COMMERCIAL AIR CONDITIONING

GENERAL CATALOGUE

2015
Treasures are always found off
the beaten path.
There’s no question in our mind who we are. We could name the
countless accolades and awards we’ve received over the years, but
it really doesn’t matter unless you know our name. In life, we are
naturally drawn to the familiar, and accordingly, follow in the
footsteps of those before us. However, there are those who dare to
step off the beaten path. Through reaching for the new, they
discover that there’s so much more out there. In this moment,
boundaries are tested and the world grows just a little bigger. 
 
Allow us to introduce ourselves. Our name is Hisense. We’ve been
around for a long time, but perhaps not in your area. In a way, we’re
also searching for more. We’ve reached the pinnacle of success in
our own country and now we’re ready to see what else we can do.
We understand that you’re more familiar with the other guys,
because they’ve been around for many years. But rest assured,
when you choose us, you are walking through the door of a new era.
 
Because we’ve never met, you may not understand why we don’t
feel quite right about tackling the market with aggressive prices and
overwhelming promotions. It’s as simple as this: we don’t think we
need to prove ourselves through talk. We believe that the best things
in life exceed expectations and shatter doubts, and are not proven
through mere words. We simply want you to be so enticed by
affordable prices and unbeatable quality that you’ll veer away from
the familiar.
 
Let’s discover new frontiers together and make the world just a little
bigger today. We’ve already unlocked the door to a new era. Now,
it’s your choice to walk through it. Decide Hisense.
Hisense Introduction
Hisense is a large electronic information industry corporation of China
founded in 1969 and owns Hisense Appliance and Hisense Kelon Appliance
these two listed companies. Furthermore, Hisense is the only enterprise
group in China which has three well-known trademarks as Hisense, Kelon
and Ronshen at the same time.

Hisense adheres to the development strategy as “Technology Support,


Steady Operation” and sustains healthy development by taking optimized
industrial structure as the base, technological innovation as the drive force,
capital operation as a leverage. In the 21st century, with powerful R&D
strength and excellent internationalized management team, Hisense has
speeded up the pace of industrial expansion and formed an industrial
structure including digital multimedia, home appliances, communications,
intelligent information systems, modern real estate and service.

Multimedia Home Information


Products Appliances Communication
Products

Commercial Real Estate and Mould and


Equipment Property Management Industrial Design
CONTENTS
Customer First, Service Foremost Technological Hisense

Focus on Today's Requirement -09- High Technology Support Platform -21-


Why Choose Hisense VRF Solutions -11- Intelligent Operation, Great Reliability -29-

Strict Quality Control -12- Easy Installation, Easy Maintenance -33-

Comprehensive Air Conditioning Solutions -13- High Intelligent Control System -35-

Overall Support for Customers -15-

Benefit for End Users -18-

05
Product Line-up Optional Parts

Hi-FLEXi Series -49- Branch Pipe -147-


Hi-Smart Series -103- Switch Box -150-

Indoor Unit -111- Drain-up Mechanism Kit -150-

Total Heat Exchanger -139-

AHU Solutions -145-

06
Customer First,
Service Foremost

07
Focus on Today's Requirement
Why Choose Hisense VRF Solutions
Strict Quality Control
Comprehensive Air Conditioning Solutions
Overall Support for Customers
Benefit for End Users

08
Focus on
Today's Requirement
Focus on Energy Conservation
Customer First, Service Foremost

According to the statistics from authority, building energy consumption takes up 35% ~50% of the main energy consumption. And
air-conditioning is a big consumer of building energy consumption, taking up about 40% ~60%. So it is very important to effectively
reduce the air conditioning energy consumption.

Hours Hours Total % Ratio of Total Time


200 100%

As for commercial space, most of the time, only some of 80%


160
the indoor units are in operation. Therefore, the
capability of energy-saving depends on the efficiency 120 60%

under partial load. Hisense VRF has a remarkable 40%


80
performance under partial load, which achieves better
energy saving and reduces energy consumption. 40 20%

0 0%
30% 40% 50% 60% 70% 80% 90% 100%
Central Air-conditioning Load Distribution of an Office Building During a Cooling Season

Hisense heat recovery Hi-FLEXi R series realizes simultaneous cooling and heating through perfect combination of DC inverter
technology and heat recovery technology, which realizes a 20% energy saving compared with traditional air conditioning, achieving
lower running cost.

Focus on Environmental Protection

R410A Refrigerant, Protect Ozone Layer


Hisense VRF products adopt efficient and reliable environment-friendly refrigerant R410A , which
is non-toxic to humans and will not damage the Earth's ozone layer, create a comfortable, clean
living environment for you. Environment-friendly Refrigerant

RoHS Reaction
Actively respond to Europe RoHS directive, control the use of hazardous substance strictly. RoHS
stands for Restriction of Hazardous Substance Directive, which specifies six substances ( Lead
(Pb), Mercury (Hg), Cadmium (Cd), Hexavalent chromium (Cr), PBDE or PBB ) banned from using in
electrical and electronic equipment. Hisense actively reponded to RoHS directive and implement-
ed a series of programs and measures, which aims to preserve human health and ensure that the
recycling and treatment of wasted eletronic and electrical equipment meet the environmental
stardard.

09
Focus on
Today's Requirement
Focus on Healthy Indoor Environment

Customer First, Service Foremost


Sophisticated Antibacterial Technology
Hisense high performance antibacterial filter adopts double-layer antibacterial structure
( long-acting antibacterial filter and high performance antibacterial filter ), which can
purify indoor air, restrain and kill bacteria, as well as inhibit the reproduction of bacteria
and mould on the high performance filter material and maintain fresh air in room.
Double-layer Antibacterial Filter

Fresh Air Introduction


Hisense VRF system can introduce outdoor fresh air into indoor space through All Fresh Air Indoor Unit and Total Heat Exchang-
er, which constantly remains the indoor oxygen content and interior freshness and creates a healthy environment for people’s
live.

Noise Control
The creation and use of mechanical equipment has brought human prosperity and progress, but noise pollution has been increasingly
strong in recent years. As we all know noise pollution has lots of negetive effects on our relaxation, work, study, and even on our
health, so noise control is becoming more and more significant. Hisnese realizes excellent noise control through a series of improve-
ment on compressor, fan motor and fan structure. The noise level of outdoor units has been reduced dramatically, and the lowest
noise level of Hisense indoor units is down to 21dB.

20dB(A) 21 dB(A) 30 dB(A) 40 dB(A) 70 dB(A)


※ In bedroom noise of 30dB (A)
Whisper In operation Quiet library Bustling street
does not affect sleep

※ Noise level of Slim Ceiling Ducted type AVE-07/09* at low speed.

10
Why Choose
Hisense VRF Solutions
High Technology and Outstanding Operation Performance
Customer First, Service Foremost

Based on high technology and manufacturing ability, Hisense has been developing rapidly these years. And Hisense has gained great
reputation in the commercial air conditioning field. Hisense adopts strict quality control standard during the manufacturing and test
process, ensuring best quality of products. Hisense VRF’s outstanding operation performance and system reliability ensures low running
cost over its entire service time.

Comprehensive Product Lineup


Hisense VRF provides a comprehensive product lineup including air cooled outdoor unit, water cooled outdoor unit, meeting different
application conditions. And Hisense also provides many types of indoor units with more than 100 models, you can choose the suitable
indoor unit according to the practical situation and decoration style, creating personalized living and working space.

Modular Combination Design Gives Greater Flexibility


Hisense VRF’s modular combination design provides a greater flexibility to balance heat loads in different parts of the building. And the
double backup function ensures the system has certain output when malfunctions occured in one modular of the combined system. In
contrast, a chiller unit runs the whole system, which requires an expensive backup unit to avoid a complete stop. So if it fails, the total
system will stop working. VRF products also offer extended piping lengths so that the system can be designed flexibly to satisfy
buildings with different sizes and structures.

Higher Space Efficiency


VRF system is much more space efficient than a chiller unit, because it doesn’t require special operation room and much less floor space
is needed. It is estimated by authority that a 2 or 4 pipe fan coil system could take up around 7% of the overall lettable floor area of the
building, while a comparable VRF building would take up between 3-5% . This means that Hisense VRF allows developers to maximise
the rental space. Hisense also have outdoor units with different structures to meet different installation spaces, which greatly improve the
installation flexibility. The most flexible and efficient use of office space will be really helpful to win more projects in this highly competi-
tive market.

Easier Transportation and Installation


The compact and light weight design make Hisense VRF much easier to be transported and installed. The outer dimension of the largest
base modular is 1,720×1,210×750mm with a floor area of 0.9m2 and a weight of 318Kg, so the outdoor units can be transported separately
by the elevator, which improves the installation efficiency dramatically and lower the installation cost.

Intelligent Control System


Industry-leading inverter control technique is adopted in Hisense VRF products, so the control accuracy and reliability of the inverter are
greatly improved. There are multiple thermal sensors in the system, which will make real-time detection and feedback, so the tempera-
ture will be precisely controlled.
Hisense VRF products are compatible to BMS and Smart Home control system, which makes it much easier to realize central control and
monitoring. Air conditioning electric charge allocation system helps the building owners and users to monitor the energy consumption
and better expense control.
There are various intelligent controllers for selection, realizing more intelligent and convenient control.

11
Strict Quality Control

Hisense's production base is located in Hisense Information Industrial Park in Qingdao Economic Development Zone with a total area of

Customer First, Service Foremost


about 80,000 square meters. The annual output is more than 1.1 million units.
Hisense possesses state-level technology center. With the discipline of “Technology Oriented”, the research and development group
has been dedicating itself to improvement of product features and new technologies, by developing and growing stronger constantly,
the superb manufacturing process and technical level making Hisense at top level in the industry all the time.

Computer Simulation Development---the Most Advanced and Engergy


Saving Development Mode
In Hisense, the most advanced computer simulation technology is applied to all the new products. From the original design,
modeling to the later-stage performance test and any other necessarity till the finally product is formed. This development mode not
only accelerate the delevoping process, but also can reduce plenty energy consumption during the developing stage.

Excellence-led Manufacture Mode---Efficiency and Energy Saving


To realize the smooth assembling and zero-stock of spares, Hisense conducts the excellence-led manufacture mode to guarantee
the high quality, high efficiency as well as low energy consumption. Make real low-carbon product.

Strict Quality Control and Component Test---High Quality, High


Efficiency and Low Energy Consumption
Hisense applies full range of Japan imported inspection facility aided by extremely strict quality inspection system and standard to
guarantee the reliable quality of every single components of any machine and offer the end users a green life with superior quality
product.

12
Comprehensive Air
Conditioning Solutions
Air Cooled Outdoor Systems
Customer First, Service Foremost

Heat Pump - for Either Heating or Cooling Operation From One System

G series
Latest Full DC inverter series with large capacity range, realizing significant improvement in
operation efficiency under partial load.
Reliable operation and intelligent control make Hi-FLEXi G series a perfect choice for your air
conditioning solution.
Compact structure and light weight, making it much easier for transportation and installation.
8~54HP

M series
Advanced multi-split technology improves the system performance and energy efficiency.
Flexible design and installation provides better air conditioning solution for workplace, leisure and
living space.

8~48HP

C series
Hi-FLEXi C series aim at improving the comfort of space; every detail is fully considered in the
process of design and installation, accordingly bring you completely new space experience.
Front flow structure greatly improves the flexibility in installation.

8/10/12HP

Heat Recovery - for Simultaneous Heating and Cooling Within One System

R series
Realizing simultaneous heating and cooling operation within one refrigerant system, which not only meets
various requirements of different customers, but also contributes to energy conservation.
Flexible design and installation provide better air conditioning solution for workplace, leisure and living
8~54HP space.

Water Source Application Systems

W series
Wide application ranges include surface water circuit, underground water circuit, seawater source, urban
sewage source, soil source.
Allows heat recovery within one system because of the storage of energy in the water circuit.
3~20HP Suitable for multi-story and large building due to the many possibilities of water piping.

13
Comprehensive Air
Conditioning Solutions

Customer First, Service Foremost


Hisense Mini VRF System

L series
Hi-Smart L Series, household central air conditioning system, is specially designed for medium and large
high-end real estate. The outstanding appearance and function design, the application of leading technology
and high quality components make it a perfect choice for users.
4/5/6HP

E series
Hi-Smart E Series, household central air conditioning system, of which the compact outdoor units bring
high flexibility of installation and maintenance, and with the light and slim indoor units creates an elegant
and high taste domestic environment.
3/4/5HP

Fresh Air Ventilation System

All Fresh Air Indoor Unit


All fresh air indoor unit is an independent ventilation device with cooling and heating source, it can provide
plenty of fresh air to the house to guarantee the air quality, preventing the cross infection. The air flow rate is
660~6,000m /h 3 from 660m3/h to 6000m3/h, which can satisfy the need of large space.

Total Heat Exchanger


The total heat exchanger realizes the heat exchange between supply air and return air, realizing heat
recovery and ventilation without increasing air conditioning load.
The outdoor fresh air is filtered by the filter equipped in the unit, and then the cool or warm fresh air is
150~5,000m 3/h
transported to every room through the air duct.

Wired Controller

AHU Solution for Air Handling Applications


Control Box

Expansion
Valve Box

AHU
The Hisense AHU-KIT can integrate external heat exchangers of air handling units (AHU) into a Hisense
Wired Controller
VRF system to be used for air conditioning, which can provide more flexible air conditioning solutions and
Wired Controller
save more renovation cost in the building air conditioning renovation.

4~20HP

14
Overall Support
for Customers
Echoing the service idea of "Customer First", Hisense is making efforts to provide overall support to our customers, including
Customer First, Service Foremost

product promotion, air conditioning solution design, installation and commissioning, maintenance, etc. Meanwhile, Hisense has
professional training team, related training facility and on-line training platform to conduct a comprehensive training on products, AC
solutions design, installation and commissioning to our customers.

New Product Training and Promotion


Before any new product is launched into the market, we will provide detailed product specification, related promotion material as well as
related training courses to help our customers have an overall understanding on the new product.

Air Conditioning Solutions Design


A good design is the foundation of installation and commissioning. Hisense has a special department--Customer Suppport Department,
to offer VRF solutions with a series of professional designing softwares ( Selection software, Design software and CFD software ).
Hisense will give a professional VRF solution in a rapid period when customers pass down their requirements.

Support For Installation and Commissioning


VRF can run stably and reliably only if it is installed correctly and regularly. Hisense is very strict with the product quality control as well
as the installation. All the installers must attend and pass the specific training to get authorization to install our machines and we have
standard installation video and billboard to assist. Besides, we will dispatch professional technicians if necessary to give guidance and
supervision to guarantee standardization of the installation and commissioning.

15
Overall Support
for Customers
Selection Software

Customer First, Service Foremost


With the philosophy of All for Users, Hisense developed a Central Air Conditioning Selection Software which not only helps users to
choose proper Hisense equipment but also to do the central air conditioning system design work.
This software makes the specialized central air conditioning project design work more simply and realistic for nonspecialist. Whether you
are a consultant or a salesman, you can work out a systematic piping and wiring diagram with its user-friendly interface. Furthermore, a
quick quotation of a project can be provided with the selection of equipment and installation material.

Project Information Indoor Unit Selection


Project information input Room information input
Choose power supply Cooling and heating load calculation
Choose temperature condition Automatic & manual indoor unit selection

Outdoor Unit Selection Capacity Correction


Choose connection ratio Pipe length and height difference input
Match indoor units and outdoor units Indoor and outdoor unit correction
Automatic & manual outdoor unit selection Poor capacity warning

Piping Diagram Wiring Diagram


Automatic & manual outdoor and indoor unit pipe connection Power and communication
Branch pipe selection cable connection
Segmental pipe length input Cable size calculation
Automatic connection error warning Terminals connection
Pipe size calculation Controller connection

Central Control Diagram Reports Output


Central controller connection
BMS diagram

16
Overall Support
for Customers
Data Collector
Customer First, Service Foremost

Main Function
Hisense VRF test run
Recognize warning and error
Maintenance and monitoring
Central control test

Collector Software

.....
AC system
Power supply
cable USER

ble
Network Cable
..... USB Cable
AC system

Data Collector

..... Shielded twisted pair cable


AC system

Note: The data collector can be powered by the USB, but if it needs to use it for a long time, we recommend to use more stable external power supply.

Power Supply DC12V or USB power supply


Power Consumption Below 1.5W
Dimensions L×W×H: 180mm×110mm×40mm
Weight 0.55kg
Wire range Less than 1000m
Connected IDU NO. 128 IDUs
One checker software can only be connected to one checker hardware.

17
%HQHßWIRU(QG8VHUV
Precise Temperature Control

Customer First, Service Foremost


Hisense indoor units adopt 2000-Steps electronic expansion valves, which can make precise refrigerant flow adjustment automatically
according to the actual load of indoor units with more accurate temperature regulation. There are multiple thermal sensors in the system,
which will make real-time detection and feedback on the outdoor temperature, indoor temperature and outlet air temperature etc. The
temperature is maintained within 0.5℃ of the set temperature.

Top-class Low Noise Level in Operation


The lowest noise level of Hisense indoor units in operation is down to 21dB (A), so they create great comfort for end users while meet the
common air-conditioning demand.

Various Types of Indoor Units for Selection


Hisense Hi-FLEXi and Hi-Smart series provide a wide selection of indoor units for different spaces and decoration styles, creating
personalized living space.

Intelligent Controls
Hisense provides various controllers and control schemes, which helps end users enjoy the great convenience brought by the improve-
ment of technology while meets the common air conditioning demand.

18
Technological Hisense

19
High Technology Support Platform
Intelligent Operation, Great Reliability

Easy Installation, Easy Maintenance


High Intelligent Control System

20
High Technology
Support Platform
Advanced Technology is The Cornerstone of Hisense VRF
Technological Hisense

1 2
3

1 New Efficient Propeller Fan 2 High-performance Heat Exchanger 3 Dc Fan Motor

Compact structure
Efficient inner screwed copper pipe Efficient DC drive
Better dynamic balancing
Newly developed high efficiency fin Smooth operation and low noise
High efficient and low noise

4 DC-Inverter(DIP-IPM) 5 Super-cooling Refrigerant Cycle 6 High


h Pre
Pressure Chamber Scroll Compressor

Two-stage supper cooling technique and


High integrated circuit design
efficient subcoolng heat exchanger help New scroll compressor
High performance and high efficient
increase the super-cooling degree and Stable, reliable and efficient
High-accuracy control
improve cooling capacity

21
High Technology
Support Platform
New Scroll Compressor

Technological Hisense
Comperssor Suction Line
Comperssor Discharge Line
Refrigeration Oil Flow Line

Asymmetric scroll
disc

Inner oil separating


structure
Supply oil according
to pressuredifference,
more stable

DC variable speed
motor
Big silencing chamber,
lower noise

High Pressure Low Pressure


New Scroll Compressor Chamber Compressor Chamber Compressor

Exclusive Asymmetric Scroll Technology


The asymmetric scroll structure of compressor effectively helps reduce the refrigerant gas leakage loss in the process of suction and
compression, enhances operating efficiency and reliability.

Asymmetric scroll: the time difference between the suction of outside Symmetric scroll: the outside chamber and inside chamber end gas
chamber and inside chamber is 180°; The pressure of outside chamber suction at the same time, the pressure of outside chamber and inside
and inside chamber are different. The pressure distribution in chamber are equal. The pressure distribution in compressing
compressing chambers are asymmetric. chamber are symmetric.

Inside Chamber Pi=Ps


Achieve Suction

Reduce Suction Loss


and Leakage Loss Inside Chamber Pi=Ps
Outside Chamber Po>Pi Outside Chamber Po=Ps
During Compression Achieve Suction
High Efficient

22
High Technology
Support Platform
DC Inverter-driven Compressor Motor
By the use of DC motor, the performance is improved at around 20 ~ 40Hz where the operation time of the inverter compressor is
Technological Hisense

longest. Meanwhile, the rotor of compressor's motor is divided into two parts to suppress electromagnetic interference (EMI) which
achieves low noise.

Rotor Shape Optimized Neodymium Magnet Used Motor Efficiency (%)

95 DC Motor
·High Efficient
·Eliminate Peculiar ·Low Height
Electromagnetic ·Low Copper Loss
·High Efficiency AC Motor

7200(rpm)
3600
DC Motor Rotor Centralized Winding Stator 2400
1200
0

180°Sine Wave DC Inverter-Driven Technique


The application of advanced sensorless three phase vectoring control technique on permanent magnetism synchronous motor ensures
the output current of DIP-IPM DC inverter to be a smooth sine wave curve, and accordingly enables motor to operate smoothly with
efficiency dramatically increased. At the same time, both harmonic current and electromagnetic noise are suppressed.

30° 120° 60° Current Current


180° 180°
120° 120°
Sine wave
Square Wave
Voltage
Time
Time Voltage

Conventional Control Mode 180° Sine Wave DC Inverter-Driven Technique

Precise Room Temperature Control


The operating speed of DC motor in compressor can be adjusted continuously and freely relating to the variability of system capacity. This
technique integrated with auto-adaptive control technique automatically adjusts capacity output according to actual air conditioning load
in order to achieve a smoother curve of temperature fluctuation to satisfy higher requirements of coziness.

Load% Load%

Capacity Output Capacity Output


Indoor Load Indoor Load

Hisense Precise Inverter Control Time(h) Conventional Inverter Control Time(h)

23
High Technology
Support Platform
Multiple Oil Circuit Protection
Oil balance between outdoor units is realized through two-stage oil separation technology, oil-return technology, and oil balancing between

Technological Hisense
modules, which ensures more secure and reliable operation of the system.

The first-stage oil separation The second-stage oil separation


Make first-stage oil separation through efficient oil separation A small amount of oil discharged from the compressor is separated by

structure inside high-pressure chamber compressor, only a small the second-stage oil separation through large-capacity, high efficiency

amount of oil is brought out of the compressor. centrifugal oil separator, the separation efficiency can be over 99%.

First-stage oil separation Second-stage oil separation

The First-Stage Oil-Return Operation


Outdoor unit 1 Outdoor unit 2
The accumulator adopts porous oil return technology
4
with a built-in efficient fine strainer; it not only ensures
the oil balance between the compressors within the
module, but also plays a role in the oil balance between 3 2

the modules.
1

Accumulator

The Second-Stage Oil-Return Operation


The system implements oil-return operation based on the compressor frequency and Oil return
operation
corresponding operation time, which avoids the oil retention in the indoor heat exchanger Compressor
Frequency
and outdoor heat exchanger when the system is running at low load for a long time, and
avoids compressor failure due to lack of refrigeration oil. The oil-return operation time is High

only 60 seconds, after the oil-return control, it will automatically return to the previous Time
operation state.
Z
Low :
In winter under heating mode, the oil return operation is implemented without changing to Z

the cooling, which guarantees the heating effect.

24
High Technology
Support Platform
Oil Balancing Control Between Outdoor Units
Through adjusting the relationship between the amount of discharge oil and return oil in the compressor, accumulator and the
Technological Hisense

oil separator, it can realize automatic balance of lubricants between the various outdoor units without oil balance pipes, avoid
fluctuations of system pressure and temperature caused by oil balance pipe mode, and simplify the construction and improve
the operational stability and comfort of system.

Without oil balance piping in outdoor unit, making


the oil return more stable, more efficient, and more
convenient for installation.

Without oil
Liquid pipe balance pipe

Gas pipe

New Type Efficient Heat Exchanger


New type high-performance heat exchanger adopts efficient thermal conductive Φ7.0mm copper pipes and new type fins, which
reduces the air-flow resistance, realizes better heat exchange effect, more sufficient, and improves the heat transfer efficiency
considerably. Furthermore, the amount of frost on heat exchanger will decrease quickly in winter, which improves the heating effect .

Optimized refrigerant circuit design


Through specially designed refrigerant flow, the efficiency of heat exchanger is more optimized.

Common refrigerant circuit Optimized refrigerant circuit

Gas Gas Liquid


Liquid
refrigerant refrigerant
refrigerant refrigerant

Gas Liquid Gas


Liquid phase
Liquid phase

Gas phase
Gas phase

refrigerant refrigerant refrigerant


Gas-liquid Liquid
Gas-liquid refrigerant
mixed phase mixed phase
Gas Liquid Gas
refrigerant refrigerant refrigerant

Increase the proportion of liquid


refrigerant in the heat exchanger to
improve heat transfer efficiency
Gas-liquid Liquid refrigerant
Gas refrigerant
mixed phase

25
High Technology
Support Platform
Stepped Efficient Heat Transfer Fins
Adopt new type fins and copper pipes which can improve the heat transfer efficiency

Technological Hisense
Previous fins The latest developed fins Hierarchical diagram of
hydrophilic aluminum foil

Lubricating layer
Hydrophilic coating
Efficient inner screwed
Corrosion-resistant coating
copper tube
Ő Fin

Ő
Overlapping section Overlapping section
surface of fins surface of fins  Not easy to frost in heating mode;
 Slow down the corrosion of heat exchanger by corrosive gases;
 Destroying the surface tension of water droplets accelerates the

Wind direction Wind direction down flow speed of defrost water or condensate water and
Thick Thin improves the air conditioning performance.

Improvement of Heat Transfer Reduction of Air Flow Resistance


Heat Transfer Coefficient

Air Flow Resistance

Approach Stream Velocity Amount of Frost

Two-stage Supper-cooling Circulation


A sub-cooling section is designed in the heat exchanger of outdoor unit to realize the first stage supper-cooling. Furthermore, a high
efficient recooler is applied to achieve the second-stage supper-cooling. The total supper-cooling degree is up to 27℃.

Two-stage super-cooling cycle diagram 2-stage super-cooling pressure enthalpy diagram

First stage of
super-cooling

Second stage of
super-cooling The increased cooling
Heat exchanger capacity in super-cooling
super-cooling section cycle
Sub-cooler
○ The two-stage super-cooling cycle improves cooling capacity;
○ The pressure loss of the refrigerant flowing in the pipe is reduced
○ The Increased super-cooling degree promotes the stable operation
of the electronic expansion valve; Cooling capacity
○ The increased super-cooling degree helps increase the total piping length.

26
High Technology
Support Platform

Intelligent Defrosting Mode


The outdoor unit adopts outdoor temperature sensor and heat exchanger temperature sensor to make variable-parameter defrosting,
Technological Hisense

accurately grasp the defrosting opportunity, and significantly reduce the amount of frost, only 1/3 of that under ordinary defrosting mode.
Meanwhile together with unique bottom anti-frost design structure, “2 in 1” heat exchanger, it can ensure that there is no frost at the bottom
of outdoor heat exchanger during winter heating. When defrosting, the mixture of ice and water left along the fins is heated fully to liquid
and discharged through the bottom drain hole, so as to avoid accumulation of frost at the bottom leading to poor heating performance.

Hisense optimal defrost mode


Defrosting
Heating operation Heating operation

Little frost Still not much frost Little frost Still not much frost

Heating
Heating operation Heating operation Heating operation Heating operation
operation

Traditional defrosting mode


Heating operation Heating operation Heating operation Heating operation Heating operation
Bottom anti-frost design when heating

Traditional multi-split AC defrosting mode only refers to Time and Temperature parameter , besides these, Hisense adopts the pressure
defrosting mode, which adopts the pressure sensor to get the pressure signal and completes the variable parameters defrosting
operation through the Pressure, Temperature and Time parameter.

Rapid Heating Start-up


Combining the soft start of DC inverter compressor and rapid start of fixed speed compressor, the system can achieve 100%
heating capacity output instantly and quickly meet the air-conditioning demand. (Taking 460.6KBtu/h unit as an example)

HP

Need about 90 seconds to reach 100%


capacity output (Data of 48HP Model)

90 5 10 15 20 25 min
seconds

27
High Technology
Support Platform

Precise Temperature Control

Technological Hisense
Temperature Sensing Refrigerant Flow Control
There are multiple thermal probes in the system, which will make Indoor units adopt microcomputer electric expansion valve
real-time detection and feedback on the outdoor temperature, with 2000-stage automatic adjustment function, which can
indoor temperature and outlet air temperature etc, the system make precise flow adjustment automatically according to
output is adjusted by the master controller. the actual load of indoor units with more accurate
temperature regulation and better energy efficiency.
n an

Unique Design
outlet air temperature sensor

2000-Stage Electric Expansion Valve

Precise Room Temperature Control


Hisense sets temperature sensors on air outlet /air inlet of indoor units and remote controller, and adopts microcomputer control
2000-pulse high precision electronic expansion valve to adjust refrigerant flow rate, high precision electronic expansion valve to adjust
refrigerant flow rate, which can maintain the room temperature within 0.5℃ of setting temperature and satisfy the indoor comfort
requirement.

Conventional
Temperature Control
Too Hot

Most Comfortable
±0.5
Comfortable

Too Cold Hisense


Setting Temp. Temperature Control

Condensed Water Protection Function


Float switch is as a standard part in Hisense indoor unit. To protect the ceiling from getting wet or soaking, the float switch will
work to stop the indoor unit, when condensed water can’t be drained in time because of blockage in the drain pipe or drain pump
breakdown.

28
Intelligent Operation
Great Reliability

25-Step Fan Speed Control


The DC variable-speed motor is adopted in outdoor unit, which results in efficiency promotion and power input reduc-
Technological Hisense

tion. The outdoor fan speed can be adjusted by 25 steps.

25-step

Air Streamline Grill

 The stability of discharge pressure and suction pressure of compressor is assured


 The stability of flow (capacity) dynamic allocation of indoor unit is assured
 Quick response of control system is improved, accordingly the system stability,
durability and reliability are assured
Efficient Axial Fan

Outdoor Unit Noise Control


Adopt high quality scroll compressor Noise Deadening of Fan Motor
Sophisticated manufacturing technology, with The material of fan motor is cast aluminum. The motor bracket is
characteristics of little vibration and low noise. of non-resonant hanger structure, which ensures stable motor
performance, lowers vibrating noise.

New Efficient Axial Fan Low Noise Mode at Night


The newly developed efficient axial fan with new blade shape The outdoor unit has a peculiar function of night-shift setting,
helps decrease turbulence around. It is made of special material which reduces the noise level by Max. 15dB ( 76KBtu/h ) when in
which has an obvious effect to absorb vibrating noise and full-load operation.
minimizes the “Buzz” dramatically.

Load Change Curve

Peak Temperature

Temperature Change Curve

Noise Change Curce

New Blade Optimized Radial Airflow Angel

29
Intelligent Operation
Great Reliability
Automatic Reset Function
The operating data can be recorded automatically as power failure occurs. When the power supply is restored, the system can fulfill

Technological Hisense
automatic start-up ( Manual operation is also allowed ), the previous operation mode can be renewed without being reset, which brings
more intelligent and considerate service to users.

The system operates normally After power off ( memory storage ) Restore to the previous state when
before power off system stops running the power supply is recovered.

01 02 03

Rotational Operation to Distribute Load of Outdoor Units


Regulating the operation time of each outdoor unit leads to load reduction on compressors. Therefore, outdoor unit endurance is improved.

ON OFF OFF OFF ON OFF

Last Time This Time

Rotational Operation

OFF OFF ON

Next Time

30
Intelligent Operation
Great Reliability
Double Back-up Operation Function, Double Service Guarantee
The back-up operation function that prevents the system from coming to a complete stop can be fulfilled in two ways.
Technological Hisense

As one of outdoor units breaks down, the rest of outdoor units in the same refrigerant system can turn to operate urgently ( more
than 154KBtu/h system practicable ).
As one compressor is failed, the other compressor in the same outdoor unit can be set to emergency operation mode.

Standby Operating Failed


Status Status Status

Compressor Backup Outdoor Unit Backup

Central air conditioning system is working under partial load most of the time; Hi-FLEXI G series optimizes the software and system especially
for partial load, making the system more energy efficient under partial load condition.

Smart and Precise Unit Capacity Allocation ( For Full DC Inverter Series )
Tests show that multi-split air conditioning units are most efficient under 40% 70% partial load condition, and the power consumption is
lowest. Take 20HP units ( double module ) as an example, when the units operate under 12HP load, the load distribution of each module:
common product is 10HP ( full load ) +2HP ( ultra-low load ); Hisense Hi-FlEXI G series is 6HP+6 HP ( intermediate load ).
~

VS
Hisense Hi-FlEXI G Series: Traditional product:
d
The efficiency will be the highest and the power consumption will be In normal operation, the module combination is operated at full load + ultra-low
lowest when each module unit is working at 40% - 75% partial load. load, which influences the service life of units and consumes more power.

31
Intelligent Operation
Great Reliability

Demand Mode ( For Full DC Inverter Series )


The intelligent demand mode can adjust the air conditioning operation automatically according to peak-valley requirements of electricity.

Technological Hisense
It achieves balance between the comfort and energy saving while meeting the power demand for daily work.

When the power consumption value exceeds


the set range, it will be restricted
Power Saving 20%
Power Consumption

t
cos
ting
era
Op
Setting Power
Greater efficiency within the set range

Operati
Daily running time ng cost
Morning Night

For mode settings, please contact your local service engineer. The output capacity of the unit at this moment is less than the rated value
because operating power is limited.

Fan Protection Function


In case that the external forces make outdoor unit fan rotate inversely, the fan will be stopped first when the air conditioner is started, and then
the fan will rotate normally in accordance with procedures to protect the blades from damage.

Convention Fan Protection Function

External forces make the fan Instantaneous reverse rotation with sudden
counter-rotating increased torque may cause damage to the External forces make the fan counter-rotating Stop the fan before start Forward rotation with
blades the unit small starting torque,
protect fan blades

Anti-snow Function
Connector Outdoor Unit PCB SS3:Snow sensor
In the event of bad weather like snowstorm, even if outdoor unit
SS3
is not operating, the sensor for snow on outdoor PCB can still be
shorted because of natural snowflake, then the outdoor fan Power Supply

motor starts rotating at full speed to prevent outdoor unit from


X1
being covered by snow. When air conditioning starts up, the fan
Control Circuit
motor will turn to normal speed. Anti-snow Function Graph
*This Function Needs Optional Accessory

32
Easy Installation
Easy Maintenance
Compact Structure and Light Weight Design,Easy Installation
Easy and flexibility of installation are further enhanced by adopting the outdoor unit’s light weight and compact design.
Technological Hisense

Series Size(mm) Weight(Kg)


Hi-FLEXi G series 1,720×1,210×750 318
Hi-FLEXi M series 1,720×1,210×750 310
Hi-FLEXi R series 1,720×1,210×750 318
Hi-FLEXi W series 1,000×780×550 160
Hi-FLEXi C series 1,650×1,100×390 171
Hi-Smart L series 1,380×950×370 97
Hi-Smart E series 800×950×370 78

The maximum size and weight of the basic module of each series. Model Outer Dimension

Layered Installation, Flexibly Corresponding to High-rise Buildings


For high-rise buildings, machine layer can be left to place outdoor units, or machine room can be set up on each floor. By using
exhaust duct to exhaust the air, short circuit of return air can be avoided with long air exhaust distance, which ensures good
ventilation and heat exchange effects of outdoor units.

Temperature ℃
46.9443

45.4512

43.9582

42.4651

40.9721

39.4790

37.9859

36.4929

34.9998
Airflow Schematic Exhaust duct installation Layered installation effect picture

Automatic Addressing
System can assign indoor unit addresses without manual setting automatically, it is suitable for the use of multiple indoor units of large system.

One-touch Test Run


The one-touch test run can be operated at the outdoor unit side, and it can also be operated at the indoor unit side, which makes it
much earlier for the commissioning.

ON ON
Realizing test run
through the controller
at the indoor unit side Realizing test run
1 2 3 4 5 6 1 2 3 4 5 through the DIP-switch
at the outdoor unit
Cooling mode test run Heating mode test run
6 side.

33
Easy Installation
Easy Maintenance
Intelligent Operation

Technological Hisense
Hisense VRF system is highly intelligentized and has no requirement for machine room and operators,realizing much more flexible and
convenient control and lower cost.

Intelligent Operation Inspection


The 7-segment LED on the outdoor unit makes it easy to monitor and check
the details about the operating status, refrigerant temperature, pressure,
compressor operation frequency and time, error code and other factors for
maintenance, which makes both operation management and maintenance
more convenient.

Data Collector
Data Collector is designed to quickly inspect the units operating
status. Problems can be found out as early as possible, then
solution can be taken accordingly.

Anti-corrosion Treatment for Outdoor Units - Optional


The anti-corrosion treated outdoor units have been designed to provided corrosion resistance against acid rain and salt corrosion. If you
need the anti-corrosion type, please contact us.
High Intelligent
Control System
Hisense Mobile Intelligent Terminal
Technological Hisense

Main Function
ON/OFF control, operation mode, temperature
setting, air flow setting, louver setting. Wireless router

Operate according to a schedule.


Display the alarm code.
Contextual model function can be set, e.g. LAN
IPAD
Off Home model and Energy-Saving model.
Max.16 indoor units can be controlled.

HYJE-H01H

Adapter Specifications
Model name HYJE-H01H Isolation Voltage AC 3000V

Input voltage AC 110 ~240V 50/60Hz Operating temperature 0℃~40℃

Maximum operating current 10mA(220 V) Operating humidity 30%RH~60%RH

* The standard parts of this system includes the converter HYJE-H01H and the client control software HRM-G01 ( it can be downloaded and installed in
the APP STORE ), The IPAD is the registered trademark of Apple Inc.

35
High Intelligent
Control System
Various Controllers
Wired Controller: HYXE-J01H

Technological Hisense
Features:
4 inch large LCD screen with a resolution of 320×185.
HYXE-J01H
Functions are displayed in iconic form, more intuitive. (Touch keys)
Operation navigation, more convenient.
It can be used in main-auxiliary control mode or in concert with wireless receiver.
Various displaying settings: backlit control, contrast ratio setting, backlit displaying time setting, keytone setting, indicator light brightness
setting, clock setting, language switch ( Between Chinsese and English ).

Main Functions
Cooling/Heating/Dry/Fan/Auto Fan Speed/Swing Louver Temperature Setting Timer

Holiday Setting Weekly Setting Check Air Filter Cleaning Reminding

Error Code Display Error History Display Mode Lock Address Setting

Various Control Solutions Weekly Schedule Setting


Five different schedule timers can be set for each day of the week.

8
Temp. 27
27
27 C
25

25 C

8:30 10:30 15:30 17:30 Time

Indoor Unit Address Change


In the process of installation work,
indoor unit address can be changed
through wired controller HYXE-J01H.

Specifications
Model Name HYXE-J01H
Power Supply DC 12 ~ 17 V
Outer Dimension 120X120X16mm
Max. Connectable IDU Number 16

36
High Intelligent
Control System
Wired Controller: HYXE-F01H

Feature:
Technological Hisense

Fashion appearance with crystal panel and keys


Large LCD backlit screen
HYXE-F01H

Main Functions
Cooling/Heating/Dry/Fan/Auto Fan Speed/Swing Louver Temperature Setting Timer

One Touch Test Run Air Filter Cleaning Reminding Error Code Display Check

One-touch Test Run


The one-touch test run can be operated at the outdoor unit side, and it can also be operated at the indoor unit side, which makes it
much easier for the commissioning.

ON ON
Realizing test run Realizing test run
through the controller through the DIP-switch
at the outdoor unit
at the indoor unit side 6 side.
1 2 3 4 5 6 1 2 3 4 5
Cooling mode test run Heating mode test run

Specifications
Model Name HYXE-F01H
Power Supply DC 12~17 V
Outer Dimension 120X120X19mm
Max. Connectable IDU Number 16

Wired Controller: HYXE-A01H

Main Functions HYXE-A01H

Cooling/Heating/Dry/Fan/Auto Fan Speed/Swing Louver Temperature Setting Timer

Test Run Air Filter Cleaning Reminding Error Code Display Check

Specifications
Model Name HYXE-A01H
Power Supply DC 12~17 V
Outer Dimension 120X120X19mm
Max. Connectable IDU Number 16

37
High Intelligent
Control System
Wired Controller: HYXE-G01H

Technological Hisense
Features:
Compact structure with a size of 86×86mm.
Large LCD backlit screen, simple appearance. HYXE-G01H
Built-in wireless receiver under the panel, two kinds of control mode for selection.

Main Functions
Cooling/Heating/Dry/Fan/Auto Fan Speed/Swing Louver Temperature Setting Timer

Built-in Wireless Receiver Air Filter Cleaning Reminding Error Code Display Check

Compact structure design


Two Kinds Of Control Mode

86mm

86mm

Specifications
Model Name HYXE-G01H
Power Supply DC 12~17 V
Outer Dimension 86X86X12.4mm
Max. Connectable IDU Number 1

38
High Intelligent
Control System
Wired Controller: HYE-Q01/ HYE-L01

Feature:
Technological Hisense

Latest wireless controller with fashionable look.


Newly extended sleep mode and quiet mode.

Main Functions
Cooling/Heating/Dry/Fan/Auto Fan Speed/Swing Louver Temperature Setting Timer

One Touch Test Run Air Filter Cleaning Reminding Error Code Display Check

Sleep Mode Setting (HYE-L01) Quiet Mode Setting (HYE-L01)

Newly Extended Sleep Mode and Quiet Mode

QUIET
Press it to change to quiet mode. Repress it or “FAN” to exit.

SLEEP
Press it to change to sleep mode.
The default status is working in quiet mode for 8h. And in the first two hours, temperature will
increases 1℃/h in cooling mode, while decrease 1℃/h in heating mode. Also, we can reset the
sleep time and air flow in the sleep mode.

Time setting

60min.
Wide Control Angle 60min.

Cooling Operation 2C
Start temperature 1 C

Heating operation
Start temperature
1 C
2C

60min.
60min.
Time setting

Specifications
Model Name HYE-Q01 HYE-L01
Power Supply 2 AAA Batteries 2 AAA Batteries
Outer Dimension 125X55X16.5mm 148X60X17mm
Max. Connectable IDU Number 16 16

HYE-L01 can apply to all the indoor units, but it can only realize sleep and quiet function with the new wall mounted type.

39
High Intelligent
Control System
Receiver Kit for Wireless Control - Optional

Technological Hisense
Model Name Image Indoor unit Type Indoor unit Model

Ceiling Ducted Type(L) AVD07~54UXC(2)SBL

Ceiling Ducted Type(H) AVD07~54UXC(2)SBH

HYRE-VO1H Low Height Ceiling Ducted Tpe AVE22~71UXC(2)SBL

Slim Height Ceiling Ducted Tpe AVE07~14UXC(2)SGL

Floor Concealled Type AVH09 ~24UXC(2)SBA

HYRE-TO1H 4-Way Cassette Type AVC09~54UXC(2)SEB

Hotel Room Card Control - Optional

The "Room Card Control Function" of Hisense VRF indoor unit means control the on and off of the indoor unit through the room card.
When under function, the AC system is powered on. The room card can control whether the room lighting is powered on or off and also
can control the indoor unit on or off, which as a result can achieve switching off the lights and the AC and energy-saving by withdrawing
the room card when people leave.

Hotel Room Card Control Room Card

40
High Intelligent
Control System

Centralized ON/OFF Controller: HYJ-J01H


Technological Hisense

Features:

Large size touch-key control design. HYJ-J01H


Slim design with a thickness of 13mm
It can control up to 16 wired controller groups,realizing centralized ON/OFF control.

Main Functions Compact Structure Design Centralized ON/OFF Control


Group Control(ON/OFF)

Power Outage Reminder

Indoor Units Auto Login in

Error Reminder

Specifications
Model Name HYJ-J01H
Power Supply AC1Φ85~265V 50/60Hz
Outer Dimension 120X120X12.5mm
Max. Connectable IDU Number 128

7-Day Timer: HYDE-E01H

Main Functions HYDE-E01H

3 Periods Setting on Weekday Holiday Setting Two Modes of Timetable Timer

Specifications
Model Name HYDE-E01H
Power Supply Central controller supply/ Indoor unit supply
Outer Dimension 120X120X20mm
Max. Connectable IDU Number ---

41
High Intelligent
Control System
Central Controller: HYJE-D02H

Technological Hisense
HYJE-D02H

Main Functions

Cooling/Heating/Dry/Fan/Auto Fan Speed/Swing Louver Temperature Setting Error Code Display

Operation Monitoring Controller Disable Indoor Unit Selection Check

Hotel

Office & Lounge

Office & Lounge

Lobby

Specifications
Model Name HYJE-D02H
Power Supply AC1Ф,220V,50/60Hz
Outer Dimension 120X120X20mm
Max. Connectable IDU Number 160
Max. Connectable Remote Control Groups 64

42
High Intelligent
Control System

Building Management System


Technological Hisense

Compatible to multiple communication protocol of BACnet, RS-485 etc. Connectible to BMS or Smart Home System via HC-A64BNP or
HLRSCON all of which can connect to Max. 64 indoor units.

Real-time operation status monitoring for inquiry


Operation order from monitoring center

BACnet HC-A64BNP

BACnet
(Ethernet(LAN))
Intranet
Intranet
Central Monitoring BMS

HC-A64BNP UPS Fire Alarm Disaster Illumination


Prevention

Air Conditioning

Hisense Supply
Air Conditioning

Air Conditioning
Central Station

Running-state Monitoring / On-off Setting Operating Mode Setting Temperature Setting and Monitoring

Airflow Setting and Monitoring Alarm Monitoring and Code Display Communication Failure Display

Wireless Controller Permission/Prohibition Indoor Temp. Monitoring Filter Cleaning Prompting

43
High Intelligent
Control System

RS-485 HLRSCON

Technological Hisense
Outdoor Units Indoor Units
RS-485(232)network

Hisense

BMS

HLRSCON

Smart Home Controller

On-Off Setting Operating Mode Setting Airflow Setting and Monitoring Wind Setting and Monitoring

Temperature Setting Inlet Air Temp. Monitoring All Units On/Off Control Alarm Monitoring and Code Display

Converter Specifications

HC-A64BNP HLRSCON

Converter

Item

BMS connection BACnet RS-485

Power supply AC100~240V±10%(50/60Hz) AC100~240V±10%(50/60Hz)

Connectable central controller HYJE-D02H HYJE-D02H

MAX.number of connectable indoor units 64 64

Dimension(LX W XH) 240mm X 204mm X 70mm 171mm X 140mm X 43mm

44
High Intelligent
Control System

Hi-Dom Air Conditioning Management System


Technological Hisense

Hi-Dom air conditioning management system adopts communication bus connection, air conditioning indoor units are connected to
the computer through network converter; the system is all controlled automatically by a computer with powerful functions and simple
operation. One single computer control system can manage 2,048 indoor units.

Main Functions
Running-state Monitoring Access Control
Determine the Temperature Limit Automatic Operation According to Settings
Running Records Display Multifunction Alarm
Controller Prohibition Function Service Monitoring

Adapter

Indoor unit

Outdoor
O td U
Unitit

Assistant remote
Wired controller Wireless remote Master remote
controller
controller controller

Indoor unit

Monitoring
Center

ications
Commun
network
Wired controller Wired controller

Client Management Center

All the indoor units and outdoor units connected with one adapter comprise one communication BUS system .
Max.128 indoor units can be connected to a BUS system.
Max.16 adapters can be controlled by one computer.
Max.2048 indoor units are under control.

45
High Intelligent
Control System

Air Conditioning Electric Charge Allocation System

Technological Hisense
Hisense electric charge allocation system consists of meter reading system and air conditioning management system. In accordance with
the operation time and capacity output of indoor and outdoor units, the opening degree of EEV, the electric charge allocation software
allocates the total power consumption to each indoor unit.

Note:Due to different laws and regulations in different regions, Hisense electrical charge calculation software need to customize
processing in project according to the users' requirement.

Electric meter

Adapter

AC system
Power supply
cable

Adapter

Adapter
Network connector
AC system

Shielded twisted pair cable

AC system

Electric Charge Allocation System

Hi-Dom System Specifications


Model name Power Supply Dimension(mm) Charging Function
Adapter
HCCS-H128H2C1YM DC 12V 180X110X40 With charging function
(Hi-Dom)
HCCS-H128H2C1NM DC 12V 180X110X40 Without charging function

46
Product line-up

47
Hi-FLEXi Series
Hi-Smart Series
Indoor Unit
Total Heat Exchanger
AHU Solution

48
Hi-FLEXi G Series

Latest Full DC Inverter Series


All the compressors adopted in Hi-FLEXi G series are high efficiency high-pressure chamber scroll compressors.
Product line-up

Inverter Compressor
+
Inverter Compressor

Hi-FLEXi G series is the latest full DC inverter-driven multi-split central air conditioning product. It is the concentrated expression of
Hisense's R&D capacity and technical strength. Multiple advanced technology is adopted:
High efficiency high-pressure chamber scroll compressor
Latest DC inverter-driven control technique
Stepless fan speed regulation and fan production technology
Smart and precise unit capacity allocation technology
Intelligent Demand Mode control technology

Wide Operating Range


The system can run within a wide temperature range, the lowest heating operation can reach -23℃WB, ensure a good heating effect in
winter.

-23℃ WB +19℃WB

Heating operation range

-5℃ DB +50℃ DB

Cooling operation range

-25 -15 -5 5 15 25 35 45 55

49
Hi-FLEXi G Series

Stepless Fan Speed Regulation Technology


Full DC inverter series outdoor unit fan motor adopts DC inverter-driven motor which improves the motor efficiency by 40% and
reduces the input power significantly. The outdoor unit fan can achieve stepless speed regulation according to the ambient tempera-
ture changes

Product line-up
Streamlined air grille ◎Stepless frequency conversion adjustment of the fan
Fan speed
High 1050rpm

Stepless speed
regulation

Common speed
regulation
Low 0

◎The stability of discharge pressure and suction pressure of the


Efficient axial fan
compressor is assured;
◎The stability of the indoor unit flow ( capacity ) dynamic allocation
is assured and the fluctuation is reduced;
◎Quick response of control systems is improved, accordingly the stability,
durability and reliability of units are assured.

Smart and Precise Unit Capacity Allocation


Tests show that multi-split air conditioning units are most efficient under 40%~70% partial load condition, and the power consumption is lowest.
Take 20HP units ( double module ) as an example, when the units operate under 12HP load, the load distribution of each module: common
product is 10HP ( full load ) +2HP ( ultra-low load ); Hisense Hi-FlEXI G series is 6HP+6 HP ( intermediate load ).

VS
Hisense Hi-FlEXI G Series: Traditional product:
d
The efficiency will be the highest and the power consumption will be In normal operation, the module combination is operated at full load + ultra-low
lowest when each module unit is working at 40% - 75% partial load. load, which influences the service life of units and consumes more power.

50
Hi-FLEXi G Series

Extra-high External Static Pressure Design


Product line-up

Max. 80Pa

Adopt high-efficiency DC fan motor


The use of high-efficiency fan reduces energy consumption of the motor
Can achieve industry-leading level of external static pressure 80Pa
Max. 80Pa

The efficient axial fan is designed adopting CFD, finite element method, aviation dynamic fluid simulation analysis and other
advanced concepts; its air inlet angle and outlet angle are optimized; together with unique horn air vent design, the external static
pressure of outdoor unit is higher, which can better exhaust air and ensure smooth air flow.

Layered Installation, Flexibly Corresponding to High-rise Buildings

For high-rise buildings, machine layer can be left to place outdoor units, or machine room can be set up on each floor. By using
exhaust duct to exhaust the air, short circuit of return air can be avoided with long exhaust distance, which ensures good
ventilation and heat exchange effects of outdoor units.

Temperature ℃
46.9443

45.4512

43.9582

42.4651

40.9721

39.4790

37.9859

36.4929

34.9998
Airflow Schematic Exhaust duct installation Layered installation effect picture

51
Hi-FLEXi G Series

More Flexible Refrigerant Piping Work

Actual piping length: 165m


Height difference between the highest and lowest indoor units: 15m

Product line-up
Height difference between outdoor and indoor units: 70m ( when outdoor units are higher than indoor units )

Height difference between outdoor and indoor units: 90m ( when outdoor units are lower than indoor units )

Note:The recommended height difference between ODU and IDU: 50m when the ODU is higher than IDU; 40m when the ODU is lower than IDU
If the installation height difference is beyond the recommended value, please contact our technique engineer.

Max. Height Difference Between


Max. Piping Length: 165m Outdoor Units and Indoor Units: 70m
Total Piping Length: 1000m

Between 1st Branch


and Indoor Unit: 90m or less
Max. Height Difference
Between Indoor Units: 15m

Long Piping Length

52
Hi-FLEXi G Series

Outdoor Unit Specifications


Product line-up

8/10/12HP 14/16/18HP

Hi-FLEXi G Series HP 8HP 10HP 12HP 14HP 16HP 18HP


AC3Φ380 ~ 415V/50Hz AVWT-76UESRG AVWT-96UESRG AVWT-114UESRG AVWT-136UESSG AVWT-154UESSG AVWT-170UESSG
Model Power Supply
AC3Φ380V/60Hz AVWT-76U7SRG AVWT-96U7SRG AVWT-114U7SRG AVWT-136U7SSG AVWT-154U7SSG AVWT-170U7SSG
Combination
KW 22.4 28.0 33.5 40.0 45.0 50.0
Nominal Capacity
KBtu/h 76.5 95.6 114.3 136.5 153.6 170.6
Cooling Operation
Power Consumption KW 5.22 7.29 8.7 10.99 13.12 15.11
EER 4.29 3.84 3.85 3.64 3.43 3.31
KW 25.0 31.5 37.5 45.0 50.0 56.0
Nominal Capacity
KBtu/h 85.3 107.5 128.0 153.6 170.6 191.1
Heating Opeartion
Power Consumption KW 5.57 7.48 9.35 10.98 12.41 14.7
COP 4.49 4.21 4.01 4.10 4.03 3.81
Air Flow Rate m³/h 9,300 10,200 10,500 11,700 11,700 11,700
Outer Dimension mm 1,720×950×750 1,720×950×750 1,720×950×750 1,720×1,210×750 1,720×1,210×750 1,720×1,210×750
Packing Dimension mm 1,882×1,018×828 1,882×1,018×828 1,882×1,018×828 1,882×1,278×828 1,882×1,278×828 1,882×1,278×828
Net Weight Kg 224 225 227 312 315 318
Gross Weight Kg 237 238 240 327 330 333
Compressor Quantity 1 1 1 2 2 2
Condenser Fan Quantity 1 1 1 1 1 1
Cabinet Color Ivory White Ivory White
Gas Line mm Ф19.05 Ф22.2 Ф25.4 Ф25.4 Ф28.6 Ф28.6
Refrigerant Piping
Liquid Line mm Ф9.53 Ф9.53 Ф12.7 Ф12.7 Ф12.7 Ф15.88
Max. number of connectable IDU 13 16 19 23 26 26
Max. Piping Length m 165 165 165 165 165 165
Between ODU&IDU m 70(90) 70(90) 70(90) 70(90) 70(90) 70(90)
Height Difference
Between IDUs m 15 15 15 15 15 15
Noise Level dB(A) 56 57 59 59 59 60
Cooling ℃ DB -5 ~50 -5 ~50 -5 ~50 -5 ~50 -5 ~50 -5 ~50
Operation Range
Heating ℃ WB -23~ 19 -23~ 19 -23~ 19 -23~ 19 -23~ 19 -23~ 19

Note:
1. Rated cooling capacity and rated heating capacity are tested in the following conditions:
Cooling conditions: indoor air inlet temperature: 27℃ DB 19℃ WB, Outdoor air inlet temperature: 35℃ DB, pipe length : 7.5m, pipe height difference: 0m
Heating conditions: indoor air inlet temperature: 20℃ DB, Outdoor air inlet temperature: 7℃ DB 6℃ WB, pipe length: 7.5m, pipe height difference : 0m
2.The above noise values are measured in the anechoic chamber without reflected echo, therefore the impact of the reflected echo must be included at the scene.
3.The final appearance of outdoor units is subject to the actual products.

53
Hi-FLEXi G Series

Outdoor Unit Specifications

Product line-up
20HP 22/24/26HP

Hi-FLEXi G Series HP 20HP 22HP 24HP 26HP


AC3Φ380~415V/50Hz AVWT-190UESZG AVWT-212UESZG AVWT-232UESZG AVWT-250UESZG
Model Power Supply
AC3Φ380V/60Hz AVWT-190U7SZG AVWT-212U7SZG AVWT-232U7SZG AVWT-250U7SZG
Combination AVWT-76U* AVWT-114U* AVWT-76U* AVWT-136U* AVWT-96U* AVWT-136U* AVWT-114U* AVWT-136U*
KW 56.0 61.5 69.0 73.0
Nominal Capacity
KBtu/h 191.1 209.9 235.5 249.1
Cooling Operation
Power Consumption KW 13.90 16.20 18.28 19.74
EER 4.03 3.80 3.77 3.70
KW 63.0 69.0 77.5 82.5
Nominal Capacity
KBtu/h 215.0 235.5 264.5 281.6
Heating Opeartion
Power Consumption KW 14.95 16.55 18.44 20.34
COP 4.21 4.17 4.20 4.06
Air Flow Rate m³/h 19,800 21,000 21,900 22,200
Outer Dimension mm 1,720×(950+950)×750 1,720×(950+1210)×750 1,720×(950+1,210)×750 1,720×(950+1,210)×750
Packing Dimension mm - - - -
Net Weight Kg 224+227 224+312 225+312 227+312
Gross Weight Kg 237+240 237+327 238+327 240+327
Compressor Quantity 2 3 3 3
Condenser Fan Quantity 2 2 2 2
Cabinet Color Ivory White Ivory White
Gas Line mm Ф28.6 Ф28.6 Ф28.6 Ф31.75
Refrigerant Piping
Liquid Line mm Ф15.88 Ф15.88 Ф15.88 Ф19.05
Max. number of connectable IDU 33 36 40 43
Max. Piping Length m 165 165 165 165
Between ODU&IDU m 70(90) 70(90) 70(90) 70(90)
Height Difference
Between IDUs m 15 15 15 15
Noise Level dB(A) 61 61 61 62
Cooling ℃ DB -5 ~50 -5 ~50 -5 ~50 -5 ~50
Operation Range
Heating ℃ WB -23~ 19 -23~ 19 -23~ 19 -23~ 19

Note:
1. Rated cooling capacity and rated heating capacity are tested in the following conditions:
Cooling conditions: indoor air inlet temperature: 27℃ DB 19℃ WB, Outdoor air inlet temperature: 35℃ DB, pipe length : 7.5m, pipe height difference: 0m
Heating conditions: indoor air inlet temperature: 20℃ DB, Outdoor air inlet temperature: 7℃ DB 6℃ WB, pipe length: 7.5m, pipe height difference : 0m
2.The above noise values are measured in the anechoic chamber without reflected echo, therefore the impact of the reflected echo must be included at the scene.
3.The final appearance of outdoor units is subject to the actual products.

54
Hi-FLEXi G Series

Outdoor Unit Specifications


Product line-up

28/30/32/34/36HP

Hi-FLEXi G Series HP 28HP 30HP 32HP 34HP 36HP


AC3Φ380 ~415V/50Hz AVWT-272UESZG AVWT-290UESZG AVWT-308UESZG AVWT-324UESZG AVWT-340UESZG
Model Power Supply
AC3Φ380V/60Hz AVWT-272U7SZG AVWT-290U7SZG AVWT-308U7SZG AVWT-324U7SZG AVWT-340U7SZG
AVWT-136U* AVWT-136U* AVWT-154U* AVWT-154U* AVWT-170U*
Combination
AVWT-136U* AVWT-154U* AVWT-154U* AVWT-170U* AVWT-170U*
KW 80.0 85.0 90.0 95.0 100.0
Nominal Capacity
KBtu/h 273.0 290.1 307.2 324.2 341.3
Cooling Operation
Power Consumption KW 21.98 24.07 26.24 28.25 30.22
EER 3.64 3.53 3.43 3.36 3.31
KW 90.0 95.0 100.0 106.0 112.0
Nominal Capacity
KBtu/h 307.2 324.2 341.3 361.8 382.3
Heating Opeartion
Power Consumption KW 22.02 23.42 24.82 27.11 29.40
COP 4.09 4.06 4.03 3.91 3.81
Air Flow Rate m³/h 23,400 23,400 23,400 23,400 23,400
Outer Dimension mm 1,720×(1,210+1,210)×750 1,720×(1,210+1,210)×750 1,720×(1,210+1,210)×750 1,720×(1,210+1,210)×750 1,720×(1,210+1,210)×750
Packing Dimension mm - - - - -
Net Weight Kg 312+312 312+315 315+315 315+318 318+318
Gross Weight Kg 327+327 327+330 330+330 330+333 333+333
Compressor Quantity 4 4 4 4 4
Condenser Fan Quantity 2 2 2 2 2
Cabinet Color Ivory White Ivory White
Gas Line mm Ф31.75 Ф31.75 Ф31.75 Ф31.75 Ф38.1
Refrigerant Piping
Liquid Line mm Ф19.05 Ф19.05 Ф19.05 Ф19.05 Ф19.05
Max. number of connectable IDU 47 50 53 56 59
Max. Piping Length m 165 165 165 165 165
Between ODU&IDU m 70(90) 70(90) 70(90) 70(90) 70(90)
Height Difference
Between IDUs m 15 15 15 15 15
Noise Level dB(A) 62 62 62 63 63
Cooling ℃ DB -5 ~50 -5 ~50 -5 ~50 -5 ~50 -5 ~50
Operation Range
Heating ℃ WB -23~19 -23~19 -23~19 -23~19 -23~19

Note:
1. Rated cooling capacity and rated heating capacity are tested in the following conditions:
Cooling conditions: indoor air inlet temperature: 27℃ DB 19℃ WB, Outdoor air inlet temperature: 35℃ DB, pipe length : 7.5m, pipe height difference: 0m
Heating conditions: indoor air inlet temperature: 20℃ DB, Outdoor air inlet temperature: 7℃ DB 6℃ WB, pipe length: 7.5m, pipe height difference : 0m
2.The above noise values are measured in the anechoic chamber without reflected echo, therefore the impact of the reflected echo must be included at the scene.
3.The final appearance of outdoor units is subject to the actual products.

55
Hi-FLEXi G Series

Outdoor Unit Specifications

Product line-up
38/40/42HP

Hi-FLEXi G Series HP 38HP 40HP 42HP


AC3Φ380 ~415V/50Hz AVWT-364UESZG AVWT-382UESZG AVWT-398UESZG
Model Power Supply
AC3Φ380V/60Hz AVWT-364U7SZG AVWT-382U7SZG AVWT-398U7SZG
AVWT-114U* AVWT-114U* AVWT-114U*
Combination
AVWT-114U* AVWT-136U* AVWT-114U* AVWT-154U* AVWT-114U* AVWT-170U*
KW 109.0 112.0 118.0
Nominal Capacity
KBtu/h 372.0 382.3 402.7
Cooling Operation
Power Consumption KW 28.43 30.58 32.52
EER 3.83 3.66 3.63
KW 118.0 125.0 132.0
Nominal Capacity
KBtu/h 402.7 426.6 450.5
Heating Opeartion
Power Consumption KW 29.71 31.11 33.37
COP 3.97 4.02 3.96
Air Flow Rate m³/h 32,700 32,700 32,700
Outer Dimension mm 1,720×(950+950+1,210)×750 1,720×(950+950+1,210)×750 1,720×(950+950+1,210)×750
Packing Dimension mm - - -
Net Weight Kg 227+227+312 227+227+315 227+227+318
Gross Weight Kg 240+240+327 240+240+330 240+240+333
Compressor Quantity 4 4 4
Condenser Fan Quantity 3 3 3
Cabinet Color Ivory White
Gas Line mm Ф38.1 Ф38.1 Ф38.1
Refrigerant Piping
Liquid Line mm Ф19.05 Ф19.05 Ф19.05
Max. number of connectable IDU 64 64 64
Max. Piping Length m 165 165 165
Between ODU&IDU m 70(90) 70(90) 70(90)
Height Difference
Between IDUs m 15 15 15
Noise Level dB(A) 64 64 64
Cooling ℃ DB -5 ~50 -5 ~50 -5 ~50
Operation Range
Heating ℃ WB -23~19 -23~19 -23~19

Note:
1. Rated cooling capacity and rated heating capacity are tested in the following conditions:
Cooling conditions: indoor air inlet temperature: 27℃ DB 19℃ WB, Outdoor air inlet temperature: 35℃ DB, pipe length : 7.5m, pipe height difference: 0m
Heating conditions: indoor air inlet temperature: 20℃ DB, Outdoor air inlet temperature: 7℃ DB 6℃ WB, pipe length: 7.5m, pipe height difference : 0m
2.The above noise values are measured in the anechoic chamber without reflected echo, therefore the impact of the reflected echo must be included at the scene.
3.The final appearance of outdoor units is subject to the actual products.

56
Hi-FLEXi G Series

Outdoor Unit Specifications


Product line-up

44/46/48HP

Hi-FLEXi G Series HP 44HP 46HP 48HP


AC3Φ380 ~415V/50Hz AVWT-420UESZG AVWT-438UESZG AVWT-454UESZG
Model Power Supply
AC3Φ380V/60Hz AVWT-420U7SZG AVWT-438U7SZG AVWT-454U7SZG
AVWT-114U* AVWT-114U* AVWT-114U*
Combination
AVWT-136U* AVWT-170U* AVWT-154U* AVWT-170U* AVWT-170U* AVWT-170U*
KW 125.0 132.0 136.0
Nominal Capacity
KBtu/h 426.6 450.5 464.2
Cooling Operation
Power Consumption KW 34.84 36.91 38.83
EER 3.59 3.58 3.50
KW 140.0 145.0 150.0
Nominal Capacity
KBtu/h 477.8 494.9 511.9
Heating Opeartion
Power Consumption KW 35.06 36.51 38.80
COP 3.99 3.97 3.87
Air Flow Rate m³/h 33,900 33,900 33,900
Outer Dimension mm 1,720×(950+1,210+1,210)×750 1,720×(950+1,210+1,210)×750 1,720×(950+1,210+1,210)×750
Packing Dimension mm - - -
Net Weight Kg 227+312+318 227+315+318 227+318+318
Gross Weight Kg 240+327+333 240+330+333 240+333+333
Compressor Quantity 5 5 5
Condenser Fan Quantity 3 3 3
Cabinet Color Ivory White
Gas Line mm Ф38.1 Ф38.1 Ф38.1
Refrigerant Piping
Liquid Line mm Ф19.05 Ф19.05 Ф19.05
Max. number of connectable IDU 64 64 64
Max. Piping Length m 165 165 165
Between ODU&IDU m 70(90) 70(90) 70(90)
Height Difference
Between IDUs m 15 15 15
Noise Level dB(A) 64 64 65
Cooling ℃ DB -5 ~50 -5 ~50 -5 ~50
Operation Range
Heating ℃ WB -23~19 -23~19 -23~19

Note:
1. Rated cooling capacity and rated heating capacity are tested in the following conditions:
Cooling conditions: indoor air inlet temperature: 27℃ DB 19℃ WB, Outdoor air inlet temperature: 35℃ DB, pipe length: 7.5m, pipe height difference: 0m
Heating conditions: indoor air inlet temperature: 20℃ DB, Outdoor air inlet temperature: 7℃ DB 6℃ WB, pipe length: 7.5m, pipe height difference : 0m
2.The above noise values are measured in the anechoic chamber without reflected echo, therefore the impact of the reflected echo must be included at the scene.
3.The final appearance of outdoor units is subject to the actual products.

57
Hi-FLEXi G Series

Outdoor Unit Specifications

Product line-up
50/52/54HP

Hi-FLEXi G Series HP 50HP 52HP 54HP


AC3Φ380 ~415V/50Hz AVWT-476UESZG AVWT-494UESZG AVWT-510UESZG
Model Power Supply
AC3Φ380V/60Hz AVWT-476U7SZG AVWT-494U7SZG AVWT-510U7SZG
AVWT-136U* AVWT-154U* AVWT-170U*
Combination
AVWT-170U* AVWT-170U* AVWT-170U* AVWT-170U* AVWT-170U* AVWT-170U*
KW 140.0 145.0 150.0
Nominal Capacity
KBtu/h 477.8 494.9 511.9
Cooling Operation
Power Consumption KW 41.21 43.32 45.33
EER 3.40 3.35 3.31
KW 155.0 160.0 165.0
Nominal Capacity
KBtu/h 529.0 546.1 563.1
Heating Opeartion
Power Consumption KW 40.36 41.86 44.16
COP 3.84 3.82 3.74
Air Flow Rate m³/h 35,100 35,100 35,100
Outer Dimension mm 1,720×(1,210+1,210+1,210)×750 1,720×(1,210+1,210+1,210)×750 1,720×(1,210+1,210+1,210)×750
Packing Dimension mm - - -
Net Weight Kg 312+318+318 315+318+318 318+318+318
Gross Weight Kg 327+333+333 330+333+333 333+333+333
Compressor Quantity 6 6 6
Condenser Fan Quantity 3 3 3
Cabinet Color Ivory White
Gas Line mm Ф38.1 Ф38.1 Ф38.1
Refrigerant Piping
Liquid Line mm Ф19.05 Ф19.05 Ф19.05
Max. number of connectable IDU 64 64 64
Max. Piping Length m 165 165 165
Between ODU&IDU m 70(90) 70(90) 70(90)
Height Difference
Between IDUs m 15 15 15
Noise Level dB(A) 65 65 65
Cooling ℃ DB -5 ~50 -5 ~50 -5 ~50
Operation Range
Heating ℃ WB -23~19 -23~19 -23~19

Note:
1. Rated cooling capacity and rated heating capacity are tested in the following conditions:
Cooling conditions: indoor air inlet temperature: 27℃ DB 19℃ WB, Outdoor air inlet temperature: 35℃ DB, pipe length : 7.5m, pipe height difference: 0m
Heating conditions: indoor air inlet temperature: 20℃ DB, Outdoor air inlet temperature: 7℃ DB 6℃ WB, pipe length: 7.5m, pipe height difference : 0m
2.The above noise values are measured in the anechoic chamber without reflected echo, therefore the impact of the reflected echo must be included at the scene.
3.The final appearance of outdoor units is subject to the actual products.

58
Hi-FLEXi G Series

Outdoor Unit Dimensional Data


Model: AVWT-76UE(7)SRG, AVWT-96UE(7)SRG and AVWT-114UE(7)SRG Unit: mm

131 688 131


Product line-up

(Ø26 x 4)

7 29

4-Holes
18

(38 x 15)
(235 x 113)
(Ø26 x 2)
213

Service Cover

Electrical Control Box

Gas Line Refrigerant


767

Piping Connection
ØA Field-Supplied Pipe Size
1720

345 Liquid Line

Q
185 Gas Line

Liquid Line Refrigerant


Piping Connection
ØC Field-Supplied Pipe Size
100
640

Hole for
Power Supply Wiring
(Ø52 x 2)
60

Hole for
Refrigerant Piping and
Control Line Wiring
155 Gas Line
20

145
100

155 Liquid Line


285 78 608
238 298 238 88 750
950 765

Viewed from Q

Hole for
Power Supply Wiring
(Ø52 x 2)

Hole for
Refrigerant Piping and
Control Line Wiring

NOTES:
AVWT-76UE(7)SRG
1. Drain water is discharged from the unit during the operation.
AVWT-96UE(7)SRG
a. Choose a place where well drainage is available. Provide a groove for drain.
AVWT-114UE(7)SRG
b. Do not provide an upward slope from the unit to avoid reverse flow of the drain.
Provide a second drain pan under the outdoor unit, to collect drain water securely.
c. Do not use the drain boss (optional) in a cold area. (Drain water in the drain pipe may be frozen and the drain pipe may crack.)
2. The dimensions marked with indicates the mounting pitch dimension for anchor bolts.

59
Hi-FLEXi G Series

Model: AVWT-136UE(7)SSG, AVWT-154UE(7)SSG and AVWT-170UE(7)SSG Unit: mm

Viewed from P
131 948 131

Product line-up
98 227 560 227 Hole for

105
18
Condensate Drain
(Ø26 x 4)

729 Hole for

157
Power Supply Wiring
(Ø52)

4-Holes Hole for Holes for


18

(38 x 15) Refrigerant Piping Control Line or


(245 x 138) Power Supply Wiring
(Ø26 x 2)

Service Cover
213

Electrical Control Box

Gas Line Refrigerant


767

Piping Connection
ØA Field-Supplied Pipe Size
1720

Q
325 Liquid Line
180 Gas Line

Liquid Line Refrigerant


Piping Connection
ØC Field-Supplied Pipe Size
6 40

100

Hole for
P Power Supply Wiring
(Ø52 x 2)
60

Hole for
Refrigerant Piping and
Control Line Wiring
100
20

145 170 Gas Line


205 175 Liquid Line

285 78 608
238 558 238 88 750
1210 765

Viewed from Q
Field Installation (Example)

Insulation
Accessory Pipe

Brazing

Anchor Bolt
(276)

(M12)

(Front Side)
(Rear Side)
Hole for
Power Supply Wiring (Standard)
less than 30
50

(Ø52 x 2)
70 Concrete
Foundation

Hole for
Refrigerant Piping and
Control Line Wiring
NOTES:
1. Drain water is discharged from the unit during the operation.
a. Choose a place where well drainage is available. Provide a groove for drain.
b. Do not provide an upward slope from the unit to avoid reverse flow of the drain.
AVWT-136UE(7)SSG 25.4 12.7
Provide a second drain pan under the outdoor unit, to collect drain water securely.
AVWT-154UE(7)SSG 28.6 12.7
c. Do not use the drain boss (optional) in a cold area. (Drain water in the drain pipe may be frozen and the drain pipe may crack.)
AVWT-170UE(7)SSG 28.6 15.88
2. The dimensions marked with indicates the mounting pitch dimension for anchor bolts.

60
Hi-FLEXi G Series

Pipe Diameter for Outdoor Unit


Outdoor Unit
Piping Size for AVWT-76UE(7)SRG to AVWT-170UE(7)SSG (Base Unit)
Product line-up

a
To Indoor Units
Refrigerant Piping

( ĭ mm)

Model AVWT-76UE(7)SRG AVWT-96UE(7)SRG AVWT-114UE(7)SRG AVWT-136UE(7)SSG AVWT-154UE(7)SSG AVWT-170UE(7)SSG

Gas 19.05 22.2 25.4 25.4 28.6 28.6


Piping Size a
Liquid 9.53 9.53 12.7 12.7 12.7 15.88

Piping Size for AVWT-190UE(7)SZG to AVWT-340UE(7)SZG (2 Units Combination)

< Figure for AVWT-232UE(7)SZG >

(Indoor Unit on Left Side) (Indoor Unit on Right Side)

Outdoor Unit A Outdoor Unit B Outdoor Unit B Outdoor Unit A

a b b a
c c
To Indoor Units Manifold Pipe Manifold Pipe To Indoor Units

( ĭ mm)
AVWT- AVWT- AVWT- AVWT- AVWT- AVWT- AVWT- AVWT- AVWT-
Model
190UE(7)SZG 212UE(7)SZG 232UE(7)SZG 250UE(7)SZG 272UE(7)SZG 290UE(7)SZG 308UE(7)SZG 324UE(7)SZG 340UE(7)SZG
Outdoor AVWT- AVWT- AVWT- AVWT- AVWT- AVWT- AVWT- AVWT- AVWT-

Combination Unit A 76UE(7)SRG 76UE(7)SRG 96UE(7)SRG 114UE(7)SRG 136UE(7)SSG 136UE(7)SSG 154UE(7)SSG 154UE(7)SSG 170UE(7)SSG
Unit Outdoor AVWT- AVWT- AVWT- AVWT- AVWT- AVWT- AVWT- AVWT- AVWT-
Unit B 114UUE(7)SRG 136UE(7)SSG 136UE(7)SSG 136UE(7)SSG 136UE(7)SSG 154UE(7)SSG 154UE(7)SSG 170UE(7)SSG 170UE(7)SSG
Manifold Pipe HFQ-M22F HFQ-M32F

Gas 28.6 28.6 28.6 31.75 31.75 31.75 31.75 31.75 38.1
a
Liquid 15.88 15.88 15.88 19.05 19.05 19.05 19.05 19.05 19.05

Gas 25.4 25.4 25.4 25.4 25.4 28.6 28.6 28.6 28.6
Piping Size b
Liquid 12.7 12.7 12.7 12.7 12.7 12.7 12.7 15.88 15.88

Gas 19.05 19.05 22.2 25.4 25.4 25.4 28.6 28.6 28.6
c
Liquid 9.53 9.53 9.53 12.7 12.7 12.7 12.7 12.7 15.88

*
Refer to the table for the outdoor unit model, the manifold pipe model and the piping diameter.

61
Hi-FLEXi G Series

Piping Size for AVWT-364UE(7)SZG to AVWT-510UE(7)SZG (Triple Units Combination)

Product line-up
< Figure for AVWT-364UE(7)SZG >

(Indoor Unit on Left Side) (Indoor Unit on Right Side)

Outdoor Unit A Outdoor Unit B Outdoor Unit C Outdoor Unit C Outdoor Unit B Outdoor Unit A

c d d c
a b d a
e e

To Indoor Units Manifold Pipe 1 Manifold Pipe 2 To Indoor Units


Manifold Pipe 2 Manifold Pipe 1

( ĭ mm)
AVWT- AVWT- AVWT- AVWT- AVWT- AVWT- AVWT- AVWT- AVWT-
Model
364UE(7)SZG 382UE(7)SZG 398UE(7)SZG 420UE(7)SZG 438UE(7)SZG 454UE(7)SZG 476UE(7)SZG 494UE(7)SZG 510UE(7)SZG
Outdoor AVWT- AVWT- AVWT- AVWT- AVWT- AVWT- AVWT- AVWT- AVWT-
Unit A 114UE(7)SRG 114UE(7)SRG 114UE(7)SRG 114UE(7)SRG 114UE(7)SRG 114UE(7)SRG 136UE(7)SSG 154UE(7)SSG 170UE(7)SSG
Combination Outdoor AVWT- AVWT- AVWT- AVWT- AVWT- AVWT- AVWT- AVWT- AVWT-
Unit Unit B 114UE(7)SRG 114UE(7)SRG 114UE(7)SRG 136UE(7)SSG 154UE(7)SSG 170UE(7)SSG 170UE(7)SSG 170UE(7)SSG 170UE(7)SSG
Outdoor AVWT- AVWT- AVWT- AVWT- AVWT- AVWT- AVWT- AVWT- AVWT-
Unit C 136UE(7)SSG 154UE(7)SSG 170UE(7)SSG 170UE(7)SSG 170UE(7)SSG 170UE(7)SSG 170UE(7)SSG 170UE(7)SSG 170UE(7)SSG
Manifold Pipe HFQ-M32F+HFQ-M32F

Gas 38.1 38.1 38.1 38.1 38.1 38.1 38.1 38.1 38.1
a
Liquid 19.05 19.05 19.05 19.05 19.05 19.05 19.05 19.05 19.05

Gas 28.6 28.6 28.6 31.75 31.75 31.75 31.75 31.75 31.75
b
Liquid 15.88 15.88 15.88 19.05 19.05 19.05 19.05 19.05 19.05

Gas 25.4 28.6 28.6 28.6 28.6 28.6 28.6 28.6 28.6
Piping Size c
Liquid 12.7 12.7 15.88 15.88 15.88 15.88 15.88 15.88 15.88

Gas 25.4 25.4 25.4 25.4 28.6 28.6 28.6 28.6 28.6
d
Liquid 12.7 12.7 12.7 12.7 12.7 15.88 15.88 15.88 15.88

Gas 25.4 25.4 25.4 25.4 25.4 25.4 25.4 28.6 28.6
e
Liquid 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 15.88

*
Refer to the table for the outdoor unit model, the manifold pipe model and the piping diameter.

62
Hi-FLEXi M Series

DC Inverter-driven Compressor Motor


Product line-up

Fixed Speed Compressor


+
Inverter Compressor

Hisense VRF Hi-FLEXI M Series inverter air conditioning system adopt high efficiency scroll compressor and leading
frequency inverter control technology, realizing significant improvement in operation efficiency under partial load.

High efficiency scroll compressor


Leading inverter control technology
The structure of front flow series is very compact
Small volume and light weight, save transport and installation space
Intelligent control system

Wide Operating Range


The system can run within a wide temperature range, the lowest heating operation can reach -20℃WB, ensure a good heating effect in
winter.

-20℃ WB +15.5℃WB

Heating operation range

-5℃ DB +48℃ DB

Cooling operation range

-25 -15 -5 5 15 25 35 45 55

63
Hi-FLEXi M Series

Extra-high External Static Pressure Design

Product line-up
Max. 60Pa

Adopt high-efficiency DC fan motor


The use of high-efficiency fan reduces energy consumption of the motor
Can achieve industry-leading level of external static pressure 60Pa
Max. 60Pa

The efficient axial fan is designed adopting CFD, finite element method, aviation dynamic fluid simulation analysis and other
advanced concepts; its air inlet angle and outlet angle are optimized; together with unique horn air vent design, the external static
pressure of outdoor unit is higher, which can better exhaust air and ensure smooth air flow.

Layered Installation, Flexibly Corresponding to High-rise Buildings

For high-rise buildings, machine layer can be left to place outdoor units, or machine room can be set up on each floor. By using
exhaust duct to exhaust the air, short circuit of return air can be avoided with long exhaust distance, which ensures good
ventilation and heat exchange effects of outdoor units.

Temperature ℃
46.9443

45.4512

43.9582

42.4651

40.9721

39.4790

37.9859

36.4929

34.9998
Airflow Schematic Exhaust duct installation Layered installation effect picture

64
Hi-FLEXi M Series

More Flexible Refrigerant Piping Work

Actual piping length: 165m


Height difference between the highest and lowest indoor units: 15m
Product line-up

Height difference between outdoor and indoor units: 70m (when outdoor units are higher than indoor units)

Height difference between outdoor and indoor units: 90m (when outdoor units are lower than indoor units)

Note:The recommended height difference between ODU and IDU: 50m when the ODU is higher than IDU;40m when the ODU is lower than IDU
If the installation height difference is beyond the recommended value, please contact our technique engineer.

Max. Height Difference Between


Max. Piping Length: 165m Outdoor Units and Indoor Units: 70m
Total Piping Length: 1000m

Between 1st Branch


and Indoor Unit: 90m or less
Max. Height Difference
Between Indoor Units: 15m

Long Piping Length

65
Hi-FLEXi M Series

Outdoor Unit Specifications

Product line-up
8/10/12HP 14/16HP

Hi-FLEXi M Series HP 8HP 10HP 12HP 14HP 16HP


AC3Φ380~415V/50Hz AVWT-86U6SR AVWT-96U6SR AVWT-114U6SR AVWT-136U6SS AVWT-154U6SS
Model Power Supply AC3Φ380V/60Hz AVWT-86U7SR AVWT-96U7SR AVWT-114U7SR AVWT-136U7SS AVWT-154U7SS
AC1Ф,220V/60Hz AVWT-86U9SR AVWT-96U9SR AVWT-114U9SR AVWT-136U9SS AVWT-154U9SS
KW 25.2 28 33.5 40 45
Nominal Capacity
Cooling Operation KBtu/h 86.0 95.5 114.3 136.5 153.5
Consumption Power KW 6.36 7.65 10.18 12.31 13.93
EER 3.96 3.66 3.29 3.25 3.23
KW 27 31.5 37.5 45 50
Nominal Capacity
KBtu/h 92.1 107.5 128.0 153.5 170.6
Heating Opeartion
Consumption Power KW 6.54 7.76 10.12 11.55 12.82
COP 4.13 4.06 3.71 3.90 3.90
Air Flow Rate m³/h 9,300 10,200 10,500 11,700 11,700
Outer Dimension mm 1,720×950×750 1,720×1,210×750
Packing Dimension mm 1,890X1,000X810 1,890X1,000X810 1,890X1,000X810 1,890X1,260X810 1,890X1,260X810
Net Weight Kg 223 225 228 295 310
Gross Weight Kg 235 237 255 310 325
Compressor Quantity 1 1 1 2 2
Condenser Fan Quantity 1 1 1 1 1
Cabinet Color Ivory White Ivory White
Gas Line mm φ19.05 φ22.2 φ25.4 φ25.4 φ28.6
Refrigerant Piping
Liquid Line mm φ9.53 φ9.53 φ12.7 φ12.7 φ12.7
Max. number of connectable IDU 13 16 19 23 26
Max. Piping Length m 165 165 165 165 165

Between ODU&IDU m 70(90) 70(90) 70(90) 70(90) 70(90)


Height Difference 15 15 15 15
Between IDUs m 15
Noise Level dB(A) 58 58 60 60 62

Cooling ℃ DB -5~48℃ -5~48℃ -5~48℃ -5~48℃ -5~48℃


Operation Range
Heating ℃ WB -20~15.5℃ -20~15.5℃ -20~15.5℃ -20~15.5℃ -20~15.5℃

NOTES:
1.The nominal cooling capacity and heating capacity are based on following conditions: 2. The sound pressure is based on the following conditions.1 Meter from the unit service
Cooling Operation Conditions cover surface, and 1.5 Meter from floor level. The above data is based on the cooling
Indoor Air Inlet Temperature: 27℃ DB(80°F DB), 19.0℃WB(66.2°F WB) mode. In case of heating mode, the sound pressure level increases by approximately 1
2dB. The above data was measured in an anechoic chamber so that reflected sound
Outdoor Air Inlet Temperature: 35℃ DB(95°F DB)
should be taken into consideration in the field.
Piping Length: 7.5 Meters Piping Lift: 0 Meter
Heating Operation Conditions 3. Except for the specified combination in the table, there is no other combination of the base unit.
Indoor Air Inlet Temperature: 20℃ DB(68°F DB), 4. The width of outer dimension, it is the value when each distance between the base
Outdoor Air Inlet Temperature: 7℃DB(45°F DB), 6℃WB(43°F WB) outdoor units is specified to 20mm.

66
Hi-FLEXi M Series

Outdoor Unit Specifications


Product line-up

18/20HP 22/24/26HP

Hi-FLEXi M Series HP 18HP 20HP 22HP 24HP 26HP


AC3Φ380~415V/50Hz AVWT-182U6SZ AVWT-190U6SZ AVWT-210U6SZ AVWT-232U6SZ AVWT-250U6SZ
Model Power Supply AC3Φ380V/60Hz AVWT-182U7SZ AVWT-190U7SZ AVWT-210U7SZ AVWT-232U7SZ AVWT-250U7SZ
AC1Ф,220V/60Hz AVWT-182U9SZ AVWT-190U9SZ AVWT-210U9SZ AVWT-232U9SZ AVWT-250U9SZ

Combination AVWT-86U* AVWT-96U* AVWT-86U* AVWT-96U* AVWT-114U*


AVWT-96U* AVWT-96U* AVWT-136U* AVWT-136U* AVWT-136U*

KW 53.2 56 61.5 68 73
Nominal Capacity
KBtu/h 181.5 191.1 209.8 232.0 249.1
Cooling Operation
Power Consumption KW 14.01 15.3 18.67 19.96 22.49
EER 3.80 3.66 3.29 3.41 3.25
KW 58.5 63 69 76.5 81.5
Nominal Capacity
KBtu/h 199.6 215.0 235.4 261.0 278.1
Heating Opeartion
Power Consumption KW 14.3 15.52 18.09 19.31 21.67
COP 4.09 4.06 3.98 3.96 3.81
Air Flow Rate m³/h 19,500 20,400 21,000 21,900 22,200
Outer Dimension mm 1,720×(950+950)×750 1,720×(950+1,210)×750
Packing Dimension mm --- --- --- --- ---
Net Weight Kg 223+225 225+225 223+295 225+295 225+295
Gross Weight Kg 235+237 237×2 235+310 237+310 255+310
Compressor Quantity 2 2 3 3 3
Condenser Fan Quantity 2 2 2 2 2
Cabinet Color Ivory White Ivory White
Gas Line mm φ28.6 φ28.6 φ28.6 φ28.6 φ31.75
Refrigerant Piping
Liquid Line mm φ15.88 φ15.88 φ15.88 φ15.88 φ19.05
Max. number of connectable IDU 26 33 36 40 43
Max. Piping Length m 165 165 165 165 165
Between ODU&IDU m 70(90) 70(90) 70(90) 70(90) 70(90)
Height Difference
Between IDUs m 15 15 15 15 15
Noise Level dB(A) 61 61 62 63 63
Cooling ℃ DB -5 ~48℃ -5 ~48℃ -5 ~48℃ -5 ~48℃ -5 ~48℃
Operation Range
Heating ℃ WB -20~ 15.5℃ -20~ 15.5℃ -20~ 15.5℃ -20~ 15.5℃ -20~ 15.5℃

NOTES:
1.The nominal cooling capacity and heating capacity are based on following conditions: 2. The sound pressure is based on the following conditions.1 Meter from the unit service
Cooling Operation Conditions cover surface, and 1.5 Meter from floor level. The above data is based on the cooling
Indoor Air Inlet Temperature: 27℃ DB(80°F DB), 19.0℃WB(66.2°F WB) mode. In case of heating mode, the sound pressure level increases by approximately 1
2dB. The above data was measured in an anechoic chamber so that reflected sound
Outdoor Air Inlet Temperature: 35℃ DB(95°F DB)
should be taken into consideration in the field.
Piping Length: 7.5 Meters Piping Lift: 0 Meter
Heating Operation Conditions 3. Except for the specified combination in the table, there is no other combination of the base unit.
Indoor Air Inlet Temperature: 20℃ DB(68°F DB), 4. The width of outer dimension, it is the value when each distance between the base
Outdoor Air Inlet Temperature: 7℃DB(45°F DB), 6℃WB(43°F WB) outdoor units is specified to 20mm.

67
Hi-FLEXi M Series

Outdoor Unit Specifications

Product line-up
28/30/32HP

Hi-FLEXi M Series HP 28HP 30HP 32HP


AC3Φ380~ 415V/50Hz AVWT-272U6SZ AVWT-290U6SZ AVWT-307U6SZ
Model Power Supply AC3Φ380V/60Hz AVWT-272U7SZ AVWT-290U7SZ AVWT-307U7SZ
AC1Ф,220V/60Hz AVWT-272U9SZ AVWT-290U9SZ AVWT-307U9SZ

Combination AVWT-136U* AVWT-136U* AVWT-154U*


AVWT-136U* AVWT-154U* AVWT-154U*

KW 78.5 85 90
Nominal Capacity
KBtu/h 267.8 290.0 307.1
Cooling Operation
Power Consumption KW 24.62 26.24 27.86
EER 3.17 3.24 3.23
KW 87.5 95 100
Nominal Capacity
KBtu/h 298.6 324.1 341.2
Heating Opeartion
Power Consumption KW 23.1 24.37 25.64
COP 3.90 3.90 3.90
Air Flow Rate m³/h 23,400 23,400 23,400
Outer Dimension mm 1,720×(1,210+1,210)×750
Packing Dimension mm --- --- ---
Net Weight Kg 295+295 295+310 310+310
Gross Weight Kg 310+310 310+325 325+325
Compressor Quantity 4 4 4
Condenser Fan Quantity 2 3 3
Cabinet Color Ivory White
Gas Line mm φ31.75 φ31.75 φ31.75
Refrigerant Piping
Liquid Line mm φ19.05 φ19.05 φ19.05
Max. number of connectable IDU 47 50 53
Max. Piping Length m 165 165 165
Between ODU&IDU m 70(90) 70(90) 70(90)
Height Difference
Between IDUs m 15 15 15
Noise Level dB(A) 63 63 63
Cooling ℃ DB -5 ~48℃ -5 ~48℃ -5 ~48℃
Operation Range
Heating ℃ WB -20~15.5℃ -20 ~15.5℃ -20~15.5℃

NOTES:
1.The nominal cooling capacity and heating capacity are based on following conditions: 2. The sound pressure is based on the following conditions.1 Meter from the unit service
Cooling Operation Conditions cover surface, and 1.5 Meter from floor level. The above data is based on the cooling
Indoor Air Inlet Temperature: 27℃ DB(80°F DB), 19.0℃WB(66.2°F WB) mode. In case of heating mode, the sound pressure level increases by approximately 1
2dB. The above data was measured in an anechoic chamber so that reflected sound
Outdoor Air Inlet Temperature: 35℃ DB(95°F DB)
should be taken into consideration in the field.
Piping Length: 7.5 Meters Piping Lift: 0 Meter
Heating Operation Conditions 3. Except for the specified combination in the table, there is no other combination of the base unit.
Indoor Air Inlet Temperature: 20℃ DB(68°F DB), 4. The width of outer dimension, it is the value when each distance between the base
Outdoor Air Inlet Temperature: 7℃DB(45°F DB), 6℃WB(43°F WB) outdoor units is specified to 20mm.

68
Hi-FLEXi M Series

Outdoor Unit Specifications


Product line-up

34/36/38/40HP

Hi-FLEXi M Series HP 34HP 36HP 38HP 40HP


AC3Φ380 ~415V/50Hz AVWT-328U6SZ AVWT-345U6SZ AVWT-365U6SZ AVWT-386U6SZ
Model Power Supply AC3Φ380V/60Hz AVWT-328U7SZ AVWT-345U7SZ AVWT-365U7SZ AVWT-386U7SZ
AC1Ф,220V/60Hz AVWT-328U9SZ AVWT-345U9SZ AVWT-365U9SZ AVWT-386U9SZ
AVWT-86U* AVWT-96U* AVWT-114U* AVWT-114U*
Combination AVWT-96U* AVWT-96U* AVWT-114U* AVWT-114U*
AVWT-154U* AVWT-154U* AVWT-136U* AVWT-154U*

KW 96 101 106.5 113


Nominal Capacity
KBtu/h 327.6 344.6 365.1 385.6
Cooling Operation
Power Consumption KW 27.94 29.23 32.67 34.29
EER 3.51 3.46 3.28 3.30
KW 108 113 119 126.5
Nominal Capacity
KBtu/h 368.5 385.6 406 431.6
Heating Opeartion
Power Consumption KW 27.12 28.34 31.79 33.06
COP 3.98 3.99 3.77 3.78
Air Flow Rate m³/h 31,200 32,100 32,700 32,700
Outer Dimension mm 1,720×(950+950+1,210)×750
Packing Dimension mm --- --- --- ---
Net Weight Kg 208+210+310 225+225+310 228+228+295 228+228+310
Gross Weight Kg 235+237+325 237+237+325 255+255+310 255+255+325
Compressor Quantity 4 4 4 4
Condenser Fan Quantity 3 3 3 3
Cabinet Color Ivory White
Gas Line mm φ31.75 φ38.1 φ38.1 φ38.1
Refrigerant Piping
Liquid Line mm φ19.05 φ19.05 φ19.05 φ19.05
Max. number of connectable IDU 56 59 64 64
Max. Piping Length m 165 165 165 165
Between ODU&IDU m 70(90) 70(90) 70(90) 70(90)
Height Difference
Between IDUs m 15 15 15 15
Noise Level dB(A) 64 64 64 64
Cooling ℃ DB -5 ~48℃ -5 ~48℃ -5 ~48℃ -5 ~48℃
Operation Range
Heating ℃ WB -20~15.5℃ -20~15.5℃ -20~15.5℃ -20~15.5℃

NOTES:
1.The nominal cooling capacity and heating capacity are based on following conditions: 2. The sound pressure is based on the following conditions.1 Meter from the unit service
Cooling Operation Conditions cover surface, and 1.5 Meter from floor level. The above data is based on the cooling
Indoor Air Inlet Temperature: 27℃ DB(80°F DB), 19.0℃WB(66.2°F WB) mode. In case of heating mode, the sound pressure level increases by approximately 1
2dB. The above data was measured in an anechoic chamber so that reflected sound
Outdoor Air Inlet Temperature: 35℃ DB(95°F DB)
should be taken into consideration in the field.
Piping Length: 7.5 Meters Piping Lift: 0 Meter
Heating Operation Conditions 3. Except for the specified combination in the table, there is no other combination of the base unit.
Indoor Air Inlet Temperature: 20℃ DB(68°F DB), 4. The width of outer dimension, it is the value when each distance between the base
Outdoor Air Inlet Temperature: 7℃DB(45°F DB), 6℃WB(43°F WB) outdoor units is specified to 20mm.

69
Hi-FLEXi M Series

Outdoor Unit Specifications

Product line-up
42/44HP 46/48HP

Hi-FLEXi M Series HP 42HP 44HP 46HP 48HP


AC3Φ380~415V/50Hz AVWT-402U6SZ AVWT-426U6SZ AVWT-444U6SZ AVWT-460U6SZ
Model Power Supply AC3Φ380V/60Hz AVWT-402U7SZ AVWT-426U7SZ AVWT-444U7SZ AVWT-460U7SZ
AC1Ф,220V/60Hz AVWT-402U9SZ AVWT-426U9SZ AVWT-444U9SZ AVWT-460U9SZ
AVWT-114U* AVWT-114U* AVWT-136U* AVWT-154U*
Combination AVWT-136U* AVWT-154U* AVWT-154U* AVWT-154U*
AVWT-154U* AVWT-154U* AVWT-154U* AVWT-154U*
KW 118 123.5 130 135
Nominal Capacity
KBtu/h 402.6 421.4 443.6 460.6
Cooling Operation
Power Consumption KW 36.42 38.04 40.17 41.79
EER 3.24 3.25 3.24 3.23
KW 131.5 137.5 145 150
Nominal Capacity
KBtu/h 448.7 469.2 494.7 511.8
Heating Opeartion
Power Consumption KW 34.49 35.76 37.19 38.46
COP 3.84 3.85 3.90 3.90
Air Flow Rate m³/h 33,900 33,900 35,100 35,100
Outer Dimension mm 1,720×(950+1,210+1,210)×750 1,720×(1,210+1,210+1,210)×750
Packing Dimension mm --- --- --- ---
Net Weight Kg 228+295+310 228+310+310 295+310+310 310+310+310
Gross Weight Kg 255+310+325 255+325+325 310+325+325 325+325+325
Compressor Quantity 6 6 6 6
Condenser Fan Quantity 3 3 3 3
Cabinet Color Ivory White
Gas Line mm φ38.1 φ38.1 φ38.1 φ38.1
Refrigerant Piping
Liquid Line mm φ19.05 φ19.05 φ19.05 φ19.05
Max. number of connectable IDU 64 64 64 64
Max. Piping Length m 165 165 165 165
Between ODU&IDU m 70(90) 70(90) 70(90) 70(90)
Height Difference
Between IDUs m 15 15 15 15
Noise Level dB(A) 64 64 65 65
Cooling ℃ DB -5 ~48℃ -5 ~48℃ -5 ~48℃ -5 ~48℃
Operation Range
Heating ℃ WB -20~15.5℃ -20~15.5℃ -20~15.5℃ -20~15.5℃

NOTES:
1.The nominal cooling capacity and heating capacity are based on following conditions: 2. The sound pressure is based on the following conditions.1 Meter from the unit service
Cooling Operation Conditions cover surface, and 1.5 Meter from floor level. The above data is based on the cooling
Indoor Air Inlet Temperature: 27℃ DB(80°F DB), 19.0℃WB(66.2°F WB) mode. In case of heating mode, the sound pressure level increases by approximately 1
2dB. The above data was measured in an anechoic chamber so that reflected sound
Outdoor Air Inlet Temperature: 35℃ DB(95°F DB)
should be taken into consideration in the field.
Piping Length: 7.5 Meters Piping Lift: 0 Meter
Heating Operation Conditions 3. Except for the specified combination in the table, there is no other combination of the base unit.
Indoor Air Inlet Temperature: 20℃ DB(68°F DB), 4. The width of outer dimension, it is the value when each distance between the base
Outdoor Air Inlet Temperature: 7℃DB(45°F DB), 6℃WB(43°F WB) outdoor units is specified to 20mm.

70
Hi-FLEXi M Series

Outdoor Unit Dimensional Data


Model: AVWT-86U6(7)SR, AVWT-96U6(7)SR and AVWT-114U6(7)SR Unit: mm

Viewed from P
131 688 131
Product line-up

98 227 300 227 Hole for

105
18
Condensate Drain
(Ø26 x 4)

Hole for
729

157
Power Supply Wiring
(Ø52)

4-Holes
18

Hole for Holes for


(38 x 15)
Refrigerant Piping Control Line or
(235 x 113) Power Supply Wiring
(Ø26 x 2)
213

Service Cover

Electrical Control Box

Gas Line Refrigerant


767

Piping Connection
ØA Field-Supplied Pipe Size
1720

345 Liquid Line

Q
185 Gas Line

Liquid Line Refrigerant


Piping Connection
ØC Field-Supplied Pipe Size
100
640

Hole for
P Power Supply Wiring
(Ø52 x 2)
60

Hole for
Refrigerant Piping and
Control Line Wiring
155 Gas Line
20

145
100

155 Liquid Line


285 78 608
238 298 238 88 750
950 765

Viewed from Q
Field Installation (Example)

Accessory Pipe
Insulation

Brazing
(295)

Anchor Bolt
(M12)
(Front Side) (Rear Side)
Hole for
(Standard)
50

Power Supply Wiring


less than 30

(Ø52 x 2) Concrete
70
Foundation

Hole for
Refrigerant Piping and
Control Line Wiring

NOTES:
1. Drain water is discharged from the unit during the operation. Dimension
a. Choose a place where well drainage is available. Provide a groove for drain. A C
Model
b. Do not provide an upward slope from the unit to avoid reverse flow of the drain. AVWT-86U6(B)(7)SR
AVWT-86U6(7)SR 19.05 9.53
Provide a second drain pan under the outdoor unit, to collect drain water securely. AVWT-96U6(7)SR
AVWT-96U6(B)(7)SR 22.2 9.53
c. Do not use the drain boss (optional) in a cold area. (Drain water in the drain pipe may be frozen and the drain pipe may crack.) AVWT-114U6(B)(7)SR
AVWT-114U6(7)SR 25.4 12.7
2. The dimensions marked with indicates the mounting pitch dimension for anchor bolts.

71
Hi-FLEXi M Series

Model: AVWT-136U6(7)SS and AVWT-154U6(7)SS Unit: mm

Viewed from P
131 948 131 98 227 560 227 Hole for

Product line-up
105
18
Condensate Drai
(Ø26 x 4)

Hole for
729

157
Power Supply Wiring
(Ø52)

4-Holes Hole for Holes for


18

(38 x 15) Refrigerant Piping Control Line or


(245 x 138) Power Supply Wiring
(Ø26 x 2)

Service Cover
213

Electrical Control Box

Gas Line Refrigerant


767

Piping Connection
ØA Field-Supplied Pipe Size
1720

Q
325 Liquid Line
180 Gas Line

Liquid Line Refrigerant


Piping Connection
ØC Field-Supplied Pipe Size
640

100

Hole for
P Power Supply Wiring
(Ø52 x 2)
60

Hole for
Refrigerant Piping and
Control Line Wiring
100
20

145 170 Gas Line


205 175 Liquid Line

285 78 608
238 558 238 88 750
1210 765

Viewed from Q
Field Installation (Example)

Insulation
Accessory Pipe

Brazing

Anchor Bolt
(276)

(M12)

(Front Side)
(Rear Side)
Hole for
Power Supply Wiring (Standard)
less than 30
50

(Ø52 x 2)
70 Concrete
Foundation

Hole for
Refrigerant Piping and
Control Line Wiring
NOTES:
1. Drain water is discharged from the unit during the operation.
a. Choose a place where well drainage is available. Provide a groove for drain. Dimension
b. Do not provide an upward slope from the unit to avoid reverse flow of the drain. A C
Model
Provide a second drain pan under the outdoor unit, to collect drain water securely. AVWT-136U6(7)SS
U6(B)(7) 25.4 12.7
c. Do not use the drain boss (optional) in a cold area. (Drain water in the drain pipe may be frozen and the drain pipe may crack.) AVWT-154U6(7)SS
U6(B)(7) 28.6 12.7
2. The dimensions marked with indicates the mounting pitch dimension for anchor bolts.

72
Hi-FLEXi M Series

Pipe Diameter for Outdoor Unit

Piping Size for AVWT-86U6(7)SR to AVWT-154U6(7)SS (Base Unit) Outdoor Unit


Product line-up

a
To Indoor Units
Refrigerant Piping
(ĭmm)

Model AVWT-86U6(7)SR AVWT-96U6(7)SR AVWT-114U6(7)SR AVWT-136U6(7)SS AVWT-154U6(7)SS

Gas 19.05 22.2 25.4 25.4 28.6


Piping Size a
Liquid 9.53 9.53 12.7 12.7 12.7

Piping Size for AVWT-182U6(7)SZ to AVWT-307U6(7)SZ (2 Units Combination)

< Figure for AVWT-232U6(7)SZ >

(Indoor Unit on Left Side) (Indoor Unit on Right Side)

Outdoor Unit A Outdoor Unit B Outdoor Unit B Outdoor Unit A

a b b a
c c
To Indoor Units Manifold Pipe Manifold Pipe To Indoor Units
(ĭmm)

Model AVWT-182* AVWT-190* AVWT-210* AVWT-232* AVWT-250* AVWT-272* AVWT-290* AVWT-307*


Outdoor
AVWT-96* AVWT-96* AVWT-136* AVWT-136* AVWT-136* AVWT-136* AVWT-154* AVWT-154*
Combination Unit A
Unit Outdoor
AVWT-86* AVWT-96* AVWT-86* AVWT-96* AVWT-114* AVWT-136* AVWT-136* AVWT-154*
Unit B
Manifold pipe HFQ-M22F HFQ-M32F

Gas 28.6 28.6 28.6 28.6 31.75 31.75 31.75 31.75


a
Liquid 15.88 15.88 15.88 15.88 19.05 19.05 19.05 19.05

Gas 22.2 22.2 25.4 25.4 25.4 25.4 28.6 28.6


Piping Size b
Liquid 9.53 9.53 12.7 12.7 12.7 12.7 12.7 12.7

Gas 19.05 22.2 19.05 22.2 25.4 25.4 25.4 28.6


c
Liquid 9.53 9.53 9.53 9.53 12.7 12.7 12.7 12.7

*
Refer to the table for the outdoor unit model, the manifold pipe model and the piping diameter.

73
Hi-FLEXi M Series

Piping Size for AVWT-328U6(7)SZ to AVWT-460U6(7)SZ (Triple Units Combination)

< Figure for AVWT-365U6(7)SZ >

Product line-up
(Indoor Unit on Left Side) (Indoor Unit on Right Side)

Outdoor Unit A Outdoor Unit B Outdoor Unit C Outdoor Unit C Outdoor Unit B Outdoor Unit A

c d d c
a b d a
e e

To Indoor Units Manifold Pipe 1 Manifold Pipe 2 To Indoor Units


Manifold Pipe 2 Manifold Pipe 1

(ĭmm)

Model AVWT-328* AVWT-345* AVWT-365* AVWT-386* AVWT-402* AVWT-426* AVWT-444* AVWT-460*


Outdoor
AVWT-154* AVWT-154* AVWT-136* AVWT-154* AVWT-154* AVWT-154* AVWT-154* AVWT-154*
Unit A
Combination Outdoor
AVWT-96* AVWT-96* AVWT-114* AVWT-114* AVWT-136* AVWT-154* AVWT-154* AVWT-154*
Unit Unit B
Outdoor
AVWT-86* AVWT-96* AVWT-114* AVWT-114* AVWT-114* AVWT-114* AVWT-136* AVWT-154*
Unit C
Manifold pipe HFQ-M22F + HFQ-M32F HFQ-M32F + HFQ-M32F

Gas 31.75 38.1 38.1 38.1 38.1 38.1 38.1 38.1


a
Liquid 19.05 19.05 19.05 19.05 19.05 19.05 19.05 19.05

Gas 28.6 28.6 28.6 28.6 31.75 31.75 31.75 31.75


b
Liquid 15.88 15.88 15.88 15.88 19.05 19.05 19.05 19.05

Gas 28.6 28.6 25.4 28.6 28.6 28.6 28.6 28.6


Piping Size c
Liquid 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7

Gas 22.2 22.2 25.4 25.4 25.4 28.6 28.6 28.6


d
Liquid 9.53 9.53 12.7 12.7 12.7 12.7 12.7 12.7

Gas 19.05 22.2 25.4 25.4 25.4 25.4 25.4 28.6


e
Liquid 9.53 9.53 12.7 12.7 12.7 12.7 12.7 12.7

*
Refer to the table for the outdoor unit model, the manifold pipe model and the piping diameter.

74
Hi-FLEXi R Series

Humanized Design, Flexible Response to the Change of Demand


Meeting various requirements of consumers who are sensitive to temperature and diverse space with different function from the
perspective of humanity especially at the turn of the season, like the complex of equipment rooms and offices, or the guest rooms
and dining hall in the same hotel etc.
Product line-up

The latest heat recovery multi-split system achieves indoor units cooling and heating at the same time and being switched between
two modes individually,which flexibly satisfies personalized need of different users.

Cooling Cooling Cooling


Interior Zone
of Building

Office Equipmeat Room Office

Office Office Meeting Room

Heating Heating Stop


Exterior Zone
of Building

Office Gym Room IT Room

75
Hi-FLEXi R Series

Configuration of Heat Recovery Operation System


Hi-Flexi R Series heat recovery operation system is composed of heat recovery outdoor unit, indoor unit, switch box, multi-kits and
refrigerant pipes. One switch box unit could connect to one or multiple indoor units. The indoor units equipped with a same switch box
unit will keep the same operation mode. The indoor units connecting directly to the refrigerant liquid pipe and the low pressure gas pipe

Product line-up
instead of via switch box unit will stick to cooling only operation.

Switch Box

Switch Box Switch Box Switch Box

Wide Operating Range


The system can run within a wide temperature range, the lowest heating operation can reach -20℃WB, ensure a good heating effect in
winter.

-20℃ WB +15.5℃WB

Heating operation range

-5℃ DB +48℃ DB

Cooling operation range

-25 -15 -5 5 15 25 35 45 55

76
Hi-FLEXi R Series

Extra-high External Static Pressure Design


Product line-up

Max. 60Pa

Adopt high-efficiency DC fan motor


The use of high-efficiency fan reduces energy consumption of the motor
Can achieve industry-leading level of external static pressure 60Pa
Max. 60Pa

The efficient axial fan is designed adopting CFD, finite element method, aviation dynamic fluid simulation analysis and other
advanced concepts; its air inlet angle and outlet angle are optimized; together with unique horn air vent design, the external static
pressure of outdoor unit is higher, which can better exhaust air and ensure smooth air flow.

Layered Installation, Flexibly Corresponding to High-rise Buildings


For high-rise buildings, machine layer can be left to place outdoor units, or machine room can be set up on each floor. By using
exhaust duct to exhaust the air, short circuit of return air can be avoided with long exhaust distance, which ensures good
ventilation and heat exchange effects of outdoor units.

Temperature ℃
46.9443

45.4512

43.9582

42.4651

40.9721

39.4790

37.9859

36.4929

34.9998
Airflow Schematic Exhaust duct installation Layered installation effect picture

77
Hi-FLEXi R Series

High Flexible Design and Installation

More Flexible Refrigerant Piping Work


Actual piping length: 165m

Product line-up
Max. equivalent piping length: 190m
Height difference between the highest and lowest indoor units: 15m or less
Max.height difference between outdoor and indoor units: 70m (when outdoor units are higher than indoor units)
Max.height difference between outdoor and indoor units: 90m (when outdoor units are lower than indoor units)

Max. piping length between


outdoor units:10m
Max.piping length :165m
Total piping length :1000m
Outdoor units

Max.height
difference between
outdoor units Max.height difference between
and indoor Indoor units Switch Box: 15m
units: 70m Piping

Switch Box

Max.height between indoor


units: 15m

Max.distance between
the 1st branch and Max.height between indoor units after
indoor unit: 90m
the same Switch Box: 3m

Note:The recommended height difference between ODU and IDU: 50m when the ODU is higher than IDU;40m when the ODU is lower than IDU

If the installation height difference is beyond the recommended value, please contact our technique engineer.

78
Hi-FLEXi R Series

Outdoor Unit Specifications


Product line-up

8/10/12HP 14/16/18HP

Hi-FLEXi R Series HP 8HP 10HP 12HP 14HP 16HP 18HP


AC3Φ 380~415V/50HZ AVWT-76FESR AVWT-96FESR AVWT-114FESR AVWT-136FESS AVWT-154FESS AVWT-170FESS
Model Power Supply
AC3Φ 380V/60HZ AVWT-76F7SR AVWT-96F7SR AVWT-114F7SR AVWT-136F7SS AVWT-154F7SS AVWT-170F7SS

Combination

KW 22.4 28.0 33.5 40.0 45.0 50.0


Nominal Capacity
KBtu/h 76.5 95.5 114.3 136.5 153.5 170.6
Cooling Operation
Power Consumption KW 5.65 7.65 10.18 12.25 13.74 16.60
EER 3.96 3.66 3.29 3.27 3.28 3.01
KW 25.0 31.5 37.5 45.0 50.0 56.0
Nominal Capacity
KBtu/h 85.3 107.5 128.0 153.5 170.6 191.1
Heating Operation
Power Consumption kW 5.81 7.76 10.12 11.30 12.60 15.30
COP 4.30 4.06 3.71 3.98 3.97 3.66
Air Flow Rate m³/h 9,300 10,200 10,500 11,700 11,700 11,700
Outer Dimensions(H×W×D) mm 1,720×950×750 1,720×950×750 1,720×950×750 1,720×1,210×750 1,720×1,210×750 1,720×1,210×750
Packing Dimensions mm 1,828×1,018×824 1,828×1,018×824 1,828×1,018×824 1,882×1,278×824 1,882×1,278×824 1,882×1,278×824
Net Weight Kg 225 227 246 298 312 318
Gross Weight Kg 235 237 255 310 325 330
Compressor Quantity 1 1 1 2 2 2
Compressor Fan Quantity 1 1 1 1 1 1
Cabinet Color Ivory White Ivory White
Gas Line mm Ф19.05 Ф22.2 Ф25.4 Ф25.4 Ф28.6 Ф28.6
Heat Pump Operation System
Liquid Line mm Ф9.53 Ф9.53 Ф12.7 Ф12.7 Ф12.7 Ф15.88
Liquid Line mm Ф9.53 Ф9.53 Ф12.7 Ф12.7 Ф12.7 Ф15.88
Heat Recovery
Low Pressure Gas Line mm Ф19.05 Ф22.2 Ф25.4 Ф25.4 Ф28.6 Ф28.6
Operation System
High Pressure Gas Line mm Ф15.88 Ф19.05 Ф22.2 Ф22.2 Ф22.2 Ф22.2
Max. Connectable No. of Indoor Units 13.0 16.0 19.0 23.0 26.0 26.0
Refrierant Piping Flare-nut Connection(With Flare Nuts)
Between ODU and IDU m 70(90) 70(90) 70(90) 70(90) 70(90) 70(90)
Height Difference
Between IDUs m 15.0 15.0 15.0 15.0 15.0 15.0
Noise Level dB(A) 58 58 60 62 62 63
Cooling ℃DB -5~48℃ -5~48℃ -5~48℃ -5~48℃ -5~48℃ -5~48℃
Operation Range
Heating ℃WB -20~15.5℃ -20~15.5℃ -20~15.5℃ -20~15.5℃ -20~15.5℃ -20~15.5℃

NOTES:
1.The nominal cooling capacity and heating capacity are based on following conditions: 2. The sound pressure is based on the following conditions.1 Meter from the unit service
Cooling Operation Conditions cover surface, and 1.5 Meter from floor level. The above data is based on the cooling
Indoor Air Inlet Temperature: 27℃ DB(80°F DB), 19.0℃WB(66.2°F WB) mode. In case of heating mode, the sound pressure level increases by approximately 1
2dB. The above data was measured in an anechoic chamber so that reflected sound
Outdoor Air Inlet Temperature: 35℃ DB(95°F DB)
should be taken into consideration in the field.
Piping Length: 7.5 Meters Piping Lift: 0 Meter
Heating Operation Conditions 3. Except for the specified combination in the table, there is no other combination of the base unit.
Indoor Air Inlet Temperature: 20℃ DB(68°F DB), 4. The width of outer dimension, it is the value when each distance between the base
Outdoor Air Inlet Temperature: 7℃DB(45°F DB), 6℃WB(43°F WB) outdoor units is specified to 20mm.

79
Hi-FLEXi R Series

Outdoor Unit Specifications

Product line-up
20HP 22/24/26HP

Hi-FLEXi M Series HP 20HP 22HP 24HP 26HP


AC3Φ 380 ~415V/50HZ AVWT-190FESZ AVWT-212FESZ AVWT-232FESZ AVWT-250FESZ
Model Power Supply
AC3Φ 380V/60HZ AVWT-190F7SZ AVWT-212F7SZ AVWT-232F7SZ AVWT-250F7SZ
AVWT-76FESR AVWT-76FESR AVWT-96FESR AVWT-114FESR
Combination
AVWT-114FESR AVWT-136FESS AVWT-136FESS AVWT-136FESS
KW 56.0 61.5 69.0 73.0
Nominal Capacity
KBtu/h 190.8 213.0 232.0 250.8
Cooling Operation
Power Consumption KW 15.83 17.90 19.90 22.43
EER 3.54 3.44 3.47 3.25
KW 63.0 69.0 77.5 82.5
Nominal Capacity
KBtu/h 213.3 239.0 261.0 281.5
Heating Operation
Power Consumption KW 15.93 17.11 19.06 21.42
COP 3.95 4.03 4.07 3.85
Air Flow Rate m³/h 19,800 21,000 21,900 22,200
Outer Dimensions(H×W×D) mm 1,720×(950+950)×750 1,720×(950+1,210)×750 1,720×(950+1,210)×750 1,720×(950+1,210)×750
Packing Dimensions mm --- --- --- ---
Net Weight Kg 225+246 225+298 227+298 246+298
Gross Weight Kg 235+255 235+310 237+310 255+310
Compressor Quantity 2 3 3 3
Compressor Fan Quantity 2 2 2 2
Cabinet Color Ivory White
Gas Line mm Ф28.6 Ф28.6 Ф28.6 Ф31.75
Heat Pump Operation System
Liquid Line mm Ф15.88 Ф15.88 Ф15.88 Ф19.05
Liquid Line mm Ф15.88 Ф15.88 Ф15.88 Ф19.05
Heat Recovery
Low Pressure Gas Line mm Ф28.6 Ф28.6 Ф28.6 Ф31.75
Operation System
High Pressure Gas Line mm Ф22.2 Ф25.4 Ф25.4 Ф25.4
Max. Connectable No. of Indoor Units 33.0 36.0 40.0 43.0
Refrierant Piping Flare-nut Connection(With Flare Nuts)
Between ODU and IDU m 70(90) 70(90) 70(90) 70(90)
Height Difference
Between IDUs m 15.0 15.0 15.0 15.0
Noise Level dB(A) 62 63 63 64
Cooling ℃DB -5~48℃ -5~48℃ -5~48℃ -5~48℃
Operation Range
Heating ℃WB -20~15.5℃ -20~15.5℃ -20~15.5℃ -20~15.5℃

NOTES:
1.The nominal cooling capacity and heating capacity are based on following conditions: 2. The sound pressure is based on the following conditions.1 Meter from the unit service
Cooling Operation Conditions cover surface, and 1.5 Meter from floor level. The above data is based on the cooling
Indoor Air Inlet Temperature: 27℃ DB(80°F DB), 19.0℃WB(66.2°F WB) mode. In case of heating mode, the sound pressure level increases by approximately 1
2dB. The above data was measured in an anechoic chamber so that reflected sound
Outdoor Air Inlet Temperature: 35℃ DB(95°F DB)
should be taken into consideration in the field.
Piping Length: 7.5 Meters Piping Lift: 0 Meter
Heating Operation Conditions 3. Except for the specified combination in the table, there is no other combination of the base unit.
Indoor Air Inlet Temperature: 20℃ DB(68°F DB), 4. The width of outer dimension, it is the value when each distance between the base
Outdoor Air Inlet Temperature: 7℃DB(45°F DB), 6℃WB(43°F WB) outdoor units is specified to 20mm.

80
Hi-FLEXi R Series

Outdoor Unit Specifications


Product line-up

28/30/32/34/36HP

Hi-FLEXi M Series HP 28HP 30HP 32HP 34HP 36HP


AC3Φ 380~ 415V/50HZ AVWT-272FESZ AVWT-290FESZ AVWT-308FESZ AVWT-324FESZ AVWT-340FESZ
Model Power Supply
AC3Φ 380V/60HZ AVWT-272F7SZ AVWT-290F7SZ AVWT-308F7SZ AVWT-324F7SZ AVWT-340F7SZ
AVWT-136FESS AVWT-136FESS AVWT-154FESS AVWT-154FESS AVWT-170FESS
Combination
AVWT-136FESS AVWT-154FESS AVWT-154FESS AVWT-170FESS AVWT-170FESS
KW 80.0 85.0 90.0 95.0 100.0
Nominal Capacity
KBtu/h 273.0 290.0 307.0 324.1 341.2
Cooling Operation
Power Consumption KW 24.50 25.99 27.48 3034.00 33.20
EER 3.27 3.27 3.28 0.03 3.01
KW 90.0 95.0 100.0 106.0 112.0
Nominal Capacity
KBtu/h 307.1 324.1 341.2 361.7 382.1
Heating Operation
Power Consumption KW 22.60 23.90 25.20 27.90 30.60
COP 3.98 3.97 3.97 3.80 3.66
Air Flow Rate m³/h 23,400 23,400 23,400 23,400 23,400
Outer Dimensions(H×W×D) mm 1,720×(1,210+1,210)×750 1,720×(1,210+1,210)×750 1,720×(1,210+1,210)×750 1,720×(1,210+1,210)×750 1,720×(1,210+1,210)×750
Packing Dimensions mm --- --- --- --- ---
Net Weight Kg 298+298 298+312 312+312 312+318 318+318
Gross Weight Kg 310+310 310+325 325+325 325+330 330+330
Compressor Quantity 4 4 4 4 4
Compressor Fan Quantity 2 2 2 2 2
Cabinet Color Ivory White Ivory White
Gas Line mm Ф31.75 Ф31.75 Ф31.75 Ф31.75 Ф38.1
Heat Pump Operation System
Liquid Line mm Ф19.05 Ф19.05 Ф19.05 Ф19.05 Ф19.05
Liquid Line mm Ф19.05 Ф19.05 Ф19.05 Ф19.05 Ф19.05
Heat Recovery
Low Pressure Gas Line mm Ф31.75 Ф31.75 Ф31.75 Ф31.75 Ф31.75
Operation System
High Pressure Gas Line mm Ф28.6 Ф28.6 Ф28.6 Ф28.6 Ф28.6
Max. Connectable No. of Indoor Units 47.0 50.0 53.0 56.0 59.0
Refrierant Piping Flare-nut Connection(With Flare Nuts)
Between ODU and IDU m 70(90) 70(90) 70(90) 70(90) 70(90)
Height Difference
Between IDUs m 15.0 15.0 15.0 15.0 15.0
Noise Level dB(A) 65 65 65 66 66
Cooling ℃DB -5~48℃ -5~48℃ -5~48℃ -5~48℃ -5~48℃
Operation Range
Heating ℃WB -20~15.5℃ -20~15.5℃ -20~15.5℃ -20~15.5℃ -20~15.5℃

NOTES:
1.The nominal cooling capacity and heating capacity are based on following conditions: 2. The sound pressure is based on the following conditions.1 Meter from the unit service
Cooling Operation Conditions cover surface, and 1.5 Meter from floor level. The above data is based on the cooling
Indoor Air Inlet Temperature: 27℃ DB(80°F DB), 19.0℃WB(66.2°F WB) mode. In case of heating mode, the sound pressure level increases by approximately 1
2dB. The above data was measured in an anechoic chamber so that reflected sound
Outdoor Air Inlet Temperature: 35℃ DB(95°F DB)
should be taken into consideration in the field.
Piping Length: 7.5 Meters Piping Lift: 0 Meter
Heating Operation Conditions 3. Except for the specified combination in the table, there is no other combination of the base unit.
Indoor Air Inlet Temperature: 20℃ DB(68°F DB), 4. The width of outer dimension, it is the value when each distance between the base
Outdoor Air Inlet Temperature: 7℃DB(45°F DB), 6℃WB(43°F WB) outdoor units is specified to 20mm.

81
Hi-FLEXi R Series

Outdoor Unit Specifications

Product line-up
38/40/42HP

Hi-FLEXi M Series HP 38HP 40HP 42HP


AC3Φ 380 ~415V/50HZ AVWT-364FESZ AVWT-382FESZ AVWT-398FESZ
Model Power Supply
AC3Φ 380V/60HZ AVWT-364F7SZ AVWT-382F7SZ AVWT-398F7SZ
AVWT-114FESR AVWT-114FESR AVWT-114FESR
Combination AVWT-114FESR AVWT-114FESR AVWT-114FESR
AVWT-136FESS AVWT-154FESS AVWT-170FESS
KW 109.0 112.0 118.0
Nominal Capacity
KBtu/h 365.1 382.1 399.2
Cooling Operation
Power Consumption KW 32.61 34.10 36.96
EER 3.34 3.28 3.19
KW 118.0 125.0 132.0
Nominal Capacity
KBtu/h 409.5 426.5 447.5
Heating Operation
Power Consumption KW 31.54 32.84 35.54
COP 3.74 3.81 3.71
Air Flow Rate m³/h 32,700 32,700 32,700
Outer Dimensions(H×W×D) mm 1,720×(950+950+1,210)×750 1,720×(950+950+1,210)×750 1,720×(950+950+1,210)×750
Packing Dimensions mm --- --- ---
Net Weight Kg 246+246+298 246+246+312 246+246+318
Gross Weight Kg 255+255+310 255+255+325 255+255+330
Compressor Quantity 4 4 4
Compressor Fan Quantity 3 3 3
Cabinet Color Ivory White
Gas Line mm Ф38.1 Ф38.1 Ф38.1
Heat Pump Operation System
Liquid Line mm Ф19.05 Ф19.05 Ф19.05
Liquid Line mm Ф19.05 Ф19.05 Ф19.05
Heat Recovery
Low Pressure Gas Line mm Ф38.1 Ф38.1 Ф38.1
Operation System
High Pressure Gas Line mm Ф31.75 Ф31.75 Ф31.75
Max. Connectable No. of Indoor Units 64.0 64.0 64.0
Refrierant Piping Flare-nut Connection(With Flare Nuts)
Between ODU and IDU m 70(90) 70(90) 70(90)
Height Difference
Between IDUs m 15.0 15.0 15.0
Noise Level dB(A) 66 66 66
Cooling ℃DB -5~48℃ -5~48℃ -5~48℃
Operation Range
Heating ℃WB -20~15.5℃ -20~15.5℃ -20~15.5℃

NOTES:
1.The nominal cooling capacity and heating capacity are based on following conditions: 2. The sound pressure is based on the following conditions.1 Meter from the unit service
Cooling Operation Conditions cover surface, and 1.5 Meter from floor level. The above data is based on the cooling
Indoor Air Inlet Temperature: 27℃ DB(80°F DB), 19.0℃WB(66.2°F WB) mode. In case of heating mode, the sound pressure level increases by approximately 1
2dB. The above data was measured in an anechoic chamber so that reflected sound
Outdoor Air Inlet Temperature: 35℃ DB(95°F DB)
should be taken into consideration in the field.
Piping Length: 7.5 Meters Piping Lift: 0 Meter
Heating Operation Conditions 3. Except for the specified combination in the table, there is no other combination of the base unit.
Indoor Air Inlet Temperature: 20℃ DB(68°F DB), 4. The width of outer dimension, it is the value when each distance between the base
Outdoor Air Inlet Temperature: 7℃DB(45°F DB), 6℃WB(43°F WB) outdoor units is specified to 20mm.

82
Hi-FLEXi R Series

Outdoor Unit Specifications


Product line-up

44/46/48HP

Hi-FLEXi M Series HP 44HP 46HP 48HP


AC3Φ 380~ 415V/50HZ AVWT-420FESZ AVWT-438FESZ AVWT-454FESZ
Model Power Supply
AC3Φ 380V/60HZ AVWT-420F7SZ AVWT-438F7SZ AVWT-454F7SZ
AVWT-114FESR AVWT-114FESR AVWT-114FESR
Combination AVWT-136FESS AVWT-154FESS AVWT-170FESS
AVWT-170FESS AVWT-170FESS AVWT-170FESS
KW 125.0 132.0 136.0
Nominal Capacity
KBtu/h 421.4 438.4 455.5
Cooling Operation
Power Consumption KW 39.03 40.52 43.38
EER 3.20 3.26 3.14
KW 140.0 145.0 150.0
Nominal Capacity
KBtu/h 472.6 494.7 511.8
Heating Operation
Power Consumption KW 36.72 38.02 40.72
COP 3.81 3.81 3.68
Air Flow Rate m³/h 33,900 33,900 33,900
Outer Dimensions(H×W×D) mm 1,720×(950+1,210+1,210)×750 1,720×(950+1,210+1,210)×750 1,720×(950+1,210+1,210)×750
Packing Dimensions mm --- --- ---
Net Weight Kg 246+298+318 246+312+318 246+318+318
Gross Weight Kg 255+310+330 255+325+330 255+330+330
Compressor Quantity 5 5 5
Compressor Fan Quantity 3 3 3
Cabinet Color Ivory White
Gas Line mm Ф38.1 Ф38.1 Ф38.1
Heat Pump Operation System
Liquid Line mm Ф19.05 Ф19.05 Ф19.05
Liquid Line mm Ф19.05 Ф19.05 Ф19.05
Heat Recovery
Low Pressure Gas Line mm Ф38.1 Ф38.1 Ф38.1
Operation System
High Pressure Gas Line mm Ф31.75 Ф31.75 Ф31.75
Max. Connectable No. of Indoor Units 64.0 64.0 64.0
Refrierant Piping Flare-nut Connection(With Flare Nuts)
Between ODU and IDU m 70(90) 70(90) 70(90)
Height Difference
Between IDUs m 15.0 15.0 15.0
Noise Level dB(A) 67 67 67
Cooling ℃DB -5~48℃ -5~48℃ -5~48℃
Operation Range
Heating ℃WB -20~15.5℃ -20~15.5℃ -20~15.5℃

NOTES:
1.The nominal cooling capacity and heating capacity are based on following conditions: 2. The sound pressure is based on the following conditions.1 Meter from the unit service
Cooling Operation Conditions cover surface, and 1.5 Meter from floor level. The above data is based on the cooling
Indoor Air Inlet Temperature: 27℃ DB(80°F DB), 19.0℃WB(66.2°F WB) mode. In case of heating mode, the sound pressure level increases by approximately 1
2dB. The above data was measured in an anechoic chamber so that reflected sound
Outdoor Air Inlet Temperature: 35℃ DB(95°F DB)
should be taken into consideration in the field.
Piping Length: 7.5 Meters Piping Lift: 0 Meter
Heating Operation Conditions 3. Except for the specified combination in the table, there is no other combination of the base unit.
Indoor Air Inlet Temperature: 20℃ DB(68°F DB), 4. The width of outer dimension, it is the value when each distance between the base
Outdoor Air Inlet Temperature: 7℃DB(45°F DB), 6℃WB(43°F WB) outdoor units is specified to 20mm.

83
Hi-FLEXi R Series

Outdoor Unit Specifications

Product line-up
50/52/54HP

Hi-FLEXi M Series HP 50HP 52HP 54HP


AC3Φ 380~ 415V/50HZ AVWT-476FESZ AVWT-494FESZ AVWT-510FESZ
Model Power Supply
AC3Φ 380V/60HZ AVWT-476F7SZ AVWT-494F7SZ AVWT-510F7SZ
AVWT-136FESS AVWT-154FESS AVWT-170FESS
Combination AVWT-170FESS AVWT-170FESS AVWT-170FESS
AVWT-170FESS AVWT-170FESS AVWT-170FESS
KW 140.0 145.0 150.0
Nominal Capacity
KBtu/h 477.7 494.7 511.8
Cooling Operation
Power Consumption KW 45.45 46.94 49.80
EER 3.08 3.09 3.01
KW 155.0 160.0 165.0
Nominal Capacity
KBtu/h 528.9 545.9 563.0
Heating Operation
Power Consumption KW 41.90 43.20 45.90
COP 3.70 3.70 3.59
Air Flow Rate m³/h 35,100 35,100 35,100
Outer Dimensions(H×W×D) mm (1,720×1,210×750)×3 (1,720×1,210×750)×3 (1,720×1,210×750)×3
Packing Dimensions mm --- --- ---
Net Weight Kg 298+318+318 312+318+318 318+318+318
Gross Weight Kg 310+330+330 325+330+330 330+330+330
Compressor Quantity 6 6 6
Compressor Fan Quantity 3 3 3
Cabinet Color Ivory White
Gas Line mm Ф38.1 Ф38.1 Ф38.1
Heat Pump Operation System
Liquid Line mm Ф19.05 Ф19.05 Ф19.05
Liquid Line mm Ф19.05 Ф19.05 Ф19.05
Heat Recovery
Low Pressure Gas Line mm Ф38.1 Ф38.1 Ф38.1
Operation System
High Pressure Gas Line mm Ф31.75 Ф31.75 Ф31.75
Max. Connectable No. of Indoor Units 64.0 64.0 64.0
Refrierant Piping Flare-nut Connection(With Flare Nuts)
Between ODU and IDU m 70(90) 70(90) 70(90)
Height Difference
Between IDUs m 15.0 15.0 15.0
Noise Level dB(A) 67 67 68
Cooling ℃DB -5~48℃ -5~48℃ -5~48℃
Operation Range
Heating ℃WB -20~15.5℃ -20~15.5℃ -20~15.5℃

NOTES:
1.The nominal cooling capacity and heating capacity are based on following conditions: 2. The sound pressure is based on the following conditions.1 Meter from the unit service
Cooling Operation Conditions cover surface, and 1.5 Meter from floor level. The above data is based on the cooling
Indoor Air Inlet Temperature: 27℃ DB(80°F DB), 19.0℃WB(66.2°F WB) mode. In case of heating mode, the sound pressure level increases by approximately 1
2dB. The above data was measured in an anechoic chamber so that reflected sound
Outdoor Air Inlet Temperature: 35℃ DB(95°F DB)
should be taken into consideration in the field.
Piping Length: 7.5 Meters Piping Lift: 0 Meter
Heating Operation Conditions 3. Except for the specified combination in the table, there is no other combination of the base unit.
Indoor Air Inlet Temperature: 20℃ DB(68°F DB), 4. The width of outer dimension, it is the value when each distance between the base
Outdoor Air Inlet Temperature: 7℃DB(45°F DB), 6℃WB(43°F WB) outdoor units is specified to 20mm.

84
Hi-FLEXi R Series

Outdoor Unit Dimensional Data


Model: AVWT-76FESR, AVWT-96FESR and AVWT-114FESR Unit: mm

Viewed from P
98 227 300 227 Hole for

105
131 688 131 Condensate Drain
Product line-up

(Ø26 x 4)
18

Hole for

157
Power Supply Wiring
729

(Ø52)

Hole for Holes for


4-Holes Refrigerant Piping Control Line or
18

(38 x 15) (235 x 113) Power Supply Wiring


(Ø26 x 2)
213

Service Cover

Electrical Control Box

Gas Line Refrigerant


Piping Connection
(Low Pressure)
767

ØA Field-Supplied Pipe Size


Gas Line Refrigerant
Piping Connection
1720

(High Pressure)
ØB Field-Supplied Pipe Size
345 Liquid Line

Q
185 Gas Line

Liquid Line Refrigerant


Piping Connection
ØC Field-Supplied Pipe Size
640

100

Hole for
P Power Supply Wiring
(Ø52 x 2)
60

Hole for
Refrigerant Piping and
Control Line Wiring
20

145
100

155 Gas Line


205 155 Liquid Line
285 78 608
238 298 238 88 750
950 765

Viewed from Q Field Installation (Example)

Accessory Pipe
Insulation

Brazing
(295)

Anchor Bolt
(M12)
(Front Side) (Rear Side)
(Standard)
50

less than 30

Hole for Concrete


Power Supply Wiring 70
Foundation
(Ø52 x 2)

Heat Pump System (2 Pipes)


Dimension
Hole for A B C
Model
Refrigerant Piping and AVWT-76FESR - 19.05 9.53
Control Line Wiring
AVWT-96FESR - 22.2 9.53
AVWT-114FESR - 25.4 12.7
NOTES:
1. Drain water is discharged from the unit during the operation. Heat Recovery System (3 Pipes)
a. Choose a place where well drainage is available. Provide a groove for drain. Dimension
A B C
b. Do not provide an upward slope from the unit to avoid reverse flow of the drain. Model

Provide a second drain pan under the outdoor unit, to collect drain water securely. AVWT-76FESR 19.05 15.88 9.53
AVWT-96FESR 22.2 19.05 9.53
c. Do not use the drain boss (optional) in a cold area. (Drain water in the drain pipe may be frozen and the drain pipe may crack.)
AVWT-114FESR 25.4 22.2 12.7
2. The dimensions marked with indicates the mounting pitch dimension for anchor bolts.

85
Hi-FLEXi R Series

Model: AVWT-136FESS, AVWT-154FESS and AVWT-170FESS Unit: mm


Viewed from P
131 948 131 98 227 560 227 Hole for

105
Condensate Drain

18
(Ø26 x 4)

Product line-up
Hole for

157
729
Power Supply Wiring
(Ø52)

4-Holes Hole for Holes for


18

(38 x 15) Refrigerant Piping Control Line or


(245 x 138) Power Supply Wiring
(Ø26 x 2)

Service Cover
213

Electrical Control Box

Gas Line Refrigerant


Piping Connection
(Low Pressure)
767

ØA Field-Supplied Pipe Size


Gas Line Refrigerant
Piping Connection
1720

(High Pressure)
ØB Field-Supplied Pipe Size Q
325 Liquid Line
180 Gas Line

Liquid Line Refrigerant


Piping Connection
ØC Field-Supplied Pipe Size
640

100

Hole for
P Power Supply Wiring
(Ø52 x 2)
60

Hole for
Refrigerant Piping and
Control Line Wiring
100
20

145 170 Gas Line


205 175 Liquid Line

285 78 608
238 558 238 88 750
1210 765

Viewed from Q
Field Installation (Example)

Insulation
Accessory Pipe

Brazing

Anchor Bolt
(276)

(M12)

(Front Side)
(Rear Side)
Hole for
Power Supply Wiring (Standard)
less than 30
50

(Ø52 x 2)
70 Concrete
Foundation

Hole for Heat Pump System (2 Pipes)


Refrigerant Piping and Dimension
A B C
Control Line Wiring Model
AVWT-136FESS - 25.4 12.7
NOTES: AVWT-154FESS - 28.6 12.7
1. Drain water is discharged from the unit during the operation. AVWT-170FESS - 28.6 15.88
a. Choose a place where well drainage is available. Provide a groove for drain.
Heat Recovery System (3 Pipes)
b. Do not provide an upward slope from the unit to avoid reverse flow of the drain. Dimension
Provide a second drain pan under the outdoor unit, to collect drain water securely. A B C
Model
c. Do not use the drain boss (optional) in a cold area. (Drain water in the drain pipe may be frozen and the drain pipe may crack.) AVWT-136FESS 25.4 22.2 12.7
2. The dimensions marked with indicates the mounting pitch dimension for anchor bolts. AVWT-154FESS 28.6 22.2 12.7
AVWT-170FESS 28.6 22.2 15.88

86
Hi-FLEXi R Series

Pipe Diameter for Outdoor Unit

Piping Size for AVWT-86U6(7)SR to AVWT-154U6(7)SS (Base Unit) Outdoor Unit


Product line-up

a
To Indoor Units
Refrigerant Piping
(ĭ mm)

Model AVWT-76FESR AVWT-96FESR AVWT-114FESR AVWT-136FESS AVWT-154FESS AVWT-170FESS

Gas 19.05 22.2 25.4 25.4 28.6 28.6


Piping Size a
Liquid 9.53 9.53 12.7 12.7 12.7 15.88

Piping Size for AVWT-190FESZ to AVWT-340FESZ (2 Units Combination)

< Figure for AVWT-232FESZ >

(Indoor Unit on Left Side) (Indoor Unit on Right Side)

Outdoor Unit A Outdoor Unit B Outdoor Unit B Outdoor Unit A

a b b a
c c
To Indoor Units Manifold Pipe Manifold Pipe To Indoor Units

(ĭmm)

Model AVWT-190FESZ AVWT-212FESZ AVWT-232FESZ AVWT-250FESZ AVWT-272FESZ AVWT-290FESZ AVWT-308FESZ AVWT-324FESZ AVWT-340FESZ
Outdoor
AVWT-114FESR AVWT-136FESS AVWT-136FESS AVWT-136FESS AVWT-136FESS AVWT-154FESS AVWT-154FESS AVWT-170FESS AVWT-170FESS
Combination Unit A
Unit Outdoor
AVWT-76FESR AVWT-76FESR AVWT-96FESR AVWT-114FESR AVWT-136FESS AVWT-136FESS AVWT-154FESS AVWT-154FESS AVWT-170FESS
Unit B
Manifold Pipe HFQ-M22F HFQ-M32F

Gas 28.6 28.6 28.6 31.75 31.75 31.75 31.75 31.75 38.1
a
Liquid 15.88 15.88 15.88 19.05 19.05 19.05 19.05 19.05 19.05

Gas 25.4 25.4 25.4 25.4 25.4 28.6 28.6 28.6 28.6
Piping Size b
Liquid 12.7 12.7 12.7 12.7 12.7 12.7 12.7 15.88 15.88

Gas 19.05 19.05 22.2 25.4 25.4 25.4 28.6 28.6 28.6
c
Liquid 9.53 9.53 9.53 12.7 12.7 12.7 12.7 12.7 15.88

*
Refer to the table for the outdoor unit model, the manifold pipe model and the piping diameter.

87
Hi-FLEXi R Series

Piping Size for AVWT-328U6(7)SZ to AVWT-460U6(7)SZ (Triple Units Combination)

< Figure for AVWT-365U6(7)SZ >

Product line-up
(Indoor Unit on Left Side) (Indoor Unit on Right Side)

Outdoor Unit A Outdoor Unit B Outdoor Unit C Outdoor Unit C Outdoor Unit B Outdoor Unit A

c d d c
a b d a
e e

To Indoor Units Manifold Pipe 1 Manifold Pipe 2 To Indoor Units


Manifold Pipe 2 Manifold Pipe 1

(ĭmm)

Model AVWT-328* AVWT-345* AVWT-365* AVWT-386* AVWT-402* AVWT-426* AVWT-444* AVWT-460*


Outdoor
AVWT-154* AVWT-154* AVWT-136* AVWT-154* AVWT-154* AVWT-154* AVWT-154* AVWT-154*
Unit A
Combination Outdoor
AVWT-96* AVWT-96* AVWT-114* AVWT-114* AVWT-136* AVWT-154* AVWT-154* AVWT-154*
Unit Unit B
Outdoor
AVWT-86* AVWT-96* AVWT-114* AVWT-114* AVWT-114* AVWT-114* AVWT-136* AVWT-154*
Unit C
Manifold pipe HFQ-M22F + HFQ-M32F HFQ-M32F + HFQ-M32F

Gas 31.75 38.1 38.1 38.1 38.1 38.1 38.1 38.1


a
Liquid 19.05 19.05 19.05 19.05 19.05 19.05 19.05 19.05

Gas 28.6 28.6 28.6 28.6 31.75 31.75 31.75 31.75


b
Liquid 15.88 15.88 15.88 15.88 19.05 19.05 19.05 19.05

Gas 28.6 28.6 25.4 28.6 28.6 28.6 28.6 28.6


Piping Size c
Liquid 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7

Gas 22.2 22.2 25.4 25.4 25.4 28.6 28.6 28.6


d
Liquid 9.53 9.53 12.7 12.7 12.7 12.7 12.7 12.7

Gas 19.05 22.2 25.4 25.4 25.4 25.4 25.4 28.6


e
Liquid 9.53 9.53 12.7 12.7 12.7 12.7 12.7 12.7

*
Refer to the table for the outdoor unit model, the manifold pipe model and the piping diameter.

88
Hi-FLEXi W Series

Wide Application Area


Product line-up

Building Water-cycling System Adoption of Underground Water


Generally, it is known as water-cycling system, in which the circulation water is Open-well system bears the load in water system by use of underground water,
heated by electrical or gas boiler in winter and dissipates the heat out of it by the the merits of which are the completion of relatively constant circulation water
use of cooling tower in summer to maintain the temperature of system, especially temperature (generally within a range of 12-15℃) and the application in place
at the turn of the season, it can realize the maximum energy-saving in operation. where the geology and soil allow water recharge. Therefore, environment
protection and lower running costs are achieved.

Adoption of Surface Water Urban Sewage, Recycled Water, Trade Effluent


Place closed-cycle heat exchange pipe line lake or pond or other surface water Waste water heat cycling system recycles a variety of low-grade waste heat,
near buliding. Heating or cooling is performed for building through exchange heat which is one of effective ways to solve the problem of high energy consumption
between closed-cycle water and surface water. The depth and area of water are for hot water in buildings. The significant reduction of temperate difference
very important and must be approved to meet the requirement of building load. between cool and heat source not only contributes to energy conservation but
also great water source saving.

Adoption of Soil Source Adoption of Seawater Source


Punch holes and bury plastic composite heat exchange pipes underground Through heat exchange between seawater and circulation water in water-source
(including vertical type and horizontal type).Vertical type is applicable for the place heat pump system, seawater-source cycling system introduce low-temperature
with small area and being in need of deep pipe burying while horizontal type can and low-grade heat of seawater into the building space to achieve heating and
be used in large space. Heat exchange between underground pipes and soil cooling.The biggest advantage of this system is the effective application of
helps realize air conditioning, higher initial investment and lower running costs. resources, which contributes to none seawater consumption, none seawater
pollution and high.

89
Hi-FLEXi W Series

Water Source Application Advantages


Hisense water-source inverter-driven multi-split air conditioning incorporates the merits of air-cooled inverter-driven multi-split
system and water-soil-source heat pump system. It has high flexibility of variable load adjustment, high partial load efficiency and
high combination freedom in multi-split system, and also has the advantage of high energy efficiency and stable operation in
water-soil-source heat pump system, then greatly improves the unit's overall operating performance.

Product line-up
High Efficiency, Superb Model COP 30%

Hisense Flexi W series central air conditioning integrates


inverter-driven technology with water-source heat
exchange technology. Through all the aspects of optimiza-
tion design, a high COP value can be maintained in a larger
operating range of cooling and heating.
Aircooled Hi-FLEXi W Series

Refrigerant Evaporates Directly, Primary Heat Exchange

Primary Heat Exchange, Less


Energy Loss
Middle-and-low-temperature water(10~45℃) is flowing in Indoor Unit
waterside pipeline, which results in less loss in intermedi-
ate links. Furthermore, a direct evaporation technology
Chiller
of refrigerant is applied in indoor units, which avoids heat
exchange efficiency decrease caused by secondary Water Pipe

heat exchange and greatly enhances COP value in air


conditioning system. Hisense Hi-FLEXI W Series

90
Hi-FLEXi W Series

Simultaneous Cooling and Heating, More Energy-saving in Heat


Recovery System
The requirement of simultaneous cooling and heating operation has been increasing due to the large modern buildings with complex
structure, function and more demand for comfort, especially at the turn of the season or in winter. Conventional central air condition-
ing system consumes more energy when cooling and heating coexist. Hi-FLEXi W series divides space into interior and exterior
Product line-up

sections, easily satisfies the requirement of simultaneous cooling and heating in the same building, realizes heat recovery and
maximum energy-saving.

Heat Exhaust
Cooling

Cooling
Heat Exhaust

Heating
Heat Suction

Cooling
Heat Exhaust

Heat Recovery Among Different Floors Heat Recovery on the Same Floor

*Heat recovery is achieved by taking water as heat carrier among multiple units connected to the same water circulation system.

Stable Performance
By the use of water source and soil source, the performance of Hi-FLEXi W
series will not be affected by high temperature. Even if in hot summer, its Constant
Water Temp.
cooling capacity will not attenuate. Likewise, in heating operation,practically, the
heat source temperature is higher and relatively uniform, so that the frosting
and defrosting will not occur, which contributes to stable performance. No effect on System

Flexible Placement Greatly Improves the Utilization Rate of Space


Generally, conventional centralized water source heat pump units are of large size. In addition, they need special machineroom to be
placed centrally. By contrast, Hi-FLEXi W series has the following main features in the installation:

◎Compact Structure, Easy Transportation .

3-6HP:H800XW800XD370mm 8-10HP:H1000XW780XD550mm

91
Hi-FLEXi W Series

Modular Structure, Flexible Installation

Product line-up
3200mm
or more
The same module size helps realize modular combination, and
multiple units can be stacked

A wide selection of multi-kit can be chosen according to total capacity of


indoor units connected downstream, which greatly facilitates refrigerant
pipe work on site and simplifies the procedure of construction.

about 2,000mm
about 1,000mm

AVWW-154 16HP 8HP+8HP

AVWW-170 18HP 8HP+10HP

AVWW-190 20HP 10HP+10HP

Long Refrigerant Pipe Design, Suitable for High Rise


Thanks to the integration of water cycling system and refrigerant cycling system, there is no limitation for the length of water pipe-line,
which easily meets the AC need of large-scale and high-rise building. Furthermore, Hi-FLEXi W series allows a maximum refrigerant pipe
length of 75m between chiller units and indoor units, which contributes to more flexible design. In conventional centralized water source
heat pump system, the chiller units provide heat (cold) source directly for indoor units, more power consumption of water pump and more
energy loss of refrigerating medium will arise from long pipe-line in system.


③ Model 3HP 4/5/6HP 8/10/16/18/20HP

Max.Equivalent Piping Length 30 75 120

Total Piping Length 45 120 300




Max.Distance Between
15 30 40
1st Branch and Indoor Unit

Max.Height Difference
5 15 15
Between Indoor Units

Max.Height Difference Between


I. U. and O. U. ( O. U. is lower than I. U. ) 15(15) 30(30) 50(40)

* In case of high-rise building, the water pressure limitation that the


plate heat exchanger can bear must be taken into consideration.

92
Hi-FLEXi W Series

Outdoor Unit Specifications


Product line-up

AC1Ф, 220 ~240V/50Hz AVWW-28UCSA AVWW-38UCSA AVWW-48UCSA AVWW-54UCSA


Model Power Supply
AC1Ф, 220V/60Hz AVWW-28U2SA AVWW-38U2SA AVWW-48U2SA AVWW-54U2SA
KW 8.00 11.20 14.00 15.50
Nominal Capacity*1
KBtu/h 27.3 38.2 47.8 52.9
Cooling Operation
EER Rated Input KW 1.90 2.60 3.41 3.88
EER 4.21 4.31 4.11 3.99
KW 9.00 12.50 16.00 18.00
Nominal Capacity*1
KBtu/h 30.7 42.7 54.6 61.4
Heating Opeartion
Rated Input KW 1.80 2.40 3.14 3.60
COP 5.00 5.21 5.10 5.00
Height mm 800 800 800 800
Width mm 800 800 800 800
Outer Dimensions
Depth mm 370 370 370 370
Aera m² 0.3 0.3 0.3 0.3
Packing Dimensions mm 980×450×930 980×450×930 980×450×930 980×450×930
Net Weight Kg 78 100 100 100
Gross Weight Kg 85 107 107 107
Water Temperature*3 ℃ 10~45 10~45 10~45 10~45
Water-Side Heat Exchanger Water Flow Rate l/min 30 38 48 53
Water Pressure Drop kPa 30 30 35 40
Sound Pressure Level *2 Cooling/Heating dB(A) 49 51 51 51
Refrigerant Liquid Pipe mm Ф9.53 Ф9.53 Ф9.53 Ф9.53
Refrigerant Gas Pipe mm Ф15.88 Ф15.88 Ф15.88 Ф15.88
Piping Connection Water Pipe DN25 DN25 DN25 DN25
Thread of Connector G1B G1B G1B G1B
Drain Pipe mm Ф18 Ф18 Ф18 Ф18
Water-Side Bearing Pressure Ability Kgf/cm 20 20 20 20
Max. Connectable Indoor Units 4 5 6 7

NOTES:
*1. Operation Condition:
Cooling:Indoor Temperature 27℃ DB/19℃ WB,Outdoor Temperature 27℃ DB,Water Inlet/Outlet 30/35℃.
Heating:Indoor Temperature 20℃ DB/15℃ WB,Outdoor Temperature 20℃ DB,Water Inlet 20℃.
*2. The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
*3. When unit is operating out of the allowable water temperature range, it won’t start normally and will alarm.

93
Hi-FLEXi W Series

Outdoor Unit Specifications

Product line-up
AC3Ф, 380~ 415V/50Hz AVWW-76UESB AVWW-96UESB AVWW-154UCSB AVWW-170UCSB AVWW-190UCSB
Model Power Supply
AC3Ф, 380V/60Hz AVWW-76U7SB AVWW-96U7SB AVWW-154U7SB AVWW-170U7SB AVWW-190U7SB
KW 22.40 28.00 45.00 50.00 56.00
Nominal Capacity*1
KBtu/h 76.5 95.6 153.6 170.6 191.1
Cooling Operation KW
Rated Input 4.42 6.26 8.84 10.68 12.52
EER 5.07 4.77 5.07 4.68 4.47
KW 25.00 31.50 50.00 56.00 63.00
Nominal Capacity*1
KBtu/h 85.3 107.5 170.6 191.1 215.0
Heating Opeartion
Rated Input KW 4.2 5.81 8.4 10.01 11.62
COP 6.00 5.42 5.95 5.95 5.42
Height mm 1000 1000 1000 1000 1000
Width mm 780 780 780+780 780+780 780+780
Outer Dimensions
Depth mm 550 550 550 550 550
Aera m² 0.4 0.4 0.86 0.86 0.86
Packing Dimensions mm 850X600X1,120 850X600X1,120 -- -- --
Net Weight Kg 160 160 160+160 160+160 160+160
Gross Weight Kg 165 165 165+165 165+165 165+165
Water Temperature*3 ℃ 10 ~ 45 10 ~ 45 10 ~ 45 10 ~ 45 10 ~ 45
Water-Side Heat Exchanger Water Flow Rate l/min 76.8 96 153.6 172.8 192
Water Pressure Drop KPa 35 40 35 40 40
Sound Pressure Level *2 Cooling/Heating dB(A) 50 51 51 51 52
Refrigerant Liquid Pipe mm Ф12.7 Ф12.7 Ф15.88 Ф15.88 Ф15.88
Refrigerant Gas Pipe mm Ф19.05 Ф22.2 Ф28.6 Ф28.6 Ф28.6
Piping Connection Water Pipe DN32 DN32 DN32 DN32 DN32
Thread of Connector G1 1/4B G1 1/4B G1 1/4B G1 1/4B G1 1/4B
Drain Pipe mm Ф18 Ф18 Ф18 Ф18 Ф18
Water-Side Bearing Pressure Ability Kgf/cm 20 20 20 20 20
Max. Connectable Indoor Units 13 16 20 20 20

NOTES:
*1. Operation Condition:
Cooling:Indoor Temperature 27℃ DB/19℃ WB,Outdoor Temperature 27℃ DB,Water Inlet/Outlet 30/35℃.
Heating:Indoor Temperature 20℃ DB/15℃ WB,Outdoor Temperature 20℃ DB,Water Inlet 20℃.
*2. The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
*3. When unit is operating out of the allowable water temperature range, it won’t start normally and will alarm.

94
Hi-FLEXi W Series

Outdoor Unit Dimensional Data

AVWW-28UC(2)SA, AVWW-38UC(2)SA, AVWW-48UC(2)SA and AVWW-54UC(2)SA Unit: mm


Product line-up

Hole for Wiring

Liquid Line Refrigerant


Piping Connection
Water Outlet
9.52

Gas Line Refrigerant


Piping Connection Water Inlet
15.88

95
Hi-FLEXi W Series

AVWW-76U(7)ESB, AVWW-96U(7)ESB Unit: mm

Product line-up
Viewed from A

4-Holes

Holes for Refrigerant Piping

Hole for Wiring

Gas Line Refrigerant


Piping Connection
8HP: 19.05 Flare Nut Connection
10HP: 22.2 Flange Connection

Liquid Line Refrigerant


Piping Connection
12.7 Flare Nut Connection
Water Outlet

Center of Gravity Center of Gravity

Water Inlet

96
Hi-FLEXi C Series

Technology to Improve Heat Exchanger Performance


In the Hi-FLEXi C series model, wind speed distribution is rendered uniform by making the direction of the wind flow same to the
fan and the heat exchanger. As a result, the performance of the heat exchanger is optimized and energy is saved.
Product line-up

Ventilation Resistance Reduction Effect


Current Modle Hi-FLEXi C Series
(Top-flow Type)

Air Outlet
Hi-FLEXI C series
Heat Exchanger
Heat Exchanger

Top-flow Type Hi-FLEXi C Series

Ventilation Resistance Reduction Effect


Air Inlet
Air Inlet

Air Velocity(m/s) Air Velocity(m/s) Hi-FLEXI C series

Top-flow Type Hi-FLEXi C Series

Low Noise Technologies

DC Fan Motor
The smooth rotating fan motor with low
vibration reduces the noise level. Super High-stream Fan DC Fan Motors

Super High-stream Fan


Supper high-stream fan of Φ544mm
New Fin with
cuts down the noise level.
Less Pressure Loss

Low Pressure Loss Air Outlet Grille


The rib structure synchronized with
rotation flow from the fan reduces the
air resistance at the air outlet grille.

New Fin with Less Pressure Loss Less Pressure Loss


The rib structure synchronized with Air Outlet Grille

rotation flow from the fan reduces the air


resistance at the air outlet grille.

97
Hi-FLEXi C Series

Features
Provide in a compact body, but allows installation conditions comparable with those of a high-performance multi-split air condition-
ing system.
The compact and light body facilitates delivery and installation.

Product line-up
The adoption of a slim body improves flexibility in mounting, enabling installation in a small space or a formerly dead space.

Top-class Compact and Light Weight Design


Facilitation and flexibility at installation are further advanced by adopting outdoor units light weight and compact design
compared to the current top-flow model.

Top-flow Type Hi-FLEXi C Series

Slim and Refined Body Design


The compact outdoor unit can be flexibly placed according to outdoor condition. Low-height in-the-ceiling type can be easily
installed inside the low-height residential ceiling with a height of 192mm, which makes low height indoor units and elegant home
decoration style set off mutually.

98
Hi-FLEXi C Series

Various Model Types Easily Match Different Layout


Wide capacity range of outdoor units enables free model combination according to the actual situation of building. There are 9
types of indoor units for selection. Designer can choose the appropriate type and capacity range of indoor units according to the
Product line-up

interior decoration and furnitures.

Greater Convenience During Delivery and Installation

With its light and compact body, the Hi-FLEXi C Series can be
easily carried in the elevator even in a small urban site.
Light and compact body
No cranes required for delivery facilitates renewal

The unit can be carried at one time.


Elevators can be used for delivery.

99
Hi-FLEXi C Series

Long Piping Design

The piping can be designed and constructed up to a total Piping length 100m (total piping length of 250m)

Product line-up
Piping length: 100 m(Equivalent length :125m)

Max .length after first branch : 40m

Max.length after branch : 15m

Height difference between indoor units : 15m

Max. height difference between ODU and IDU Outdoor unit is higher: 50m Indoor unit is higher : 40m

Total piping length: 250m

4 5
3
1

100
Hi-FLEXi C Series

Outdoor Unit Specifications


Product line-up

Hi-FLEXi C HP 8HP 10HP 12HP


AC3Φ380~415V/50Hz AVW-76UESR AVW-96UESR AVW-114UESR
Model Power Supply
AC3Φ380V/60Hz AVW-76U7SR AVW-96U7SR AVW-114U7SR
KW 22.4 28.0 33.5
Nominal Capacity
KBtu/h 76.5 95.6 114.3
Cooling Operation
Consumption Power KW 6.3 8.3 10.7
EER 3.6 3.4 3.1
KW 25.0 31.5 37.5
Nominal Capacity
KBtu/h 85.3 107.5 128.0
Heating
Consumption Power KW 5.9 7.8 9.9
COP 4.2 4.0 3.8
Air Flow Rate m³/h 7,260 9,000 9,780
Outer Dimension mm 1,650×1,100×390
Packing Dimension mm 1,748×1,151×500
Net Weight Kg 168 168 171
Gross Weight Kg 179 179 182
Gas Line mm Ф19.05 Ф22.2 Ф25.4
Refrigerant piping
Liquid Line mm Ф9.53 Ф12.7 Ф12.7
Max. number of connectable IDU 10 10 10
Max. Piping Length m 100 100 100
Between ODU & IDU m 50(40) 50(40) 50(40)
Height Difference
Between IDUs m 15 15 15
Noise Level dB(A) 53/55 56/58 56/61
Cooling ℃ DB -5~43 -5~43 -5~43
Operation Range
Heating ℃ WB -20~15 -20~15 -20~15

101
Hi-FLEXi C Series

Product line-up
AVW-76UE(7)SR

AVW-96UE(7)SR

AVW-114UE(7)SR

AVW-76UE(7)SR

102
Hi-Smart L Series

High User Experience

Free Combination
One outdoor unit of Hi-Smart L series can connect maximum 7 indoor units in different types. The free combination not only
Product line-up

meets the air condition needs of large space, but also helps match the indoor decoration. Flexible choice and better system
configuration start a tour of Luxury life.

Refrigerant Pipe
Drain Pipe

Slim and Refined Body Design


The compact outdoor unit can be flexibly placed according to outdoor condition. Low-height in-the-ceiling type can be easily
installed inside the low-height residential ceiling with a height of 192mm, which makes low height indoor units and elegant home
decoration style set off mutually.

103
Hi-Smart L Series

Long Piping Design


Long refrigerant piping design makes project design and installation works more convenient.

Max. height difference between the highest and the lowest indoor units is 10m.

Product line-up
Max. height difference between outdoor and indoor units is 30m.
Max. piping length is 75m.
Total piping length can be 120m.

Max. 75m

30m

10m

1104
10
04
Hi-Smart L Series

Outdoor Unit Specifications


Product line-up

Hi-Smart L series HP 4 5 6
AC1Φ, 220 ~240V/50Hz AVW-38UCSC AVW-48UCSC AVW-54UCSC
AC1Φ, 220V/60Hz AVW-38U2SC AVW-48U2SC AVW-54U2SC
Model Power Supply
AC3Φ, 380 ~415V/50Hz --- AVW-48UESC AVW-54UESC
AC3Φ, 380V/60Hz --- AVW-48U7SC AVW-54U7SC
Kw 11.2 14.0 15.5
Nominal Capacity
KBtu/h 38.2 47.8 52.9
Cooling Operation
Power Consumption KW 2.99 3.92 4.44
EER 3.75 3.57 3.49
KW 12.5 16.0 18.0
Nominal Capacity
KBtu/h 42.7 54.6 61.4
Heating Opeartion
Power Consumption KW 2.98 4.03 4.74
COP 4.19 3.97 3.80
Air Flow Rate m³/h 5,400 5,400 6,000
Outer Dimension mm 1,380×950×370
Packing Dimension mm 1,040×460×1,500
Net Weight Kg 93 95 97
Gross Weight Kg 106 108 110
Liquid Line mm Φ9.53 Φ9.53 Φ9.53
Refrigerant Piping
Gas Line mm Φ15.88 Φ15.88 Φ15.88
Max. number of connectable IDU 6 7 7
Noise Level Cooling/Heating dB(A) 52/54 52/55 54/56
Cooling Operation ℃ DB -5~46℃DB
Operation Range
Heating Operation ℃ WB -20~15.5℃WB
Branch Pipe HFQ-052F

NOTES:
2. The sound pressure lever is based on following
1.The nominal cooling capacity and heating capacity are based on following conditions:
Cooling Operation Conditions conditions.1.5m beneath the unit.
Indoor Air Inlet Temperature: 27℃ DB(80ºF DB) Heating Operation Conditions The above date was measured in an anechoic
19.0℃ WB(66.2ºF WB) Indoor Air Inlet Temperature: 20℃ DB(68ºF DB) chamber so that reflected sound should be taken
Outdoor Air Inlet Temperature: 35℃ DB(95ºF DB) Outdoor Air Inlet Temperature: 7℃ DB(45ºF DB) into consideration in the field.
Piping Length: 7.5Meters Piping Lift: 0 Meter 6℃ WB(43ºF WB)

105
Hi-Smart L Series

Outdoor Unit Dimensional Data AVW-38~54UC(2)SC Unit: mm

Service Space Product line-up

NOTES:
1.Stop valve is installed in the hood.
2.The interval dimension between fixed bolts for installation is 600×410.

106
Hi-Smart E Series

Leading Low Carbon New Life


The Earth is the home of ours!Pay close attention to the climate change together with Hisense, choose R410A environmentally friendly
refrigerant and focus on low carbon lifestyle. Low carbon lifestyle is a kind of love, a kind of attitude and even a kind of responsibility.
Earth protection and living environment protection start from the choice of Hisense.
Product line-up

Five Core Technologies

1
Intelligent and
5
Intelligent Defrosting
High Efficient Technology

2 4
DC Inverter-driven
Technology 3
Low Noise and
3D Temperature
Control Technology

Low Frequency Operation

Unique Designs Create Refined Life


Intelligent Multi-split Design
Hi-Smart E outdoor unit adopts the leading single-piping connection
technology and connects multiple indoor units freely. The indoor unit
adopts 2000-step micro-computer EEV (electronic expansion valve)
to achieve automatic refrigerant flow control according to indoor
load, which results in more precise and comfortable temperature
control.
Refrigerant Pipe

Drain Pipe

107
Hi-Smart E Series

Slim and Refined Body Design


The compact outdoor unit can be flexibly placed according to outdoor condition. Low-height in-the-ceiling type can be easily
installed inside the low-height residential ceiling with a height of 192mm, which makes low height indoor units and elegant home
decoration style set off mutually.

Product line-up
192mm

Flexible Long Piping Design Max. 25m

Max. piping length is 40m. Max. height difference


between outdoor and indoor units is 20m. Height
difference between highest and lowest indoor units is
3.5m. Design and installation are more convenient. 20m

NOTES: 2.0m
Hi-Smart E Series has 3 types of indoor units for selection:
Low-height ceiling ducted type
Slim ceiling ducted type
Wall mounted type

108
Hi-Smart E Series

Outdoor Unit Specifications


Product line-up

Hi-Smart E series HP 3 4 5
AC1Φ, 220 ~240V/50Hz AVW-28UCSB AVW-34UCSB AVW-43UCSB

Model Power Supply AC1Φ, 220V/60Hz AVW-28U2SB AVW-34U2SB AVW-43U2SB


AC3Φ, 380~415V/50Hz --- --- AVW-43UESB
AC3Φ, 380V/60Hz --- --- AVW-43U7SB
KW 8.0 10.0 12.5
Nominal Capacity
KBtu/h 27,300 34,100 42,700
Cooling Operation
Power Consumption KW 2.66 2.86 3.81
EER 3.01 3.50 3.28
KW 9.5 11.2 14.0
Nominal Capacity
KBtu/h 32,400 38,200 47,800
Heating Opeartion
Power Consumption KW 2.42 2.75 3.68
COP 3.93 4.07 3.80
Air Flow Rate m³/h 2,970 4,140 4, 680
Outer Dimension mm 800×950×370
Packing Dimension mm 1,020×460×940
Net Weight Kg 65 73 78
Gross Weight Kg 75 83 88
Liquid Line mm Φ9.53 Φ9.53 Φ9.53
Refrigerant Piping
Gas Line mm Φ15.88 Φ15.88 Φ15.88
Max. number of connectable IDU 3 4 4
Noise Level Cooling/Heating dB(A) 50/52 53/54 54/57
Cooling Operation ℃ DB 10~43℃DB
Operation Range
Heating Operation ℃ WB -15~15℃WB
Branch Pipe HFQ-052F

NOTES:
1.The nominal cooling and heating capacities show the capacities when the outdoor with the 100% rating of indoor unit.
Cooling Operation Conditions
Indoor Air Inlet Temperature:27℃DB/19℃WB
Outdoor Air Inlet Temperature:35℃DB
Piping Length:7.5Meters Piping Lift:0 Meter
2.The sound pressure level is based on following conditions:
1.5 Meters from floor Level,and 1Meter from the unit service cover surface.
The above data was measured in an anechoic chamber so that reflected sounde shoudle be taken into consideration in the field.

109
Hi-Smart E Series

Outdoor Unit Dimensional Data

AVW-28~43UC(2)SB Unit: mm

Product line-up
Piping and Wiring Hole

Ground

Gas Pipe Connection

Air Outlet

Piping and Wiring Hole


Piping and Wiring Hole

Note:
1. The unit is equipped with stop valve; field refrigerant pipes are connected to stop valve through flare opening.
2. Illustrated 110 dimension marked with ** is to avoid possible conflict with the foundation, etc. in piping from the bottom.
3. Dimension marked with * is the location dimension of anchor holes.

Service Space

110
Indoor Unit

Hisense Hi-Flexi & Hi-Smart series provide a wide selection of indoor units for indoor decoration and create a
personalized living space.
Product line-up

HP 0.8 1.0 1.3 1.5 1.8 2.0 2.3 2.5 3.0 3.3 4.0 5.0 6.0 8 10
kBtu/h 7 9 12 14 17 18 22 24 27 30 38 48 54 76 96

Ceiling Ducted
(Low Static Pressure)

Ceiling Ducted
(High Static Pressure)

Low-Height
Ceiling Ducted

Slim Ceiling Ducted

4-Way Cassette

Compact 4-Way
Cassette

Ceiling & Floor

New Wall Mounted

Wall Mounted

Floor Concealed

(Only For G/M/R/C Series)

NOTES:
Hi-smart E has 3 types of indoor units for selection:
1.Low-height ceiling ducted type
2.Slim ceiling ducted type
3.Wall mounted type

111
Indoor Unit

Various Model Types Easily Match Different

Wide capacity range of outdoor units enables free model combination

Product line-up
according to the actual situation of building. There are 9 types of indoor
units for selection. Planner can choose appropriate type and capacity of
indoor units according to interior decoration and functions.

Flexible Ways of Air Supply and Air Return


Different duct types can be chosen to suit different construction structure and interior decoration, which meets various personalized
requirement of customers.

Ceiling Supply Ceiling Return Side Supply Ceiling Return Side Supply Side Return Side Supply Bottom Return

Precise Room Temperature Control


Hisense sets temperature sensors on air outlet /air inlet of indoor units and remote controller, and adopts microcomputer control 2000-pulse
high precision electronic expansion valve to adjust refrigerant flow rate, high precision electronic expansion valve to adjust refrigerant flow
rate, which can maintain the room temperature within 0.5℃ of setting temperature and satisfy the indoor comfort requirement.

Top Class Low Noise Design


In accordance with application situation and structure, Hisense has been studying the technical means and installation methods for noise
reduction of indoor units from various aspects of fan motor, fan blade and air duct layout, which provides customers with the quietest air
conditioned environment.

30dB(A) Noise Level Have


Whisper Operation No Impact on Sleep Quiet Library Street

20 dB(A) 21 dB(A) 30dB(A) 40dB(A) 70dB(A)

112
Indoor Unit

Ceiling Ducted Type


(Low Static Pressure)

Installation Space-saving Fresh Indoor Air


Product line-up

Less than 270mm in height can Minimum 5mm By introducing fresh outdoor air and being equipped with air
be easily fit into the limited 270mm
filter to keep indoor air clean.
space in the false ceiling
(7.5-24.2KBtu/h). 7.5-24.2KBtu/h False Ceiling
Excellent Air Flow Duct

Cooling and heating air distributed from


the unit to indoor space through ducts,
which creates a comfortable environ-
Flexibly Supports A Wide Indoor Unit

ment.
Range Of Installation
Duct
Air Filter,Air Grid
Optional Parts
Canvas Duct(Field-supplied)
Air Inlet (Field-supplied)
Drain-up mechanism can be supplied as optional part.

NOTE:
When bottom air inlet is adopted, sound pressure will increase according to factors Maximum 900mm

such as installation mode and the room structure.

Condensate Drain-up

Indoor Unit Ceiling Ducted type (Low Static Pressure)


AC1Ф, 220 AVD-07 AVD-09 AVD-12 AVD-14 AVD-17 AVD-18 AVD-22 AVD-24 AVD-27 AVD-30 AVD-38 AVD-48 AVD-54 AVD-76 AVD-96
Model ~240V/50Hz UXCSAL UXCSAL UXCSAL UXCSAL UXCSBL UXCSBL UXCSBL UXCSBL UXCSCL UXCSCL UXCSCL UXCSDL UXCSDL UX6SEL*1 UX6SFL*1
Power Supply AC1Ф, AVD-07 AVD-09 AVD-12 AVD-14 AVD-17 AVD-18 AVD-22 AVD-24 AVD-27 AVD-30 AVD-38 AVD-48 AVD-54 AVD-76 AVD-96
220V/60Hz UX2SAL UX2SAL UX2SAL UX2SAL UX2SBL UX2SBL UX2SBL UX2SBL UX2SCL UX2SCL UX2SCL UX2SDL UX2SDL UX7SEL*2 UX7SFL*2
KW 2.2 2.8 3.6 4.3 5.0 5.6 6.3 7.1 8.4 9.0 11.2 14.2 16.0 22.4 28.0
Nominal Cooling Kcal/h 1,900 2,400 3,100 3,700 4,300 4,800 5,400 6,100 7,200 7,700 9,600 12,200 13,800 19,300 24,100
Capacity
Btu/h 7,500 9,600 12,300 14,700 17,100 19,100 21,500 24,200 28,700 30,700 38,200 48,500 54,600 76,500 95,600
KW 2.8 3.3 4.2 4.9 5.6 6.5 7.5 8.5 9.6 10.0 13.0 16.3 18.0 25.0 31.5
Nominal Heating Kcal/h
Capacity 2,400 2,800 3,600 4,200 4,800 5,600 6,500 7,300 8,300 8,600 11,200 14,000 15,500 21,500 27,100
Btu/h 9,600 11,300 14,300 16,700 19,100 22,200 25,600 29,000 32,800 34,100 44,400 55,600 61,400 85,300 107,500
Noise Level dB(A) 30-26-24 30-26-24 32-30-28 32-30-28 33-31-29 33-31-29 34-32-30 34-32-30 38-34-30 38-34-30 39-35-31 41-38-33 43-39-34 50 52
(H/M/L)
H mm 270 270 270 270 270 270 270 270 350 350 350 350 350 470 470
Outer W mm
Dimensions 650+75 650+75 650+75 650+75 900+75 900+75 900+75 900+75 900+75 900+75 900+75 1300+75 1300+75 1060 1250
D mm 720 720 720 720 720 720 720 720 800 800 800 800 800 1120 1120
Net Weight Kg 25 25 25 25 34 34 34 34 44 44 44 56 56 94 106
Air Flow Rate m 3/h 480/420 480/420 780/660 780/660 900/780 900/780 960/840 960/840 1550/1350 1550/1350 1550/1350 2150/1800 2200/1900
(H/M/L) /360 /360 /540 /540 /660 /660 /720 /720 /1150 /1150 /1150 /1500 /1500 3480 4320
Motor Power W 110 110 150 150 150 150 150 190 300 300 300 430 430 950 1120
Piping Connections Flare-nut Connection(with Flare Nuts) Brazing
Liquid Line mm Ф6.35 Ф6.35 Ф6.35 Ф6.35 Ф6.35 Ф6.35 Ф9.53 Ф9.53 Ф9.53 Ф9.53 Ф9.53 Ф9.53 Ф9.53 Ф9.53 Ф9.53
Gas Line mm Ф12.7 Ф12.7 Ф12.7 Ф12.7 Ф15.88 Ф15.88 Ф15.88 Ф15.88 Ф15.88 Ф15.88 Ф15.88 Ф15.88 Ф15.88 Ф19.05 Ф22.2
Condensate Drain VP25(Outer Diameter Ф32 )
External Static Pa 30 30 30 30 30 30 30 30 60 60 60 60 60 100 100
Pressure
Packing Volume m3 0.21 0.21 0.21 0.21 0.27 0.27 0.27 0.27 0.38 0.38 0.38 0.52 0.52 0.90 1.06

NOTES:
1.The nominal cooling capacity and heating capacity are based on following 2. The sound pressure level is based on following conditions: 1.5m beneath the unit.
conditions: With discharge duct (2.0m) and return duct(1.0m)
Cooling Operation Conditions The above data was measured in an anechoic chamber so that reflected sound
Indoor Air Inlet Temperature: 27℃ DB(80°F DB), 19.0℃WB(66.2°F WB) should be taken into consideration in the field.
Outdoor Air Inlet Temperature: 35℃ DB(95°F DB) When bottom air inlet is adopted, sound pressure will increase according to factors
3.
Piping Length: 7.5 Meters Piping Lift: 0 Meter such as installation mode and the room structure.
Heating Operation Conditions *1: AC3Φ, 380V/50Hz, *2: AC3Φ, 380V/60Hz
Indoor Air Inlet Temperature: 20℃ DB(68°F DB)
Outdoor Air Inlet Temperature: 7℃DB(45°F DB), 6℃WB(43°F WB)

113
Indoor Unit

Ceiling Ducted Type


(High Static Pressure)

Installation Space-saving Fresh Indoor Air

Product line-up
Less than 270mm in height can Minimum 5mm By introducing fresh outdoor air and being equipped with air
be easily fit into the limited 270mm
filter to keep indoor air clean.
space in the false ceiling
(7.5-24.2KBtu/h). 7.5-24.2KBtu/h False Ceiling
Excellent Air Flow Duct

Cooling and heating air distributed from


the unit to indoor space through ducts,
which creates a comfortable environ-
Flexibly Supports a Wide Indoor Unit

ment.
Range of Installation
Duct
Air Filter,Air Grid
Optional Parts
Canvas Duct(Field-supplied)
Air Inlet (Field-supplied)
Drain-up mechanism can be supplied as optional part.

NOTE:
When bottom air inlet is adopted, sound pressure will increase according to factors Maximum 900mm

such as installation mode and the room structure.

Condensate Drain-up

Indoor Unit Ceiling Ducted type (Low Static Pressure)


AC1Ф, 220 AVD-07 AVD-09 AVD-12 AVD-14 AVD-17 AVD-18 AVD-22 AVD-24 AVD-27 AVD-30 AVD-38 AVD-48 AVD-54 AVD-76 AVD-96
Model ~240V/50Hz UXCSAH UXCSAH UXCSAH UXCSAH UXCSBH UXCSBH UXCSBH UXCSBH UXCSCH UXCSCH UXCSCH UXCSDH UXCSDH UX6SEH*1 UX6SFH*1
Power Supply AC1Ф, AVD-07 AVD-09 AVD-12 AVD-14 AVD-17 AVD-18 AVD-22 AVD-24 AVD-27 AVD-30 AVD-38 AVD-48 AVD-54 AVD-76 AVD-96
220V/60Hz UX2SAH UX2SAH UX2SAH UX2SAH UX2SBH UX2SBH UX2SBH UX2SBH UX2SCH UX2SCH UX2SCH UX2SDH UX2SDH UX2SFH UX2SFH
KW 2.2 2.8 3.6 4.3 5.0 5.6 6.3 7.1 8.4 9.0 11.2 14.2 16.0 22.4 28.0
Nominal Cooling Kcal/h 1,900 2,400 3,100 3,700 4,300 4,800 5,400 6,100 7,200 7,700 9,600 12,200 13,800 19,300 24,100
Capacity
Btu/h 7,500 9,600 12,300 14,700 17,100 19,100 21,500 24,200 28,700 30,700 38,200 48,500 54,600 76,500 95,600
KW 2.8 3.3 4.2 4.9 5.6 6.5 7.5 8.5 9.6 10.0 13.0 16.3 18.0 25.0 31.5
Nominal Heating Kcal/h 2,800 3,600 4,200 4,800 5,600 6,500 7,300 8,300 8,600 11,200 14,000 15,500 21,500 27,100
Capacity 2,400
Btu/h 9,600 11,300 14,300 16,700 19,100 22,200 25,600 29,000 32,800 34,100 44,400 55,600 61,400 85,300 107,500
Noise Level dB(A) 33-31-29 33-31-29 33-31-29 33-31-29 34-32-30 34-32-30 36-34-32 36-34-32 41-39-34 41-39-34 43-40-36 44-41-36 43-40-37 52 54
(H/M/L)
H mm 270 270 270 270 270 270 270 270 350 350 350 350 350 470 470
Outer 1060 1250
Dimensions W mm 650+75 650+75 650+75 650+75 900+75 900+75 900+75 900+75 900+75 900+75 900+75 1300+75 1300+75
D mm 720 720 720 720 720 720 720 720 800 800 800 800 800 1120 1120
Net Weight Kg 25 25 25 25 34 34 34 34 44 44 44 56 56 94 106
Air Flow Rate m3/h 480/420 480/420 780/660 780/660 900/780 900/780 960/840 960/840 1600/1400 1600/1400 1600/1400 2100/1750 2150/1800 3480 4650
(H/M/L) /360 /360 /540 /540 /660 /660 /720 /720 /1150 /1150 /1150 /1450 /1550
Motor Power W 110 110 150 150 150 150 150 190 300 300 300 430 430 1030 1280
Piping Connections Flare-nut Connection(with Flare Nuts) Brazing
Liquid Line mm Ф6.35 Ф6.35 Ф6.35 Ф6.35 Ф6.35 Ф6.35 Ф9.53 Ф9.53 Ф9.53 Ф9.53 Ф9.53 Ф9.53 Ф9.53 Ф9.53 Ф9.53
Gas Line mm Ф12.7 Ф12.7 Ф12.7 Ф12.7 Ф15.88 Ф15.88 Ф15.88 Ф15.88 Ф15.88 Ф15.88 Ф15.88 Ф15.88 Ф15.88 Ф19.05 Ф22.2
Condensate Drain VP25(Outer Diameter Ф32 )
External Static Pa 50(80) 50(80) 50(80) 50(80) 50(80) 50(80) 50(80) 50(80) 120(90) 120(90) 120(90) 120(90) 120(90) 220 220
Pressure
Packing Volume m3 0.21 0.21 0.21 0.21 0.27 0.27 0.27 0.27 0.38 0.38 0.38 0.52 0.52 0.90 1.06

NOTES:
1.The nominal cooling capacity and heating capacity are based on following 2. The sound pressure level is based on following conditions: 1.5m beneath the unit.
conditions: With discharge duct (2.0m) and return duct(1.0m)
Cooling Operation Conditions The above data was measured in an anechoic chamber so that reflected sound
Indoor Air Inlet Temperature: 27℃ DB(80°F DB), 19.0℃WB(66.2°F WB) should be taken into consideration in the field.
Outdoor Air Inlet Temperature: 35℃ DB(95°F DB) 3. When bottom air inlet is adopted, sound pressure will increase according to factors
Piping Length: 7.5 Meters Piping Lift: 0 Meter such as installation mode and the room structure.
Heating Operation Conditions *1: AC3Φ, 380V/50Hz,
Indoor Air Inlet Temperature: 20℃ DB(68°F DB) *2: AC3Φ, 380V/60Hz: AVD- 76UX7SEH; AVD-96UX7SFH
Outdoor Air Inlet Temperature: 7℃DB(45°F DB), 6℃WB(43°F WB)

114
Indoor Unit

Ceiling Ducted Type(L/H)

Models: AVD- 07~54* Model Unit: mm


Unit:mm
Product line-up

l - φ6
b (Around the Flange) Air Inlet
40 a
e c x 300 = d
300 4 - 40 x 12
20

(for Suspension Bolt)


30
22

x
g
33.5

22
m
n

Wired controller
22

Viewed from A
30

120
20

300 l - φ6
e (Around the Flange) Drain Pipe Connection Drain Pipe Connection
c x 300 = d
(Standard Position) (VP25) (Optional Drain-Up Mechanism)

Refrigerant Gas Pipe Connection


(With iji Flare Nut)

Air Outlet Refrigerant Liquid Pipe Connection

2xv=w
(With ijh Flare Nut) u 45
a 75(Electrical Control Box)
2x90=180
220

A
90

v
r
q
p

97

23

35
s
t

246(Refrigerant Liquid Pipe Connection)


f 321(Refrigerant Gas Pipe Connection)
48.5 j (Refrigerant Gas Pipe Connection)
377
90(Drain Pipe Connection)
402
k (Refrigerant Liquid Pipe Connection)

Dimension
Model a b c d e f g h i j k l
07~14 650 730 1 300 215 553 583 6.35 12.7 70 92 10
17/18 900 980 2 600 190 803 833 6.35 15.88 77 92 12
22/24 900 980 2 600 190 803 833 9.53 15.88 77 95 12
27/30 900 980 2 600 190 803 833 9.53 15.88 78 95 12
38 900 980 2 600 190 803 833 9.53 15.88 81 95 12
48/54 1300 1380 3 900 240 1203 1233 9.53 15.88 81 95 14

Dimension
Model m n p q r s t u v w x
07~24 676 720 23 270 182 222 43 220 100 200 226
27~54 756 800 103 350 204 244 123 300 140 280 306

115
Indoor Unit

Product line-up
Models: AVD-76/96* Model Unit:mm

(Around the Flange)

Viewed from A
(for Suspension Bolt)

916

Air Outlet

(Around the Flange)


Air Inlet
Refrigerant Liquid Pipe
9.53 Brazing
Drain Piping Refrigerant Gas Pipe
22.2(19.05)Brazing
Air Inlet

NOTES: Data in the bracket is for AVD-76* model

116
Indoor Unit

Low-height
Ceiling Ducted Type (Height 192mm)

Installation Space-saving Excellent Air Flow Duct

With height of 192mm Cooling and heating air distributed


Product line-up

Minimum 5mm
may be easily installed from the unit to indoor space through
inside narrow residential 192mm ducts, which creates a comfortable
ceiling. environment.
False Ceiling

Satisfy Varied Requests on Installation


Available air inlet as rear or Indoor Unit

bottom entry, consumers can


Adjustable Indoor Unit Static Pressure
choose relevant air inlet mode Duct
Indoor unit can adjust static pressure automatically according Canvas Duct(Field-supplied) Air Filter,Air Grid
according to the practical Air Inlet (Field-supplied)
to the house structure and installation condition, ensure that
installation space. (Installation Diagram of Air Bottom Inlet)
the indoor unit operates in the optimum exhaust state.

Duct Duct
Drain-up Mechanism as Standard part
Drain-up length achieves
Elastic Hose Drain-up Length 900mm
900mm which enables
convenient drain piping and
When the required duct is short, When the required duct is long,
the static pressure can be set lower. the static pressure can be set higher; enlarges the flexibility of
installation.

Indoor Unit Ceiling Ducted type (Low Static Pressure)


AC1Ф, 220 AVE-07UXCSAL AVE-09UXCSAL AVE-12UXCSAL
Model ~ 240V/50Hz
AVE-14UXCSAL AVE-17UXCSBL AVE-18UXCSBL AVE-22UXCSBL AVE-24UXCSBL
Power Supply AC1Ф, AVE-07UX2SAL AVE-09UX2SAL
220V/60Hz
AVE-12UX2SAL AVE-14UX2SAL AVE-17UX2SBL AVE-18UX2SBL AVE-22UX2SBL AVE-24UX2SBL
KW 2.2 2.8 3.6 4.3 5.0 5.6 6.3 7.1
Nominal Cooling Kcal/h 1,900 2,400 3,100
Capacity 3,700 4,300 4,800 5,400 6,100
Btu/h 7,500 9,600 12,300 14,700 17,100 19,100 21,500 24,200
KW 2.8 3.3 4.2 4.9 5.8 6.5 7.5 8.5
Nominal Heating Kcal/h 2,400 2,800 3,600
Capacity 4,200 5,000 5,600 6,500 7,300
Btu/h 9,600 11,300 14,300 16,700 19,800 22,200 25,600 29,000
Noise Level dB(A) 27-24-21 27-24-21 32-30-27
(H/M/L) 32-30-27 34-30-28 34-30-28 36-32-29 36-32-29
H mm 192 192 192 192 192 192 192 192
Outer 900 900 900
Dimensions W mm 900 1170 1170 1170 1170
D mm 447 447 447 447 447 447 447 447
Net Weight Kg 20 20 21 21 26 26 26 26
Air Flow Rate m3/h 500/440/350 500/440/350 640/590/520
(H/M/L) 640/590/520 870/750/630 870/750/630 950/820/710 950/820/710
Motor Power W 50 50 70 70 100 100 110 110
Piping Connections Flare-nut Connection(with Flare Nuts)
Liquid Line mm Ф6.35 Ф6.35 Ф6.35 Ф6.35 Ф6.35 Ф6.35 Ф9.53 Ф9.53
Gas Line mm Ф12.7 Ф12.7 Ф12.7 Ф12.7 Ф15.88 Ф15.88 Ф15.88 Ф15.88
Condensate Drain VP25(Outer Diameter Ф32 )
External Static Pa 10(30) 10(30) 10(30)
Pressure 10(30) 10(30) 10(30) 10(30) 10(30)
Packing Volume m3 0.15 0.15 0.15 0.15 0.18 0.18 0.18 0.18

NOTES:
1.The nominal cooling capacity and heating capacity are based on following conditions: 2. The sound pressure level is based on following conditions: 1.5m beneath the unit. With discharge duct
Cooling Operation Conditions (2.0m) and return duct(1.0m)
Indoor Air Inlet Temperature: 27℃ DB(80°F DB), 19.0℃WB(66.2°F WB) The above data was measured in an anechoic chamber so that reflected sound should be taken into
Outdoor Air Inlet Temperature: 35℃ DB(95°F DB) consideration in the field.
Piping Length: 7.5 Meters Piping Lift: 0 Meter When bottom air inlet is adopted, sound pressure will increase according to factors such as installation
Heating Operation Conditions mode and the room structure.
Indoor Air Inlet Temperature: 20℃ DB(68°F DB)
Outdoor Air Inlet Temperature: 7℃DB(45°F DB), 6℃WB(43°F WB)

117
Indoor Unit

Models: AVE-07~14*AL Model Unit:mm

54 630

759

Product line-up
Refrigerant Refrigerant Drain Pipe
Gas Pipe Liquid Pipe Connection
Electrical
Control Box φ12.7 φ 6.35 (Drain-up
477
456
421

Mechanism)
447
Air Inlet

20

9
Air Outlet

29 47
109
80

171
192

80
900
938

87
1018
1053
72 8

44 30 6

Models: AVE-17~24*BL Model Unit:mm

1029
477
456
421

1170
1208
1288
1323

54 940
192

Refrigerant Refrigerant Drain Pipe


Gas Pipe Liquid Pipe Connection
Electrical a (Drain-up
b
Control Box Mechanism)
447
Air Inlet
20

Air Outlet
29 47

Dimension a b
Model
109
80

φ 15.88 φ 6.35
171
192

80

17/18
22/24 φ 15.88 φ 9.53
87

72 8

44 30 6

118
Indoor Unit

Slim Ceiling Ducted Type


(Width 700mm, Height 192 mm)
Installation Space-saving Excellent Air Flow
Duct
With a width of 700mm Cooling and heating air distributed from the
Product line-up

Minimum 5mm
and height of 192mm unit to indoor space through ducts, which
192mm

may be easily installed creates a comfortable environment.


700mm
inside narrow
residential ceiling. False Ceiling
Satisfy Varied Requests on Installation
Available air inlet as rear or bottom Indoor Unit

Adjustable Indoor Unit Static Pressure entry, consumers can choose


Duct
Indoor unit can adjust static pressure automatically according relevant air inlet mode according to Canvas Duct(Field-supplied) Air Filter,Air Grid
Air Inlet (Field-supplied)

to the house structure and installation condition, ensure that the practical installation space. (Installation Diagram of Air Bottom Inlet)

the indoor unit operates in the optimum exhaust state.

Duct Duct Drain-up Mechanism as Standard Part


Drain-up length achieves 900mm
Elastic Hose
which enables convenient drain Drain-up Length 900mm

piping and enlarges the flexibility


When the required duct is short, When the required duct is long,
the static pressure can be set lower. the static pressure can be set higher; of installation.

Indoor Unit Slim Ceiling Ducted Type


AC1Ф, 220 AVE-07UXCSGL AVE-09UXCSGL AVE-12UXCSGL AVE-14UXCSGL
Model ~ 240V/50Hz
Power Supply AC1Ф,
220V/60Hz AVE-07UX2SGL AVE-09UX2SGL AVE-12UX2SGL AVE-14UX2SGL
KW 2.2 2.8 3.6 4.3
Nominal Cooling Kcal/h 1,900 2,400 3,100 3,700
Capacity
Btu/h 7,500 9,600 12,300 14,700
KW 2.8 3.3 4.2 4.9
Nominal Heating Kcal/h 2,400 2,800 3,600
Capacity 4,200
Btu/h 9,600 11,300 14,300 16,700
Noise Level dB(A) 27-23-21 27-23-21 31-29-27 31-29-27
(H/M/L)
H mm 192 192 192 192
Outer mm
Dimensions W 700 700 700 700
D mm 602 602 602 602
Net Weight Kg 21 21 21 21
Air Flow Rate m3/h 450/380/335 450/380/335
(H/M/L) 590/510/470 590/510/470
Motor Power W 50 50 60 60
Piping Connections Flare-nut Connection(with Flare Nuts)
Liquid Line mm Ф6.35 Ф6.35 Ф6.35 Ф6.35
Gas Line mm Ф12.7 Ф12.7 Ф12.7 Ф12.7
Condensate Drain VP25(Outer Diameter Ф32 )
External Static Pa 10(30) 10(30) 10(30) 10(30)
Pressure
Packing Volume m3 0.15 0.15 0.15 0.15

NOTES:
1.The nominal cooling capacity and heating capacity are based on following conditions: 2. The sound pressure level is based on following conditions: 1.5m beneath the unit. With discharge duct
Cooling Operation Conditions (2.0m) and return duct(1.0m)
Indoor Air Inlet Temperature: 27℃ DB(80°F DB), 19.0℃WB(66.2°F WB) The above data was measured in an anechoic chamber so that reflected sound should be taken into
Outdoor Air Inlet Temperature: 35℃ DB(95°F DB) consideration in the field.
Piping Length: 7.5 Meters Piping Lift: 0 Meter When bottom air inlet is adopted, sound pressure will increase according to factors such as installation
Heating Operation Conditions mode and the room structure.
Indoor Air Inlet Temperature: 20℃ DB(68°F DB)
Outdoor Air Inlet Temperature: 7℃DB(45°F DB), 6℃WB(43°F WB)

119
Indoor Unit

Models: AVE-07~14*GL Model

Product line-up
Unit:mm

Liquid Pipe Gas Pipe Water Outlet Electrical Box Return Air Inlet
(Pump)

Air Outlet

120
Hi-FLEXi C Series

Technology to Improve Heat Exchanger Performance


In the Hi-FLEXi C series model, wind speed distribution is rendered uniform by making the direction of the wind flow same to the
fan and the heat exchanger. As a result, the performance of the heat exchanger is optimized and energy is saved.
Product line-up

Ventilation Resistance Reduction Effect


Current Modle Hi-FLEXi C Series
(Top-flow Type)

Air Outlet
Hi-FLEXI C series
Heat Exchanger
Heat Exchanger

Top-flow Type Hi-FLEXi C Series

Ventilation Resistance Reduction Effect


Air Inlet
Air Inlet

Air Velocity(m/s) Air Velocity(m/s) Hi-FLEXI C series

Top-flow Type Hi-FLEXi C Series

Low Noise Technologies

DC Fan Motor
The smooth rotating fan motor with low
vibration reduces the noise level. Super High-stream Fan DC Fan Motors

Super High-stream Fan


Supper high-stream fan of Φ544mm
New Fin with
cuts down the noise level.
Less Pressure Loss

Low Pressure Loss Air Outlet Grille


The rib structure synchronized with
rotation flow from the fan reduces the
air resistance at the air outlet grille.

New Fin with Less Pressure Loss Less Pressure Loss


The rib structure synchronized with Air Outlet Grille

rotation flow from the fan reduces the air


resistance at the air outlet grille.

97
Hi-FLEXi C Series

Features
Provide in a compact body, but allows installation conditions comparable with those of a high-performance multi-split air condition-
ing system.
The compact and light body facilitates delivery and installation.

Product line-up
The adoption of a slim body improves flexibility in mounting, enabling installation in a small space or a formerly dead space.

Top-class Compact and Light Weight Design


Facilitation and flexibility at installation are further advanced by adopting outdoor units light weight and compact design
compared to the current top-flow model.

Top-flow Type Hi-FLEXi C Series

Slim and Refined Body Design


The compact outdoor unit can be flexibly placed according to outdoor condition. Low-height in-the-ceiling type can be easily
installed inside the low-height residential ceiling with a height of 192mm, which makes low height indoor units and elegant home
decoration style set off mutually.

98
Hi-FLEXi C Series

Various Model Types Easily Match Different Layout


Wide capacity range of outdoor units enables free model combination according to the actual situation of building. There are 9
types of indoor units for selection. Designer can choose the appropriate type and capacity range of indoor units according to the
Product line-up

interior decoration and furnitures.

Greater Convenience During Delivery and Installation

With its light and compact body, the Hi-FLEXi C Series can be
easily carried in the elevator even in a small urban site.
Light and compact body
No cranes required for delivery facilitates renewal

The unit can be carried at one time.


Elevators can be used for delivery.

99
Hi-FLEXi C Series

Long Piping Design

The piping can be designed and constructed up to a total Piping length 100m (total piping length of 250m)

Product line-up
Piping length: 100 m(Equivalent length :125m)

Max .length after first branch : 40m

Max.length after branch : 15m

Height difference between indoor units : 15m

Max. height difference between ODU and IDU Outdoor unit is higher: 50m Indoor unit is higher : 40m

Total piping length: 250m

4 5
3
1

100
Hi-FLEXi C Series

Outdoor Unit Specifications


Product line-up

Hi-FLEXi C HP 8HP 10HP 12HP


AC3Φ380~415V/50Hz AVW-76UESR AVW-96UESR AVW-114UESR
Model Power Supply
AC3Φ380V/60Hz AVW-76U7SR AVW-96U7SR AVW-114U7SR
KW 22.4 28.0 33.5
Nominal Capacity
KBtu/h 76.5 95.6 114.3
Cooling Operation
Consumption Power KW 6.3 8.3 10.7
EER 3.6 3.4 3.1
KW 25.0 31.5 37.5
Nominal Capacity
KBtu/h 85.3 107.5 128.0
Heating
Consumption Power KW 5.9 7.8 9.9
COP 4.2 4.0 3.8
Air Flow Rate m³/h 7,260 9,000 9,780
Outer Dimension mm 1,650×1,100×390
Packing Dimension mm 1,748×1,151×500
Net Weight Kg 168 168 171
Gross Weight Kg 179 179 182
Gas Line mm Ф19.05 Ф22.2 Ф25.4
Refrigerant piping
Liquid Line mm Ф9.53 Ф12.7 Ф12.7
Max. number of connectable IDU 10 10 10
Max. Piping Length m 100 100 100
Between ODU & IDU m 50(40) 50(40) 50(40)
Height Difference
Between IDUs m 15 15 15
Noise Level dB(A) 53/55 56/58 56/61
Cooling ℃ DB -5~43 -5~43 -5~43
Operation Range
Heating ℃ WB -20~15 -20~15 -20~15

101
Hi-FLEXi C Series

Product line-up
AVW-76UE(7)SR

AVW-96UE(7)SR

AVW-114UE(7)SR

AVW-76UE(7)SR

102
Hi-Smart L Series

High User Experience

Free Combination
One outdoor unit of Hi-Smart L series can connect maximum 7 indoor units in different types. The free combination not only
Product line-up

meets the air condition needs of large space, but also helps match the indoor decoration. Flexible choice and better system
configuration start a tour of Luxury life.

Refrigerant Pipe
Drain Pipe

Slim and Refined Body Design


The compact outdoor unit can be flexibly placed according to outdoor condition. Low-height in-the-ceiling type can be easily
installed inside the low-height residential ceiling with a height of 192mm, which makes low height indoor units and elegant home
decoration style set off mutually.

103
Hi-Smart L Series

Long Piping Design


Long refrigerant piping design makes project design and installation works more convenient.

Max. height difference between the highest and the lowest indoor units is 10m.

Product line-up
Max. height difference between outdoor and indoor units is 30m.
Max. piping length is 75m.
Total piping length can be 120m.

Max. 75m

30m

10m

1104
10
04
Hi-Smart L Series

Outdoor Unit Specifications


Product line-up

Hi-Smart L series HP 4 5 6
AC1Φ, 220 ~240V/50Hz AVW-38UCSC AVW-48UCSC AVW-54UCSC
AC1Φ, 220V/60Hz AVW-38U2SC AVW-48U2SC AVW-54U2SC
Model Power Supply
AC3Φ, 380 ~415V/50Hz --- AVW-48UESC AVW-54UESC
AC3Φ, 380V/60Hz --- AVW-48U7SC AVW-54U7SC
Kw 11.2 14.0 15.5
Nominal Capacity
KBtu/h 38.2 47.8 52.9
Cooling Operation
Power Consumption KW 2.99 3.92 4.44
EER 3.75 3.57 3.49
KW 12.5 16.0 18.0
Nominal Capacity
KBtu/h 42.7 54.6 61.4
Heating Opeartion
Power Consumption KW 2.98 4.03 4.74
COP 4.19 3.97 3.80
Air Flow Rate m³/h 5,400 5,400 6,000
Outer Dimension mm 1,380×950×370
Packing Dimension mm 1,040×460×1,500
Net Weight Kg 93 95 97
Gross Weight Kg 106 108 110
Liquid Line mm Φ9.53 Φ9.53 Φ9.53
Refrigerant Piping
Gas Line mm Φ15.88 Φ15.88 Φ15.88
Max. number of connectable IDU 6 7 7
Noise Level Cooling/Heating dB(A) 52/54 52/55 54/56
Cooling Operation ℃ DB -5~46℃DB
Operation Range
Heating Operation ℃ WB -20~15.5℃WB
Branch Pipe HFQ-052F

NOTES:
2. The sound pressure lever is based on following
1.The nominal cooling capacity and heating capacity are based on following conditions:
Cooling Operation Conditions conditions.1.5m beneath the unit.
Indoor Air Inlet Temperature: 27℃ DB(80ºF DB) Heating Operation Conditions The above date was measured in an anechoic
19.0℃ WB(66.2ºF WB) Indoor Air Inlet Temperature: 20℃ DB(68ºF DB) chamber so that reflected sound should be taken
Outdoor Air Inlet Temperature: 35℃ DB(95ºF DB) Outdoor Air Inlet Temperature: 7℃ DB(45ºF DB) into consideration in the field.
Piping Length: 7.5Meters Piping Lift: 0 Meter 6℃ WB(43ºF WB)

105
Hi-Smart L Series

Outdoor Unit Dimensional Data AVW-38~54UC(2)SC Unit: mm

Service Space Product line-up

NOTES:
1.Stop valve is installed in the hood.
2.The interval dimension between fixed bolts for installation is 600×410.

106
Hi-Smart E Series

Leading Low Carbon New Life


The Earth is the home of ours!Pay close attention to the climate change together with Hisense, choose R410A environmentally friendly
refrigerant and focus on low carbon lifestyle. Low carbon lifestyle is a kind of love, a kind of attitude and even a kind of responsibility.
Earth protection and living environment protection start from the choice of Hisense.
Product line-up

Five Core Technologies

1
Intelligent and
5
Intelligent Defrosting
High Efficient Technology

2 4
DC Inverter-driven
Technology 3
Low Noise and
3D Temperature
Control Technology

Low Frequency Operation

Unique Designs Create Refined Life


Intelligent Multi-split Design
Hi-Smart E outdoor unit adopts the leading single-piping connection
technology and connects multiple indoor units freely. The indoor unit
adopts 2000-step micro-computer EEV (electronic expansion valve)
to achieve automatic refrigerant flow control according to indoor
load, which results in more precise and comfortable temperature
control.
Refrigerant Pipe

Drain Pipe

107
Hi-Smart E Series

Slim and Refined Body Design


The compact outdoor unit can be flexibly placed according to outdoor condition. Low-height in-the-ceiling type can be easily
installed inside the low-height residential ceiling with a height of 192mm, which makes low height indoor units and elegant home
decoration style set off mutually.

Product line-up
192mm

Flexible Long Piping Design Max. 25m

Max. piping length is 40m. Max. height difference


between outdoor and indoor units is 20m. Height
difference between highest and lowest indoor units is
3.5m. Design and installation are more convenient. 20m

NOTES: 2.0m
Hi-Smart E Series has 3 types of indoor units for selection:
Low-height ceiling ducted type
Slim ceiling ducted type
Wall mounted type

108
Hi-Smart E Series

Outdoor Unit Specifications


Product line-up

Hi-Smart E series HP 3 4 5
AC1Φ, 220 ~240V/50Hz AVW-28UCSB AVW-34UCSB AVW-43UCSB

Model Power Supply AC1Φ, 220V/60Hz AVW-28U2SB AVW-34U2SB AVW-43U2SB


AC3Φ, 380~415V/50Hz --- --- AVW-43UESB
AC3Φ, 380V/60Hz --- --- AVW-43U7SB
KW 8.0 10.0 12.5
Nominal Capacity
KBtu/h 27,300 34,100 42,700
Cooling Operation
Power Consumption KW 2.66 2.86 3.81
EER 3.01 3.50 3.28
KW 9.5 11.2 14.0
Nominal Capacity
KBtu/h 32,400 38,200 47,800
Heating Opeartion
Power Consumption KW 2.42 2.75 3.68
COP 3.93 4.07 3.80
Air Flow Rate m³/h 2,970 4,140 4, 680
Outer Dimension mm 800×950×370
Packing Dimension mm 1,020×460×940
Net Weight Kg 65 73 78
Gross Weight Kg 75 83 88
Liquid Line mm Φ9.53 Φ9.53 Φ9.53
Refrigerant Piping
Gas Line mm Φ15.88 Φ15.88 Φ15.88
Max. number of connectable IDU 3 4 4
Noise Level Cooling/Heating dB(A) 50/52 53/54 54/57
Cooling Operation ℃ DB 10~43℃DB
Operation Range
Heating Operation ℃ WB -15~15℃WB
Branch Pipe HFQ-052F

NOTES:
1.The nominal cooling and heating capacities show the capacities when the outdoor with the 100% rating of indoor unit.
Cooling Operation Conditions
Indoor Air Inlet Temperature:27℃DB/19℃WB
Outdoor Air Inlet Temperature:35℃DB
Piping Length:7.5Meters Piping Lift:0 Meter
2.The sound pressure level is based on following conditions:
1.5 Meters from floor Level,and 1Meter from the unit service cover surface.
The above data was measured in an anechoic chamber so that reflected sounde shoudle be taken into consideration in the field.

109
Hi-Smart E Series

Outdoor Unit Dimensional Data

AVW-28~43UC(2)SB Unit: mm

Product line-up
Piping and Wiring Hole

Ground

Gas Pipe Connection

Air Outlet

Piping and Wiring Hole


Piping and Wiring Hole

Note:
1. The unit is equipped with stop valve; field refrigerant pipes are connected to stop valve through flare opening.
2. Illustrated 110 dimension marked with ** is to avoid possible conflict with the foundation, etc. in piping from the bottom.
3. Dimension marked with * is the location dimension of anchor holes.

Service Space

110
Indoor Unit

Hisense Hi-Flexi & Hi-Smart series provide a wide selection of indoor units for indoor decoration and create a
personalized living space.
Product line-up

HP 0.8 1.0 1.3 1.5 1.8 2.0 2.3 2.5 3.0 3.3 4.0 5.0 6.0 8 10
kBtu/h 7 9 12 14 17 18 22 24 27 30 38 48 54 76 96

Ceiling Ducted
(Low Static Pressure)

Ceiling Ducted
(High Static Pressure)

Low-Height
Ceiling Ducted

Slim Ceiling Ducted

4-Way Cassette

Compact 4-Way
Cassette

Ceiling & Floor

New Wall Mounted

Wall Mounted

Floor Concealed

(Only For G/M/R/C Series)

NOTES:
Hi-smart E has 3 types of indoor units for selection:
1.Low-height ceiling ducted type
2.Slim ceiling ducted type
3.Wall mounted type

111
Indoor Unit

Various Model Types Easily Match Different

Wide capacity range of outdoor units enables free model combination

Product line-up
according to the actual situation of building. There are 9 types of indoor
units for selection. Planner can choose appropriate type and capacity of
indoor units according to interior decoration and functions.

Flexible Ways of Air Supply and Air Return


Different duct types can be chosen to suit different construction structure and interior decoration, which meets various personalized
requirement of customers.

Ceiling Supply Ceiling Return Side Supply Ceiling Return Side Supply Side Return Side Supply Bottom Return

Precise Room Temperature Control


Hisense sets temperature sensors on air outlet /air inlet of indoor units and remote controller, and adopts microcomputer control 2000-pulse
high precision electronic expansion valve to adjust refrigerant flow rate, high precision electronic expansion valve to adjust refrigerant flow
rate, which can maintain the room temperature within 0.5℃ of setting temperature and satisfy the indoor comfort requirement.

Top Class Low Noise Design


In accordance with application situation and structure, Hisense has been studying the technical means and installation methods for noise
reduction of indoor units from various aspects of fan motor, fan blade and air duct layout, which provides customers with the quietest air
conditioned environment.

30dB(A) Noise Level Have


Whisper Operation No Impact on Sleep Quiet Library Street

20 dB(A) 21 dB(A) 30dB(A) 40dB(A) 70dB(A)

112
Indoor Unit

Ceiling Ducted Type


(Low Static Pressure)

Installation Space-saving Fresh Indoor Air


Product line-up

Less than 270mm in height can Minimum 5mm By introducing fresh outdoor air and being equipped with air
be easily fit into the limited 270mm
filter to keep indoor air clean.
space in the false ceiling
(7.5-24.2KBtu/h). 7.5-24.2KBtu/h False Ceiling
Excellent Air Flow Duct

Cooling and heating air distributed from


the unit to indoor space through ducts,
which creates a comfortable environ-
Flexibly Supports A Wide Indoor Unit

ment.
Range Of Installation
Duct
Air Filter,Air Grid
Optional Parts
Canvas Duct(Field-supplied)
Air Inlet (Field-supplied)
Drain-up mechanism can be supplied as optional part.

NOTE:
When bottom air inlet is adopted, sound pressure will increase according to factors Maximum 900mm

such as installation mode and the room structure.

Condensate Drain-up

Indoor Unit Ceiling Ducted type (Low Static Pressure)


AC1Ф, 220 AVD-07 AVD-09 AVD-12 AVD-14 AVD-17 AVD-18 AVD-22 AVD-24 AVD-27 AVD-30 AVD-38 AVD-48 AVD-54 AVD-76 AVD-96
Model ~240V/50Hz UXCSAL UXCSAL UXCSAL UXCSAL UXCSBL UXCSBL UXCSBL UXCSBL UXCSCL UXCSCL UXCSCL UXCSDL UXCSDL UX6SEL*1 UX6SFL*1
Power Supply AC1Ф, AVD-07 AVD-09 AVD-12 AVD-14 AVD-17 AVD-18 AVD-22 AVD-24 AVD-27 AVD-30 AVD-38 AVD-48 AVD-54 AVD-76 AVD-96
220V/60Hz UX2SAL UX2SAL UX2SAL UX2SAL UX2SBL UX2SBL UX2SBL UX2SBL UX2SCL UX2SCL UX2SCL UX2SDL UX2SDL UX7SEL*2 UX7SFL*2
KW 2.2 2.8 3.6 4.3 5.0 5.6 6.3 7.1 8.4 9.0 11.2 14.2 16.0 22.4 28.0
Nominal Cooling Kcal/h 1,900 2,400 3,100 3,700 4,300 4,800 5,400 6,100 7,200 7,700 9,600 12,200 13,800 19,300 24,100
Capacity
Btu/h 7,500 9,600 12,300 14,700 17,100 19,100 21,500 24,200 28,700 30,700 38,200 48,500 54,600 76,500 95,600
KW 2.8 3.3 4.2 4.9 5.6 6.5 7.5 8.5 9.6 10.0 13.0 16.3 18.0 25.0 31.5
Nominal Heating Kcal/h
Capacity 2,400 2,800 3,600 4,200 4,800 5,600 6,500 7,300 8,300 8,600 11,200 14,000 15,500 21,500 27,100
Btu/h 9,600 11,300 14,300 16,700 19,100 22,200 25,600 29,000 32,800 34,100 44,400 55,600 61,400 85,300 107,500
Noise Level dB(A) 30-26-24 30-26-24 32-30-28 32-30-28 33-31-29 33-31-29 34-32-30 34-32-30 38-34-30 38-34-30 39-35-31 41-38-33 43-39-34 50 52
(H/M/L)
H mm 270 270 270 270 270 270 270 270 350 350 350 350 350 470 470
Outer W mm
Dimensions 650+75 650+75 650+75 650+75 900+75 900+75 900+75 900+75 900+75 900+75 900+75 1300+75 1300+75 1060 1250
D mm 720 720 720 720 720 720 720 720 800 800 800 800 800 1120 1120
Net Weight Kg 25 25 25 25 34 34 34 34 44 44 44 56 56 94 106
Air Flow Rate m 3/h 480/420 480/420 780/660 780/660 900/780 900/780 960/840 960/840 1550/1350 1550/1350 1550/1350 2150/1800 2200/1900
(H/M/L) /360 /360 /540 /540 /660 /660 /720 /720 /1150 /1150 /1150 /1500 /1500 3480 4320
Motor Power W 110 110 150 150 150 150 150 190 300 300 300 430 430 950 1120
Piping Connections Flare-nut Connection(with Flare Nuts) Brazing
Liquid Line mm Ф6.35 Ф6.35 Ф6.35 Ф6.35 Ф6.35 Ф6.35 Ф9.53 Ф9.53 Ф9.53 Ф9.53 Ф9.53 Ф9.53 Ф9.53 Ф9.53 Ф9.53
Gas Line mm Ф12.7 Ф12.7 Ф12.7 Ф12.7 Ф15.88 Ф15.88 Ф15.88 Ф15.88 Ф15.88 Ф15.88 Ф15.88 Ф15.88 Ф15.88 Ф19.05 Ф22.2
Condensate Drain VP25(Outer Diameter Ф32 )
External Static Pa 30 30 30 30 30 30 30 30 60 60 60 60 60 100 100
Pressure
Packing Volume m3 0.21 0.21 0.21 0.21 0.27 0.27 0.27 0.27 0.38 0.38 0.38 0.52 0.52 0.90 1.06

NOTES:
1.The nominal cooling capacity and heating capacity are based on following 2. The sound pressure level is based on following conditions: 1.5m beneath the unit.
conditions: With discharge duct (2.0m) and return duct(1.0m)
Cooling Operation Conditions The above data was measured in an anechoic chamber so that reflected sound
Indoor Air Inlet Temperature: 27℃ DB(80°F DB), 19.0℃WB(66.2°F WB) should be taken into consideration in the field.
Outdoor Air Inlet Temperature: 35℃ DB(95°F DB) When bottom air inlet is adopted, sound pressure will increase according to factors
3.
Piping Length: 7.5 Meters Piping Lift: 0 Meter such as installation mode and the room structure.
Heating Operation Conditions *1: AC3Φ, 380V/50Hz, *2: AC3Φ, 380V/60Hz
Indoor Air Inlet Temperature: 20℃ DB(68°F DB)
Outdoor Air Inlet Temperature: 7℃DB(45°F DB), 6℃WB(43°F WB)

113
Indoor Unit

Ceiling Ducted Type


(High Static Pressure)

Installation Space-saving Fresh Indoor Air

Product line-up
Less than 270mm in height can Minimum 5mm By introducing fresh outdoor air and being equipped with air
be easily fit into the limited 270mm
filter to keep indoor air clean.
space in the false ceiling
(7.5-24.2KBtu/h). 7.5-24.2KBtu/h False Ceiling
Excellent Air Flow Duct

Cooling and heating air distributed from


the unit to indoor space through ducts,
which creates a comfortable environ-
Flexibly Supports a Wide Indoor Unit

ment.
Range of Installation
Duct
Air Filter,Air Grid
Optional Parts
Canvas Duct(Field-supplied)
Air Inlet (Field-supplied)
Drain-up mechanism can be supplied as optional part.

NOTE:
When bottom air inlet is adopted, sound pressure will increase according to factors Maximum 900mm

such as installation mode and the room structure.

Condensate Drain-up

Indoor Unit Ceiling Ducted type (Low Static Pressure)


AC1Ф, 220 AVD-07 AVD-09 AVD-12 AVD-14 AVD-17 AVD-18 AVD-22 AVD-24 AVD-27 AVD-30 AVD-38 AVD-48 AVD-54 AVD-76 AVD-96
Model ~240V/50Hz UXCSAH UXCSAH UXCSAH UXCSAH UXCSBH UXCSBH UXCSBH UXCSBH UXCSCH UXCSCH UXCSCH UXCSDH UXCSDH UX6SEH*1 UX6SFH*1
Power Supply AC1Ф, AVD-07 AVD-09 AVD-12 AVD-14 AVD-17 AVD-18 AVD-22 AVD-24 AVD-27 AVD-30 AVD-38 AVD-48 AVD-54 AVD-76 AVD-96
220V/60Hz UX2SAH UX2SAH UX2SAH UX2SAH UX2SBH UX2SBH UX2SBH UX2SBH UX2SCH UX2SCH UX2SCH UX2SDH UX2SDH UX2SFH UX2SFH
KW 2.2 2.8 3.6 4.3 5.0 5.6 6.3 7.1 8.4 9.0 11.2 14.2 16.0 22.4 28.0
Nominal Cooling Kcal/h 1,900 2,400 3,100 3,700 4,300 4,800 5,400 6,100 7,200 7,700 9,600 12,200 13,800 19,300 24,100
Capacity
Btu/h 7,500 9,600 12,300 14,700 17,100 19,100 21,500 24,200 28,700 30,700 38,200 48,500 54,600 76,500 95,600
KW 2.8 3.3 4.2 4.9 5.6 6.5 7.5 8.5 9.6 10.0 13.0 16.3 18.0 25.0 31.5
Nominal Heating Kcal/h 2,800 3,600 4,200 4,800 5,600 6,500 7,300 8,300 8,600 11,200 14,000 15,500 21,500 27,100
Capacity 2,400
Btu/h 9,600 11,300 14,300 16,700 19,100 22,200 25,600 29,000 32,800 34,100 44,400 55,600 61,400 85,300 107,500
Noise Level dB(A) 33-31-29 33-31-29 33-31-29 33-31-29 34-32-30 34-32-30 36-34-32 36-34-32 41-39-34 41-39-34 43-40-36 44-41-36 43-40-37 52 54
(H/M/L)
H mm 270 270 270 270 270 270 270 270 350 350 350 350 350 470 470
Outer 1060 1250
Dimensions W mm 650+75 650+75 650+75 650+75 900+75 900+75 900+75 900+75 900+75 900+75 900+75 1300+75 1300+75
D mm 720 720 720 720 720 720 720 720 800 800 800 800 800 1120 1120
Net Weight Kg 25 25 25 25 34 34 34 34 44 44 44 56 56 94 106
Air Flow Rate m3/h 480/420 480/420 780/660 780/660 900/780 900/780 960/840 960/840 1600/1400 1600/1400 1600/1400 2100/1750 2150/1800 3480 4650
(H/M/L) /360 /360 /540 /540 /660 /660 /720 /720 /1150 /1150 /1150 /1450 /1550
Motor Power W 110 110 150 150 150 150 150 190 300 300 300 430 430 1030 1280
Piping Connections Flare-nut Connection(with Flare Nuts) Brazing
Liquid Line mm Ф6.35 Ф6.35 Ф6.35 Ф6.35 Ф6.35 Ф6.35 Ф9.53 Ф9.53 Ф9.53 Ф9.53 Ф9.53 Ф9.53 Ф9.53 Ф9.53 Ф9.53
Gas Line mm Ф12.7 Ф12.7 Ф12.7 Ф12.7 Ф15.88 Ф15.88 Ф15.88 Ф15.88 Ф15.88 Ф15.88 Ф15.88 Ф15.88 Ф15.88 Ф19.05 Ф22.2
Condensate Drain VP25(Outer Diameter Ф32 )
External Static Pa 50(80) 50(80) 50(80) 50(80) 50(80) 50(80) 50(80) 50(80) 120(90) 120(90) 120(90) 120(90) 120(90) 220 220
Pressure
Packing Volume m3 0.21 0.21 0.21 0.21 0.27 0.27 0.27 0.27 0.38 0.38 0.38 0.52 0.52 0.90 1.06

NOTES:
1.The nominal cooling capacity and heating capacity are based on following 2. The sound pressure level is based on following conditions: 1.5m beneath the unit.
conditions: With discharge duct (2.0m) and return duct(1.0m)
Cooling Operation Conditions The above data was measured in an anechoic chamber so that reflected sound
Indoor Air Inlet Temperature: 27℃ DB(80°F DB), 19.0℃WB(66.2°F WB) should be taken into consideration in the field.
Outdoor Air Inlet Temperature: 35℃ DB(95°F DB) 3. When bottom air inlet is adopted, sound pressure will increase according to factors
Piping Length: 7.5 Meters Piping Lift: 0 Meter such as installation mode and the room structure.
Heating Operation Conditions *1: AC3Φ, 380V/50Hz,
Indoor Air Inlet Temperature: 20℃ DB(68°F DB) *2: AC3Φ, 380V/60Hz: AVD- 76UX7SEH; AVD-96UX7SFH
Outdoor Air Inlet Temperature: 7℃DB(45°F DB), 6℃WB(43°F WB)

114
Indoor Unit

Ceiling Ducted Type(L/H)

Models: AVD- 07~54* Model Unit: mm


Unit:mm
Product line-up

l - φ6
b (Around the Flange) Air Inlet
40 a
e c x 300 = d
300 4 - 40 x 12
20

(for Suspension Bolt)


30
22

x
g
33.5

22
m
n

Wired controller
22

Viewed from A
30

120
20

300 l - φ6
e (Around the Flange) Drain Pipe Connection Drain Pipe Connection
c x 300 = d
(Standard Position) (VP25) (Optional Drain-Up Mechanism)

Refrigerant Gas Pipe Connection


(With iji Flare Nut)

Air Outlet Refrigerant Liquid Pipe Connection

2xv=w
(With ijh Flare Nut) u 45
a 75(Electrical Control Box)
2x90=180
220

A
90

v
r
q
p

97

23

35
s
t

246(Refrigerant Liquid Pipe Connection)


f 321(Refrigerant Gas Pipe Connection)
48.5 j (Refrigerant Gas Pipe Connection)
377
90(Drain Pipe Connection)
402
k (Refrigerant Liquid Pipe Connection)

Dimension
Model a b c d e f g h i j k l
07~14 650 730 1 300 215 553 583 6.35 12.7 70 92 10
17/18 900 980 2 600 190 803 833 6.35 15.88 77 92 12
22/24 900 980 2 600 190 803 833 9.53 15.88 77 95 12
27/30 900 980 2 600 190 803 833 9.53 15.88 78 95 12
38 900 980 2 600 190 803 833 9.53 15.88 81 95 12
48/54 1300 1380 3 900 240 1203 1233 9.53 15.88 81 95 14

Dimension
Model m n p q r s t u v w x
07~24 676 720 23 270 182 222 43 220 100 200 226
27~54 756 800 103 350 204 244 123 300 140 280 306

115
Indoor Unit

Product line-up
Models: AVD-76/96* Model Unit:mm

(Around the Flange)

Viewed from A
(for Suspension Bolt)

916

Air Outlet

(Around the Flange)


Air Inlet
Refrigerant Liquid Pipe
9.53 Brazing
Drain Piping Refrigerant Gas Pipe
22.2(19.05)Brazing
Air Inlet

NOTES: Data in the bracket is for AVD-76* model

116
Indoor Unit

Low-height
Ceiling Ducted Type (Height 192mm)

Installation Space-saving Excellent Air Flow Duct

With height of 192mm Cooling and heating air distributed


Product line-up

Minimum 5mm
may be easily installed from the unit to indoor space through
inside narrow residential 192mm ducts, which creates a comfortable
ceiling. environment.
False Ceiling

Satisfy Varied Requests on Installation


Available air inlet as rear or Indoor Unit

bottom entry, consumers can


Adjustable Indoor Unit Static Pressure
choose relevant air inlet mode Duct
Indoor unit can adjust static pressure automatically according Canvas Duct(Field-supplied) Air Filter,Air Grid
according to the practical Air Inlet (Field-supplied)
to the house structure and installation condition, ensure that
installation space. (Installation Diagram of Air Bottom Inlet)
the indoor unit operates in the optimum exhaust state.

Duct Duct
Drain-up Mechanism as Standard part
Drain-up length achieves
Elastic Hose Drain-up Length 900mm
900mm which enables
convenient drain piping and
When the required duct is short, When the required duct is long,
the static pressure can be set lower. the static pressure can be set higher; enlarges the flexibility of
installation.

Indoor Unit Ceiling Ducted type (Low Static Pressure)


AC1Ф, 220 AVE-07UXCSAL AVE-09UXCSAL AVE-12UXCSAL
Model ~ 240V/50Hz
AVE-14UXCSAL AVE-17UXCSBL AVE-18UXCSBL AVE-22UXCSBL AVE-24UXCSBL
Power Supply AC1Ф, AVE-07UX2SAL AVE-09UX2SAL
220V/60Hz
AVE-12UX2SAL AVE-14UX2SAL AVE-17UX2SBL AVE-18UX2SBL AVE-22UX2SBL AVE-24UX2SBL
KW 2.2 2.8 3.6 4.3 5.0 5.6 6.3 7.1
Nominal Cooling Kcal/h 1,900 2,400 3,100
Capacity 3,700 4,300 4,800 5,400 6,100
Btu/h 7,500 9,600 12,300 14,700 17,100 19,100 21,500 24,200
KW 2.8 3.3 4.2 4.9 5.8 6.5 7.5 8.5
Nominal Heating Kcal/h 2,400 2,800 3,600
Capacity 4,200 5,000 5,600 6,500 7,300
Btu/h 9,600 11,300 14,300 16,700 19,800 22,200 25,600 29,000
Noise Level dB(A) 27-24-21 27-24-21 32-30-27
(H/M/L) 32-30-27 34-30-28 34-30-28 36-32-29 36-32-29
H mm 192 192 192 192 192 192 192 192
Outer 900 900 900
Dimensions W mm 900 1170 1170 1170 1170
D mm 447 447 447 447 447 447 447 447
Net Weight Kg 20 20 21 21 26 26 26 26
Air Flow Rate m3/h 500/440/350 500/440/350 640/590/520
(H/M/L) 640/590/520 870/750/630 870/750/630 950/820/710 950/820/710
Motor Power W 50 50 70 70 100 100 110 110
Piping Connections Flare-nut Connection(with Flare Nuts)
Liquid Line mm Ф6.35 Ф6.35 Ф6.35 Ф6.35 Ф6.35 Ф6.35 Ф9.53 Ф9.53
Gas Line mm Ф12.7 Ф12.7 Ф12.7 Ф12.7 Ф15.88 Ф15.88 Ф15.88 Ф15.88
Condensate Drain VP25(Outer Diameter Ф32 )
External Static Pa 10(30) 10(30) 10(30)
Pressure 10(30) 10(30) 10(30) 10(30) 10(30)
Packing Volume m3 0.15 0.15 0.15 0.15 0.18 0.18 0.18 0.18

NOTES:
1.The nominal cooling capacity and heating capacity are based on following conditions: 2. The sound pressure level is based on following conditions: 1.5m beneath the unit. With discharge duct
Cooling Operation Conditions (2.0m) and return duct(1.0m)
Indoor Air Inlet Temperature: 27℃ DB(80°F DB), 19.0℃WB(66.2°F WB) The above data was measured in an anechoic chamber so that reflected sound should be taken into
Outdoor Air Inlet Temperature: 35℃ DB(95°F DB) consideration in the field.
Piping Length: 7.5 Meters Piping Lift: 0 Meter When bottom air inlet is adopted, sound pressure will increase according to factors such as installation
Heating Operation Conditions mode and the room structure.
Indoor Air Inlet Temperature: 20℃ DB(68°F DB)
Outdoor Air Inlet Temperature: 7℃DB(45°F DB), 6℃WB(43°F WB)

117
Indoor Unit

Models: AVE-07~14*AL Model Unit:mm

54 630

759

Product line-up
Refrigerant Refrigerant Drain Pipe
Gas Pipe Liquid Pipe Connection
Electrical
Control Box φ12.7 φ 6.35 (Drain-up
477
456
421

Mechanism)
447
Air Inlet

20

9
Air Outlet

29 47
109
80

171
192

80
900
938

87
1018
1053
72 8

44 30 6

Models: AVE-17~24*BL Model Unit:mm

1029
477
456
421

1170
1208
1288
1323

54 940
192

Refrigerant Refrigerant Drain Pipe


Gas Pipe Liquid Pipe Connection
Electrical a (Drain-up
b
Control Box Mechanism)
447
Air Inlet
20

Air Outlet
29 47

Dimension a b
Model
109
80

φ 15.88 φ 6.35
171
192

80

17/18
22/24 φ 15.88 φ 9.53
87

72 8

44 30 6

118
Indoor Unit

Slim Ceiling Ducted Type


(Width 700mm, Height 192 mm)
Installation Space-saving Excellent Air Flow
Duct
With a width of 700mm Cooling and heating air distributed from the
Product line-up

Minimum 5mm
and height of 192mm unit to indoor space through ducts, which
192mm

may be easily installed creates a comfortable environment.


700mm
inside narrow
residential ceiling. False Ceiling
Satisfy Varied Requests on Installation
Available air inlet as rear or bottom Indoor Unit

Adjustable Indoor Unit Static Pressure entry, consumers can choose


Duct
Indoor unit can adjust static pressure automatically according relevant air inlet mode according to Canvas Duct(Field-supplied) Air Filter,Air Grid
Air Inlet (Field-supplied)

to the house structure and installation condition, ensure that the practical installation space. (Installation Diagram of Air Bottom Inlet)

the indoor unit operates in the optimum exhaust state.

Duct Duct Drain-up Mechanism as Standard Part


Drain-up length achieves 900mm
Elastic Hose
which enables convenient drain Drain-up Length 900mm

piping and enlarges the flexibility


When the required duct is short, When the required duct is long,
the static pressure can be set lower. the static pressure can be set higher; of installation.

Indoor Unit Slim Ceiling Ducted Type


AC1Ф, 220 AVE-07UXCSGL AVE-09UXCSGL AVE-12UXCSGL AVE-14UXCSGL
Model ~ 240V/50Hz
Power Supply AC1Ф,
220V/60Hz AVE-07UX2SGL AVE-09UX2SGL AVE-12UX2SGL AVE-14UX2SGL
KW 2.2 2.8 3.6 4.3
Nominal Cooling Kcal/h 1,900 2,400 3,100 3,700
Capacity
Btu/h 7,500 9,600 12,300 14,700
KW 2.8 3.3 4.2 4.9
Nominal Heating Kcal/h 2,400 2,800 3,600
Capacity 4,200
Btu/h 9,600 11,300 14,300 16,700
Noise Level dB(A) 27-23-21 27-23-21 31-29-27 31-29-27
(H/M/L)
H mm 192 192 192 192
Outer mm
Dimensions W 700 700 700 700
D mm 602 602 602 602
Net Weight Kg 21 21 21 21
Air Flow Rate m3/h 450/380/335 450/380/335
(H/M/L) 590/510/470 590/510/470
Motor Power W 50 50 60 60
Piping Connections Flare-nut Connection(with Flare Nuts)
Liquid Line mm Ф6.35 Ф6.35 Ф6.35 Ф6.35
Gas Line mm Ф12.7 Ф12.7 Ф12.7 Ф12.7
Condensate Drain VP25(Outer Diameter Ф32 )
External Static Pa 10(30) 10(30) 10(30) 10(30)
Pressure
Packing Volume m3 0.15 0.15 0.15 0.15

NOTES:
1.The nominal cooling capacity and heating capacity are based on following conditions: 2. The sound pressure level is based on following conditions: 1.5m beneath the unit. With discharge duct
Cooling Operation Conditions (2.0m) and return duct(1.0m)
Indoor Air Inlet Temperature: 27℃ DB(80°F DB), 19.0℃WB(66.2°F WB) The above data was measured in an anechoic chamber so that reflected sound should be taken into
Outdoor Air Inlet Temperature: 35℃ DB(95°F DB) consideration in the field.
Piping Length: 7.5 Meters Piping Lift: 0 Meter When bottom air inlet is adopted, sound pressure will increase according to factors such as installation
Heating Operation Conditions mode and the room structure.
Indoor Air Inlet Temperature: 20℃ DB(68°F DB)
Outdoor Air Inlet Temperature: 7℃DB(45°F DB), 6℃WB(43°F WB)

119
Indoor Unit

Models: AVE-07~14*GL Model

Product line-up
Unit:mm

Liquid Pipe Gas Pipe Water Outlet Electrical Box Return Air Inlet
(Pump)

Air Outlet

120
Hisense International Co., Ltd.
Add:17, Donghai Xi Road, Qingdao,China.
Tel:+86-532-83878888 Fax:+86-532-83866770 http://www.hisense.com E-mail: exportvrf@hisense.com

HCAC-CA2015G02

NOTICE:
When installing or relocating the air conditioners, use the specific refrigerant (R410A) only to charge the refrigerant lines. Any other refrigerant or air is not allowed to enter the lines.
If the refrigerant is mixed with air, then it may cause abnormal high pressure in the refrigerant lines, resulting in explosion or other hazards.
The use of any refrigerant other than the specific refrigerant for the system will cause mechanical failure, system malfunction or unit breakdown.
In worse case, this could lead to a serious impediment to securing the product safety.
Hisense's liability shall not cover the malfunctions or accidents resulting from the use of the wrong type of refrigerant.