Professional Documents
Culture Documents
GENERATOR SYSTEMS
Contents
Generator Systems................................................................. 1
Generation System Basics................................................... 2
Main Generator Components ........................................... 2
Magnetic Field and Voltage ............................................. 4
Phase and Voltage ......................................................... 5
Generator Design ............................................................... 6
Rotor ............................................................................ 6
Amortisseur Windings................................................. 6
Salient Pole Rotor....................................................... 6
Non-Salient Pole Rotor ................................................ 6
Permanent Magnet Rotor ............................................ 7
Stator ........................................................................... 7
Windings ................................................................... 9
Insulation Systems ....................................................... 12
Rotor Insulation........................................................ 12
Stator Insulation Combinations .................................. 13
Insulation Life .......................................................... 14
Coil Connections .......................................................... 17
Generator Features and Attachments ............................. 19
Bearings .................................................................. 20
Space Heaters ......................................................... 20
Ingress Protection (IP)............................................... 20
Physical Data............................................................... 21
Nameplate ............................................................... 22
NEMA & IEC Design Considerations ............................... 23
Temperature Rise ..................................................... 23
Maximum Momentary Overloads................................ 25
Maximum Deviation Factor........................................ 25
Telephone Influence Factor (TIF) ................................ 25
Single Frequency Weighting Short Circuit
Requirements........................................................... 26
Overspeed ............................................................... 26
Generator Performance Characteristics ............................... 27
Rated and Per Unit ....................................................... 27
Efficiency ................................................................ 27
Fault Current/Short Circuits ........................................... 28
Reactance ............................................................... 31
Transient Reactance (X’d).......................................... 32
Sub-Transient Reactance (X”d)................................... 34
Synchronous Reactance (Xd) ..................................... 36
Negative Sequence Reactance (X2) ............................ 37
Zero Sequence Reactance (Xo) .................................. 37
Harmonics & Distortion..................................................... 39
Miscellaneous Terms ........................................................ 43
Overspeed Capability ................................................ 43
Heat Dissipation ....................................................... 43
Derating .................................................................. 43
Generator Limits .............................................................. 44
Exciter & Regulator Characteristics and Performance ........... 45
Excitation System ........................................................ 45
Self-Excitation ......................................................... 46
Permanent Magnet Excitation .................................... 46
Voltage Regulation ....................................................... 46
Performance ............................................................ 49
Specifications .......................................................... 50
Frequency Sensing ................................................... 51
Type ....................................................................... 52
Foreword
This section of the Application and Installation Guide generally describes
Generator Systems for Caterpillar® engines listed on the cover of this
section. Additional engine systems, components and dynamics are addressed
in other sections of this Application and Installation Guide.
Engine-specific information and data is available from a variety of sources.
Refer to the Introduction section of this guide for additional references.
Systems and components described in this guide may not be available or
applicable for every engine.
©2008 Caterpillar®
All rights reserved.
Application and Installation Guide Generator Systems
Generator Systems
Electricity is a useful source of energy because it is versatile; much more
versatile than mechanical energy. It can be used for a variety of tasks, such
as lighting, heating and rotating electrical machinery and it can be used in a
variety of locations, such as offshore oilrigs, natural gas fields, remote areas
and urban confines.
Caterpillar generators convert the mechanical energy of an engine, or
prime mover, to electricity. The well-proven, innovative designs of Caterpillar
generators have lead to several highly reliable lines of generators used in
electric power generation applications worldwide. All Caterpillar electric
sets use AC generators. The AC generator, also called an alternator,
converts mechanical energy to electrical energy and acts as a voltage
source for the load.
This module describes basic concepts involved in the various Caterpillar
generator designs. It addresses basic electrical generation concepts,
generator design and performance as well as voltage regulation.
It is important to note that the information in this section applies, primarily,
to synchronous generators. The term synchronous describes the relationship
between the engine rpm and the generator output frequency; they are
exactly proportional.
SECTION CONTENTS
©2008 Caterpillar®
All rights reserved. Page 1
Generator Systems Application and Installation Guide
©2008 Caterpillar®
Page 2 All rights reserved.
Application and Installation Guide Generator Systems
©2008 Caterpillar®
All rights reserved. Page 3
Generator Systems Application and Installation Guide
©2008 Caterpillar®
Page 4 All rights reserved.
Application and Installation Guide Generator Systems
Figure 2
©2008 Caterpillar®
All rights reserved. Page 5
Generator Systems Application and Installation Guide
Generator Design
Generators are constructed in Amortisseur Windings
various ways to satisfy different Amortisseur windings, also known
load and customer requirements. as damper windings, are special
At Prime power ratings, SR4B conducting bars laid into a squirrel
generators are limited to 105°C cage configuration. They are set in
(221°F) temperature rise over an the notches in the rotor and then
assumed 40°C (104°F) ambient and are shorted on the end by either a
may be used on a continuous duty shorting ring or shorting laminations.
(24 hours per day) basis. They are used to increase machine
stability. This is due to the windings
SR5 generators are limited to a
and rotors relationship to the
125°C (257°F) temperature rise
synchronous speed. If the rotor is
over the same conditions.
at synchronous speed, there is no
At Standby power ratings, SR4B induced voltage through the
generators are limited to 130°C amortisseur bars, hence there is no
(266°F) temperature rise over an interaction. Conversely, if there is
assumed 40°C (104°F) ambient a differential between the rotor and
and are used many times for back-up synchronous speed, a voltage will
power needs, and are rated on a be induced in the windings. This
temporary use basis. voltage produces a current flow and
SR5 generators are limited to a in turn creates a magnetic field.
150°C (302°F) temperature rise The interaction of the two magnetic
over the same conditions. fields in turn cause a torque that will
The rating is expressed in kilowatts correct this speed difference
(kW) at 0.8 power factor. A resulting in speed and torque
common ratio, kW divided by stability.
0.8 permits calculation of kilovolt- Salient Pole Rotor
amperes (kVA) on all generators. A rotor configured with the
individual rotor poles protruding from
Rotor the center of the rotor is known as a
The rotor is defined as any rotating salient pole rotor.
winding or element of a generator.
It can be described as an assembly The rotating salient pole field
of thin magnetic steel laminations, arrangement is affected by
tightly compressed and then riveted, reluctance torque and is used for
bolted or welded together to form a engine-driven generators on most
magnetic path. It is around this core machines in the 20 kVA (16 kW)
that the field windings, or coils of and larger sizes.
conducting material, are wound Non-Salient Pole Rotor
around or inserted. A non-salient pole rotor, or
cylindrical rotor, is typically made
from solid cylindrical material and
©2008 Caterpillar®
Page 6 All rights reserved.
Application and Installation Guide Generator Systems
usually has grooves cut into the pole thick steel stampings/ laminations
faces to place the windings. stacked together. Stacking machines
A rotating non-salient pole field, use automatic welding to assure
or cylindrical rotor, isn’t affected correct stator skew, stack pressure,
by reluctance torque and it is mainly and slot alignment. Stator stampings
used for large, steam turbine-driven are usually stamped from special
generators. The non-salient silicone steel.
configuration usually has grooves The stator core is subjected to
cut into the pole faces to place the an alternating magnetic flux which
windings. induces currents, called “eddy
currents”, in the core that create
Permanent Magnet Rotor
losses. Creating the core from
A permanent magnet (PM) field
stacked stampings rather than from
eliminates the need for an exciter
one solid piece of steel inhibits eddy
and therefore is very cost effective
currents, reducing losses. The
in smaller size generators. The
silicone added to the steel stampings
disadvantage to this is that its flux
and an oxide coating help to inhibit
density (field strength) is constant
eddy currents.
and voltage regulation is poor.
However, if it is to be used in an In addition to eddy current losses
application with a steady load and in the stator core, there are
minor fluctuations, a PM field can hysteresis losses. One definition of
be very effective. hysteresis is the failure of a property
that has been altered by an external
A rotating armature, stationary
agent to return to its original value
field generator is used mainly in
when the cause of the alteration is
small, low-voltage machines. A
removed. Figure 5 illustrates
common use for this generator is as
hysteresis.
an exciter for brushless generators.
For additional discussion of PM The B-H curve in Figure 5 shows
used in larger generator excitation that unmagnetized iron starts at zero
systems, refer to Exciter & Regulator and proceeds to saturation as the
Characteristics and Performance- magnetomotive force (MMF)
Permanent Magnet. increases. In simpler terms, the
unmagnetized iron becomes
Stator magnetized. As MMF is reduced to
The stator is defined as any zero again (or as the iron loses its
stationary winding or element of a magnetism), a residual B’ results.
generator. The stator core is where The residual B’ means that the iron
the usable electricity is generated. does not entirely lose its magnetism
The windings carrying the usable when MMF returns to zero. The
electricity are placed in the stator same curve loops around as MMF
core slots. becomes negative then positive
The stator core is made up of again from an AC exciting current.
hundreds of 0.0185 in. to 0.025 in. Since the hysteresis loop results in
©2008 Caterpillar®
All rights reserved. Page 7
Generator Systems Application and Installation Guide
©2008 Caterpillar®
Page 8 All rights reserved.
Application and Installation Guide Generator Systems
Stator Windings
Figure 8
©2008 Caterpillar®
All rights reserved. Page 9
Generator Systems Application and Installation Guide
Random Winding
Figure 9
Coil Pitch
When a coil is wound 180
electrical degrees, the voltages on Figure 10
the conductors on either side are
equal in magnitude and opposite in Random wound coils are wound
direction and are said to be a full with round copper magnet wire that
pitch coil. Sometimes a coil is is insulated with a moisture resistant
wound less than 180° and is said to heavy polyester film and amide-imide
be a fractional pitch coil. The reason overcoat. Containing multiple
for this is to reduce certain harmonic conductors per turn, the coils
factors that will be discussed later consist of one or many turns each
in this guide. SR5 generators are and are wound in a double diamond
2/3-pitch. shape. Random wound coils are cost
Winding Types effective and are suited for low
Winding types can be random or power ratings, standby applications,
formed. Random windings utilize clean environments, and low
coils of round wire. Material costs operating hours.
are lower, but this method leaves The random wound stator is
spaces between the individual wires. treated using a dip and bake
Formed windings utilize square or process. The stator is dipped and
©2008 Caterpillar®
Page 10 All rights reserved.
Application and Installation Guide Generator Systems
©2008 Caterpillar®
All rights reserved. Page 11
Generator Systems Application and Installation Guide
©2008 Caterpillar®
Page 12 All rights reserved.
Application and Installation Guide Generator Systems
bow out. When centrifugal force is Windings are coated with various
broken down into its components, layers of insulation. Insulation
there is a vertical force (FV) and a materials can be used individually
side force (FS). The side force or in combinations and may be
causes the coils to bow out. comprised of acrylics, asphalts,
To prevent field coils from bowing epoxies, melamines, phenolics,
out due to centrifugal force, wedges polyamides, polyimides, polyesters,
are placed in-between the poles with polyethylenes and silicones. Possible
their two sides holding the coils insulation systems include:
tightly against the poles. Extra • Magnet wire with a polyester
wedges and bracing are sometimes and amide-imide overcoat.
added for extra assurance that rotor • Nomex™-mylar™-nomex™
materials do not move. ground insulation. (Mylar
The purpose of the Amortisseur or is a DuPont polyester film.)
damper windings (discussed earlier) Table 2 shows examples of system
is to prevent rotational oscillations voltages that may be encountered.
in the rotor. These windings provide However, the list is by no means
a motoring effect and produce a complete. In the US, system
torque in the rotor working against voltages are based on 120V with
such oscillations, thereby providing multiples of that voltage.
superior voltage stability. This is
Nominal System Identical System
particularly important during parallel Voltages* Voltage
operation where generators carrying
120 110, 115, 125
uneven loads can result in voltage
120/240 110/220, 115/230
and operational instability which
translates to added stress on the 208Y/120 199Y/115
insulation. Damper windings will 240 220, 230
minimize these oscillations. Damper 480 440, 460
windings also dampen oscillations 600 550, 575
occurring from short-circuit and 2400 2200, 2300, 2500
engine pulses.
4160Y/2400 3810, 4000
Tests are performed on the rotor
to assure that there is no material Table 2
movement in the rotor. A prototype
spin test runs at 125% rated speed Caterpillar system voltages
for two hours at 170°C (338°F). are divided into three classes to
differentiate between types of
Stator Insulation Combinations generators. The classes are Low
Stator insulation is categorized into Voltage, Medium Voltage and High
classes based on their ability to Voltage.
withstand heat for a specified period
• Low Voltage — A class of
of time. Class H is temperature rated
nominal system voltages of
at 180°C (356°F) and Class F at
1 KV or less
155°C (311°F).
©2008 Caterpillar®
All rights reserved. Page 13
Generator Systems Application and Installation Guide
©2008 Caterpillar®
Page 14 All rights reserved.
Application and Installation Guide Generator Systems
Figure 13
©2008 Caterpillar®
All rights reserved. Page 15
Generator Systems Application and Installation Guide
©2008 Caterpillar®
Page 16 All rights reserved.
Application and Installation Guide Generator Systems
©2008 Caterpillar®
All rights reserved. Page 17
Generator Systems Application and Installation Guide
©2008 Caterpillar®
Page 18 All rights reserved.
Application and Installation Guide Generator Systems
Open Delta
Figure 17
Figure 18 Figure 20
Several single-phase connections
are possible for 2-wire or 3-wire
Generator Features and
loads. These connections are Attachments
normally used only on smaller Several attachments and features
generators at or below 250 kW. can also be configured to assist
An open delta, as shown in Figure in meeting generator requirements.
19 is reconfigured from an original These include bearings,
delta from three-phase to single- environmental protection devices
phase use; this type of connection, and space heaters.
©2008 Caterpillar®
All rights reserved. Page 19
Generator Systems Application and Installation Guide
©2008 Caterpillar®
Page 20 All rights reserved.
Application and Installation Guide Generator Systems
Inertia
Water Ingress Protection Inertia data is essential to studies
(second digit of IP designation) of transient response, such as the
Second
Description effect of a larger generator with
Digit more rotor weight and greater mass
0 Non-Protected Machine moment of inertia. When the
Machine protected against
1 information is given to an engineer,
dripping water
Machine protected against
it must be correctly identified.
2 dripping water when machine These figures list the mass
is tilted up to 15° moment of inertia in System
Machine protected against
3 International (SI) units and English
spraying water
Machine protected against
units. Other symbols used to
4 designate inertia of rotating
splashing water
Machine protected against machinery are WK2, WR2, and GD2.
5
water jets The standard inertia presentation
Machine protected against below is globally recognized and can
6
heavy seas
be readily converted to other inertia
Machine protected against
7
effects of immersion designations.
Table 5 Force x Distance x Time2
N•m sec2 = Newton x meter x Second2
Two types of IP protection are lb•in. sec2 = lb x in. x Second2
totally enclosed water cooled
(TEWAC) and totally enclosed air To convert to moment of inertia
cooled (TEAC). (WK2) in SI units:
Multiply N•m sec2 by 9.803
Physical Data m/sec2.
Rotor Weight Multiply lb•in. sec2 by 2.683 to get
Rotor weight indicates the total inertia (WK2) in lb•ft2, the common
weight of the generator rotor. When English unit designation.
used with the formula for inertia, the
Center of Gravity
flywheel effect of the generator can Center of gravity is information
be found. Engineers may use these that gives the location of the
figures when generator loads are generator center of weight in three
sudden or cyclic. planes. With the total generator
Stator Weight weight, the information can be used
Stator weight is given in kilograms to determine the center of gravity
and pounds and gives an indication of an assembly consisting of engine,
of the capacity of a generator. generator, radiator, and base.
Engineers generally assume that a Combined calculations require
heavier stator contains more reducing all values to moments
working copper and iron and (lb•in. or kg•mm). These are
therefore has greater capabilities. summed algebraically in each plane
of reference.
©2008 Caterpillar®
All rights reserved. Page 21
Generator Systems Application and Installation Guide
©2008 Caterpillar®
Page 22 All rights reserved.
Application and Installation Guide Generator Systems
©2008 Caterpillar®
All rights reserved. Page 23
Generator Systems Application and Installation Guide
Temperature Rise
Method of Temperature Rise, Degrees C°
Item Machine Part Temperature Class of Insulation System
Determination A B F H
a. Armature Windings
1. All kVA ratings Resistance 60 80 105 125
2. 1563 kVA and Embedded
70 90 115 140
less detector**
3. Over 1563 kVA
a) 7000 volts and Embedded
65 85 110 135
less detector**
Embedded
b) Over 7000 volts 60 80 105 125
detector**
b. Field Winding Resistance 60 80 105 125
c. The temperature attained by cores, amortisseur windings, collector rings, and
miscellaneous parts (such as brushholders, brushes, pole tips, etc.) shall not
injure the insulation or the machine in any respect.
* For machines which operate under prevailing barometric pressure and which are designed not to exceed the specified
temperature rise at altitudes from 3300 feet (1000 meters) to 13000 feet (4000 meters), the temperature rises, as
checked by tests at low altitudes, shall be less than those listed in the foregoing table by 1 percent of the specified
temperature rise for each 330 feet (100 meters) of altitude in excess of 3300 feet (1000 meters).
** Embedded detectors are located within the slot of the machine and can be either resistance elements or
thermocouples. For machines equipped with embedded detectors, this method shall be used to demonstrate conformity with
the standard (see 20.63).
NOTES:
1—Temperature rises in the above table are based upon generators rated on a continuous duty basis. Synchronous
generators may be rated on a stand-by duty basis (see 22.85). In such cases, it is recommended that temperature rises not
exceed those in the foregoing table by more than 25°C under continuous operation at a stand-by rating.
2—Diesel engine specifications often call for machines which are suitable for 10-percent overload for 2 hours out of any
24 consecutive hours of operation. Generators having a corresponding overload capability are sometimes required. In such
cases, it is recommended that the generators and their excitation systems be designed to deliver 110 percent of kVA at
rated power factor, frequency, and voltage with temperature rises under rated load conditions not exceeding those given in
the above table.
3—Temperature rises in the foregoing table are based upon a reference ambient temperature of 40°C. However, it is
recognized that synchronous generators may be required to operate at an ambient temperature higher than 40°C. The
temperature rises of the generators given in the foregoing table shall be reduced by the number of degrees that the ambient
temperature exceeds 40°C. (Exception—for totally enclosed water-air-cooled machines, the temperature of the cooling air
is the temperature of the air leaving the coolers. Totally enclosed water-air-cooled machines are normally designed for the
maximum cooling water temperature encountered at the location where each machine is to be installed. With a cooling
water temperature not exceeding that for which the machine is designed.
a. On machines designed for cooling water temperatures from 5°C to 30°C — the temperature of the air leaving the
coolers shall not exceed 40°C.
b. On machines designed for higher cooling water temperatures — the temperature of the air leaving the coolers shall be
permitted to exceed 40°C provided the temperature rises of the machine parts are then limited to values less than those
given in the table by the number of degrees that the temperature of the air leaving the coolers exceeds 40°C.)
Table 6
©2008 Caterpillar®
Page 24 All rights reserved.
Application and Installation Guide Generator Systems
©2008 Caterpillar®
All rights reserved. Page 25
Generator Systems Application and Installation Guide
©2008 Caterpillar®
Page 26 All rights reserved.
Application and Installation Guide Generator Systems
©2008 Caterpillar®
All rights reserved. Page 27
Generator Systems Application and Installation Guide
©2008 Caterpillar®
Page 28 All rights reserved.
Application and Installation Guide Generator Systems
Figure 21
©2008 Caterpillar®
All rights reserved. Page 29
Generator Systems Application and Installation Guide
Assume each coil in Figure 24 and • For resistance of 1-2, 2-3, 3-1
Figure 25 represents an equal (line-to-line), multiply the coil
resistance value in ohms. The resistance by 4.
numbers shown represent the line • For resistance of 1-4, 2-5, 3-
and neutral in the stator windings. 6, 7-0, 8-0, 9-0 (individual
The figures show the points at coil resistance), single coil
which the listed resistance value resistance applies.
or a multiple of it applies.
• For resistance of 1-0, 2-0,
In Figure 24, the generator coils and 3-0, multiply the coil
are connected in parallel for low resistance by 2.
voltage.
Resistance measurements will be
valid only if made with instruments
capable of measuring very low
resistance. Do not attempt to use
an Ohmmeter. The inaccuracy is
too great to have any value.
Resistance values vary with
temperature. Given resistance values
apply only at 25°C (77°F).
Correction must be applied at other
Figure 24
temperatures. For temperatures
• For resistance of 1-2, 2-3, or other than 25°C, multiply the listed
3-1 (line-to-line), single coil value by 0.00393 and then by the
resistance value applies. total temperature difference
between 25°C and the existing
• For resistance of 1-0, 2-0, or temperature. Add the result to the
3-0 (line-to-neutral), divide the listed value if the temperature is
coil resistance by 2. higher. Subtract the result if the
In Figure 25, the generator coils temperature is lower.
are connected in series for high A reverse process can find internal
voltage. temperature of generator coils. The
generator stator resistance must be
accurately measured.
Open Circuit Time Constant
The open circuit time constant is
determined from a test performed as
follows:
• The generator is operating at
normal rated voltage with no
Figure 25 load.
©2008 Caterpillar®
Page 30 All rights reserved.
Application and Installation Guide Generator Systems
©2008 Caterpillar®
All rights reserved. Page 31
Generator Systems Application and Installation Guide
©2008 Caterpillar®
Page 32 All rights reserved.
Application and Installation Guide Generator Systems
©2008 Caterpillar®
All rights reserved. Page 33
Generator Systems Application and Installation Guide
©2008 Caterpillar®
Page 34 All rights reserved.
Application and Installation Guide Generator Systems
©2008 Caterpillar®
All rights reserved. Page 35
Generator Systems Application and Installation Guide
In time, within one to five cycles, are about one-half the transient
the asymmetrical current declines reactance per unit value.
to a very low value. From that time Some engineers also use sub-
forward, the symmetrical current is transient reactance to determine
the only significant current. the approximate voltage dip on
The maximum asymmetrical short a generator when starting large
circuit RMS current can be found by motors.
multiplying the RMS symmetrical
Synchronous Reactance (Xd)
value by square root of 3. In the After transient conditions have
above example, the generator will occurred, current flow is determined
produce 2190 x √3 = 3793 RMS by the synchronous reactance.
amperes, asymmetrical. This is a steady state value and
Calculations involving circuit is effective after approximately
breakers normally require peak five seconds.
currents. Symmetrical and
asymmetrical currents from a
Caterpillar generator can be
converted to peak values by
multiplying either value by the
square root of 2. In the above
example, the generator will
produce: 2190 x √2 = 3096
peak symmetrical amperes or
3793 x √2 = 5363 peak
asymmetrical amperes. Figure 29
Note that a smaller sub-transient
Synchronous reactance is
reactance per unit value results in
identified by the symbol Xd and
higher available short-circuit current.
has a per unit value of 2.0 to 4 in
Available short-circuit current is Caterpillar generators. This factor
sometimes expressed as a multiplier is used to determine the steady-
(called available current ratio), which state fault current capability of a
is the reciprocal of the per unit sub- separately excited generator. This is
transient reactance. For this the short circuit current which would
generator: be produced after five seconds. Self-
1 excited generators, such as the SR4,
= 8.326
0.1201 lose excitation before five seconds.
Therefore, the synchronous
Rated current times that multiplier reactance factor cannot be used to
equals RMS symmetrical current: determine the actual steady-state
fault current. The factor does,
263 Amperes x 8.326 = 2190
however, give a comparison with
Per unit sub-transient reactance other generators by considering the
values of Caterpillar generators
©2008 Caterpillar®
Page 36 All rights reserved.
Application and Installation Guide Generator Systems
©2008 Caterpillar®
All rights reserved. Page 37
Generator Systems Application and Installation Guide
©2008 Caterpillar®
Page 38 All rights reserved.
Application and Installation Guide Generator Systems
©2008 Caterpillar®
All rights reserved. Page 39
Generator Systems Application and Installation Guide
©2008 Caterpillar®
Page 40 All rights reserved.
Application and Installation Guide Generator Systems
©2008 Caterpillar®
All rights reserved. Page 41
Generator Systems Application and Installation Guide
©2008 Caterpillar®
Page 42 All rights reserved.
Application and Installation Guide Generator Systems
Miscellaneous Terms
Overspeed Capability may be necessary. Refer to the
Overspeed capability is the ability altitude/temperature de-rating chart
of the generator to handle the in TMI or consult your Caterpillar
sudden increase over rated rpm due dealer.
to the removal of a large load. This Where the temperature of the
is usually on the order of 125 to ventilating air to the generator
150% of rated rpm. exceeds 40°C (104°F), de-rating of
Heat Dissipation the generator may be necessary. See
Heat dissipation occurs when a Figure 33 for general capabilities.
device is heated due to current flow. Non-Linear & Unbalanced Loads
Some electrical energy is then lost Non-linear loads & unbalanced
from the energy used in the heating loads generate harmonic currents
of this device. that cause waveform distortion of
Derating the generator. In this situation,
Generator de-rating refers to the excess heat can be created and
need to lower a generator’s rated a larger generator may be needed.
operating capabilities due to an Crest Factor
environmental reason or a load Crest factor is the peak voltage
affect. This situation requires the divided by the RMS voltage.
use of a larger generator than
Distortion Factor
would be necessary under normal
Distortion factor is the sum of
conditions. Several examples of
the harmonics divided by the RMS
these conditions are as follows:
voltage.
Altitude
For application over 3300 ft
elevation, derating of the generator
Figure 33
©2008 Caterpillar®
All rights reserved. Page 43
Generator Systems Application and Installation Guide
Generator Limits
Rating limits are occasionally thermal limits. Unfortunately, it is
illustrated as shown in Figure 34; typically not possible to monitor the
kVA and kW versus power factor. temperature directly because this is,
The fluctuations in the kVA line normally, a rotating device. In this
represent the generator operating right quadrant, the generator output
limits. It is important to note that is only limited by the generator’s
every generator’s limit tendency to become self-excited
characteristics are different and with a high leading power factor.
cannot be classified by size or type. While operating in the leading
For example, the limits for a standby power factor condition, there is
generator are less limiting than for a tendency for an overvoltage
an equivalent prime-continuous condition. An overvoltage condition
generator. In another example, field may affect the successful operation
heating limits may be the limiting of the automatic voltage regulator.
factor at 0.8 PF, or they may not If the generator operates in the
limit the generator at all. left quadrant of Figure 34, it has a
The engine is many times the lagging power factor. It is limited
limiting factor in a genset as shown here by both the rotor (field) and
by the engine kW limit line. stator (armature) heating. Many
If the generator operates in the times, the field temperature limit
leading power factor quadrant, it is lower than the armature limit,
operates on a capacitive load. In this especially at low power factor
condition, the rotor is subject to values.
heat generation and may reach
Figure 34
©2008 Caterpillar®
Page 44 All rights reserved.
Application and Installation Guide Generator Systems
©2008 Caterpillar®
All rights reserved. Page 45
Generator Systems Application and Installation Guide
©2008 Caterpillar®
Page 46 All rights reserved.
Application and Installation Guide Generator Systems
©2008 Caterpillar®
All rights reserved. Page 47
Generator Systems Application and Installation Guide
©2008 Caterpillar®
Page 48 All rights reserved.
Application and Installation Guide Generator Systems
©2008 Caterpillar®
All rights reserved. Page 49
Generator Systems Application and Installation Guide
©2008 Caterpillar®
Page 50 All rights reserved.
Application and Installation Guide Generator Systems
©2008 Caterpillar®
All rights reserved. Page 51
Generator Systems Application and Installation Guide
©2008 Caterpillar®
Page 52 All rights reserved.
LEBW4993-01 ©2008 Caterpillar Printed in U.S.A.
All rights reserved.