (230VAC)
EXISTING EXISTING
C562 2 YL 4C-2.5mm² YL 2 C214 X1 4B 69KV DS NEW FOR DS LOCAL CLOSING/OPENING
195 MCSB to check if existing cables C 56 CONDUIT
CABLE 170
C563 3 BL 344CBN-C56 BL 3 C215 X1 8 TRENCH REM CLOSING CMD
are sufficient in length
69kV TR02 C564 4 GN GN 4 C218 X1 7 5DS05 (8XF02CBN) REM OPENING CMD
C604 4 4 C604
DS OPEN FOR CB INTERLOCK
EXISTING C605 5 12C-2.5mm² 5 C605
EXISTING
C606 6 344CBN-C60 6 C606 69KV DS NEW
199 MCSB C 60 CONDUIT
CABLE DS CLOSE FOR CB INTERLOCK 160
C607 7 7 C607 TRENCH
C608 8 8 C608
C609 9 9 C609
C6010 10 10 C6010 DS ALARMS
to check if existing cables
C6011 11 11 C6011
are sufficient in length
69kV TR01 C6012 12 12 C6012 5DS03 (8XF01CBN)
C611 1 RD RD 1 C611 X1 4A +VE COMMON (230VAC)
EXISTING EXISTING
C612 2 YL 4C-2.5mm² YL 2 C612 X1 4B 69KV DS NEW FOR DS LOCAL CLOSING/OPENING
200 MCSB to check if existing cables C 61 CONDUIT
CABLE 160
C613 3 BL 344CBN-C61 BL 3 C613 X1 8 TRENCH REM CLOSING CMD
are sufficient in length
69kV TR01 C614 4 GN GN 4 C614 X1 7 5DS05 (8XF01CBN) REM OPENING CMD
C621 1 1 C621 X2 5 X2: 7 +VE COMMON
C622 2 2 C622 X2 6 DS CLOSE (DISCREPANCY SW)
C623 3 3 C623 X2 8 DS OPEN (DISCREPANCY SW)
C624 4 4 C624
DS OPEN FOR CB INTERLOCK
C625 5 12C-2.5mm² 5 C625
EXISTING EXISTING
C626 6 344CBN-C62 6 C626 69KV DS NEW
201 MCSB C 62 CONDUIT
CABLE DS CLOSE FOR CB INTERLOCK 160
C627 7 7 C627 TRENCH
C628 8 8 C628
C629 9 9 C629
C6210 10 10 C6210 DS ALARMS
to check if existing cables
C6211 11 11 C6211
are sufficient in length
69kV TR01 C6212 12 12 C6212 5DS05 (8XF01CBN)