Professional Documents
Culture Documents
The nominal discharge current rating of the lightning arresters shall be 5 KA.
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 1/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
The following routine and type tests as laid down in IS : 3070 (Part-I) shall be carried out.
Routine Test: Dry Power frequency spark over test.
Type Tests (Confirmation) :
The distribution fuse cutouts shall be outdoor, open, drop-out expulsion type fuse cutouts suitable
for installation in 50 Hz, 11 KV distribution system.
The rated voltage shall be 12 KV.
The rated current shall be 100 A.
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 2/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
The cutouts shall be of single vent type (downward) having a front connected fuse carrier suitable for
angle mounting.
All ferrous parts shall be hot dip galvanized in accordance with the latest version of IS : 2632. Nuts
and bolts shall conform to IS : 1364. Spring washers shall be electro-galvanized.
The top current carrying parts shall be made of a highly conductive copper alloy and the contact
portion shall be silver plated for corrosion resistance and efficient current flow.
The contact shall have a socket cavity for latching and holding firmly the fuse carrier until the fault
interruption is completed within the fuse.
The top assembly shall have an aluminum alloy terminal connector. The top assembly shall be robust
enough to absorb bulk of the forces during the fuse carrier closing and opening operations and shall
not over-stress the spring contact. It shall also prohibit accidental opening of the fuse carrier due to
vibrations or impact.
The conducting parts shall be made of high strength highly conductive copper alloy and the contact
portion shall be silver plated for corrosion resistance and shall provide a low resistance current path
from the bo om fuse carrier contacts to the bo om terminal connector.
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 3/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
The fuse carrier top contact shall have a solid replaceable cap made from highly conductive,
anticorrosive copper alloy and the contact portion shall be silver plated to provide a low resistance
current path from the Fuse Base Top Contact to the Fuse Link.
It shall make a firm contact with the bu on head of the fuse link and shall provide a protective
enclosure to the fuse link to check spreading of arc during fault interruptions.
The fuse carrier shall be provided with a cast bronze opening eye (pull ring) suitable for operation
with a hook stick from the ground level to pull-out or close-in the fuse carrier by manual operation.
The fuse carrier bo om assembly shall be made of bronze castings with silver plating at the contact
points to efficiently transfer current to fuse base.
It shall make smooth contact with the fuse base bo om assembly during closing operation. The
bo om assembly shall have a lifting eye for the hook stick for removing or replacing the fuse carrier.
The fuse base shall be a bird-proof, single unit porcelain insulator with a creepage distance (to earth)
not less than 320 mm. The top and bo om assemblies as also the middle clamping hardware shall be
either embedded in the porcelain insulator with sulphur cement or suitably clamped in position.
For embedded components, the pull out strength should be such as to result in breaking of the
porcelain before pull out occurs in a test. For porcelain insulators, the beam strength shall not be less
than 1000 kg.
Fuse Tube:
The fuse tube shall be made of fiber glass coated with ultraviolet inhibitor on the outer surface and
having arc quenching bone fire liner inside.
The tube shall have high bursting strength to sustain high pressure of the gases during fault
interruption.
The inside diameter of the fuse tube shall be 17.5 mm. The solid cap of the fuse carrier shall clamp the
bu on head of the fuse link, closing the top end of the fuse and allowing only the downward venting
during fault interruption.
Dielectric tests
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 4/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
The cutouts shall be provided with a suitable arrangement for mounting these on 74 X 40 mm or 100
X 50 mm channel cross arm in such a way that the center line of the base is at an angle of 15 to 20 deg
from the vertical and shall provide the necessary clearances from the support.
Mounting arrangement shall be made of high strength galvanized steel flat and shall be robust
enough to sustain the various stresses encountered during all operating conditions of the cutout.
The porcelain shall be sound, free form defects, through verified and smoothly glazed. Unless
otherwise specified, the glaze shall be brown color.
The glaze shall cover all the porcelain parts of insulators except those areas which serve as support
during firing are left unglazed for the purpose of assembly.
The design of insulators shall be such that stresses due to expansion and contraction in any part of
the insulator shall not lead to deterioration.
The porcelain shall not engage directly with hard metal. Cement used in construction of insulators
shall not cause fracture by expansion or loosening by contraction and proper care shall be taken to
locate the individual parts correctly during cementing.
The cement shall not give rise to chemical reaction with metal fi ings and its thickness shall be as
uniform as possible.
The insulators should preferably be manufactured in automatic temperature controlled kilns to
obtain uniform baking for be er electrical and mechanical properties.
Both pin and strain insulators shall conform to Type B of IS : 731. The strain insulators shall be of
Tongue and Clevis type.
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 5/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
Mechanical Failing Load (For Pin Insulators only) : The insulators shall be suitable for a minimum
failing load of 10 KN applied in transverse director.
Electro-Mechanical Failing Load (For Strain Insulators) : The insulators shall be suitable for a
minimum failing load of 70 KN applied axially.
1. Visual examination
2. Verification of dimensions
3. Visible discharge test
4. Impulse Voltage withstand Test
5. Wet Power Frequency Voltage withstand Test
6. Temperature Cycle Test
7. Mechanical Failing Load Test
8. 24 hour Mechanical Strength Test for Strain Insulators
9. Puncture Test
10. Porosity Test
11. Galvanizing Test
12. Electro-Mechanical Failing Load Test
1. Virtual examination
2. Mechanical routine test
3. Electrical routine test
1. Verification of Dimensions
2. Temperature Cycle Test
3. Electro-Mechanical Failing Load Test
4. Puncture Test
5. Porosity Test
6. Galvanizing Test
Pin Insulators:
The pins shall of single piece obtained preferably by the process of forging.
They shall not be made by joining, welding, shrink fi ing or any other process using more than one
piece material. The pins shall be of good finish, free from flaws and other defects.
The finish of the collar shall be such that sharp angle between the collar and the shank is avoided.
Aluminum ferrous pins, nuts and washers, except those made of stainless steel, shall be galvanized.
The threads of nuts and taped hole when cut after galvanizing shall be well oiled or greased.
Pins shall be of small steel head type S 165 P as per IS : 2486 (Part-II) having stalk length of 165 mm
and shank length of 150 mm with minimum failing load of 10 KN.
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 7/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
Mechanical test
Visual examination test
Helically formed ties used for holding the conductor on the pin insulator shall be made of aluminum
alloy or aluminized steel or aluminum clad steel wires and shall conform to the requirements of IS :
12048. The ties shall be suitable for pin insulator dimensions of Pt.- I and conductor sizes specified.
Elastomer pad for insulator shall be used with the ties to avoid abrasion of the conductor coming into
direct contact with the insulator.
Aluminum alloy die cast thimble-clevis for a aching to the tongue of strain, insulator on one end and
for accommodating the loop of the helically formed dead-end fi ing at the other end in its smooth
internal contour.
The thimble shall be suitable for all sizes of ACSR conductors as specified. The thimble clevis shall
be a ached to the insulator by a steel cu ing pin used with a non-ferrous split pin of brass or
stainless steel.
The thimble shall have clevis dimensions as per IS: 2486 (Pt – II).
Helically formed dead end grip having a prefabricated loop to fit into the grooved contour of the
thimble on one end and for application over the conductor at the other end.
The formed fi ing shall conform to the requirement of IS : 12048.
Tests
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 8/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
The helically formed fi ings for strain insulators shall be subjected to tests as per IS : 12048.
The other hardware fi ings shall be tested as per IS: 2486 (Part-I).
Note: As the helically formed fi ings are made to suit specific sizes of conductors, the purchase
should clearly specify the number of fi ings required for each size of conductor
Fi ings for strain insulators with conventional dead-end clamps for use with tongue & clevis or ball
& socket type insulators shall consist of the following components :
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 9/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
The porcelain insulator shall be sound, free from defects, thoroughly verified and smoothly glazed.
The design of the insulator shall be such that the stresses to expansion and contraction in any part of
the insulator shall not lead to its deterioration.
The glaze, unless otherwise specified, shall be brown in color.
The glaze shall cover the entire porcelain surface parts except those areas that serve as supports
during firing.
The standard guy strain insulators shall be designations ‘A’ and ‘C’ as per IS: 5300.
The recommended type of guy strain insulators for use on guy wires of overhead lines of different
voltage levels are as follows:
Power Line Voltage :11KV
Designation of Insulators: C
Dry one minute Power Frequency withstand Voltage: 27 KV (rms)
Wet one minute Power Frequency withstand Voltage: 13 KV (rms)
Minimum Failing Load: 88(KN)
1. Visual examination
2. Verification of dimensions
3. Temperature cycle test
4. Dry one-minute power frequency voltage withstand test
5. Wet one-minute power frequency voltage withstand test
6. Mechanical strength test
7. Porosity test
8. Acceptance Tests : (to be conducted in the following order)
9. Verification of dimensions
10. Temperature cycle test
11. Mechanical strength test
12. Porosity test
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 10/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
The standard guy strain insulators shall be of designations ‘A‘ and ‘C‘ as per IS:5300.
The recommended type of guy strain insulators for use on guy wires of overhead lines of different
voltage levels are as follows :
The insulators shall be suitable for the minimum failing loads specified as under:
1. Visual examination
2. Verification of dimensions
3. Temperature cycle test
4. Dry one-minute power-frequency voltage withstand test
5. Wet one-minute power frequency voltage withstand test
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 11/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
1. Verification of dimensions
2. Temperature cycle test
3. Mechanical strength test
4. Porosity test
As per provisions of IE Rules 1956, Danger Notice Plates in Hindi or English and, in addition, in the
local language with the sign of skull and bones are required to be provided on power line supports
and other installations.
It is further stipulated in the I.E. Rules that such Notice Plates are not required to be provided on
supports like PCC, tubular, wood, steel rails, etc. which cannot be climbed easily without the aid of
ladder or special appliances.
To adopt a uniform pa ern and for helping easy procurement, a specification on Danger Notice
Plates has been drawn up.
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 12/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
All le erings shall be centrally spaced. The dimensions of the le ers, figures and their respective
position shall be as shown in figs.
The size of le ers in the words in each language and spacing between them shall be so chosen that
these are uniformly wri en in the space earmarked for them.
Under Rule No. 35 of Indian Electricity Rules, 1956, the owner of every medium, high and extra high
voltage installation is required to affix permanently in a conspicuous position a danger notice in
Hindi or English and, in addition, in the local language, with the sign of skull and bones.
The type and size of le ering to be done in Hindi is indicated in the specimen danger notice plates
shown in Fig. 2 and 4 and those in English are shown in Figs.
Adequate space has been provided in the specimen danger notice plates for having the le erings in
local language for the equivalent of’ Danger’,’ 415′ ‘11000’ and ‘Volts’.
The plate shall be made from mild steel sheet of at least 1.6mm thick and vitreous enameled white,
with le ers, figures and the conventional skull and cross-bones in signal red color (refer IS:5-1978) on
the front side. The rear side of the plate shall also be enameled.
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 13/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 14/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
No two joints shall occur in the aluminums wires closer together than 15 meters.
No joints shall be permi ed in steel wires used for ACSR of Sizes 20mm2 aluminums area
(7/2.11mm), 30mm2 aluminums area (7/2.59mm), 50mm2 aluminums area (7/3.35mm) and 80mm2
aluminums area (7/4.09 mm).
In the case of ACSR of 100mm2 aluminums area (6/4.72mm + 7/1.57 mm) having seven galvanized
steel wires, joints, in individual wires shall be permi ed but no two such joints shall be less than 15
meters apart in the complete steel core.
The samples of individual wires for the tests shall normally be taken before stranding. The
manufacturer shall carry out test on samples taken out at least from 10% of aluminums wire spools
and 10% of steel wire coils. However, when desired by the purchaser, the test sample may be taken
from the stranded wires.
The wires used for all aluminums conductors shall comply with the following tests as per
IS:398(Pt.I)-1976.
The wires used for aluminums conductors, steel reinforced shall comply with the following tests as
per IS:398
3. Wrapping test
4. Resistance test
5. Galvanizing test
The gross mass for various conductors shall not exceed by more than 10% of the values given in the
following
(1) AAC
(2)ACSR
1. AAC
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 16/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
1. ACSR
1. Manufacturers’ name
2. Trade mark, if any
3. Drum or identification number
4. Size of conductor
5. Number and lengths of conductor
6. Gross mass of the package
7. Net mass of conductor
8. I.S.I certification mark, if any
A research project for evolving economical designs of cement concrete poles for use on 11 KV and LT
Lines was entrusted to the Cement Research Institute (CRI) of India.
The basic design parameters for these poles as given in Clause 6 of this Specification were approved
by the Fifth Conference on standardization of Specifications and Construction Practices in Rural
Electrification held in May, 1974.
Some of these design parameters which were based on certain foreign codes/practices and certain
other provisions of this Specification, although at variance with the stipulations of IS:1678 – 1960, had
been adopted to achieve economy in the designs. However, these modifications have since been
incorporated in the revised IS:1678 – 1978.
This Specification covers PCC poles with an overall length of 7.5 M, 8.0 M and 9.0 M suitable for use
in overhead 11 KV and L.T. power lines and double pole structures for 11/0.4 KV substations.
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 17/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
IS: 1678-1978, Specification for pre stressed concrete poles for overhead power, traction and
telecommunication lines.
IS: 2905-1966. Methods of test for concrete poles for over-head power and telecommunication lines.
IS: 7321-1974. Code of practice for selection, handling and erection of concrete poles for over-head
power and telecommunication lines.
That fraction of the working load which may be considered of long duration over a period of one
year.
The ratio of ultimate transverse load to the transverse load at first crack.
The direction of the line bisecting the angle contained by the conductor at the pole. In the case of a
straight run, this will be normal to the run of the line.
For design, the transverse load at first crack shall be taken as not less than the value of the working
load.
The maximum load in the transverse direction, that is ever likely to occur, including the wind
pressure on the pole.
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 18/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
This load is assumed to act at a point 600 mm below the top with the bu end of the pole planted to
the required depth as intended in the design.
The conditions existing when the pole ceases to sustain a load increment owing to either crushing of
concrete, or snapping of the pre stressing tend on or permanent stretching of the steel in any part of
the pole.
The load at which failure occurs, when it is applied at a point 600 mm below the top and
perpendicular to the axis of the pole along the transverse direction with the bu end of the pole
planted to the required depth as intended in the design.
These poles shall be used at tangent locations for 11KV and L.T. lines in wind pressure zones of 50
kg/M2, 75 Kg/M2 and 100 Kg/M2 in accordance with REC Construction Standards referred to in the
following:
Pole length: 8M
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 19/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
9.0 M Poles
These poles shall be used for double pole structures of distribution transformer centers as per REC
Construction Standards F-1 to F-4 and for special locations in 11 KV and L.T. Lines, such as road
crossings etc.
(1) Cement
The cement used in the manufacture of pre stressed concrete poles shall be ordinary or rapid
hardening port land cement conforming to IS: 269 – 1976 (Specification for ordinary and low heat
port land cement) or IS: 8041 E-1978 (Specification for rapid hardening port land cement).
(2) Aggregates
Aggregates used for the manufacture of pre-stressed concrete poles shall conform to IS : 383 – 1970
(Specification for coarse and fine aggregates from natural sources for concrete). The nominal
maximum size of aggregates shall in no case exceed 12mm.
(3) Water
Water should be free from chlorides, sulphates, other salts and organic ma er. Potable water will be
generally suitable.
(4) Admixtures
Admixtures should not contain Calcium Chloride or other chlorides and salts which are likely to
promote corrosion of pre-stressing steel.
The pre-stressing steel wires, including those used as un tensioned wires should conform to IS : 1785
(Part-I) – 1966 (Specification for plain hard drawn steel wire for pre stressed concrete. Part-I cold
drawn stress relieved wire), IS: 1785 (Part-II) – 1967 (Specification for plain hard-drawn steel wire).,
or IS : 6003 – 1970 (Specification for indented wire for pre-stressed concrete).
The type designs given in Annexure-I are for plain wires of 4 mm diameter with a guaranteed
ultimate strength of 175 Kg/mm2.
Itshall be designed to the requirements laid down for controlled concrete (also called design mix
concrete) in IS : 1343 – 1980 (Code of practice for pre stressed concrete) and IS : 456 – 1978 (Code of
practice for plain and reinforced concrete), subject to the following special conditions;
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 20/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
The poles shall be planted directly in the ground with a planting depth of 1.5 meters.
The working load on the poles should correspond to those that are likely to come on the pole during
their service life. Designs given in Annexure-I are for 140 Kg. and 200 Kg. Applied at 0.6 M from top.
The factor of safety for all these poles shall not be less than 2.5.
The average permanent load should be 40% of the working load.
The F.O.S. against first crack load shall be 1.0.
At average permanent load, permissible tensile stress in concrete shall be 30 Kg/cm2.
At the design value of first crack load, the modulus of rupture shall not exceed 55.2 kg/cm2 for M-420
concrete.
The ultimate moment capacity in the longitudinal direction should be at least one fourth of that in
the transverse direction.
The maximum compressive stress in concrete at the time of transfer of pre stress should not exceed
0.8 times the cube strength.
The concrete strength at transfer shall not be less than half the 28 days strength ensured in the design,
i.e. 420 x 0.5= 210 Kg/cm2.
For model check calculations on the design of poles, referred to in Annexure-I, a reference may be
made to the REC “Manual on Manufacturing of solid PCC
The cross-sectional dimensions and the details of pre stressing wire should conform to the particulars
given in Annexure-I.
The provisions of holes for fixing cross-arms and other fixtures should conform to the REC standards
referred to in clause 4 of this specification and in accordance with the construction practices adopted
by the State Electricity Boards.
All pre stressing wires and reinforcements shall be accurately fixed as shown in the drawings and
maintained in position during manufacture. The un tensioned reinforcement, as indicated in the
drawings, should be held in position by the use of stirrups which should go round all the wires.
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 21/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
All wires shall be accurately stretched with uniform pre stress in each wire.
Each wire or group of wires shall be anchored positively during casting. Care shall be taken to see
that the anchorages do not yield before the concrete a ains the necessary strength.
The cover of concrete measured from the outside of the pre stressing tendon shall be normally 20
mm.
The high tensile steel wire shall be continuous over the entire length of the tendon.
Welding shall not be allowed in any case. However, jointing or coupling may be permi ed provided
the strength of the joint or coupling is not less than the strength of each individual wire.
Concrete shall be compacted by spinning, vibrating, shocking or other suitable mechanical means.
Hand compaction shall not be permi ed.
The concrete shall be covered with a layer of sacking, canvas, hessian or similar absorbent material
and kept constantly wet up to the time when the strength of concrete is at least equal to the minimum
strength of concrete at transfer of pre stress. Thereafter, the pole may be removed from the mould
and watered at intervals to prevent surface cracking of the unit, the interval should depend on the
atmospheric humidity and temperature.
Itshall be de tensioned only after the concrete has a ained the specified strength at transfer (i.e. 210
Kg/cm2). The cubes cast for the purpose of determining the strength at transfer should be cured, as
far as possible, under conditions similar to those under which the poles are cured.
The transfer stage shall be determined based on the daily tests carried out on concrete cubes till the
specified strength indicated above is reached. Thereafter the test on concrete shall be carried out as
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 22/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
detailed in IS: 1343 – 1960 (Code of practice for pre stressed concrete).
The manufacturer shall supply when required by the purchaser or his representative, result of
compressive test conducted in accordance with IS : 456 -1964 (Code of practice for plain and
reinforced concrete) on concrete cubes made from the concrete used for the poles.
If the purchaser so desires, the manufacturer shall supply cubes for test purposes and such cubes
shall be tested in accordance with IS: 456 – 1964 (Code of practice for plain and reinforced concrete).
The de tensioning shall be done by slowly releasing the wires, without imparting shock or sudden
load to the poles. The rate of de tensioning may be controlled by any suitable means either
mechanical (screw type) or hydraulic.
The poles shall not be de tensioned or released by cu ing the pre stressing wires using flames or bar
croppers while the wires are still under tension.
It shall be provided for handling and transport, one each at a distance of 0.15 times the overall length,
from either end of the pole.
Eye-hooks, if provided, should be properly anchored and should be on the face that has the shorter
dimension of the cross-section. Holes, if provided for lifting purposes, should be perpendicular to the
broad face of the pole.
Stacking should be done in such a manner that the broad side of the pole is vertical. Each tier in the
stack should be supported on timber sleepers located at 0.15 times the overall length, measured from
the end. The timber supports in the stack should be aligned in a vertical line.
Poles should be transported with their broad faces placed vertically and in such a manner that shocks
are avoided. Supports should be so arranged that they are located approx. at a distance equal to 0.15
times the overall length from the ends.
The erection of the pole should be carried out in such a way that the erection loads are applied so as
to cause moment with respect to the major axis. i.e. the rope used for hoisting the pole should be
parallel to the broader face of the pole.
Poles made from ordinary Portland cement shall be tested only on the completion of 28 days and
poles made from rapid-hardening cement only on the completion of 14 days, after the day of
manufacture.
The pole may be tested in either horizontal or vertical position. If tested in horizontal position,
provisions shall be made to compensate for the overhanging weight of the pole, for this purpose the
over-hanging portion of the pole may be supported on a movable trolley or similar device.
The pole shall be rigidly supported at the bu end for a distance equal to the agreed depth of
planting i.e. 1.5 M.
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 23/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
Load shall be applied at a point 600 mm from the top of the pole and shall be steadily and gradually
increased to design value of the transverse load at first crack. The deflection at this load shall be
measured.
A pre stressed concrete pole shall be deemed not to have passed the test if visible cracks appear at a
stage prior to the application of the design transverse load for the first crack.
The load shall then be reduced to zero and increased gradually to a load equal to the first crack load
plus 10% of the minimum ultimate transverse load, and held up for 2 minutes.
This procedure shall be repeated until the load reaches the value of 80 per cent of the minimum
ultimate transverse load and thereafter increased by 5 per cent of the minimum ultimate transverse
load until failure occurs. Each time the load is applied, it shall be held for 2 minutes.
The load applied to pre stressed concrete pole at the point of failure shall be measured to the nearest
five Kilograms.
The pole shall be deemed not to have passed the test if the observed ultimate transverse load is less
than the design ultimate transverse load.
After completion of the transverse strength test, the sample pole shall be taken and checked for cover.
The cover of the pole shall be measured at 3 points, one within 1.8 meters from the bu end of the
pole, the second within 0.6 meter from the top and the third at an intermediate point and the mean
value compared with the specified value.
The mean value of the measured cover should not differ by more than(±)1 mm from the specified
cover. The individual values should not differ by more than (±) 3 mm from specified value.
If these requirements are not met, the workmanship with reference to aligning of the end plates and
pre stressing wires and assembly of moulds should be improved and inspection at pre-production
stage tightened suitably.
The pole shall be clearly and indelibly marked with the following particulars either during or after
manufacture but before testing at a position so as to be easily read after erection in position.
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 24/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
Overhead lines:
The general precautions during storage and handling of shall be taken in accordance with relevant IS
code.
While laying the conductor shall betaken from top of the drum and the repeated in the direction of
arrow on it.. Care shall be taken to avoid contact with steel works, fence, etc by giving soft wood
protection, using wooden rollers.
Proper tools shall be used during stringing work. During stringing operation standard sag table or
chart shall be followed and care shall be taken to ensure that there are no kinks in the conductor.
Joints in conductors shall be staggered. Mid span joints in conductors shall be avoided.
After stringing the conductor, it shall be clamped permanently with shackle or strain clamps. An
angle or section shall be selected while pulling up conductors.
Jumpers:
While stringing, sufficient length shall of conductors be kept at shackle terminations for making
jumpers. Jumpers shall be neat and as far as possible symmetrical to run of conductors. These shall
be made to prevent occurrence of faults due to wind or birds. PG clamps may be preferred to binding
of conductors at jumper location or service taps.
Cross Arms :
The cross arms shall be made of MS Structural steel. The length of cross arms shall be suitable for
accommodating the number of insulators on them with spacing of conductor. A gap of minimum 50
mm shall be left from the center of pin hole to end of cross arm on either side. The cross arm shall be
complete with pole clamp made of MS flat of size not less than 50 x 6 mm with necessary nuts, bolts,
washers, etc. The length of cross arm for carrying guard wires shall always run not less than 300 mm
beyond outer most bare conductor of configuration.
Cross arms shall be properly clamped to the support taking into consideration the orientation of
lines.
The porcelain insulators shall be confirming to IS 731 – 1971 for overhead lines. This shall be glazed,
crack / burr free.
The insulator shall have adequate mechanical strength, high degree of resistance to electrical
puncture and resistance to climatic and atmospheric a ack.
All iron parts shall be hot dip galvanized & all joints shall be airtight. Pin insulators / shackle
insulators / disc insulators shall be erected on cross arms and ‘D’ iron clamp shall be used or as
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 25/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
specified by Engineer-in-charge. Shackle insulators shall be used in conjunction with ‘D’ iron clamps
when configuration of conductor is vertical.
These shall also be erected on cross arm at intermediate support in case of long lines, deviation from
straight lines. Care shall be taken that insulators are not damaged during erection.
Binding material:
Binding of conductor with the insulator shall be done with soft aluminum wire / conductor. The
binding of conductor to insulator shall be sufficiently firm and tight to ensure that no intermi ent
contact develops. The end of binding wire shall be tightly twisted in close spaced spiral around the
conductor to ensure good electrical contact and strengthen the conductor.
Support of overhead line shall be of adequate strength confirming in all respects to rules 76 of Indian
electricity rules.
Pole spacing and clearance between lowest conductor above the ground level across / along the street
shall be in accordance with rule 85 of Indian electricity rules. Suitable foundation shall be provided
for erection of poles.
The foundation shall include excavation in all types of soil and rocks and back filling, RCC,
reinforcement, formwork.
Excavation for foundations for poles / stay / strut : After the location of supports / stay are pegged
accurately, the excavation work shall be taken up and care should be taken while excavating that pits
are not oversized.
The pit should be excavated in the direction of the line. The depth and size of pit shall be such that
normally 1/6th of the length of pole is buried in the ground and suitable for foundation of support.
For stay the position of pit shall normally be such stay makes as large an angle as possible with the
support and it shall be in the range of 40 to 60 degrees.
The length of stay rod shall project 450 mm above the ground level. The pit for strut shall be located
at a distance not less than 1.8M from the pole.
The depth of pit shall be such that at least 1.2M of the strut is buried in the ground.
Stay / strut:
Stay set shall consist of stay rod, anchor plate, bow tightened / turn buckle, thimbles, stay wire and
stain insulators.
The stay rod shall be with stay grip in case of turn buckle is used instead of bow tightened. The
entire stay set assembly shall be galvanized. The stay wire shall be either 7/4.0 mm diameter or 7/3.15
mm diameter GI having tensile strength of not less than 70 kgf/sq mm and confirming to IS 2141. T
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 26/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
The anchor plate shall be of MS galvanized and not less than 300 mm x 300 mm x 6.4 mm thick. The
stay rod / buckle rods shall be minimum 16/19 mm diameter galvanized steel rod having tensile
strength not less than 42 kgf/sq mm. Minimum length of stay rod and buckle shall be 1800 mm and
450 mm respectively.
The anchor plate shall be galvanized MS plate. The stay rod with anchor plate shall be embedded in
cement concrete 1:3:6. A stay shall be provided at all angle and terminal poles. Double stay shall be
provided at all dead ends and in such case, these shall be as far as possible to be set parallel to each
other.
Cage guard:
All metal supports of overhead lines and metallic fi ing a ached shall be permanently and
effectively earthed. Cage guard / cradle guard shall be made of 6 SWG GI wire confirming to IS 2633
including ne ing, stretching and jointing of cage and lacing by 10/12 SWG GI wire, binding by 14/16
SWG GI wire.
Danger boards:
All supports carrying HV lines shall be fi ed with danger plates confirming to IS 2551 at height of 3
M from ground indicating the voltage of line. The script shall be both in ‘English/Hindi’.
Necessary arrangement for preventing unauthorized persons from ascending any of the supports
and structure carrying HV lines without the aid of ladder or special appliance shall be made.
Unless otherwise specified barbed wire confirming to IS 278 having four points barbed spaced 75 +/-
12 mm apart shall be wrapped helically with a pitch of 75 mm around the limb of support and firmly
commencing from the height of 3.5 M and up to 5 or 6 M as directed by the engineer.
Lightning arrestor:
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 27/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
Lightning arrestor suitable for HT lines shall be installed one unit per phase at terminations,
transformer stations, etc.
The devices shall be connected ahead of fuse provided if any. Independent earth electrode shall be
provided for LA.
The earth lead from earth electrode to LA shall be continuous. The LA shall confirm to IS 3070 and
shall be non linear distribution class.
The LA shall be non-linear type, distribution class, outdoor type suitable for effectively earthed
system. The LA shall consist of line terminal stud, earth terminal stud, number of spark gaps in series
with non-linear resistor, the whole assembly housed inside a hermetically sealed porcelain bushing.
Neoprene rubber gasket shall be provided between metal caps and porcelain bushing. Non-linear
resistor shall be silicon carbide blocks metalized at both ends to ensure good electrical contact
between terminals, non-linear resistor & spark gaps.
Mounting bracket shall be hot dip galvanized suitable for mounting LA on structure.
The method shall be adopted where the cable route is through open country, along road / lanes, etc
and where no frequent excavations are encountered and re excavation is possible without affecting
other work.
Width of trenches:
The width of trench for laying single cable shall be 35 cm Where more than one cable are to be laid in
the same trench in horizontal formation, width of trench shall be increased such that the inter-axial
spacing between the cables for 415 volts shall be 20 cm and for 11 shall be 35 cm.
Depth of trenches:
Where cables are laid in single formation, the total depth of trench shall not be less than 75 cm for
cable up to 1.1 KV grade and shall not be less than 120 cm for cable above 1.1 KV grade. Wherever
more than one tier formation is unavoidable and vertical formation is adopted, the depth of trench
shall be increased by 30 cm for each additional tier to be formed.
Protective covering:
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 28/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
Cable laid in trenches shall have covering of clean dry sand not less than 170 mm above the base
cushion of sand before the protective cover is laid.
The cables shall be protected by B class/second class brick of not less than 20 cm x 10 cm x 10 cm or
protective cover placed on top of the sand and both sides of cable for full length of the cable to the
satisfaction of Engineer-in-charge.
Back filling:
The trenches shall be back filled wit excavated earth free from stones or other scrap edged debris and
shall be rammed and watered, if necessary, in successive layers not exceeding 300 mm unless
otherwise specified.
Route marker:
Route marker shall be provided along straight runs of cables and at points of change in direction as
approved by Engineer-in-charge and in general at intervals not exceeding 100 meters in straight run.
Route marker shall be made out of 100 mm x 100 mm x 5 mm GI/Al plate bolted or welded on 35 mm
x 35 mm x 6 mm MS angle iron of 600 mm long.
Such route markers shall be mounted and grouted parallel to and 0.5 meter away from the side of
trench. The work “cable” with voltage grading and size of cable shall be inscribed on the marker.
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 29/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
(h ps://electricalnotes.files.wordpress.com/2011/06/cross-arm.png)
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 30/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
(h ps://electricalnotes.files.wordpress.com/2011/06/1.png)
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 31/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
(h ps://electricalnotes.files.wordpress.com/2011/06/2.png)
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 32/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
(h ps://electricalnotes.files.wordpress.com/2011/06/3.png)
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 33/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
(h ps://electricalnotes.files.wordpress.com/2011/06/guy-strain.png)
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 34/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
(h ps://electricalnotes.files.wordpress.com/2011/06/guy-set.png)
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 35/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
(h ps://electricalnotes.files.wordpress.com/2011/06/crimped-tension.png)
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 36/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
(h ps://electricalnotes.files.wordpress.com/2011/06/strain-insulator.png)
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 37/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
(h ps://electricalnotes.files.wordpress.com/2011/06/pipe-earthing.png)
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 38/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
(h ps://electricalnotes.files.wordpress.com/2011/06/pin-ins.png)
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 39/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
(h ps://electricalnotes.files.wordpress.com/2011/06/insulator-pin.png)
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 40/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
(h ps://electricalnotes.files.wordpress.com/2011/06/danger-board.png)
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 41/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
(h ps://electricalnotes.files.wordpress.com/2011/06/danger-board-11kv.png)
About Jignesh.Parmar
Jignesh Parmar has completed M.Tech (Power System Control), B.E(Electrical). He is member of
Institution of Engineers (MIE) and CEng,India. Membership No:M-1473586.He has more than 16 years
experience in Transmission -Distribution-Electrical Energy theft detection-Electrical Maintenance-
Electrical Projects (Planning-Designing-Technical Review-coordination -Execution). He is Presently
associate with one of the leading business group as a Deputy Manager at Ahmedabad,India. He has
published numbers of Technical Articles in “Electrical Mirror”, “Electrical India”, “Lighting
India”,”Smart Energy”, “Industrial Electrix”(Australian Power Publications) Magazines. He is Freelancer
Programmer of Advance Excel and design useful Excel base Electrical Programs as per IS, NEC,
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 42/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
IEC,IEEE codes. He is Technical Blogger and Familiar with English, Hindi, Gujarati, French languages.
He wants to Share his experience & Knowledge and help technical enthusiasts to find suitable solutions
and updating themselves on various Engineering Topics.
Reply
Eng. Asad says:
March 25, 2013 at 8:36 am
Distance between tow poles of 20KV overhead line.
Reply
karthik says:
September 2, 2011 at 11:52 am
awesome sir.its highly useful for every electrical engineer
Reply
kenny james siame says:
September 19, 2011 at 9:41 pm
Hi, please send me the qoute for the DROP OUT FUSE LINK ASSEMBLY COMPLETE, 11KV.
Give me prices both FOB and CIF Zambia for 300 pieces.
I wait to hear from you.
i thank you in anticipation.
Regards
Kenny.
JSK Co LTD
Reply
Vinay Ghade says:
August 6, 2014 at 8:08 pm
Dear Sir ,
i m Vinay Ghade BE electrical engineer having around 7 years experience in designing field. i
want to go much deeper in this field. Any design course you offer or any books that is to be refer.
Reply
dillip kumar garnayak says:
September 14, 2014 at 6:49 pm
good
Reply
vikas says:
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 43/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
Reply
Jignesh.Parmar says:
October 6, 2011 at 10:39 am
Yes In both Horizontal congu. and for Vertical confug. 200mm for vertical confu.and 300mm for
horizontal confu for P-P
this is indicate in CPWD noms. Please read my Abstract notes. You will find it.
Reply
vikas says:
October 4, 2011 at 2:31 pm
Is there any IS or IE rule specifying the spacing between two conductors of 415 V overhead line.
Reply
Jignesh.Parmar says:
October 6, 2011 at 10:38 am
Yes In both Horizontal congu. and for Vertical confug. 200mm for vertical confu.and 300mm for
horizontal confu for P-P
this is indicate in CPWD noms. Please read my Abstract notes. You will find it.
Reply
Anuj Bhatnagar says:
October 20, 2011 at 8:45 am
Hi Jignesh,
Can you please send me the drawing and specification of Dead End Clamp and Suspension Clamp.
Thanks,
Anuj
email:
Reply
M.VENKATA RAO says:
November 20, 2011 at 9:52 am
Dear sir
what is the minium distance from pole to pole in 11kv overhead transmission line?
Reply
Jignesh.Parmar says:
November 27, 2011 at 3:53 pm
Minimum Distance ??? Start from Zero…Normally 25 Meter to 60 Meter according to geographic
condition,Type of Conductor,Type of Pole..
Reply
VASIM SHAIKH says:
November 22, 2011 at 5:09 am
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 44/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
can u plz give me complete details of erection. Right from pole pit dimension to stringing. Looking
for a positive reply. thanks
Reply
satheesh says:
December 1, 2011 at 6:02 am
Hello Sir
how to calculate the Drop out Fuse rating for 100 KVA transformer.and formulas..pls tell me
Reply
paulson says:
December 6, 2011 at 10:51 am
how can we terminate a 630KVA transformer y secondary side to LT overhead line.4x400sq.mm cable
is required. is there DP structure required or any other solution?
Reply
deepesh sahu says:
January 12, 2012 at 5:43 pm
it is compulsory to use “trinangular configuration in 11kv pole”?
Reply
M.SATYANARAYANA REDDY says:
January 14, 2012 at 2:19 am
it is compulsary to maintain the 90deg(Straight) angle when 33 kv line crossing the road,any
alternatives to road crossing with above 90 deg(cross)
Reply
vijay says:
February 1, 2012 at 11:18 pm
my station switch yard that is 11/415v lighting arrestor which is ahead of hg fuse set is always
busting. and my switch yard is under 33KV line . please help me out why this was happening
Reply
Pradip says:
February 4, 2012 at 9:39 am
i want to calculation of illumenation of street light scheme 3 kilo meter road length ,wide 15 mtr. pole
to pole distance 30 mtr. total no.of poles. 100 nos pole require.divder (so assume double fi img .,pole
height 9 mtr. ) & how to calulate voltage drop ,cable selections.
Reply
A. ALMOHAMADED says:
February 12, 2012 at 5:41 pm
can i know the max. load of 11kv feeder. and the long
Reply
Jignesh.Parmar says:
February 13, 2012 at 2:24 pm
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 45/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
Depends on:
(1) Conductor Size (Amp)
(2) Length of line
(3) Permissible Voltage Drop
(4) Type of Load
Reply
k.karthick says:
February 28, 2012 at 11:42 am
wonderful sir,
Reply
Parag says:
April 6, 2012 at 8:06 am
Please provide us total details & drawings for v cross arms, straight cross arms & others.
Thanks,
Reply
Muhammad Farooq Khan says:
June 7, 2012 at 4:50 pm
Hi,
I want to calculate the conductor size of 38 km 11kv OHL. my total load is given in A(KVA) which is
21000KVA.
Please help me out. suggest me a formula and size of conductor.
Reply
Jignesh.Parmar says:
June 8, 2012 at 5:03 pm
Calculate % Regulation from excel sheet given in Excel tools
Reply
Muhammad Farooq Khan says:
June 9, 2012 at 5:15 am
there is no such tool to calculate the Conductor size for OVERHEAD LINE CONDUCTOR.
did ACSR 7/3.40 mm can bear the above given load? for case of 11kv
Reply
Rolly Mondelo says:
June 18, 2012 at 12:17 pm
Dear sir
what is the minimum horizontal and vertical distance from street light pole in a 32 KV overhead
transmission line ?
Reply
Rolly Mondelo says:
June 18, 2012 at 1:08 pm
sir, also send me the standard horizontal and vertical clearance in any high voltage transmission
line…. thank you and more power!…
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 46/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
Reply
M.Viswanathan says:
June 22, 2012 at 12:03 pm
Dear Sir,
Reply
sanu says:
August 21, 2012 at 8:22 am
respected sir,
can u please tell me from where i can get rec construction manual.and which publisher is publishing
that book.i graetly need that book.thanks
Reply
Ehsan Ullah says:
September 1, 2012 at 4:30 am
Dear sir,
please tell me the depth of 11 kva pole.
Reply
Jignesh.Parmar says:
September 2, 2012 at 3:31 am
11KVA !!
Reply
Mohd Faisal ansari says:
November 28, 2016 at 7:20 pm
1520 mm
Total length of pole = 8500 mm
Reply
Sharad Taide says:
September 21, 2012 at 4:18 pm
Can u please tell me the safest horizontal and vertical distance from the steel shed. height of steel
shed is 6m & 8 M
Reply
faucet says:
November 1, 2012 at 7:38 pm
It’s in reality a great and useful piece of info. I am satisfied that you shared this helpful information
with us. Please keep us informed like this. Thanks for sharing.
Reply
M.VENKATA RAO says:
November 2, 2012 at 7:07 am
Sir if phase sequence changes in HT side of transformer then L.T side phase sequence changes or not?
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 47/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
Reply
daniel says:
November 7, 2012 at 11:38 pm
can i hv the diagram or picture of cradle guard?
Reply
wamidhtaha says:
November 10, 2012 at 11:37 am
Dear Sir i need please ( Electrical pole, span, sag, calculation in excel sheet )
if you can send it to my mail
thank you foreward
Reply
srinivas says:
January 9, 2013 at 1:01 pm
Dear sir,
please information Electrical pole, span, sag, calculation in excel sheet ) electrical installation
estimating & costing.
Thank you,
Regards,
srinivasulu.R
Reply
wamidhtaha says:
January 12, 2013 at 10:47 am
Dear Sirs;
are you can this exel sheet for( Electrical pole, span, sag, calculation)
i necessary need it
i wait your replay in my mail
thank you forward for your a ention
eng. wamidh / iraq
Reply
Jignesh.Parmar says:
January 12, 2013 at 2:24 pm
Dear wamidhtaha,
I have not such type of Excel Sheet..
Reply
Chetan Bhavsar says:
March 23, 2013 at 7:43 am
really great great info helped in my project thanks alot……..!!!!!!!!!!!
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 48/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
Reply
Yogesh says:
April 8, 2013 at 10:12 am
Dear All,
In our project, sending end voltage is around 400Volts and receiving end voltage is 360V for
150Meters OH line. Here we are ge ing 40 V drop for a very small distance . Let me know the reason
for this voltage drop.
Reply
Jignesh.Parmar says:
April 9, 2013 at 6:07 am
Your question has insufficient information.
1.what is load.(1w..100w…….)
2.which size of over head conductor have you used.
Reply
mahesh says:
April 24, 2013 at 11:58 am
hi,
dis is mahesh
my question:- if i want to underground a cable which is already over headed from the street pole to
the transformer of rating 250kva, which sqmm cable i have to use?
Reply
Jignesh.Parmar says:
April 25, 2013 at 4:16 pm
Not ge ing your Point ???
Reply
Er G Singh says:
May 5, 2013 at 3:26 am
Hello Jignesh,
Really useful stuff, can we start a threa about earthing of UG cables?
Reply
Jignesh.Parmar says:
May 5, 2013 at 4:25 am
Already give in the Blog…search in old posts
Reply
AF says:
May 19, 2013 at 9:15 am
Indeed very informative.
A question:
I have seen that the the horizontal distance between the 3 phases (conductors) of 11kV OH line is not
same; 2 phases are relatively closer, as compared to the 3rd one. Does anybody know the reason?
Reply
Jignesh.Parmar says:
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 49/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
Reply
NIKUNJ CHAUHAN says:
May 25, 2013 at 4:42 am
RESPECTED SIR,
IF YOU HAVE NOTES OR EXCEL TOOL ABOUT CALCULATION OF LOAD FLOW ANALYSIS
THEN PLEASE UPLOAD IT.
THANK YOU.
Reply
H R Arun says:
June 11, 2013 at 9:45 am
Please provide the sctional drawings of RCC 8.0 Mtr pole, RCC 9.0 Mtr pole, PSC 9.0 Mtr pole
Reply
Rafiq says:
June 22, 2013 at 11:35 am
HI,
How many transformers can be installed in 11/0.4 KV package SUBSTATION/?
Thank You
Reply
dillip kumar garnayak says:
September 14, 2014 at 7:02 pm
HI,
How many transformers can be installed in 11/0.4 KV package SUBSTATION and all transformer
calculation
Reply
Ramesh says:
June 27, 2013 at 6:40 am
sir, please send me maintenance schedule double pole isolation unit
Reply
Raja says:
July 20, 2013 at 7:25 pm
Really , great use to me
Reply
Prabakaran Balaraman says:
July 25, 2013 at 5:59 pm
sir, plz say about the clearance distance between the pole to pole and also distance between ground
surface to conductor
Reply
BHAGWAN SURYAWANSHI says:
August 8, 2013 at 10:03 pm
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 50/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
Tanks for giving that much information I am very happy to read this can i get much more
information from you
Reply
Saroja Ranjan Pa anayak says:
August 14, 2013 at 10:13 pm
Dear Sir,
A 11 KV substation is installed on the road at a distance of 5 ft from my residential house and 3 feet
from my boundary wall. Request you to mention the minimum distance that is to be maintained
during HV substation installations
Reply
jolly bhatia says:
August 16, 2013 at 7:06 am
Hi
Can u tell me what should be the maximum current which we can get on l t side on 11 kv line and
what should be the ra ing of the transformer..
Reply
s.ali says:
September 21, 2013 at 6:58 am
time to time i collect information related to my job which stands very helpful for me, thanks, this
time i want information regarding calculation of sag in 11kv transmission line i am diploma engineer
in electrical engineering by qualification with experience.
Reply
vinod says:
October 22, 2013 at 8:56 am
Whether i can get complete Bill of Material for 11KV switchyard and 11KV overhead transmission
line
Reply
M.Y. DESAI says:
October 29, 2013 at 9:33 am
Hi,
Sir.
wheather 415 v multistranded with insulation aluminum conductors for overhead lind available in
market, if yes pl.send details.
Thanks.
Reply
utkal mishra says:
November 23, 2013 at 7:25 pm
respected sir
sir please tell me what type of problem will occur if we ll binding a conductor with insulator by AAC
in lt line?
regards
er.UTKAL MISHRA
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 51/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
Reply
Badshah Mohideen says:
December 5, 2013 at 5:08 am
Hi Mr. Jignesh,
Congratulate for the website and your excellent effort. I have a doubt, Whether the jumpers can be
used as a Isolation point during outages of 11KV & 33 KV OHL lines i.e. to isolate section of OHL,
the jumpers can removed and used as isolation points.
Reply
ankush says:
December 28, 2013 at 6:08 pm
thanks
Reply
Ashok Kr. Thakur says:
December 30, 2013 at 3:01 pm
Hello Mr. Jignesh, Cud u kindly let me know the weight of 6 swg GI wire that is rqd for cage guard
of 11kv OHL?
Reply
STEWART MAWANA says:
March 27, 2014 at 10:19 am
Hy Mr Jignesh, cld you pliz kindly assist on hw can I calculate cable size when wiring a 600VA
TX which draws 75A at a supply of 0-240-230-180 and 100 and its output is 24Vac
Reply
REHAAN HASSAN says:
April 12, 2014 at 7:30 pm
In rural area and population density is high and locality full with bamboos and large trees in
magrahat of south 24 parganas of west bengal. At these type of places what is the distance between
two poles for wring of 440 said lines and also for 220 said lines as suggested and directed by
government. And what measures should be taken.
Reply
angelito cortez says:
June 20, 2014 at 8:39 pm
Good day sir,please can send me the distance of transmission tower 33 kV with wire size 366.2 mm
square and what is the required height of tower use in open area in well site (oil and gas company)
Reply
Mario Enriquez says:
June 23, 2014 at 4:00 pm
Mr. Jignesh,
Currently, 12KV aluminum wires run over a waterway 290 feet, pole-to-pole. How much wire sag is
there between the poles, assuming wires have been installed to standard specifications for 12KV
distribution? What reduction in wire sag can be expected if the span is reduced to 220 feet? (Thanks
for your impressive site.)
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 52/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
Reply
sunil mane says:
August 24, 2014 at 5:15 pm
I want to know
11 kv conductors types and their current capacity. pl.
Reply
dillip kumar garnayak says:
September 14, 2014 at 6:51 pm
11kva cabule meserment
Reply
Venu says:
August 25, 2014 at 6:11 am
Hi JIGNESH i need all component list(small components also like fuse) of distribution system from
11kv to 240v please give me a list
Reply
angelito cortez says:
August 29, 2014 at 8:40 am
Im so glad to thank you its a great great information can i get more information from you.God
bless you always.may i know the drop voltage of different size of cable in every meter.and what is
the required size of cable i use for every Kva
Reply
shrikrishna dubey says:
August 31, 2014 at 9:23 am
sir why we are using 9 kv LA in 11 kv system ?
Reply
Hidayat says:
September 4, 2014 at 7:03 pm
what is C&DF test. what is dissipation factor
Reply
D B Dandapat says:
September 9, 2014 at 11:44 am
(i) I have 11 KV O/H distribution line about 1.7 KM (only) and each individual poles are earthed with
Earth spikes ( Earth resistance of each loaction is less than 5 Ohm). But Inspector is insisting us to
provide continious earthing for the said O/H line as per IE rules. I could not traced the same from IE
rule book. Expecting your reply and possible help.
(ii) Where dumpers are being operated, what will be the ground clearance (min) for 11 KV O/H line
Reply
imprasad79 says:
September 12, 2014 at 6:32 am
(1) Continuous earth wire of proper size which is solidly earthed at substation is to run all along the
route of overhead line. For reason of safety after every fifth span , the pole is to be provided with the
earth from the ground. This wire is solidly connected to the earth provided at the substation and later
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 53/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
on every sixth pole is earthed. Galvanized iron wire of 8 SWG or bigger size is used as earthing
conductor. The maximum continuity resistance of earth should not be more than 5 Ohms.
(11) Minimum clearance of conductor above ground while crossing the road or a public through fare
for 11 KV is 6.1 Meter and Vertical Clearance above building if 11 KV line is passing over it is 3.66
Meter .Considering a dumper of Cat 777 OB Dump Truck (Empty) 100t-TRK 9780x6105x5147 , its
height will be approx 5.2 Meter .
Using all the above mentioned data , Pole of 9 Meter will give enough clearance which suffice your
purpose.
Reply
saman says:
October 14, 2014 at 7:57 am
why we are using 3 insulator bracet for 11kVA
Reply
Kaiser Ahmad says:
November 20, 2014 at 6:20 pm
Dear Sir
What should be the working load for a PCC Pole, 9.0 Mtr long with FOS:2.5.
The pole has to be used for 11kV line in a wind pressure zone of 75kg/sqmm.
Reply
ntejeswar says:
November 24, 2014 at 2:38 am
dear sir
this is very useful for me and i want 11kv/0.440kv single line diagram of outdoor sub station
Reply
vinod naik says:
November 24, 2014 at 1:21 pm
sir i want RCC pole standard drawing for all 7.5m , 9m ,11m..
Reply
Dileep Kumar Sahu says:
December 9, 2014 at 11:39 am
What is the meaning of conductor names (ACSR Dog,Rabbit & Weasel)? Do they belong to specific
voltage line rating?
Reply
prabir dua says:
December 15, 2014 at 9:56 am
I Politely request you Can you send to me all type of electrical is coad list .
Reply
Vinod Rana says:
January 8, 2015 at 11:12 am
Mr Parmar
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 54/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
Rgs
Reply
Vinod Rana says:
January 8, 2015 at 11:14 am
PL read 110100 as 11100 volts
Reply
AMAN says:
January 13, 2015 at 2:26 am
THANK YOU.IT IS VERY HELPFUL.
Reply
sakthivel says:
January 21, 2015 at 3:30 am
please tel me the insulator name which used in dp yard
Reply
tkmishra says:
January 29, 2015 at 11:13 am
R/s we are engaged in distribution system dealing with 33kv 11 kv and 440 v, working in mpeb (now
mppkvvcl we required to purchase items locally but we don’t have suitable specification book . Can
u suggest me some such books
Reply
Samson Paul says:
March 13, 2015 at 10:08 am
Hello,
I really like this article sine this article is so informative for me as I am currently doing my final year
project on designing a 11kV distribution grid exteñsion with the utility company in my country.
Am a final year electrical engineering student at the Papua New Guinea University of Technology.
Reply
rasel says:
March 20, 2015 at 4:04 pm
Would you please inform me what should be the standard height of a 11/. 44kv sub station building
as per electrical rules.
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 55/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
Thanks
Reply
Anand Kumar K.S., Sr.Technical officer, Electrical Division, CSIR-National Aerospace
Laboratories, Bangalore says:
March 27, 2015 at 1:41 pm
Dear sir information is very useful to professional engineers
Reply
N.NYNARKUMAR says:
March 31, 2015 at 7:36 am
Dear sir
I would like to thankful to say to that , I am nynarkumar i am working on rggvy project and i have
complete in one year, today i am studied in your Rec specifications. it is very valuable information
for all site engineers. but i have a small dough for transformer earthing And LA installation. please
give me the valuable answer.
Reply
D.B.V.R.K.S.Sarma says:
May 26, 2015 at 12:11 am
Respected sir
Good morning the information you have provided is useful for every personal who is a ached with
electrical distribution system, thanks for providing the information, now coming to my doubt i.e I
want to know the reason behind maintaining a distance of 1200 mm in between line support and
earthing electrode in distribution system.
Reply
jhulan says:
June 3, 2015 at 8:14 am
How many 9m stp Pole requere 1km 11 kv line
Reply
Kashmira Lal says:
July 3, 2015 at 7:01 am
Dear Jignesh,
Thanks,
Kashmira
Reply
Dharmendra says:
July 5, 2015 at 4:11 am
Good
Reply
MUKESH KUMAR says:
July 7, 2015 at 1:56 pm
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 56/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
Dear Jignesh,
I saw a pair of shield or ground wire strung/ running below phase conductors in 11 KV overhead
power line. Is this required in a 3 phase 11 KV/ 415 volts overhead distribution lines/ street lighting
utility poles also; specially on street crossing? I don’t see one in my locality. Please clarify.
Reply
D.Sarma says:
July 12, 2015 at 3:54 pm
ThoseTho may be guard wires, provided to protect the beneath area when the line conductor cuts
because of over loading or any kind of damage.
Reply
Amit Gupta says:
July 10, 2015 at 7:11 am
How to locate a fault in 11 KV OH line easily. The Line is running through farmers’ land and some of
tree touches the OH line cause earth fault or/and over current fault result in triping the system.
Reply
N.Vignesh says:
July 17, 2015 at 4:07 am
Sir,
I need sag calculation format, kindly reply as soon as possible
Reply
Samson Paul says:
July 18, 2015 at 4:13 am
Hello sir,
Can you please tell me the maximum demand a 11kV can be able to supply?
Reply
sanjoo rawat says:
August 2, 2015 at 12:05 pm
sir,
In LT distribution we are using bamboo seperators. but why in the rainy season LT line got short
circuit. can you explain and help me.
Reply
nomi says:
August 27, 2015 at 9:01 pm
In transmission we use insulators of brown colour …. what is the purpose of making the insulator in
brown colour?… ans?
Reply
nomi says:
August 27, 2015 at 9:03 pm
can we use white colour insulators in transmission line?
Reply
Himanshu Bansal says:
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 57/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
Reply
Ramesh says:
October 18, 2015 at 8:10 am
Dear sir
May i know the transmission line pole/tower heights for different voltage levels i.e starts from
11kVto 400kV
Reply
Reetesh agarwal says:
December 30, 2015 at 3:12 pm
Kind a n: The Project Purchase Manager
Dear Sir,
Cable lugs-Copper/Aluminium/Bimetallic –
Brass Cable Glands-
Ground rods – Copper Bonded /Pure Cu/SS/Galv Steel
Ground Clamps,accessories,Earthing tapes and Conductors
Lightning protection fi ings –
Exothermic weld Materials
SS cable ties and tags
OH line Clamps and Connectors
Pole line Hardware-11KV,33KV & 1.1KV
All the above products are manufactured to international standards.
We wish to supply range of electrical products to your company’s Various Electrical Projects.
If you have any requirements on above listed products,please do contact us with your enquiry
——————————————————————————–
Reetesh Agarwal-Manager
Reply
Upnesh sood says:
January 26, 2016 at 8:45 am
diploma in elec. engg.
Reply
Baka says:
March 2, 2016 at 11:00 pm
What’s the effect of an 11kv overhead line touching a 415v overhead line
Reply
Olovie Charles Emem says:
March 30, 2016 at 7:44 am
very good work
Reply
arun sharma says:
April 15, 2016 at 11:42 am
Generally which type of conductor will use in LT overhead line form distribution transformer and its
current caring capacity.
Above details are required for 100 KVA DTs and 400 KVA DTs
Reply
Ahmed says:
April 19, 2016 at 11:19 pm
Mr. Jagnesh
Can you please tell me what is the safe distance or clearance level from the EMF produce by 11KV
transmission lines, with respect of condensate tanks crossing under the lines.
Regards
Ahmed
Reply
MOHAMMAD IQBAL WANI says:
April 29, 2016 at 11:31 am
SIR, I HAVE SEARCHED ABOUT LT EARTHING ROD AS PER f5 AND f10 DRAWING OF REC
BUT I DID NOT FIND IT KINDLY HEELP ME
Reply
VipinPeter says:
April 30, 2016 at 6:03 am
What will be the common steel section used for the cross arms of a 11kv monopole line……?
Reply
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 59/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
Reply
swarup bandurao sarode says:
June 26, 2016 at 3:58 am
It is very usefull
Reply
Debasis Bha acharya says:
July 19, 2016 at 5:05 am
Dear Mr. Jignesh
Can you provide me any Format / process for recording T & D loss in Feeder Separation scheme. Will
be obliged to have a li le guidance on this. Regards.
Reply
Virupanna Kumbar Viru says:
August 31, 2016 at 2:28 pm
HI,, WHAT IS THE MAXIMUM SPAN LENGTH BETWEEN TWO POLES OF 11KV SYSTEM?
Reply
Zafar Iqbal says:
September 2, 2016 at 4:58 pm
What a lovely nd learn able link
I love it
Reply
Sanjeev Sharma says:
September 3, 2016 at 2:55 pm
Dear Sir, i am encountring a problem of reoccouring of extraordinary CT meter panel blast every 4-5
months.No local expert in electrical could diagnose the fault reoccurance. Can you help me some
way ………Sanjeev 09876363863 ( Chandigarh).
Reply
Ambuja garnaik says:
September 7, 2016 at 7:32 am
very good,but it not mention the direction of v-cross arm towards dtr/where the line goes from
tapping point.
Reply
dinesh saini says:
September 9, 2016 at 3:28 am
Awesome notes for electrical engineers
Reply
hemant singh says:
September 15, 2016 at 10:07 am
Sir, i want to know per km pole erection material in HT-LT Line i.e; HT-Pole, DP, LT Pole, STAY SET
(HT-LT)
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 60/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
Reply
Ramesh Suhag says:
September 19, 2016 at 10:14 am
LT line pole to pole distance
Reply
Gerald says:
October 5, 2016 at 5:49 pm
what’s the formula for calculating current of the drop out fuses of the transformer
Reply
Harekrushna Tudu says:
November 22, 2016 at 10:36 am
Hello Sir,
Can You tell me whether we use GI wire for 33/11 kv feeder lines.If used then what will be their size
and wt in kg/Km.
Reply
amit moruskar says:
November 25, 2016 at 7:10 am
It is very uesfull and very knowageble information for all new conractor and engeenier … thank you
very much
Reply
Mohd Faisal ansari says:
November 28, 2016 at 7:17 pm
Why earthing electrode and spike rod is kept at 1200 mm away from pole?
Reply
nagendra mathur says:
December 1, 2016 at 9:02 am
Great article. Thanks .
Is there any limit to the size of the conductor/ power that can be transmi ed over 11 KV overhead
line or any guideline regarding this aspect from REC or any statutory body
Reply
eldho Varghese says:
January 12, 2017 at 6:36 am
Dear sir
please send clearance between transmission line using 14 m A pole include 33 kV double circuit line
,11 Kv line and LT line
Reply
sreekanth says:
January 12, 2017 at 12:00 pm
what size aggregate used in 11kv/415v Substation?
Reply
Atanu Pa anayak says:
January 20, 2017 at 12:41 pm
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 61/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
hi sir,
can u provide me a full required items detials with diagram with marking of the items of 9 mtr psc
poles with 2phase 2w line
Reply
soundarrajan.a says:
January 29, 2017 at 1:02 pm
Exlant use
Reply
isaac says:
January 30, 2017 at 6:01 pm
Hi please may you send me this pages in my Email account .
Reply
Md Irfan Khan says:
February 25, 2017 at 5:40 am
Dear Sir,
As mentioned about the Anti-climbing device about the barbed wire does it needs any clip or
clamping arrangement or it can be tied to itself.
Thanks
Irfan
Reply
Mohmmad Rehman says:
April 28, 2017 at 1:07 pm
sir
transmission line only 11,22,33
Reply
Design Shree Radhe Industries says:
June 9, 2017 at 9:05 am
Sir
Kindly give what is difference for the 33KV-31mm/kv and Grater then 35mm/kv,
Gpanchal
Reply
bhargavy bn says:
July 3, 2017 at 11:32 am
Sir,
In 11kV system, on 9Mtr PSCC single pole, which side should the transformer be mounted and why
!!!!
Reply
Jhangir ilyas says:
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 62/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
Reply
sanjay sharma says:
August 16, 2017 at 1:19 pm
Dear Sir hey, how to calculate h- Pole (GO Switch ) Fuse Rating .Suppose my ht current is 137A .
many time change fuse but my line is break down .please suggest ……………….
Reply
D. R. Shah says:
August 20, 2017 at 11:32 pm
what should be the degine of 11 KV line earthing instead of conventinal type each pole earthing of
coal and salt ? Pl. help me to design chemical type earthing among a group of 5 pole in which we
may provide a chemical type ba er earthing on 3 rd pole and connect through continuous GI 8no
wire to 2-2 pole both sides in a group earthing.
Reply
Mohd Nadeem says:
August 22, 2017 at 7:05 am
Sir
please give me all information about transmission lines low and medium
Reply
Kanchan Gaurav says:
October 16, 2017 at 7:15 pm
sir,
how many types of stay used for
distribution lines?
Reply
kuldeep singh says:
December 21, 2017 at 11:24 am
How much distance is required for construction work near lt line.
Reply
Nihal says:
January 17, 2018 at 1:09 pm
sir,what are the standard values of impedance and susceptance for 11kv line
Reply
Gopi Kandula says:
January 18, 2018 at 9:36 am
sir,
can u tell me what are the permissions required for laying of 11 kv over head line wirh AAA
conductor for energy transmission
Reply
Alim says:
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 63/64
1/25/2019 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles
Reply
Kantilal S Taunk says:
April 27, 2018 at 6:06 pm
K L S TAUNK
SIR
I want to know the procedure of earthing if PCC poles and providing earth wire on the 11kv lines.
Reply
Babu Prasanthkumar says:
September 20, 2018 at 5:50 pm
please send me 11kv overhead power line construction standards
Reply
This site uses Akismet to reduce spam. Learn how your comment data is processed.
https://electricalnotes.wordpress.com/2011/06/08/11kv415v-overhead-line-specification-rec/ 64/64