GP01017F/00/EN/01.

13 Products Solutions Services


71219978
Valid as of version
01.00.zz

Description of device parameters


Micropilot FMR50/FMR51/
FMR52/FMR53/FMR54/FMR56/
FMR57
FOUNDATION Fieldbus
Level radar
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus Table of contents

Table of contents

1 Important document information . . . . 4 3.9.4 Expert → Diagnostics → Data


logging . . . . . . . . . . . . . . . . . . . . . . 134
1.1 Document function . . . . . . . . . . . . . . . . . . . . . 4 3.9.5 Expert → Diagnostics → Min/Max
1.2 Document conventions . . . . . . . . . . . . . . . . . . . 4 values . . . . . . . . . . . . . . . . . . . . . . . 137
1.2.1 Symbols for certain types of 3.9.6 Expert → Diagnostics → Simulation . 140
information . . . . . . . . . . . . . . . . . . . . 4 3.9.7 Expert → Diagnostics → Device
1.2.2 Symbols in graphics . . . . . . . . . . . . . . . 4 check . . . . . . . . . . . . . . . . . . . . . . . 141
1.2.3 Symbols at the device . . . . . . . . . . . . . 4 3.9.8 Expert → Diagnostics → Advanced
diagnostics 1/2 . . . . . . . . . . . . . . . . 144
2 Overview of the operating menu . . . . . 5
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 156
3 The "Expert" menu . . . . . . . . . . . . . . . . 18
3.1 Expert → System . . . . . . . . . . . . . . . . . . . . . . 21
3.1.1 Expert → System → Display . . . . . . . . 22
3.1.2 Expert → System → Configuration
backup display . . . . . . . . . . . . . . . . . 30
3.1.3 Expert → System → Administration . . 34
3.2 Expert → Sensor . . . . . . . . . . . . . . . . . . . . . . . 37
3.2.1 Overview . . . . . . . . . . . . . . . . . . . . . . 37
3.2.2 Description of parameters . . . . . . . . . 38
3.2.3 Expert → Sensor → Medium . . . . . . . . 43
3.2.4 Expert → Sensor → Level . . . . . . . . . . 45
3.2.5 Expert → Sensor → Linearization . . . . 55
3.2.6 Expert → Sensor → Information . . . . . 64
3.2.7 Expert → Sensor → Sensor
properties . . . . . . . . . . . . . . . . . . . . . 69
3.2.8 Expert → Sensor → Distance . . . . . . . . 71
3.2.9 Expert → Sensor → Gas phase
compensation . . . . . . . . . . . . . . . . . . 79
3.2.10 Expert → Sensor → Sensor
diagnostics . . . . . . . . . . . . . . . . . . . . 86
3.2.11 Expert → Sensor → Safety settings . . . 87
3.2.12 Expert → Sensor → Envelope curve . . . 95
3.2.13 Expert → Sensor → Mapping . . . . . . . 97
3.2.14 Expert → Sensor → Tank bottom
evaluation . . . . . . . . . . . . . . . . . . . . 107
3.2.15 Expert → Sensor → Echo tracking . . . 109
3.2.16 Expert → Sensor → External input . . 114
3.3 Expert → Output . . . . . . . . . . . . . . . . . . . . . 116
3.3.1 Expert → Output → Switch output . . 116
3.4 Expert → Communication . . . . . . . . . . . . . . . 121
3.4.1 Expert → Communication →
Resource block . . . . . . . . . . . . . . . . 121
3.5 The "Analog inputs" submenu . . . . . . . . . . . . 122
3.6 The "Discrete inputs" submenu . . . . . . . . . . . 123
3.7 The "Analog outputs" submenu . . . . . . . . . . . 124
3.8 The "Discrete outputs" submenu . . . . . . . . . . 125
3.9 Expert → Diagnostics . . . . . . . . . . . . . . . . . . 126
3.9.1 Expert → Diagnostics → Diagnostics
list . . . . . . . . . . . . . . . . . . . . . . . . . 128
3.9.2 Expert → Diagnostics → Event
logbook . . . . . . . . . . . . . . . . . . . . . . 129
3.9.3 Expert → Diagnostics → Device
information . . . . . . . . . . . . . . . . . . 131

Endress+Hauser 3
Important document informationMicropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

1 Important document information

1.1 Document function


The document is part of the Operating Instructions and serves as a reference for
parameters, providing a detailed explanation of each individual parameter of the operating
menu.

1.2 Document conventions

1.2.1 Symbols for certain types of information

Symbol Meaning

Tip
Indicates additional information.
A0011193

Reference to documentation
Refers to the corresponding device documentation.
A0011194

Reference to page
Refers to the corresponding page number.
A0011195

Reference to graphic
Refers to the corresponding graphic number and page number.
A0011196

Operation via local display


Indicates navigation to the parameter via the local display.
A0013140

Operation via operating tool


Indicates navigation to the parameter via the operating tool.
A0013143

Write-protected parameter
Indicates a parameter that can be locked against changes by entering a user-specific code.
A0013144

1.2.2 Symbols in graphics

Symbol Meaning

1, 2, 3 ... Item numbers

A, B, C, ... Views

A-A, B-B, C-C, ... Sections

1.2.3 Symbols at the device

Symbol Meaning

Safety instructions
Observe the safety instructions contained in the associated Operating Instructions.

Temperature resistance of the connection cables


Specifies the minimum value of the temperature resistance of the connection cables.

4 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION FieldbusOverview of the operating menu

2 Overview of the operating menu


The following table lists all parameters the "Expert" menu may contain. The page
number refers to where a description of the parameter can be found.
Depending on the device version and parametrization some parameters will not be
available in a given situation. For details on the conditions refer to the "Prerequisite"
category in the description of the respective parameter.

Navigation Direct access Description

Expert → Direct access 0106 (→  18)

Locking status 0004 (→  18)

Access status display 0091 (→  18)

Access status tooling 0005 (→  19)

Enter access code 0092 (→  19)

Navigation Direct access Description

Expert → System → Display → Language 0104 (→  23)

Format display 0098 (→  23)

Value 1 display 0107 (→  25)

Decimal places 1 0095 (→  25)

Value 2 display 0108 (→  25)

Decimal places 2 0117 (→  25)

Value 3 display 0110 (→  25)

Decimal places 3 0118 (→  25)

Value 4 display 0109 (→  25)

Decimal places 4 0119 (→  25)

Display interval 0096 (→  26)

Display damping 0094 (→  26)

Header 0097 (→  26)

Header text 0112 (→  27)

Separator 0101 (→  27)

Number format 0099 (→  28)

Decimal places menu 0573 (→  28)

Contrast display 0105 (→  28)

Backlight 0111 (→  29)

Access status display 0091 (→  18)

Navigation Direct access Description

Expert → System → Configuration backup Operating time 0652 (→  31)


display →

Last backup 0102 (→  31)

Configuration management 0100 (→  31)


1)
Backup state 0121 (→  32)

Comparison result 0103 (→  32)

1) not available for operation via display

Endress+Hauser 5
Overview of the operating menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Navigation Direct access Description

Expert → System → Administration → Activate SW option 0029 (→  36)

Device reset 1013 (→  36)

Define access code 0 (→  35)

Confirm access code 0 (→  35)

Navigation Direct access Description

Expert → Sensor → Distance unit 0551 (→  38)

Temperature unit 0557 (→  38)

Tank type 1175 (→  38)

Tube diameter 1117 (→  39)

Bin property 1176 (→  39)

Max. filling speed liquid 1212 (→  40)

Max. draining speed liquid 1202 (→  40)

Max. filling speed solid 1214 (→  40)

Max. draining speed solid 1213 (→  41)

Advanced process conditions 1177 (→  41)

Application parameter 1126 (→  42)

Navigation Direct access Description

Expert → Sensor → Medium → Medium type 1049 (→  43)

Medium group 1208 (→  43)

Medium property 1165 (→  44)

Calculated DC value 1118 (→  44)

Navigation Direct access Description

Expert → Sensor → Level → Distance offset 2309 (→  46)

Distance 2231 (→  46)

Empty calibration 2343 (→  47)

Full calibration 2308 (→  48)

Level unit 0576 (→  49)

Level limit mode 2314 (→  50)

High limit 2312 (→  50)

Low limit 2313 (→  51)

Level correction 2325 (→  51)

Output mode 2317 (→  52)

Level 2319 (→  52)

Level linearized 2318 (→  53)

Tank/silo height 1148 (→  53)

Navigation Direct access Description

Expert → Sensor → Linearization → Linearization type 2339 (→  57)

Unit after linearization 2340 (→  58)

6 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION FieldbusOverview of the operating menu

Navigation Direct access Description

Free text 2341 (→  59)

Level linearized 2318 (→  53)

Maximum value 2315 (→  60)

Diameter 2342 (→  60)

Intermediate height 2310 (→  60)

Table mode 2303 (→  61)

Table number 2370 (→  62)

Level 2383/2389 (→  62)

Customer value 2384 (→  63)

Activate table 2304 (→  63)

Navigation Direct access Description

Expert → Sensor → Information → Signal quality 1047 (→  65)

Absolute echo amplitude 1127 (→  65)

Relative echo amplitude 1089 (→  66)

Tank bottom echo 1128 (→  67)


amplitude

Found echoes 1068 (→  67)

Used calculation 1115 (→  67)

Tank trace state 1206 (→  67)

Measurement frequency 1180 (→  68)

Electronic temperature 1062 (→  68)

Navigation Direct access Description

Expert → Sensor → Sensor properties → Sensor module 1101 (→  69)

Free field special 1150 (→  69)

Navigation Direct access Description

Expert → Sensor → Distance → Distance 1124 (→  73)

Dead time 1199 (→  74)

Integration time 1092 (→  76)

Blocking distance 1144 (→  78)

Navigation Direct access Description

Expert → Sensor → Gas phase compensation GPC mode 1034 (→  83)


External pressure selector 1073 (→  83)

External pressure 1220 (→  84)

Gas phase compensation 1209 (→  84)


factor

Present reference distance 1076 (→  84)

Reference distance 1033 (→  84)

Endress+Hauser 7
Overview of the operating menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Navigation Direct access Description

Reference echo threshold 1168 (→  85)

Const. GPC factor 1217 (→  85)

Navigation Direct access Description

Expert → Sensor → Sensor diagnostics → Start self check 1133 (→  86)

Result self check 1134 (→  86)

Noise of signal 1105 (→  86)

Navigation Direct access Description

Expert → Sensor → Safety settings → Output echo lost 2307 (→  91)

Valeu echo lost 2316 (→  91)

Status echo lost 11671 (→  91)

Ramp at echo lost 2323 (→  92)

Delay echo lost 1193 (→  92)

Safety distance 1093 (→  93)

In safety distance 1018 (→  93)

Status in safety distance 11672 (→  94)

Acknowledge alarm 1130 (→  94)

Navigation Direct access Description

Expert → Sensor → Envelope curve → Envelope curve 1207 (→  96)

Navigation Direct access Description

Expert → Sensor → Mapping → Confirm distance 1045 (→  104)

Distance 1124 (→  104)

Mapping end point 1022 (→  105)

Present mapping 1182 (→  105)

Record map 1069 (→  105)

Navigation Direct access Description

Expert → Sensor → Tank bottom evaluation → Tank bottom range 1149 (→  108)

Navigation Direct access Description

Expert → Sensor → Echo tracking → Evaluation mode 1112 (→  112)

History reset 1145 (→  112)

History learning control 1074 (→  112)

History learning 1094 (→  113)

Navigation Direct access Description

Expert → Sensor → External input → Level external input 1 2305 (→  114)

Function input 1 Level 2311 (→  114)

8 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION FieldbusOverview of the operating menu

Navigation Direct access Description

Fixed value input 1 2332 (→  114)

Level external input 2 2306 (→  114)

Function input 2 Level 2331 (→  114)

Fixed value input 2 2333 (→  114)

Control measurement 1083 (→  115)

Measurement 1082 (→  115)

Navigation Direct access Description

Expert → Output → Switch output → Switch output function 0481 (→  116)

Assign diagnostic level 0482 (→  116)

Assign limit 0483 (→  116)

Switch-on value 0466 (→  117)

Switch-off value 0464 (→  117)

Assign status 0485 (→  118)

Switch-on delay 0467 (→  119)

Switch-off delay 0465 (→  119)

Switch output failure mode 0486 (→  119)

Switch status 0461 (→  120)

Invert output signal 0470 (→  120)

Navigation Direct access Description


1)
Expert → Communication → Resource block → Block tag 10702
1)
Static revision 10735
1)
Tag description 10736
1)
Strategy 10734
1)
Alert key 10696
1)
Target mot 10728
1)
Actual mode 10725
1)
Permitted mode 10727
1)
Normal mod 10726
1)
Blockerror 10703
1)
Resource state 10730
1)
DD resource 10708
1)
Manufacturer ID 10721
1)
Device type 10711
1)
Device revision 10710
1)
DD revision 10709
1)
Grant 10718
1)
Deny 10717
1)
Hard types 10719
1)
Restart 10800
1)
Features 10713

Endress+Hauser 9
Overview of the operating menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Navigation Direct access Description


1)
Feature selection 10714
1)
Cycle type 10707
1)
Cycle selection 10706
1)
Minimum cycle time 10724
1)
Memory size 10723
1)
Nonvolatile cycle time 10729
1)
Free space 10715
1)
Free time 10716
1)
Clear fault state 10704
1)
Confirm time 10705
1)
Fault state 10712
1)
Limit notify 10720
1)
Max notify 10722
1)
Set fault state 10731
1)
Shed remote cascade 10732
1)
Shed remote out 10733
1)
Unacknowledged 10740
1)
Update state 10741
1)
Time stamp 10739
1)
Static revision 10738
1)
Relative index 10737
1)
Write lock 10747
1)
Unacknowledged 10700
1)
Alarm state 10697
1)
Time stamp 10699
1)
Subcode 10698
1)
Value 10701
1)
Current 10692
1)
Unacknowledged 10694
1)
Unreported 10695
1)
Disabled 10693
1)
Acknowledge option 10691
1)
Write priority 10748
1)
Unacknowledged 10745
1)
Alarm state 10742
1)
Time stamp 10744
1)
Subcode 10743
1)
Discrete value 10746
1)
ITK version 10794

1) Block parameter according to the FOUNDATION Fieldbus specification

10 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION FieldbusOverview of the operating menu

Navigation Direct access Description


1)
Expert → Analog intputs → Analog input N → Block tag 6901
1)
Static revision 6973
1)
Tag description 6974
1)
Strategy 6972
1)
Alert key 6916
1)
Target mode 6960
1)
Actual mode 6957
1)
Permitted mode 6959
1)
Normal mode 6958
1)
Block error 6922
1)
Status 6964
1)
Value 6965
1)
Status 6906
1)
Value 6907
1)
Simulate status 6967
1)
Out value 1704
1)
Simulate value 6968
1)
Transducer status 6969
1)
Transducer value 6970
1)
Simulate En/Disable 6966
1)
EU at 100% 6982
1)
EU at 0% 6981
1)
Units index 6983
1)
Decimal 6980
1)
EU at 100% 6963
1)
EU at 0% 6962
1)
Units index 6908
1)
Decimal 6961
1)
Grant 6926
1)
Deny 6925
1)
I/O options 6941
1)
Channel 6902
1)
Status options 6971
1)
Linearization type 6905
1)
Low cutoff 6956
1)
Status 6923
1)
Value 6924
1)
Process value filter time 6909
1)
Unacknowledged 6978
1)
Update state 6979
1)
Time stamp 6977
1)
Static revision 6976
1)
Relative index 6975

Endress+Hauser 11
Overview of the operating menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Navigation Direct access Description


1)
Unacknowledged 6920
1)
Alarm state 6917
1)
Time stamp 6919
1)
Subcode 6918
1)
Value 6921
1)
Current 6912
1)
Unacknowledged 6914
1)
Unreported 6915
1)
Disabled 6913
1)
Acknowledge option 6910
1)
Alarm hysteresis 6911
1)
High high priority 6938
1)
High high limit 6937
1)
High priority 6940
1)
High limit 6939
1)
Low priority 6955
1)
Low limit 6947
1)
Low low priority 6954
1)
Low low limit 6953
1)
Unacknowledged 6935
1)
Alarm state 6932
1)
Time stamp 6934
1)
Subcode 6933
1)
Float value 6936
1)
Unacknowledged 6930
1)
Alarm state 6927
1)
Time stamp 6929
1)
Subcode 6928
1)
Float value 6931
1)
Unacknowledged 6945
1)
Alarm state 6942
1)
Time stamp 6944
1)
Subcode 6943
1)
Float value 6946
1)
Unacknowledged 6951
1)
Alarm state 6948
1)
Time stamp 6950
1)
Subcode 6949
1)
Float value 6952

1) Block parameter according to the FOUNDATION Fieldbus specification

12 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION FieldbusOverview of the operating menu

Navigation Direct access Description


1)
Expert → Discrete inputs → Discrete input N → Block tag 6851
1)
Static revision 6884
1)
Tag description 6885
1)
Strategy 6883
1)
Alert key 6846
1)
Target mode 6873
1)
Actual mode 6870
1)
Permitted mode 6872
1)
Normal mode 6871
1)
Block error 6857
1)
Status 6875
1)
Value 6876
1)
Status 6853
1)
Value 6854
1)
Simulate status 6878
1)
Simulate value 6879
1)
Transducer status 6880
1)
Transducer value 6881
1)
Simulate En/Disable 6877
1)
Transducer state 6891
1)
Output state 6874
1)
Deny 6867
1)
Grant 6868
1)
I/O options 6869
1)
Status options 6882
1)
Channel 6852
1)
Process value filter time 6855
1)
Status 6865
1)
Value 6866
1)
Unacknowledged 6889
1)
Update state 6890
1)
Time stamp 6888
1)
Static revision 6887
1)
Relative index 6886
1)
Acknowledge option 6841
1)
Current 6842
1)
Disabled 6843
1)
Unacknowledged 6844
1)
Unreported 6845
1)
Alarm state 6847
1)
Subcode 6848
1)
Time stamp 6849
1)
Unacknowledged 6850

Endress+Hauser 13
Overview of the operating menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Navigation Direct access Description


1)
Value 6856
1)
Alarm state 6858
1)
Subcode 6859
1)
Time stamp 6860
1)
Unacknowledged 6861
1)
Discrete value 6862
1)
Discrete limit 6863
1)
Discrete priority 6864

1) Block parameter according to the FOUNDATION Fieldbus specification

Navigation Direct access Description


1)
Expert → Analog outputs → Multiple analog output → Block tag 11351
1)
Static revision 11371
1)
Tag description 11372
1)
Strategy 11370
1)
Alert key 11365
1)
Target mode 11369
1)
Actual mode 11366
1)
Permitted mode 11368
1)
Normal mode 11367
1)
Block error 11364
1)
Channel 11352
1)
Status options 11363
1)
Fault state time 11354
1)
Fault state val 1 11355
1)
Fault state val 2 11356
1)
Fault state val 3 11357
1)
Fault state val 4 11358
1)
Fault state val 5 11359
1)
Fault state val 6 11360
1)
Fault state val 7 11361
1)
Fault state val 8 11362
1)
Fault state status 11353

1) Block parameter according to the FOUNDATION Fieldbus specification

Navigation Direct access Description


1)
Expert → Discrete outputs → Multiple discrete output → Block tag 11252
1)
Static revision 11270
1)
Tag description 11271
1)
Strategy 11269
1)
Alert key 11251
1)
Target mode 11267

14 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION FieldbusOverview of the operating menu

Navigation Direct access Description


1)
Actual mode 11264
1)
Permitted mode 11266
1)
Normal mode 11265
1)
Block error 11272
1)
Channel 11253
1)
Status options 11268
1)
Fault state time 11255
1)
Fault state value discrete 1 11256
1)
Fault state value discrete 2 11257
1)
Fault state value discrete 3 11258
1)
Fault state value discrete 4 11259
1)
Fault state value discrete 5 11260
1)
Fault state value discrete 6 11261
1)
Fault state value discrete 7 11262
1)
Fault state value discrete 8 11263
1)
Fault state status 11254

1) Block parameter according to the FOUNDATION Fieldbus specification

Navigation Direct access Description

Expert → Diagnostics → Actual diagnostics 0691 (→  126)

Previous diagnostics 0690 (→  126)

Operating time from restart 0653 (→  126)

Operating time 0652 (→  31)

Navigation Direct access Description

Expert → Diagnostics → Diagnostics listseliste → Diagnostics 1 0692 (→  128)

Diagnostics 2 0693 (→  128)

Diagnostics 3 0694 (→  128)

Diagnostics 4 0695 (→  128)

Diagnostics 5 0696 (→  128)

Navigation Direct access Description

Expert → Diagnostics → Event logbook → Filter options 0705 (→  129)

Event list - (→  129)

Navigation Direct access Description

Expert → Diagnostics → Device information → Device 0011 (→  131)

Serial number 0009 (→  131)

Firmware version 0010 (→  131)

Device name 0013 (→  131)

Extended order code 10795 (→  132)

Endress+Hauser 15
Overview of the operating menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Navigation Direct access Description

Extended order code 1 10796 (→  132)

Extended order code 2 10797 (→  132)

ENP version 0012 (→  132)

Hardware revision 10793 (→  132)

ITK Version 10794 (→  133)

Device type 10711 (→  133)

Device Revision 10710 (→  133)

DD Revision 10709 (→  133)

Navigation Direct access Description

Expert → Diagnostics → Data logging → Assign channel 1 0851 (→  134)

Assign channel 2 0852 (→  134)

Assign channel 3 0853 (→  134)

Assign channel 4 0854 (→  134)

Logging interval 0856 (→  134)

Clear logging data 0855 (→  135)

Display channel 1 - (→  135)

Display channel 2 - (→  135)

Display channel 3 - (→  135)

Display channel 4 - (→  135)

Navigation Direct access Description

Expert → Diagnostics → Min/max values → Max. level value 2357 (→  137)

Time max. level 2385 (→  137)

Min. level value 2358 (→  137)

Time min. level 2386 (→  137)

Max. draining speed 2320 (→  137)

Max. filling speed 2360 (→  138)

Reset min./max. 2324 (→  138)

Max. electronics 1031 (→  138)


temperature

Time max. electronics 1204 (→  138)


temperature

Min. electronics 1040 (→  139)


temperature

Time min. electronics 1205 (→  139)


temperature

Rest min./max. 1173 (→  139)


temperature

Navigation Direct access Description

Expert → Diagnostics → Simulation → Assign simulation process 2328 (→  140)


variable

Value process variable 2329 (→  140)

16 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION FieldbusOverview of the operating menu

Navigation Direct access Description

Switch output simulation 0462 (→  140)

Switch status 0463 (→  141)

Simulation device alarm 0654 (→  141)

Navigation Direct access Description

Expert → Diagnostics → Device check → Start device check 1013 (→  141)

Result device check 1014 (→  142)

Last check time 1203 (→  142)

Level signal 1016 (→  142)

Area of incoupling 1186 (→  143)

Navigation Direct access Description

Expert → Diagnostics → Advanced diagnostics 1/2 Assign diagnostic signal 11179 (→  149)
→ 1/2

Link AD 1/2 to 11180 (→  149)

Linking logic AD 1/2 11181 (→  149)

Sample time 1/2 11187 (→  150)

Calculation type 1/2 11174 (→  150)

Check mode 1/2 11175 (→  150)

Calculation unit 1/2 11188 (→  151)

Upper limit 1/2 11182 (→  151)

Lower limit 1/2 11184 (→  152)

Hysteresis 1/2 11178 (→  152)

Maximum value 1/2 11183 (→  153)

Minimum value 1/2 11185 (→  153)

Reset min./max. 1/2 11186 (→  153)

Assign status signal to AD 11176 (→  153)


event 1/2

Assign event behaviour 1/2 11177 (→  154)

Alarm delay 11171 (→  154)

Endress+Hauser 17
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

3 The "Expert" menu

Direct access (0106)

Navigation Expert → Direct access

Write access Maintenance

Prerequisite Only visible for operation via display module, not for operation via software tool (e.g.
FieldCare).

Description Enter the direct access code to access a parameter directly.

Input range 0 to 65 535

Additional information In this document, the direct access code is indicated in brackets following the parameter
name, e.g. Locking status (0004).

Locking status (0004)

Navigation Expert → Locking status

Write access Read-only parameter

Description Indicates the write protection with the highest priority that is currently active.

Display options • Hardware locked


• WHG locked
• Temporarily locked

Additional information On the display module, the -symbol appears in front of parameters that cannot be
modified since they are write-protected.

Access status display (0091)

Navigation Expert → Access status display


Expert → System → Display → Access status display

Write access Read-only parameter

Prerequisite Only visible for devices with operating and display module (SD02 or SD03)

Description Indicates access authorization to parameters via local display.

18 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Display options • Operator


• Maintenance
• Service

Additional information • The access authorization can be changed via the Enter access code parameter
(→  19).
• If additional write protection is active, this restricts the current access authorization
even further. The write protection status can be viewed via the Locking status
parameter (→  18).
• If a -symbol appears in front of a parameter, the parameter cannot be changed via
the local display with the current access authorization.

Access status tooling (0005)

Navigation Expert → Access status tooling

Write access Read-only parameter

Prerequisite Only visible for operation via operating tool (e.g. FieldCare), not for operation via display
module.

Description Indicates access authorization to parameters via operating tool (e.g. FieldCare).

Display options • Operator


• Maintenance
• Service

Additional information If additional write protection is active, this restricts the current access authorization
even further. The write protection status can be viewed via the Locking status
parameter (→  18).

Enter access code (0092)

Navigation Expert → Enter access code

Write access Operator

Description Enter access code to disable write protection of parameters

Input range 0 to 9 999

Endress+Hauser 19
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Additional information For local operation, the customer-specific access code, which has been defined in the
Expert → System → Define access code sequence, has to be entered.
If an incorrect access code is entered, the user retains his current access authorization.
The write protection affects all parameters marked with the -symbol in the document.
On the local display, the -symbol in front of a parameter indicates that the parameter is
write-protected.
If no key is pressed for 10 minutes, or the user goes from the navigation and editing mode
back to the measured value display mode, the device automatically locks the write-
protected parameters after another 60 s.
Please contact your Endress+Hauser Sales Center if you lose your access code.

20 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

3.1 Expert → System


The System submenu contains all general parameters which affect neither the
measurement nor the measured value communication.

Submenus
Submenu Meaning Description

Display Parametrization of the local display module (allocation of measured (→  22)


values, display format etc.)

Configuration backup • Backup of the device configuration in the display module (→  30)
display • Copying of the device configuration into another device

Administration • Unlocking software options (→  34)


• Reset of a device
• Definition of an access code

Endress+Hauser 21
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

3.1.1 Expert → System → Display


For operating tools: The Display submenu is only visible if a display module is
connected to the device.

Overview
The Display submenu is used to parametrize the representation of measured values on the
local display module. Up to four measured values can be allocated to the local display
module. Additionally, display characteristics such as the format of numbers, the associated
texts or the display contrast can be configured.

Parameter Meaning Description

Language Selection of the display language (→  23)

Format Display Selection of the display format (number and size of the displayed (→  23)
measuring values)

Value 1 display Allocation of a measured variable to the first display value (→  25)

Decimal places 1 Number of decimal places for the first display value (→  25)

Value 2 display Allocation of a measured variable to the second display value (→  25)

Decimal places 2 Number of decimal places for the second display value (→  25)

Value 3 display Allocation of a measured variable to the third display value (→  25)

Decimal places 3 Number of decimal places for the third display value (→  25)

Value 4 display Allocation of a measured variable to the fourth display value (→  25)

Decimal places 4 Number of decimal places for the fourth display value (→  25)

Display interval Time the individual variables are displayed in the case of an alternating (→  26)
display

Display damping Time constant for the damping of displayed values (→  26)

Header Selection of the header text: (→  26)


• Device tag
• Free text

Header text Definition of the header text in the case of Header = Free text (→  27)

Separator Selection of the decimal separator (point of comma) (→  27)

Number format Selection of the number format for distance values (decimal or ft-in-1/16") (→  28)

Decimal places menu Number of decimals for values in the operating menu (not the measuring (→  28)
values)

Contrast display Contrast of the LCD (20 ... 80%) (→  28)

Backlight Switch-on/switch-off of the display module SD03 (→  29)

Access status display Displays the user role for operation via the display module (→  18)

22 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Description of parameters

Language (0104)

Navigation Expert → System → Display → Language

Write access Operator

Description Set display language

Options • English
• One additional operating language (see product structuture, feature 500, "Additional
Operation Language")

Factory setting English

Format dipslay (0098)

Navigation Expert → System → Display → Format display

Write access Operator

Description Select how measured values are shown on the display.

Options • 1 value, max. size


• 1 bargraph + 1 value
• 2 values
• 1 value large + 2 values
• 4 values

Factory setting 1 value, max. size

Endress+Hauser 23
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Additional information 1 value, max. size

4841.000
1 Â mm
A0019963

1 bargraph + 1 value

1 Â
93.5 %
1 Â 159.0
mm
A0019964

2 values

1 Â 93.5
%
1 Â 159.0
mm
A0019965

1 value large + 2 values

1 Â 159.0 mm
V 1 Â 23.5 V
1 Â 93.5
%
A0019966

4 values

1 Â 93.5 %
1 Â 159.0 mm
V 1 Â 93.5 V
1 Â 26.3 °C

A0019968

• The Value 1 display - Value 4 display parameters are used to specify what
measured values are shown on the display and in what order (→  25).
• If more measured values are specified than the display mode selected permits, the
values alternate on the device display. The display time until the next change is
configured using the Display interval parameter (→  26).

24 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Value 1 display (0107)


Value 2 display (0108)
Value 3 display (0110)
Value 4 display (0109)

Navigation Expert → System → Display → Value 1/2/3/4 display

Write access Maintenance

Description Select the measured value that is shown on the local display.

Options • None 1)
• Level linearized
• Distance
• Terminal voltage
• Electronics temperature
• Absolute echo amplitude
• Relative echo amplitude
• Analog output adv. diagnostics 1
• Analog output adv. diagnostics 2

1) Can not be selected for "Value 1 display".

Factory setting • Value 1 display: Level linearized


• Value 2 display: None
• Value 3 display: None
• Value 4 display: None

Additional information The Format display parameter is used to specify how many measured values are displayed
simultaneously and how (→  23).

Decimal places 1 (0095)


Decimal places 2 (0117)
Decimal places 3 (0118)
Decimal places 4 (0119)

Navigation Expert → System → Display → Decimal places 1/2/3/4

Write access Maintenance

Prerequisite A measured value is specified in the Value 1/2/3/4 display parameter (→  25).

Description Select the number of decimal places for the display value.

Options •x
• x.x
• x.xx
• x.xxx
• x.xxxx

Factory setting x.xx

Endress+Hauser 25
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Additional information This setting does not affect the measuring or computational accuracy of the device.

Display interval (0096)

Navigation Expert → System → Display → Display interval

Write access Operator

Description Set time measured values are shown on display if display alternates between values.

Input range 1 to 10 s

Facotry setting 5s

Additional information An alternating display only occurs automatically if the number of measured values defined
exceeds the number of values the selected display format can display simultaneously.
• The Value 1 display - Value 4 display parameters are used to specify what
measured values are shown on the display (→  25).
• The display format of the displayed measured values is specified using the
Format display parameter (→  23).

Display damping (0094)

Navigation Expert → System → Display → Display damping

Write access Maintenance

Description Set display reaction time to fluctuations in the measured value.

Input range 0 to 999 s

Factory setting 0 s

Header (0097)

Navigation Expert → System → Display → Header

Write access Maintenance

Description Select header contents on local display

Options • Device tag


• Free text

Factory setting Device tag

26 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Additional information
1 XXXXXXXXX

A0013375

1 Position of the header text on the display

Device tag
Is defined in the Setup → Device tag parameter.
Free text
Is defined in the Header text parameter (→  27).

Header text (0112)

Navigation Expert → System → Display → Header text

Write access Maintenance

Prerequisite The Free text option is selected in the Header parameter (→  26).

Description Enter display header text

Input range Max. 12 characters, such as letters, numbers or special characters (e.g. @, %, /)

Factory setting ------------

Additional information
1 XXXXXXXXX

A0013375

1 Position of the header text on the display

User entry
The number of characters displayed depends on the characters used.

Separator (0101)

Navigation Expert → System → Display → Separator

Write access Maintenance

Description Select decimal separator for displaying numerical values

Options • . (point)
• , (comma)

Endress+Hauser 27
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Factory setting . (point)

Number format (0099)

Navigation Expert → System → Display → Number format

Write access Maintenance

Description Choose number format for the display

Options • Decimal
• ft-in-1/16" (Only valid for distance units)

Factory setting Decimal

Decimal places menu (0573)

Navigation Expert → System → Display → Decimal places menu

Write access Maintenance

Description Select number of decimal places for the representation of numbers within the operating
menu.

Options •x
• x.x
• x.xx
• x.xxx
• x.xxxx

Factory setting x.xxxx

Additional information This parameter only determines the representation of numbers within the operating menu
(e.g. Empty calibration, Full calibration). It does not affect the measured value
representation.
For measured values, the number of decimal places is defined in the Decimal places 1 to
Decimal places 4 parameters (→  25).
This setting does not affect the measurement and calculation accuracy of the device.

Contrast display (0105)

Navigation Expert → System → Display → Contrast display

Write access Operator

Description Adjust local display contrast setting to ambient conditions (e.g. lighting or reading angle).

28 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Input range 20 to 80 %

Factory setting 30 %

Additional information Set the contrast via push-buttons:


• Brighter: press the and buttons simultaneously
E

• Darker: press the and buttons simultaneously


E

Backlight (0111)

Navigation Expert → System → Display → Backlight

Write access Operator

Prerequisite Only visible if the display module SD03 with optical keys is connected (SD02 with push
buttons does not have a backlight).

Description Switch the local display backlight on and off.

Options • Disable
• Enable

Factory setting Disable

Access status display (→  18)


(0091)

Endress+Hauser 29
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

3.1.2 Expert → System → Configuration backup display


The Configuration backup display submenu is only visible if a display module is
connected to the device.

Overview
All software configurations are initially stored in a memory module (HistoROM) in the
housing and are thus permanently connected with the device. As an additional option, the
display module contains a backup memory for the device configuration. The transmission
of configuration data between these two memory modules is controlled by the
Configuration backup display submenu. It provides the following options:
• Backup of a configuration from the device into the display module.
• Restore a device configuration.
This option can be used to restore a configuration back into the device which has
previously been saved in the display module.
• Duplicate a device configuration.
If the configuration has been saved into the display module, the module can be
connected to a different device and the configuration can be duplicated to this device.
This allows to efficiently configure a number of devices in the same way.
• Compare the configurations in the device and in the display module.
The comparison result indicates whether the device configuration has been changed
since the last backup.

Parameters of the "Configuration backup display" submenu

Parameter Meaning Description

Operating time Displays the operating time since the first setup. (→  31)

Last backup Displays at which time the last backup has been performed. (→  31)

Configuration • Cancel (→  31)


management no action
• Execute backup
Saves the current device configuration into the display module.
• Restore
Writes the configuration back from the display module to the device.
• Duplicate
Copies the configuration from the display module to a device
(different from the device the configuration was saved from)
• Compare
Compares the configuration stored in the display module to the
current configuration in the device.
• Clear backup
Deletes the configuration data stored in the display module.

Backup state 1) Displays the current progress of a backup operation (→  32)

Comparison result Displays the comparison result: (→  32)


• Settings identical
• Settings not identical
• No backup
• Backup corrupt
• Check not done

1) is not available when operating via the display module

30 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Description of parameters

Operating time (0652)

Navigation Expert → System → Configuration backup display → Operating time


Expert → Diagnostics → Operating time

Write acces Read-only parameter

Description Indicates how long the device has been in operation.

Display format Days (d), hours (h), minutes (m) and seconds (s)

Additional information Display


The maximum number of days is 9999, which is equivalent to approximately 27 years.

Last backup (0102)

Navigation Expert → System → Configuration backup display → Last backup

Write acces Read-only parameter

Description Indicates the operating time at which the last data backup was saved to the display
module.

Display format Days (d), hours (h), minutes (m) and seconds (s)

Configuration management (0100)

Navigation Expert → System → Configuration backup display → Configuration management

Write access Maintenance

Description Select action for managing the device data in the display module.

Endress+Hauser 31
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Options • Cancel
No action is executed and the user exits the parameter.
• Execute backup
A backup copy of the current device configuration in the HistoROM (built-in in the
device) is saved to the display module of the device. The backup copy comprises the
transmitter and sensor data of the device.
• Restore
The last backup copy of the device configuration is copied from the display module to the
HistoROM of the device. The backup copy comprises the transmitter and sensor data of
the device.
• Duplicate
The transmitter configuration is duplicated to another device using the transmitter
display module.
• Compare
The device configuration saved in the display module is compared to the current device
configuration of the HistoROM.
• Clear backup data
The backup copy of the device configuration is deleted from the display module of the
device.

Factory setting Cancel

Additional information Compare


The comprison result can be viewed in the Comparison result parameter (→  32).

HistoROM
A HistoROM is a non-volatile device memory in the form of an EEPROM.
While the respective action is in progress, the configuration cannot be edited via the
local display and a message on the processing status appears on the display.

Backup state (0121)

Navigation Expert → System → Conf. backup display → Backup state

Write access Read-only parameter

Prerequisite Only visible in the operating tool (not on the local display)

Description Displays the status of the data backup process.

Display options • None


• Store in progress
• Restore in progress
• Import in progress
• Delete in progress
• Compare in progress

Comparison result (0103)

Navigation Expert → System → Configuration backup display → Comparison result

32 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Write access Read-only parameter

Description Comparison between present device data and display backup

Display options • Settings identical


The current device configuration of the HistoROM is identical to the backup copy in the
display module.
• Settings not identical
The current device configuration of the HistoROM is not identical to the backup copy in
the display module.
• No backup available
There is no backup copy of the device configuration of the HistoROM in the display
module.
• Backup settings corrupt
The current device configuration of the HistoROM is corrupt or not compatible with the
backup copy in the display module.
• Check not done
The device configuration of the HistoROM has not yet been compared to the backup copy
in the display module.
• Dataset incompatible
The comparison is impossible due to incompatibility.

Additional information The comparison is started via the Compare option in the Configuration
management parameter (→  31).

Endress+Hauser 33
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

3.1.3 Expert → System → Administration

Overview
The Administration submenu contains all parameters for the management of the device.
Its structure depends on the user interface:

The "Administration" submenu on the display module


Parameter Meaning Description

Define access code → Define By defining a user-specific acces code the device configuration (→  35)
access code can be protected against unintended changes.

Define access code → Confirm The access code defined in Define access code must be (→  35)
access code confirmed by repeating it in this parameter.

Activate SW option Unlock certain software options (→  36)

Device reset Resets the configuration to a defined state. (→  36)

The "Administration" submenu for operating tools (e.g. FieldCare)


Parameter Meaning Description

Activate SW option Unlock certain software options (→  36)

Device reset Resets the configuration to a defined state. (→  36)

Define access code By defining a user-specific acces code the device configuration can be (→  35)
protected against unintended changes.

34 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

The "Define access code" sequence 1)

Define access code

Navigation Expert → System → Administration → Define access code → Define access code
Expert → System → Administration → Define access code

Write access Maintenance

Description Define user-specific access code in order to protect the device against unintended changes.

Input range 0 to 9 999

Factory setting 0

Additional information If the factory setting is not changed or 0 is defined as the access code, the parameters are
not write-protected and the configuration data of the device can then always be modified.
The user is logged on in the role of Maintenance .
The write protection affects all parameters marked with the symbol in the
document. On the local display, the symbol in front of a parameter indicates that the
parameter is write-protected.
Once the access code has been defined, write-protected parameters can only be
modified if the access code is entered in the Expert → Enter access code parameter.
Please contact your Endress+Hauser Sales Center if you lose your access code.

For display operation: The new access code is only valid after it has been confirmed in
the Confirm access code parameter and after the user has returned to the main
screen (measured value display).

Confirm access code

Navigation Expert → System → Administration → Define access code → Confirm access code

Write access Maintenance

Prerequisite Only visible for operation via display module, not for operation via operating software (e.g.
FieldCare).

Description Confirm the access code by repeating the value entered in the Define access code
parameter.

Input range 0 to 9 999

Factory setting 0

1) This sequence only exists for operation via the display module. For operation via operating software (e.g. FieldCare), the "Define access code"
parameter is located directly in the "Administration" submenu.

Endress+Hauser 35
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Further parameters

Activate SW option (0029)

Navigation Expert → System → Administration → Activate SW option

Write access Maintenance

Description Enter a code to activate specific software options.

Device reset (1013)

Navigation Expert → System → Administration → Device reset

Write access Maintenance

Description Use this function to reset the device configuration - either entirely or in part - to a defined
state.

Options • Cancel
No action is executed and the user exits the parameter.
• To factory defaults
Every parameter is reset to the order-code specific factory setting.
• To delivery settings
Every parameter is reset to the delivery setting. The delivery setting may differ from the
factory default if customer specific settings have been ordered.
• Of customer settings
Every customer parameter is reset to its factory setting. Service parameters, however,
retain their current value.
• To transducer defaults
Every measurment-related parameter is reset to its factory setting. Service parameters
and communication-related parameters, however, retain their current value.
• Restart device
The restart resets every parameter whose data are in the volatile memory (RAM) to the
factory setting (e.g. measured value data). The device configuration is not modified.

Factory setting Cancel

Additional information To delivery settings


This option is only visible if customer-specific settings have been ordered.

36 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

3.2 Expert → Sensor

3.2.1 Overview
The Sensor submenu contains all parameters related to the measurement and the sensor
settings.

Parameters
Parameter Meaning Description

Distance unit Measuring unit for basic distances (e.g empty and full calibration) (→  38)

Temperature unit Measuring unit for temperatures (e.g. sensor temperature, (→  38)
electronics temperature)

Tank type Selection of the tank type (for liquid measurements) (→  38)

Tube diameter Specification of the bypass or stilling well diameter (for liquid (→  39)
measurements)

Bin property Selection of the bin type (for solid measurements) (→  39)

Max. filling speed liquid Specification of the maximum filling speed (for liquid (→  40)
measurements)

Max. draining speed liquid Specification of the maximum draining speed (for liquid (→  40)
measurements)

Max. filling speed solid Specification of the maximum filling speed (for solid (→  40)
measurements)

Max. draining speed solid Specification of the maximum draining speed (for solid (→  41)
measurements)

Advanced process Specification of additional process conditions (if required) (→  41)


conditions

Application parameter Indicates whether settings depending on the application (→  42)


parameters have been changed after the definition of the
application parameters.

Submenus
Submenu Meaning Description

Medium Properties of the medium (→  43)

Level Parametrization of a level measurement (→  45)

Linearization Transformation of the measured level into a volume or weight for (→  55)
arbitrarily shaped vessels

Information Informs about the current state of the measurement (→  64)

Sensor properties Definition of measurement related properties of the probe (→  69)

Distance Filtering of the raw distance (→  71)

Gas phase Compensation of the influences of a gas or steam above the measured (→  79)
compensation medium.

Sensor diagnostics Informs about the state of the probe and the HF cable. (→  86)

Safety settings Defines the behavior of the device in critical situations (e.g. lost echo, (→  87)
level in safety distance).

Envelope curve Preprocessing of the envelope curve (→  95)

Mapping Suppression of interference echos (→  97)

Tank bottom Evaluation of echoes in the proximity of the tank bottom (→  107)
evaluation

Echo tracking Tracking of level, interface, multiple and interference echos in order to (→  109)
identify the correct echo unambiguously.

Endress+Hauser 37
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

3.2.2 Description of parameters

Distance unit (0551)

Navigation Expert → Sensor → Distance unit

Write access Maintenance

Description Length unit for distance calculation

Options • mm
•m
• ft
• in

Factory setting m

Temperature unit (0557)

Navigation Expert → Sensor →Temperature unit

Write access Maintenance

Description Select temperature unit

Options • °C
• °F
•K
• °R

Factory setting °C

Tank type (1175)

Navigation Expert → Sensor → Tank type

Write access Maintenance

Prerequisite Medium type = Liquid

Description Defines the tank type

38 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Options • Process vessel with agitator


• Process vessel standard
• Storage vessel
• Bypass / pipe
• Open channel
• Wave guide antenna
• Stilling well
• Sphere
• Workbench test
The antenna type of the device determines which of these options are available.

Factory setting Process vessel standard

Additional information Depending on the Tank type parameter the parameters Max. filling speed liquid and
Max. draining speed liquid are preset among others.

Tube diameter (1117)

Navigation Expert → Sensor → Tube diameter

Write access Maintenance

Prerequisite Tank type = Bypass / pipe

Description Defines the diameter of the bypass or stilling well.

Input range 0 ... 9999 mm (0 ... 390 inch)

Factory setting 0 mm (0 in)

Additional information The tube diameter must be entered for bypass and stilling well applications in order to
optimally adapt the measurement to the measuring point.

Bin property (1176)

Navigation Expert → Sensor → Bin property

Write access Maintenance

Prerequisite Medium type = Solid

Description Defines the bin property

Options • Bin / pile


• Buffer silo (fast)
• Crusher / belt
• Silo
• Workbench test

Endress+Hauser 39
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Factory setting Silo

Additional information Depending on the Bin type parameter, the parameters Max. filling speed solid and Max.
draining speed solid are preset, among others.

Max. filling speed liquid (1212)

Navigation Expert → Sensor → Max. filling speed liquid

Write access Maintenance

Prerequisite Medium type = Liquid

Description Select expected maximum filling speed

Options • Slow < 1cm (0.4in)/min


• Medium < 10cm (4in)/min
• Standard < 1m (40in)/min
• Fast < 2m (80in) /min
• Very fast > 2m (80in) /min
• No filter / test

Factory setting Standard < 1m (40in)/min

Max. draining speed liquid (1202)

Navigation Expert → Sensor → Max. draining speed liquid

Write access Maintenance

Prerequisite Medium type = Liquid

Description Select expected maximum draining speed

Options • Slow < 1cm (0.4in)/min


• Medium < 10cm (4in)/min
• Standard < 1m (40in)/min
• Fast < 2m (80in) /min
• Very fast > 2m (80in) /min
• No filter / test

Factory setting Standard < 1m (40in)/min

Max. filling speed solid (1214)

Navigation Expert → Sensor → Max. filling speed solid

40 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Write access Maintenance

Prerequisite Medium type = Solid

Description Select maximum expected filling speed.

Options • Very slow < 0.5m (1.6ft) /h


• Slow < 1 m (3.3ft) /h
• Standard < 2m (6,5ft) /h
• Medium < 4m (13ft) /h
• Fast < 8m (26ft) /h
• Very fast > 8m (26ft) /h
• No filter / test

Factory setting Standard < 2m (6,5ft) /h

Additional information The Max. filling speed solid parameter must be set according to the actual process
velocity.

Max. draining speed solid (1213)

Navigation Expert → Sensor → Max. draining speed solid

Write access Maintenance

Prerequisite Medium type = Solid

Description Select maximum expected draining speed.

Options • Very slow < 0.5m (1.6ft) /h


• Slow < 1 m (3.3ft) /h
• Standard < 2m (6,5ft) /h
• Medium < 4m (13ft) /h
• Fast < 8m (26ft) /h
• Very fast > 8m (26ft) /h
• No filter / test

Factory setting Standard < 2m (6,5ft) /h

Additional information The Max. draining speed solid parameter must be set according to the actual process
velocity.

Advanced process conditions (1177)

Navigation Expert → Sensor → Advanced process conditions

Write access Maintenance

Description Defines additional process conditions (if necessary)

Endress+Hauser 41
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Options • None
• Weak signal
• Many obstacles
• Small tanks (< 1m/3ft)
• Changing DC values
• Foam (> 5cm/0.16ft)

Factory setting None

Additional information • Weak signal


Increases the sensitivity of the device in case of weak signals.
• Many obstacles
Can improve the behavior of the device in case of many obstacles in a silo if strongly
damping media (e.g. flour) are measured.
• Small tanks (< 1m/3ft)
Can improve the near-range measurement in small vessels.
• Changing DC values
Adjusts the signal evaluation of the device to strongly changing DC values of the
measured medium.
• Foam (> 5cm/0.16ft)
Adjusts the signal evaluation of the device to conditions with foam > 5 cm (1.6 in).

Application parameter (1126)

Navigation Expert → Sensor → Application parameter

Write access Read-only parameter

Description Indicates whether parameters have been changed after the basic setup.

Display options • Changed


• Not changed

Additional information Indicates whether a setting which depends on the application parameters (e.g. "Process
property", Advanced process conditions", "Tank type" and "Pipe diameter") has been changed
after the basic setup.
• Changed
Parameters have been changed. The device is no longer in the state defined by the
application parameters.
• Not changed
There have been no changes. The device is still in the state defined by the application
parameters.

42 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

3.2.3 Expert → Sensor → Medium

Overview
The Medium submenu is used to specify the relevant properties of the measured medium,
especially the dielectric constant (DC).

Parameter Meaning Description

Medium type Options: "Liquid" or "Solid" (→  43)


1)
Medium group Rough selection of the DC ("Water based" or (→  43)
"Others")

Medium property Finer selection of the DC (→  44)

Calcualted DC value Displays the calculated DC. (→  44)

1) Only available for "Medium type" = "Liquid".

Description of parameters

Medium type (1049)

Navigation Expert → Sensor → Medium → Medium type

Write access Service

Description Indicates the medium type

Display options • Liquid


• Solid

Factory setting • FMR50: Liquid


• FMR51: Liquid
• FMR52: Liquid
• FMR53: Liquid
• FMR54: Liquid
• FMR56: Solid
• FMR57: Solid

Medium group (1208)

Navigation Expert → Sensor → Medium → Medium group

Write access Maintenance

Prerequisite Medium type = Liquid

Description Defines the medium group of the measured product.

Options • Water based (DC ≥ 4)


• Others (DC > 1.9)

Endress+Hauser 43
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Factory setting Others (DC > 1.9)

Additional information If required, smaller DC values can be entered into Expert → Sensor → Medium → Medium
property. This, however, may reduce the measuring range.
Refer to the Technical Information (TI) of the respective device.

Medium property (1165)

Navigation Expert → Sensor → Medium → Medium property

Write access Maintenance

Description DC: Dielectric constant

Options • Unknown
• DC 1.4 to 1.6
• DC 1.6 to 1.9
• DC 1.9 to 2.5
• DC 2.5 to 4
• DC 4 to 7
• DC 7 to 15
• DC > 15

Factory setting Unknown

Additonal information Dielectric constants of important media commonly used in the industry are
summarized in the document SD106F, which can be downloaded from the Endress
+Hauser web page (www.endress.com).

Calculated DC value (1118)

Navigation Expert → Sensor → Medium → Calculated DC value

Write access Read-only parameter

Description DC: Dielectric constant

Additional information Indicates a DC value calculated by the device. The calculation is only possible for small DC
values as it requires the tank bottom signal.

44 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

3.2.4 Expert → Sensor → Level

Overview
The Level submenu is used to parametrize the calculation of the level from the measured
distance.

1 2 3 4 5

R
L 100%

D
D

100%
D0

100% B
A DL

E
D0 D L0 L

L0
B

F
DD 0%
t A
0% 0%

A0016141

1 Calculation of the level from the measured distance


1 Correction of the measured distance
2 Level calculation
3 Level limitation
4 Correction of the level
5 Definition of the output value: Level (A) or Ullage (B)

Parameters of the "Level" submenu

Task Required parameters Parameter Description

Correction of the measured distance Distance offset (2309) (→  46)

Distance (2231) (→  46)

Level calculation Empty calibration (2343) (→  47)

Full calibration (2308) (→  48)

Level unit (0576) (→  49)

Level limitation Level limit mode (2314) (→  50)

High limit (2312) (→  50)

Low limit (2313) (→  51)

Level correction Level correction (2325) (→  51)

Definition of the output value Output mode (2317) (→  52)

Level indication Level (2319) (→  52)

Level linearized (2318) (→  53)

Definition of the tank or silo height Tank/silo height (→  53)

Endress+Hauser 45
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Description of parameters

Distance offset (2309)

Navigation Expert → Sensor → Level → Distance offset

Write access Maintenance

Description Definition of the distance offset

Input range -200.000,0 ... +200.000,0 mm (-60 ... +60 ft)

Factory setting 0.0 mm

Additonal Information The value speicified in this parameter is added to the measured distance between the
reference point of the measurement and the level echo.
• Positive values increase the distance and thus decrease the level.
• Negative values decrease the distance and thus increase the level.

R R
D0

D0
D

DD(<0)
DD(>0)

A0016081

2 Effect of the "Distance offset" parameter


ΔD Distance offset
D0 Measured distance (as indicated in "Expert → Sensor → Distance → Distance")
D Corrected distance (is used to calculate the level)
R Reference point

A value entered into this parameter is taken into account in the calculation of the
level. However, it does not influence the indicated distance.

Distance (2231)

Navigation Expert → Sensor → Level → Distance

Write access Read-only parameter

46 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Description Displays the measured distance D from the


reference point (lower edge of the flange or
threaded connection) to the level.
D

A0019483

A0019485

Additional information The value is displayed in the selected "Level unit" (→  49).

Empty calibration (2343)

Navigation Expert → Sensor → Level → Empty calibration

Write access Maintenance

Description Distance process connection to min. level

Input range 0 to 100 m (0 to 328 ft)

Factory setting • FMR50: 40 m (131 ft)


• FMR51: 40 m (131 ft)
• FMR52: 40 m (131 ft)
• FMR53: 20 m (66 ft)
• FMR54: 20 m (66 ft)
• FMR56: 30 m (98 ft)
• FMR57: 70 m (230 ft)
A different value can be defined when ordering the device.

Endress+Hauser 47
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Additional information The empty calibration E is the distance


between the reference point (lower edge of the
flange or threaded connection) and the
minimum level (0%).

0%

A0019486

0%

A0019488

Full calibration (2308)

Navigation Expert → Sensor → Level → Full calibration

Write access Maintenance

Description Span: max. level - min. level

Input range 0.001 to 100 m (0.003 to 328 ft)

Factory setting Empty calibration - Blocking distance


A different value can be defined when ordering the device.

48 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Additional information The full calibration F is the distance between


the minimum level (0%) and the maximum
level (100%).
100%

0%

A0019487

100%

0%

A0019489

Level unit (0576)

Navigation Expert → Sensor → Level → Level unit

Write access Maintenance

Description Defines the level unit

Options •%
•m
• mm
• ft
• in

Factory setting %

Additional information The level unit may differ from the distance unit defined in the Distance unit parameter
(→  38):
• The distance unit is used for the basic calibration ("Empty calibration" and "Full
calibration").
• The level unit is used to display the (unlinearized) level.

Endress+Hauser 49
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Level limit mode (2314)

Navigation Expert → Sensor → Level → Level limit mode

Write access Maintenance

Description Defines the typ of level limitation

Options • Off
• Low limit
• High limit
• Low and high limit

Factory setting Low limit

Additional information The parameter determines to which direction the level is limited. The exact limits are
defined in the High limit and Low limit parameters.

A B C
L L L
100% 100% 100%
1 1
a a
2 2 2 2
b b

0% 0% 0%
t 1 t 1 t

A0016083

3 Effect of the parameters "Level limit mode", "High limit" and "Low limit"
A Level limit mode = High limit
B Level limit mode = Low limit
C Level limit mode = Low and high limit
a High limit
b Low limit
1 Level before limitation
2 Level after limitation

High limit (2312)

Navigation Expert → Sensor → Level → High limit

Write access Maintenance

Prerequisite Level limit mode = High limit or Low and high limit

Description Defines the upper limit of the level signal.

50 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Input range Depending on the selected distance unit:


• 0.0 to 100.0 %
• 0.0 to +200.0 m
• 0.2 to +656.2 ft
• 0.0 to +7874.0 inch
• 00.0 to +200,000.0 mm

Factory setting 100%

Additional information Levels exceeding the value specified in this parameter will be ignored. Instead, the device
uses the value specified in this parameter (for measured value transformation and output).

Low limit (2313)

Navigation Expert → Sensor → Level → Low limit

Write access Maintenance

Prerequisite Level limit mode = Low limit or Low and high limit

Description Defines the lower limit of the level signal.

Input range Depending on the selected distance unit:


• 0.0 to 100.0 %
• 0.0 to +200.0 m
• 0.0 to +656.2 ft
• 0.0 to +7874.0 inch
• 00.0 to +200,000.0 mm

Factory setting 0%

Additional information Levels falling below the value specified in this parameter will be ignored. Instead, the
device uses the value specified in this parameter (for measured value transformation and
output).

Level correction (2325)

Navigation Expert → Sensor → Level → Level correction

Write access Maintenance

Description Defines a level correction

Input range Depending on the selected level unit:


• -100.0 to 100.0 %
• -200.0 to +200.0 m
• -656.2 to +656.2 ft
• -7874.0 to +7874.0 inch
• -200,000.0 to +200,000.0 mm

Endress+Hauser 51
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Factory setting 0%

Additional information The value specified in this parameter is added to the measured level (before linearization).

Output mode (2317)

Navigation Expert → Sensor → Level → Output mode

Write access Maintenance

Description Defines the output mode

Options • Ullage
• Level linearized

Factory setting Level linearized

Additional information • Ullage


The unfilled space of the tank or silo is indicated.
• Level linearized
The level is indicated (more precisely: the linearized value if a linearization has been
activated).

100%
B
A

0%

A0016086

4 Definition of the "Output mode" parameter


A Level linearized
B Ullage

Level (2319)

Navigation Expert → Sensor → Level → Level

Write access Read-only parameter

52 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Description Displays the measured level L (before


linearization)

0%

A0019482

L
0%

A0019484

Additional information The value is displayed in the selected "Level unit" (→  49).

Level linearized (2318)

Navigation Expert → Sensor → Level → Level linearized


Expert → Sensor → Linearization → Level linearized

Write access Read-only parameter

Description Displays the linearized level.

Additional information The unit of this parameter is defined in the Unit after linearization parameter
(→  58).

Tank/silo height

Navigation Expert → Sensor → Level → Tank/silo height

Endress+Hauser 53
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Write access Maintenance

Description Total height of the tank or silo as measured from the process connection.

Input range –999.999 to +999.999 m (–3 280 to +3 280 ft)

Factory setting 4 m (13.1 ft)

Additional information If the parametrized measuring range (Empty


calibration) differs significantly from the tank
or silo height, it is recommended to enter the
tank or silo height. On default, Tank/Silo
height is always equal to Empty calibration.
E
Example: Continuous level monitoring in the
upper third of a tank or silo. 0%
1

A0019867

E Empty calibration
1 Tank/Silo height

0%

A0019868

E Empty calibration
1 Tank/Silo height

54 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

3.2.5 Expert → Sensor → Linearization

Overview

2
A
L
100%
L 1 B L‘
0%
M L‘
L
100%
C L2
L1
0% L‘1L‘2 L‘
L
100%

H
D
0% M L‘
L
100%

h
E
0% M L‘
L
100%
F
h
0% M L‘
L
100%
G d

0%
M L‘
L
100%
H d

0%
M L‘

A0019648

5 Linearization: Transformation of the level into a volume or weight; the transformation is dependent on
the shape of the vessel.
1 Selection of linearization type and unit
2 Parametrization of the linearization
A Linearization type = None
B Linearization type = Linear
C Linearization type = Table
D Linearization type = Pyramid bottom
E Linearization type = Conical bottom
F Linearization type = Angled bottom
G Linearization type = Horizontal cylinder
H Linearization type = Sphere
L Level before linearization (measured in level unit)
L' Level after linearization (corresponds to volume or weight)
M Maximum value
d Diameter
h Intermediate height

Endress+Hauser 55
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Parameters of the "Linearization" submenu

Task Required parameters Parameter description

Selection of linearization type and unit after Linearization type (→  57)


linearization
Unit after linearization (→  58)

Free text (→  59)


1)
Display of the linearized level Level linearized (→  53)

Parametrization of the linearization Linearization type = Linear

Maximum value (→  60)

Linearization type = Horizontal cylinder / Sphere

Maximum value (→  60)

Diameter (→  60)

Linearization type = Pyramid bottom / Conical bottom / Angled


bottom

Maximum value (→  60)

Intermediate height (→  60)

Linearization type = Table

Table mode (→  61)


1)
Table number (→  62)

Level (→  62)

Customer value (→  63)

Activate table (→  63)

1) Only for operation via operating tool (e.g. FieldCare), not on the local display module

56 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Description of parameters

Linearization type (2339)

Navigation Expert → Sensor → Linearization → Linearization type

Write access Maintenance

Description Defines the type of linearization

Options • None
The level is transmitted to the output 100%
without linearization.
• Linear (A) A
• Table (B)
• Pyramid bottom (C) 0%
• Conical bottom (D)
• Angled bottom (E) 100%
• Horizontal cylinder (F)
• Sphere (G) B

0%

100%

C/D

0%

100%

0%

100%
F/G

0%

A0013299

Factory setting None

Endress+Hauser 57
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Additional information • None


The level is transmitted in the level unit without linearization.
• Linear
The output value (volume/weight) is directly proportional to the level L. This is valid, for
example, for vertical cylinders. Additionally, the following parameters have to be
specified:
– Unit after linearization (2340)
– Maximum value (2315): Maximum volume or weight
• Table
The relationship between the measured level L and the output value (volume/weight) is
given by a linearization table consisting of up to 32 pairs of values "level - volume" or
"level - weight", respectively.
Additionally, the following parameters have to be specified:
– Unit after linearization (2340)
– Table mode (2303)
– For each table point: Level (2383)
– For each table point: Customer value (2384)
– Activate table (2304)
• Pyramid bottom
The output value corresponds to the volume or weight in a silo with pyramid bottom.
Additionally, the following parameters have to be specified:
– Unit after linearization (2340)
– Maximum value (2315): Maximum volume or weight
– Intermediate height (2310): The height of the pyramid
• Conical bottom
The output value corresponds to the volume or weight in a tank with conical bottom.
Additionally, the following parameters have to be specified:
– Unit after linearization (2340)
– Maximum value (2315): Maximum volume or weight
– Intermediate height (2310): The height of the conical part of the tank
• Angled bottom
The output value corresponds to the volume or weight in a silo with an angled bottom.
Additionally, the following parameters have to be specified:
– Unit after linearization (2340)
– Maximum value (2315): Maximum volume or weight
– Intermediate height (2310): Height of the angled bottom
• Horizontal cylinder
The output value corresponds to the volume or weight in a horizontal cylinder tank.
Additionally, the following parameters have to be specified:
– Unit after linearization (2340)
– Maximum value (2315): Maximum volume or weight
– Diameter (2342)
• Sphere
The output value corresponds to the volume or weight in a spherical tank. Additionally,
the following parameters have to be specified:
– Unit after linearization (2340)
– Maximum value (2315): Maximum volume or weight
– Diameter (2342)

Unit after linearization (2340)

Navigation Expert → Sensor → Linearization → Unit after linearization

Write access Maintenance

58 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Prerequisite Only visible if a linearization has been selected (i.e. Linearization type ≠ None)

Description Defines the unit of the linearized value.

Options • Free text


•t
• lb
• ton
• kg
• impGal
• UsGal
• cf
• cm3
• dm3
• m3
• hl
•l
•%

Factory setting %

Additional information The selected unit is only used to be indicated on the display. The measured value is not
transformed according to the selected unit.
It is also possible to parametrize a distance-to-distance linearization, i.e. a
transformation from the level unit to a different distance unit. To do so, select the
Table linearization mode. In order to define the new level unit, select the Free text
option in the Unit after linearization parameter and enter the unit into the Free text
parameter.

Free text (2341)

Navigation Expert → Sensor → Linearization → Free text

Write access Maintenance

Prerequisite Only visible for Unit linearized = Free text.

Description Definiton of the unit

Input range Up to 32 alphanumerical characters (letters, numbers, special characters)

Factory setting Free text

Level linearized (2318) (→  53)

Prerequisite Only visible for operation via operating tool (e.g. FieldCare), not on the local display
module.

Endress+Hauser 59
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Maximum value (2315)

Navigation Expert → Sensor → Linearization → Maximum value

Write access Maintenance

Prerequisites Only visible if one of the following linearization types has been selected:
• Linear
• Pyramid bottom
• Conical bottom
• Angled bottom
• Horizontal cylinder
• Sphere

Description Definition of the maximum content of the vessel (100%), as measured in the Unit
linearized.

Input range -50000 ... +50000

Factory setting 100

Diameter (2342)

Navigation Expert → Sensor → Linearization → Diameter

Write access Maintenance

Prerequisites Only visible if one of the following linearization types has been selected:
• Horizontal cylinder
• Sphere

Description Definition of the tank diameter

Input range 0 ... 9999.999 m (32808 ft)

Factory setting 2 m (6.6 ft)

Additional information The value must be specified in the selected distance unit (→  38).

Intermediate height (2310)

Navigation Expert → Sensor → Linearization → Intermediate height

Write access Maintenance

60 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Prerequisites Only visible if one of the following linearization types has been selected:
• Pyramid bottom
• Conical bottom
• Angled bottom

Description Definition of the intermediate height H

H
0%

A0013264

Input range 0 to 200 m (0 to 656 ft)

Factory setting 0 m (0 ft)

Additional information The value must be specified in the selected distance unit (→  38).

Table mode (2303)

Navigation Expert → Sensor → Linearization → Table mode

Write access Maintenance

Prerequisite Only visible if the "Table" linearization type has been selected.

Description Defines the method used to enter linearization points into the table.

Options • Manual
The level and the associated linearized value are entered manually for each linearization
point.
• Semi-automatic
The level is measured by the device for each linearization point. The associated
linearized value is entered manually.
• Clear table
Deletes the existing linearization table.
• Sort table
Rearranges the linerization points into an ascending order.

Factory setting Manual

Endress+Hauser 61
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Additional information Conditions the linearization table must meet:


• The table may consist of up to 32 pairs of values "Level - Linearized Value".
• The table must be monotonic (monotonically increasing or decreasing).
• The first linearization point must refer to the minimum level.
• The last linearization point must refer to the maximum level.
Entering the table
• Via FieldCare: The table points may be entered via the parameters Table number,
Level and Customer value. As an alternative, the graphical table editor can be
used: Device Operation → Device Functions → Additional Functions →Linearization
(Online/Offline)
• Via the local display module: Access the graphical table editor by the Edit table
option. The table is dispayed on the display module and can be edited row by row.
The factory setting for the level unit is "%". If you want to enter the linearization table
in physical units, a suitable level unit has to be selected beforehand in the Expert →
Sensor → Level → Level unit parameter.

Table number (2370)

Navigation Expert → Sensor → Linearization → Table number

Write access Maintenance

Prerequisite • Only visible for Linearization type = Table


• Only visible via operating tool (e.g. FieldCare), but not on the local display module.

Description Number of the table point which will be defined by the next two parameters (Level and
Cusotmer value).

Input range 1 to 32

Factory setting 1

Level (2383/2389)

Navigation Expert → Sensor → Linearization → Level

Write access • For Table mode = Semiautomatic: Maintenance


• For Table mode = Manual: Read-only parameter

Prerequisite • Only visible for Linearization type = Table


• Only visible via operating tool (e.g. FieldCare), but not on the local display module.

Description Definition or display of the (unlinearized) level of the respective linearization point.

Input range Depending on the parametrized measuring range. See the parameters Empty
calibration(→  47) and Full calibration(→  48).

Factory setting 0

62 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Additional information For Table mode = Manual: Level is a writable parameter.


For Table mode = Semi-automatic: Level is a read-only parameter.

Customer value (2384)

Navigation Expert → Sensor → Linearization → Customer value

Write access Maintenance

Prerequisite • Only visible for Linearization type = Table


• Only visible via operating tool (e.g. FieldCare), but not on the local display module.

Description Specification of the linearized value of the respective linearization point.

Input range -3,0 x 1038 ... +3,0 x 1038

Factory setting 0

Activate table (2304)

Navigation Expert → Sensor → Linearization → Activate table

Write access Maintenance

Prerequisite Only visible if the "Table" linearization type has been selected.

Description Enables or disables the linearization table.

Options • Disable
A linearization is not calculated. If the Linearization type parameter has been set to
Table, the error message F435 is generated.
• Enable
The measured value is linearized according to the table before being sent to the output.

Factory setting Disable

Additional information When editing the table, this parameter is automatically reset to the Disable option. After
finishing the editing procedure it must be set to the Enable option again.

Endress+Hauser 63
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

3.2.6 Expert → Sensor → Information

Overview
The Information submenu comprises all display parameters which give information about
the current state of the measurement:

Parameter ParameterDescription

Signal quality (1047) (→  65)

Absolute echo amplitude (1127) (→  65)

Relative echo amplitude (1089) (→  66)

Tank bottom echo amplitude (1128) (→  67)

Found echoes (1068) (→  67)

Used calculation (1115) (→  67)

Tank trace state (1206) (→  67)

Measurement frequency (1180) (→  68)

Electronic temperature (1062) (→  68)

64 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Description of parameters

Signal quality (1047)

Navigation Expert → Sensor→ Information → Signal quality

Write access Read-only parameter

Description Indicates the signal quality.

Display options • Strong


The evaluated echo exceeds the threshold by at least 10 dB
• Medium
The evaluated echo exceeds the threshold by at least 5 dB.
• Weak
The evaluated echo exceeds the threshold by less than 5 dB.
• No signal
The device does not find a usable echo and generates the following error message
– F941 if the Alarm option has been selected in the Output echo lost parameter
(→  91).
– S941 if another option has been selected in the Output echo lost parameter
(→  91).

Additional information The signal quality indicated in this parameter always refers to the currently evaluated
echo: either the level echo or the tank bottom echo. To differentiate between these two,
the quality of the tank bottom echo is always displayed in brackets.

Absolute echo amplitude (1127)

Navigation Expert → Sensor→ Information → Absolute echo amplitude

Write access Read-only parameter

Description Indicates the absolute amplitude of the level echo.

Endress+Hauser 65
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Additional information

A0019961

1 Absolute echo amplitude in the envelope curve, measured in dB

Relative echo amplitude (1089)

Navigation Expert → Sensor→ Information → Relative echo amplitude

Write access Read-only parameter

Description Indicates the relative amplitude of the level echo, i.e. the difference between the level echo
and the echo threshold.
In the envelope curve display of FieldCare, the absolute echo amplitude is indicated
instead of the relative amplitude (see the number on the top right of the echo peak in
the example).

Additional information

A0019962

1 The relative echo amplitude is the difference between the weighting curve (blue) and the peak in the envelope
curve (red).

66 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Tank bottom echo amplitude (1128)

Navigation Expert → Sensor→ Information → Tank bottom echo amplitude

Write access Read-only parameter

Description Indicates the amplitude of the tank bottom echo

Additional information The tank bottom echo amplitude is only evaluated for media with a small DC value.

Found echoes (1068)

Navigation Expert → Sensor→ Information → Found echos

Write access Read-only parameter

Description Indicates which echoes have been found.

Display options • None


• Level
• Level and TB
• TB (TT)
• Multiple echo (TT)
• Tank bottom

Used calculation (1115)

Navigation Expert → Sensor→ Information → Used calculation

Write access Read-only parameter

Description Indicates which echoes are used for the calculation fo the measured value.

Display options • None


• Level
• Tank bottom
• TB (TT)
• Multiple echo (TT)
• Level and TB

Tank trace state (1206)

Navigation Expert → Sensor→ Information → Tank trace state

Endress+Hauser 67
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Write access Read-only parameter

Description Indicates the current state of the tank trace.

Display options • Not active


A valid tank trace is not available.
• EOP (TT)
A valid EOP tank trace is available.
• Multiple echo (TT)
A valid multiple echo tank trace is available.
• EOP + Multiple echo (TT)
A valid EOP and multiple echo tank trace is available.

Measurement frequency (1180)

Navigation Expert → Sensor→ Information → Measurement frequency

Write access Read-only parameter

Description Displays the current measurement frequency (number of pulses per second).

Electronic temperature (1062)

Navigation Expert → Sensor→ Information → Electronic temperature

Write access Read-only parameter

Description Displays the current temperature of the electronics.

Additional information The unit is defined in the Expert → Sensor → Temperature unit parameter .

68 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

3.2.7 Expert → Sensor → Sensor properties

Overview
The Sensor properties submenu comprises all parameters which describe the
measurement-related properties of the probe and the envelope curve.

Overview of the parameters

Eigenschaft Zugehörige Parameter Parameterbeschreibung

Basic properties of the probe (→  69) Sensor module (→  69)

Free field special (→  69)

Basic properties of the probe

Sensor module (1101)

Navigation Expert → Sensor → Sensor properties → Sensor module

Write access Read-only parameter

Description Indicates the type of sensor module.

Display options • SMR6


Radar sensor module 6 GHz; valid for:
– FMR53
– FMR54
• SMR26L
Radar sensor module 26 GHz; valid for:
– FMR50 without "Advanced dynamics" application package
– FMR51 without "Advanced dynamics" application package
– FMR52 without "Advanced dynamics" application package
• SMR26S
Radar sensor module 26 GHz; valid for:
– FMR50 with "Advanced dynamics" application package
– FMR51 with "Advanced dynamics" application package
– FMR52 with "Advanced dynamics" application package
– FMR56
– FMR57

Free field special (1150)

Navigation Expert → Sensor → Sensor properties → Free field special

Write access Maintenance

Description This parameter can be switched on in the case of free-field applications (e.g. below a
bridge).

Endress+Hauser 69
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Options • No
• Yes

Factory setting No

70 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

3.2.8 Expert → Sensor → Distance

Overview
The Distance submenu contains all parameters by which the filtering of the raw distance
D1 is controlled. The resulting distance D0 is used for the subsequent level calculation
(→  45).

1 2

D1 D0

A0016175

6 The configurable distance filters


1 Dead time
2 Low pass filter (defined by integration time)

Endress+Hauser 71
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Parameters of the "Distance" submenu

Task Required parameters Description

Display of the distances (→  73) Distance (→  73)

Definition of the dead time (→  74) Dead time (→  74)

Configuration of the low pass filter (→  76) Integration time (→  76)

Definition of the blocking distance (→  78) Blocking distance (→  78)

72 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Display of the distances

Distance (1124)

Navigation Expert → Sensor → Distance → Distance

Write access Read-only parameter

Description Displays the measured distance D from the


reference point (lower edge of the flange or
threaded connection) to the level.
D

A0019483

Endress+Hauser 73
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Definition of the dead time

Dead time (1199)

Navigation Expert → Sensor → Distance → Dead time

Write access Maintenance

Description Defines the dead time (in seconds).

Input range 0 to 60 s

Factory setting Dependent on the following parameters:


• for Medium type = Liquid
– Max. filling speed liquid
– Max. draining spid liquid
• for Medium type = Solid
– Max filling speed solid
– Max. draining speed solid

Dependencies of the "Dead time" parameter for "Medium type" = "Liquid"

Max. filling speed liquid Max. draining speed liquid

Slow Medium Standard Fast Very fast No filter / test


< 1cm (0,4in)/min < 10cm (4in)/min < 1m (40in)/min < 2m (80in)/min > 2m (80in)/min

Slow
8s 6s 4s 2s 0s 0s
< 1cm (0,4in)/min

Medium
6s 6s 4s 2s 0s 0s
< 10cm (4in)/min

Standard
4s 4s 4s 2s 0s 0s
< 1m (40in)/min

Fast
2s 2s 2s 2s 0s 0s
< 2m (80in)/min

Very fast
0s 0s 0s 0s 0s 0s
> 2m (80in)/min

No filter / test 0s 0s 0s 0s 0s 0s

74 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Dependencies of the "Dead time" parameter for "Medium type" = "Solid"

Max. filling Max. draining speed solid


speed solid
Very slow Slow Standard Medium Fast Very fast No filter / test
< 0,5m < 1m (3,3ft)/h < 2m (6,5ft)/h < 4m (13ft)/h < 8m (26ft)/h > 8m (26ft)/h
(1,6ft)/h

Very slow
< 0,5m 180 s 180 s 120 s 60 s 40 s 0s 0s
(1,6ft)/h

Slow
180 s 180 s 120 s 60 s 40 s 0s 0s
< 1m (3,3ft)/h

Standard
120 s 120 s 60 s 60 s 40 s 0s 0s
< 2m (6,5ft)/h

Medium
60 s 60 s 60 s 40 s 40 s 0s 0s
< 4m (13ft)/h

Fast
40 s 40 s 40 s 40 s 20 s 0s 0s
< 8m (26ft)/h

Very fast
0s 0s 0s 0s 0s 0s 0s
> 8m (26ft)/h

No filter / test 0s 0s 0s 0s 0s 0s 0s

Additional information Application


Sudden changes of the measured distance are ignored during the time span defined in this
parameter. In this way it is possible to prevent short-term interferences form disturbing
the output signal.

2 3

1 t

A0016164

7 Effect of the dead time


1 Dead time
2 Signal before the dead time filter
3 Signal after the dead time filter

Disadvantages
• The device slows down.
• Fast level changes are registered with a delay.

Endress+Hauser 75
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Parametrization of the low pass filter


The low pass filter dampens the distance signal with a user defined integration time τ.
After a sudden change of the level, it lasts about 5 x τ until the new measured value is
obtained.

D
1

5xt t
A0016169

8 Low pass filter


1 Signal before the low pass filter
2 Signal after the low pass filter
τ Integration time

Integration time (1092)

Navigation Expert → Sensor → Distance → Integration time

Write access Maintenance

Description Defines the integration time (in seconds).

Input range 0 to 200 000 s

Factory setting Dependent on the following parameters:


• for Medium type = Liquid
– Max. filling speed liquid
– Max. draining spid liquid
• for Medium type = Solid
– Max filling speed solid
– Max. draining speed solid

76 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Dependencies of the "Integration time" parameter for "Medium type" = "Liquid"

Max. filling speed liquid Max. draining speed liquid

Slow Medium Standard Fast Very fast No filter / test


< 1cm (0,4in)/min < 10cm (4in)/min < 1m (40in)/min < 2m (80in)/min > 2m (80in)/min

Slow
30 s 15 s 5s 1s 0s 0s
< 1cm (0,4in)/min

Medium
15 s 15 s 5s 1s 0s 0s
< 10cm (4in)/min

Standard
5s 5s 5s 1s 0s 0s
< 1m (40in)/min

Fast
1s 1s 1s 1s 0s 0s
< 2m (80in)/min

Very fast
0s 0s 0s 0s 0s 0s
> 2m (80in)/min

No filter / test 0s 0s 0s 0s 0s 0s

Dependencies of the "Integration time" parameter for "Medium type" = "Solid"

Max. filling Max. draining speed solid


speed solid
Very slow Slow Standard Medium Fast Very fast No filter / test
< 0,5m < 1m (3,3ft)/h < 2m (6,5ft)/h < 4m (13ft)/h < 8m (26ft)/h > 8m (26ft)/h
(1,6ft)/h

Very slow
< 0,5m 250 s 200 s 200 s 100 s 50 s 1s 0s
(1,6ft)/h

Slow
200 s 200 s 200 s 100 s 50 s 1s 0s
< 1m (3,3ft)/h

Standard
200 s 200 s 100 s 100 s 50 s 1s 0s
< 2m (6,5ft)/h

Medium
100 s 100 s 100 s 50 s 50 s 1s 0s
< 4m (13ft)/h

Fast
50 s 50 s 50 s 50 s 20 s 1s 0s
< 8m (26ft)/h

Very fast
1s 1s 1s 1s 1s 1s 0s
> 8m (26ft)/h

No filter / test 0s 0s 0s 0s 0s 0s 0s

Additional information Increasing the integration time results in a calmer measuring signal. However, this also
means that the measuring signal indicates level changes with a certain delay.

Endress+Hauser 77
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Definition of the blocking distance

Blocking distance (1144)

Navigation Expert → Sensor → Distance → Blocking distance

Write access Maintenance

Description Defines the distance below the process connection in which no measurement is performed.

Input range 0 to 200 m (0 to 656 ft)

Factory setting 0 m (0 ft)

Additional information Echoes from within the blocking distance are


not taken into account in the signal evaluation.

BD

A0019492

78 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

3.2.9 Expert → Sensor → Gas phase compensation

Overview
High pressures reduce the propagation velocity of the measuring signals in the gas/vapor
above the fluid. This effect depends on the kind of gas/vapor and of its temperature. This
results in a systematic measuring error that gets bigger as the distance increases between
the reference point of the measurement (flange) and the product surface.

Influence of a gas layer


The following table illustrates this measured error for a few typical gases/vapors (with
regard to distance; a positive value means that too large a distance is being measured):

Gas layer Temperature Pressure

°C °F 1 bar (14.5 psi) 10 bar (145 psi) 50 bar (725 psi) 100 bar (1 450 psi) 160 bar (2 320 psi)

Air/ 20 68 0.00 % 0.22 % 1.2 % 2.4 % 3.89 %


Nitrogen
200 392 –0.01 % 0.13 % 0.74 % 1.5 % 2.42 %

400 752 –0.02 % 0.08 % 0.52 % 1.1 % 1.70 %

Hydrogen 20 68 –0.01 % 0.10 % 0.61 % 1.2 % 2.00 %

200 392 –0.02 % 0.05 % 0.37 % 0.76 % 1.23 %

400 752 –0.02 % 0.03 % 0.25 % 0.53 % 0.86 %

Water 100 212 0.02 % - - - -


(saturated
steam) 180 356 - 2.1 % - - -

263 505.4 - - 8.6 % - -

310 590 - - - 22 % -

364 687 - - - - 41.8 %

Types of gas phase compensation


The influence of the gas phase can be compensated for in the following ways:
• Gas phase compensation with reference signal 2)(→  80)
• Constant gas phase compensation factor (→  81)
• For PROFIBUS PA and FOUNDATION Fieldbus: Compensation with external pressure
measurement (→  82)

2) This type of gas phase compensationis not recommended for Micropilot.

Endress+Hauser 79
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Gas phase compensation with reference signal


This type of gas phase compensation needs an artificaial reference echo at a definite
distance from the process connection. The reference signal must always be above the
maximum level. The position of the reference echo depends on the pressure of the gas
phase. The device uses this echo shift to calculate the correction factor for the distance
measurement.

80 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Constant gas phase compensation factor


If the properties of the gas phase (pressure, temperature, composition) do not change over
the time and are known, a gas phase compensation can also be performed without a
reference signal. Instead, a constant, user-defined correction factor is applied in this case.
This factor is used to adjust the envelope curve and thus the measured echo distance.

A
B

B = FA

A0020199

9 Gas phase compensation with a constant correction factor F


A Position of the level echo in the original envelope curve
B Position of the level echo in the corrected envelope curve.

Parameter Meaning Parameter description

GPC mode Select the Const. GPC factor option. (→  83)

Const. GPC factor Enter correction factor for distances (→  85)

Endress+Hauser 81
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Compensation with external pressure measurement (PROFIBUS PA and FOUNDATION


Fieldbus)
The compensation with external pressure measurement is only available for devices
with PROFIBUS PA or FOUNDATION Fieldbus.
In many cases the dielectric constant is proportional to the pressure of the gas phase. If the
proprotionality factor is known, a gas phase compensation can be performed by measuring
the pressure externally.
The device receives the externally measured pressure p of the gas phase through one of
the Analog Input Blocks and uses the user defined gas phase compensation factor F to
calculate the dielectric constant ε of the gas phase according to the following formula:
ε = 1 + Fp
ε is then used to calculate the correction of the measured distances.

2
ENDRESS + HAUSER

A0016304

 10 Gas phase compensation with external pressure measurement


1 Levelflex
2 Segment coupler
3 PLC
4 Absolute pressure transmitter

Parameter Meaning Parameter


description

GPC mode Select the External correction option. (→  83)

External pressure selector Select the AO block through which the externally (→  83)
measured pressure is received.

External pressure Displays the pressure read in from the AO block (→  84)

Gas phase compensation factor Enter the factor F. (→  84)

Suitable value of the gas phase compensation factor for saturated steam in the
temperature range 100 to 350 °C (212 to 662 °F):
F = 0.00505 / bar

82 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Description of the parameters

GPC mode (1034)

Navigation Expert → Sensor → Gas phase compensation → GPC mode

Write access Maintenance

Description Selection of the GPC mode

Options • Off
The gas phase compensation is deactivated.
• On
This option can only be selected for probes with reference echo. The gas phase
compensation is calculated from the position of this reference echo. The displayed
envelope curve does already contain the correction.
• Without correction
This option can only be selected for probes with reference echo.The correction factor is
calculated from the reference echo but not applied to the measurement.
This option is only used for diagnostic purposes and should not be used for normal
applications. The envelope curve is displayed without the correction.
• External correction
This option can only be selected for devices with PROFIBUS PA or FOUNDATION
Fieldbus. The device receives the externally measured pressure through an AO block and
uses it together with the gas phase compensation factor F to calculate the gas phase
compensation. The displayed envelope curve does already contain the correction.
• Const. GPC factor
The correction factor is a constant defined by the user. A reference echo or an externally
measured pressure are not needed. The displayed envelope curve does already contain
the correction.

Factory setting Off

External pressure selector (1073)

Navigation Expert → Sensor → Gas phase compensation → External pressure selector

Write access Maintanance

Prerequisite Only available for PROFIBUS PA or FOUNDATION Fieldbus and if GPC mode = External
correction

Description Defines the AO block through which the external pressure used for gas phase
compensation is received.

Options • None
• Analog output 1
• Analog output 2
• Analog output 3
• Analog output 4

Endress+Hauser 83
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Factory setting None

External pressure (1220)

Navigation Expert → Sensor → Gas phase sompensation → External pressure

Write access Read-only parameter

Prerequisite Only available for PROFIBUS PA or FOUNDATION Fieldbus and if GPC mode = External
correction

Description Displays the pressure which is currently read-in from the AO block.

Gas phase compensation factor (1209)

Navigation Expert → Sensor → Gas phase compensation → Gas phase compensation factor

Write access Maintenance

Prerequisite Only available for PROFIBUS PA or FOUNDATION Fieldbus and if GPC mode = External
correction

Description Defines the gas phase compensation factor F.

Input range -1038 ... + 1038

Factory setting 0

Additional information Suitable value for saturated steam in the temperature range 100 to 350 °C (212 to 662 °F):
F = 0.00505 / bar

Present reference distance (1076)

Navigation Expert → Sensor → Gas phase compensation → Present reference distance

Write access Read-only prarameter

Prerequisite GPC mode = On or Without correction

Description Displays the currently measured distance of the reference echo.

Reference distance (1033)

84 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Navigation Expert → Sensor → Gas phase compensation → Reference distance

Write access Maintenance

Prerequisite GPC mode = On oder Without correction

Description Input parameter for the actual distance of the reference echo.

Input range 0 to 200 m

Factory setting 0.3 m

Additonal information The distance of the aritificially generated reference echo has to be entered into this
parameter. The reference echo must always be in the gas phase; the level must never rise
above the reference echo.

Reference echo threshold (1168)

Navigation Expert → Sensor → Gas phase compensation → Reference echo threshold

Write access Maintenance

Prerequisite GPC mode = On or Without correction

Description Definition of the threshold for the reference echo

Input range –999 to +999 dB

Werkeinstellung –80 dB

Additonal information Only echoes exceeding the defined threshold are accepted as reference echo.

Const. GPC factor (1217)

Navigation Expert → Sensor → Gas phase compensation → Const. GPC factor

Write access Maintenance

Prerequisite GPC mode = Const. GPC factor

Description Definition of a constant correction factor for the measured distance.

Input range 0.5 to 1.5

Factory setting 1 (i.e.: without correction)

Endress+Hauser 85
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

3.2.10 Expert → Sensor → Sensor diagnostics

Start self check (1133)

Navigation Expert → Sensor → Sensor diagnostics → Start self check

Write access Maintenance

Description Starts a self check of the device.

Options • No
• Yes

Factory setting No

Result self check (1134)

Navigation Expert → Sensor → Sensor diagnostics → Result self check

Write access Read-only parameter

Description Displays the result of the self check of the device.

Display options • Unknown


• None
• Not used
• Valid range
• Not ok
• Ok
• Invalid range
• Not defined
• Check not done

Noise of signal (1105)

Navigation Expert → Sensor → Sensor diagnostics → Noise of signal

Write access Read-only parameter

Beschreibung Displays the noise of signal in the envelope curve (in dB).

86 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

3.2.11 Expert → Sensor → Safety settings

Overview
The Safety settings submenu contains all parameters which determnine the behavior of
the device in critical situations such as an echo loss or an undershooting of a user defined
safety distance.

Behavior in the case of an echo loss


The behavior in the case of an echo loss is defined in the Output echo lost parameter
(→  91). Depending on the selected option, suitable values have to be assigned to a
number of further parameters.

Option selected in "Output Required additional parameters Parameter description


echo lost"

Last valid value Delay time echo lost (→  92)

Status echo lost (FOUNDATION Fieldbus) (→  91)

Ramp at echo lost Ramp at echo lost (→  92)

Delay time echo lost (→  92)

Status echo lost (FOUNDATION Fieldbus) (→  91)

Value echo lost Value echo lost (→  91)

Delay time echo lost (→  92)


1)
Alarm

1) The alarm bahavior ist defined in the submenus "Current output" (HART) or "Analog input" (PROFIBUS PA,
FOUNDATION Fieldbus).

L
0

2 3

t
A0016206

 11 "Output echo lost" = "Last valid value"


1 Echo loss
2 "Delay time echo lost"
3 The last valid measured value is held.

Endress+Hauser 87
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

L
0

3
1 5

%
2
min
4
E

t
A0016207

 12 "Output echo lost" = "Ramp at echo lost"


1 Echo loss
2 "Delay time echo lost"
3 For a positive ramp: The measured value is increased with a constant rate until it reaches the maximum value
(100%).
4 For a negative ramp: The measured value is decreased with a constant rate until it reaches the minimum
value (0%).
5 The ramp is specified as "percentage of the defined measuring span per minute".

L
0

3
1

t
A0016208

 13 "Output echo lost" = "Value echo lost"


1 Echo loss
2 "Delay time echo lost"
3 "Value echo lost"

88 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Safety distance
In order to get a warning message if the level rises into the proximity of the upper blocking
distance, a safety distance can be defined in the Safety distance parameter.

1
2
A0016210

 14 Definition of the safety distance


1 Upper blocking distance
2 Safety distance

The behavior of the device in case the level rises into the safety distance is defined in the
In safety distance and Acknowledge alarm parameters.

L
0
2

S942
E

t
A0016211

 15 "In safety distance" = "Alarm": If the safety distance is undershot, the device generates an alarm.
1 Safety distance
2 Defined output value for alarms

Endress+Hauser 89
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

L
0

!
S942
E

t
A0016212

 16 "In safety distance" = "Warning": If the safety distance is undershot, the device continues measuring but
nevertheless generates a warning.
1 Safety distance

L
0
2

3
S942

t
A0016213

 17 "In safety distance" = "Self holding": If the safety distance is undershot, the device generates an alarm. The
measurement is not resumed until this alarm has been acknowledged by the user.
1 Safety distance
2 Defined alarm output value
3 Acknowledge alarm

Parameter Meaning Parameter description

Safety distance Length of the safety distance as measured from the reference (→  93)
point of the measurement.

In safety distance Defines the behavior in case the safety distance is undershot. (→  93)

Acknowledge alarm Reactivates the measurement after the level has fallen below (→  94)
the safety distance again 1).

1) Only required for "In safety distance" = "Self holding"

90 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Description of parameters

Output echo lost (2307)

Navigation Expert → Sensor → Safety settings → Output echo lost

Write access Maintenance

Description Defines the output signal in the case of a lost echo.

Options • Last valid value


The last valid value is kept in the case of a lost echo.
• Ramp echo lost
In the case of a lost echo the output value is continously shifted towards 0% or 100%.
The slope of the ramp is defined in the Ramp echo lost parameter.
• Value echo lost
In the case of a lost echo the output assumes the value defined in the Value echo lost
parameter.
• Alarm
In the case of a lost echo the device generates an alarm.

Factory settings Last valid value

Value echo lost (2316)

Navigation Expert → Sensor → Safety settings → Value echo lost

Write access Maintenance

Prerequisite Only visible if the Value echo lost option has been selected in the Output echo lost
parameter.

Description Defines the constant output value in the case of a lost echo.

Input range 0 ... 200000

Factory setting 0

Additional information The unit is the same as for the output value:
• Without linearization: As defined in the Level unit parameter (→  49).
• With linearization: As defined in the Unit after linearization parameter (→  58).

Status echo lost (11671)

Navigation Expert → Sensor → Safety settings → Status echo lost

Write access Operator

Endress+Hauser 91
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Description Defines the status in case of a lost echo

Options • Good
• Uncertain
• Bad

Factory setting Bad

Ramp at echo lost (2323)

Navigation Expert → Sensor → Safety settings → Ramp at echo lost

Write access Maintenance

Condition Only visible if the Ramp echo lost option has been selected in the Output echo lost
parameter.

Description Defines the slope of the ramp in the case of a


lost echo. 100%
B

A
C

0%
t

min

A0013269

A Delay echo lost


B Ramp echo lost (positive value)
C Ramp echo lost (negative value)

Input range -9999999.0 ... + 9999999.0 %/min

Factory setting 0 %/min

Additional information • The unit for the slope of the ramp is "percentage of the measuring range per minute" (%/
min).
• For a negative slope of the ramp: The measured value is continuously shifted downwards
until it reaches 0%.
• For a positive slope of the ramp: The measured value is continuosly shifted upwards until
it reaches 100%.

Delay time echo lost (1193)

Navigation Expert → Sensor → Safety settings → Delay time echo lost

92 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Write access Maintenance

Description Defines the delay in the case of a lost echo.

Input range 0 ... 99999.9 s

Factory setting 60 s

Additional information After an echo loss, the device waits for the time specified in this parameter before reacting
as specified in the Output echo lost parameter. This helps to avoid interruptions of the
mesurement by short-term interferences.

Safety distance (1093)

Navigation Expert → Sensor → Safety settings → Safety distance

Write access Maintenance

Description Definition of the safety distance

Input range –200 to +200 m

Factory setting 0m

Additional information The safety distance is measured from the reference point of the measurement (lower edge
of the flange or threaded connection). The safety distance can be used to generate a
warning before the level rises into the blocking distance. The In safety distance parameter
defines the rection of the device if the level rises into the safety distance.

In safety distance (1018)

Navigation Expert → Sensor → Safety settings → In safety distance

Write access Maintenance

Description Defines the behavior if the level rises into the safety distance.

Options • Off (i.e. no reaction)


• Alarm
The device assumes the alarm state and generates the diagnostic event S942 "In safety
distance".
• Warning
The device assumes the warning state and generates the diagnostic event S942 "In safety
distance".
• Self holding
The device assumes the defined alarm state. Additionally, the diagnostic event S942 "In
safety distance" is generated.
If the level drops out of the safety distance, the alarm remains active. The measurement
is continued only after a reset of the self holding via the Acknowledge Alarm
parameter.

Endress+Hauser 93
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Factory setting Warning

Status in safety distance (11672)

Navigation Expert → Sensor → Safety settings → Status in safety distance

Write access Operator

Description Defines the status in case the safety distance is undershot.

Options • Good
• Uncertain
• Bad

Factory setting Bad

Acknowledge alarm (1130)

Navigation Expert → Sensor → Safety settings → Acknowledge alarm

Write access Maintenance

Prerequisite In safety distance = Self holding

Description Resets the self holding alarm of the device.

Options • No
The alarm is not rest.
• Yes
The alarm is reset. The measurement is resumed.

Factory setting No

94 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

3.2.12 Expert → Sensor → Envelope curve


The Envelope curve submenu is only available on the display module (not in
FieldCare). It is used to display the envelope curve on the display module. When
operating via FieldCare, the envelope curve can be displayed in the envelope curve
editor (Device Operation → Device Functions → Additional Functions → Envelope
Curve).

Endress+Hauser 95
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Description of parameters

Envelope curve (1207)

Navigation Expert → Sensor → Envelope curve → Envelope curve

Write access Maintenance

Preerequisite Only visible for operation via display module; not visible for FieldCare operation.

Description Defines which curves are included in the envelope curve display on the display module.

Options • Envelope curve


• Envelope + Map
• Envelope + Ref.
• Raw envelope curve
• Envelope + EWC

Factory setting Envelope curve

Additional information The display of the selected curve can be accessed in the following way:

A0014279

96 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

3.2.13 Expert → Sensor → Mapping

Overview
The mapping is used to suppress interference signals which may be generated by internal
tank or silo fittings. A mapping curve, representing the envelope curve of an empty tank
or silo as precisely as possible, is used for the mapping.
In the case of a static envelope curve evaluation 3), all echos below the mapping curve are
ignored in the signal evaluation.

[dB]
0

20

40

1
60
3 3 3 4

80

100 2

120
[m (in)]

A0020608

1 Mapping curve
2 Envelope curve
3 Interference echos; covered by the mapping curve
4 Level echo; exceeds the envelope curve

In the case of a dynamic envelope curve evaluation 3) echos from below the map can also
be taken into account. In this case the static envelope curve evaluation serves as a starting
point as long as enough history information is not yet available.

3) For the difference between static and dynamic envelope curve evaluation refer to the "Expert → Sensor → Echo tracking" submenu.

Endress+Hauser 97
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Recording the mapping curve


There are different methods of recording the mapping curve:
• Factory map
• Overlay map
• Record new map

Factory map
The factory map is adapted to the individual antenna and is therefore permanently stored
in the device and not recorded by the user. It covers the near field of the antenna (ringing
area).

1=
2=
A [dB]

D
4 [m (ft)]

A0020643

1 Envelope curve
2 Factory map
3 Level distance
4 Empty distance

If a new mapping is recorded, the factory map nevertheless remains in the device and can
be reactivated when required by selecting the Factory map option in the Confirm
distance parameter.

Overlaying the map


In this case the existing mapping curve (i.e. the factory map or a previously recorded map)
initially remains valid.
During the defined Mapping overlay time the envelope curve is observed. At each
position the heighest value reached during the mapping overlay time is used for the new
mapping curve. Depending on the circumstances this may be the amplitude of the old
mapping curve or an amplitude obtained during the mapping overlay time.
With the help of the overlay mapping it is possible to map not only static but also dynamic
signals (e.g. from an agitator).
Mapping overlaying will be used if one of the options Distance ok or Tank empty has
been selected in the Confirm distance parameter.

New recording of the mapping curve


In this case the existing map is deleted and a new map is recorded.
In contrast to the overlaying, only the current envelope curve is used here and there is no
mapping overlay time. Therefore the new recording is faster than the overlaying. However,
dynamic interference echos can not be suppressed in this way.

A new recording of the map is started in the following way:


1. Go to the Confirm distance parameter and select Manual map.

98 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

2. Go to the Record map parameter and select the Record map option.

Endress+Hauser 99
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Partial mapping / Deleting a map partially


The overlaying or new recording of the map does not necessarily cover the complete
measuring range. Instead a partial mapping can be performed.
• The mapping starts at –0.25 m (–0.8 ft), i.e. above the reference point.
• The end point of the mapping range can be defined in the Mapping end point
parameter.
After these settings, the recording of the mapping curve is started as decribed above.

The map can also be partially deleted. This is performed as follows:


1. Enter the end point of the area to be deleted into the Mapping end point parameter.
2. Go to the Record map parameter and select the Delete partial map option.

100 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Mapping in the tank bottom area


Irrespective of the definded mapping range, no mapping is recorded near the end of the
measuring range (defined in Expert → Sensor → Level → Tank/silo height). The range
for which this is the case, is defined in the Map gap parameter. In this gap the map
assumes a constant value as defined by the End of mapping and End mapping amplitude
parameters:

"End of mapping" = "Last map value"


With this setting the last value of the map remains valid within the Map gap.

1=
2=
A [dB]
4

t
3

A0020647

1 Envelope curve
2 Map
3 Tank/silo height
4 Map gap

"End of mapping" = "Adjustable"


With this setting the value of the mapping curve within the Map gap is defined in the End
mapping amplitude paramter.

1=
2=
A [dB]
4
5

t
3

A0020648

1 Envelope curve
2 Map
3 Tank/silo height
4 Map gap
5 End mapping amplitude

Endress+Hauser 101
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Parameters of the "Mapping" submenu

On the local display


In the first part of the Mapping submenu two parameters are displayed on the local
display at the same time. The upper parameter can be edited. The lower parameter is
displayed for reference purposes only.

Parameter Meaning Description

Confirm distance Confirm whether the displayed distance (→  104)


matches the actual distance.

Distance Displays the currently measured distance (→  104)

Mapping end point Defines the distance up to which the map is (→  105)
recorded.

Present mapping Indicates the distance up to which a mapping (→  105)


has already been recorded.

Record map Starts the recording of the map (→  105)

Mapping end point Indicates the distance up to which the map is (→  105)
recorded.

Distance Displays the currently measured distance (→  104)

Present mapping Indicates the distance up to which a mapping (→  105)


has already been recorded.

End of mapping Defines the behavior or the map in the Map (→  106)
gap.

End mapping amplitude Amplitude of the map in the Map gap (→  106)

102 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

In the operating tool (e.g. FieldCare)

Parameter Meaning Description

Distance Displays the currently measured distance (→  104)

Confirm distance Confirm whether the displayed distance (→  104)


matches the actual distance.

Present mapping Indicates the distance up to which a mapping (→  105)


has already been recorded.

Mapping end point Defines the distance up to which the map is (→  105)
recorded.

Record map Starts the recording of the map (→  105)

End of mapping Defines the behavior or the map in the Map (→  106)
gap.

End mapping amplitude Amplitude of the map in the Map gap (→  106)

Endress+Hauser 103
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Description of parameters

Confirm distance (1045)

Navigation Expert → Sensor → Mapping → Confirm distance

Write access Maintenance

Description Confirmation whether the measured distance matches the actual distance. Depending on
the selection the device automatically determines the range over which the mapping will
be recorded.

Options • Manual map


To be selected if the range of mapping is to be defined manually in the Mapping end
point parameter. In this case it is not necessary to confirm the distance.
• Distance ok
To be selected if the measured distance matches the actual distance. The device
performs a mapping and quits the sequence ("End of sequence" appears on the display).
• Distance unknown
To be selected if the actual distance is unknown. A mapping can not be performed and
the device quits the sequence ("End of sequence" appears on the display).
• Distance too small
To be selected if the measured distance is smaller than the actual distance. The device
searches the next echo and returns to the Confirm distance parameter. The new
distance is displayed. The comparison must be repeated until the displayed distance
matches the actual distance. If this is the case, the recording of the map can be started
by selecting Distance ok.
• Distance too big 1)
To be selected if the measured distance is bigger than the actual distance. The device
adjusts the signal evaluation and returns to the Confirm distance parameter. The
distance is recalculated and displayed. The comparison must be repeated until the
displayed distance matches the actual distance.
• Tank empty
To be selected if the tank is completely empty. The device records a mapping covering
the complete length of the probe and quits the sequence ("End of sequence" appears on
the display).
• Factory map
To be selected if the present mapping curve (if one exists) is to be deleted and the
factory map is to be used instead. The device returns to the Confirm distance parameter
and a new mapping can be recorded.

1) Only available for "Expert → Sensor → Echo tracking → Evaluation mode" = "Short time history" or "Long time history".

Factory setting Distance unknown

Additional information On the local display the measured distance is displayed together with this parameter.
If the teaching procedure Distance too small or Distance too big is quit before the
distance has been confirmed, a map is not recorded and the teaching procedure is
reset after 60 s.

Distance (1124)

104 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Navigation Expert → Sensor → Mapping → Distance

Write access Read-only parameter

Description Displays the currently measured distance.

Mapping end point (1022)

Navigation Expert → Sensor → Mapping → Mapping end point

Write access Maintenance

Prerequisite Only visible if the Manual map option has been selected in the Confirm distance
parameter.

Description Definition of the distance up to which the mapping curve will be recorded.

Input range 0.1 m (0.33 ft) to Tank/silo height

Factory setting 0.1 m (0.33 ft)

Additional information The distance is measured from the reference point, i.e. from the lower edge of the
mounting flange or the threaded connection.
On the local display the Present mapping parameter is displayed together with this
parameter. Present mapping states up to which distance a mapping has already been
recorded.

Present mapping (1182)

Navigation Expert → Sensor → Mapping → Present mapping

Write access Read-only parameter

Description Indicates up to which distance a mapping has already been recorded.

Record map (1069)

Navigation Expert → Sensor → Mapping → Record map

Write access Maintenance

Prerequisite Only visible if a value has been entered into the Mapping end point parameter.

Description Starts the recording of the map.

Endress+Hauser 105
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Selection • No
The map is not recorded. The device quits the sequence ("End of sequence" is displayed).
• Record map
The map is recorded. When the recording is completed, the new measured distance and
the new mapping range appear on the display. These values must be confirmed by
pressing . The device quits the sequence. ("End of sequence" is displayed.)
• Overlay map
The new map is generated by overlaying the existing map by the envelope curves taken
from the period defined in the Mapping overlay time parameter.
• Factory map
The map permanently stored in the device is used.
• Delete partial map
The map is deleted between the points defined by Mapping start point and Mapping
end point.

Factory setting No

End of mapping (1224)

Navigation Expert → Sensor → Mapping → End of mapping

Write access Maintenance

Description Defines the behavior of the map at within the defined Map gap.

Options • Adjustable (0 ... 342)


• Last map value

Factory setting Adjustable (342)

End mapping amplitude (1109)

Navigation Expert → Sensor → Mapping → End map. ampl.

Write access Maintenance

Description Amplitude of the map within the Map gap

Input range –99 999 to 99 999 dB

Factory setting –90 dB

106 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

3.2.14 Expert → Sensor → Tank bottom evaluation

Overview
The tank bottom evaluation is intended to prevent an echo loss if the tank is empty.

A [dB] 4
5

3
D [m (ft)]
1 2

4
A0020631

1 Tank/silo height
2 Tank bottom range
3 Min. amplitude TBD
4 Lower level area
5 Tank bottom echo

I no echo is found within the defined tank height (Tank/silo height parameter 4)), the
tank bottom searches beyond this distance in the Tank bottom range to see whether an
echo from the tank bottom exists.
If a tank bottom echo has been found, a level of 0% is assumed. If neither a direct level
echo nor a tank bottom echo has been found, an echo loss is reported (error message
S941).
• Level echoes from within the measruing range always have a higher priority than
the tank bottom echo.
• The first echo factor is not applied to the tank bottom echo.

Parameters of the "Tank bottom evaluation" submenu


Parameter Meaning Description

Tank bottom range Defines the range below Tank/silo height in which a tank bottom echo is (→  108)
searched for if no direct level echo has been detected.

4) Navigation path: Expert → Sensor → Level → Tank/silo height

Endress+Hauser 107
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Description of parameters

Tank bottom range (1149)

Navigation Expert → Sensor → Tank bottom evaluation → Tank bottom range

Write access Maintenance

Description Defines the range (starting from Tank/silo height) in which the tank bottom echo is
searched for.

Input range 0 to 99.999 m (0 to 328 ft)

Factory setting 1 m (3.28 ft)

Min. amplitude TBD (1189)

Navigation Expert → Sensor → Tank bottom evaluation → Min. ampl. TBD

Write access Service

Description Defines the threshold for tank bottom echoes.

Input range 0 to 9 999 dB

Factory setting 15 dB

Lower level area (1225)

Navigation Expert → Sensor → Tank bottom evaluation → Lower level area

Write access Service

Description Defines the range in which the last measured level must have been before a tank bottom
echo evaluation is performed.

Input range 0 to 200 m (0 to 656.17 ft)

Factory setting 1 m (3.28 ft)

108 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

3.2.15 Expert → Sensor → Echo tracking

Basic principles of the echo tracking


Three types of echo evaluation can be selected in the Evaluation mode parameter:

Evaluation mode "History off"


The envelope curve is evaluated statically. First echo criteria are taken into consideration
(see the Expert → Sensor → First echo factor submenu).

Evaluation mode "Short time history"


The static envelope curve evalauation is taken as a starting point.
The position of the individual echoes is tracked. The track contains the position, the
velocity, the relative and the absolute echo amplitude. Normally the strongest echo within
a search window is selected and allocated to the track.

t1 A

D1 D

t2 A a D
D3
D2
D1

D2 D
t1 t2 t3 t

t3 A a

D3 D

A0018587

 18 Definition of a track: In a new envelope curve, the echo is searched for in a window of width "a" centered
around the echo position in the previous envelope curve. The change of the echo position in the course of
time defines the track.

Evaluation mode "Long time history" (only available for level measurements)
A so-called tank history is used for the determination of the level and a consistency check
of the echoes. For a given tank with a given medium, the positions of the level, interface,
multiple and end-of-probe or tank bottom echoes are in a defined relation to each other.
This relationship is recorded during the operation of the device and stored in the tank
history. On the basis of this tank history, echoes can be reliably allocated, even if one echo
is lost temporarily or if the device was switched off for a while.

Endress+Hauser 109
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Schematic exmaples

[mV]
1 2 3

D1

D1

6
5 4

D0
A0020671

 19 Example 1: Tank history with interference echo and tank-bottom echo


D0 Actual level distance
D1 Distance of the signal in the envelope curve
1 Level echo
2 Interference echo
3 Tank-bottom echo
4 Track "Tank-bottom echo" (stored in the tank history)
5 Track "Level echo" (stored in the tank history)
6 Track "Interference echo" (stored in the tank history)

[mV] 1
2

D1

D1
3

D0
A0020672

 20 Example 2: Tank history with a multiple echo


D0 Actual level distance
D1 Distance of the signal in the envelope curve
1 Level echo
2 Multiple echo
3 Track "Multiple echo" (stored in the tank history)
4 Track "Level echo" (stored in the tank history)

110 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

The parameters of the "Echo tracking" submenu

Parameter Bedeutung Beschreibung

Evaluation mode Selection of the type of signal evaluation: (→  112)


• History off
• Short time history
• Long time history

History reset Reset of the echo tracking; options: (→  112)


• Restart echo tracking
The echo tracking is reset but the tank history remains stored.
• Delete history
The echo tracking and the tank history are reset.

History learning Only for PROFIBUS PA and FOUNDATION Fieldbus devices (→  112)
control Defines which DO block is used to activate or deactivate the recording of the
tank history.

History learning Only for PROFIBUS PA and FOUNDATION Fieldbus devices (→  113)
Activates or deactivates the recording of the tank history (if the Manual
option has been selected in the History learning control parameter.

Endress+Hauser 111
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Description of the parameters

Evaluation mode (1112)

Navigation Expert → Sensor → Echo tracking → Evaluation mode

Write access Maintenance

Description Selection of the evaluation mode for echo tracking.

Options • History off


The envelope curve is evaluated only statically.
• Short time history
In addition to the static algorithms a dynamic echo trace is continuously created.
• Long time history
In addition to the static algorithms and the dynamic echo trace a tank trace is
continuously created. Using the tank trace the device can determine the level even if the
level echo ist lost temporarily.

Factory setting The Evaluation mode parameter is preset depending on the Tank type or Bin type
parameter, respectively.

History reset (1145)

Navigation Expert → Sensor → Echo tracking → History reset

Write access Maintenance

Description Resets the history of the echo and tank tracking.

Options • Reset done


Does not initiate an action but is only a display option. It is displayed as soon as the reset
operation has been accomplished.
• Reset echo tracking
The echo tracking is reset. The tank trace, however, is maintained.
• Delete history
The echo tracking and tank trace are reset.

Factory setting Reset done

History learning control (1074)

Navigation Expert → Sensor → Echo tracking → Hist. learn.ctrl

Write access Maintenance

Prerequisite Only available for PROFIBUS PA and FOUNDATION Fieldbus devices

112 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Description Defines, which DO block is used to start and stop the recording of the tank track.

Options • Manual
• Digital output 1
• Digital output 2
• Digital output 3
• Digital output 4

Factory setting Manual

History learning (1094)

Navigation Expert → Sensor → Echo tracking → History learning

Write access Maintenance

Prerequisite Only available for PROFIBUS PA and FOUNDATION Fieldbus devices

Description Starts and stops the recording of the echo track (in case the Manual option has been
selected in the History learning control parameter.

Options • Off
• On

Factory setting On

Endress+Hauser 113
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

3.2.16 Expert → Sensor → External input


The External input submenu is only available on devices with PROFIBUS PA or
FOUNDATION Fieldbus.

Overview
The behavior of the sensor can be controlled via two external switch inputs: measurement
can be switched on and off. Furthermore, a specific value can be assigned to the level when
the digital switch signal is present, regardless of the actual filling height.

The parameters

Level external input 1/2 (2305/2306)

Navigation Expert → Sensor → External input → Level external input 1/2

Write permission Maintenance

Description External input 1 or 2 is assigned a DO block via which the switch signal is read in.

Options • None
• Digital output 1
• Digital output 2
• Digital output 3
• Digital output 4

Factory setting None

Function input 1/2 level (2311/2331)

Navigation Expert → Sensor → External input → Function input 1/2 level

Write permission Maintenance

Description Defines the response of the level to the presence of a switch signal at external input 1 or 2.

Options • Off
• Minimum (0%)
• Maximum (100%)
• Hold last value
• Fixed value

Factory setting Off

Fixed value input 1/2 (2332/2333)

Navigation Expert → Sensor → External input → Fixed value input 1/2

114 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Write permission Maintenance

Prerequisite Only visible if Function input 1/2 level = Fixed value

Description Defines the level value in the event of a switch signal at external input 1 or 2.

User entry 0 to 200 000

Factory setting 0

Additional information The specific unit after linearization that has been selected applies.

Control measurement (1083)

Navigation Expert → Sensor → External input → Control measurement

Write permission Maintenance

Description Specifies the DO block via which measurement can be switched on and off.

Options • Manual
• Digital output 1
• Digital output 2
• Digital output 3
• Digital output 4

Factory setting Manual

Measurement (1082)

Navigation Expert → Sensor → External input → Measurement

Write permission Maintenance

Description Is used to switch measurement on and off manually.

Options • On
• Off

Factory setting On

Endress+Hauser 115
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

3.3 Expert → Output

3.3.1 Expert → Output → Switch output

Switch output function (0481)

Navigation Expert → Output → Switch output → Switch output function

Description Defines the function of the switch output (open collector).

Options • Off
The output is always open (not conductive).
• On
The output is always closed (conductive).
• Event level
The output is normally closed and is only opened if a diagnostic event is present. The
Assign diagnostic level parameter (→  116)determines for which type of event the
output is opened.
• Limit
The output is normally closed and is only opened if a measured varaible exceeds or falls
below a defined limit. The limit values are defined by the parameters Assign
limit(→  116), Switch-on value(→  117)and Switch-off value(→  117).
• Digital output
The switching state of the output tracks the output value of a DI function block or the DI
output of the advanced diagnostics. The function block is selected in the Assign status
parameter.

Factory setting Off

Assign diagnostic level (0482)

Navigation Expert → Output → Switch output → Assign diagnostic level

Prerequisite Only visible for Switch output function = Event level.

Description Defines to which class of diagnostic events the output reacts.

Options • Alarm
• Alarm + warning
• Warning

Factory setting Alarm

Assign limit (0483)

Navigation Expert → Output → Switch output → Assign limit

116 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Prerequisite Only visible for Switch output function = Limit.

Description Defines the variable to be checked for limit transgression and allocates it to the switch
output.

Options • Off
No measured variable is allocated.
• Level linearized
• Distance
• Terminal voltage
• Electronic temperature
• Relative echo amplitude

Factory setting Off

Switch-on value (0466)


Switch-off value (0464)

Navigation Expert → Output → Switch output → Switch-on value / Switch-off value

Prerequisite Only visible for Switch output function = Limit and Assign limit ≠ Off.

Description Define the switch-on point and switch-off point for the limit evaluation.

Range of values Depending on the selected measuring variable (Parameter Assign limit).

Factory setting Depending on the selected measuring variable (Parameter Assign limit).

Endress+Hauser 117
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Additional information The switching behavior depends on the relative position of the two switch points.
Switch-on point > Switch-off point:
The output is closed if the measured value exceeds the switch-on point.
The output is opened if the measured value falls below the switch-off point.

B
t

D
t

A0015585

A Switch-on point
B Switch-off point
C Output closed
D Output opened

Switch-on point < Switch-off point:


The output is closed if the measured value falls below the switch-on point.
The output is opened if the measured value exceeds the switch-off point.

A
t

D
t

A0015586

A Switch-on point
B Switch-off point
C Output closed
D Output opened

Assign status (0485)

Navigation Expert → Output → Switch output → Assign status

118 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Prerequisite Only visible for Switch output function = Digital output.

Description Allocates a DI block or the DI output of the advanced diagnostics to the switch output.

Options • Off
No digital block is allocated.
• Digital output AD 1
• Digital output AD 2
• Digital output 1
• Digital output 2
• Digital output 3
• Digital output 4

Factory setting Off

Switch-on delay (0467)

Navigation Expert → Output → Switch output → Switch-on delay

Prerequisite Only visible for Switch output function = Limit and Assign limit ≠ Off.

Description Defines the delay for the switching on of the output.

Range of values 0 to 100 s

Factory setting 0s

Switch-off delay (0465)

Navigation Expert → Output → Switch output → Switch-off delay

Prerequisite Only visible for Switch output function = Limit and Assign limit ≠ Off.

Description Defines the delay for the switching off of the output.

Range of values 0 to 100 s

Factory setting 0s

Switch output failure mode (0486)

Navigation Expert → Output → Switch output → Switch output failure mode

Description Defines the switching state of the output in the case of an error.

Endress+Hauser 119
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Options • Actual status


The switch output remains in the state it was in when the error occurred
• Open
• Closed

Factory setting Open

Switch status (0461)

Navigation Expert → Output → Switch output → Switch status


Diagnostics → Measured value → Switch status

Description Indicates the current state of the switch output.

Display options • Open


• Closed

Invert output signal (0470)

Navigation Expert → Output → Switch output → Invert output signal

Description Allows to invert the behavior of the switch output.

Options • No
The behavior of the switch output is as described above.
• Yes
The states Opend and Closed are inverted as compared to the description above.

120 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

3.4 Expert → Communication

3.4.1 Expert → Communication → Resource block


This submenu contains the parameters of the Resource Block according to the
FOUNDATION Fieldbus specification.

Endress+Hauser 121
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

3.5 The "Analog inputs" submenu


There is an Analog input N submenu for each Analog Input Block of the device. This
submenu contains all parameters of the Analog Input Block according to the
FOUNDATION Fieldbus specification.

122 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

3.6 The "Discrete inputs" submenu


There is a Discrete input N submenu for each Discrete Input Block of the device. This
submenu contains all parameters of the Discrete Input Block according to the
FOUNDATION Fieldbus specification.

Endress+Hauser 123
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

3.7 The "Analog outputs" submenu


The Multiple analog output submenu contains the parameters of the Multiple Analog
Output Block according to the FOUNDATION Fieldbus specification.

124 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

3.8 The "Discrete outputs" submenu


The Multiple discrete output submenu contains the parameters of the Multiple Discrete
Output Block according to the FOUNDATION Fieldbus specification.

Endress+Hauser 125
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

3.9 Expert → Diagnostics

Actual diagnostics (0691)

Write access Read-only parameter

Navigation Expert → Diagnostics → Actual diagnostics

Description Use this function to display the current diagnostics message. If two or more messages
occur simultaneously, the message with the highest priority is shown on the display.
Information on what is causing the message, and remedy measures, can be viewed via
the symbol on the display.

User interface Symbol for event behavior, diagnostics event, time the event occurred and event text

Additional information User interface


Example for display format:
S441 01d4h12min30s
Current output 1

Previous diagnostics (0690)

Write access Read-only parameter

Navigation Expert → Diagnostics → Previous diagnostics

Description Use this function to display the diagnostics message last displayed before the current
message. This condition can still apply.
Information on what is causing the message, and remedy measures, can be viewed via
the symbol on the display.

User interface Symbol for event behavior, diagnostics event, time the event occurred and event text

Additional information User interface


Example for display format:
C411 01d5h14min20s
Upload/download active

Operating time from restart (0653)

Write access Read-only parameter

Navigation Expert → Diagnostics → Operating time from restart

126 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Description Use this function to display the time the device has been in operation since the last device
restart.

User interface Days (d), hours (h), minutes (m) and seconds (s)

Operating time (0652) (→  31)

Endress+Hauser 127
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

3.9.1 Expert → Diagnostics → Diagnostics list

Diagnostics 1 - 5 (0692 - 0696)

Write access Read-only parameters

Navigation Expert → Diagnostics → Diagnostics list → Diagnostics 1


Expert → Diagnostics → Diagnostics list → Diagnostics 2
Expert → Diagnostics → Diagnostics list → Diagnostics 3
Expert → Diagnostics → Diagnostics list → Diagnostics 4
Expert → Diagnostics → Diagnostics list → Diagnostics 5

Description Use this function to display the current diagnostics messages with the highest priority to
the fifth-highest priority.

Unser interface Symbol for event behavior, diagnostics event and event text

Additional information User interface


Example 1 for display format:
S441 01d4h12min30s
Current output 1

Example 2 for display format:


F276 10d8h12min22s
I/O module error

Timestamp (0683 - 0687)

Write access Read-only parameters

Navigation Expert → Diagnostics → Diagnostics list → Timestamp

Description Displays the operating time at which the diagnostic message occurred.

128 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

3.9.2 Expert → Diagnostics → Event logbook

Filter options (0705)

Write access Maintenance

Navigation Expert → Diagnostics → Event logbook → Filter options

Description Use this function to select the category whose event messages are displayed in the events
list.
The status signals are categorized according to NAMUR NE 107: F = failure, M =
maintenance request, C = function check, S = out of specification

Options • All
• Failure (F)
• Mainenance required (M)
• Function check (C)
• Out of specification (S)
• Information (I)

Factory setting All

Event list

Navigation Expert → Diagnostics → Event logbook → Event list

Description Use this function to display the history of event messages of the category selected in the
Filter options parameter (→  129). A maximum of 20 event messges are displayed in
chronological order. If the advanced HistoROM function is enabled in the device, the event
list can contain up to 100 entries.
The following symbols indicate whether an event has occurred or has ended:
• : Event has occurred
• : Event has ended
Information on what is causing the message, and remedy measures, can be viewed via
the -button.

User interface • For event messages in category I: information event, event text, "recording event" symbol
and time event occurred
• For event messages in category F, M, C, S (status signal): diagnostic event, event text,
"recording event" symbol and time event occurred

Endress+Hauser 129
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Additional information User interface


Example 1 for display format:
I 1091 24d12h13m00s
Configuration modified

Example 2 for display format:


S441 01d4h12min30s
Current output 1

HistoROM
A HistoROM is a "non-volatile" device memory in the form of an EEPROM.

130 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

3.9.3 Expert → Diagnostics → Device information

Device (0011)

Write access Read-only parameter

Navigation Expert → Diagnostics → Device information → Device

Description Use this function to view the device designation.

Serial number (0009)

Write access Read-only parameter

Navigation Expert → Diagnostics → Device information → Serial number

Description Use this function to view the serial number of the device. It can also be found on the
nameplate.
Uses of the serial number
• To identify the device quickly, e.g. when contacting Endress+Hauser.
• To obtain specific information on the device using the Device Viewer:
www.endress.com/deviceviewer

User interface Max. 11-digit character string comprising letters and numbers

Firmware version (0010)

Write access Read-only parameter

Navigation Expert → Diagnostics → Device information → Firmware version

Description Use this function to view the device firmware version installed.

Anzeige Max. 6-digit character string in the format xx.yy.zz

Device name (0013)

Write access Read-only parameter

Navigation Expert → Diagnostics → Device information → Device name

Description Use this function to view the name of the device. It can also be found on the nameplate.

Endress+Hauser 131
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Extended order code (10795)

Write access Read-only parameter

Navigation Expert → Diagnostics → Device information → Extended order code

Description Use this function to view the order code of the device. It can also be found on the
nameplate.
Uses of the order code
• To order an identical spare device.
• To identify the device quickly and easily, e.g. when contacting Endress+Hauser.

Extended order code 1/2 (10796/10797)

Write access Read-only parameter

Navigation Expert → Diagnostics → Device information → Extended order code 1


Expert → Diagnostics → Device information → Extended order code 2

Description Use these parameters to display the fist and second part of the extended order code. On
account of length restrictions, the extended order code is split into a maximum of 2
parameters.
The extended order code indicates the version of all the features of the product structure
for the device and thus uniquely identifies the device. It can also be found on the
nameplate.
Uses of the extended order code
• To order an identical spare device
• To check the ordered device features against the shipping note.

ENP version (0012)

Write access Read-only parameter

Navigation Expert → Diagnostics → Device information → ENP version

Description Use this function to view the version of the electroni nameplate (ENP).

User interface 6-digit number in the format xx.yy.zz

Hardware revision (10793)

Write access Read-only parameter

132 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Navigation Expert → Diagnostics → Device information → Hardware revision

Description Displays the hardware revision of the device.

ITK Version (10794)

Write access Read-only parameter

Navigation Expert → Diagnostics → Device information → ITK Version

Description Displays the ITK Version of the device.

Device type (10711)

Write access Read-only parameter

Navigation Expert → Diagnostics → Device information → Device type

Description Displays the Device type.

Device Revision (10710)

Write access Read-only parameter

Navigation Expert → Diagnostics → Device information → Device Revision

Description Displays the Device Revision.

DD Revision (10709)

Write access Read-only parameter

Navigation Expert → Diagnostics → Device information → DD Revision

Description Displays the DD Revision.

Endress+Hauser 133
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

3.9.4 Expert → Diagnostics → Data logging


The menu is only displayed if the extended function of the HistoROM is enabled in the
device.

Assign channel 1 -4 (0851 - 0854)

Write access Maintenance

Navigation Expert → Diagnostics → Data logging → Assign channel 1


Expert → Diagnostics → Data logging → Assign channel 2
Expert → Diagnostics → Data logging → Assign channel 3
Expert → Diagnostics → Data logging → Assign channel 4

Description Use this functionto assign a process variable to the data logging channel.
A total of 500 measured values can be logged. This means:
• 500 data points if 1 logging channel is used
• 250 data points if 2 logging channels are used
• 166 data points if 3 logging channels are used
• 125 data points if 4 logging channels are used
Once the maximum number of data points is reached, the oldest data points in the data log
are cyclically overwritten in such a way that the last 500, 250, 166 or 125 measured
values are always in the log (ring memory principle).
The log contents are cleared if the option selected is changed.

Auswahl • Off
• Level
• Distance
• Current output 1
• Measured current
• Terminal voltage
• Electronics temperature
• Absolute echo amplitude
• Relative echo amplitude
• Signal noise

Factory setting Off

Logging interval (0856)

Write access Maintenance

Navigation Expert → Diagnostics → Data logging → Logging interval

134 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Description Definition of the logging interval tlog for data logging. This defines the interval between
the individual data points in the data log, and thus the maximum loggable process time
Tlog.
• If 1 logging channel is used: T log = 500 ⋅ t log
• If 2 logging channels are used: T log = 250 ⋅ t log
• If 3 logging channels are used: T log = 166 ⋅ t log
• If 4 logging channels are used: T log = 125 ⋅ t log
Once this time elapses, the oldest data points in the data log are cyclically overwritten such
that a time of Tlog always remains in the meory (ring memory principle).
Nach Ablauf dieser Zeit werden die ältesten im Speicher vorhandenen Datenpunkte
zyklisch überschrieben, so dass immer eine Zeit von Tlog im Speicher bleibt (Ringspeicher-
Prinzip).
The log contents are cleared if the length of the logging interval is changed.

Input range 1 to 3600 s

Factory setting 10 s

Additional information Example


If 1 logging channel is used:
• Tlog = 500 ⋅ 1 s = 500 s ≈ 8.5 min
• Tlog = 500 ⋅ 10 s = 5 000 s ≈ 1.5 h
• Tlog = 500 ⋅ 80 s = 40 000 s ≈ 11 h
• Tlog = 500 ⋅ 3 600 s = 1 800 000 s ≈ 20 d

Clear logging data (0855)

Write access Maintenance

Navigation Expert → Diagnostics → Data logging → Clear logging data

Description Use this function to clear the entire logging data.

Options • Cancel
The data are not cleared. All the data are retained.
• Clear data
The logging data are cleared. The logging process starts from scratch.

Factory setting Cancel

Display channel 1 - Display channel 4

Navigation Expert → Diagnostics → Data logging → Display channel 1


Expert → Diagnostics → Data logging → Display channel 2
Expert → Diagnostics → Data logging → Display channel 3
Expert → Diagnostics → Data logging → Display channel 4

Endress+Hauser 135
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Description Use this function to view the measured value trend for the logging channel in the form of a
chart.

A0013859

• x-axis: depending on the number of channels selected displays 250 to 1000 measured
values of a process variable.
• y-axis: displays the approximate measured value span and constantly adapts this to the
ongoing measurement.
The process variable whose measured valu curve is displayed is specified in the Assign
channel 1 - Assign channel 4 parameters (→  134).

136 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

3.9.5 Expert → Diagnostics → Min/Max values

Max. level value (2357)

Write access Display-only parameter

Navigation Expert → Diagnostics → Min/max values → Max. level value

Description Use this parameter to view the maximum level measured until now (drag indicator).

Time max. level (2385)

Write access Read-only parameter

Navigation Expert → Diagnostics → Min/max values → Time max. level

Description Use this parameter to view the operating time at which the maximum level has been
measured.

Min. level value (2358)

Write access Read-only parameter

Navigation Expert → Diagnostics → Min/max values → Min. level value

Description Use this parameter to view the minimum level measured until now (drag indicator).

Time min. level (2386)

Write access Read-only parameter

Navigation Expert → Diagnostics → Min/max values → Time min. level

Description Use this parameter to view the operating time at which the minimum level has been
measured.

Max. draining speed (2320)

Write access Read-only parameter

Endress+Hauser 137
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Navigation Expert → Diagnostics → Min/max values → Max. draining speed

Description Use this parameter to view the maximum draining speed measured until now (drag
indicator).

Max. filling speed (2360)

Write access Read-only parameter

Navigation Expert → Diagnostics → Min/max values → Max. filling speed

Description Use this parameter to view the maximum filling speed measured until now (drag
indicator).

Reset min./max. (2324)

Write access Service

Navigation Expert → Diagnostics → Min/max values → Reset min./max.

Description Resets the drag indicator of the selected process variable.


Access to this parameter is reserved to the Endress+Hauser service staff. It can only be
accessed after entering the service code.

Max. electronics temperature (1031)

Write access Read-only parameter

Navigation Expert → Diagnostics → Min/max values → Max. electronics temperature

Description Use this parameter to view the maximum electronics temperature measured until now
(drag indicator).

Time max. electronics temperature (1204)

Write access Read-only parameter

Navigation Expert → Diagnostics → Min/max values → Time max. electronics temperature

Description Use this parameter to view the operating time at which the maximum electronics
temperature has been measured.

138 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Min. electronics temperature (1040)

Write access Read-only parameter

Navigation Expert → Diagnostics → Min/max values → Min. electronics temperature

Description Use this parameter to view the minimum electronics temperature measured until now
(drag indicator).

Time min. electronics temperature (1205)

Write access Read-only parameter

Navigation Expert → Diagnostics → Min/max values → Time min. electronics temperature

Description Use this parameter to view the operating time at which the minimum electronics
temperature has been measured.

Reset min./max. temperature (1173)

Write access Service

Navigation Expert → Diagnostics → Min/max values → Reset min./max. temperature

Description Resets the drag indicator of the electronics temperature.


Access to this parameter is reserved to the Endress+Hauser service staff. It can only be
accessed after entering the service code.

Endress+Hauser 139
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

3.9.6 Expert → Diagnostics → Simulation

Assign simulation process variable (2328)

Write access Maintenance

Navigation Expert → Diagnostics → Simulation → Assign proc. var.

Description Use this function to select a process variable for the simulation process that is activated.
The display alternates between the measured value and a diagnostics message of the
"function check" category (C) while simulation is in progress.
The simulation value of the selected process variable is defined in the Value process
variable parameter.

Options • Off
• Level
• Level linearized

Factory setting Off

Value process variable (2329)

Write access Maintenance

Navigation Expert → Diagnostics → Simulation → Value proc. var.

Prerequisite One of the following options is selected in the Assign simulation process variable
parameter:
• Level
• Level linearized

Beschreibung Use this function to enter a simulation value for the selected process variable. Subsequent
measured value processing and the signal output use this simulation value. In this way,
users can verify whether the measuring device has been configured correctly.

Input range Depends on the process variable selected

Factory setting The current value of the selected process variable at the moment the simulation is
activated.

Switch output simulation (0462)

Navigation Expert → Diagnostics → Simulation → Switch output simulation

Description Use this parameter to activate or deactivate the simulation of the switch output.

140 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Auswahl • Off
• On

Werkseinstellung Off (i.e. no simulation)

Switch status (0463)

Navigation Expert → Diagnostics → Simulation → Switch status

Prerequisite Only visible for Switch output simulation = On.

Description Use this parameter to define the switch status for the simulation.

Auswahl • Open
• Closed

Werkseinstellung Open

Simulation device alarm (0654)

Navigation Expert → Diagnostics → Simulation → Simulation device alarm

Description Use this function to switch the device alarm on and off. In this way, users can verify the
correct adjustment of the current output and the correct function of downstream switching
units.
The display alternates between the measured value and a diagnostics message of the
"function check" category (C) while simulation is in progress:

Options • On
• Off

Factory setting Off

3.9.7 Expert → Diagnostics → Device check

Start device check (1013)

Write access Maintenance

Navigation Expert → Diagnostics → Device check → Start device check

Description Start of a device check.

Endress+Hauser 141
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Selection • No
No device check is performed.
• Yes
A device check is performed.
If the error S941 "Echo lost" is present, a device check is not possible. First you have to
eliminte the cause of this error.

Factory setting No

Result device check (1014)

Write access Read-only parameter

Navigation Expert → Diagnostics → Device check → Result device check

Description Indicates the result of the device check.

Display • Installation ok
• Accuracy reduced
A measurement is possible. However, the measuring accuracy may be reduced due to the
signal amplitudes.
• Measurement capability reduced
A measurement is currently possible. Howerver, there is the risk of an echo loss. Check
the mounting position of the device and the dielectric constant of the medium.
• Check not done

Last check time (1203)

Write access Read-only parameter

Navigation Expert → Diagnostics → Device check → Last check time

Description Displays the operating time at which the last device check has been performed.

Additional information Display format


Days (d), hours (h), minutes (m), seconds (s): 0000d00h00m00s

Level signal (1016)

Write access Read-only parameter

Navigation Expert → Diagnostics → Device check → Level signal

Prerequisite Only visible if a device check has been performed.

Description Displays the result of the device check for the level signal.

142 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Display • Check not done


• Check not ok
Check the mounting position of the device and the dielectric constant of the medium.
• Check ok

Area of incoupling (1186)

Write access Read-only parameter

Navigation Expert → Diagnostics → Device check → Area of incoupling

Description Indicates the area of ringing zone.

Endress+Hauser 143
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

3.9.8 Expert → Diagnostics → Advanced diagnostics 1/2

Basic principles
The Advanced Diagnostics offers additional options to monitor the process. The device
contains two Advanced Diagnostics Blocks which can be used separately or in combination.
A measuring variable can be assigned to the input of each Advanced Diagnostics Block.
Based on a freely configurable time interval, the variable can be submitted to a statistical
function (e.g. maximum, minimum, mean, slope). Finally, a limit detection can be
parametrized and its result can be transmitted to a digital output.
The result can be displayed and evaluated by a DCS or PLC. If required, it can also be linked
to the second Advanced Diagnostics block and thus it is possible to combine the two results
by the logical operators AND or OR.

144 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Application example: Foam detection


Preconditions
• The process runs at a fixed level (in the example: 80 %)
• If foam occurs during the operation, the vessel should automatically be sprinkled with
water from the top or an antifoam agent should be added to dissolve the foam.
Reaction of the radar signal in the case of foam formation
The echo amplitude decreases in the case of foam formation. This can be used by the
Advanced Diagnostics to detect the foam. The foam detection, however, should only be
active as long as the level is between 75 % and 85 %.

A A

85%

75%

A0019640

 21 Decrease of the amplitude in case of foam formation


A Amplitude threshold for foam detection

Step 1: Determination of the amplitude threshold


Observe the echo amplitude while the process is running at the given level (in the example:
80 %) and determine the lower limit for the amplitude (in the example: 10 dB).
The Maximum value 1/2(→  153) and Minimum value 1/2(→  153) parameters
can be used for this.

Step 2: Configuration of the level monitoring
In order to ensure that the level actually is in the vicinity of the given value: Configure
Advanced Diagnostics 1 as follows:
• Assign diagnostic signal 1 = Level linearized
• Check mode 1 = Out of range
Out of range checks whether the level is outside a defined range. As long as this is the
case, the block outputs "0" (INACTIVE). If the level gets into the defined range, the block
outputs "1" (ACTIVE).
• Upper limit 1 = 85 %
• Lower limit 1 = 75 %
With this setting, the output of Advanced Diagnostics 1 assumes the following value:
• 0 (INACTIVE) - if the level is outside the defined range (out of range).
• 1 (ACTIVE) - if the level is within the defined range. The foam detection should only be
active in this case.

Endress+Hauser 145
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Step 3: Configuration of the foam detection.


Configure Advanced Diagnostics 2 as follows:
• Assign diagnostic signal 2 = Relative echo amplitude
• Calculation type 2 = Mean
• Sample time 2 = 60 s
• Check mode 2 = Lower limit
• Lower limit 2 = 10 dB
With this setting Advanced Diagnostics 2 (internally) assumes the following value:
• 0 (INACTIVE) - if the amplitude exceeds 10 dB (i.e.: there is no foam)
• 1 (ACTIVE) - if the amplitude is below 10 dB (i.e.: foam detected).

Step 4: Configuration of the logic block linking
Configure Advanced Diagnostics 2 as follows:
• Link AD 2 to = Digital output AD 1
• Linking logic AD 2 = AND
With this setting, the output of Advanced Diagnostics 2 assumes the following value:
• 0 (INACTIVE) - if at least one of the two blocks is in the "0" (INACTIVE) status.
• 1 (ACTIVE) - if both blocks are in the "1" (ACTIVE) status.
For the example this means:
– A diagnostic signal is output, if the level is within the defined range and the signal
amplitude is below 10 dB. This signal can be linked to the status output of the device
(→  116).
– If, on the other hand, the level is out of the defined range or if the signal amplitude
exceeds 10 dB, no diagnostic signal is transmitted via the switch output.
The status can also be linked to the DI block and transmitted to the fieldbus.

146 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

A L

1
1.2 1.5 2.7 2.8
1.3 2.6
L 1.1
1.4

2
2.2 2.4

A 2.1 2.5

2.3

A0019641

 22 Configuration of the Advanced Diagnostics for foam detection


L Level
A Amplitude
1 Advanced diagnostics 1: Monitoring the level
1.1 "Assign diagnostic signal 1" = "Level linearized"
1.2 "Check mode 1" = "In range"
1.3 "Upper limit" = 85 %
1.4 "Lower limit" = 75 %
1.5 Digital output of Advanced Diagnostics 1
2 Advanced Diagnostics 2: Monitoring the amplitude
2.1 "Assign diagnostic signal 2" = "Relative echo amplitude"
2.2 "Calculation type 2" = "Mean"
2.3 "Sample time" = 60 s
2.4 "Check mode" = "Lower limit"
2.5 "Lower limit" = 10 dB
2.6 "Link AD 2 to" = "Digital output AD1"
2.7 "Linking logic AD 2" = "AND"
2.8 Digital output of Advanced Diagnostics 2

Endress+Hauser 147
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Overview of the parameters

Parameter Description

Assign diagnotic signal 1/2 (→  149)

Link AD 1/2 to (→  149)

Linking logic AD 1/2 (→  149)

Sample time 1/2 (→  150)

Calculation type 1/2 (→  150)

Check mode 1/2 (→  150)

Calculation unit 1/2 (→  151)

Upper limit 1/2 (→  151)

Lower limit 1/2 (→  152)

Hysteresis1/2 (→  152)

Maximum value 1/2 (→  153)

Minimum value 1/2 (→  153)

Reset Min./Max. 1/2 (→  153)

Assign status signal to AD event 1/2 (→  153)

Assign event behaviour 1/2 (→  154)

Alarm delay 1/2 (→  154)

148 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

The parameters

Assign diagnostic signal 1/2 (11179)

Navigation Expert → Diagnostics → Advanced diagnostics → Assign diagnostic signal 1/2

Write access Maintenance

Descriptions Assigns a measuring variable, which is needed for diagnostic purposes, to the Advanced
Diagnostics Block.

Options • None
• Level linearized
• Unfiltered distance
• Relative echo amplitude
• Electronic temperature
• Measured current
• Terminal voltage
• Area of incoupling

Factory setting None

Link AD 1/2 to (11180)

Navigation Expert → Diagnostics → Advanced diagnostics → Link AD 1/2 to

Write access Maintenance

Descriptions Links the Advanced Diagnostics Block 1 or 2 to the other Advanced Diagnostics Block in
order to include the linking logic into the configuration (→  144).

Options • None
• Digital output AD 1
• Digital output AD 2

Factory setting None

Linking logic AD 1/2 (11181)

Navigation Expert → Diagnostics → Advanced diagnostics → Linking logic AD 1/2

Write access Maintenance

Prerequisite Only visible if the Advanced Diagnostics Block has been linked to the digital oputput of the
other Advanced Diagnostics Block via the Link AD 1/2 to parameter.

Descriptions Defines the linking logic between the two Advanced Diagnostics Blocks AD1 and AD2.

Endress+Hauser 149
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Options • AND
• OR

Factory setting AND

Sample time 1/2 (11187)

Navigation Expert → Diagnostics → Advanced diagnostics → Sample time 1/2

Write access Maintenance

Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.

Descriptions Defines the scanning time in seconds for the calculation.

Input range 1 to 3 600 s

Factory setting 10 s

Calculation type 1/2 (11174)

Navigation Expert → Diagnostics → Advanced diagnostics → Calculation type 1/2

Write access Maintenance

Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.

Descriptions Defines, which quantity is derived from the assigned measured variable.

Options • Off
• Maximum
• Minimum
• Mean
• Standard deviation
• Difference Max. - Min.
• Slope

Factory setting Off

Additional information The calculation is performed based on the defined Sample time. (I.e. the maximum,
minimum, mean, standard deviation, difference max.-min. or average slope within the
sample time are calculated.)

Check mode 1/2 (11175)

150 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Navigation Expert → Diagnostics → Advanced diagnostics → Check mode 1/2

Write access Maintenance

Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.

Descriptions Defines the check mode.

Options • Off
• Upper limit
• Lower limit
• In range
• Out of range

Factory setting Off

Additional information If a calculation has been selected in the Calculation type parameter, the check does not
refer to the assigned measuring variable but to the quantity calculated from it.

Calculation unit 1/2 (11188)

Navigation Expert → Diagnostics → Advanced diagnostics → Calculation unit 1/2

Write access Operator

Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.

Descriptions Defines the unit for the selected Calculation type.

Options Depending on the selected Calculation type and the measuring variable selected in Assign
diagnostic signal.

Factory setting Depending on the selected Calculation type and the measuring variable selected in Assign
diagnostic signal.

Upper limit 1/2 (11182)

Navigation Expert → Diagnostics → Advanced diagnostics → Upper limit 1/2

Write access Maintenance

Prerequisite Only visible if one of the following options has been selected in the Check mode
parameter:
• Upper limit
• In range
• Out of range

Endress+Hauser 151
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Descriptions Defines the upper limit for the selected check mode.

Options Depending on the selected Calculation type and the measuring variable selected in Assign
diagnostic signal.

Factory setting Depending on the selected Calculation type and the measuring variable selected in Assign
diagnostic signal.

Lower limit 1/2 (11184)

Navigation Expert → Diagnostics → Advanced diagnostics → Lower limit 1/2

Write access Maintenance

Prerequisite Only visible if one of the following options has been selected in the Check mode
parameter:
• Lower limit
• In range
• Out of range

Descriptions Defines the lower limit for the selected check mode.

Options Depending on the selected Calculation type and the measuring variable selected in Assign
diagnostic signal.

Factory setting Depending on the selected Calculation type and the measuring variable selected in Assign
diagnostic signal.

Hysteresis 1/2 (11178)

Navigation Expert → Diagnostics → Advanced diagnostics → Hysteresis 1/2

Write access Maintenance

Prerequisite Only visible if one of the following options has been selected in the Check mode
parameter:
• Upper limit
• Lower limit
• In range
• Out of range

Descriptions Defines the hysteresis for the selected check mode.

Options Depending on the selected Calculation type and the measuring variable selected in Assign
diagnostic signal.

Factory setting Depending on the selected Calculation type and the measuring variable selected in Assign
diagnostic signal.

152 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Maximum value 1/2 (11183)

Navigation Expert → Diagnostics → Advanced diagnostics → Maximum value 1/2

Write access Read-only parameter

Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.

Descriptions Indicates the maximum value the assigned measuring variable has attained (dragging
indicator).

Minimum value 1/2 (11185)

Navigation Expert → Diagnostics → Advanced diagnostics → Minimum value 1/2

Write access Read-only parameter

Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.

Descriptions Indicates the minimum value the assigned measuring variable has attained (dragging
indicator).

Reset min./max. 1/2 (11186)

Navigation Expert → Diagnostics → Advanced diagnostics → Reset min./max. 1/2

Write access Maintenance

Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.

Description Resets the Maximum value and Minimum value dragging indicators.

Options • Off
• Reset max.
• Reset min.
• Reset min./max.

Factory setting Off

Assign status signal to AD event 1/2 (11176)

Endress+Hauser 153
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Navigation Expert → Diagnostics → Advanced diagnostics → Assign status signal to AD event


1/2

Write access Maintenance

Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.

Description Assigns an event category according to NAMUR NE107 to the event of the Advanced
Diagnostics Block.

Options • Failure (F)


• Maintenance required (M)
• Function check (C)
• Out of specification (S)

Factory setting Maintenance required (M)

Assign event behaviour 1/2 (11177)

Navigation Expert → Diagnostics → Advanced diagnostics → Assign event behaviour 1/2

Write access Maintenance

Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.

Description Assigns an event behavior to the event of the Advanced Diagnostics Block.

Options • Off
• Alarm
• Warning
• Logbook entry only

Factory setting Warning

Alarm delay 1/2 (11171)

Navigation Expert → Diagnostics → Advanced diagnostics → Alarm delay 1/2

Write access Maintenance

Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.

Description Assigns an event behavior to the event of the Advanced Diagnostics Block.

Input range 0 to 3 600 s

154 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu

Factory setting 10 s

Endress+Hauser 155
Index Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Index
A Decimal places 2 (Parameter) . . . . . . . . . . . . . . . . . . 25
Absolute echo amplitude (Parameter) . . . . . . . . . . . . 65 Decimal places 3 (Parameter) . . . . . . . . . . . . . . . . . . 25
Access status display (Parameter) . . . . . . . . . . . . . . . 18 Decimal places 4 (Parameter) . . . . . . . . . . . . . . . . . . 25
Access status tooling (Parameter) . . . . . . . . . . . . . . . 19 Decimal places menu (Parameter) . . . . . . . . . . . . . . . 28
Acknowledge alarm (Parameter) . . . . . . . . . . . . . . . . 94 Define access code (Parameter) . . . . . . . . . . . . . . . . . 35
Activate SW option (Parameter) . . . . . . . . . . . . . . . . 36 Delay time echo lost (Parameter) (Parameter) . . . . . . 92
Activate table (Parameter) . . . . . . . . . . . . . . . . . . . . . 63 Device (Parameter) . . . . . . . . . . . . . . . . . . . . . . . . . 131
Actual diagnostics (Parameter) . . . . . . . . . . . . . . . . 126 Device name (Parameter) . . . . . . . . . . . . . . . . . . . . 131
Advanced process conditions (Parameter) . . . . . . . . . 41 Device reset (Parameter) . . . . . . . . . . . . . . . . . . . . . . 36
Alarm delay 1 (Parameter) . . . . . . . . . . . . . . . . . . . 154 Device Revision (Parameter) . . . . . . . . . . . . . . . . . . 133
Alarm delay 2 (Parameter) . . . . . . . . . . . . . . . . . . . 154 Device type (Parameter) . . . . . . . . . . . . . . . . . . . . . 133
Application parameter (Parameter) . . . . . . . . . . . . . . 42 Diagnostics 1 (Parameter) . . . . . . . . . . . . . . . . . . . . 128
Area of incoupling (Parameter) . . . . . . . . . . . . . . . . 143 Diagnostics 2 (Parameter) . . . . . . . . . . . . . . . . . . . . 128
Assign channel 1 (Parameter) . . . . . . . . . . . . . . . . . 134 Diagnostics 3 (Parameter) . . . . . . . . . . . . . . . . . . . . 128
Assign channel 2 (Parameter) . . . . . . . . . . . . . . . . . 134 Diagnostics 4 (Parameter) . . . . . . . . . . . . . . . . . . . . 128
Assign channel 3 (Parameter) . . . . . . . . . . . . . . . . . 134 Diagnostics 5 (Parameter) . . . . . . . . . . . . . . . . . . . . 128
Assign channel 4 (Parameter) . . . . . . . . . . . . . . . . . 134 Diameter (Parameter) . . . . . . . . . . . . . . . . . . . . . . . . 60
Assign diagnostic level (Parameter) . . . . . . . . . . . . . 116 Direct access (Parameter) . . . . . . . . . . . . . . . . . . . . . 18
Assign diagnostic signal 1 (Parameter) . . . . . . . . . . 149 Display channel 1 (Parameter) . . . . . . . . . . . . . . . . . 135
Assign diagnostic signal 2 (Parameter) . . . . . . . . . . 149 Display channel 2 (Parameter) . . . . . . . . . . . . . . . . . 135
Assign event behaviour 1 (Parameter) . . . . . . . . . . . 154 Display channel 3 (Parameter) . . . . . . . . . . . . . . . . . 135
Assign event behaviour 2 (Parameter) . . . . . . . . . . . 154 Display channel 4 (Parameter) . . . . . . . . . . . . . . . . . 135
Assign limit (Parameter) . . . . . . . . . . . . . . . . . . . . . 116 Display damping (Parameter) . . . . . . . . . . . . . . . . . . 26
Assign simulation process variable (Parameter) . . . . 140 Display interval (Parameter) . . . . . . . . . . . . . . . . . . . 26
Assign status (Parameter) . . . . . . . . . . . . . . . . . . . . 118 Distance (Parameter) . . . . . . . . . . . . . . . . . . . . . . 46, 73
Assign status signal to AD event 1 (Parameter) . . . . 153 Distance offset (Parameter) . . . . . . . . . . . . . . . . . . . . 46
Assign status signal to AD event 2 (Parameter) . . . . 153 Distance unit (Parameter) . . . . . . . . . . . . . . . . . . . . . 38
Distanz (Parameter) . . . . . . . . . . . . . . . . . . . . . . . . 104
B Document
Backlight (Parameter) . . . . . . . . . . . . . . . . . . . . . . . . 29 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Backup state (Parameter) . . . . . . . . . . . . . . . . . . . . . 32 Document function . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Bin property (Parameter) . . . . . . . . . . . . . . . . . . . . . . 39
Blocking distance (Parameter) . . . . . . . . . . . . . . . . . . 78 E
Electronic temperature (Parameter) . . . . . . . . . . . . . . 68
C Empty calibration (Parameter) . . . . . . . . . . . . . . . . . . 47
Calculated DC value (Parameter) . . . . . . . . . . . . . . . . 44 End mapping amplitude (Parameter) . . . . . . . . . . . . 106
Calculation type 1 (Parameter) . . . . . . . . . . . . . . . . 150 End of mapping (Parameter) . . . . . . . . . . . . . . . . . . 106
Calculation type 2 (Parameter) . . . . . . . . . . . . . . . . 150 ENP version (Parameter) . . . . . . . . . . . . . . . . . . . . . 132
Calculation unit 1 (Parameter) . . . . . . . . . . . . . . . . . 151 Enter access code (Parameter) . . . . . . . . . . . . . . . . . . 19
Calculation unit 2 (Parameter) . . . . . . . . . . . . . . . . . 151 Envelope curve (Parameter) . . . . . . . . . . . . . . . . . . . . 96
Check mode 1 (Parameter) . . . . . . . . . . . . . . . . . . . 150 Evaluation mode (Parameter) . . . . . . . . . . . . . . . . . 112
Check mode 2 (Parameter) . . . . . . . . . . . . . . . . . . . 150 Event list (Parameter) . . . . . . . . . . . . . . . . . . . . . . . 129
Clear logging data (Parameter) . . . . . . . . . . . . . . . . 135 Extended order code (Parameter) . . . . . . . . . . . . . . . 132
Comparison result (Parameter) . . . . . . . . . . . . . . . . . 32 Extended order code 1 (Parameter) . . . . . . . . . . . . . 132
Configuration management (Parameter) . . . . . . . . . . 31 Extended order code 2 (Parameter) . . . . . . . . . . . . . 132
Confirm access code (Parameter) . . . . . . . . . . . . . . . . 35 External pressure (Parameter) . . . . . . . . . . . . . . . . . . 84
Confirm distance (Parameter) . . . . . . . . . . . . . . . . . 104 External pressure selector (Parameter) . . . . . . . . . . . . 83
Const. GPC factor (Parameter) . . . . . . . . . . . . . . . . . . 85
Contrast display (Parameter) . . . . . . . . . . . . . . . . . . . 28 F
Control measurement (parameter) . . . . . . . . . . . . . . 115 Filter options (Parameter) . . . . . . . . . . . . . . . . . . . . 129
Customer value (Parameter) . . . . . . . . . . . . . . . . . . . 63 Firmware version (Parameter) . . . . . . . . . . . . . . . . . 131
Fixed value input 1/2 (parameter) . . . . . . . . . . . . . . 114
D Format display (Parameter) . . . . . . . . . . . . . . . . . . . . 23
DD Revision (Parameter) . . . . . . . . . . . . . . . . . . . . . 133 Found echoes (Parameter) . . . . . . . . . . . . . . . . . . . . . 67
Dead time (Parameter) . . . . . . . . . . . . . . . . . . . . . . . 74 Free field special (Parameter) . . . . . . . . . . . . . . . . . . 69
Decimal places 1 (Parameter) . . . . . . . . . . . . . . . . . . 25 Free text (Parameter) . . . . . . . . . . . . . . . . . . . . . . . . 59

156 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus Index

Full calibration (Parameter) . . . . . . . . . . . . . . . . . . . . 48 Maximum value 1 (Parameter) . . . . . . . . . . . . . . . . 153


Function input 1/2 level (parameter) . . . . . . . . . . . . 114 Maximum value 2 (Parameter) . . . . . . . . . . . . . . . . 153
Measurement frequency (Parameter) . . . . . . . . . . . . . 68
G Medium group (Parameter) . . . . . . . . . . . . . . . . . . . . 43
Gas layer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79 Medium property (Parameter) . . . . . . . . . . . . . . . . . . 44
Gas phase compensation factor (Parameter) . . . . . . . . 84 Medium type (Parameter) . . . . . . . . . . . . . . . . . . . . . 43
GPC mode (Parameter) . . . . . . . . . . . . . . . . . . . . . . . 83 Messung (Parameter) . . . . . . . . . . . . . . . . . . . . . . . 115
Min. amplitude TBD (Parameter) . . . . . . . . . . . . . . . 108
H Min. electronics temperature (Parameter) . . . . . . . . 139
Hardware revision (Parameter) . . . . . . . . . . . . . . . . 132 Min. level value (Parameter) . . . . . . . . . . . . . . . . . . 137
Header (Parameter) . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Minimum value 1 (Parameter) . . . . . . . . . . . . . . . . . 153
Header text (Parameter) . . . . . . . . . . . . . . . . . . . . . . 27 Minimum value 2 (Parameter) . . . . . . . . . . . . . . . . . 153
High limit (Parameter) . . . . . . . . . . . . . . . . . . . . . . . 50
History learning (Parameter) . . . . . . . . . . . . . . . . . . 113 N
History learning control (Parameter) . . . . . . . . . . . . 112 Noise of signal (Parameter) . . . . . . . . . . . . . . . . . . . . 86
History reset (Parameter) . . . . . . . . . . . . . . . . . . . . 112 Number format (Parameter) . . . . . . . . . . . . . . . . . . . 28
Hysteresis 1 (Parameter) . . . . . . . . . . . . . . . . . . . . . 152
Hysteresis 2 (Parameter) . . . . . . . . . . . . . . . . . . . . . 152 O
Operating time (Parameter) . . . . . . . . . . . . . . . . . . . . 31
I Operating time from restart (Parameter) . . . . . . . . . 126
In safety distance (Parameter) . . . . . . . . . . . . . . . . . . 93 Output echo lost (Parameter) . . . . . . . . . . . . . . . . . . . 91
Integration time (Parameter) . . . . . . . . . . . . . . . . . . . 76 Output mode (Parameter) . . . . . . . . . . . . . . . . . . . . . 52
Intermediate height (Parameter) . . . . . . . . . . . . . . . . 60
Invert output signal (Parameter) . . . . . . . . . . . . . . . 120 P
ITK Version (Parameter) . . . . . . . . . . . . . . . . . . . . . 133 Present mapping (Parameter) . . . . . . . . . . . . . . . . . 105
Present reference distance (Parameter) . . . . . . . . . . . 84
L Previous diagnostics (Parameter) . . . . . . . . . . . . . . . 126
Language (Parameter) . . . . . . . . . . . . . . . . . . . . . . . . 23
Last backup (Parameter) . . . . . . . . . . . . . . . . . . . . . . 31 R
Last check time (Parameter) . . . . . . . . . . . . . . . . . . 142 Rampe bei Echoverlust (Parameter) . . . . . . . . . . . . . . 92
Level (Parameter) . . . . . . . . . . . . . . . . . . . . . . . . 52, 62 Record map (Parameter) . . . . . . . . . . . . . . . . . . . . . 105
Level correction (Parameter) . . . . . . . . . . . . . . . . . . . 51 Reference distance (Parameter) . . . . . . . . . . . . . . . . . 84
Level external input (parameter) . . . . . . . . . . . . . . . 114 Reference echo threshold (Parameter) . . . . . . . . . . . . 85
Level limit mode (Parameter) . . . . . . . . . . . . . . . . . . . 50 Relative echo amplitude (Parameter) . . . . . . . . . . . . . 66
Level linearized (Parameter) . . . . . . . . . . . . . . . . . . . 53 Reset min./max. (Parameter) . . . . . . . . . . . . . . . . . . 138
Level signal (Parameter) . . . . . . . . . . . . . . . . . . . . . 142 Reset min./max. 1 (Parameter) . . . . . . . . . . . . . . . . 153
Level unit (Parameter) . . . . . . . . . . . . . . . . . . . . . . . . 49 Reset min./max. 2 (Parameter) . . . . . . . . . . . . . . . . 153
Linearization type (Parameter) . . . . . . . . . . . . . . . . . 57 Reset min./max. temperature (Parameter) . . . . . . . . 139
Link AD 1 to (Parameter) . . . . . . . . . . . . . . . . . . . . 149 Result device check (Parameter) . . . . . . . . . . . . . . . . 142
Link AD 2 to (Parameter) . . . . . . . . . . . . . . . . . . . . 149 Result self check (Parameter) . . . . . . . . . . . . . . . . . . . 86
Linking logic AD 1 (Parameter) . . . . . . . . . . . . . . . . 149
Linking logic AD 2 (Parameter) . . . . . . . . . . . . . . . . 149 S
Locking status (Parameter) . . . . . . . . . . . . . . . . . . . . 18 Safety distance (Parameter) . . . . . . . . . . . . . . . . . . . . 93
Logging interval (Parameter) . . . . . . . . . . . . . . . . . . 134 Sample time 1 (Parameter) . . . . . . . . . . . . . . . . . . . 150
Low limit (Parameter) . . . . . . . . . . . . . . . . . . . . . . . . 51 Sample time 2 (Parameter) . . . . . . . . . . . . . . . . . . . 150
Lower level area (Parameter) . . . . . . . . . . . . . . . . . . 108 Sensor module (Parameter) . . . . . . . . . . . . . . . . . . . . 69
Lower limit 1 (Parameter) . . . . . . . . . . . . . . . . . . . . 152 Separator (Parameter) . . . . . . . . . . . . . . . . . . . . . . . . 27
Lower limit 2 (Parameter) . . . . . . . . . . . . . . . . . . . . 152 Serial number (Parameter) . . . . . . . . . . . . . . . . . . . 131
Signal quality (Parameter) . . . . . . . . . . . . . . . . . . . . . 65
M Simulation device alarm (Parameter) . . . . . . . . . . . . 141
Mapping end point (Parameter) . . . . . . . . . . . . . . . . 105 Start device check (Parameter) . . . . . . . . . . . . . . . . . 141
Max. draining speed (Parameter) . . . . . . . . . . . . . . . 137 Start self check (Parameter) . . . . . . . . . . . . . . . . . . . . 86
Max. draining speed liquid (Parameter) . . . . . . . . . . . 40 Status echo lost (Parameter) . . . . . . . . . . . . . . . . . . . 91
Max. draining speed solid (Parameter) . . . . . . . . . . . . 41 Status in safety distance (Parameter) . . . . . . . . . . . . . 94
Max. electronics temperature (Parameter) . . . . . . . . 138 Switch output failure mode (Parameter) . . . . . . . . . . 119
Max. filling speed (Parameter) . . . . . . . . . . . . . . . . . 138 Switch output function (Parameter) . . . . . . . . . . . . . 116
Max. filling speed liquid (Parameter) . . . . . . . . . . . . . 40 Switch output simulation (Parameter) . . . . . . . . . . . 140
Max. filling speed solid (Parameter) . . . . . . . . . . . . . . 40 Switch status (Parameter) . . . . . . . . . . . . . . . . 120, 141
Max. level value (Parameter) . . . . . . . . . . . . . . . . . . 137 Switch-off delay (Parameter) . . . . . . . . . . . . . . . . . . 119
Maximum value (Parameter) . . . . . . . . . . . . . . . . . . . 60 Switch-off value (Parameter) . . . . . . . . . . . . . . . . . . 117

Endress+Hauser 157
Index Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus

Switch-on delay (Parameter) . . . . . . . . . . . . . . . . . . 119


Switch-on value (Parameter) . . . . . . . . . . . . . . . . . . 117

T
Table mode (Parameter) . . . . . . . . . . . . . . . . . . . . . . 61
Table number (Parameter) . . . . . . . . . . . . . . . . . . . . . 62
Tank bottom echo amplitude (Parameter) . . . . . . . . . 67
Tank bottom range (Parameter) . . . . . . . . . . . . . . . . 108
Tank trace state (Parameter) . . . . . . . . . . . . . . . . . . . 67
Tank type (Parameter) . . . . . . . . . . . . . . . . . . . . . . . 38
Tank/silo height (Parameter) . . . . . . . . . . . . . . . . . . 53
Temperature unit (Parameter) . . . . . . . . . . . . . . . . . . 38
Time max. electronics temperature (Parameter) . . . . 138
Time max. level (Parameter) . . . . . . . . . . . . . . . . . . 137
Time min. electronics temperature (Parameter) . . . . 139
Time min. level (Parameter) . . . . . . . . . . . . . . . . . . 137
Timestamp (Parameter) . . . . . . . . . . . . . . . . . . . . . 128
Tube diameter (Parameter) . . . . . . . . . . . . . . . . . . . . 39

U
Unit after linearization (Parameter) . . . . . . . . . . . . . . 58
Upper limit 1 (Parameter) . . . . . . . . . . . . . . . . . . . . 151
Upper limit 2 (Parameter) . . . . . . . . . . . . . . . . . . . . 151
Used calculation (Parameter) . . . . . . . . . . . . . . . . . . . 67

V
Value 1 display (Parameter) . . . . . . . . . . . . . . . . . . . 25
Value 2 display (Parameter) . . . . . . . . . . . . . . . . . . . 25
Value 3 display (Parameter) . . . . . . . . . . . . . . . . . . . 25
Value 4 display (Parameter) . . . . . . . . . . . . . . . . . . . 25
Value echo lost (Parameter) . . . . . . . . . . . . . . . . . . . . 91
Value process variable (Parameter) . . . . . . . . . . . . . 140

158 Endress+Hauser
*71219978*
71219978

www.addresses.endress.com