Table of contents
Endress+Hauser 3
Important document informationMicropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Symbol Meaning
Tip
Indicates additional information.
A0011193
Reference to documentation
Refers to the corresponding device documentation.
A0011194
Reference to page
Refers to the corresponding page number.
A0011195
Reference to graphic
Refers to the corresponding graphic number and page number.
A0011196
Write-protected parameter
Indicates a parameter that can be locked against changes by entering a user-specific code.
A0013144
Symbol Meaning
A, B, C, ... Views
Symbol Meaning
Safety instructions
Observe the safety instructions contained in the associated Operating Instructions.
4 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION FieldbusOverview of the operating menu
Endress+Hauser 5
Overview of the operating menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
6 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION FieldbusOverview of the operating menu
Endress+Hauser 7
Overview of the operating menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Expert → Sensor → Tank bottom evaluation → Tank bottom range 1149 (→ 108)
8 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION FieldbusOverview of the operating menu
Endress+Hauser 9
Overview of the operating menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
10 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION FieldbusOverview of the operating menu
Endress+Hauser 11
Overview of the operating menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
12 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION FieldbusOverview of the operating menu
Endress+Hauser 13
Overview of the operating menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
14 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION FieldbusOverview of the operating menu
Endress+Hauser 15
Overview of the operating menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
16 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION FieldbusOverview of the operating menu
Expert → Diagnostics → Advanced diagnostics 1/2 Assign diagnostic signal 11179 (→ 149)
→ 1/2
Endress+Hauser 17
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Prerequisite Only visible for operation via display module, not for operation via software tool (e.g.
FieldCare).
Additional information In this document, the direct access code is indicated in brackets following the parameter
name, e.g. Locking status (0004).
Description Indicates the write protection with the highest priority that is currently active.
Additional information On the display module, the -symbol appears in front of parameters that cannot be
modified since they are write-protected.
Prerequisite Only visible for devices with operating and display module (SD02 or SD03)
18 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Additional information • The access authorization can be changed via the Enter access code parameter
(→ 19).
• If additional write protection is active, this restricts the current access authorization
even further. The write protection status can be viewed via the Locking status
parameter (→ 18).
• If a -symbol appears in front of a parameter, the parameter cannot be changed via
the local display with the current access authorization.
Prerequisite Only visible for operation via operating tool (e.g. FieldCare), not for operation via display
module.
Description Indicates access authorization to parameters via operating tool (e.g. FieldCare).
Additional information If additional write protection is active, this restricts the current access authorization
even further. The write protection status can be viewed via the Locking status
parameter (→ 18).
Endress+Hauser 19
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Additional information For local operation, the customer-specific access code, which has been defined in the
Expert → System → Define access code sequence, has to be entered.
If an incorrect access code is entered, the user retains his current access authorization.
The write protection affects all parameters marked with the -symbol in the document.
On the local display, the -symbol in front of a parameter indicates that the parameter is
write-protected.
If no key is pressed for 10 minutes, or the user goes from the navigation and editing mode
back to the measured value display mode, the device automatically locks the write-
protected parameters after another 60 s.
Please contact your Endress+Hauser Sales Center if you lose your access code.
20 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Submenus
Submenu Meaning Description
Configuration backup • Backup of the device configuration in the display module (→ 30)
display • Copying of the device configuration into another device
Endress+Hauser 21
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Overview
The Display submenu is used to parametrize the representation of measured values on the
local display module. Up to four measured values can be allocated to the local display
module. Additionally, display characteristics such as the format of numbers, the associated
texts or the display contrast can be configured.
Format Display Selection of the display format (number and size of the displayed (→ 23)
measuring values)
Value 1 display Allocation of a measured variable to the first display value (→ 25)
Decimal places 1 Number of decimal places for the first display value (→ 25)
Value 2 display Allocation of a measured variable to the second display value (→ 25)
Decimal places 2 Number of decimal places for the second display value (→ 25)
Value 3 display Allocation of a measured variable to the third display value (→ 25)
Decimal places 3 Number of decimal places for the third display value (→ 25)
Value 4 display Allocation of a measured variable to the fourth display value (→ 25)
Decimal places 4 Number of decimal places for the fourth display value (→ 25)
Display interval Time the individual variables are displayed in the case of an alternating (→ 26)
display
Display damping Time constant for the damping of displayed values (→ 26)
Header text Definition of the header text in the case of Header = Free text (→ 27)
Number format Selection of the number format for distance values (decimal or ft-in-1/16") (→ 28)
Decimal places menu Number of decimals for values in the operating menu (not the measuring (→ 28)
values)
Access status display Displays the user role for operation via the display module (→ 18)
22 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Description of parameters
Language (0104)
Options • English
• One additional operating language (see product structuture, feature 500, "Additional
Operation Language")
Endress+Hauser 23
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
4841.000
1 Â mm
A0019963
1 bargraph + 1 value
1 Â
93.5 %
1 Â 159.0
mm
A0019964
2 values
1 Â 93.5
%
1 Â 159.0
mm
A0019965
1 Â 159.0 mm
V 1 Â 23.5 V
1 Â 93.5
%
A0019966
4 values
1 Â 93.5 %
1 Â 159.0 mm
V 1 Â 93.5 V
1 Â 26.3 °C
A0019968
• The Value 1 display - Value 4 display parameters are used to specify what
measured values are shown on the display and in what order (→ 25).
• If more measured values are specified than the display mode selected permits, the
values alternate on the device display. The display time until the next change is
configured using the Display interval parameter (→ 26).
24 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Description Select the measured value that is shown on the local display.
Options • None 1)
• Level linearized
• Distance
• Terminal voltage
• Electronics temperature
• Absolute echo amplitude
• Relative echo amplitude
• Analog output adv. diagnostics 1
• Analog output adv. diagnostics 2
Additional information The Format display parameter is used to specify how many measured values are displayed
simultaneously and how (→ 23).
Prerequisite A measured value is specified in the Value 1/2/3/4 display parameter (→ 25).
Description Select the number of decimal places for the display value.
Options •x
• x.x
• x.xx
• x.xxx
• x.xxxx
Endress+Hauser 25
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Additional information This setting does not affect the measuring or computational accuracy of the device.
Description Set time measured values are shown on display if display alternates between values.
Input range 1 to 10 s
Facotry setting 5s
Additional information An alternating display only occurs automatically if the number of measured values defined
exceeds the number of values the selected display format can display simultaneously.
• The Value 1 display - Value 4 display parameters are used to specify what
measured values are shown on the display (→ 25).
• The display format of the displayed measured values is specified using the
Format display parameter (→ 23).
Factory setting 0 s
Header (0097)
26 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Additional information
1 XXXXXXXXX
A0013375
Device tag
Is defined in the Setup → Device tag parameter.
Free text
Is defined in the Header text parameter (→ 27).
Prerequisite The Free text option is selected in the Header parameter (→ 26).
Input range Max. 12 characters, such as letters, numbers or special characters (e.g. @, %, /)
Additional information
1 XXXXXXXXX
A0013375
User entry
The number of characters displayed depends on the characters used.
Separator (0101)
Options • . (point)
• , (comma)
Endress+Hauser 27
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Options • Decimal
• ft-in-1/16" (Only valid for distance units)
Description Select number of decimal places for the representation of numbers within the operating
menu.
Options •x
• x.x
• x.xx
• x.xxx
• x.xxxx
Additional information This parameter only determines the representation of numbers within the operating menu
(e.g. Empty calibration, Full calibration). It does not affect the measured value
representation.
For measured values, the number of decimal places is defined in the Decimal places 1 to
Decimal places 4 parameters (→ 25).
This setting does not affect the measurement and calculation accuracy of the device.
Description Adjust local display contrast setting to ambient conditions (e.g. lighting or reading angle).
28 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Input range 20 to 80 %
Factory setting 30 %
Backlight (0111)
Prerequisite Only visible if the display module SD03 with optical keys is connected (SD02 with push
buttons does not have a backlight).
Options • Disable
• Enable
Endress+Hauser 29
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Overview
All software configurations are initially stored in a memory module (HistoROM) in the
housing and are thus permanently connected with the device. As an additional option, the
display module contains a backup memory for the device configuration. The transmission
of configuration data between these two memory modules is controlled by the
Configuration backup display submenu. It provides the following options:
• Backup of a configuration from the device into the display module.
• Restore a device configuration.
This option can be used to restore a configuration back into the device which has
previously been saved in the display module.
• Duplicate a device configuration.
If the configuration has been saved into the display module, the module can be
connected to a different device and the configuration can be duplicated to this device.
This allows to efficiently configure a number of devices in the same way.
• Compare the configurations in the device and in the display module.
The comparison result indicates whether the device configuration has been changed
since the last backup.
Operating time Displays the operating time since the first setup. (→ 31)
Last backup Displays at which time the last backup has been performed. (→ 31)
30 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Description of parameters
Display format Days (d), hours (h), minutes (m) and seconds (s)
Description Indicates the operating time at which the last data backup was saved to the display
module.
Display format Days (d), hours (h), minutes (m) and seconds (s)
Description Select action for managing the device data in the display module.
Endress+Hauser 31
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Options • Cancel
No action is executed and the user exits the parameter.
• Execute backup
A backup copy of the current device configuration in the HistoROM (built-in in the
device) is saved to the display module of the device. The backup copy comprises the
transmitter and sensor data of the device.
• Restore
The last backup copy of the device configuration is copied from the display module to the
HistoROM of the device. The backup copy comprises the transmitter and sensor data of
the device.
• Duplicate
The transmitter configuration is duplicated to another device using the transmitter
display module.
• Compare
The device configuration saved in the display module is compared to the current device
configuration of the HistoROM.
• Clear backup data
The backup copy of the device configuration is deleted from the display module of the
device.
HistoROM
A HistoROM is a non-volatile device memory in the form of an EEPROM.
While the respective action is in progress, the configuration cannot be edited via the
local display and a message on the processing status appears on the display.
Prerequisite Only visible in the operating tool (not on the local display)
32 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Additional information The comparison is started via the Compare option in the Configuration
management parameter (→ 31).
Endress+Hauser 33
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Overview
The Administration submenu contains all parameters for the management of the device.
Its structure depends on the user interface:
Define access code → Define By defining a user-specific acces code the device configuration (→ 35)
access code can be protected against unintended changes.
Define access code → Confirm The access code defined in Define access code must be (→ 35)
access code confirmed by repeating it in this parameter.
Define access code By defining a user-specific acces code the device configuration can be (→ 35)
protected against unintended changes.
34 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Navigation Expert → System → Administration → Define access code → Define access code
Expert → System → Administration → Define access code
Description Define user-specific access code in order to protect the device against unintended changes.
Factory setting 0
Additional information If the factory setting is not changed or 0 is defined as the access code, the parameters are
not write-protected and the configuration data of the device can then always be modified.
The user is logged on in the role of Maintenance .
The write protection affects all parameters marked with the symbol in the
document. On the local display, the symbol in front of a parameter indicates that the
parameter is write-protected.
Once the access code has been defined, write-protected parameters can only be
modified if the access code is entered in the Expert → Enter access code parameter.
Please contact your Endress+Hauser Sales Center if you lose your access code.
For display operation: The new access code is only valid after it has been confirmed in
the Confirm access code parameter and after the user has returned to the main
screen (measured value display).
Navigation Expert → System → Administration → Define access code → Confirm access code
Prerequisite Only visible for operation via display module, not for operation via operating software (e.g.
FieldCare).
Description Confirm the access code by repeating the value entered in the Define access code
parameter.
Factory setting 0
1) This sequence only exists for operation via the display module. For operation via operating software (e.g. FieldCare), the "Define access code"
parameter is located directly in the "Administration" submenu.
Endress+Hauser 35
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Further parameters
Description Use this function to reset the device configuration - either entirely or in part - to a defined
state.
Options • Cancel
No action is executed and the user exits the parameter.
• To factory defaults
Every parameter is reset to the order-code specific factory setting.
• To delivery settings
Every parameter is reset to the delivery setting. The delivery setting may differ from the
factory default if customer specific settings have been ordered.
• Of customer settings
Every customer parameter is reset to its factory setting. Service parameters, however,
retain their current value.
• To transducer defaults
Every measurment-related parameter is reset to its factory setting. Service parameters
and communication-related parameters, however, retain their current value.
• Restart device
The restart resets every parameter whose data are in the volatile memory (RAM) to the
factory setting (e.g. measured value data). The device configuration is not modified.
36 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
3.2.1 Overview
The Sensor submenu contains all parameters related to the measurement and the sensor
settings.
Parameters
Parameter Meaning Description
Distance unit Measuring unit for basic distances (e.g empty and full calibration) (→ 38)
Temperature unit Measuring unit for temperatures (e.g. sensor temperature, (→ 38)
electronics temperature)
Tank type Selection of the tank type (for liquid measurements) (→ 38)
Tube diameter Specification of the bypass or stilling well diameter (for liquid (→ 39)
measurements)
Bin property Selection of the bin type (for solid measurements) (→ 39)
Max. filling speed liquid Specification of the maximum filling speed (for liquid (→ 40)
measurements)
Max. draining speed liquid Specification of the maximum draining speed (for liquid (→ 40)
measurements)
Max. filling speed solid Specification of the maximum filling speed (for solid (→ 40)
measurements)
Max. draining speed solid Specification of the maximum draining speed (for solid (→ 41)
measurements)
Submenus
Submenu Meaning Description
Linearization Transformation of the measured level into a volume or weight for (→ 55)
arbitrarily shaped vessels
Gas phase Compensation of the influences of a gas or steam above the measured (→ 79)
compensation medium.
Sensor diagnostics Informs about the state of the probe and the HF cable. (→ 86)
Safety settings Defines the behavior of the device in critical situations (e.g. lost echo, (→ 87)
level in safety distance).
Tank bottom Evaluation of echoes in the proximity of the tank bottom (→ 107)
evaluation
Echo tracking Tracking of level, interface, multiple and interference echos in order to (→ 109)
identify the correct echo unambiguously.
Endress+Hauser 37
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Options • mm
•m
• ft
• in
Factory setting m
Options • °C
• °F
•K
• °R
Factory setting °C
38 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Additional information Depending on the Tank type parameter the parameters Max. filling speed liquid and
Max. draining speed liquid are preset among others.
Additional information The tube diameter must be entered for bypass and stilling well applications in order to
optimally adapt the measurement to the measuring point.
Endress+Hauser 39
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Additional information Depending on the Bin type parameter, the parameters Max. filling speed solid and Max.
draining speed solid are preset, among others.
40 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Additional information The Max. filling speed solid parameter must be set according to the actual process
velocity.
Additional information The Max. draining speed solid parameter must be set according to the actual process
velocity.
Endress+Hauser 41
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Options • None
• Weak signal
• Many obstacles
• Small tanks (< 1m/3ft)
• Changing DC values
• Foam (> 5cm/0.16ft)
Description Indicates whether parameters have been changed after the basic setup.
Additional information Indicates whether a setting which depends on the application parameters (e.g. "Process
property", Advanced process conditions", "Tank type" and "Pipe diameter") has been changed
after the basic setup.
• Changed
Parameters have been changed. The device is no longer in the state defined by the
application parameters.
• Not changed
There have been no changes. The device is still in the state defined by the application
parameters.
42 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Overview
The Medium submenu is used to specify the relevant properties of the measured medium,
especially the dielectric constant (DC).
Description of parameters
Endress+Hauser 43
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Additional information If required, smaller DC values can be entered into Expert → Sensor → Medium → Medium
property. This, however, may reduce the measuring range.
Refer to the Technical Information (TI) of the respective device.
Options • Unknown
• DC 1.4 to 1.6
• DC 1.6 to 1.9
• DC 1.9 to 2.5
• DC 2.5 to 4
• DC 4 to 7
• DC 7 to 15
• DC > 15
Additonal information Dielectric constants of important media commonly used in the industry are
summarized in the document SD106F, which can be downloaded from the Endress
+Hauser web page (www.endress.com).
Additional information Indicates a DC value calculated by the device. The calculation is only possible for small DC
values as it requires the tank bottom signal.
44 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Overview
The Level submenu is used to parametrize the calculation of the level from the measured
distance.
1 2 3 4 5
R
L 100%
D
D
100%
D0
100% B
A DL
E
D0 D L0 L
L0
B
F
DD 0%
t A
0% 0%
A0016141
Endress+Hauser 45
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Description of parameters
Additonal Information The value speicified in this parameter is added to the measured distance between the
reference point of the measurement and the level echo.
• Positive values increase the distance and thus decrease the level.
• Negative values decrease the distance and thus increase the level.
R R
D0
D0
D
DD(<0)
DD(>0)
A0016081
A value entered into this parameter is taken into account in the calculation of the
level. However, it does not influence the indicated distance.
Distance (2231)
46 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
A0019483
A0019485
Additional information The value is displayed in the selected "Level unit" (→ 49).
Endress+Hauser 47
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
0%
A0019486
0%
A0019488
48 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
0%
A0019487
100%
0%
A0019489
Options •%
•m
• mm
• ft
• in
Factory setting %
Additional information The level unit may differ from the distance unit defined in the Distance unit parameter
(→ 38):
• The distance unit is used for the basic calibration ("Empty calibration" and "Full
calibration").
• The level unit is used to display the (unlinearized) level.
Endress+Hauser 49
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Options • Off
• Low limit
• High limit
• Low and high limit
Additional information The parameter determines to which direction the level is limited. The exact limits are
defined in the High limit and Low limit parameters.
A B C
L L L
100% 100% 100%
1 1
a a
2 2 2 2
b b
0% 0% 0%
t 1 t 1 t
A0016083
3 Effect of the parameters "Level limit mode", "High limit" and "Low limit"
A Level limit mode = High limit
B Level limit mode = Low limit
C Level limit mode = Low and high limit
a High limit
b Low limit
1 Level before limitation
2 Level after limitation
Prerequisite Level limit mode = High limit or Low and high limit
50 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Additional information Levels exceeding the value specified in this parameter will be ignored. Instead, the device
uses the value specified in this parameter (for measured value transformation and output).
Prerequisite Level limit mode = Low limit or Low and high limit
Factory setting 0%
Additional information Levels falling below the value specified in this parameter will be ignored. Instead, the
device uses the value specified in this parameter (for measured value transformation and
output).
Endress+Hauser 51
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Factory setting 0%
Additional information The value specified in this parameter is added to the measured level (before linearization).
Options • Ullage
• Level linearized
100%
B
A
0%
A0016086
Level (2319)
52 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
0%
A0019482
L
0%
A0019484
Additional information The value is displayed in the selected "Level unit" (→ 49).
Additional information The unit of this parameter is defined in the Unit after linearization parameter
(→ 58).
Tank/silo height
Endress+Hauser 53
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Description Total height of the tank or silo as measured from the process connection.
A0019867
E Empty calibration
1 Tank/Silo height
0%
A0019868
E Empty calibration
1 Tank/Silo height
54 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Overview
2
A
L
100%
L 1 B L‘
0%
M L‘
L
100%
C L2
L1
0% L‘1L‘2 L‘
L
100%
H
D
0% M L‘
L
100%
h
E
0% M L‘
L
100%
F
h
0% M L‘
L
100%
G d
0%
M L‘
L
100%
H d
0%
M L‘
A0019648
5 Linearization: Transformation of the level into a volume or weight; the transformation is dependent on
the shape of the vessel.
1 Selection of linearization type and unit
2 Parametrization of the linearization
A Linearization type = None
B Linearization type = Linear
C Linearization type = Table
D Linearization type = Pyramid bottom
E Linearization type = Conical bottom
F Linearization type = Angled bottom
G Linearization type = Horizontal cylinder
H Linearization type = Sphere
L Level before linearization (measured in level unit)
L' Level after linearization (corresponds to volume or weight)
M Maximum value
d Diameter
h Intermediate height
Endress+Hauser 55
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Diameter (→ 60)
Level (→ 62)
1) Only for operation via operating tool (e.g. FieldCare), not on the local display module
56 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Description of parameters
Options • None
The level is transmitted to the output 100%
without linearization.
• Linear (A) A
• Table (B)
• Pyramid bottom (C) 0%
• Conical bottom (D)
• Angled bottom (E) 100%
• Horizontal cylinder (F)
• Sphere (G) B
0%
100%
C/D
0%
100%
0%
100%
F/G
0%
A0013299
Endress+Hauser 57
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
58 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Prerequisite Only visible if a linearization has been selected (i.e. Linearization type ≠ None)
Factory setting %
Additional information The selected unit is only used to be indicated on the display. The measured value is not
transformed according to the selected unit.
It is also possible to parametrize a distance-to-distance linearization, i.e. a
transformation from the level unit to a different distance unit. To do so, select the
Table linearization mode. In order to define the new level unit, select the Free text
option in the Unit after linearization parameter and enter the unit into the Free text
parameter.
Prerequisite Only visible for operation via operating tool (e.g. FieldCare), not on the local display
module.
Endress+Hauser 59
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Prerequisites Only visible if one of the following linearization types has been selected:
• Linear
• Pyramid bottom
• Conical bottom
• Angled bottom
• Horizontal cylinder
• Sphere
Description Definition of the maximum content of the vessel (100%), as measured in the Unit
linearized.
Diameter (2342)
Prerequisites Only visible if one of the following linearization types has been selected:
• Horizontal cylinder
• Sphere
Additional information The value must be specified in the selected distance unit (→ 38).
60 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Prerequisites Only visible if one of the following linearization types has been selected:
• Pyramid bottom
• Conical bottom
• Angled bottom
H
0%
A0013264
Additional information The value must be specified in the selected distance unit (→ 38).
Prerequisite Only visible if the "Table" linearization type has been selected.
Description Defines the method used to enter linearization points into the table.
Options • Manual
The level and the associated linearized value are entered manually for each linearization
point.
• Semi-automatic
The level is measured by the device for each linearization point. The associated
linearized value is entered manually.
• Clear table
Deletes the existing linearization table.
• Sort table
Rearranges the linerization points into an ascending order.
Endress+Hauser 61
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Description Number of the table point which will be defined by the next two parameters (Level and
Cusotmer value).
Input range 1 to 32
Factory setting 1
Level (2383/2389)
Description Definition or display of the (unlinearized) level of the respective linearization point.
Input range Depending on the parametrized measuring range. See the parameters Empty
calibration(→ 47) and Full calibration(→ 48).
Factory setting 0
62 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Factory setting 0
Prerequisite Only visible if the "Table" linearization type has been selected.
Options • Disable
A linearization is not calculated. If the Linearization type parameter has been set to
Table, the error message F435 is generated.
• Enable
The measured value is linearized according to the table before being sent to the output.
Additional information When editing the table, this parameter is automatically reset to the Disable option. After
finishing the editing procedure it must be set to the Enable option again.
Endress+Hauser 63
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Overview
The Information submenu comprises all display parameters which give information about
the current state of the measurement:
Parameter ParameterDescription
64 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Description of parameters
Additional information The signal quality indicated in this parameter always refers to the currently evaluated
echo: either the level echo or the tank bottom echo. To differentiate between these two,
the quality of the tank bottom echo is always displayed in brackets.
Endress+Hauser 65
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Additional information
A0019961
Description Indicates the relative amplitude of the level echo, i.e. the difference between the level echo
and the echo threshold.
In the envelope curve display of FieldCare, the absolute echo amplitude is indicated
instead of the relative amplitude (see the number on the top right of the echo peak in
the example).
Additional information
A0019962
1 The relative echo amplitude is the difference between the weighting curve (blue) and the peak in the envelope
curve (red).
66 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Additional information The tank bottom echo amplitude is only evaluated for media with a small DC value.
Description Indicates which echoes are used for the calculation fo the measured value.
Endress+Hauser 67
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Description Displays the current measurement frequency (number of pulses per second).
Additional information The unit is defined in the Expert → Sensor → Temperature unit parameter .
68 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Overview
The Sensor properties submenu comprises all parameters which describe the
measurement-related properties of the probe and the envelope curve.
Description This parameter can be switched on in the case of free-field applications (e.g. below a
bridge).
Endress+Hauser 69
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Options • No
• Yes
Factory setting No
70 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Overview
The Distance submenu contains all parameters by which the filtering of the raw distance
D1 is controlled. The resulting distance D0 is used for the subsequent level calculation
(→ 45).
1 2
D1 D0
A0016175
Endress+Hauser 71
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
72 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Distance (1124)
A0019483
Endress+Hauser 73
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Input range 0 to 60 s
Slow
8s 6s 4s 2s 0s 0s
< 1cm (0,4in)/min
Medium
6s 6s 4s 2s 0s 0s
< 10cm (4in)/min
Standard
4s 4s 4s 2s 0s 0s
< 1m (40in)/min
Fast
2s 2s 2s 2s 0s 0s
< 2m (80in)/min
Very fast
0s 0s 0s 0s 0s 0s
> 2m (80in)/min
No filter / test 0s 0s 0s 0s 0s 0s
74 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Very slow
< 0,5m 180 s 180 s 120 s 60 s 40 s 0s 0s
(1,6ft)/h
Slow
180 s 180 s 120 s 60 s 40 s 0s 0s
< 1m (3,3ft)/h
Standard
120 s 120 s 60 s 60 s 40 s 0s 0s
< 2m (6,5ft)/h
Medium
60 s 60 s 60 s 40 s 40 s 0s 0s
< 4m (13ft)/h
Fast
40 s 40 s 40 s 40 s 20 s 0s 0s
< 8m (26ft)/h
Very fast
0s 0s 0s 0s 0s 0s 0s
> 8m (26ft)/h
No filter / test 0s 0s 0s 0s 0s 0s 0s
2 3
1 t
A0016164
Disadvantages
• The device slows down.
• Fast level changes are registered with a delay.
Endress+Hauser 75
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
D
1
5xt t
A0016169
76 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Slow
30 s 15 s 5s 1s 0s 0s
< 1cm (0,4in)/min
Medium
15 s 15 s 5s 1s 0s 0s
< 10cm (4in)/min
Standard
5s 5s 5s 1s 0s 0s
< 1m (40in)/min
Fast
1s 1s 1s 1s 0s 0s
< 2m (80in)/min
Very fast
0s 0s 0s 0s 0s 0s
> 2m (80in)/min
No filter / test 0s 0s 0s 0s 0s 0s
Very slow
< 0,5m 250 s 200 s 200 s 100 s 50 s 1s 0s
(1,6ft)/h
Slow
200 s 200 s 200 s 100 s 50 s 1s 0s
< 1m (3,3ft)/h
Standard
200 s 200 s 100 s 100 s 50 s 1s 0s
< 2m (6,5ft)/h
Medium
100 s 100 s 100 s 50 s 50 s 1s 0s
< 4m (13ft)/h
Fast
50 s 50 s 50 s 50 s 20 s 1s 0s
< 8m (26ft)/h
Very fast
1s 1s 1s 1s 1s 1s 0s
> 8m (26ft)/h
No filter / test 0s 0s 0s 0s 0s 0s 0s
Additional information Increasing the integration time results in a calmer measuring signal. However, this also
means that the measuring signal indicates level changes with a certain delay.
Endress+Hauser 77
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Description Defines the distance below the process connection in which no measurement is performed.
BD
A0019492
78 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Overview
High pressures reduce the propagation velocity of the measuring signals in the gas/vapor
above the fluid. This effect depends on the kind of gas/vapor and of its temperature. This
results in a systematic measuring error that gets bigger as the distance increases between
the reference point of the measurement (flange) and the product surface.
°C °F 1 bar (14.5 psi) 10 bar (145 psi) 50 bar (725 psi) 100 bar (1 450 psi) 160 bar (2 320 psi)
310 590 - - - 22 % -
Endress+Hauser 79
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
80 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
A
B
B = FA
A0020199
Endress+Hauser 81
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
2
ENDRESS + HAUSER
A0016304
External pressure selector Select the AO block through which the externally (→ 83)
measured pressure is received.
External pressure Displays the pressure read in from the AO block (→ 84)
Suitable value of the gas phase compensation factor for saturated steam in the
temperature range 100 to 350 °C (212 to 662 °F):
F = 0.00505 / bar
82 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Options • Off
The gas phase compensation is deactivated.
• On
This option can only be selected for probes with reference echo. The gas phase
compensation is calculated from the position of this reference echo. The displayed
envelope curve does already contain the correction.
• Without correction
This option can only be selected for probes with reference echo.The correction factor is
calculated from the reference echo but not applied to the measurement.
This option is only used for diagnostic purposes and should not be used for normal
applications. The envelope curve is displayed without the correction.
• External correction
This option can only be selected for devices with PROFIBUS PA or FOUNDATION
Fieldbus. The device receives the externally measured pressure through an AO block and
uses it together with the gas phase compensation factor F to calculate the gas phase
compensation. The displayed envelope curve does already contain the correction.
• Const. GPC factor
The correction factor is a constant defined by the user. A reference echo or an externally
measured pressure are not needed. The displayed envelope curve does already contain
the correction.
Prerequisite Only available for PROFIBUS PA or FOUNDATION Fieldbus and if GPC mode = External
correction
Description Defines the AO block through which the external pressure used for gas phase
compensation is received.
Options • None
• Analog output 1
• Analog output 2
• Analog output 3
• Analog output 4
Endress+Hauser 83
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Prerequisite Only available for PROFIBUS PA or FOUNDATION Fieldbus and if GPC mode = External
correction
Description Displays the pressure which is currently read-in from the AO block.
Navigation Expert → Sensor → Gas phase compensation → Gas phase compensation factor
Prerequisite Only available for PROFIBUS PA or FOUNDATION Fieldbus and if GPC mode = External
correction
Factory setting 0
Additional information Suitable value for saturated steam in the temperature range 100 to 350 °C (212 to 662 °F):
F = 0.00505 / bar
84 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Description Input parameter for the actual distance of the reference echo.
Additonal information The distance of the aritificially generated reference echo has to be entered into this
parameter. The reference echo must always be in the gas phase; the level must never rise
above the reference echo.
Werkeinstellung –80 dB
Additonal information Only echoes exceeding the defined threshold are accepted as reference echo.
Endress+Hauser 85
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Options • No
• Yes
Factory setting No
Beschreibung Displays the noise of signal in the envelope curve (in dB).
86 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Overview
The Safety settings submenu contains all parameters which determnine the behavior of
the device in critical situations such as an echo loss or an undershooting of a user defined
safety distance.
1) The alarm bahavior ist defined in the submenus "Current output" (HART) or "Analog input" (PROFIBUS PA,
FOUNDATION Fieldbus).
L
0
2 3
t
A0016206
Endress+Hauser 87
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
L
0
3
1 5
%
2
min
4
E
t
A0016207
L
0
3
1
t
A0016208
88 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Safety distance
In order to get a warning message if the level rises into the proximity of the upper blocking
distance, a safety distance can be defined in the Safety distance parameter.
1
2
A0016210
The behavior of the device in case the level rises into the safety distance is defined in the
In safety distance and Acknowledge alarm parameters.
L
0
2
S942
E
t
A0016211
15 "In safety distance" = "Alarm": If the safety distance is undershot, the device generates an alarm.
1 Safety distance
2 Defined output value for alarms
Endress+Hauser 89
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
L
0
!
S942
E
t
A0016212
16 "In safety distance" = "Warning": If the safety distance is undershot, the device continues measuring but
nevertheless generates a warning.
1 Safety distance
L
0
2
3
S942
t
A0016213
17 "In safety distance" = "Self holding": If the safety distance is undershot, the device generates an alarm. The
measurement is not resumed until this alarm has been acknowledged by the user.
1 Safety distance
2 Defined alarm output value
3 Acknowledge alarm
Safety distance Length of the safety distance as measured from the reference (→ 93)
point of the measurement.
In safety distance Defines the behavior in case the safety distance is undershot. (→ 93)
Acknowledge alarm Reactivates the measurement after the level has fallen below (→ 94)
the safety distance again 1).
90 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Description of parameters
Prerequisite Only visible if the Value echo lost option has been selected in the Output echo lost
parameter.
Description Defines the constant output value in the case of a lost echo.
Factory setting 0
Additional information The unit is the same as for the output value:
• Without linearization: As defined in the Level unit parameter (→ 49).
• With linearization: As defined in the Unit after linearization parameter (→ 58).
Endress+Hauser 91
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Options • Good
• Uncertain
• Bad
Condition Only visible if the Ramp echo lost option has been selected in the Output echo lost
parameter.
A
C
0%
t
min
A0013269
Additional information • The unit for the slope of the ramp is "percentage of the measuring range per minute" (%/
min).
• For a negative slope of the ramp: The measured value is continuously shifted downwards
until it reaches 0%.
• For a positive slope of the ramp: The measured value is continuosly shifted upwards until
it reaches 100%.
92 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Factory setting 60 s
Additional information After an echo loss, the device waits for the time specified in this parameter before reacting
as specified in the Output echo lost parameter. This helps to avoid interruptions of the
mesurement by short-term interferences.
Factory setting 0m
Additional information The safety distance is measured from the reference point of the measurement (lower edge
of the flange or threaded connection). The safety distance can be used to generate a
warning before the level rises into the blocking distance. The In safety distance parameter
defines the rection of the device if the level rises into the safety distance.
Description Defines the behavior if the level rises into the safety distance.
Endress+Hauser 93
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Options • Good
• Uncertain
• Bad
Options • No
The alarm is not rest.
• Yes
The alarm is reset. The measurement is resumed.
Factory setting No
94 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Endress+Hauser 95
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Description of parameters
Preerequisite Only visible for operation via display module; not visible for FieldCare operation.
Description Defines which curves are included in the envelope curve display on the display module.
Additional information The display of the selected curve can be accessed in the following way:
A0014279
96 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Overview
The mapping is used to suppress interference signals which may be generated by internal
tank or silo fittings. A mapping curve, representing the envelope curve of an empty tank
or silo as precisely as possible, is used for the mapping.
In the case of a static envelope curve evaluation 3), all echos below the mapping curve are
ignored in the signal evaluation.
[dB]
0
20
40
1
60
3 3 3 4
80
100 2
120
[m (in)]
A0020608
1 Mapping curve
2 Envelope curve
3 Interference echos; covered by the mapping curve
4 Level echo; exceeds the envelope curve
In the case of a dynamic envelope curve evaluation 3) echos from below the map can also
be taken into account. In this case the static envelope curve evaluation serves as a starting
point as long as enough history information is not yet available.
3) For the difference between static and dynamic envelope curve evaluation refer to the "Expert → Sensor → Echo tracking" submenu.
Endress+Hauser 97
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Factory map
The factory map is adapted to the individual antenna and is therefore permanently stored
in the device and not recorded by the user. It covers the near field of the antenna (ringing
area).
1=
2=
A [dB]
D
4 [m (ft)]
A0020643
1 Envelope curve
2 Factory map
3 Level distance
4 Empty distance
If a new mapping is recorded, the factory map nevertheless remains in the device and can
be reactivated when required by selecting the Factory map option in the Confirm
distance parameter.
98 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
2. Go to the Record map parameter and select the Record map option.
Endress+Hauser 99
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
100 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
1=
2=
A [dB]
4
t
3
A0020647
1 Envelope curve
2 Map
3 Tank/silo height
4 Map gap
1=
2=
A [dB]
4
5
t
3
A0020648
1 Envelope curve
2 Map
3 Tank/silo height
4 Map gap
5 End mapping amplitude
Endress+Hauser 101
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Mapping end point Defines the distance up to which the map is (→ 105)
recorded.
Mapping end point Indicates the distance up to which the map is (→ 105)
recorded.
End of mapping Defines the behavior or the map in the Map (→ 106)
gap.
End mapping amplitude Amplitude of the map in the Map gap (→ 106)
102 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Mapping end point Defines the distance up to which the map is (→ 105)
recorded.
End of mapping Defines the behavior or the map in the Map (→ 106)
gap.
End mapping amplitude Amplitude of the map in the Map gap (→ 106)
Endress+Hauser 103
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Description of parameters
Description Confirmation whether the measured distance matches the actual distance. Depending on
the selection the device automatically determines the range over which the mapping will
be recorded.
1) Only available for "Expert → Sensor → Echo tracking → Evaluation mode" = "Short time history" or "Long time history".
Additional information On the local display the measured distance is displayed together with this parameter.
If the teaching procedure Distance too small or Distance too big is quit before the
distance has been confirmed, a map is not recorded and the teaching procedure is
reset after 60 s.
Distance (1124)
104 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Prerequisite Only visible if the Manual map option has been selected in the Confirm distance
parameter.
Description Definition of the distance up to which the mapping curve will be recorded.
Additional information The distance is measured from the reference point, i.e. from the lower edge of the
mounting flange or the threaded connection.
On the local display the Present mapping parameter is displayed together with this
parameter. Present mapping states up to which distance a mapping has already been
recorded.
Prerequisite Only visible if a value has been entered into the Mapping end point parameter.
Endress+Hauser 105
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Selection • No
The map is not recorded. The device quits the sequence ("End of sequence" is displayed).
• Record map
The map is recorded. When the recording is completed, the new measured distance and
the new mapping range appear on the display. These values must be confirmed by
pressing . The device quits the sequence. ("End of sequence" is displayed.)
• Overlay map
The new map is generated by overlaying the existing map by the envelope curves taken
from the period defined in the Mapping overlay time parameter.
• Factory map
The map permanently stored in the device is used.
• Delete partial map
The map is deleted between the points defined by Mapping start point and Mapping
end point.
Factory setting No
Description Defines the behavior of the map at within the defined Map gap.
106 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Overview
The tank bottom evaluation is intended to prevent an echo loss if the tank is empty.
A [dB] 4
5
3
D [m (ft)]
1 2
4
A0020631
1 Tank/silo height
2 Tank bottom range
3 Min. amplitude TBD
4 Lower level area
5 Tank bottom echo
I no echo is found within the defined tank height (Tank/silo height parameter 4)), the
tank bottom searches beyond this distance in the Tank bottom range to see whether an
echo from the tank bottom exists.
If a tank bottom echo has been found, a level of 0% is assumed. If neither a direct level
echo nor a tank bottom echo has been found, an echo loss is reported (error message
S941).
• Level echoes from within the measruing range always have a higher priority than
the tank bottom echo.
• The first echo factor is not applied to the tank bottom echo.
Tank bottom range Defines the range below Tank/silo height in which a tank bottom echo is (→ 108)
searched for if no direct level echo has been detected.
Endress+Hauser 107
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Description of parameters
Description Defines the range (starting from Tank/silo height) in which the tank bottom echo is
searched for.
Factory setting 15 dB
Description Defines the range in which the last measured level must have been before a tank bottom
echo evaluation is performed.
108 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
t1 A
D1 D
t2 A a D
D3
D2
D1
D2 D
t1 t2 t3 t
t3 A a
D3 D
A0018587
18 Definition of a track: In a new envelope curve, the echo is searched for in a window of width "a" centered
around the echo position in the previous envelope curve. The change of the echo position in the course of
time defines the track.
Evaluation mode "Long time history" (only available for level measurements)
A so-called tank history is used for the determination of the level and a consistency check
of the echoes. For a given tank with a given medium, the positions of the level, interface,
multiple and end-of-probe or tank bottom echoes are in a defined relation to each other.
This relationship is recorded during the operation of the device and stored in the tank
history. On the basis of this tank history, echoes can be reliably allocated, even if one echo
is lost temporarily or if the device was switched off for a while.
Endress+Hauser 109
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Schematic exmaples
[mV]
1 2 3
D1
D1
6
5 4
D0
A0020671
[mV] 1
2
D1
D1
3
D0
A0020672
110 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
History learning Only for PROFIBUS PA and FOUNDATION Fieldbus devices (→ 112)
control Defines which DO block is used to activate or deactivate the recording of the
tank history.
History learning Only for PROFIBUS PA and FOUNDATION Fieldbus devices (→ 113)
Activates or deactivates the recording of the tank history (if the Manual
option has been selected in the History learning control parameter.
Endress+Hauser 111
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Factory setting The Evaluation mode parameter is preset depending on the Tank type or Bin type
parameter, respectively.
112 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Description Defines, which DO block is used to start and stop the recording of the tank track.
Options • Manual
• Digital output 1
• Digital output 2
• Digital output 3
• Digital output 4
Description Starts and stops the recording of the echo track (in case the Manual option has been
selected in the History learning control parameter.
Options • Off
• On
Factory setting On
Endress+Hauser 113
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Overview
The behavior of the sensor can be controlled via two external switch inputs: measurement
can be switched on and off. Furthermore, a specific value can be assigned to the level when
the digital switch signal is present, regardless of the actual filling height.
The parameters
Description External input 1 or 2 is assigned a DO block via which the switch signal is read in.
Options • None
• Digital output 1
• Digital output 2
• Digital output 3
• Digital output 4
Description Defines the response of the level to the presence of a switch signal at external input 1 or 2.
Options • Off
• Minimum (0%)
• Maximum (100%)
• Hold last value
• Fixed value
114 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Description Defines the level value in the event of a switch signal at external input 1 or 2.
Factory setting 0
Additional information The specific unit after linearization that has been selected applies.
Description Specifies the DO block via which measurement can be switched on and off.
Options • Manual
• Digital output 1
• Digital output 2
• Digital output 3
• Digital output 4
Measurement (1082)
Options • On
• Off
Factory setting On
Endress+Hauser 115
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Options • Off
The output is always open (not conductive).
• On
The output is always closed (conductive).
• Event level
The output is normally closed and is only opened if a diagnostic event is present. The
Assign diagnostic level parameter (→ 116)determines for which type of event the
output is opened.
• Limit
The output is normally closed and is only opened if a measured varaible exceeds or falls
below a defined limit. The limit values are defined by the parameters Assign
limit(→ 116), Switch-on value(→ 117)and Switch-off value(→ 117).
• Digital output
The switching state of the output tracks the output value of a DI function block or the DI
output of the advanced diagnostics. The function block is selected in the Assign status
parameter.
Options • Alarm
• Alarm + warning
• Warning
116 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Description Defines the variable to be checked for limit transgression and allocates it to the switch
output.
Options • Off
No measured variable is allocated.
• Level linearized
• Distance
• Terminal voltage
• Electronic temperature
• Relative echo amplitude
Prerequisite Only visible for Switch output function = Limit and Assign limit ≠ Off.
Description Define the switch-on point and switch-off point for the limit evaluation.
Range of values Depending on the selected measuring variable (Parameter Assign limit).
Factory setting Depending on the selected measuring variable (Parameter Assign limit).
Endress+Hauser 117
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Additional information The switching behavior depends on the relative position of the two switch points.
Switch-on point > Switch-off point:
The output is closed if the measured value exceeds the switch-on point.
The output is opened if the measured value falls below the switch-off point.
B
t
D
t
A0015585
A Switch-on point
B Switch-off point
C Output closed
D Output opened
A
t
D
t
A0015586
A Switch-on point
B Switch-off point
C Output closed
D Output opened
118 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Description Allocates a DI block or the DI output of the advanced diagnostics to the switch output.
Options • Off
No digital block is allocated.
• Digital output AD 1
• Digital output AD 2
• Digital output 1
• Digital output 2
• Digital output 3
• Digital output 4
Prerequisite Only visible for Switch output function = Limit and Assign limit ≠ Off.
Factory setting 0s
Prerequisite Only visible for Switch output function = Limit and Assign limit ≠ Off.
Description Defines the delay for the switching off of the output.
Factory setting 0s
Description Defines the switching state of the output in the case of an error.
Endress+Hauser 119
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Options • No
The behavior of the switch output is as described above.
• Yes
The states Opend and Closed are inverted as compared to the description above.
120 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Endress+Hauser 121
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
122 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Endress+Hauser 123
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
124 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Endress+Hauser 125
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Description Use this function to display the current diagnostics message. If two or more messages
occur simultaneously, the message with the highest priority is shown on the display.
Information on what is causing the message, and remedy measures, can be viewed via
the symbol on the display.
User interface Symbol for event behavior, diagnostics event, time the event occurred and event text
Description Use this function to display the diagnostics message last displayed before the current
message. This condition can still apply.
Information on what is causing the message, and remedy measures, can be viewed via
the symbol on the display.
User interface Symbol for event behavior, diagnostics event, time the event occurred and event text
126 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Description Use this function to display the time the device has been in operation since the last device
restart.
User interface Days (d), hours (h), minutes (m) and seconds (s)
Endress+Hauser 127
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Description Use this function to display the current diagnostics messages with the highest priority to
the fifth-highest priority.
Unser interface Symbol for event behavior, diagnostics event and event text
Description Displays the operating time at which the diagnostic message occurred.
128 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Description Use this function to select the category whose event messages are displayed in the events
list.
The status signals are categorized according to NAMUR NE 107: F = failure, M =
maintenance request, C = function check, S = out of specification
Options • All
• Failure (F)
• Mainenance required (M)
• Function check (C)
• Out of specification (S)
• Information (I)
Event list
Description Use this function to display the history of event messages of the category selected in the
Filter options parameter (→ 129). A maximum of 20 event messges are displayed in
chronological order. If the advanced HistoROM function is enabled in the device, the event
list can contain up to 100 entries.
The following symbols indicate whether an event has occurred or has ended:
• : Event has occurred
• : Event has ended
Information on what is causing the message, and remedy measures, can be viewed via
the -button.
User interface • For event messages in category I: information event, event text, "recording event" symbol
and time event occurred
• For event messages in category F, M, C, S (status signal): diagnostic event, event text,
"recording event" symbol and time event occurred
Endress+Hauser 129
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
HistoROM
A HistoROM is a "non-volatile" device memory in the form of an EEPROM.
130 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Device (0011)
Description Use this function to view the serial number of the device. It can also be found on the
nameplate.
Uses of the serial number
• To identify the device quickly, e.g. when contacting Endress+Hauser.
• To obtain specific information on the device using the Device Viewer:
www.endress.com/deviceviewer
User interface Max. 11-digit character string comprising letters and numbers
Description Use this function to view the device firmware version installed.
Description Use this function to view the name of the device. It can also be found on the nameplate.
Endress+Hauser 131
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Description Use this function to view the order code of the device. It can also be found on the
nameplate.
Uses of the order code
• To order an identical spare device.
• To identify the device quickly and easily, e.g. when contacting Endress+Hauser.
Description Use these parameters to display the fist and second part of the extended order code. On
account of length restrictions, the extended order code is split into a maximum of 2
parameters.
The extended order code indicates the version of all the features of the product structure
for the device and thus uniquely identifies the device. It can also be found on the
nameplate.
Uses of the extended order code
• To order an identical spare device
• To check the ordered device features against the shipping note.
Description Use this function to view the version of the electroni nameplate (ENP).
132 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
DD Revision (10709)
Endress+Hauser 133
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Description Use this functionto assign a process variable to the data logging channel.
A total of 500 measured values can be logged. This means:
• 500 data points if 1 logging channel is used
• 250 data points if 2 logging channels are used
• 166 data points if 3 logging channels are used
• 125 data points if 4 logging channels are used
Once the maximum number of data points is reached, the oldest data points in the data log
are cyclically overwritten in such a way that the last 500, 250, 166 or 125 measured
values are always in the log (ring memory principle).
The log contents are cleared if the option selected is changed.
Auswahl • Off
• Level
• Distance
• Current output 1
• Measured current
• Terminal voltage
• Electronics temperature
• Absolute echo amplitude
• Relative echo amplitude
• Signal noise
134 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Description Definition of the logging interval tlog for data logging. This defines the interval between
the individual data points in the data log, and thus the maximum loggable process time
Tlog.
• If 1 logging channel is used: T log = 500 ⋅ t log
• If 2 logging channels are used: T log = 250 ⋅ t log
• If 3 logging channels are used: T log = 166 ⋅ t log
• If 4 logging channels are used: T log = 125 ⋅ t log
Once this time elapses, the oldest data points in the data log are cyclically overwritten such
that a time of Tlog always remains in the meory (ring memory principle).
Nach Ablauf dieser Zeit werden die ältesten im Speicher vorhandenen Datenpunkte
zyklisch überschrieben, so dass immer eine Zeit von Tlog im Speicher bleibt (Ringspeicher-
Prinzip).
The log contents are cleared if the length of the logging interval is changed.
Factory setting 10 s
Options • Cancel
The data are not cleared. All the data are retained.
• Clear data
The logging data are cleared. The logging process starts from scratch.
Endress+Hauser 135
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Description Use this function to view the measured value trend for the logging channel in the form of a
chart.
A0013859
• x-axis: depending on the number of channels selected displays 250 to 1000 measured
values of a process variable.
• y-axis: displays the approximate measured value span and constantly adapts this to the
ongoing measurement.
The process variable whose measured valu curve is displayed is specified in the Assign
channel 1 - Assign channel 4 parameters (→ 134).
136 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Description Use this parameter to view the maximum level measured until now (drag indicator).
Description Use this parameter to view the operating time at which the maximum level has been
measured.
Description Use this parameter to view the minimum level measured until now (drag indicator).
Description Use this parameter to view the operating time at which the minimum level has been
measured.
Endress+Hauser 137
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Description Use this parameter to view the maximum draining speed measured until now (drag
indicator).
Description Use this parameter to view the maximum filling speed measured until now (drag
indicator).
Description Use this parameter to view the maximum electronics temperature measured until now
(drag indicator).
Description Use this parameter to view the operating time at which the maximum electronics
temperature has been measured.
138 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Description Use this parameter to view the minimum electronics temperature measured until now
(drag indicator).
Description Use this parameter to view the operating time at which the minimum electronics
temperature has been measured.
Endress+Hauser 139
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Description Use this function to select a process variable for the simulation process that is activated.
The display alternates between the measured value and a diagnostics message of the
"function check" category (C) while simulation is in progress.
The simulation value of the selected process variable is defined in the Value process
variable parameter.
Options • Off
• Level
• Level linearized
Prerequisite One of the following options is selected in the Assign simulation process variable
parameter:
• Level
• Level linearized
Beschreibung Use this function to enter a simulation value for the selected process variable. Subsequent
measured value processing and the signal output use this simulation value. In this way,
users can verify whether the measuring device has been configured correctly.
Factory setting The current value of the selected process variable at the moment the simulation is
activated.
Description Use this parameter to activate or deactivate the simulation of the switch output.
140 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Auswahl • Off
• On
Description Use this parameter to define the switch status for the simulation.
Auswahl • Open
• Closed
Werkseinstellung Open
Description Use this function to switch the device alarm on and off. In this way, users can verify the
correct adjustment of the current output and the correct function of downstream switching
units.
The display alternates between the measured value and a diagnostics message of the
"function check" category (C) while simulation is in progress:
Options • On
• Off
Endress+Hauser 141
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Selection • No
No device check is performed.
• Yes
A device check is performed.
If the error S941 "Echo lost" is present, a device check is not possible. First you have to
eliminte the cause of this error.
Factory setting No
Display • Installation ok
• Accuracy reduced
A measurement is possible. However, the measuring accuracy may be reduced due to the
signal amplitudes.
• Measurement capability reduced
A measurement is currently possible. Howerver, there is the risk of an echo loss. Check
the mounting position of the device and the dielectric constant of the medium.
• Check not done
Description Displays the operating time at which the last device check has been performed.
Description Displays the result of the device check for the level signal.
142 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Endress+Hauser 143
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Basic principles
The Advanced Diagnostics offers additional options to monitor the process. The device
contains two Advanced Diagnostics Blocks which can be used separately or in combination.
A measuring variable can be assigned to the input of each Advanced Diagnostics Block.
Based on a freely configurable time interval, the variable can be submitted to a statistical
function (e.g. maximum, minimum, mean, slope). Finally, a limit detection can be
parametrized and its result can be transmitted to a digital output.
The result can be displayed and evaluated by a DCS or PLC. If required, it can also be linked
to the second Advanced Diagnostics block and thus it is possible to combine the two results
by the logical operators AND or OR.
144 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
A A
85%
75%
A0019640
Endress+Hauser 145
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
146 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
A L
1
1.2 1.5 2.7 2.8
1.3 2.6
L 1.1
1.4
2
2.2 2.4
A 2.1 2.5
2.3
A0019641
Endress+Hauser 147
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Parameter Description
Hysteresis1/2 (→ 152)
148 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
The parameters
Descriptions Assigns a measuring variable, which is needed for diagnostic purposes, to the Advanced
Diagnostics Block.
Options • None
• Level linearized
• Unfiltered distance
• Relative echo amplitude
• Electronic temperature
• Measured current
• Terminal voltage
• Area of incoupling
Descriptions Links the Advanced Diagnostics Block 1 or 2 to the other Advanced Diagnostics Block in
order to include the linking logic into the configuration (→ 144).
Options • None
• Digital output AD 1
• Digital output AD 2
Prerequisite Only visible if the Advanced Diagnostics Block has been linked to the digital oputput of the
other Advanced Diagnostics Block via the Link AD 1/2 to parameter.
Descriptions Defines the linking logic between the two Advanced Diagnostics Blocks AD1 and AD2.
Endress+Hauser 149
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Options • AND
• OR
Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.
Factory setting 10 s
Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.
Descriptions Defines, which quantity is derived from the assigned measured variable.
Options • Off
• Maximum
• Minimum
• Mean
• Standard deviation
• Difference Max. - Min.
• Slope
Additional information The calculation is performed based on the defined Sample time. (I.e. the maximum,
minimum, mean, standard deviation, difference max.-min. or average slope within the
sample time are calculated.)
150 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.
Options • Off
• Upper limit
• Lower limit
• In range
• Out of range
Additional information If a calculation has been selected in the Calculation type parameter, the check does not
refer to the assigned measuring variable but to the quantity calculated from it.
Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.
Options Depending on the selected Calculation type and the measuring variable selected in Assign
diagnostic signal.
Factory setting Depending on the selected Calculation type and the measuring variable selected in Assign
diagnostic signal.
Prerequisite Only visible if one of the following options has been selected in the Check mode
parameter:
• Upper limit
• In range
• Out of range
Endress+Hauser 151
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Descriptions Defines the upper limit for the selected check mode.
Options Depending on the selected Calculation type and the measuring variable selected in Assign
diagnostic signal.
Factory setting Depending on the selected Calculation type and the measuring variable selected in Assign
diagnostic signal.
Prerequisite Only visible if one of the following options has been selected in the Check mode
parameter:
• Lower limit
• In range
• Out of range
Descriptions Defines the lower limit for the selected check mode.
Options Depending on the selected Calculation type and the measuring variable selected in Assign
diagnostic signal.
Factory setting Depending on the selected Calculation type and the measuring variable selected in Assign
diagnostic signal.
Prerequisite Only visible if one of the following options has been selected in the Check mode
parameter:
• Upper limit
• Lower limit
• In range
• Out of range
Options Depending on the selected Calculation type and the measuring variable selected in Assign
diagnostic signal.
Factory setting Depending on the selected Calculation type and the measuring variable selected in Assign
diagnostic signal.
152 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.
Descriptions Indicates the maximum value the assigned measuring variable has attained (dragging
indicator).
Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.
Descriptions Indicates the minimum value the assigned measuring variable has attained (dragging
indicator).
Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.
Description Resets the Maximum value and Minimum value dragging indicators.
Options • Off
• Reset max.
• Reset min.
• Reset min./max.
Endress+Hauser 153
The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.
Description Assigns an event category according to NAMUR NE107 to the event of the Advanced
Diagnostics Block.
Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.
Description Assigns an event behavior to the event of the Advanced Diagnostics Block.
Options • Off
• Alarm
• Warning
• Logbook entry only
Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.
Description Assigns an event behavior to the event of the Advanced Diagnostics Block.
154 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Factory setting 10 s
Endress+Hauser 155
Index Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
Index
A Decimal places 2 (Parameter) . . . . . . . . . . . . . . . . . . 25
Absolute echo amplitude (Parameter) . . . . . . . . . . . . 65 Decimal places 3 (Parameter) . . . . . . . . . . . . . . . . . . 25
Access status display (Parameter) . . . . . . . . . . . . . . . 18 Decimal places 4 (Parameter) . . . . . . . . . . . . . . . . . . 25
Access status tooling (Parameter) . . . . . . . . . . . . . . . 19 Decimal places menu (Parameter) . . . . . . . . . . . . . . . 28
Acknowledge alarm (Parameter) . . . . . . . . . . . . . . . . 94 Define access code (Parameter) . . . . . . . . . . . . . . . . . 35
Activate SW option (Parameter) . . . . . . . . . . . . . . . . 36 Delay time echo lost (Parameter) (Parameter) . . . . . . 92
Activate table (Parameter) . . . . . . . . . . . . . . . . . . . . . 63 Device (Parameter) . . . . . . . . . . . . . . . . . . . . . . . . . 131
Actual diagnostics (Parameter) . . . . . . . . . . . . . . . . 126 Device name (Parameter) . . . . . . . . . . . . . . . . . . . . 131
Advanced process conditions (Parameter) . . . . . . . . . 41 Device reset (Parameter) . . . . . . . . . . . . . . . . . . . . . . 36
Alarm delay 1 (Parameter) . . . . . . . . . . . . . . . . . . . 154 Device Revision (Parameter) . . . . . . . . . . . . . . . . . . 133
Alarm delay 2 (Parameter) . . . . . . . . . . . . . . . . . . . 154 Device type (Parameter) . . . . . . . . . . . . . . . . . . . . . 133
Application parameter (Parameter) . . . . . . . . . . . . . . 42 Diagnostics 1 (Parameter) . . . . . . . . . . . . . . . . . . . . 128
Area of incoupling (Parameter) . . . . . . . . . . . . . . . . 143 Diagnostics 2 (Parameter) . . . . . . . . . . . . . . . . . . . . 128
Assign channel 1 (Parameter) . . . . . . . . . . . . . . . . . 134 Diagnostics 3 (Parameter) . . . . . . . . . . . . . . . . . . . . 128
Assign channel 2 (Parameter) . . . . . . . . . . . . . . . . . 134 Diagnostics 4 (Parameter) . . . . . . . . . . . . . . . . . . . . 128
Assign channel 3 (Parameter) . . . . . . . . . . . . . . . . . 134 Diagnostics 5 (Parameter) . . . . . . . . . . . . . . . . . . . . 128
Assign channel 4 (Parameter) . . . . . . . . . . . . . . . . . 134 Diameter (Parameter) . . . . . . . . . . . . . . . . . . . . . . . . 60
Assign diagnostic level (Parameter) . . . . . . . . . . . . . 116 Direct access (Parameter) . . . . . . . . . . . . . . . . . . . . . 18
Assign diagnostic signal 1 (Parameter) . . . . . . . . . . 149 Display channel 1 (Parameter) . . . . . . . . . . . . . . . . . 135
Assign diagnostic signal 2 (Parameter) . . . . . . . . . . 149 Display channel 2 (Parameter) . . . . . . . . . . . . . . . . . 135
Assign event behaviour 1 (Parameter) . . . . . . . . . . . 154 Display channel 3 (Parameter) . . . . . . . . . . . . . . . . . 135
Assign event behaviour 2 (Parameter) . . . . . . . . . . . 154 Display channel 4 (Parameter) . . . . . . . . . . . . . . . . . 135
Assign limit (Parameter) . . . . . . . . . . . . . . . . . . . . . 116 Display damping (Parameter) . . . . . . . . . . . . . . . . . . 26
Assign simulation process variable (Parameter) . . . . 140 Display interval (Parameter) . . . . . . . . . . . . . . . . . . . 26
Assign status (Parameter) . . . . . . . . . . . . . . . . . . . . 118 Distance (Parameter) . . . . . . . . . . . . . . . . . . . . . . 46, 73
Assign status signal to AD event 1 (Parameter) . . . . 153 Distance offset (Parameter) . . . . . . . . . . . . . . . . . . . . 46
Assign status signal to AD event 2 (Parameter) . . . . 153 Distance unit (Parameter) . . . . . . . . . . . . . . . . . . . . . 38
Distanz (Parameter) . . . . . . . . . . . . . . . . . . . . . . . . 104
B Document
Backlight (Parameter) . . . . . . . . . . . . . . . . . . . . . . . . 29 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Backup state (Parameter) . . . . . . . . . . . . . . . . . . . . . 32 Document function . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Bin property (Parameter) . . . . . . . . . . . . . . . . . . . . . . 39
Blocking distance (Parameter) . . . . . . . . . . . . . . . . . . 78 E
Electronic temperature (Parameter) . . . . . . . . . . . . . . 68
C Empty calibration (Parameter) . . . . . . . . . . . . . . . . . . 47
Calculated DC value (Parameter) . . . . . . . . . . . . . . . . 44 End mapping amplitude (Parameter) . . . . . . . . . . . . 106
Calculation type 1 (Parameter) . . . . . . . . . . . . . . . . 150 End of mapping (Parameter) . . . . . . . . . . . . . . . . . . 106
Calculation type 2 (Parameter) . . . . . . . . . . . . . . . . 150 ENP version (Parameter) . . . . . . . . . . . . . . . . . . . . . 132
Calculation unit 1 (Parameter) . . . . . . . . . . . . . . . . . 151 Enter access code (Parameter) . . . . . . . . . . . . . . . . . . 19
Calculation unit 2 (Parameter) . . . . . . . . . . . . . . . . . 151 Envelope curve (Parameter) . . . . . . . . . . . . . . . . . . . . 96
Check mode 1 (Parameter) . . . . . . . . . . . . . . . . . . . 150 Evaluation mode (Parameter) . . . . . . . . . . . . . . . . . 112
Check mode 2 (Parameter) . . . . . . . . . . . . . . . . . . . 150 Event list (Parameter) . . . . . . . . . . . . . . . . . . . . . . . 129
Clear logging data (Parameter) . . . . . . . . . . . . . . . . 135 Extended order code (Parameter) . . . . . . . . . . . . . . . 132
Comparison result (Parameter) . . . . . . . . . . . . . . . . . 32 Extended order code 1 (Parameter) . . . . . . . . . . . . . 132
Configuration management (Parameter) . . . . . . . . . . 31 Extended order code 2 (Parameter) . . . . . . . . . . . . . 132
Confirm access code (Parameter) . . . . . . . . . . . . . . . . 35 External pressure (Parameter) . . . . . . . . . . . . . . . . . . 84
Confirm distance (Parameter) . . . . . . . . . . . . . . . . . 104 External pressure selector (Parameter) . . . . . . . . . . . . 83
Const. GPC factor (Parameter) . . . . . . . . . . . . . . . . . . 85
Contrast display (Parameter) . . . . . . . . . . . . . . . . . . . 28 F
Control measurement (parameter) . . . . . . . . . . . . . . 115 Filter options (Parameter) . . . . . . . . . . . . . . . . . . . . 129
Customer value (Parameter) . . . . . . . . . . . . . . . . . . . 63 Firmware version (Parameter) . . . . . . . . . . . . . . . . . 131
Fixed value input 1/2 (parameter) . . . . . . . . . . . . . . 114
D Format display (Parameter) . . . . . . . . . . . . . . . . . . . . 23
DD Revision (Parameter) . . . . . . . . . . . . . . . . . . . . . 133 Found echoes (Parameter) . . . . . . . . . . . . . . . . . . . . . 67
Dead time (Parameter) . . . . . . . . . . . . . . . . . . . . . . . 74 Free field special (Parameter) . . . . . . . . . . . . . . . . . . 69
Decimal places 1 (Parameter) . . . . . . . . . . . . . . . . . . 25 Free text (Parameter) . . . . . . . . . . . . . . . . . . . . . . . . 59
156 Endress+Hauser
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus Index
Endress+Hauser 157
Index Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
T
Table mode (Parameter) . . . . . . . . . . . . . . . . . . . . . . 61
Table number (Parameter) . . . . . . . . . . . . . . . . . . . . . 62
Tank bottom echo amplitude (Parameter) . . . . . . . . . 67
Tank bottom range (Parameter) . . . . . . . . . . . . . . . . 108
Tank trace state (Parameter) . . . . . . . . . . . . . . . . . . . 67
Tank type (Parameter) . . . . . . . . . . . . . . . . . . . . . . . 38
Tank/silo height (Parameter) . . . . . . . . . . . . . . . . . . 53
Temperature unit (Parameter) . . . . . . . . . . . . . . . . . . 38
Time max. electronics temperature (Parameter) . . . . 138
Time max. level (Parameter) . . . . . . . . . . . . . . . . . . 137
Time min. electronics temperature (Parameter) . . . . 139
Time min. level (Parameter) . . . . . . . . . . . . . . . . . . 137
Timestamp (Parameter) . . . . . . . . . . . . . . . . . . . . . 128
Tube diameter (Parameter) . . . . . . . . . . . . . . . . . . . . 39
U
Unit after linearization (Parameter) . . . . . . . . . . . . . . 58
Upper limit 1 (Parameter) . . . . . . . . . . . . . . . . . . . . 151
Upper limit 2 (Parameter) . . . . . . . . . . . . . . . . . . . . 151
Used calculation (Parameter) . . . . . . . . . . . . . . . . . . . 67
V
Value 1 display (Parameter) . . . . . . . . . . . . . . . . . . . 25
Value 2 display (Parameter) . . . . . . . . . . . . . . . . . . . 25
Value 3 display (Parameter) . . . . . . . . . . . . . . . . . . . 25
Value 4 display (Parameter) . . . . . . . . . . . . . . . . . . . 25
Value echo lost (Parameter) . . . . . . . . . . . . . . . . . . . . 91
Value process variable (Parameter) . . . . . . . . . . . . . 140
158 Endress+Hauser
*71219978*
71219978
www.addresses.endress.com