Power System Protection Part – VI Dr.Prof.Mohammed Tawfeeq Al-Zuhairi
Line Classification
Distribution: 33 kV and lower
Subtransmission: 33 – 132 kV
Transmission: 132 kV and higher
HV : 132 – 220 kV
EHV: 400 – 750 kV
UHV: 1000 kV and higher
321
Power System Protection Part – VI Dr.Prof.Mohammed Tawfeeq Al-Zuhairi
Fig.1
321
Power System Protection Part – VI Dr.Prof.Mohammed Tawfeeq Al-Zuhairi
321
Power System Protection Part – VI Dr.Prof.Mohammed Tawfeeq Al-Zuhairi
settings.
Fig 2(c)
The disadvantage of this method is that in case of occurrence of fault
near the source (point A for example) a large current will be produced
and is very destructive if not remove quickly. This means that the
heaviest faults are cleared slowly.
The fault current can be calculated as:
321
Power System Protection Part – VI Dr.Prof.Mohammed Tawfeeq Al-Zuhairi
321
Power System Protection Part – VI Dr.Prof.Mohammed Tawfeeq Al-Zuhairi
321
Power System Protection Part – VI Dr.Prof.Mohammed Tawfeeq Al-Zuhairi
The current tap setting CTS and time dial setting TDS are found
according to the following strategies which come from experience:
311
Power System Protection Part – VI Dr.Prof.Mohammed Tawfeeq Al-Zuhairi
Example 1
For the 13.8 kV feeding system shown in Fig.1, determine satisfactory relay settings .
Pertinent system data is provided in Table1.Assume three relays per breaker, one for each
phase ,Fig.2. Consider only 3-phase faults with short circuit MVA = 10. Use the overcurrent
relay whose characteristic is given in Fig.3.
Fig.1
Fig.2
313
Power System Protection Part – VI Dr.Prof.Mohammed Tawfeeq Al-Zuhairi
Table 1.
Bus S in MVA P.F (lag) Breaker CT ratio
2 3 0.8 B2 400/5
3 5 0.8 B3 400/5
Fig.3
312
Power System Protection Part – VI Dr.Prof.Mohammed Tawfeeq Al-Zuhairi
Solution
311
Power System Protection Part – VI Dr.Prof.Mohammed Tawfeeq Al-Zuhairi
311
Power System Protection Part – VI Dr.Prof.Mohammed Tawfeeq Al-Zuhairi
a
b c
Use 2.2 sec. IDMTL characteristic for time multiplier setting (TMS) = 1 according to British
Standard given in the following figure1:
Figure1
Solution :
For PS=100%
311
Power System Protection Part – VI Dr.Prof.Mohammed Tawfeeq Al-Zuhairi
For relay at B:
This relay should respond to fault at C (backup) and respond to fault near B:
Fault at C
For discrimination between & , let the time margin = 0.5 sec
Hence
For fault at C:
311
Power System Protection Part – VI Dr.Prof.Mohammed Tawfeeq Al-Zuhairi
311
Power System Protection Part – VI Dr.Prof.Mohammed Tawfeeq Al-Zuhairi
311