You are on page 1of 1
ipecification of CO2 Gas System in the server room Re-gas and service gas bottles in the server room with a CO2 natural gas. The sizes of the cylinders are 118 kg, 20 kg and $9 kg respectively. Ensure that the electronic panel outside the serve room is fully functional with key control for manual and auto. Test the pressure of cylinders if there is any leakage thereof Allow warranty for the work done on cylinders and supplied gas within the period of five years 6. Provide manual for the control panel and a warning signage of CO2 gas elaborating the risks thereof when entering or working in the server room. eee yas important to note that the above systems must be installed according to the South A\tican National Standards for Clean Agent Gaseous Systems (SANS14520) and CO2 Gas Systems (SANS306). Gas Suppression Systems work hand-in-hand with Fire Detection Systems a8 you require a means to trigger (24VDC from panel) a gas discharge. It is important to conduct an Integrity Test in the room to ensure that the gas is contained long enough in the room for it to be sufficient.