You are on page 1of 25

-.L’:L :? ““.

”’
. . .
—- ———-. —___ .- _

Downloaded from http://www.everyspec.com


MI1-STD-704
6 OCTOBER1959
SUPERSEDING
MIL-E-7894A(ASG)
17 MAY 1955

MILITARY STANDARD

ELECTRICPOWER, AIRCRA~,
CHARACTERISTICSAND UTILIZATION OF

,,
~.
,,//”
____ ____ ___ ——-
Downloaded from http://www.everyspec.com

\. .._. _.____. _— ——–—

MI.-STD-7O4
6 Octobar 1959

DEPARTMENT OF DEFENSE
ARMED FORCSS SUPPLY SUPPORT CENTER
WASHINGTON25, D. C.

ELRCTRIC POWER, AIRCRAFT, CHARACTERISTICS


AND UTILIZATION OF
MIL-STD-704 6 October 1959

1. This standard has been approved by the Department of Defense


and is msndatmy for use by the Army, the Navy, and the Air Force,
effective 6 October 1959.

2. In accordance with established procedure, the Transportation


Caps, Bureau of Aeronautics, end Air Force have been designated, re-
spectively, as Army-Navy-Air Force custodians of this standard.

3. Recommended corrections, additions, or deletions should be


addressed to the Standardization Division, Armed Fomes Supply Support
Center, Washington 25, D. C.

ii

,_ .2 ‘““ .... . . . . . . . . .

__. —— —

Downloaded from http://www.everyspec.com

-,._ ______ --
.
MIL-STD-704
6 Octobw 1959

Page
1. GENERAL ........................................... i
1.1 scope . . . . . .......................................... 1
12 ............................................. 1

2. APPLICABLE DOCUMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
.% DEFINITIONS ..................... .................. 1
3.1 Average value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
3.2 Ground . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
3.3 Trandent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
3.4 Total harmonic content . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ... . 1
3.5 Frequency modrdation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
3.6 Frequency modulation rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
3.’7 Frequency drift . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
3.8 Frequency drift rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
3.9 A-c VO]tll& . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
3.10 Voltage modulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
3.11 Voltage mcdulatkmf requeneyc harackietk ..............
3.12 Ripple . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . :
3.13 Unssfewndition ...................................... 2
3.14 Aireraft operation peril@ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
3.15 Utilization equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
3.16 Category `'A'' utiliition equipment . . . . . . . . . . . . . . . . . . . . . . 2
3.17 Category `'B'' utiliition equipment . . . . . . . . . . . . . . . . . . . . . . 2
3.18 Category ``C''utilisetion equipment . . . . . . . . . . . . . . . . . . . . . . 2

4. GENERAL REQUIREMENTS ........... ............... 2


4.1 Power ayateJm9 . . . . . . . . . . . . . . ........... ............... 2
4.1.1 A-cpawer . . . . . . . . . . . . . . . ........... ............... 2
4.1.2 D-c power . . . . . . . . . . . . . . ........... ............... 2
4.2 Utiliition equipment . . . . . . . . ........... ............... 2

5. DETAIL REQUIREMENTS ............................ 2


6.1 A-epower syatemcharackiatica ..;.. . . . . . . . . . . . . . . . . . . . 2
6.1.1 L-ine-@n&tml . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
5.1.2 LindcAine ........................................ ,2
5.1.3 steady-state voltage . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . 3
6.1.3.1 Single pke ....................................... 3
5.1.3.2 Three phase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
5.1.3.3 Phaaedisplscementa ................................ 3
5.1.3.4 Unhalanee ........................................ 3
5.1.3.5 Wave form . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
5.1.3.6 Modtdation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
5.1.3.6.1 Amplitude ........................................ 3
5.1.3.6.2 Frequency characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
5.1.4 Transient voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
. ..
m

.
Downloaded from http://www.everyspec.com

M1l-!m-704
6 Octobor 1959

CONTENTS (Gmtinned)
Pags
5.1.4.1 Normal ektric-ayatem opemtion .. . . . . . . . . . . . . . . . . . . . . . 3
5.1.4.2 Abnormal electri*syatem operation . . . . . . . . . . . . . . . . . . . . 7
5.1.5 Stdy-irtat efrequency . . . . . . . . . . . . . . . . . . . . . . . . ... . . . . 7
6.1.5.1 Drift . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5.1.5.2 Modulation ampfitude . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5.1.5.3 Mcdulationrate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5.1.6 Transient frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
6.1.6.1 Normslelechiesyatem operation . . . . . . . . . . . . . . . . . . . . . . 7
5.1.6.2 AbnormsIe ktri*systernoper ation ................... 7
5.1.7 PheseseWencY . . . . . . . . . . . . . . . . . . . . . . ..! . . . . . . . . . . . 7
5.2 D-cpower syti-ehamcteristice ........................ 3
5.2.1 St=dy-state voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5.2.2 Ripple . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5.2.2.1 Frcqoenc.v chsracteristica . . . . . . . . . . . . . . . . . . . . . . . . . . . .. 8
5.2.3 Tnmsientv oltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5.2.3.1 Normslekc.trksystemoper scion.... .................. 3
5.2.3,2 Abnormsl ekctric-systemop eration ................... 8

6. UTILIZATION OF AIRCRAFT ELECTRIC POWER .. . . . . 3


6.1 Power types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
6.2 Conversion . . . . . . ... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
6.2.1 A-cto26voltadc.. ................................ 3
6,3 Normslelectric-system operation . . . . . . . . . . . . . . . . . . . . . . . . . 11
6.4 Abnormal electric-system opaation . . . . . . . . . . . . . . . . . . . . . . 11
6.5 Other electric-system operation . . . . . . . . . . . . . . . . . . . . . . . . . . 11
6.6 Voltage tmnsienta . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
6.7 warmup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
6.8 Influence onekrtricsyate m........ ............ ........ 11
6.3.1 Self-modulation .................................... 11
6.9 A-c Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
6.9.1 Tfmephase.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
6.9.2 Single phsse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
6.9.3 Phaw balance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
6.9.4 Power factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
6.9.5 Phase faihwe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
6.10 Power failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
6.11 .Yandby power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
6.12 Power tolerance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
6.13 Power requirements data (Requircxl for NaVY equipment only) 12
6.13.1 SsmplefOrm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

7. NOTES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
7.1 h’ormal electric-system operation . . . . . . . . . . . . . . . . . . . . . . . . 15
7.2 Abnormal ekctric-systemop eration ...................... 17
7.3 Emergency electric-system op=stion ..................... 17
7.4 Reference voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
7.?5 Referent.e frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
7.6 Conl-ersion of a transient to its evaluated step function loci. . . 17

iv

__. —... _,. .,_— .“’

:
-.—.-—— .._ __ _
Downloaded from http://www.everyspec.com

—. ——.
,-----

MIL-STD-704
6 Ocbbar 1959

CONTENTS (Continued)
Page
7.6.1 Fault tramienta. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
7.7 L.inedrop eompmeation .. ......... ..................... 19
7.8 Equipment detiilspwification . .... .. .. .... .. .. .... ... ... ’19
7.9 AssmnPtfomc . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
7.9.1 SrnSllest primary ekctricsyat em.... ................. . 19
7.9.2 EIectilc-system balance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
7.9.9 Generatiig+ystem chsracteristica . . . . . . . . . . . . . . . . . . . . . 20
7.9.4 Electric-syatem chsracteristica ...,... ................. 20
7.9.6 Nortnal loading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
7.9.6 Initisl warmup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
7.9.7 System power factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
7.9.8 Power-aystem rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

FIGURES
1. Frequency characteristics of a-c voltage modulation envelope . . 4
2. Transient a-c voltage step function loci limits . . . . . . . . . . . . . . 5
3. Transient frequency tilts .............................. 6
4. D]agram of phase seq~eney and line designations . . . . . . . . . . . 7
.5. Frequency characteristics of ripple in 28-volt d-c electric
systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
& Transient d-c voltage step function loci limits . . . . . . . . . . . . . . 10
7’. Unbalance Iti]ta for 3-phsse utilisation equipment . . . . . . . . . . 13
8. Lagging power factor ltilts for utilisation equipment . . . . . . . . 14
9. Sample form for submittal of power requirements data . . . . . . 16
10. Sample conversion of an overvoltage transient to its evaluated
step functio nloe i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
11. Standard MIL-STD-704 power utilization checfdkt . . . . . . . . . 19

TABLES
T. Steady-state a-evoltsge ltilts . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
IL Steady+tatcd -cvoltagel emits.... ....................... S

.._._, v
,, . ..-
—..
.

._— —
.
~..-—. —— -- -.——.
Downloaded from http://www.everyspec.com
.

‘--------- ._ -.. ..
_____ _____ ______ __

MIL-STO-704
6 October 1959

MIUTARY STANDARD
ELECTRIC POWER, AIRCRAFT,
CHARACTERISTICS AND UTILIZATION OF

1. (; ENERAI, 3.5 Frequency modulation. Frequency mod-


ulation is the cyclic or random dynruntc vari-
1,1 Scope. ‘fhis standard delineates the ation, or bnth, of instantaneous frequency
characteristics of electric power to be sup abeut a mean frequency during steady-state
plied to sirborne equipment at the equipment electric-system operation. The frequency
terminals and the requirements for the utili- modulation is normally within” narrow fre-
zation of such electric power by the airlmme quency Iirnita and eccnra as a result of speed
equipment. variations in a generator rotor owing to the
dynamic operation of the rotor coupling and
1.2 Purpose. The purpose of this standard drive speed regulation.
is to foster compatibility between aircraft
electric systems and airborrre utilization 3.6 Frequency modulation rate. The fre-
equipment to the extent of confining the eir- quency mmhdation rate is ‘the rate of change
cmft electric ~wer characteristics within of frequency owing to frequency modulation
definitive limits and restricting the require- when plotted against Ulme.
ments imposed on the electric pewer by the
airbnrne utilisation equipment. 3.7 Frequency drift. Frequency drift is tbe
extremely slow and random variation in fre-
2. APPLICABJ,E DOCUMENTS quency within the steady-state limits occnr-
ring as a result of environmental effects and
2.1 Not appliesbie. wear on the electric power-drive system.

3. DEFINITIONS 3.8 Frequency drift rate. The frequency


drift rate is the rate of change of frequency
Xl Average vrdue. The average valne of owing to frequency drift when plotted
phase quantities is the arithmetical sum of against time.
the phase values divided by the number of
3.9 A-c voltage. The a-c voltage values
phases.
stated herein shall be for any phase of those
supplied utilization equipment, a phase being
3.2 Ground. The primary aircraft structure considered a line to neutral. All a-c voltage
is the referenced ground for the negative of values are mot mean square (rrns) values.
the dc and the neutral of the sc in the power
generation and pnwer utilization systems.
3.10 Voltage modulation. Voltage morfula-
tion is the cyclic variation or random rlY-
3.3 Transients. A transient is the charrg- namic Variations, or both, about an average
ing condition of a characteristic which gees of the a-c peak voltage dining steady-state
beyond the steady-state limits and returns electric-eystem operation such es caused by
to the steady-state limits within a specified voltage regulation and speed variations. The
time period. modulation envelope is formed by a continu-
ous crmve connecting each sine wave peak to
3.4 Total harmonic content. The total har- the successive sine wave peak.
monic content of a complex wave is the total
rrns voltage remaining when the fundamental 3.11 Voltage mndulaticur frequency char-
component is removed. acteristics. The frequency charactel”istic Of

1
..
—.

—.
.. —-- ,— -—- —--. — .-- .--.-—

Downloaded from http://www.everyspec.com
-.

MIL-STD-704
6 Octobor 19S9

voltage modulation is defined as the comprm- During opcratimr, voltage limits include al-
ent frequencies which make up the modula- lowance for 8 volts a-c line drop or 2 volts
tion envelope wave form. d-c line drop, or both.

:1.12 Ripple. Ripple is the a-c variation of 4. GENERAL REQUIREMENTS


voltage about a fixed d-c voltage during
steady-state d-c electric-system operation. 4.1 Power systems. Characteristics of air-
craft puwer at the input terminals of utili-
:1.13 Unsafe condition. An unsafe condition zation equipment shall be within the limits
is any condition within aircraft that jeopar- stated in section 5 under the conditions of
dizes the safety of the aircraft and the per- power utilization prescribed bisection 6.
sonnel aboard.
4.1.1 A-cpowcr. Thea.cpower system shall
3.14 Aircraft operational period. The oper- he a ,3-phase, 4-wire “Y” system, having a
ational period of an aircraft is defined as the nominal voltage of 115/200 and a nominal
time interval between the start of prepara- frequency of 400 cps. The neutral point of the
tion for flight and the post flight engine source of power is connected to ground (see
stiutdown with consequent deactivation of 3.2), and the ground is considered the fourth
ttie aircraft electric system. conductor.

j 3.15 Utilization equipment. Utilization 4.1.2 D-cpocuer. Thed-cpower systam shall


equipment will be considered aa comprising be a 2-wire, grounded system having a nomi-
either an individual unit, set, or a complete nrd voltage of 28 volts. The negative of the
system to which the electrical power is ap- power source isconnected to ground and the
plierl or disconnected, or both, as a whole. ground is considered the second wire.

3.16 Category “A” utilisation equipment: 4.2 Utilization equipment. Utilization equip-
Category “A” equipment are those utilisa- ment shall maintain specified performance,
tion equipments whose installation in aircraft using the puwer with characteristics which
will be controlled so that line drops will be are listed in section 5. When nse of power
limited to 2-volts a-c line drop or $+volt dc. is required having other characteristics or
or botb. The line drup is the voltage differ- narrower tolerances than specified herein, the
ence between the point of voltage regulation conversion to other characteristics or closer
and the power input terminals of the equip- tolerances shall be accomplished as a part of
ment. Use of this category should be held to tbe utilization equipment. Utilization equip
a minimum. and its use will be subject to ment desigaed for a specific aircraft applica-
approval by the procuring activity. tion may deviate from these requirements
only upon approval of the procuring activity.
3.17 category “B” utilimtion equipment.
Category “B” equipment are thoee utilization 5. DETAII. REQUIREMENTS
equipments destined for aircraft for which
the line rtrups will be less than 4 volts sc or 5.1 A-cpawer eystem characteristics.
1 volt dc, or both. When a detd equipment
specification does not desigaate a category, 5.1.1 Liw-to-nsutd. Characteristics of line-
the equipment will be considered a category ~rreutral puwer shall be within the ltilts
“B” equipment. specified herein.

3.18 Category “C” utilization equipment. 5.1.2 Line-to-lim. Characteristics of line-to-


Category “C” equipment are those equip- line power shall be as a result of line-to-neu-
ments which are intermittently operated. tral charecteristicsb eingasspscified,

~
j -:—
Downloaded from http://www.everyspec.com
..—

MIL-STO-704
60ctober 1959

TABLMI. Steady-state a-c voltage Iimita


..-.. —..- . .. . .

Madeof
.Oemtl.” 1----------- ::Z=T-AZ;ZEZ
N.arm.l E—r Normal
——
Em-r-w

Cateaory “A” 10%6h 119.5 107to 1ss 110.5to 117.5 10s t.a120
——
Category“B” 107.5to 119.5 105to 122 108.5to 117.5 10s to 120

Categwy‘rC” I lo3.5t0119.6I Ioltolzz I m4.,tol,7.5 I lo2to 120

5.1.3 Steud@de voltage. The eteady-state (c) Individual harmonic content: 3 per-
phase voltage shall be within the limits of cent of the fundamental (rma)
table I. These limits are applicable during with linear IOad9, or 4 perceut of
330- to 420-cPs operation. Mcdee of elestilc- the fundamental (me) with non-
syatem operation shown in table I and sub- Itnear loads, when measured with
sequent are explained in sdion 7. Utilisation a harmonic analyzer.
equipment categories shown in table I and
subsequent are defined in aestion 3.
5.1.3.6 Moddutien.
5.1.3.1 Single phuse. The steady-state vOlt-
age for a single phase shall be within the 5.1.3.6.1 AmpMu&. The modulation of volt-
lindte of table I. age (w= 3.1O) shall not exceed an amplitude
of 3.5 volts when measured 32 the peak-to-
5.1.3.2 Three phase. The steady-state volt- velley dflerence between the minbmnn voltage
age average for the three phases shall bs rmched and the maximum voltage rearhed on
within the limits of table I. the modulation envelope over a pariod of at
least 1 eewnd. A sketch of voltage modulation
5.1.3.3 Phase dieplucementu. The dBplece- is ehown in figure 1.
ment betwaen adjacent phaam ehafl hs within
the ltiIt9 of 120” * 1.5”. 5.1.3.6.2 FmqNensu .+uwuchietics. The fr+
quency components of the veltaga modulation
5.1.3.4 Unbakwcce. Maxiimn spread in envelope wave form (see 3.11) shelf be wit.ldm
phase voltages shall be less than 3 volts k the Iinits specified in figure L
tween the phase with the highest voltage and
the phase with the lowest voltage for all afr-
5.1.4 ‘l%zmid voltage. Voltage tram9kn@
craft operations.
wfien converted to their evaluated *P func-
tion losi (se@ 7.6), aid bs @hbr the limits
5.1.3.5 Wme fem. The voltage wave form
of figure 2 for all operation of the airsraft
shall bc within the following bits:
elestric system. The mmt severe phaee tran-
(a) Crest factor: 1.41 * 0.1. sient shall ba uaad in detemnbdng mnform-
anm to figure 2.
(b) Total harmonic content: 4 persent
of the fundamental (ma) with
linear loads, or 5 percent of the 5.1.4.1 Normal electric-swtenc opemtiun.
fundamental (rms) with non- The evaluated step funstion Ioei of the a-s
linear loads, when measured wtth voltage transients for all normal elestric-sya-
a distortion meter se distortion of tem operations shall be witldm the limits 2
the fundamental frequency. and 3 of figure 2.

3
,. .—.
.
,7 .— __
...—- ———-.—-.—-.—- _—
MIL-STD-704
6 Odder 1959
)
I — !
I I
-—-i––t–t–l–

Downloaded from http://www.everyspec.com

— 3




0 0 0 Ou
m Lx
-. c
*
( ‘“dA) A311VA 01 )lV3d NOllVlilaOW
4
,.—----” —
—..
,= --— _——
1,
.. ..-. —_
.. ———-—

MIL-STD-704
6 Odder 1959
Downloaded from http://www.everyspec.com

S11OA Swm
b
>.___
.
—- .—— _____ ___
-> :.:. .
— ‘-— -—. --—-—
‘.
..— —.._._—
MIL-m704
6 WObw 1959


.
\

r--— — — —

\, I —
— .
Downloaded from http://www.everyspec.com

\ —

\l —
m

— -~
Y—
I
/



. .._


..— —..
fg ●


go
N
go:
*

..-
6
.. -

. .-
. . . ..
._ —._
Downloaded from http://www.everyspec.com

. .

MIL-STD-704
6 &tek1959

GENERATOR
UTILIZATION
EQUIPMENT
I
A

x
NEU’TRAL
& A I

PHASE SEQUENCE; A*B .C

“A c B
F1cuea4. Diawamofphuw sequenceand line den”enaiiona

5.1.4.2 Abrwmmd eteetric-wtem operition. 5.1.5.3 Moddation ru$r. Rates of frequency


‘l’be evaluated step function loci of the a-c _ (See 3.6) Owing to frequeney modnla-
voltage transients which result frmn abnormal tionahaU benotgreater tAan18epe per
electAc-system operation shall be less than second.
the limks 1 and 4 of figure 2.
3.1.6 Tmneient @&-rIou. FrCqUeneytrSOS-
3.1.5 Steady-state freqaencp. The a-c power sient9shall be contaimcd within the limits of
SW- frequency shall be maintained at 400 figure 3 for all aircraft operations. Rates. of
& 20 cpe for study-state operation. frequency change during a -lent alwdl not
exceed 500 cpa per eeeond for any period
5.1.5.1 Drift.Variation within steady-state longer than 15 miflisccmh.
freqoency limits owing to drift (see 3.7) ehafl
be not more then * 5 cps for any period of 5.1.6.1 Normal efectric - eystsm operation.
steady-stab electric-system operation. F= Frequency transients es a ramlt of normal
quency variation owing to drift shall not occur system operations (see 7.1) ~11 be *thin
at a rate (see 3.8) greater than 15 cpa per the Iiiits of 2 and 3 of figure 3.
minute.
5.1.6.2 Abnormal ef.%tricastem operation.
5.1.5.2 Modulation am@L&. Veriatiomof Frequency transients as a result of abnormal
frequency owing to frequency modulation (see electric-system operations (we 7.2) shell be
3.5) during any l-minute period shall be with- within the limits 1 and 4 of figure 3.
in a band of * 2 cps about a mean frequency.
The’ mean frequency rnsy drift within the 5.1.7 Phaee sequence. The electric dieti]bu-
limits defined by 5.1.5.1. tion and utilization system+ shall have a phase

.—. , ,: ~. 7
+... ,....- _ —
..// –
.
/
_ _.—- —--
Downloaded from http://www.everyspec.com

— -- .—.—.—._, .. . . . .. ... . .—

MIL-STD-704
6 October 19S9

l’ABIJC IL Steadu-state d-c voltage limi&

‘$ *E c
, Thesea?tedCO”diti,,n.
of Uircr.ft
operation
*,,within
the“O,malmod,ofClectriesmtem
.bwrau.m.
2After3 mimtu of ..M ad W.,nmp .irc,tit .aWrnti.an, OK sti&sab d~e EE.Jti da b wje,h *, Bmlts med
1., tdm,m .aml’ma.m.
1 Wheresi
mraftlanding.pernt;.ms
b..,dmratio.s 5 min.tm thewider v.hge
exceedinz linlitf
allowed
forIa.dlnc
sMI &
formu],.f.,
randn beyondtheumi” ,Ilowcd m.ratb,r,
6 u,ir,utes.

sequence of A, B, C corrcaponding to T, — T, 5.2.3.2 Abnormal efectric-.vftstem opew%n.


— T, of the power source. Figure 4 diagrams The evaluated step function loci of the d-c volt.
this relationship. age transients which result from abnormal
electric-system operation shall be less than the
5.2 D-c prover system characteristics limits 1 and 4 of figure 6.

5.2.1 Steady-state vottage. Steady-state volt- 6. UTILIZATION OF AIRCRAFT


age shall be within the ltilts specified in ELECTRIC POWER
table II.

5.2.2 Ripple. The a-c peak of ripple voltage 6.1 Power types. The utilization equipment
to average d-c voltage (see 3.12) shell be less specification shall specify as shown in 6.13.1
than 1.5 volts, when measnred with a peak which of the types of power listed herein is
reading vacuum tube voltmeter in series with required. The equipmeut may require one or
a 4.0 microfarad capacitor. The higher of the both of these types of fmwer. No other types
two values measured when the voltmeter is of inpnt power shall be used witbout written
successively connected for each of two polari- permission from the prccnring activity. It is
ties shall be considered the ripple voltage. preferred that equipment he required to use,
where practicable, ordy the a-c type of power
5.2.2.1 FrequenmJ ciwacteristics. The fre- listed berein.
quency components of the ~ipple shall be with.
in the limits of figure 5 when measursd as 6.2 Conversion, Equipment which requires
conductd interference. conversion of input power to power with
other characteristics shall accept the power
5.2.3 ?%ansid voltage. Voltage transients, as defined herein for modification and use.
when converted to their evaluated step func- Modification and use shall be integral with
tion loci, shall be -within the limits of tigure the utilization systems or utilization equip-
6 for all operations of the aircraft electric ment.
system.
6.2.1 Ac to ~8 VOW dc. Utilisation equip-
3.2.3.1 h’owud electric- $qIstem operation. ment of a sise to require a-c input power above
The evaluatsd step function ioci of the d-c 500 va may include integral static converters
voltage tranaienta for all normal electric-sys - to obtain up to 5 amperes of 28-volt d-c pawer
tern operations shall be within the limits 2 and in lieu of requiring the 28-volt d-c power speci-
3 of figure 6. fied herein.

8 :---- ~~
,, -

.._ —-—— —--


.— —— ———
.-
._. _—— -——. . . .. . . . ---- _,
MIL-STD-704
6 October 1959
0
Downloaded from http://www.everyspec.com

0
W
o
*
o
W* Cu .Ej
0 o
awe,
-. N -. ~oo00 0 0
00 0 0 0 00 0 0
S11OA SH8
.— / .. ,”.
.- —.
.-
.— -
— .- .- —.
MIL-STD-704
6 -r 1959
F
P
c
;

:
Downloaded from http://www.everyspec.com

1%

it ; —

/— — G
w
\ (n
u
s
i i=

— —
.—
/
— T l–


.—
— [
10
.. .
. — -. .. .
.—.
---- -
.,---- ———_
Downloaded from http://www.everyspec.com

-. —

MIL-STD-704
6 Oetobr 1959

6.6 Normat electrtc-eystem operation. Dur- (1) Recover automatieeuy to apeet-


tng normot operation of the electric system tkd performanq mdese the
(See 5.1.6, 5.1.4.1, 5.1.5, 5.1.6.1, 5.2.1, end debit epeddcation for a
5.2,2.1), utilization equipment shall: given utitisation equipment
(a) Mvide 100-percent performance, PermitS IUSUUSI reset of
equipment after the abnor-
except when the detail specifica-
mal electric-system operation.
tion for a given utilization equip
ment defines specitic regions of (2) Have negligible effest on reli.
the electric system characteris- ability owing to,the abnonnat
tics with corresponding degrees electri*syetem operation.
of performance degradation (see
7.8). 6.5 Other electric-system operation. While
the electric system operatea in regions of
(b) Remain safe. characteristics other than specided in section
(c) When degraded performance bee 5, utilisation equipment shalt:
been permitted for gtvon regions
(a) Not be required to perform.
of given characteristics, after OP
eration in such regions with r+ (b) Not be required to perform after
turn to other regions of normal return of the electric system into
electrbsystem operation, the nti- the regions of characteristics spe-
tisation equipment shall: cified in sestion 5.

(1) Automatically recover to 100- 6.6 Voltage transients. For the purpose of
percent performance.
testing performance of utilization equipment
(2) Remain unaffected in reliabil- during conditions of input voltage tilents,
ity. voltage transients shatl be mnsidered se any
voltage at its corresponding time on the
6.4 Abnormal electric - system operation. limits of figures 2 and 6.
M abnommt operation of the electrh
system (see 5.1.4.2, 5.1.6.2, end 5.2.3.2) utiti- 6.7 Warmup. Time required for equipment
cation equipment: to warmup prior to obtaining speciSed par-
(a) Shell have no performance require- formence shall be kept to e minimum. ‘l%ne
ments, unless the detail speeifi- to return to specified performance, after a
tion for a given utiiation equip power interruption, shall not exceed the ac-
ment requires specific degrees of tuat thermal or mechanical requirements, or
performance to be maintained both, Warmup shall he leas than 5 minutes
within specific regions of the elec- unless approved in wrtting by the procuring
tric-system charasteristfss (see activity.
7.6) .
6.8 In6qence on electrtc system. There
(b) Shrdl remain safe.
shatt be no influence by utilization equipment
(c) May have momen~ 10SS of fonc- on the cherastmistics of power at the input
tion; however, this momentary to its terminals which would cause these
loss shall not atTect later equip characteristics to go beyond the limits epeci-
ment performance. tted in sedion 6.
(d) After abnormal operation of the
electric system and with return 6.6.1 Setf+lodukzfiox The modulation in-
of the ekcti:c system to normal duesd by vruying loads within utilisation
operation, utilisation equfpment equipment shaS not at the ti “ of the
shall : utiSsettOn equipment, cause voltage moduIa-

11

. . . -.

‘...
—-.

...— .. . . —. — ———. — —.. _ /


–-— —.
Downloaded from http://www.everyspec.com


-. . __. —... .—

MiL-sfD-704
6 October 19S9

tion or ripple to go beyond the limits of 6.10 Power failure. For those eqniprnenta
5.1.3.6 and 5.2.2. This self-mwhdation is caus- which require both a-c and d-e power, one
ed by variations in the current reqnircd by of these power sources may fail. Failure of
: the equipment, in turn causing a varying one power source shall not result in an unsafe
voltage drop in the wiring of the power cir- condition. During the loss of the one power
cuit to the equipment. source, no equipment performance is ra-
quired.
6.9 A-c power.
6.11 Standby power. For those modes of
6.9.1 !Thrwephase. For loads less than 500 equipment operation in which performance is
~a, 3-phase power shall be nsed when prac. not required but power ia required to msin-
tirable. Fm- a-c input demands excesding 500 tsin equipment standby readiness, the stand-
va, 3-phsse power shall be required. The aver- by power requirement should bc kept to a
age of three phases st.eady+tate voltage limits minimum.
in table I are applicable only when a phase of
the three phases is not utilizsd as a single- 6.12 Puwer tolerance. Input power require-
phsse lead. ments shall not vary by more than + 10 per-
cent and – 10 percent of an established limit
6.9.2 Single phae. For a-c input demands between production units of a given utilisation
not exceeding 500 va, it is allowable for the equipment. The specified tolerance Itilta do not
equipment to require single-phase power. include changw in equipment power demands
Equipment which is inherently single phase as a resnlt of engineering changes rnsde dur-
in pewer consumption shall present, if practic- ing production.
able, a three-phase demand by being internally
SCgrCgS@d into three singk-phase loads. Sin- 6.13 Power requirements data (required
gle-php~ pewer shall be M only on a line-to- for Navy equipment only). Power require
neutrsl basis. ment data shall be submitted to the procur-
ing activity. The data shall be successively
6.9.3 Phase fmkmce. Equipment requiring submitted as soon as available based on:
three-phsse power shall rsquirs sqns} phase (a) Specification requirements.
volt-am- and power factor insofar as
(b) Preliminary design data for the
practicable. The pk~e volt-ampere difference
equipment.
between the highest and lowwt phase values,
assmning bslsneed voltages, shafl hc les than (c) Measurements made on the first
the limits specified in figure ‘7. models.
(d) Measurements made on representa-
6.9.4 Power fader. Equipment utilizing a-c tive production units.
power shall be designed to present as near a (e) Power requirements revisions CSU5
unity pawer factor & practicable for all modes ed by proposed equipment changes.
of equipment operation. The fully loaded
equipment shall present a power factor on the NOTE: When the Air Force is the procur-
worst phase not les9 than the limits spccifisd ing activity, a copy of the power re-
in figure 8. quirements data shall be submitted tu
the Wright Air Development Center,
6.9.5 Phu.re faikre. One phase of three- Wright-Patterson Alr Force Base,
phase power can fail. Failure of one phase Ohio; Attention: WCLES.
shall not result in an unsafe condition. During
failure of the one phase, no cqnipment per- 6.13.1 Sampfe form. The sample form for
formance” is requirsd unless speei3ed in the submittal of the power raqn~ements data shall
equipment detail spccifleation. be os shown on figure 9. It shall be submittsd

,, M..
~–
---
-, .--—
,—.. .—— — —- --

‘\_____ ——
Downloaded from http://www.everyspec.com

..- —-— — ,.. . —

MIL-STD-704 ‘
6 Octeber 19S9

r
30
3-PII.4SE WAD (KVA) UNR4LANCE (VA)
200
28 i 390
7
12 E
i+
20
2A
825
900
950
24

-1 30 1,000

20

16

12

0
0 200 400 600 600 I,Ooo
MAXIMUM UNBALANCE (VA)

FXOUFZ 7. VnbaknceIimti for @uue utikiim 6Qt{w$71t

_— - 13

,,
—..
:. ,

__ -—. .. --——.--—.-—— _
Downloaded from http://www.everyspec.com
..
..
——— —--- —- +-. _

hU1-STD-704
6 O@ober 19S9

30.0
CATEOORY
flAfl ANO ‘Btt ncl!

2.0 P.F . KVA P.F. KVA


0.10 0.025 0.10 0.025
0.30 0.090 0.30 0.120
1.8 0.50 0.200 0.40 0.300
0.65 0.400 0.46 0.600
0.75 0.750 0.50 1.00
1.6 0.75 30.0 0.50 30.0
n i I t 1 I
u
o
J
a
>
x
E
1-
U
a

0.4 ———

0.2

0.1 0.2 o.~ 0.4 0.6 0.8 1.0

POWER FACTOR
FISVIW
8. &gp”ng powerfactor limiti for utilizationequimt

on 8 by 10Y2 sheeta. Inetroctions for complet- (c) Enter braekete at the tep of the
ing the form shall be as follows: power requirements cokmms “M”
for measured, “C” for calculated,
(a) Cross out category of equipment not or “R” for referenced. to indicate
the source of information. Refer-
erence “R” can be detailed in the
(b) Fill in brecketa to indisste mode or
medes of equipment operation line “Source of Information” or
such as Warmnp, Standby, Oper- under “REMARKS” as applicable.
ate, ‘Low Power, Power Duty (d) Under “Operating Time” enter oper-
Cycle, Start, etc. Prepare sepa- ating time for the corresponding
rate load requirement data for mode. Strike out “(min)” or
each mede of operation. “ (SSC)” se applicaMe. Under “Spe-

14

L—. .. —.! -.
. . .
Downloaded from http://www.everyspec.com

,. .-— ——-—. .. _
-. --—.. ,.,

MLS7D-704
6 October
19S9

died” write the specified time for recordof currentveranstime


the mode of operation being re- characteristics
shall
bepresented
ported. es supplementary data These
data are not a reqnkmant for
(e) If the operation is cyclk deecrii
loads rated lees than 600 va or 20
the cycle under “Note.”
amperes dc.
(f)
. . The rower reouirementa shall be
(k) Description of any internal electri-
rnekeured in ~line-tmieutral basis
cal protective devices shall be
with the reference voltage aad
listed under “REMARKS.”
fmquoncy applied to the termi-
rude of the equipment and entwed (1) information may be included under
in the appropriate spaces. A-e “REMARKS” regarding Subehlll.
measurements shall be efTective tird improvement of utilisation
values (rme), with an aeeuracy of equipment performance, reltabd-
at least 1 percent. D-e meaeur+ ity, weight. ~d ske beyond apeei-
ments should be accurate to 8A tication requirements by main-
of 1 percent. The angle entered taining charackistica different
under ~ shrdl be the angle b+ then specified herein under s-
tween the corresponding line cur- tion 5. If possible, the degrees of
rent and the line A to neutrrd improvement corresponding to
voltage. changes of the given character-
istics should bo listed. Note under
(d When the current lags, the voltage, “REMARKS” sny unusual or uni-
vars and PF shall be entered que power conditions, data, or
without sign; when the current is limits which will aeeist the appli-
leading, these items &l] ho boxed cations engineer in determining
es indicated in the following ex- the proper application of the
ample: ~ equipment. Information, when
(h) All power requimmenta entries known, shonld be inclndod to indi-
ebaU be the steady+tate demand cate maximum or minimnm (or
for the mode of operation rep=mt- botb) power source impedance
ed. If unusual changes in power limitations for satisfactory equip-
denmnd occur during a givem ment operation.
mode of operation, description of
the conditions and demende shall 7. NOTES
be made under “REMARKS.”
(i) Power requirements for utilization 7.1 Normal electrtwyatem operation, Nor-
equipment whose application will mal operation of the electric system are alt
determine the input pewer shall functional electrksyeteln operations requtr-
be baaed on full-load (nameplate) ed for airersft operation, eireraft mission
rating. Conditions of loading ver- ,and electric-system controlled continuity.
eus power demand shall be ex- These operations eecur at any given imtant
plained under “REMARKS.” Pow- and any number of times during tlight prep.
er reqnimmente for intermittent eretion, takeoff, airkorne eonditione, landing, ,
dnty equipment shall have the and CUChOri~. ExamPle9 Of SUCb OPWStiOllS
reted duty cycle deacriied under are ewitcbing of utilisation equipment load%
‘%EMARKS.”
~tif ~ ch~gee, bus A- and ayn-
(j) If the equipment has trsnsient pow- &mmzation, and pamlleEmgof electric power
er requirements, an oecillographic sources.

15
.r -—-

.---”” “—-—““‘—
.
Downloaded from http://www.everyspec.com —.

-. ———- ..-— ------- —. -._—

MIL-STLL704
6 October1959
SECURPTY CLASSIFICATION
ELECTRIC POWER REQUIREMENTS FOR AIRCRAFT EQUIPMENT:
SHEET OF
EQUIPMENT CATEGORY (WA”) (“B$)) (’tC”)

5 SECOND NAX POWER REQUIREMENTS FOR ( ) MoDE (S) OF OPERATION

2*F ‘%=, %2E 2


REMARKS: Inrushtransient
showncm supplementary
datasheet
No.

1 MINUTE MAX POWER REQUIREMENTS FOR ( ) MODE(S) OF OPERATION

3’EE =+==%%
REMARKS : Inrushtransient
shownon suppkunentav
datasheet
No,

:,15 MINUTE POWER REQUIREMENTS FOR ( ) MODE(S) OF OPERATION

lF-’#-E+=E G :
REMARKS : Inrush
transient
shownon supplementary
datasheet
No.

MANUFACTURED UNDER SPECS :


Deviations
Affecting
PowerData Authorized by I Refermce

; I
s.
SOURCE OF 1NFORMATION
Unlessotherwise
stated
herein,
thisequipment
conforms
totherequirements
ofMIL-STD-704.

SIGNED : _

DATE :

COMPANY:
(Army) (BuAer) (AirForce)
APPROVED : DATE :

FIGURE9. .%mpk form for 8ubmitW of powerrequirementsdata

16.
——.. —--—


., —-—— -. ..—_. ._
Downloaded from http://www.everyspec.com

..—. .—
.

MIL-S7D-704
6 October 19S9

7.2 Abnormat eketrfc - system operation.


Abnormal operation of the electric system is
the unexpected but momentary loss of con- where: V.= Variable transient voltage
trol of the electric system. The initiating
se a fnnetion of time,
action of the abnormal Operetiori is uncon-
t.= Total tbne being considered
trolled aud the exact moment of its occur-
on a continuous bssta,
rence is not anticipated. However, recovery
from this operation is a controlled action. V.= Voltage at ~ which pro-
Tl!is operation occurs perhaps once during a vides an equivalent step
, flight ores a result of battle damage or it function of the transient
: may never occur during tbe life of an air- from zero to t.,
~ craft. Ari example of an abnormal operation T.= Time at a value of V. being
! is the faulting of electric power to the struc- considered wti]ch provides
~ ture of an aircraft and its subsequent clear- an. equ@lent stip fmw
: ing by fau!t protective devices. tion of the previous part
of the transient.
7.3 Emergency electric - system operation. AT= Arbitrary tibne increments
~ Emergency operationisdefinedas thatcon- used to convert the tran-
: ditionof the electric system during flight sient to a step function
i when the primary electric system becomes loci,
; unableto supplysufficient or properelectric V,= Voltage at the start of the
power, thus requiring the use of a limited A t increment.
independent alternate source of power. V,= Voltage at the end of the
A t increment.
7.4 Reference voltage. For the messuw
Zem time is the start of the transient end
ment of input power and calibration of utili-
is considered to be the point in tbne when
sation equipment. the following reference
V. initially changes from one Wr unit. For
voltages shall he used:
all transients occurring in the normal mode
(a) 115 volts line-to-neutral for the of ekctric-system operation, the peak voltage
115/20C-vOlt a-c system. or minimum voltage is reached very rapidfy.
(b) 28 volts lin~twgrcmnd for the 28- Evaluation of these traAerda should reflect
Volt d-e SYStelll. the minimum or maximum readwd by con-
sidering the transient starting at the maxi.
7.5 Reference frequency. For the meas- mum or minimum voltage fmm time cam
urement of input pewer and calibration of (start of transient) until its coinr %nce of
utilisation equipment, the reference fre- the actual transient. !tle coincidence is shown
quency of 400 cps shell be used. as point A in figure 10. Figure 10 is a sample
coiwersion of an overvoltage transient to ite
7.6 Conversion of a transient to its evsJu- evaluated step function loci
ated step function leei. On a basis of con-
verting a complex voltage transient (V.) 7.6.1 Fanft trenefenta. The conversion of
into a function of ite reasonable equivalent a fault transient to its step function led
rms on a continuous basis (f V. (~) = V.), should be made on a continuous basii from
the basic formulae used for the conversion time zero (initial time at start of the tran-
are: eient). Conformance to the reqairament shall
be indicated by the step function loci of the
fault transient r emaining @thin the Iirnita
for ahnormrd mode of electric-system oPsrs-
tion of 6gures 2 end 6. Additionally, confonn-

17
~-.
—-——- - ‘-

.
..—..—
_—. — ---
,.
..— — .—.
MIL-STD-704
6 Octobw 1959
Downloaded from http://www.everyspec.com

G’
SL-IOASWM
..?
-—
.,.-, .\., _-. .. . .. --
Downloaded from http://www.everyspec.com
.- .—
‘:. “>
. - —— ._ .. .._.,, _ . ... . . . . . ._

MIL-STD-704
6 O@eber 1959

ITEM
L MIL-S~704 POWER REQUIRED (AC) ~
2 MILS~704 POWER REQUIRED (DC)
S. O~ER TYPE POWER REQUIRED
4. CATEGORY’IA*EQUIPllENT
& CATEGORY”B” EQUIPMENT
S. CATEGOItY llC”
EQUIPMENT
7. DURING NORMAL 0PER4TION, REGIONS AND DEGREES OF
DEGRADED PIilRFORMANCE ARE PERMITTED
8. DURING ASNORMAL OPERATION, REGIONS AND DEGREE6 OF
PERFORBL4NCE ARE REQUIRED
9. MANUAL RESET 1S PERMITTED AFTER ABNORMAL OPERATION
10.FULL EQUIPMENT PERFORMANCE IS REQUIRED FOR TEE
FOLLOWING AIRCRAFT OPERATING CONDT?IONS:
START AND WAIUdUP
TAKEoFF AND CLIm
CRUISE AND CRUISE-COMBAT
LANDING
EMERGENCY
11.EQUIPMENT PERFORMANCE IS RBQUIRED WITB LOSS OF
FOWERFROMONE PHASE
w

NOTES : .

FImnm 11. Skmdani DIIL-STD-704


mu Afirotien
.Ad&M8t

snce shoti,d be obtained in that the actual checkoff listiltuetrated in tlgure 11 to specifp
fa~t volta~e should not exceed the minimum considerations applicable to tbie %ndard.
or msxim@n step function voltages specified The notee detail the qualifying especta for
in f@res 2 and 6. each item.

7.7 Line drop compensation. Upon specific 7.9 Assumptions.


approval from the procuring activity, the
categories “A” and “B” utilization equip 7.9.1 SmaileatVAmamlelectric euetem. The
ment may incorporate means to compensate
for line drop.Itispreferred that the means 50 sm~ dc
consist of taps brought out to the input pow-
er connection for selection at time of instal- 7.9.S Ekctric-euetem bahce. Balance m
lation. the cketric system is withii 15 percent i.~,
no linen are loaded so that the maximum va
7.8 Equipment detail epeeikttion. The ditYerentislbetween linca is more then 15 per.
equipment detail specification may use the cent of ~ the %phase vs capacity.

19
___—
Downloaded from http://www.everyspec.com —.
.


--- —–

MIL-STD-704
6 OdOber19s9

7.9.3 Gen@ating+@em duznwteridiea. NO 7.9.8 Power-s@era rating. Power SJL9b15


generating-ayatem considered
Chars&m “ tic is will be rated from discreet capaeitks such as
unless it is usual and normal for the genemt- 1.5, 2.5, 10, 20, 30, 40, 60, 90, and 120 kva ac
ing system to be tied to the bus at tbe time and 50, 100, 200, 300, and 400 sm~ dc.
the charackriatic becomes evident.
Notiea When Government drarvin~specifications,
7.9.4 Efectrk-s@em ckmw%riaticg. Char- orotherdataareussdforanYPurpcwotherthanin
acteristicscoveredin thisstandmd are based connection witha definitely related Government Pr-
ocurement .operatkm, theUnikd StatesGovernment
on the eleetric+yatem power source being:
thereby incurs no responsibility nor any obligation
Hydraulic (constant speed drhe) what-sower; andtbefactthattbeGovernment may
haveformulated, furniabcd, or inany way supplkd
Air turbine (constant speed drive) thesaiddrawings, specifications, orotherdataisnot
Mechanical (constant apeed drive) b bercgardsd by implication orotherwise asinanY
Turboprop mannerlicensing theholder or any otherpersonor
corporation, or conveying any rights or p+rmimion
Inverters timanufacture, use,or sell any patented invention
Transformer-rectifiers thatmay inanyway berelated thereto.
Batteries supported by generatore Copiesof.mecidsntions, stnndanls, drawings, and
publications reqnircd by contractors in connection
withspecific procurement functiomshouldbe o!+
7.9.5 Normal loading. Normal leading of an tained fromthepremriagactivity orssdir.cctcd by
electric system is between 15 percent and 35 thecontracting officer.
-t of the power-web capasity and will Copicaofthisstandard formilitary usemay be
be 30 to 85 percent for cruise-combat con- ohtafned as indicated in tbeforeword to@e Index
ditions. of Military Specifications and Standards. .:
Copies ofthisstandard may bsobtained forother
7.9.6 Inittid wwfmup. Initial warmup (first thanofficial useby individuals, firms, and CO?ItrSC-
tors fmm the Superintendent of Documen+,U. S.
5 minutes) is not inclusive with takeeff, clii, GovernmentPrinting Df?ice,Washingtons5,D. C.
cruise-combat, and landing aircraft opera-
tions. Preparing
SA.ity:
Nmv—B-m ofAuvmmItim
7.9.7 System power factor. System power Othercustodians
:
factor during cruise, and crniee-eembet air- Army-Trammortatic.n
Gxps
craft operations will be more than S5 perwnt. AirForce

,., ~
20 “’”-
- 0,..,s..6-,

\
,- !,—.

You might also like