HVAC Designs, Inc. // Collection Vol.

Work:
HVAC SYMBOLS
CEILING REGISTER RECTANGULAR THERMOSTAT @ 60"
HORIZONTAL AIR
1 WAY THROW
FMC 603.15
DUCTWORK
FMC SECTION 603
T ABOVE FLOOR
FEC 13-613
HANDLER
MOUNT
CEILING FROM
FLEXIBLE WALL MOUNTED STRUCTURE
REGISTER
2 WAY THROW
DUCTWORK
FMC SECTION 603
H HUMIDISTAT @ 60"
ABOVE FLOOR
FMC SECTIONS
303 --- 312
FMC 603.15

CEILING REGISTER AIR DISTRIBUTION DUCT MOUNTED


BOXES FMC
S SMOKE DETECTOR
DUCTLESS
3 WAY THROW
FMC 603.15 SECTION 603 D FMC SECTION 606
AIR
HANDLER
FMC
CEILING REGISTER RETURN AIR EQUIPMENT SECTIONS
4 WAY THROW PLENUM TRUNK ACCESS PANEL 303 -- 312
FMC 603.15 FMC SECTION 602 FMC SECTION 306

CEILING REGISTER SUPPLY AIR EXHAUST FAN


CORNER THROW PLENUM TRUNK EF-1 or as NOTED PACKAGE UNIT
FMC 603.15 FMC SECTION 602 FMC SECTION 403 SLAB MOUNTED
FMC SECTIONS
WALL REGISTER AIR VOLUME ZONE CONTROL 303 -- 312
2 WAY THROW CONTROL DAMPER ZD AIR DAMPER
FMC 603.15 FMC 603.15 FMC 303 -- 312

FLOOR REGISTER DUCT MOUNTED BYPASS AIR


2 WAY THROW FIRE DAMPER BP DAMPER
FMC 603.15 FMC SECTION 607 FMC 303 -- 312 PACKAGE UNIT
ROOF MOUNTED
DRYER VENT FMC SECTIONS
FLOOR GRILLE 1" UNDERCUT
ROOF / WALL 303 -- 312
FILTER RETURN DOOR
AIR FMC 603.15
D D CAP FMC 504 30 CFM T/A

CEILING GRILLE RANGE VENT TYPICAL


FILTER RETURN ROOF / WALL CAP BRANCH
R R CONDENSING UNIT DUCT
AIR FMC 603.15 FMC 505 - 506
ON SLAB
FMC SECTIONS
WALL GRILLE CONTROL / 303 -- 312
FILTER RETURN REFRIGERANT TYPICAL AIR 8x4 = DEVICE NECK SIZE
AIR FMC 603.15 PIPING FMC 1101
DEVICE
4" = BRANCH DUCT SIZE
CEILING GRILLE CONDENSATE Walk In Closet
32 = AIRFLOW CFM
ADJUSTMENTS
DUCTED T/A DRAIN TO GRASS VERTICAL AIR
FMC 603.15 FMC SECTION 307 HANDLER ON Bedroom
STAND
WALL GRILLE CONDENSATE FMC SECTIONS
303 --- 312
TYPICAL ROOM
DIRECT T/ A TO DRYWELL
FMC 603.15 FMC SECTION 307

AFF = ABOVE FINISH FLOOR CFM = CUBIC FEET / MINUTE EF = EXHAUST FAN PKG = PACKAGE UNIT SF = SUPPLY FAN
AHU = AIR HANDLING UNIT CU = CONDENSING UNIT FPM = FEET PER MINUTE R/A = RETURN AIR T/A = TRANSFER AIR
BP = BYPASS DAMPER DH = DE-HUMIDIFIER MUA = MAKE UP AIR RTU = ROOFTOP UNIT VTE = VENT TO EXTERIOR
BD = BAROMETRIC DAMPER E/A = EXHAUST AIR O/A = OUTSIDE AIR S/A = SUPPLY AIR ZD = ZONE DAMPER

BUILDING AIR BALANCE SCHEDULE


HVAC NOTES
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
1 Class 17 > 3 HRS 797 795 0 255
1 Science 17 > 3 HRS 686 685 0 255 THIS HVAC DDRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING
1 Corridor 1 0 N/A 97 0 0 0 SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH
1 Locker G 0 N/A 51 0 300 0 HVAC SYMBOL, HVAC CONTRACTOR SHOULD REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW.
1 Restroom G 0 N/A 88 0 300 0
1 Restroom B 0 N/A 81 0 300 0
X X X X X X X X ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN
2 Mech 0 > 3 HRS 51 0 0 0 IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT @ DOOR = ONLY 30 CFM OF RELIEF AIR.
2 Locker B 0 N/A 36 0 325 0
2 Restroom 0 N/A 29 0 50 0
1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS.
2 Lobby 0 N/A 535 520 0 0
2 Office 2 > 3 HRS 527 500 0 40
THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007.
2 Reading 17 > 3 HRS 485 460 0 255 2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY
2 Corridor 2 0 N/A 137 0 0 0 REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO
X X X X X X X X INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED.
3 Media 17 > 3 HRS 900 860 0 255
3 Electric 0 N/A 67 67 T/A 0 0
3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE
3 Office 102 1 > 3 HRS 336 620 0 20 GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND
3 Office 101 1 > 3 HRS 412 0 0 20 THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY.
3 Corridor 3 0 N/A 85 0 0 0 4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A
X X X X X X X X
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL
4 Computers 17 > 3 HRS 955 889 0 255
MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL.
4 Break 0 N/A 86 86 T/A 0 0 5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD
4 Office 120 1 > 3 HRS 93 93 T/A 0 20 EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS
4 Office 121 1 > 3 HRS 157 157 0 20 ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL
4 Office 123 1 > 3 HRS 157 157 0 20 DUCTWORK PER UL-181 (VAPOR SEAL + STRAP BOTH DUCT INNER CORE AND DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER
4 Office 125 1 > 3 HRS 174 174 0 20
LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT.
4 Pricipal 1 > 3 HRS 103 103 0 20
4 Office 122 1 > 3 HRS 70 70 T/A 0 20
PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA.
4 Corridor 4 0 N/A 5 0 0 0 PROVIDE BRANCH DUCT VOLUME CONTROL DAMPERS AT ALL ACCESSIBLE BRANCH DUCT TO TRUNKLINE CONNECTIONS, PROVIDE ACCESS TO DAMPERS.
X X X X X X X X 6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107.
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS
5 SERVER 0 N/A 600 405 200 0
FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS.
BUILDING TOTALS 95 > 3 HRS 7800 6325 1475 1475 7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3
INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / DOOR).
22x22,9",263 CFM
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM ) 8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING
Office PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN
BUILDING VENTILATION CALCULATION 6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION.
9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DIAGRAM
TIME CLASSIFICATION OCCUPANTS DURATION MAX. REQ. AIR ADJUSTED AIR TOTAL AIR CFM / PERSON OR SQ FOOT TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN
Lobby PEAK Classrooms 85 1.00 15 15 1275 15 CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE
PEAK Office 10 1.00 20 20 200 20
OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE,
22x22,9",263 CFM BUILDING TOTALS 95 1475 STAND ALONE DEHUMIDIFICATION / HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS.
22x22,9", 266 CFM THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 VENTILATION TABLE MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS
22x22,9", 266 CFM THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM ) TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH BUILDING OWNER.
10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT
SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR CALCULATIONS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER.
HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER.
22x22, 14", -500
EF-3 22x22, 14", -520
VTE

Restroom G Restroom B Mech Locker B 12x16


Reading Media Electric Office 102 Office 101
22x22,8",161 CFM 22x22,9",300 CFM 22x22,5",67 CFM
12x12,7",-125 CFM
Locker G 16x16,9",-300 CFM 16x16,9",-300 CFM
22x22,8",168 CFM
10x10 10x14 10x14 10x12
16x16, 9",-300 CFM 8x4,4",51 CFM 8x4,4",36 CFM 16x16,9",-200 CFM
HVAC SCHEDULES + DETAILS
22x22,5",88 CFM
22x22,5",81 CFM 22x22,9",300 CFM
22x22,8",161 CFM 24x12 22x22,9",206 CFM
14x12 14x12 10x12
6x12
EF-1 Restroom 22x22,8",161 CFM 22x22,9",206 CFM
TRANE EQUIPMENT ENVIRO AIR EQUIPMENT
VTE AIR HANDLER MARK: AHU-1,2,3,4 AIR HANDLER MARK: AHU-5 PIPE COVER - MAY MOUNT INTERIOR
8x4,4",51 CFM 22x22,9",300 CFM 22x22,8",168 CFM UNIT MODEL NUMBER: TWE065E UNIT MODEL NUMBER: ACWH1800
UNIT DIMEN H/W/D: 63X26X21
TYPICAL (x6) 16x16 24x12 NOMINAL A/C TONS : 1.5
UNIT WEIGHT: 218 REFRIGERANT PIPING + CONTROL WIRING
TRANSFER AIR SUPPLY PLENUM SIZE : DUCTLESS
22x22,16",-860 CFM SUPPLY PLENUM SIZE : 24X12 FMC 1101 - MAY ALSO ROUTE BELOW SLAB
GRILLE - WALL / Corridor
24x12 2
RETURN PLENUM SIZE : DUCTLESS
DOOR MOUNT 14x16 RETURN PLENUM SIZE : 24X18
SUPPLY FAN CFM / SP : 600 / .40
300 MAX CFM 24x18 SUPPLY FAN CFM / SP : 1800 / .40
SUPPLY FAN H/P : .35
22x22, 14", -460 24x18 24x12 SUPPLY FAN H/P : 1 CONDENSING UNIT
22x22,14",-620 CFM OUTDOOR AIR CFM: 0 FMC 303
OUTDOOR AIR CFM: 368
10x12 AHU-2 8x4,4",29 CFM
UNIT PHASE / HERTZ: 1 / 60
UNIT VOLTAGE: 200/230/ 1 / 60 WALL
MECH ROOM UNIT DIMEN LWH: 42X12X8 FLOOR FASTENER
UNIT VOLTAGE: 208 / 240
Corridor 1 ABOVE CEILING
AHU-3 HEATER KW: 7.2 / 9.6 UNIT WEIGHT: 29 FMC 301.13
MECH ROOM HEATER BREAKER: 50 / 60 HEATSTRIP KW: 2.5
22x22,6",97 CFM GRADE
AHU-1 Corridor 3 ABOVE CEILING
22x22,5",85 CFM CONDENSER MARK: CU-1,2,3,4 CONDENSER MARK: CU-5 EQUIPMENT SLAB
22x22,7",140 CFM
MECH ROOM AHU-4 NOMINAL A/C TONS : 5 UNIT MODEL NUMBER: CCW18000
ABOVE CEILING
MECH ROOM
ABOVE CEILING
UNIT MODEL NUMBER:
UNIT VOLTAGE:
2TTR4060A
208/230/ 1 / 60
UNIT VOLTAGE: 200/230/ 1 / 60
CONDENSING UNIT DETAIL
Break 24x18 Office 122 Pricipal Office UNIT MCA / BREAKER: 12.5 / 20
22x22,16",-889 CFM Office 120 UNIT MCA / BREAKER: 34 / 50 UNIT DIMEN LWH: 35X12X28
UNIT DIMEN H/W/D: 46.4X35.1X38.7 UNIT WEIGHT: 156
24x12 24x18 24x12 22x22,7",-103 CFM * FRESH REFRIGERANT PIPING + 1/2 THREADED ROD
22x22,5",86 CFM UNIT WEIGHT: 279 TOTAL COOLING BTUH: 18,400 AIR CONTROL WIRING FMC SUSPEND FROM
22x22, 18", -794 22x22,18",-686 TOTAL COOLING BTUH: 61,000 1101
22x22,9",238 CFM SENS. COOLING BTUH: 11,200 DUCT TOP CHORD
SENS. COOLING BTUH: 44,500
LAT. COOLING BTUH: 7,200 FMC 401
TYPICAL (x4) 9" FRESH AIR DUCT 22x22,9",238 CFM 22x22,6",93 CFM LAT. COOLING BTUH: 16,500 AIR HANDLER
TOTAL HEATING BTUH: 17,000
16x12 VTE,FILTER,SET TO 368 CFM TOTAL HEATING BTUH: 34,120 FMC 303
24x12 SEER: 13
22x22, 6",70 CFM SENSIBLE HEAT % 0.73
22x22,6",103 CFM THERMOSTAT MODEL:
SEER: 14
12x16 THERMOSTAT MODEL: T8411R1002 RETURN DUCT
SUPPLY AIR DUCT FMC 601
NOTES: ALTERNATE BRAND EQUIPMENT WITH
FMC 601
10x12 14x12 24x12 14x12 8x12 AUX. DRAIN PAN + FLOAT
EQUAL PERFORMANCE ARE ACCEPTABLE.
22x22,9", -174 CFM SWITCH FMC 301.2.3
22x22,9",199 CFM 22x22,8",171 CFM 22x22,8",171 CFM TRANSFER AIR EF-2 SUBMIT PERFORMANCE DATA FOR APPROVAL.
22x22,9",199 CFM FROM BREAK VTE Server * CEILING CONDENSATE DRAIN FMC 307
14x12 - CORRIDOR
22x22,9",199 CFM 22x22,9",171 CFM HIGH WALL Corridor 4 EXHAUST FAN SCHEDULE
* ACCESS PANEL FMC 306.3 ENCLOSED MECHANICAL
FAN MARK: EF-1 EF-2 EF-3
MANUFACTURER: NUTONE NUTONE GREENHECK ROOM IN ATTIC, R-19
DUCTLESS 22x22,8", -157 CFM MODEL NUMBER: 690 QT-200 CSP-264 INSULATION + SEALED
AIR HANDLER FAN TYPE: EXHAUST EXHAUST INLINE EXHAUST GWB, PROVIDE ACCESS
600 CFM S/A 22x22,8", -157 CFM * = OPTIONAL ITEM, SEE HVAC FLOOR PLAN
600 CFM R/A FAN CFM: 50 200 1225
NO OCCUPANCY TOTAL PRESSURE: 0.25 .25 .5 DRAWING FOR EXACT CONFIGURATION.

22x22,8",171 CFM AHU-5 22x22,7", 157 CFM 22x22,7", 157 CFM 22x22,8", 174 CFM
FAN VOLTAGE: 120/1/60 120/1/60 120 / 1 / 60
22x22,9",199 CFM 22x22,9",238 CFM 22x22,9",238 CFM
WALL MOUNT
FAN AMPERAGE:
FAN DIMEN LWH:
0.5
9X11X8
1.0
14X10X9
7.8
24X14X14
HORIZONTAL AIR HANDLER DETAIL
Class Science Office 121 Office 123 Office 125 DUCT OUTLET SIZE: 3 3.25X10 TO 7 19X8
Computers DUCT INLET SIZE: 12X11 15X11 23X13
FAN WEIGHT: 10 14 59
NOTES: 1,2 1,3 1,2
1 = VENT TO EXTERIOR 3 = WALL SWITH CONTROL
NOTE: AHU-5, CU-5 ARE
OPTIONAL ONLY IF
2 = INTERLOCK WITH LIGHTS x
THIS ROOM IS USED CU-5
CU-1 CU-2 FOR COMPUTER SERVERS ON SLAB CU-3 CU-4
ON SLAB ON SLAB FOR OFFICE - USE 7" S/A ON SLAB
ON SLAB
DUCT AND 22x22 GRILLE
PROJECT NAME: American Youth Academy 6949 w Designed By:
PROJECT ADDRESS: 5903 E 130th Avenue Neil Fimbel
DRAWING DATE
8/26/2008
HVAC
HVAC Designs
PROJECT STATE, ZIP: Temple Terrace Florida
813-885-2258
PERMIT SET DRAWING
North CONDITIONED SQ. FT.: 6949
CLASSIFICATION : Commercial Add + Remodel
FL BERS #884 1 OF 1
SCALE 1/8"=1'-0"
* FRESH
AIR DUCT SUPPLY
AIR DUCT
HVAC NOTES HVAC SYMBOLS
FMC 401
FMC 601 CEILING REGISTER RECTANGULAR THERMOSTAT @ 60"
* CEILING
THIS HVAC DRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING
1 WAY THROW
FMC 603.15
DUCTWORK
FMC SECTION 603
T ABOVE FLOOR
FEC 13-613
HORIZONTAL AIR
HANDLER MOUNT
SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH FROM STRUCTURE
AIR HANDLER HVAC SYMBOL, HVAC CONTRACTOR MUST REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW. CEILING REGISTER FLEXIBLE WALL MOUNTED FMC SECTIONS
FMC 303
ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND
2 WAY THROW
FMC 603.15
DUCTWORK
FMC SECTION 603
H HUMIDISTAT @ 60"
ABOVE FLOOR
303 --- 312

REFRIGERANT COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN
22x22,10",300 CFM PIPING
22x22,10",300 CFM IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT INTERIOR DOOR = ONLY 30 CFM OF RELIEF AIR. CEILING REGISTER AIR DISTRIBUTION DUCT MOUNTED
S
Unit J1 22x22,10",284 CFM + CONTROL
WIRING 1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS.
3 WAY THROW
FMC 603.15
BOXES FMC
SECTION 603 D
SMOKE DETECTOR
FMC SECTION 606
DUCTLESS AIR
FMC 1101 HANDLER
THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007. FMC SECTIONS
2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY CEILING REGISTER RETURN AIR EQUIPMENT 303 -- 312
REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO 4 WAY THROW PLENUM TRUNK ACCESS PANEL
22x22,10",284 CFM AIR HANDLER CONDENSATE
INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE FMC 603.15 FMC SECTION 602 FMC SECTION 306
STAND DRAIN
22x22,10",284 CFM FMC 307 THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED.
22x22,10",284 CFM FLOOR 3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE CEILING REGISTER SUPPLY AIR EXHAUST FAN
B CORNER THROW PLENUM TRUNK EF-1 or as NOTED
Unit J2 GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND
THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY. FMC 603.15 FMC SECTION 602 FMC SECTION 403 PACKAGE UNIT
B * = OPTIONAL ITEM, SEE HVAC FLOOR PLAN SLAB MOUNTED
RELIEF AIR VENT AHU-10A 16" DRAWING FOR EXACT CONFIGURATION. 4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A FMC SECTIONS
22x22,10",300 CFM MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL WALL REGISTER AIR VOLUME ZONE CONTROL
16x16 480 CFM 10" 303 -- 312
16" ON STAND
MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL. 2 WAY THROW CONTROL DAMPER ZD AIR DAMPER
+ BACKDRAFT DAMPER FMC 603.15 FMC 603.15 FMC 303 -- 312
(2) 24x18 R/A - 960 CFM
VERTICAL AIR 5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD
EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS
FLOOR REGISTER DUCT MOUNTED BYPASS AIR
8x4,5",63 CFM 2 STG HANDLER DETAIL ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL
DUCTWORK PER UL-181 (VAPOR SEAL + STRAP BOTH DUCT INNER CORE AND DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER 2 WAY THROW FIRE DAMPER BP DAMPER
PACKAGE UNIT
(2) 9" O/A 22x22,10",300 CFM FMC 603.15 FMC SECTION 607 FMC 303 -- 312
Toilet 10 DUCT @ LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT. ROOF MOUNTED
240 CFM
EF-1 PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA. FMC SECTIONS
FLOOR GRILLE DRYER VENT 303 -- 312
VTE 10' MINIMUM RAIL PROVIDE BRANCH DUCT VOLUME CONTROL DAMPERS AT ALL ACCESSIBLE BRANCH DUCT TO TRUNKLINE CONNECTIONS, PROVIDE ACCESS TO DAMPERS. 1" UNDERCUT DOOR
AHU-10B 12" O/A DUCT FILTER RETURN D ROOF / WALL
FROM PARKING 6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107. D 30 CFM T/A
ON STAND PIPE COVER AIR FMC 603.15 CAP FMC 504
EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS
REFRIGERANT PIPING + CONTROL WIRING FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS.
18x18 +480 CFM O/A CEILING GRILLE RANGE VENT
FMC 1101 7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON FILTER RETURN ROOF / WALL CAP
TYPICAL
30x20 R/A -1200 CFM BRANCH
10" O/A DUCT INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / DOOR). R R FMC 505 - 506 CONDENSING UNIT DUCT
Toilet 9 8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING
AIR FMC 603.15
ON SLAB
8x4,4",47 CFM
AHU-9 18x18 + 400 CFM O/A
FMC SECTIONS
ON STAND CONDENSING UNIT PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN WALL GRILLE CONTROL /
22x22,10",311 CFM 22x22,10",311 CFM FMC 303 6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION. FILTER RETURN REFRIGERANT
303 -- 312 8x4 = DEVICE NECK SIZE
9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DIAGRAM
TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN
AIR FMC 603.15 PIPING FMC 1101 TYPICAL AIR 4" = BRANCH DUCT SIZE
FASTENER DEVICE
RELIEF AIR VENT FMC 301.13 CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE CEILING GRILLE CONDENSATE 32 = AIRFLOW CFM
ADJUSTMENTS
OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE, Walk In Closet
16x16 400 CFM 10" DUCTED T/A DRAIN TO GRASS
16" STAND ALONE DEHUMIDIFICATION / HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS. VERTICAL AIR Bedroom
+ BACKDRAFT DAMPER FMC 603.15 FMC SECTION 307
MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS HANDLER ON STAND
FMC SECTIONS
B
EQUIPMENT
TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH BUILDING OWNER.
10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT
WALL GRILLE CONDENSATE
303 --- 312 TYPICAL ROOM
DIRECT T/ A TO DRYWELL
PLATFORM SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR CALCULATIONS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER. FMC 603.15 FMC SECTION 307
RAISED HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER. THIS DRAWING
PLATFORM WALL IS BASED ON MANUAL J HEAT LOAD CALCULATIONS, FOR DETAILED BUILDING ENVELOPE INFORMATION (INSULATING VALUES, WINDOW ENERGY VALUES) AFF = ABOVE FINISH FLOOR CFM = CUBIC FEET / MINUTE EF = EXHAUST FAN PKG = PACKAGE UNIT SF = SUPPLY FAN
CU-10A FLOOR SEE "TOTAL BUILDING LOAD SUMMARY" FORM, FIELD INSPECT BUILDING ENVELOPE DURING CONSTRUCTION, BE SURE THE BUILDING MATCHES THE FORM. AHU = AIR HANDLING UNIT CU = CONDENSING UNIT FPM = FEET PER MINUTE R/A = RETURN AIR T/A = TRANSFER AIR
BP = BYPASS DAMPER DH = DE-HUMIDIFIER MUA = MAKE UP AIR RTU = ROOFTOP UNIT VTE = VENT TO EXTERIOR
CU-10B BD = BAROMETRIC DAMPER E/A = EXHAUST AIR O/A = OUTSIDE AIR S/A = SUPPLY AIR ZD = ZONE DAMPER

22x22,10",311 CFM 22x22,10",311 CFM 22x22,10",311 CFM


CU-9 Unit I
CONDENSING UNIT DETAIL
CU-6

UNCONDITIONED
LOBBY
CU-7 Unit H 10' MINIMUM
18x18 + 420 CFM O/A FROM PARKING
CU-8
10" O/A DUCT
18x18 +360 CFM O/A
22x22,10",326 CFM
18x18 + 360 CFM O/A 18x18 +480 CFM O/A

22x22,10",326 CFM 10" O/A DUCT


Unit D Unit C Unit B 10" O/A DUCT 22x22,10",300 CFM
Unit G Unit F Unit E Unit A1 22x22,10",300 CFM
22x22,10",312 CFM
22x22,10",312 CFM
12" O/A DUCT

22x22,10",310 CFM

22x22,10",310 CFM
C B
22x22,10",312 CFM
22x22,10",312 CFM 16"
22x22,10",326 CFM 22x22,10",300 CFM
18" 22x22,10",300 CFM
22x22,10",310 CFM 22x22,10",310 CFM
22x22,10",326 CFM
HVAC DUCT SYSTEMS ARE TYPICAL FOR UNITS B,C,D,E,F B
30x20 R/A -1600 CFM
B
16" Unit A2
16" 30x20 R/A -1240 CFM
22x22,10",287 CFM
30x20 R/A - 1240 CFM (2) 24x18 R/A -960 CFM
AHU-2
ON STAND
2 STG AHU-1B 22x22,10",287 CFM
ON STAND
16"
22x22,10",310 CFM B

AHU-6 AHU-5 AHU-4 AHU-3


ON STAND
ON STAND ON STAND (2) 9" O/A @ 240 CFM
ON STAND
AHU-8 AHU-7 22x22,10",312 CFM
AHU-1A
22x22,10",326 CFM ON STAND
22x22,10",326 CFM ON STAND ON STAND

Toilet 3 8x4,4",53 CFM 22x22,10",287 CFM


EF-1 EF-1 Toilet 4 EF-1 EF-1 22x22,10",287 CFM
8x4,4",42 CFM VTE VTE VTE 8x4,4",42 CFM VTE

8x4,4",48 CFM
Toilet 8 Toilet 7 Toilet 6 Toilet 5 Toilet 2 Toilet 1

CU-1A CU-1B
RELIEF AIR VENT RELIEF AIR VENT CU-4 CU-3 CU-2 RELIEF AIR VENT
CU-5 RELIEF AIR VENT
16x16 420 CFM 10" 16x16 360 CFM 10" 16x16 360 CFM 10" 16x16 480 CFM 10"
+ BACKDRAFT DAMPER + BACKDRAFT DAMPER RAISED PLATFORM
+ BACKDRAFT DAMPER + BACKDRAFT DAMPER

BUILDING AIR BALANCE SCHEDULE


ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST / RELIEF AIR CFM FRESH AIR CFM
1 UNIT A1 6 > 3 HRS 1200 960 240 240
X X X X X X X X
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
2 UNIT B 9 > 3 HRS 1558 1240 360 360
2 TOILET 0 N/A 42 0 80 SWITCHED 0
X X X X X X X X
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
3 UNIT C 9 > 3 HRS 1558 1240 360 360 AMERICAN STANDARD SPLIT SYSTEM EQUIPMENT SCHEDULE BUILDING VENTILATION CALCULATION
3 TOILET 0 N/A 42 0 80 SWITCHED 0
X X X X X X X X AIR HANDLER MARK: AHU-1A,1B,10A,10B AHU-2,3,4,5,6,7 AHU-8 AHU-9 TIME CLASSIFICATION OCCS / SF DURATION MAX. REQ. AIR ADJUSTED AIR TOTAL AIR CFM / SF
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM UNIT MODEL NUMBER: 2TEC3F36A 2TEC3F48A 2TEC3F60A 2TEC3F48A PEAK Mechant (usable sq ft) 97 / 13066 1.00 0.3 0.3 3919.8 0.3
4 UNIT D 9 > 3 HRS 1558 1240 360 360 UNIT DIMEN H/W/D: 46.5X24X23.5 59.5X26X23.5 59.5X26X23.5 59.5X26X23.5 BUILDING TOTALS 3920 PROVIDED
4 TOILET 0 N/A 42 0 80 SWITCHED 0
X X X X X X X X UNIT WEIGHT: 125 151 155 151
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 VENTILATION TABLE
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM SUPPLY PLENUM SIZE : 12.02X19.22 12.02X21.22 12.02X21.22 12.02X21.22 THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
5 UNIT E 9 > 3 HRS 1558 1240 360 360 RETURN PLENUM SIZE : 18.07X19.5 18.07X21.5 18.07X21.5 18.07X21.5
5 TOILET 0 N/A 42 0 80 SWITCHED 0
X X X X X X X X SUPPLY FAN CFM / SP : 1200 / .40 1600 / .40 2000 / .40 1600 / .40
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM EXHAUST FAN SCHEDULE SUPPLY FAN H/P : 1/3 1/2 1 1/2
6 UNIT F 9 > 3 HRS 1558 1240 360 360 FAN MARK: EF-1 OUTDOOR AIR CFM: 240 360 420 400
6 TOILET 0 N/A 42 0 80 SWITCHED 0 NUTONE
X X X X X X X X MANUFACTURER: UNIT PHASE / HERTZ: 1 / 60 1 / 60 1 / 60 1 / 60
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM MODEL NUMBER: QT-80 UNIT VOLTAGE: 208 / 240 208 / 240 208 / 240 208 / 240
7 UNIT G 9 > 3 HRS 1552 1240 360 360 FAN TYPE: EXHAUST HEATER KW: 5.76 / 7.68 7.2 / 9.6 7.2 / 9.6 7.2 / 9.6
7 TOILET 0 N/A 48 0 80 SWITCHED 0
X X X X X X X X FAN CFM: 80 HEATER BREAKER: 40 / 45 50 / 60 50 / 60 50 / 60
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM TOTAL PRESSURE: .25 CONDENSER MARK: CU-1A,1B,10A,10B CU-2,3,4,5,6,7 CU-8 CU-9
8 UNIT H 12 > 3 HRS 1958 1600 400 400 FAN VOLTAGE: 120/1/60 NOMINAL A/C TONS : 3 4 5 4
8 TOILET 0 N/A 42 0 80 SWITCHED 0
X X X X X X X X FAN AMPERAGE: .7 UNIT MODEL NUMBER: 2TTR3036A 2TTR3048A 2TTR3060A 2TTR3048A
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM FAN DIMEN LWH: 9X9X6 UNIT VOLTAGE: 208/230/ 1 / 60 208/230/ 1 / 60 208/230/ 1 / 60 208/230/ 1 / 60
9 UNIT I 10 > 3 HRS 1553 1200 400 400 4 UNIT MCA / BREAKER: 18 / 30 25 / 40 32 / 50 25 / 40
DUCT OUTLET SIZE:
9 TOILET 0 N/A 47 0 80 SWITCHED 0 UNIT DIMEN H/W/D: 38X30.1X33 46.4X35.1X38.7 46.4X35.1X38.7 46.4X35.1X38.7
X X X X X X X X DUCT INLET SIZE: 10X10
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM UNIT WEIGHT: 194 273 269 273
FAN WEIGHT: 12
10 UNIT J1 5 > 3 HRS 1137 960 240 240
NOTES: 1,2 TOTAL COOLING BTUH: 34,200 47,000 58,000 47,000
10 TOILET 0 N/A 63 0 80 SWITCHED 0 SENS. COOLING BTUH: 25,400 33,800 40,000 33,800
X X X X X X X X 1 = VENT TO EXTERIOR
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
2 = INTERLOCK WITH LIGHTS LAT. COOLING BTUH: 8,800 13,200 18,000 13,200
11 UNIT A2 6 > 3 HRS 1147 960 240 240 TOTAL HEATING BTUH: 25,590 34,120 34,120 34,120
11 TOILET 0 N/A 53 0 80 SWITCHED 0 SENSIBLE HEAT % 0.74 0.72 0.69 0.72
X X X X X X X X
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM SEER: 13 13 13.5 13 PROJECT NAME: Rose Lake Plaza Phase 2 Designed By: DRAWING DATE
12 UNIT J2 4 > 3 HRS 1200 960 240 240 THERMOSTAT MODEL: T8411R1002 T8411R1002 T8411R1002 T8411R1002 PROJECT ADDRESS: 14400 N Florida Ave Neil Fimbel
9/19/2008 HVAC
HVAC Designs
PROJECT STATE, ZIP: Tampa Florida PERMIT SET DRAWING
BUILDING TOTALS 97 > 3 HRS 18000 14080 3920 3920
NOTES: ALTERNATE BRAND EQUIPMENT WITH EQUAL PERFORMANCE ARE ACCEPTABLE.
SUBMIT PERFORMANCE DATA FOR APPROVAL.
North CONDITIONED SQ. FT.: 13352
813-885-2258
FL BERS R#884 1 OF 1
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 CLASSIFICATION : New Commercial FL BERS C#8508 SCALE 1/8"=1'-0"
CYCLE EQUIPMENT OFF DURING UNOCCUPIED HOURS.
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
HVAC SYMBOLS
CEILING REGISTER RECTANGULAR THERMOSTAT @ 60"
1 WAY THROW
FMC 603.15
DUCTWORK
FMC SECTION 603
T ABOVE FLOOR
FEC 13-613
HORIZONTAL AIR
HANDLER MOUNT
FROM STRUCTURE
CEILING REGISTER FLEXIBLE WALL MOUNTED FMC SECTIONS
2 WAY THROW
FMC 603.15
DUCTWORK
FMC SECTION 603
H HUMIDISTAT @ 60"
ABOVE FLOOR
303 --- 312

CEILING REGISTER AIR DISTRIBUTION DUCT MOUNTED


3 WAY THROW BOXES FMC
S SMOKE DETECTOR
FMC 603.15 SECTION 603 D FMC SECTION 606
DUCTLESS AIR
HANDLER
FMC SECTIONS
CEILING REGISTER RETURN AIR EQUIPMENT 303 -- 312
4 WAY THROW PLENUM TRUNK ACCESS PANEL
FMC 603.15 FMC SECTION 602 FMC SECTION 306

CEILING REGISTER SUPPLY AIR EXHAUST FAN


CORNER THROW PLENUM TRUNK EF-1 or as NOTED
FMC 603.15 PACKAGE UNIT
FMC SECTION 602 FMC SECTION 403
SLAB MOUNTED
FMC SECTIONS
WALL REGISTER AIR VOLUME ZONE CONTROL
303 -- 312
2 WAY THROW CONTROL DAMPER ZD AIR DAMPER
FMC 603.15 FMC 603.15 FMC 303 -- 312

FLOOR REGISTER DUCT MOUNTED BYPASS AIR


2 WAY THROW FIRE DAMPER BP DAMPER
PACKAGE UNIT
FMC 603.15 FMC SECTION 607 FMC 303 -- 312
ROOF MOUNTED
FMC SECTIONS
FLOOR GRILLE DRYER VENT 303 -- 312
1" UNDERCUT DOOR
FILTER RETURN D ROOF / WALL
AIR FMC 603.15 D CAP FMC 504
30 CFM T/A

CEILING GRILLE RANGE VENT TYPICAL


FILTER RETURN ROOF / WALL CAP BRANCH
AIR FMC 603.15 R R FMC 505 - 506 CONDENSING UNIT DUCT
ON SLAB
FMC SECTIONS
WALL GRILLE CONTROL /
FILTER RETURN REFRIGERANT
303 -- 312 8x4 = DEVICE NECK SIZE
AIR FMC 603.15 PIPING FMC 1101 TYPICAL AIR
DEVICE
4" = BRANCH DUCT SIZE

CEILING GRILLE CONDENSATE Walk In Closet


32 = AIRFLOW CFM
ADJUSTMENTS
DUCTED T/A DRAIN TO GRASS
FMC SECTION 307 VERTICAL AIR
FMC 603.15 Bedroom
HANDLER ON STAND
FMC SECTIONS
WALL GRILLE CONDENSATE
303 --- 312 TYPICAL ROOM
8x4,4",13 CFM DIRECT T/ A
FMC 603.15
TO DRYWELL
FMC SECTION 307

M Toilet AFF = ABOVE FINISH FLOOR CFM = CUBIC FEET / MINUTE EF = EXHAUST FAN PKG = PACKAGE UNIT SF = SUPPLY FAN
M Bed Family / Nook / Kitchen
AHU = AIR HANDLING UNIT
BP = BYPASS DAMPER
CU = CONDENSING UNIT
DH = DE-HUMIDIFIER
FPM = FEET PER MINUTE
MUA = MAKE UP AIR
R/A = RETURN AIR
RTU = ROOFTOP UNIT
T/A = TRANSFER AIR
VTE = VENT TO EXTERIOR
BD = BAROMETRIC DAMPER E/A = EXHAUST AIR O/A = OUTSIDE AIR S/A = SUPPLY AIR ZD = ZONE DAMPER
M Bath
10x6,5",77 CFM HVAC NOTES
7" RANGE VTE
10x6,5",77 CFM Dining / Living
8x4,4",43 CFM THIS HVAC DRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING
SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH
HVAC SYMBOL, HVAC CONTRACTOR SHOULD REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW.

12x12,9",-215 CFM 12x8,116 CFM ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND
COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN
12x6,6",106 CFM 12x8,334 CFM IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT @ DOOR = ONLY 30 CFM OF RELIEF AIR.

A
1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS.
M Wic THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007.
2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY
12x8,116 CFM REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO
8x4,4",5 CFM INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE
A THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED.
3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE
18x18, 12",-606 CFM GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND
THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY.

10" Foyer 14" 4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A
Bed 4 MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL

Stair / Otb AHU-1 12x8,8",116 CFM


MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL.
5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD
ABOVE CEILING 10x6,6",89 CFM Powder EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS
ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL
IN SEALED MECH 18x18 R/A DUCTWORK PER UL-181 (STRAP DUCT INNER CORE + VAPOR SEAL, VAPOR SEAL DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER
14" ROOM R-19 ISUL @ CHASE 4" DRYER VTE LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT.
WYE PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA.
12x6,6",106 CFM 12" BYPASS
-500 CFM
12"
PROVIDE BRANCH DUCT VOLUME DAMPERS AT ALL BRANCH DUCT TO TRUNKLINE CONNECTIONS FOR AIR BALANCING, PROVIDE ACCESS TO DAMPERS.
6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107.
EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS
ZD ZD BP 8x4,4",31 CFM
12x12,7",-89 CFM
E
CU-1 FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS.
7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON
ACCESS TO ON SLAB INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / 30" DOOR).
10" 14" ATTIC 8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING
PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN
DUCTS DOWN 12x6,6",113 CFM 14" 8x4,4",24 CFM
6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION.
9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DRAWING
TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN
CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE
A Laundry OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE,
Lav STAND ALONE DEHUMIDIFICATION + HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS.
MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS
8x4,4",35 CFM TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH THE BUILDING OWNER.
10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT
8x4,4",5 CFM SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR BUILDING COMPONENTS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER.
HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER. THIS DRAWING
Bath 2 IS BASED ON MANUAL J HEAT LOAD CALCULATIONS, FOR DETAILED BUILDING ENVELOPE INFORMATION (INSULATING VALUES, WINDOW ENERGY VALUES)
SEE "TOTAL BUILDING LOAD SUMMARY" FORM, FIELD INSPECT BUILDING ENVELOPE DURING CONSTRUCTION, BE SURE THE BUILDING MATCHES THE FORM.

12x12,7",-99 CFM 12x12,7",-91 CFM


HVAC SCHEDULES + DETAILS
TRANE HEAT PUMP

10x6,6",99 CFM
FIRST AIR HANDLER MARK:
UNIT MODEL NUMBER:
AHU-1
2TEC3F48A * FRESH
AIR
REFRIGERANT PIPING
+ CONTROL WIRING
1/2 THREADED ROD
SUSPEND FROM
PIPE COVER - MAY MOUNT INTERIOR

FLOOR
UNIT DIMEN H/W/D: 59.5X26X23.5 FMC 1101 TOP CHORD
DUCT
UNIT WEIGHT: 151 FMC 401
SUPPLY PLENUM SIZE : 12.02X21.22 REFRIGERANT PIPING + CONTROL WIRING AIR HANDLER
FMC 1101 - MAY ALSO ROUTE BELOW SLAB FMC 303
RETURN PLENUM SIZE : 18.07X21.5
SUPPLY FAN CFM / SP : 1600 / .40
SUPPLY FAN H/P : 1/2 CONDENSING UNIT RETURN DUCT SUPPLY AIR DUCT FMC 601
10x6,6",91 CFM OUTDOOR AIR CFM: 0
WALL
FMC 303 FMC 601

SECOND UNIT PHASE / HERTZ:


UNIT VOLTAGE:
HEATER KW:
1 / 60
208 / 240
7.2 / 9.6
FLOOR FASTENER
FMC 301.13
* CEILING
AUX. DRAIN PAN + FLOAT
SWITCH FMC 301.2.3
CONDENSATE DRAIN FMC 307

FLOOR HEATER BREAKER:


CONDENSER MARK:
50 / 60
CU-1
EQUIPMENT SLAB
GRADE
* ACCESS PANEL FMC 306.3

NOMINAL A/C TONS : 4 CONDENSING UNIT DETAIL * = OPTIONAL ITEM, SEE HVAC FLOOR PLAN
UNIT MODEL NUMBER: 2TWR3048A
DRAWING FOR EXACT CONFIGURATION.
Bed2 3
Bed UNIT VOLTAGE:
UNIT MCA / BREAKER:
208/230/ 1 / 60
25 / 40
UNIT DIMEN H/W/D: 46.4X35.1X38.7 TRI - BOX REDUCER - BOX
UNIT WEIGHT: 279 W
HORIZONTAL AIR HANDLER DETAIL
TOTAL COOLING BTUH: 46,000 W
SENS. COOLING BTUH: 33,200 H
H
LAT. COOLING BTUH: 12,800
L L
TOTAL HEATING BTUH: 43,500
SENSIBLE HEAT % 0.72 * W2

SEER / HSPF : 13 / 8.4


BOX DIMENSIONS - INCHES
THERMOSTAT MODEL: PROGRAM MARK W H L W2
NOTES: ALTERNATE BRAND EQUIPMENT WITH
EQUAL PERFORMANCE ARE ACCEPTABLE. A 13 13 18 N/A
ZONING SHOWN PER MANUAL J
B 17 17 18 N/A
C 21 21 18 N/A
EXHAUST FAN SCHEDULE
D 13 13 18
FAN MARK:
MANUFACTURER:
EF-1
NUTONE E 17 17 18
*
MODEL NUMBER: 690
F 21 21 18
*
FAN TYPE:
FAN CFM:
EXHAUST
50
*
TOTAL PRESSURE: 0.25 * = CAP SIZE EQUALS OUTLET DUCT + 1"

FAN VOLTAGE: 120/1/60


FAN AMPERAGE: 0.5
FAN DIMEN LWH: 9X11X8
DUCT OUTLET SIZE: 3
DUCT INLET SIZE: 12X11
FAN WEIGHT: 10
NOTES: 1,2
1 = VENT TO EXTERIOR
2 = INTERLOCK WITH LIGHTS
x
North
PROJECT NAME: HDS Model Residence 1964 s Designed By: DRAWING DATE
PROJECT ADDRESS: Neil Fimbel 9/12/2008
HVAC
PROJECT STATE, ZIP: HVAC Designs Permit Set DRAWING
CONDITIONED SQ. FT.: 1991 813-885-2258
CLASSIFICATION : New Residence FL BERS R#884 SCALE 1/4"=1'-0"
1 OF 1
HVAC SYMBOLS
CEILING REGISTER RECTANGULAR THERMOSTAT @ 60"
1 WAY THROW
FMC 603.15
DUCTWORK
FMC SECTION 603
T ABOVE FLOOR
FEC 13-613
HORIZONTAL AIR
HANDLER MOUNT
FROM STRUCTURE
CEILING REGISTER FLEXIBLE WALL MOUNTED FMC SECTIONS
2 WAY THROW
FMC 603.15
DUCTWORK
FMC SECTION 603
H HUMIDISTAT @ 60"
ABOVE FLOOR
303 --- 312

CEILING REGISTER AIR DISTRIBUTION DUCT MOUNTED


3 WAY THROW BOXES FMC
S SMOKE DETECTOR
FMC 603.15 SECTION 603 D FMC SECTION 606
DUCTLESS AIR
HANDLER
FMC SECTIONS
CEILING REGISTER RETURN AIR EQUIPMENT 303 -- 312
4 WAY THROW PLENUM TRUNK ACCESS PANEL
FMC 603.15 FMC SECTION 602 FMC SECTION 306

CEILING REGISTER SUPPLY AIR EXHAUST FAN


CORNER THROW PLENUM TRUNK EF-1 or as NOTED
FMC 603.15 PACKAGE UNIT
FMC SECTION 602 FMC SECTION 403
SLAB MOUNTED
FMC SECTIONS
WALL REGISTER AIR VOLUME ZONE CONTROL
303 -- 312
2 WAY THROW CONTROL DAMPER ZD AIR DAMPER
FMC 603.15 FMC 603.15 FMC 303 -- 312

FLOOR REGISTER DUCT MOUNTED BYPASS AIR


2 WAY THROW FIRE DAMPER BP DAMPER
Cooler FMC 603.15 FMC SECTION 607 FMC 303 -- 312
PACKAGE UNIT
ROOF MOUNTED
FMC SECTIONS
FLOOR GRILLE DRYER VENT 303 -- 312
1" UNDERCUT DOOR
FILTER RETURN D ROOF / WALL
AIR FMC 603.15 D CAP FMC 504
30 CFM T/A

CEILING GRILLE RANGE VENT TYPICAL


FILTER RETURN ROOF / WALL CAP BRANCH
AIR FMC 603.15 R R FMC 505 - 506 CONDENSING UNIT DUCT
ON SLAB
FMC SECTIONS
WALL GRILLE CONTROL /
FILTER RETURN REFRIGERANT
303 -- 312 8x4 = DEVICE NECK SIZE
AIR FMC 603.15 PIPING FMC 1101 TYPICAL AIR
DEVICE
4" = BRANCH DUCT SIZE

CEILING GRILLE CONDENSATE Walk In Closet


32 = AIRFLOW CFM
ADJUSTMENTS
DUCTED T/A DRAIN TO GRASS
FMC SECTION 307 VERTICAL AIR
FMC 603.15 Bedroom
HANDLER ON STAND
FMC SECTIONS
WALL GRILLE CONDENSATE
303 --- 312 TYPICAL ROOM
DIRECT T/ A TO DRYWELL
FMC 603.15 FMC SECTION 307
(2) 22x22, 16", -920 CFM EA
AFF = ABOVE FINISH FLOOR CFM = CUBIC FEET / MINUTE EF = EXHAUST FAN PKG = PACKAGE UNIT SF = SUPPLY FAN
AHU = AIR HANDLING UNIT CU = CONDENSING UNIT FPM = FEET PER MINUTE R/A = RETURN AIR T/A = TRANSFER AIR
BP = BYPASS DAMPER DH = DE-HUMIDIFIER MUA = MAKE UP AIR RTU = ROOFTOP UNIT VTE = VENT TO EXTERIOR
BD = BAROMETRIC DAMPER E/A = EXHAUST AIR O/A = OUTSIDE AIR S/A = SUPPLY AIR ZD = ZONE DAMPER

Kitchen
HVAC NOTES
22x22,10",320 CFM 22x22,10",320 CFM THIS HVAC DDRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING
SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH
HVAC SYMBOL, HVAC CONTRACTOR SHOULD REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW.

ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND
COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN
IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT @ DOOR = ONLY 30 CFM OF RELIEF AIR.

1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS.
THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007.
2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY
REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO
INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE
THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED.
12x12 12x12 3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE
GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND
24x12 THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY.
4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A
MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL
MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL.
RTU-1 5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD
EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS
ON ROOF ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL
DUCTWORK PER UL-181 (VAPOR SEAL + STRAP BOTH DUCT INNER CORE AND DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER
LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT.
PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA.
PROVIDE BRANCH DUCT VOLUME CONTROL DAMPERS AT ALL ACCESSIBLE BRANCH DUCT TO TRUNKLINE CONNECTIONS, PROVIDE ACCESS TO DAMPERS.
22x22,10",320 CFM 6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107.
EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS
22x22,10",320 CFM FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS.
7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON
INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / DOOR).
8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING
PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN
6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION.
9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DIAGRAM
TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN
CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE
OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE,
KITCHEN HOOD STAND ALONE DEHUMIDIFICATION / HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS.
BY OTHERS 380 MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS
TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH BUILDING OWNER.
CFM MUA BY
BUILDING AIR BALANCE SCHEDULE A/C EQUIPMENT
10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT
SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR CALCULATIONS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER.
HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER.
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
1 COOLER ROOM 0 N/A 78 0 0 0 CONDENSATE DRAIN
1 KITCHEN 5 > 3 HRS 1922 1840 380 CFM @ HOOD 160 TO GUTTER / GRASS
X X X X X X X X TYPICAL OF 2
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
2 RESTROOM 0 N/A 18 0 50 INTERMITTENT 0 22x22,10",320 CFM HVAC SCHEDULES + DETAILS
2 ORDER / CASHIER 9 VARIES 1582 1380 0 220 22x22,10",320 CFM
X X X X X X X X ROOFTOP EQUIPMENT SCHEDULE
BUILDING TOTALS 14 VARIES 3600 3220 380 380
RTU-2 PACKAGE UNIT MARK:
UNIT MANUFACTURER:
RTU-1
TRANE
RTU-2
EXISTING
DUCT
EQUIPMENT
EXISTING UNIT MODEL NUMBER: THC063A3 THC043A3 CURB CONNECTION
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 CONNECTION
ON ROOF NOMINAL A/C TONS : 5 4 CONNECTION
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM ) UNIT CONFIGURATION: DOWNFLOW DOWNFLOW ROOFTOP MASTIC
UNIT DIMEN H/W/D: 37X45X70 37X45X70 EQUIPMENT SEAL
UNIT WEIGHT: 682 669 CURB
BUILDING VENTILATION CALCULATION SUPPLY PLENUM SIZE : 17X15 17X15
3/8 BOLT
@ 18" O.C. 1/2"
ROOFTOP
EQUIPMENT
3/8"
SCREWS
20x12 RETURN PLENUM SIZE : 23X14 23X14 SCREWS 1/4" PLATE
TIME CLASSIFICATION OCCUPANTS DURATION MAX. REQ. AIR ADJUSTED AIR TOTAL AIR CFM / PERSON OR SQ FOOT Restroom SUPPLY FAN CFM / SP : 2000 / .4 1600 / .4
ROOF
JOIST DUCT
@ 8" O.C. OR ANGLE
CURB @ 18"" O.C.
SUPPLY FAN H/P : 1 1
PEAK Dining / Order 9 1.00 20 20 180 20
PEAK HOOD MUA 0 1.00 125 125 125 0 EF-1 OUTDOOR AIR CFM:
UNIT PHASE / HERTZ:
160
3/60
220
3/60
2" U CHANNEL X
1/4" THK
SPAN 3 JOISTS
PEAK Kitchen / Prep 5 1.00 15 15 75 15 VTE 22x22, 16" UNIT VOLTAGE: 208/230 208/230
UNIT MCA: 28.8 22.6
BUILDING TOTALS 14 380 8x4,4",18 CFM -1380 CFM UNIT MAX BREAKER: 40 35 ROOFTOP
EQUIPMENT
HEATER KW: 9/12 9/12 FMC 303
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 VENTILATION TABLE 22x22, 10",316 CFM HEATER MCA: 37.5/42.4 37.5/42.4
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM ) HEATER BREAKER: 45/45 40/45
TOTAL COOLING BTUH: 62,400 49,800
R/A S/A CURB
SENS. COOLING BTUH: 47,300 39,400 DUCT DUCT
LAT. COOLING BTUH: 15,100 10,400 FMC FMC
TOTAL HEATING BTUH: 40,944 40,944 601 601
SENS. HEAT % 0.76 0.79
MECHANICALLY FASTEN CURB TO ROOF STRUCTURE FOR 140 M.P.H. WIND LOAD
22x22, 10",316 CFM COOLING EFFICIENCY: 13 13 MECHANICALLY FASTEN AND SEAL DUCTS PER FMC SECTIONS 603 AND 604
THERMOSTAT MODEL: T8411R1002 T8411R1002 MECHANICALLY FASTEN EQUIPMENT TO CURB FOR UP TO 140 M.P.H. WIND LOAD
NOTES: ALTERNATE BRAND EQUIPMENT WITH
18x12
EQUAL PERFORMANCE ARE ACCEPTABLE.
SUBMIT PERFORMANCE DATA FOR APPROVAL.
ROOFTOP PACKAGE UNIT DETAIL
EXHAUST FAN SCHEDULE
FAN MARK: EF-1
22x22, 10",316 CFM MANUFACTURER: NUTONE
MODEL NUMBER: 690
FAN TYPE: EXHAUST
FAN CFM: 50
TOTAL PRESSURE: 0.25
FAN VOLTAGE: 120/1/60
FAN AMPERAGE: 0.5
FAN DIMEN LWH: 9X11X8
DUCT OUTLET SIZE: 3
Order - Cashier DUCT INLET SIZE: 12X11
FAN WEIGHT: 10
22x22, 10",316 CFM 22x22, 10",316 CFM NOTES: 1,2
1 = VENT TO EXTERIOR
x
North 2 = INTERLOCK WITH LIGHTS

PROJECT NAME: Marcos Pizza Renov Boynton Beach 1320 e Designed By: DRAWING DATE
PROJECT ADDRESS: Neil Fimbel 8/14/2008
HVAC
PROJECT STATE, ZIP: Boynton Beach Florida, 33461 HVAC Designs Permit Set DRAWING
CONDITIONED SQ. FT.: 1320 813-885-2258
CLASSIFICATION : Restaurant Renovation FL BERS #884 SCALE 1/4"=1'-0"
1 OF 1
BUILDING AIR BALANCE SCHEDULE
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
HVAC SYMBOLS
1 Office 1 > 3 HRS 256 256 0 20 CEILING REGISTER RECTANGULAR THERMOSTAT @ 60"
1 Exam 1 VARIES 147 147 0 15
1 WAY THROW
FMC 603.15
DUCTWORK
FMC SECTION 603
T ABOVE FLOOR
FEC 13-613
HORIZONTAL AIR
HANDLER MOUNT
1 Exam 1 VARIES 261 261 0 15
FROM STRUCTURE
1 Reception 1 > 3 HRS 304 304 0 20 CEILING REGISTER FLEXIBLE WALL MOUNTED FMC SECTIONS
1
1
Restroom
Restroom
0
0
N/A
N/A
38
31
0
0
90
90
0
0
2 WAY THROW
FMC 603.15
DUCTWORK
FMC SECTION 603
H HUMIDISTAT @ 60"
ABOVE FLOOR
303 --- 312

1 Exam 1 VARIES 94 94 0 10
CEILING REGISTER AIR DISTRIBUTION DUCT MOUNTED
1 Consult 1 > 3 HRS 37 37 T/A 0 20
BOXES FMC
S SMOKE DETECTOR
3 WAY THROW
1 Exam 1 VARIES 64 64 0 15 FMC 603.15 SECTION 603 D FMC SECTION 606
DUCTLESS AIR
1 Exam 1 VARIES 64 64 0 15 HANDLER
FMC SECTIONS
1 Lab 0 VARIES 39 39 T/A 0 0 CEILING REGISTER RETURN AIR EQUIPMENT 303 -- 312
1 Work Stations 0 VARIES 665 680 0 0 4 WAY THROW PLENUM TRUNK ACCESS PANEL
X X X X X X X X FMC 603.15 FMC SECTION 602 FMC SECTION 306
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
2 Break 2 VARIES 243 243 0 15 CEILING REGISTER SUPPLY AIR EXHAUST FAN
CORNER THROW PLENUM TRUNK EF-1 or as NOTED
2 Waiting 20 VARIES 1389 1292 0 75 PACKAGE UNIT
FMC 603.15 FMC SECTION 602 FMC SECTION 403
2 Reception 2 > 3 HRS 335 335 0 40 SLAB MOUNTED
2 P Restroom 0 N/A 10 0 90 0 FMC SECTIONS
WALL REGISTER AIR VOLUME ZONE CONTROL
303 -- 312
2 E Restroom 0 N/A 23 0 90 0 2 WAY THROW CONTROL DAMPER ZD AIR DAMPER
X X X X X X X X FMC 603.15 FMC 603.15 FMC 303 -- 312
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
3 Office 1 > 3 HRS 118 118 0 20 FLOOR REGISTER DUCT MOUNTED BYPASS AIR
3 Exam 1 VARIES 124 124 0 20 2 WAY THROW FIRE DAMPER BP DAMPER
PACKAGE UNIT
FMC 603.15 FMC SECTION 607 FMC 303 -- 312
3 Exam 1 VARIES 100 100 0 20 ROOF MOUNTED
3 Reception 1 > 3 HRS 108 119 0 20 FMC SECTIONS
FLOOR GRILLE DRYER VENT 303 -- 312
3 Corridor 0 N/A 83 0 0 0 1" UNDERCUT DOOR
FILTER RETURN D ROOF / WALL
3 Exam 1 VARIES 120 120 0 20 D 30 CFM T/A
AIR FMC 603.15 CAP FMC 504
3 Exam 1 VARIES 99 99 0 20
3 Restroom 0 N/A 24 0 90 0 CEILING GRILLE RANGE VENT TYPICAL
3 Restroom 0 N/A 24 0 90 0 FILTER RETURN ROOF / WALL CAP BRANCH
AIR FMC 603.15 R R FMC 505 - 506 CONDENSING UNIT DUCT
X X X X X X X X ON SLAB
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM FMC SECTIONS
WALL GRILLE CONTROL /
4 Reception 1 > 3 HRS 253 253 0 20
FILTER RETURN REFRIGERANT
303 -- 312 8x4 = DEVICE NECK SIZE
4 Waiting 4 VARIES 514 427 0 100
4 U Restroom 0 N/A 21 0 90 0
AIR FMC 603.15 PIPING FMC 1101 TYPICAL AIR
DEVICE
4" = BRANCH DUCT SIZE

4 Storage 0 N/A 12 12 T/A 0 0 CEILING GRILLE CONDENSATE 32 = AIRFLOW CFM


ADJUSTMENTS
X X X X X X X X Walk In Closet
DUCTED T/A DRAIN TO GRASS
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM FMC 603.15 FMC SECTION 307 VERTICAL AIR Bedroom
HANDLER ON STAND
5 Exam 1 VARIES 89 89 0 15 FMC SECTIONS
5 Office 1 > 3 HRS 130 130 0 20 WALL GRILLE CONDENSATE
303 --- 312 TYPICAL ROOM
DIRECT T/ A TO DRYWELL
5 Corridor 0 N/A 257 127 0 0 FMC 603.15 FMC SECTION 307
5 Exam 1 VARIES 101 101 0 15
5 Exam 1 VARIES 89 89 0 15 AFF = ABOVE FINISH FLOOR CFM = CUBIC FEET / MINUTE EF = EXHAUST FAN PKG = PACKAGE UNIT SF = SUPPLY FAN
5 Exam 1 VARIES 105 105 0 15 AHU = AIR HANDLING UNIT CU = CONDENSING UNIT FPM = FEET PER MINUTE R/A = RETURN AIR T/A = TRANSFER AIR
5 Waiting 20 VARIES 1229 1229 0 50 BP = BYPASS DAMPER DH = DE-HUMIDIFIER MUA = MAKE UP AIR RTU = ROOFTOP UNIT VTE = VENT TO EXTERIOR
BD = BAROMETRIC DAMPER E/A = EXHAUST AIR O/A = OUTSIDE AIR S/A = SUPPLY AIR ZD = ZONE DAMPER
BUILDING TOTALS 68 VARIES 7600 6970 630 630
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3
CALCULATIONS BASED ON ASHRAE 62.1 - 2007 TABLE 6-1 - PROCEDURE PROVIDES VENTILATION FOR VARIABLE / INTERMITTENT OCCUPANTS HVAC NOTES
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )

THIS HVAC DRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING
BUILDING VENTILATION CALCULATION SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH
TIME CLASSIFICATION OCCUPANTS DURATION MAX. REQ. AIR ADJUSTED AIR TOTAL AIR CFM / PERSON HVAC SYMBOL, HVAC CONTRACTOR MUST REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW.

PEAK Office 8 1.00 20 20 160 20 ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND
PEAK Waiting 47 0.50 15 7.5 352.5 7.5 COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN
PEAK Exam Office 13 0.50 15 7.5 97.5 7.5 IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT INTERIOR DOOR = ONLY 30 CFM OF RELIEF AIR.
BUILDING TOTALS 68 610 (630 provided) 1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS.
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 VENTILATION TABLE THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007.
CALCULATIONS BASED ON ASHRAE 62.1 - 2007 TABLE 6-1 - PROCEDURE PROVIDES VENTILATION FOR VARIABLE / INTERMITTENT OCCUPANTS 2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY
REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM ) INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE
THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED.
3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE
GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND
THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY.
Exam 4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A
Exam
22x22,6",120 CFM MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL
Reception MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL.
5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD
22x22,9",253 EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS
ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL
DUCTWORK PER UL-181 (VAPOR SEAL + STRAP BOTH DUCT INNER CORE AND DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER
22x22,6",99 CFM LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT.
22x22,10",-253
PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA.
22x22,7",-120 22x22,7",129 CFM 22x22,6",89 CFM PROVIDE BRANCH DUCT VOLUME CONTROL DAMPERS AT ALL ACCESSIBLE BRANCH DUCT TO TRUNKLINE CONNECTIONS, PROVIDE ACCESS TO DAMPERS.
22x22,7",-99
Exam 6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107.
22x22,10",307 CFM EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS
22x22,14",-615 FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS.
22x22,7",-89
6x10

Waiting 22x22,7",-105 7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON
22x22,10",307 CFM INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / DOOR).
22x22,5",82 CFM Exam 8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING
Corridor
PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN
22x22,7",-101 6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION.
Exam 9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DIAGRAM
Exam 22x22,6",101 CFM TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN
12x10

22x22,9",257 Exam

12x16
CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE
10x12

22x22,6",105 CFM OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE,
8x10

22x22,6",100 CFM
STAND ALONE DEHUMIDIFICATION / HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS.
AHU-3 22x22,7",124 CFM 22x22,9",257
MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS
20x12 16x12
RELOCATED TO
MEZZANINE
TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH BUILDING OWNER.
ABOVE
MAY CONFIGURE
10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT
CU-3 EXISTING AHU
VERTICAL OR
SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR CALCULATIONS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER.
ON SLAB HORIZONTAL U Restroom Office HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER. THIS DRAWING
22x22,7"-100
IS BASED ON MANUAL J HEAT LOAD CALCULATIONS, FOR DETAILED BUILDING ENVELOPE INFORMATION (INSULATING VALUES, WINDOW ENERGY VALUES)
8x4,4",24 CFM 22x22,7",130 CFM Exam SEE "TOTAL BUILDING LOAD SUMMARY" FORM, FIELD INSPECT BUILDING ENVELOPE DURING CONSTRUCTION, BE SURE THE BUILDING MATCHES THE FORM.
22x22,8",-124 Restroom 8x4,4",21 CFM 22x22,10",307 CFM
10x12

22x22,14",-615
14x12

CU-4
ON SLAB 22x22,6",89 CFM
12x8

14x16
22x22,8",-127
24x12

22x22,12",-427
22x22,8",-130
22x22,7",-89
HVAC SCHEDULES + DETAILS
Office Restroom Storage
8x4,4",24 CFM MAY CONFIGURE 22x22,7",129 CFM Waiting
22x22,7",-118 REFRIGERANT PIPING
8x4,4",12 CFM
EXISTING AHU
VERTICAL OR
SPLIT SYSTEM EQUIPMENT SCHEDULE * FRESH
AIR DUCT SUPPLY
* FRESH
AIR + CONTROL WIRING
1/2 THREADED ROD
SUSPEND FROM
HORIZONTAL FMC 401 AIR DUCT FMC 1101
DUCT TOP CHORD
CU-5 22x22,10",307 CFM
AIR HANDLER MARK: AHU-1,2,5 AHU-3,4 FMC 601
FMC 401
ON SLAB UNIT MODEL NUMBER: EXISTING EXISTING * CEILING AIR HANDLER
FMC 303
22x22,6",108 CFM
AHU-4 AHU-5 UNIT DIMEN H/W/D: 59.5X26X23.5 44.5X24X23.5 AIR HANDLER
22x22,6",118 CFM 14x14 UNIT WEIGHT: 155 111 FMC 303
EXISTING ON EXISTING ON Corridor RETURN DUCT SUPPLY AIR DUCT FMC 601
22x22,8",-119 MEZZANINE MEZZANINE 18x16 SUPPLY PLENUM SIZE : 12.02X21.22 12.02X19.22 REFRIGERANT FMC 601
Reception ABOVE ABOVE
PIPING
RETURN PLENUM SIZE : 18.07X21.5 19.5X18.07 * RETURN AIR AUX. DRAIN PAN + FLOAT
+ CONTROL
RISER DUCT SWITCH FMC 301.2.3
SUPPLY FAN CFM / SP : 2000 / .70 800 / .60 WIRING
FMC 601 CONDENSATE DRAIN FMC 307
Consult Exam Exam Break P Restroom FMC 1101 * CEILING
22x22,10",-243 E Restroom SUPPLY FAN H/P : 1 1/4
22x22,6",93 CFM 22x22,5",64 CFM * ACCESS PANEL FMC 306.3
Exam 22x22,4",37 CFM 22x22,5",64 CFM Lab OUTDOOR AIR CFM: 130 / 130 / 130 120 / 120 AIR HANDLER CONDENSATE
STAND DRAIN
8x4,4",39 CFM
8x4,4",10 CFM UNIT PHASE / HERTZ: * * FMC 307
AHU-2 8x4,4",23 CFM UNIT VOLTAGE: * * FLOOR
* = OPTIONAL ITEM, SEE HVAC FLOOR PLAN
DRAWING FOR EXACT CONFIGURATION.
RELOCATED HEATER KW: * * * = OPTIONAL ITEM, SEE HVAC FLOOR PLAN
ABOVE DRAWING FOR EXACT CONFIGURATION.
CEILING HEATER BREAKER: * *
HORIZONTAL AIR HANDLER DETAIL
22x22,9",243 CFM CONDENSER MARK: CU-1,2,5 CU-3,4
22x22,6",-64 NOMINAL A/C TONS : 5 2
VERTICAL AIR
EF-1
10x10

22x22,6",-64
VTE
22"

UNIT MODEL NUMBER: EXISTING EXISTING HANDLER DETAIL


22x22,7",-94 22x22,10",-335 PIPE COVER - MAY MOUNT INTERIOR
(TYPICAL x7) UNIT VOLTAGE: * *
24x12

THIS AREA CONTAINS A MAY CONFIGURE UNIT MCA / BREAKER: * *


EXISTING AHU REFRIGERANT PIPING + CONTROL WIRING
FOUNTAIN - CALCULATE
VERTICAL OR UNIT DIMEN H/W/D: 46.4X35.1X38.7 37.2X26.7X30 FMC 1101 - MAY ALSO ROUTE BELOW SLAB
AND PROVIDE STAND
HORIZONTAL -
CU-1 ALONE DEHUMIDIFICATION
VERIFY EXISTING UNIT WEIGHT: 269 175
14x12

ON SLAB 8x4,4",31 CFM Work Stations AHU TYPE


22x22, 14",-680 TOTAL COOLING BTUH: 58,000 22,800
22x22,10",332 CFM CONDENSING UNIT
SENS. COOLING BTUH: 40,000 16,600 FMC 303
Waiting LAT. COOLING BTUH: 18,000 6,200
WALL
Restroom
18x12

22x22,10",335 CFM
FLOOR FASTENER
TOTAL HEATING BTUH: 34,120 17,060
CU-2 Restroom SENSIBLE HEAT % 0.69 0.73
FMC 301.13
ON SLAB GRADE
Reception SEER: 13 13
22x22,14",-646 EQUIPMENT SLAB
8x4,4",38 CFM 22x22,10",332 CFM THERMOSTAT MODEL: T8411R1002 T8411R1002
AHU-1 22x22,14",-646
NOTES: * EQUIPMENT IS EXISTING,SEE NAME PLATE CONDENSING UNIT DETAIL
ON STAND 24x12 20x12 DATA FOR EXACT INFORMATION. CLEAN AND CHECK
EQUIPMENT TO INSURE PROPER OPERATION.
20x14 12x14 22x22,10",347 CFM
SIZE AND INSTALL STAND ALONE DEHUMIDIFICATION
22x22,10",347 CFM
AT THE INDOOR FOUNTAIN AREA.
12x12

(TYPICAL x7) 22x22,10", -304


22x22,10",347 CFM
6" FRESH AIR 22x22,10", -256 22x22,10",-261
EXHAUST FAN SCHEDULE
DUCT VTE 22x22,8",-147 FAN MARK: EF-1
MANUFACTURER: NUTONE
MODEL NUMBER: QT-80
FAN TYPE: EXHAUST
22x22,10",347 CFM
FAN CFM: 90
22x22,9",258 CFM 22x22,7",146 CFM 22x22,9",261 CFM Reception 22x22,10",304 CFM
Exam TOTAL PRESSURE: .2
Office Exam FAN VOLTAGE: 120/1/60
FAN AMPERAGE: .7
FAN DIMEN LWH: 9X9X6
DUCT OUTLET SIZE: 4
DUCT INLET SIZE: 10X10
FAN WEIGHT: 12
NOTES: 1,2
1 = VENT TO EXTERIOR
2 = INTERLOCK WITH LIGHTS
x

PROJECT NAME: 14378 Spring Hill Dr Office Renovation Designed By: DRAWING DATE
PROJECT ADDRESS: 14378 Spring Hill Drive Neil Fimbel
9/28/2008 HVAC
HVAC Designs
PROJECT STATE, ZIP: Spring Hill Florida (Hernando) 813-885-2258
PERMIT SET DRAWING
CONDITIONED SQ. FT.: 7563 Revised 9/28/08
CLASSIFICATION : Commercial Office Renovation
FL BERS R#884
FL BERS C#959
1 OF 1
North SCALE 1/8"=1'-0"
HVAC SYMBOLS
CEILING REGISTER RECTANGULAR THERMOSTAT @ 60"
1 WAY THROW
FMC 603.15
DUCTWORK
FMC SECTION 603
T ABOVE FLOOR
FEC 13-613
HORIZONTAL AIR
HANDLER MOUNT
FROM STRUCTURE
CEILING REGISTER FLEXIBLE WALL MOUNTED FMC SECTIONS
2 WAY THROW
FMC 603.15
DUCTWORK
FMC SECTION 603
H HUMIDISTAT @ 60"
ABOVE FLOOR
303 --- 312

CEILING REGISTER AIR DISTRIBUTION DUCT MOUNTED


3 WAY THROW BOXES FMC
S SMOKE DETECTOR
FMC 603.15 SECTION 603
D FMC SECTION 606 DUCTLESS AIR
HANDLER
FMC SECTIONS
CEILING REGISTER RETURN AIR EQUIPMENT
303 -- 312
4 WAY THROW PLENUM TRUNK ACCESS PANEL
FMC 603.15 FMC SECTION 602 FMC SECTION 306

CEILING REGISTER SUPPLY AIR EXHAUST FAN


CORNER THROW PLENUM TRUNK EF-1 or as NOTED
FMC SECTION 602 FMC SECTION 403 PACKAGE UNIT
FMC 603.15
SLAB MOUNTED
FMC SECTIONS
WALL REGISTER AIR VOLUME ZONE CONTROL 303 -- 312
2 WAY THROW CONTROL DAMPER ZD AIR DAMPER
FMC 603.15 FMC 603.15 FMC 303 -- 312

FLOOR REGISTER DUCT MOUNTED BYPASS AIR


PARKING GARAGE NATURAL VENTILATION CALCULATION 2 WAY THROW FIRE DAMPER BP DAMPER
PACKAGE UNIT
FMC 603.15 FMC SECTION 607 FMC 303 -- 312
ROOF MOUNTED
FLOOR CLASSIFICATION OPEN WALL PERIMETER OPEN WALL HEIGHT GROSS OPEN AREA % OF OPENING GROSS PERIMETER RESULT FMC SECTIONS
FLOOR GRILLE DRYER VENT
1" UNDERCUT DOOR 303 -- 312
FILTER RETURN ROOF / WALL
1 OPEN PARKING 328 10.00 3280 54 597 PASSES AIR FMC 603.15 D D CAP FMC 504
30 CFM T/A

BUILDING TOTALS 597 CEILING GRILLE RANGE VENT TYPICAL


BRANCH
FILTER RETURN ROOF / WALL CAP DUCT
AIR FMC 603.15 R R FMC 505 - 506 CONDENSING UNIT
OPENINGS ARE UNIFORMLY DISTRIBUTED ON ALL 4 WALLS, THE OPENING AREA EXCEEDS THE MINIMUM OF 20% OPENING TO PERIMETER WALL AREA. ON SLAB
TYPICAL AIR
FMC SECTIONS
CALCULATIONS BASED ON THE 2004 + SUPPLEMENTS FLORIDA MECHANICAL CODE SECTION 403.1, 403.3 AND FLORIDA BUILDING CODE 406.3.3.1 WALL GRILLE CONTROL /
303 -- 312
DEVICE
8x4 = DEVICE NECK SIZE
FILTER RETURN REFRIGERANT
AIR FMC 603.15 PIPING FMC 1101 4" = BRANCH DUCT SIZE
Walk In Closet 32 = AIRFLOW CFM
CEILING GRILLE CONDENSATE ADJUSTMENTS
DUCTED T/ A DRAIN TO GRASS
VERTICAL AIR Bedroom
FMC 603.15 FMC SECTION 307
HANDLER ON STAND
FMC SECTIONS
WALL GRILLE CONDENSATE
DIRECT T/ A TO DRYWELL
303 --- 312 TYPICAL ROOM
FMC 603.15 FMC SECTION 307

AFF = ABOVE FINISH FLOOR CFM = CUBIC FEET / MINUTE EF = EXHAUST FAN PKG = PACKAGE UNIT SF = SUPPLY FAN
AHU = AIR HANDLING UNIT CU = CONDENSING UNIT FPM = FEET PER MINUTE R/A = RETURN AIR T/A = TRANSFER AIR
BP = BYPASS DAMPER DH = DE-HUMIDIFIER MUA = MAKE UP AIR RTU = ROOFTOP UNIT VTE = VENT TO EXTERIOR
BD = BAROMETRIC DAMPER E/A = EXHAUST AIR O/A = OUTSIDE AIR S/A = SUPPLY AIR ZD = ZONE DAMPER

OPEN PARKING GARAGE


NATURALLY VENTILATED HVAC NOTES
COMPLIES WITH FBC 406.3.3.1
PIPING UP TO ROOF
THIS HVAC DRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING
SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH
FIRE CAULK PENETRATIONS
PUMP CONDESATE DRAIN CU-1 HVAC SYMBOL, HVAC CONTRACTOR SHOULD REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW.
TO GUTTER / GRASS AREA
ON ROOF ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND
ABOVE COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN
IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT @ DOOR = ONLY 30 CFM OF RELIEF AIR.
AHU-1 22x22,9",250 CFM 1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS.
22x22,9",250 CFM
ABOVE THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007.
CEILING 2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY
REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO
INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE
THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED.
20x18 20x12 3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE
10x12 12x12,8",-105 CFM
22x22,9",250 CFM FIRST FLOOR GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND
THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY.
4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A
22x22,16",-895 CFM MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL
MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL.
12x12 OAL,8" RELIEF AIR 5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD
DUCT SET BAROMETRIC EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS
ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL
RELIEF AIR DAMPER TO
Lobby RELIEVE 105 CFM
DUCTWORK PER UL-181 (STRAP DUCT INNER CORE + VAPOR SEAL, VAPOR SEAL DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER
LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT.
PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA.
PROVIDE BRANCH DUCT VOLUME DAMPERS AT ALL BRANCH DUCT TO TRUNKLINE CONNECTIONS FOR AIR BALANCING, PROVIDE ACCESS TO DAMPERS.
6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107.
EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS
FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS.
7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON
INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / 30" DOOR).
8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING
22x22,9",250 CFM PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN
6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION.
12x12 OAL,6" FRESH AIR 9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DRAWING
DUCT SET TO 105 CFM TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN
CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE
CURB EQUIPMENT OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE,
STAND ALONE DEHUMIDIFICATION + HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS.
CONNECTION CONNECTION MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS
TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH THE BUILDING OWNER.
10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT
SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR BUILDING COMPONENTS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER.
HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER. THIS DRAWING
CURB IS BASED ON MANUAL J HEAT LOAD CALCULATIONS, FOR DETAILED BUILDING ENVELOPE INFORMATION (INSULATING VALUES, WINDOW ENERGY VALUES)
3/8 BOLT ROOFTOP SEE "TOTAL BUILDING LOAD SUMMARY" FORM, FIELD INSPECT BUILDING ENVELOPE DURING CONSTRUCTION, BE SURE THE BUILDING MATCHES THE FORM.
@ 18" O.C. 3/8"
EQUIPMENT THIS DESIGN IS FOR PEAK LOAD CONDITIONS ONLY, CONSIDER USING STAGED COOLING EQUIPMENT OR STAND ALONE DEHUMIDIFICATION FOR PART LOAD.
SCREWS
ROOF 1/4" PLATE
JOIST OR ANGLE
* FRESH REFRIGERANT PIPING 1/2 THREADED ROD CURB @ 18""
AIR + CONTROL WIRING SUSPEND FROM O.C.
FMC 1101 CONNECT TO
DUCT TOP CHORD TRUSS
FMC 401
AIR HANDLER
MEMBER HVAC SCHEDULES + DETAILS
FMC 303 ROOFTOP
EQUIPMENT
OPEN PARKING GARAGE RETURN DUCT SUPPLY AIR DUCT FMC 601
FMC 303 TRANE EQUIPMENT
FMC 601 AIR HANDLER MARK: AHU-1
NATURALLY VENTILATED AUX. DRAIN PAN + FLOAT UNIT MODEL NUMBER: 2TEC3F30A
SWITCH FMC 301.2.3
COMPLIES WITH FBC 406.3.3.1 * CEILING CONDENSATE DRAIN FMC 307
CURB UNIT DIMEN H/W/D:
UNIT WEIGHT:
46.5X24X23.5
125
SUPPLY PLENUM SIZE : 12.02X19.22
* ACCESS PANEL FMC 306.3
RETURN PLENUM SIZE : 18.07X19.5
MECHANICALLY FASTEN CURB TO ROOF STRUCTURE FOR 140 M.P.H. WIND LOAD SUPPLY FAN CFM / SP : 1000 / .40
* = OPTIONAL ITEM, SEE HVAC FLOOR PLAN SUPPLY FAN H/P : 1/3
DRAWING FOR EXACT CONFIGURATION.
MECHANICALLY FASTEN EQUIPMENT TO CURB FOR UP TO 140 M.P.H. WIND LOAD
OUTDOOR AIR CFM: 105
UNIT PHASE / HERTZ: 1 / 60

HORIZONTAL AIR HANDLER DETAIL ROOFTOP CONDENSING UNIT DETAIL UNIT VOLTAGE:
HEATER KW:
208 / 240
3.6 / 4.8
HEATER BREAKER: 25 / 30
CONDENSER MARK: CU-1
NOMINAL A/C TONS : 2.5
FIRST FLOOR AIR BALANCE SCHEDULE UNIT MODEL NUMBER: 2TTR3030A
UNIT VOLTAGE: 208/230/ 1 / 60
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM RELIEF AIR CFM FRESH AIR CFM
UNIT MCA / BREAKER: 13 / 20
1 LOBBY 14 0.5 1000 895 105 105 UNIT DIMEN H/W/D: 38X30.1X33
X X X X X X X X
UNIT WEIGHT: 198
FIRST FLOOR TOTALS 14 0.5 1000 895 105 105 TOTAL COOLING BTUH: 27,600
TYPICAL OPENING x10' HEIGHT SENS. COOLING BTUH: 20,400
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3
LAT. COOLING BTUH: 7,200
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
TOTAL HEATING BTUH: 17,060
SENSIBLE HEAT % 0.74
FIRST FLOOR VENTILATION CALCULATION SEER: 13
THERMOSTAT MODEL: T8411R1002
TIME CLASSIFICATION OCCUPANTS DURATION MAX. REQ. AIR ADJUSTED AIR TOTAL AIR CFM / SQ FOOT
NOTES: ALTERNATE BRAND EQUIPMENT WITH
PEAK Reception / Wait 14 0.50 15 7.5 105 7.5 EQUAL PERFORMANCE ARE ACCEPTABLE.
SUBMIT PERFORMANCE DATA FOR APPROVAL.
FIRST FLOOR TOTALS 105 x
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 VENTILATION TABLE
North
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM ) PROJECT NAME: Prieto Office Building 1st Floor Designed By: DRAWING DATE
PROJECT ADDRESS: Corner of Lakewood & Oakfield Neil Fimbel
1/31/2009
HVAC
HVAC Designs
PROJECT STATE, ZIP: Hillsborough County Florida 813-885-2258 PERMIT SET DRAWING
CONDITIONED SQ. FT.: 721 of 22,597
CLASSIFICATION : New Office Building
FLORIDA BERS
R#884 C#959 SCALE 1/8"=1'-0"
1 OF 3
* FRESH REFRIGERANT PIPING + 1/2 THREADED ROD

SECOND FLOOR VENTILATION CALCULATION


AIR
DUCT
CONTROL WIRING FMC
1101
SUSPEND FROM
TOP CHORD EXHAUST FAN SCHEDULE HVAC SYMBOLS
FMC 401
AIR HANDLER
TIME CLASSIFICATION OCCUPANTS DURATION MAX. REQ. AIR ADJUSTED AIR TOTAL AIR CFM / SQ FOOT CEILING REGISTER RECTANGULAR THERMOSTAT @ 60"
PEAK Conference 10 VARIES 20 19.75 197.5 19.75
FMC 303
FAN MARK: EF-1 EF-2 1 WAY THROW DUCTWORK T ABOVE FLOOR HORIZONTAL AIR
FMC 603.15 FMC SECTION 603 FEC 13-613 HANDLER MOUNT
RETURN DUCT
PEAK Office 56 1.00 20 20 1120 20 FMC 601
SUPPLY AIR DUCT FMC 601 MANUFACTURER: NUTONE NUTONE FROM STRUCTURE
CEILING REGISTER FLEXIBLE WALL MOUNTED FMC SECTIONS
PEAK Reception / Wait 23 0.50 15 7.5 172.5 7.5 AUX. DRAIN PAN + FLOAT
SWITCH FMC 301.2.3 MODEL NUMBER: QT-150 QT-110 2 WAY THROW
FMC 603.15
DUCTWORK
FMC SECTION 603
H HUMIDISTAT @ 60"
ABOVE FLOOR
303 --- 312
SECOND FLOOR TOTALS 89 1490 * CEILING CONDENSATE DRAIN FMC 307
FAN TYPE: EXHAUST EXHAUST
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 VENTILATION TABLE * ACCESS PANEL FMC 306.3 CEILING REGISTER AIR DISTRIBUTION
S DUCT MOUNTED
FAN CFM: 140 92.85 3 WAY THROW BOXES FMC SMOKE DETECTOR
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM ) TYPICAL
TYPICAL
FMC 603.15 SECTION 603
D FMC SECTION 606 DUCTLESS AIR
* = OPTIONAL ITEM, SEE HVAC FLOOR PLAN TYPICAL 12x12 LOUVER + 9" HANDLER
PIPE CHASE FRESH AIR INTAKE TOTAL PRESSURE: .25 .25
DRAWING FOR EXACT CONFIGURATION. EXHAUST AIR EQUAL TO FRESH AIR FMC SECTIONS
TO ROOF SEE AIR BALANCE CEILING REGISTER RETURN AIR EQUIPMENT
10' SEPERATION REQUIRED 303 -- 312
120/1/60 120/1/60 4 WAY THROW PLENUM TRUNK ACCESS PANEL
SCHEDULE FOR CFM FAN VOLTAGE: FMC 603.15 FMC SECTION 602 FMC SECTION 306
Restroom HORIZONTAL AIR HANDLER DETAIL
22x22,9",-195 CFM 10x6,5",63 CFM Dr Off 2
FAN AMPERAGE: 1.0 .7 SUPPLY AIR EXHAUST FAN
10' SEPERATION CEILING REGISTER
CORNER THROW PLENUM TRUNK EF-1 or as NOTED
Lunch FAN DIMEN LWH: 14X10X9 9X9X6 FMC 603.15 FMC SECTION 602 FMC SECTION 403 PACKAGE UNIT

14x12
Conference 22x22,8",184 CFM SLAB MOUNTED
22x22,12",-278 CFM Dr Off 1 22x22,8",164 CFM 22x22,8",198 CFM 22x22,8",164 CFM
DUCT OUTLET SIZE: 3.25X10 TO 7 4 WALL REGISTER AIR VOLUME ZONE CONTROL
FMC SECTIONS
22x22,8",164 CFM 22x22,8",198 CFM 22x22,8",164 CFM 303 -- 312
22x22,10",307 CFM EF-2 DUCT INLET SIZE: 15X11 10X10 2 WAY THROW CONTROL DAMPER ZD AIR DAMPER
FMC 603.15 FMC 603.15 FMC 303 -- 312
VTE
22x22,10",289 CFM 22x22,9",-184 CFM
20x12 14 12
18x20 CU-4 FAN WEIGHT: FLOOR REGISTER DUCT MOUNTED BYPASS AIR
22x22,10",278 CFM ON ROOF

12x12
22x22,8",195 CFM 2 WAY THROW FIRE DAMPER BP DAMPER
CURB
ABOVE 3rd
NOTES: 1,2 1,2 FMC 603.15 FMC SECTION 607 FMC 303 -- 312 PACKAGE UNIT
126 147 TYPICAL 106 ROOF MOUNTED
FLOOR
Admin CFM CFM 12x12,9" T/A CFM FMC SECTIONS
1 = VENT TO EXTERIOR

12x8

12x8
DUCT

12x8
22x22,10",289 CFM AHU-4 Restroom T/A T/A
Restroom
T/A FLOOR GRILLE DRYER VENT
1" UNDERCUT DOOR 303 -- 312
Storage EF-2 Restroom CU-2 FILTER RETURN ROOF / WALL
22x22,10",289 CFM 22x22,6",90 CFM ABOVE 2 = INTERLOCK WITH LIGHTS AIR FMC 603.15 D D CAP FMC 504
30 CFM T/A
16x12

CEILING VTE
CU-3 ON ROOF EF-1 CU-1
8x4,4",19 CFM CURB VTE
ON ROOF ABOVE 3rd ON ROOF
TYPICAL CEILING GRILLE RANGE VENT TYPICAL

12x12
CURB FLOOR CURB
Restroom 8x4,4",14 CFM ABOVE 3rd
8x4,4",13 CFM UNLESS 8x4,4",14 CFM ABOVE 3rd FILTER RETURN ROOF / WALL CAP BRANCH
DUCT
8x4,4",11 CFM FLOOR NOTED FLOOR EQUIPMENT AIR FMC 603.15 R R FMC 505 - 506 CONDENSING UNIT
20x12 18x20 20x12 18x20 20x12 CURB
22x22,9",-192 CFM Billing 18x20 TYPICAL CONNECTION ON SLAB
22x22,9",-183 CFM 22x22,16",-1040 CFM CONNECTION TYPICAL AIR
22x22,7",-90 CFM FMC SECTIONS DEVICE
22x22,6",-75 CFM WALL GRILLE CONTROL / 8x4 = DEVICE NECK SIZE
20x12

22x22,16",-860 CFM 22x22,14",-880 CFM 303 -- 312


FILTER RETURN REFRIGERANT
22x22,14",-868 CFM 8x4,4",14 CFM CURB AIR FMC 603.15 PIPING FMC 1101 4" = BRANCH DUCT SIZE

12x12

12x12
AHU-5 22x22,6",103 CFM 3/8 BOLT 3/8"
32

14x12
ROOFTOP Walk In Closet = AIRFLOW CFM
ABOVE
CU-6 AHU-3 AHU-2 AHU-1 @ 18" O.C. EQUIPMENT
SCREWS
1/4" CEILING GRILLE CONDENSATE ADJUSTMENTS
Restroom

8x12
CEILING Corridor ON ROOF ABOVE ABOVE ABOVE ROOF PLATE DUCTED T/ A DRAIN TO GRASS
EF-2 CURB Dr Off 3 CEILING CEILING CEILING JOIST OR VERTICAL AIR Bedroom
12x12 T/A ABOVE 3rd CURB ANGLE
FMC 603.15 FMC SECTION 307
HANDLER ON STAND
VTE HIGH WALL FLOOR 22x22,5",75 CFM @ 18""
CONNECT TO
O.C. FMC SECTIONS
TRUSS WALL GRILLE CONDENSATE
Storage 303 --- 312 TYPICAL ROOM
18x20

Exam 5 MEMBER DIRECT T/ A TO DRYWELL


22x22,4",28 CFM 22x22,6",-75 CFM
22x22,8",164 CFM FMC 603.15 FMC SECTION 307
22x22,8",164 CFM 22x22,8",164 CFM 22x22,8",198 CFM

8x12
22x22,5",65 CFM 8x4,4",19 CFM CU-5 22x22,8",198 CFM
22x22,8",164 CFM

8x12
10x6,6",100 CFM

18x20
10' SEPERATION

ROOFTOP

8x12
ON ROOF
22x22,9",252 CFM CURB EQUIPMENT AFF = ABOVE FINISH FLOOR CFM = CUBIC FEET / MINUTE EF = EXHAUST FAN PKG = PACKAGE UNIT SF = SUPPLY FAN
22x22,6",-65 CFM
Exam 4 ABOVE 3rd FMC 303
AHU = AIR HANDLING UNIT CU = CONDENSING UNIT FPM = FEET PER MINUTE R/A = RETURN AIR T/A = TRANSFER AIR
FLOOR
22x22,5",63 CFM VTE = VENT TO EXTERIOR
F Office BP = BYPASS DAMPER DH = DE-HUMIDIFIER MUA = MAKE UP AIR RTU = ROOFTOP UNIT
Server
8x12

CURB BD = BAROMETRIC DAMPER E/A = EXHAUST AIR O/A = OUTSIDE AIR S/A = SUPPLY AIR ZD = ZONE DAMPER
22x22,10",-252 CFM 22x22,5",75 CFM
AHU-6
21x12 18x21 Dr Off 4
ABOVE
Exam 3 CEILING MECHANICALLY FASTEN CURB TO ROOF STRUCTURE FOR 140 M.P.H. WIND

22x22,6",-63 CFM AHU-7 Files 20x12


22x22,14",-860 CFM
Phone 22x22,8",164 CFM 22x22,8",164 CFM 22x22,8",198 CFM 22x22,8",198 CFM 22x22,8",164 CFM 22x22,8",164 CFM
LOAD
MECHANICALLY FASTEN EQUIPMENT TO CURB FOR UP TO 140 M.P.H. WIND
LOAD
HVAC NOTES
EF-2 Corridor ABOVE

VTE
CEILING
22x22,4",28 CFM Unit 2 C Unit 2 B Unit 2 A
22x22,5",81 CFM 22x22,8",165 CFM ROOFTOP CONDENSING UNIT DETAIL
10x6,6",92 CFM 22x22,6",-63 CFM
Restroom 22x22,5",65 CFM
PIPING UP FROM CU-7 THIS HVAC DRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING
10x12

22x22,10",-223 CFM SR-82,8",165 CFM


LOBBY BELOW
ON ROOF
SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH
18x14
18x12

Exam 1 CURB HVAC SYMBOL, HVAC CONTRACTOR SHOULD REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW.
EF-2
ABOVE 3rd
FLOOR
8x4,4",54 CFM
VTE SECOND FLOOR AIR BALANCE SCHEDULE ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND
Exam 2 COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN
Restroom ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT @ DOOR = ONLY 30 CFM OF RELIEF AIR.
22x22,6",91 CFM
22x22,9",223 CFM 22x22,5",63 CFM
22x22,8",165 CFM 22x22,8",165 CFM 1 Unit 2 A 6 > 3 HRS 986 880 0 120 1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS.
THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007.
1 Restroom 0 N/A 14 0 120 0 2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY
Lab X X X X X X X X
12x14
16x12

REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO
INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE
22x22,10",-300 CFM
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED.
12x12,6",-66 CFM 22x22,7",-78 CFM 22x22,8",165 CFM 3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE
2 Unit 2 B 8 > 3 HRS 1187 1040 0 160 GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND
8x4,4",51 CFM
8x4,4",20 CFM
Recep / Wait 2 Restroom 0 N/A 13 0 160 0 THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY.
4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A
X X X X X X X X
16x10

10x6,5",66 CFM
Restroom MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL
22x22,9",249 CFM
P Infusion
EF-2 ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL.
VTE 5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD
Pharmacy Cold 3 Unit 2 C 7 > 3 HRS 986 860 0 120 EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS
ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL
3 Restroom 0 N/A 14 0 120 0 DUCTWORK PER UL-181 (STRAP DUCT INNER CORE + VAPOR SEAL, VAPOR SEAL DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER
Infusion X X X X X X X X LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT.
PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA.
22x22,14",-640 CFM ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM PROVIDE BRANCH DUCT VOLUME DAMPERS AT ALL BRANCH DUCT TO TRUNKLINE CONNECTIONS FOR AIR BALANCING, PROVIDE ACCESS TO DAMPERS.
22x22,9",213 CFM
6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107.
22x22,9",213 CFM 22x22,9",213 CFM 4 Server 0 N/A 100 100 T/A 0 0
SECOND FLOOR 4 Dr Off 4 1 > 3 HRS 75 75 0 20
EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS
FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS.
7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON
4 Dr Off 3 1 > 3 HRS 75 75 0 20 INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / 30" DOOR).
8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING
EF-1 8x4,4",43 CFM
EF-2 4 Restroom 0 N/A 19 0 96 0 PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN
VTE VTE 6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION.
Restroom
TYPICAL
UNLESS Restroom
4 Dr Off 2 1 > 3 HRS 184 184 0 20 9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DRAWING
TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN
8x4,4",13 CFM NOTED 4 Restroom 0 N/A 63 0 96 0 CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE
AHU-8 4 Dr Off 1 1 > 3 HRS 195 195 0 20 OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE,
18x20

STAND ALONE DEHUMIDIFICATION + HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS.
22x22,8",198 CFM
ABOVE
CEILING 4 Admin 1 > 3 HRS 90 90 0 20 MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS
TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH THE BUILDING OWNER.
127
CFM
4 Billing 1 > 3 HRS 278 278 0 20 10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT
SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR BUILDING COMPONENTS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER.
T/A
4 F Office 0 N/A 18 0 0 0 HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER. THIS DRAWING
22x22,8",198 CFM 4 Corridor 0 N/A 103 183 0 0 IS BASED ON MANUAL J HEAT LOAD CALCULATIONS, FOR DETAILED BUILDING ENVELOPE INFORMATION (INSULATING VALUES, WINDOW ENERGY VALUES)
X X X X X X X X
20x12

SEE "TOTAL BUILDING LOAD SUMMARY" FORM, FIELD INSPECT BUILDING ENVELOPE DURING CONSTRUCTION, BE SURE THE BUILDING MATCHES THE FORM.
22x22,8",198 CFM THIS DESIGN IS FOR PEAK LOAD CONDITIONS ONLY, CONSIDER USING STAGED COOLING EQUIPMENT OR STAND ALONE DEHUMIDIFICATION FOR PART LOAD.
12x8 12x12 8x12
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
22x22,8",198 CFM
5 Lunch 4 < 3 HRS 307 192 0 40
22x22,16",-1060 CFM
5 Restroom 0 N/A 14 0 95 0
5 Conference 10 < 3 HRS 868 868 0 120
CU-8
5
X
Storage
X X
0 N/A
X
11
X
0
X X
0
X
0 HVAC SCHEDULES + DETAILS
22x22,8",198 CFM ON ROOF
CURB 22x22,8",198 CFM ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
ABOVE 3rd
FLOOR
Unit 2 F TRANE SPLIT SYSTEM EQUIPMENT SCHEDULE
Restroom 6 Files 0 N/A 28 0 0 0
18x20

6 Storage 0 N/A 28 0 0 0 AIR HANDLER MARK: AHU-1,3,6 AHU-2,4,5,8,10 AHU-7 AHU-9


8x4,4",12 CFM
AHU-9 6 Recep / Wait 10 VARIES 825 860 0 140 UNIT MODEL NUMBER: 2TEC3F30A 2TEC3F36A 2TEC3F60A 2TEC3F42A
22x22,9",231 CFM
148
ABOVE
CEILING
6 Restroom 0 N/A 54 0 95 0 UNIT DIMEN H/W/D: 46.5X24X23.5 46.5X24X23.5 59.5X26X23.5 53.25X26X23.5
CFM
6 Phone 0 N/A 65 0 0 0 UNIT WEIGHT: 125 125 155 150
T/A
X X X X X X X X SUPPLY PLENUM SIZE : 12.02X19.22 12.02X19.22 12.02X21.22 12.02X21.22
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM RETURN PLENUM SIZE : 18.07X19.5 18.07X19.5 18.07X21.5 18.07X21.5
20x12

22x22,9",231 CFM

22x22,9",231 CFM
7 Infusion 9 VARIES 640 640 0 90 SUPPLY FAN CFM / SP : 1000 / .40 1200 / .40 2000 / .40 1400 / .40
7 Restroom 0 N/A 43 0 96 0 SUPPLY FAN H/P : 1/3 1/3 1 1/2
10x12 16x12 10x12
22x22,9",231 CFM 7 Pharmacy 1 > 3 HRS 249 300 0 20 OUTDOOR AIR CFM: 120/140/140 160/120/140/140/120 250 160
22x22,16",-1240 CFM UNIT PHASE / HERTZ: 1 / 60 1 / 60 1 / 60 1 / 60
22x22,9",231 CFM 7 Cold 0 N/A 51 0 0 0
UNIT VOLTAGE: 208 / 240 208 / 240 208 / 240 208 / 240
7 P Infusion 1 > 3 HRS 66 66 0 20
HEATER KW: 3.6 / 4.8 3.6 / 4.8 7.2 / 9.6 3.6 / 4.8
7 Restroom 0 N/A 20 0 96 0 HEATER BREAKER: 25 / 30 25 / 30 50 / 60 25 / 30
CU-9 7 Exam 2 1 > 3 HRS 223 223 0 20
ON ROOF
7 Exam 1 1 > 3 HRS 63 63 0 20
CONDENSER MARK: CU-1,3,6 CU-2,4,5,8,10 CU-7 CU-9
22x22,9",231 CFM CURB
ABOVE 3rd
FLOOR
Unit 2 G 7 Lab 1 > 3 HRS 92 0 0 20
NOMINAL A/C TONS : 2.5 3 5 3.5
UNIT MODEL NUMBER: 2TTR3030A 2TTR3036A 2TTR3060A 2TTR3042A
Restroom
AHU-10
7 Restroom 0 N/A 92 0 96 0
18x20

UNIT VOLTAGE: 208/230/ 1 / 60 208/230/ 1 / 60 208/230/ 1 / 60 208/230/ 1 / 60


107
CFM ABOVE
7 Exam 3 1 > 3 HRS 252 252 0 20 UNIT MCA / BREAKER: 13 / 20 18 / 30 32 / 50 21 / 35
T/A CEILING

8x4,4",13 CFM
7 Exam 4 1 > 3 HRS 63 63 0 20 UNIT DIMEN H/W/D: 38X30.1X33 38X30.1X33 46.4X35.1X38.7 38.4X35.1X38.7
7 Exam 5 1 > 3 HRS 65 65 0 20 UNIT WEIGHT: 198 194 269 250
22x22,8",198 CFM 7 Corridor 0 N/A 81 78 0 0 TOTAL COOLING BTUH: 27,600 34,200 58,000 41,000
X X X X X X X X
20x12

22x22,8",198 CFM SENS. COOLING BTUH: 20,400 25,400 40,000 29,800


22x22,8",198 CFM
22x22,8",198 CFM
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
12x12
LAT. COOLING BTUH: 7,200 8,800 18,000 11,200
12x8 8x12
8 Unit 2 F 7 > 3 HRS 1187 1060 0 140 TOTAL HEATING BTUH: 17,060 17,060 34,120 17,060
22x22,16",-1080 CFM
8 Restroom 0 N/A 13 0 140 0 SENSIBLE HEAT % 0.74 0.74 0.69 0.73
X X X X X X X X SEER: 13 13 13.5 13.5
CU-10
ON ROOF
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
CURB 22x22,8",198 CFM
THERMOSTAT MODEL: T8411R1002 T8411R1002 T8411R1002 T8411R1002
22x22,8",198 CFM
ABOVE 3rd
FLOOR Unit 2 H 9 Unit 2 F 8 > 3 HRS 1388 1240 0 160 NOTES: ALTERNATE BRAND EQUIPMENT WITH EQUAL PERFORMANCE ARE ACCEPTABLE.
9 Restroom 0 N/A 12 0 160 0 SUBMIT PERFORMANCE DATA FOR APPROVAL.
X X X X X X X X
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
x
North 10
10
Unit 2 F
Restroom
6
0
> 3 HRS
N/A
1187
13
1080
0
0
120
120
0
PROJECT NAME: Prieto Office Building 2nd Floor Designed By: DRAWING DATE
PROJECT ADDRESS: Corner of Lakewood & Oakfield Neil Fimbel
1/31/2009
HVAC
SECOND FLOOR TOTALS 89 VARIES 12400 10910 1490 1490 PROJECT STATE, ZIP: Hillsborough County Florida
HVAC Designs
PERMIT SET DRAWING
813-885-2258
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 CONDITIONED SQ. FT.: 10,938 of 22,597
CLASSIFICATION : New Office Building
FLORIDA BERS
R#884 C#959 SCALE 1/8"=1'-0"
2 OF 3
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
HVAC SYMBOLS
CEILING REGISTER RECTANGULAR THERMOSTAT @ 60"
1 WAY THROW
FMC 603.15
DUCTWORK
FMC SECTION 603
T ABOVE FLOOR
FEC 13-613
HORIZONTAL AIR
HANDLER MOUNT
FROM STRUCTURE
CEILING REGISTER FLEXIBLE WALL MOUNTED FMC SECTIONS
2 WAY THROW
FMC 603.15
DUCTWORK
FMC SECTION 603
H HUMIDISTAT @ 60"
ABOVE FLOOR
303 --- 312

CEILING REGISTER AIR DISTRIBUTION DUCT MOUNTED


3 WAY THROW BOXES FMC
S SMOKE DETECTOR
TYPICAL 12x12 LOUVER + BAROMETRIC FMC 603.15 SECTION 603
D FMC SECTION 606 DUCTLESS AIR
RELIEF AIR DAMPER + 12x12 RELIEF AIR HANDLER
GRILLE -- FOR INTERIOR AIR PRESSURE FMC SECTIONS
RELIEF / TYPICAL OF 4 ZONES CEILING REGISTER RETURN AIR EQUIPMENT
303 -- 312
4 WAY THROW PLENUM TRUNK ACCESS PANEL
TYPICAL FMC 603.15 FMC SECTION 602 FMC SECTION 306
EXHAUST AIR EQUAL TO FRESH AIR
CEILING REGISTER SUPPLY AIR EXHAUST FAN
Unit 3 Dwest Unit 3 Deast EF-1 or as NOTED
CORNER THROW PLENUM TRUNK
FMC SECTION 602 FMC SECTION 403 PACKAGE UNIT
FMC 603.15
22x22,9",267 CFM SLAB MOUNTED
22x22,9",267 CFM FMC SECTIONS
22x22,9",267 CFM 22x22,8",197 CFM 22x22,8",197 CFM 22x22,8",198 CFM 22x22,8",198 CFM WALL REGISTER AIR VOLUME ZONE CONTROL
22x22,8",198 CFM 22x22,8",198 CFM 303 -- 312
22x22,9",267 CFM 2 WAY THROW CONTROL DAMPER ZD AIR DAMPER
FMC 603.15 FMC 603.15 FMC 303 -- 312

FLOOR REGISTER DUCT MOUNTED BYPASS AIR


2 WAY THROW FIRE DAMPER BP DAMPER
FMC 603.15 FMC 303 -- 312 PACKAGE UNIT
22x22,9",267 CFM FMC SECTION 607
125 TYPICAL ROOF MOUNTED
22x22,9",267 CFM CFM 148 12x12,9" 106
8x14 16x14 CFM CFM
FMC SECTIONS
T/A T/A DUCT FLOOR GRILLE DRYER VENT
T/A T/A 1" UNDERCUT DOOR 303 -- 312
Restroom

12x12
12x12
12x14
22x22,18",-1400 CFM FILTER RETURN ROOF / WALL
22x22,18",-1400 CFM D D 30 CFM T/A
AIR FMC 603.15 CAP FMC 504

12x12
22x22,16",-1060 CFM 22x22,16",-1040 CFM
22x22,9",267 CFM 22x22,16",-1080 CFM
CEILING GRILLE RANGE VENT TYPICAL
BRANCH
Restroom EF-1 8x4,4",14 CFM FILTER RETURN ROOF / WALL CAP DUCT
VTE AIR FMC 603.15 R R FMC 505 - 506 CONDENSING UNIT
8x4,4",15 CFM 8x4,4",12 CFM TYPICAL
Restroom TYPICAL ON SLAB
TYPICAL AIR

18x16
UNLESS CONDENSATE DRAIN FMC SECTIONS DEVICE
NOTED TO GUTTER / GRASS WALL GRILLE CONTROL /
303 -- 312 8x4 = DEVICE NECK SIZE
RTU-5 RTU-4 RTU-3 RTU-2 RTU-1 FILTER RETURN REFRIGERANT
22x22,9",267 CFM ON ROOF
22x14 ON ROOF 22x14 ON ROOF 22x14 ON ROOF TYPICAL AIR FMC 603.15 PIPING FMC 1101 4" = BRANCH DUCT SIZE
ON ROOF
22x14 22x14 FRESH AIR INTAKE @ Walk In Closet 32 = AIRFLOW CFM

18x16
22x22,9",267 CFM ROOFTOP EQUIPMENT CEILING GRILLE CONDENSATE ADJUSTMENTS
22x22,9",267 CFM DUCTED T/ A DRAIN TO GRASS
VERTICAL AIR Bedroom

18x16

18x16
18x16
FMC 603.15 FMC SECTION 307
HANDLER ON STAND
FMC SECTIONS
WALL GRILLE CONDENSATE
22x22,198 CFM
303 --- 312 TYPICAL ROOM

12x14
22x22,198 CFM DIRECT T/ A TO DRYWELL
8x14

22x22,9",267 CFM 22x22,8",197 CFM 22x22,8",197 CFM 22x22,8",198 CFM


22x22,9",267 CFM 22x22,8",198 CFM FMC 603.15 FMC SECTION 307

12x12
12x12
12x12
22x22,9",267 CFM TYPICAL CURB MOUNTED
22x22,9",267 CFM CONDENSING UNIT ON ROOF ABOVE AFF = ABOVE FINISH FLOOR CFM = CUBIC FEET / MINUTE EF = EXHAUST FAN PKG = PACKAGE UNIT SF = SUPPLY FAN
SPLIT SYSTEMS SERVE FIRST AND AHU = AIR HANDLING UNIT CU = CONDENSING UNIT FPM = FEET PER MINUTE R/A = RETURN AIR T/A = TRANSFER AIR
SECOND FLOORS VTE = VENT TO EXTERIOR
BP = BYPASS DAMPER DH = DE-HUMIDIFIER MUA = MAKE UP AIR RTU = ROOFTOP UNIT

12x14
BD = BAROMETRIC DAMPER E/A = EXHAUST AIR O/A = OUTSIDE AIR S/A = SUPPLY AIR ZD = ZONE DAMPER

22x22,198 CFM
22x22,9",267 CFM 22x22,8",197 CFM 22x22,8",197 CFM 22x22,8",198 CFM 22x22,198 CFM HVAC NOTES
16x14

22x22,8",198 CFM
Unit 3 B
22x14

Unit 3 C Unit 3 A

THIS HVAC DRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING
22x22,9",267 CFM 18x16 12x14
SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH
22x22,18",-1400 CFM HVAC SYMBOL, HVAC CONTRACTOR SHOULD REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW.
RTU-6 22x22,9",267 CFM 22x22,9",267 CFM
ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND
Unit 3 Enorth ON ROOF

THIRD FLOOR AIR BALANCE SCHEDULE COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN
IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT @ DOOR = ONLY 30 CFM OF RELIEF AIR.
Unit 3 Esouth 22x22,9",267 CFM
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM 1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS.
22x22,9",267 CFM THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007.
2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY
1 Unit 3 A 6 > 3 HRS 1186 1080 0 120 REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO
22x22,18",-1400 CFM 1 Restroom 0 N/A 14 0 120 0 INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE
THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED.
X X X X X X X X 3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND
22x14

THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY.
22x22,9",267 CFM
4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A
2 Unit 3 B 8 > 3 HRS 1188 1040 0 160 MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL
MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL.
18x16 12x14
2 Restroom 0 N/A 12 0 160 0 5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD
12x14
X X X X X X X X EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL
DUCTWORK PER UL-181 (STRAP DUCT INNER CORE + VAPOR SEAL, VAPOR SEAL DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER
RTU-7 22x22,9",267 CFM LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT.
ON ROOF
3 Unit 3 C 7 > 3 HRS 1185 1060 0 140 PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA.
PROVIDE BRANCH DUCT VOLUME DAMPERS AT ALL BRANCH DUCT TO TRUNKLINE CONNECTIONS FOR AIR BALANCING, PROVIDE ACCESS TO DAMPERS.
3 Restroom 0 N/A 15 0 140 0 6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107.
22x22,9",267 CFM X X X X X X X X EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS
THIRD FLOOR ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM RELIEF AIR CFM FRESH AIR CFM FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS.
7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON
INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / 30" DOOR).
4 Unit 3 Deast 10 > 3 HRS 1600 1400 200 200 8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING
22x22,9",267 CFM X X X X X X X X PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN
6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION.
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM RELIEF AIR CFM FRESH AIR CFM 9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DRAWING
TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN
Restroom
5 Unit 3 Dwest 10 > 3 HRS 1600 1400 200 200 CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE
X X X X X X X X OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE,
22x22,8",198 CFM STAND ALONE DEHUMIDIFICATION + HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS.
22x22,198 CFM 127
22x22,8",198 CFM
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM RELIEF AIR CFM FRESH AIR CFM MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS
CFM 8x4,4",13 CFM TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH THE BUILDING OWNER.
T/A
6 Unit 3 Enorth 10 > 3 HRS 1600 1400 200 200 10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT
SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR BUILDING COMPONENTS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER.
X X X X X X X X HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER. THIS DRAWING
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM RELIEF AIR CFM FRESH AIR CFM IS BASED ON MANUAL J HEAT LOAD CALCULATIONS, FOR DETAILED BUILDING ENVELOPE INFORMATION (INSULATING VALUES, WINDOW ENERGY VALUES)
22x14

SEE "TOTAL BUILDING LOAD SUMMARY" FORM, FIELD INSPECT BUILDING ENVELOPE DURING CONSTRUCTION, BE SURE THE BUILDING MATCHES THE FORM.
THIS DESIGN IS FOR PEAK LOAD CONDITIONS ONLY, CONSIDER USING STAGED COOLING EQUIPMENT OR STAND ALONE DEHUMIDIFICATION FOR PART LOAD.
7 Unit 3 Esouth 10 > 3 HRS 1600 1400 200 200
12x12 18x16 12x12 Unit 3 F X X X X X X X X
22x22,16",-1060 CFM
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
8 Unit 3 F 7 > 3 HRS 1187 1060 0 140
RTU-8 8 Restroom 0 N/A 13 0 140 0
ON ROOF
X X X X X X X X HVAC SCHEDULES + DETAILS
22x22,8",198 CFM 22x22,8",198 CFM
DUCT EQUIPMENT ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
22x22,8",198 CFM CURB CONNECTION CONNECTION
CONNECTION 9 Unit 3 G 8 > 3 HRS 1587 1440 0 160
Restroom
ROOFTOP
ROOFTOP EQUIPMENT SCHEDULE EXHAUST FAN SCHEDULE
22x22,9",265 CFM EQUIPMENT
DUCT 9 Restroom 0 N/A 13 0 160 0
147
CFM 8x4,4",13 CFM 22x22,9",265 CFM CURB
SEAL
FMC 601 X X X X X X X X PACKAGE UNIT MARK: RTU-1,2,3,8,10 RTU-4,5,6,7,9 FAN MARK: EF-1
22x22,9",265 CFM 3/8 BOLT ROOFTOP (4) 3/8x2
T/A
@ 18" O.C. 1/2" EQUIPMENT SCREWS ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM UNIT MANUFACTURER: TRANE TRANE MANUFACTURER: NUTONE
(1) 1/4x2x2
SCREWS UNIT MODEL NUMBER: THC033A3 THC043A3 MODEL NUMBER: QT-150
ROOF DUCT @ 8" O.C. CURB
ANGLE 10 Unit 3 H 6 > 3 HRS 1187 1080 0 120
JOIST EACH NOMINAL A/C TONS : 3 4 FAN TYPE: EXHAUST
CORNER 10 Restroom 0 N/A 13 0 120 0
2" U CHANNEL X UNIT CONFIGURATION: DOWNFLOW DOWNFLOW FAN CFM: 140
1/4" THK
UNIT DIMEN H/W/D: 37X45X70 37X45X70
22x14

SPAN 3 JOISTS TOTAL PRESSURE: .25


THIRD FLOOR TOTALS 82 > 3 HRS 14000 12360 1640 1640 UNIT WEIGHT: 627 669
FAN VOLTAGE: 120/1/60
Unit 3 G ROOFTOP THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 SUPPLY PLENUM SIZE : 17X15 17X15
12x14 18x16 12x14
EQUIPMENT FAN AMPERAGE: 1.0
RETURN PLENUM SIZE : 23X14 23X14
22x22,18",-1440 CFM FMC 303
NOTE: TIE DOWN METHOD MAY VARY THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM ) FAN DIMEN LWH: 14X10X9
A/C CONTRACTOR MAY USE FLAT PLATE, SUPPLY FAN CFM / SP : 1200 / .4 1600 / .4
ANGLE PLATE, OR STRAP FOR TIE DOWN DUCT OUTLET SIZE: 3.25X10 TO 7
BOLT AND SCREW SIZES MAY VARY - TIE SUPPLY FAN H/P : 1 1
RTU-9
ON ROOF
R/A
DUCT
S/A
DUCT
CURB
DOWN FOR A MAXIMUM OF 140 MPH WIND
THIRD FLOOR VENTILATION CALCULATION OUTDOOR AIR CFM: 120/160/140/140/120 200/200/200/200/160
DUCT INLET SIZE: 15X11
FMC FMC UNIT PHASE / HERTZ: 3/60 3/60 FAN WEIGHT: 14
22x22,9",265 CFM 22x22,9",265 CFM 22x22,9",265 CFM 601 601 TIME CLASSIFICATION OCCUPANTS DURATION MAX. REQ. AIR ADJUSTED AIR TOTAL AIR CFM / SQ FOOT NOTES: 1,2
UNIT VOLTAGE: 208/230 208/230
MECHANICALLY FASTEN CURB TO ROOF STRUCTURE FOR 140 M.P.H. WIND LOAD PEAK Office 82 1.00 20 20 1640 20 UNIT MCA: 19.9 22.6 1 = VENT TO EXTERIOR
Restroom MECHANICALLY FASTEN AND SEAL DUCTS PER FMC SECTIONS 603 AND 604 2 = INTERLOCK WITH LIGHTS
22x22,8",198 CFM UNIT MAX BREAKER: 30 35
22x22,8",198 CFM
22x22,8",198 CFM MECHANICALLY FASTEN EQUIPMENT TO CURB FOR UP TO 140 M.P.H. WIND LOAD THIRD FLOOR TOTALS 82 1640
107 HEATER KW: 4.5/6 9/12
CFM
T/A
8x4,4",13 CFM
ROOFTOP PACKAGE UNIT DETAIL THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 VENTILATION TABLE HEATER MCA: 21.9/24.3 37.5/42.4
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM ) HEATER BREAKER: 25/25 40/45
22x14

TOTAL COOLING BTUH: 38,000 49,800


Unit 3 H SENS. COOLING BTUH: 28,800 39,400
12x12 18x16 12x12 LAT. COOLING BTUH: 9,200 10,400
22x22,16",-1080CFM TOTAL HEATING BTUH: 20,472 40,944
SENS. HEAT % 0.76 0.79
RTU-10 COOLING EFFICIENCY: 13 13
ON ROOF
22x22,8",198 CFM 22x22,8",198 CFM THERMOSTAT MODEL: T8411R1002 T8411R1002
22x22,8",198 CFM NOTES: ALTERNATE BRAND EQUIPMENT WITH
EQUAL PERFORMANCE ARE ACCEPTABLE.
SUBMIT PERFORMANCE DATA FOR APPROVAL.
x
North
PROJECT NAME: Prieto Office Building 2nd Floor Designed By: DRAWING DATE
PROJECT ADDRESS: Corner of Lakewood & Oakfield Neil Fimbel
1/31/2009
HVAC
HVAC Designs
PROJECT STATE, ZIP: Hillsborough County Florida 813-885-2258 PERMIT SET DRAWING
CONDITIONED SQ. FT.: 10,938 of 22,597
CLASSIFICATION : New Office Building
FLORIDA BERS
R#884 C#959 SCALE 1/8"=1'-0"
3 OF 3