You are on page 1of 2

AccuForce 12V - 40Ah | VRLA Battery

Specifications
Nominal Voltage 12 V
Number of cells 6
Design Life 10 years
Length 197 mm
Width 165 mm
Dimensions
Height 170 mm
Total Height 170 mm
Approx. Weight 12.8 kg
20 hours rate (2.10 A, 10.8 V) 42.0 Ah
Nominal Capacity (25ºC) 10 hours rate (4.00 A, 10.8 V) 40.0 Ah
5 hours rate (7.00 A, 10.5 V) 35.0 Ah
1 hour rate (24.80 A, 9.6 V) 24.8 Ah
Max. Discharge Current (25ºC) 400 A (5s)
Internal Resistance
8.5 mOhms
Applications Fully Charged battery (25ºC)
Self-Discharge 3% of capacity declined per month at 20ºC (average)
• Uninterruptible Power Supplies (UPS) Discharge : -15ºC~50ºC
• Electric Power Systems (EPS) Operating Temperature Range Charge : -10ºC~50ºC
• Emergency backup power supplies Storage : -20ºC~50ºC
Short Circuit Current 1050 A
• Electronic apparatus and equipment
Boost charging voltage 2.40-2.45 Vpc
• Communication power supplies Maximum charging current 12 A
• DC power supplies Charging Characteristics (25ºC) Temperature compensation -30 mV/ºC
• Auto control system Float charging voltage 2.23-2.27 Vpc
Temperature compensation -18 mV/ºC

Battery Construction
Component Positive Plate Negative Plate Container Cover Safety Valve Terminal Separator Electrolyte
Raw material Lead dioxide Lead ABS ABS Rubber Copper Fiberglass Sulfuric acid

Dimensions
197±2 165±2
170±2

M6

Constant Current Discharge (Amperes) at 25ºC


End Voltage (Volts/Cell) 10min 15min 30min 1h 2h 3h 4h 5h 8h 10h 20h
1.60 V 84.0 66.0 40.0 24.8 14.6 10.2 8.36 7.14 4.90 4.07 2.14
1.65 V 81.5 64.4 39.2 24.4 14.5 10.1 8.31 7.10 4.87 4.06 2.13
1.70 V 78.1 62.0 38.0 23.8 14.4 10.1 8.26 7.05 4.83 4.05 2.13
1.75 V 74.8 59.9 37.1 23.3 14.2 10.0 8.20 7.00 4.80 4.03 2.11
1.80 V 70.6 56.8 35.7 22.6 13.8 9.70 7.95 6.79 4.66 4.00 2.10

Constant Power Discharge (Watts) at 25ºC


End Voltage (Volts/Cell) 10min 15min 30min 1h 2h 3h 4h 5h 8h 10h 20h
1.60 V 907 725 449 283 169 120 98.4 84.4 58.2 48.6 25.7
1.65 V 880 707 440 278 168 119 97.8 83.9 57.8 48.5 25.6
1.70 V 844 681 426 271 167 118 97.1 83.3 57.4 48.4 25.5
1.75 V 807 658 416 266 164 118 96.4 82.7 57.0 48.1 25.4
1.80 V 762 623 401 258 160 114 93.5 80.3 55.3 47.8 25.2
(Note) The above characteristics data are average values obtained within three charge/discharge cycles not the mimimum values.

www.systems-sunlight.com
AccuForce 12V - 40Ah | VRLA Battery
Temperature Effects on Float Life Self Discharge Characteristics
15 110

100

10
2.30V /Cell
90
Life (years)

Capacity (%)
80
5
70

60 o
C o
C o
C
50
0
10 20 30 40 50 40
0 2 4 6 8 10 12 14 16 18 20
Temperature (ºC) Storage Time (Months)

Discharge Characteristics (25ºC) Charging Characteristics (25ºC)


Charged
Volume Current Voltage
(% ) (C A ) (V )
13.0
140 1. Discharge:100%
12.0 2. Charge voltage:2.40V/cell
120 Charged Volume
Battery Voltage (V)

0.25 3. Charge current:0.20C(A)


4. Temperature:25°C
11.0 100 15.0
0.20 Charge Voltage
10.0 80
0.15 14.0
9.00 60
0.10
40 13.0
8.00
20 0.05 Charging Current
7.00 12.0
0 1 2 3 5 10 20 30 60 2 3 5 10 20 30
0 0 0
Min H
2 4 6 8 10 12 14 16 18 20
Discharge Time Charging Time (hours)

Relationship Between Charging Voltage and Temperature Relationship Between OCV and Residual Capacity (25ºC)
14.00

12V
15.6
Open Circuit Voltage (V)

13.00
Battery Voltage (V)

15.0
Cycle
14.4 Use 12.00
Stand
13.8 by Us
e
11.00
13.2

-10 0 10 20 30 40 50 60 10.00
0 20 40 60 80 100
Ambient Temperature (ºC)
Residual Capacity(%)

Cycle Service Life in Relation to Depth of Discharge Temperature Effects on Capacity


120
0.05 C
100
0.1C
C
80 0.25
Capacity (%)
Capacity (%)

1.0C
60

3.0 C
40

20

0
-20 -10 0 10 20 30 40 50
Number of Cycles (Cycles) Temperature (ºC)

SYSTEMS SUNLIGHT S.A.


Headquarters
2 Ermou & Nikis Str., Syntagma Sq.
105 63 Athens, Attica, Greece
T +30 210 6245400 F +30 210 6245409 Global Service Department
European Manufacturing Plant 366 Tatoiou Str.
672 00 Νeo Olvio, Xanthi, Greece 136 73 Acharnes, Αttica, Greece
T +30 25410 48100 F +30 25410 95446 T +30 210 6245600 F +30 210 6245619

www.systems-sunlight.com