Inteli IO8/8

Order code: I-IO8/8


Extension/Peripheral Module
Datasheet
Product description
Peripheries dedicated to expand number of I/Os Analog output: 2 channels
of the main ComAp controller Voltage: 0 - 10 V DC
Supports wide range of sensor types and Current 0 - 20 mA
characteristics
PWMs
Connection with the main ComAp controller over
CAN bus (up to 200 m length) Certificates and standards
Extension modules are compatible with This product is CE compliant.

InteliSysNT BaseBox, InteliSysNTC EN 60068-2-6 ed.2:2008

BaseBox, InteliSys GAS, EN 60068-2-27


ed.2:2010
InteliSysNTC Hybrid, InteliSysNT BaseBox
EN 60068-2-30, May
Marine
2000
InteliGenNT, InteliGenNT BaseBox, EN 60068-2-64
InteliGenNTC BaseBox Marine EN 61010-1:2003
InteliMainsNT, InteliMainsNT BaseBox, Marine certifications:
InteliMainsNTC BaseBox DNV, GL, LR, BV,RMR, CCS,
RINA
InteliDrive DCU Marine, InteliDrive DCU
All certificates and standards are available on:
https://webstore.iec.ch/publication/4243
Key features
Binary input : 8/16 channels
Pull up, Pull down options
Binary output: 8/0 channels
Low side, High side options
Possibility to use the outputs as inputs

|Inteli IO8/8 Datasheet |Related HW ver: 1.0 |Related SW ver: 1.0 |Date of issue: 8.2.2016 1
Technical data
Power supply Binary outputs (open collector
Power supply 8 to 36 V DC output)
35 mA a @ 24 V ÷ 100 mA 500 mA
Power consumption Max current
at 8 V
Max switching voltage 36 V DC

Operating conditions
Analog outputs (not electric
Operating temperature - 30°C to + 70°C
separated)
Storage temperature - 40°C to + 80°C
range 0 – 10 V , accuracy:
Operation humidity 95% w/o condensation
Voltage ± 20 mV ± 0,5 % of actual
5-25 Hz, ±1.6 mm, 25-100 value (I 5 mA)
Vibrations max
Hz, a = 4 g
Range 0 - 20 mA,
Shocks a = 200 m/s2 accuracy: ± 100 µA ± 0,5
Current
% of actual value (R
Binary inputs max
500 Ω)
4400 Level 5 V, adjustable freq
Input resistance
Ω 200÷2400 Hz (I 20
PWM max
0 to mA), (minimal step of pulse
Input range 36 V is 2 µs)
DC Max current of AGND 100 mA
Switching voltage level for open contact 0 to
indication 2V General information
Max voltage level for close contact 6 to Protection IP20
indication 36 V CAN bus is galvanic separated from the
Galvanic
separation measurement and power supply

Dimensions, terminals and mounting

Note: The unit is mounted on DIN rail (35 mm/1.38 in).

Manufacturer:
ComAp a.s. Fax: +420 266 316 647
Czech Republic E-mail: info@comap.cz
Phone: +420 246 012 111 Internet: www.comap.cz

Inteli IO8/8 Datasheet 2