MCB Rating Sensitivity Wire

Electrical Outlets/Receptacle Watts 2 No's Remarks


(A) (mA) (mm )

Maximum 2000W allowed per


All lights(Fluorescent, CFL,
100 10/16 100 2.5 circuit. Upto 1200W with 10A SP
Incandescent)
MCB, above 1200W to maximum
2000W with 16A SP MCB.
LED Light 50 10/16 100 2.5
Can be combined with other
Strip LED light 100 10 100 2.5
lights
Chandelier small 500 10 100 2.5 1
Shall be provided as separate
Chandelier medium 1000 10 100 2.5 1
circuit
Chandelier big 1500 16 100 2.5 1
5max for
20 30 4
radial
Single socket(each socket 200w); Ring Ckt.
200 13A switched socket
13A SSO For
32 30 4
>5&<=10
socket
Same as single socket but
Double socket; 13A DSO 400 20/32 30 4/6
multiply by 2
Garbage Compactor Depends on load 20/25/32 30 6 1 Isolator
GSM Room socket 200 20 30 4 Dedicated socket
FCU 120/240/450/x 20/32 100 4/6 1 Dedicated socket
VAV 120/240/450/x 20 100 4 1 Dedicated socket
Shaver 50 10 100 2.5 1 Dedicated socket
5A socket 300 10 30 2.5
15A S/O socket 500 20 30 4 Dedicated socket
Water Heater >=1500 20 30 4 1 Dedicated socket/DP switch
Cooler 1500-2000 20 30 4 1 Dedicated socket
Washing Machine >=1500 20 30 4 1 Dedicated socket/DP switch
Dish Washer >=1500 20 30 4 1 Dedicated socket/DP switch
Dedicated socket/or with normal
Fridge/Freezer/Refrigerator 500/1000 20 30 4
socket
Bell 50 10 100 2.5 Along with lighting circuit
Mirror Light(other than
100 10 100 2.5 Along with lighting circuit
Washroom)
Mirror Light(in Washroom) 100 10 100 2.5 Along with Shaver circuit
LPG 50 10 100 2.5 Along with lighting circuit
Kitchen Hood 100 10 100 2.5 1 Along with lighting circuit
Fan 100 10 100 2.5 Along with lighting circuit
Exhaust Fan 100 10 100 2.5 Along with lighting circuit
SPUR 300/400 20 100 4 Switched Fuse circuit
Dedicated socket/DP switch with
30mA ELCB. One switch above
Cooker control/Electric cooker >=3000 32/45 30/100 6 1
and one flex 45A fused socket
outlet
Dedicated 15A socket up to
20 4 1 1810W or 1.5TR(ton
refrigeration)
Dedicated Double Pole switch
Room Air-conditioner
100 with flex outlet for other ratings.
(Window AC)
Maximum 2 air conditioners per
phase. If more than 2 air
2
conditioners the load shall be
balanced.
Split AC
Indoor unit 250-450 20 100 4 1 Dedicated socket/DP switch
Outdoor unit Depends on load 20 100 4 1 Dedicated Isolator/DP switch
AHU Depends on load MCCB/Isolator 100 1 Dedicated Isolator
Photo copiers 1200-1500 20 100 4 1 Dedicated socket
Microwave Oven(domestic) 1200-1500 20 100 4 1 Dedicated socket
Television (Medium size)   300 20 30 4 13A switched socket
Computer (without printer)   200 20 30 4 13A switched socket
Computer with printer   700-800 20 30 4 1 13A switched socket
Toaster (domestic) 800-1000 20 30 4 1 13A switched socket
Hand Dryer 20 30 4 1 13A DP switched Fused socket
Domestic Water Pump Load dependent MCCB/Isolator/Starter 30 1 Dedicated Isolator
Irrigation Pump Load dependent MCCB/Isolator/Starter 100 1 Dedicated Isolator
Jacuzzi pump Load dependent MCCB/Isolator/Starter 10 Dedicated Isolator
Underwater Lighting Load dependent 10 Dedicated Isolator
Flood Lighting Load dependent 100/300
Chiller Load dependent MCCB/Isolator 100-1000 1 Dedicated
Elevator/Escalator Load dependent MCCB/Isolator 300/500 1 Dedicated
Neon Sign Load dependent 300 1 Dedicated

CCTV(DVR) 200 20 30 4 Socket to be considered if central


power supply not provided