You are on page 1of 31

NFPA 780, “2017” REVIEW SUMMARY 

 
 
1) NFPA 780 REVISION SUMMARY 
 
NFPA first adopted Specifications for Protection of Buildings Against Lightning in 1904. 
Revised standards were adopted in 1905, 1906, 1925, 1932, and 1937. In 1945, the NFPA 
Committee and the parallel American Standards Association (ASA) Committee on Protection 
Against Lightning were reorganized and combined under the sponsorship of NFPA, the National 
Bureau of Standards, and the American Institute of Electrical Engineers (now the IEEE). In 1946, 
NFPA acted to adopt Part III and in 1947 published a revised edition incorporating this part. 
Further revisions recommended by the Committee were adopted by NFPA in 1949, 1950, 1951, 
1952, 1957, 1959, 1963, 1965, 1968, 1975, 1977, 1980, 1983, 1986, 1989, and 1992. 
 
Commencing with the 1992 edition of the Lightning Protection Code, the NFPA 
numerical designation of the document was changed from NFPA 78 to NFPA 780.  
 
With the issuance of the 1995 edition, the name of the document was changed from 
Lightning Protection Code to Standard for the Installation of Lightning Protection Systems. This 
change was directed by the Standards Council in order to make the title more accurately reflect 
the document's content. In addition, the Council directed certain changes to the scope of the 
document to clarify that the document did not cover lightning protection installation 
requirements for early streamer emission systems or lightning dissipater array systems. 
 
The 1997 edition of NFPA 780 incorporated editorial changes to make the document 
more user friendly. 
 
In issuing this document, the Standards Council noted that lightning is a stochastic, if not 
capricious, natural process. Its behavior is not yet completely understood. This standard is 
intended to provide requirements, within the limits of the current state of knowledge, for the 
installation of those lightning protection systems covered by the standard. 
 
The 2000 edition of NFPA 780 was amended to provide requirements for open 
structures such as those found on golf courses. A 1998 lightning flash density chart replaced the 
1972 lightning frequency isokeraunic chart. 
 
The 2004 edition of NFPA 780 reflected an extensive editorial revision of the standard to 
comply with the concurrent edition of the Manual of Style for NFPA Technical Committee 
Documents. Those revisions included the addition of three administrative chapters at the 
beginning of the standard:  Administration, Referenced Publications, and Definitions. Five 
technical chapters followed the administrative chapters in the same sequence as in the 2000 
edition. Other editorial revisions included the breakout of paragraphs with multiple 
requirements into an individually numbered paragraph for each requirement, the minimization 
of the use of exceptions, the use of consistent headings for sections and section subdivisions, 
and reorganization to limit paragraph numbering to six digits. The International System of Units, 
commonly known as SI or metric, was used throughout the document. The appendixes were 
renamed annexes and reordered in a more logical sequence. 
 
The 2004 edition also contained a number of technical revisions throughout the 
standard. Those revisions included the following: a main conductor, solid strip, was added for 
Class II material requirements for ordinary structures exceeding 75 ft in height; handrails could 
be used as substitute for down conductors; additional separation between ground rods was 
required where multiple ground rods are used; additional guidance was provided for those 
instances where it is necessary to install the grounding conductor directly on bedrock; the 
section entitled Surge Suppression was entirely rewritten; titanium strike termination devices 
were permitted to be used; and in Annex K, the term Faraday cage was replaced with metallic 
cage.  
 
The 2008 edition provided requirements for surge protective devices to be installed at 
all power service entrances, at the entrance of conductive communications systems and 
antenna systems, and where an electrical or electronic system conductor leaves the structure. 
 
The new definition for lightning protection system included the term conductive 
structural members. Clarification was provided relative to the use of ancillary metal parts that 
cannot be substituted for the main conductor. Strike termination devices included air terminals, 
metal masts, certain permanent metal parts of structures, and elevated conductors. Revisions 
clarified that metal masts and overhead ground wires were included in the requirements of 
Chapter 4. 
 
Significant changes were made to the requirements for the use of bimetallic clamps and 
aluminum in proximity to earth. The standard has long required that grounding electrodes be 
located near the outside perimeter of the structure, and in the 2008 edition additional guidance 
was provided to assist the system designer. Changes were also made to better address the 
requirements for grounding electrodes in shallow topsoil applications. 
 
The requirements for the use of multiple ground rods were revised. Revisions were also 
made in numerous areas of the standard for clarity and to enhance its usability. Revisions to the 
graphs and formulas for the rolling sphere method were made to facilitate their use in metric 
units. 
 
Requirements were added to address proper installation of lightning protection 
equipment on large roof top mechanical units. The installation of air terminals and main‐size 
conductors in these applications were quantified and detailed.  
 
Revisions were made to enhance and clarify the requirements for the bonding together 
of all grounded media and underground metallic piping. The intent was to provide for potential 
equalization and not to use the metallic piping as a lightning protection system grounding 
electrode. All grounding media and buried metallic conductors that might assist in providing a 
path for lightning currents in or on a structure must be interconnected to provide a common 
ground potential. Guidance was provided on the use of isolating spark gaps. 
 
Significant changes were made to the requirements pertaining to the conductors and 
other lightning protection system hardware used near the top of a heavy‐duty stack. 
 
Other significant changes included a complete rewrite of Chapter 8, Protection for 
Watercraft, providing a number of technical revisions; more user information added in Annex B, 
Principles of Lightning Protection; and a revision of Annex F, Protection for Trees. 
 
In addition to significant technical changes, the 2011 edition included new and revised 
text. With the addition of two new chapters, the 2011 edition of the standard presented a 
major change in the scope of the document. The first new chapter addressed the protection of 
structures housing ammunition and explosive materials. The second new chapter included 
requirements for providing lightning protection for wind turbines, specifically wind turbine 
structures that comprise externally rotating blades, a nacelle, and a supporting tower. The 2011 
edition was substantially reorganized to accommodate these new chapters in a logical order. 
 
The sections pertaining to strike termination devices, zones of protection, and the 
rolling sphere method were totally reorganized for better usability. The text clearly provided 
that strike termination devices include air terminals, metal masts, permanent metal parts of 
structures, and overhead ground wires. The text qualified where a metal mast would be 
permitted to serve as the down conductor. The requirements for overhead ground wires and 
masts and overhead ground wires were relocated. 
 
The 2011 edition clarified the requirements for strike termination devices at the eaves 
for a pitched roof, and a figure was added to graphically illustrate that condition. A new section 
on roof top helipads provided requirements to ensure that an adequate level of protection is 
provided to those areas within the height and safety criteria set forth by the Federal Aviation 
Administration (FAA) or other AHJs. 
 
Chapter 7 provided requirements for the protection of structures containing flammable 
vapors, flammable gases, or liquids that can give off flammable vapors. The section on floating 
roof tanks was revised in its entirety as a result of recent testing and research conducted for 
aboveground storage tanks. 
 
The lightning risk assessment methodology provided in Annex L was completely 
rewritten. The lightning risk assessment was provided to assist the building owner, safety 
professional, or architect/engineer in determining the risk of damage or injury due to lightning. 
This annex provided both a simplified, quick‐look assessment and a more detailed assessment 
for those requiring a more detailed analysis. Once the level of risk has been determined, the 
development of appropriate lightning protection measures can begin. 
 
The 2014 edition provided reorganization of Sections 4.7 and 4.8 to better align the 
requirements for strike termination devices. Reorganization of these sections in a more logical 
order clarified the requirements and application of the standard. Previously, these 
requirements were intermingled, causing confusion and possible misapplication. Section 4.8 
was also revised to clarify the requirements for protection where small objects are located on 
roofs. 
 
Section 4.14 was revised and reorganized to include parts of Section 4.20, and 
explanatory text was provided to ensure clarity, alignment, and coordination with the bonding 
interconnections of NFPA 70 ®, National Electrical Code ®. Sections 4.15 through 4.21 were 
totally restructured and revised to place similar bonding requirements together to improve the 
flow of the document for the user. Similar or repetitive requirements were combined or 
restructured to clarify the requirements. 
 
A new subsection in the 2014 edition, 4.7.13, addressed the use on buildings of fixed 
metal objects that have movable or rotating metal components, for example, jib cranes, wind 
socks, observatories/telescopes, opening roofs (typically over swimming pools), window 
washing davits/cars (left permanently on the roof, typically on a track), construction cranes, 
panning security cameras, broadcast television cameras, traffic cameras, radar dishes, weather 
vanes, gravity vents, roofmounted wind turbines, smoke hatches/blowout hatches, opening 
skylights, and photovoltaic arrays (motorized arrays that tilt to track the sun as it moves across 
the sky). 
 
NFPA 780 was revised to reformat the use of U.S. customary (inch‐pound) and metric 
(SI) units. U.S. customary units are followed by SI units in parentheses. Several formulas and 
tables were updated to provide both U.S. customary (inch‐pound) and metric (SI) units. Also, a 
new section, Section 1.4, was added to address retroactivity for NFPA 780. 
 
A new chapter, Chapter 11, was added to provide lightning protection criteria 
requirements and guidance for airfield lighting circuits. Development of this chapter began 
prior to the 2011 edition but was held by the Committee in anticipation of new material and to 
enable better alignment with federal aviation requirements. Chapter 11 provides a thorough 
look at design and installation of lightning protection systems to afford protection to those 
open areas. Several figures provide ample explanation and guidance to the user. 
 
As the demand for renewable and alternative energy sources continues, there is a rapid 
deployment of solar systems and arrays. Because these are often installed on roof tops, there is 
a risk of greater exposure. Buildings provided with lightning protection systems now see a 
greater abundance of roof top‐mounted equipment, and the lightning protection system might 
not be designed to address the new equipment. Buildings not provided with lightning 
protection systems might need to address the additional mechanical structure and equipment. 
A new Chapter 12 addressed lightning protection systems for solar systems and arrays. 
 
The requirements pertaining to catenary systems were reviewed, and significant annex 
material was provided to clarify computations for applications with metal or wood poles. 
 
For the 2017 edition, new requirements have been added relative to physical on‐site 
inspection of the completed installation and for periodic inspections or testing for compliance 
to this standard per the authority having jurisdiction. New definitions have been added for the 
following terms: ground loop conductor, integral lightning protection system, mast‐type 
lightning protection system, rated impulse withstand voltage level (withstand voltage) (UW), 
smart structure, solar array, and solar panel. Those definitions add clarity to the terms as used 
in the standard. 
 
Several figures illustrating air terminal protection for lower roof protection have been 
updated. New requirements have been established for test and connection points for concrete‐
encased electrodes to enable periodic maintenance and testing of the ground system. Zero 
property line conditions have been re‐evaluated and revised. New bonding requirements have 
been added for long horizontal metal bodies on roofs. The Committee revised many 
requirements pertaining to ungrounded metal bodies, removing the term isolated 
(ungrounded) for consistency. Section 5.3 pertaining to Facilities That Handle or Process 
Combustible or Explosive Dust has been updated, providing specific reference to NFPA 61, 
Standard for the Prevention of Fires and Dust Explosions in Agricultural and Food Processing 
Facilities; NFPA 122, Standard for Fire Prevention and Control in Metal/Nonmetal Mining and 
Metal Mineral Processing Facilities; and NFPA 664, Standard for the Prevention of Fires and 
Explosions in Wood Processing and Woodworking Facilities. Section 5.9 provides new criteria for 
installations on fabric structures. Chapter 7, Protection for Structures Containing Flammable 
Vapors, Flammable Gases, or Liquids That Can Give Off Flammable Vapors was rewritten. 
Sections in Chapter 8, Protection of Structures Housing Explosive Materials, that pertain to 
single or multiple masts, railroad tracks, installation of air terminals on earth‐covered 
magazines, wharves, and piers for explosives operations and cranes were revised. Chapter 12, 
Protection for Solar Arrays, was revised to provide more specific criteria.  
 
Two new annexes, Annex J, Protection of Smart Structures, and Annex K, Guide to 
International Standards Dealing with the Selection of SPDs for Use on Photovoltaic (PV) 
Installations, have been added to the 2017 edition. Annex L, Lightning Risk Assessment, has 
been revised to provide greater clarity and correlation of requirements with other lightning 
protection standards 
 
 
 
 
 
 
 
 
 
2) SIGNIFICANT CHANGES  
 
a) For chapters that may have significant changes only: 
 

Chapter 1 pg 7  Administration 
2014 Edition  2017 Edition  Comments 
  1.5.3 Where required by the 
authority having jurisdiction, 
compliance of the completed 
installation with the 
requirements of this standard 
shall be certified through a 
physical onsite inspection by a  A certification, inspection 
qualified and impartial  and testing program may 
organization acceptable to the  require additional 
authority having jurisdiction.  resources depending on 
  frequency required by AHJ. 
1.6.1 Periodic Inspection. 
Periodic inspections or testing 
for compliance to this 
standard shall be done at 
intervals determined by the 
authority having jurisdiction. 
 
Chapter 5 pg 29  Protection for Miscellaneous Structures
and Special Occupancies 
2014 Edition  2017 Edition  Comments 
5.9 Fabric Structures. 
5.9.1 Fabric structures shall 
be protected in accordance 
with Chapter 4. 
 
5.9.2 If a fabric structure has a 
metal frame, the metal frame  New requirements for 
shall be bonded to the  fabric structures. 
 
lightning protection system.    
 
5.9.3 If the structural metal 
framing is at least 1∕8 in. (3 
mm) thick, the framing shall 
be permitted to be used as 
main‐size conductors.  
 
5.9.4 Grounding systems shall 
be installed in accordance 
with Chapter 4 and in 
accordance with 5.9.4.1 or 
5.9.4.2 to mitigate the threat 
of step potential. 
 
5.9.4.1 All of the following 
shall be satisfied: 
 
(1) Fabric structures that have 
a fabric or earth floor shall 
have a ground loop 
conductor. 
 
(2) Fabric structures that have 
electrically continuous metal 
framing around the perimeter 
of the structure shall be 
permitted to be used as the 
ground loop conductor if it is 
at least 1∕8 in. (3 mm) thick. 
 
(3) Fabric structures that have 
a fabric or earth floor shall 
have a minimum of two radial 
grounding electrodes installed 
at opposing corners. 
 
(4) Fabric structures that have 
a fabric or earth floor shall 
have one radial electrode for 
every 60 ft (18 m) of 
protected perimeter, of 
portion thereof, in accordance 
with 4.19.4.1. 
 
5.9.4.2* A ground grid shall 
be installed under fabric 
structures with an earth or 
fabric floor 
b) If there are no substantial changes for a chapter then: 
 
Chapter 2 pg 8  Referenced Publications 
2014 Edition  2017 Edition  Comments 
  No changes   
 
Chapter 3 pg 8  Definitions
2014 Edition  2017 Edition  Comments 
3.3.7.4 Ground Loop 
Conductor. A main‐size loop 
conductor installed within 12 ft 
(3.6 m) vertically of the base of 
the structure to provide a 
common ground potential. 
 
3.3.21 Integral Lightning 
Protection System. A lightning 
protection system directly 
attached to the structure. 
 
3.3.29 Mast‐Type Lightning 
Protection System. A lightning 
protection system using one or 
more masts that are remote 
from the structure to provide 
New definitions. 
  the primary attachment point 
for a lightning discharge. 
 
3.3.35 Smart Structure. A 
structure that has a high 
degree of interconnected 
automatic systems for lighting, 
temperature control, 
multimedia systems, 
telecommunications, security, 
window and door operations, 
and other functions. 
 
3.3.36 Solar Array. A group of 
solar modules or collectors 
wired or connected together in 
a string or larger collection 
system. 
 
3.3.37* Solar Panel. A general 
term for thermal collectors or 
photovoltaic (PV) modules. 
 
3.3.47.6 Rated Impulse 
Withstand Voltage Level 
(Withstand Voltage) 
(UW). Impulse withstand 
voltage assigned by the 
manufacturer to wiring and 
equipment, or to a part of it, 
characterizing the specified 
withstand capability of its 
insulation against (transient) 
overvoltages. 
 
Chapter 4 pg 11  General Requirements 
2014 Edition  2017 Edition  Comments 
4.13.3.3 A test or connection 
point shall be provided on 
each concrete‐encased 
electrode to enable periodic 
maintenance and testing of 
the ground system. (See 
Figure 4.13.3.3.) 
  New Concrete‐Encased 
4.16.3 Long Horizontal Metal  Electrodes test/connection 
Bodies on Roofs. Long  point requirement 
horizontal grounded metal   
  bodies on roofs shall be  & 
bonded in accordance with   
4.16.3.1 through 4.16.3.3.  New requirements for Long 
  Horizontal Metal Bodies on 
4.16.3.1 Grounded metal  Roofs 
bodies on roofs exceeding 60 
ft (18 m) in horizontal length 
shall be bonded to the 
lightning protection system as 
near as practicable to their 
extremities unless inherently 
bonded through construction 
at those locations. 
 
4.16.3.2 Horizontal grounded 
metal bodies that are parallel 
to a main lightning conductor 
and that are within the 
bonding distance calculated in 
4.16.2.4 or 4.16.2.5 shall be 
bonded to the main 
conductor at intervals 
averaging not more than 100 
ft (30 m) along the main 
conductor unless inherently 
bonded through construction 
at those locations. 
 
4.16.3.3 Horizontal grounded 
metal bodies that cross a 
main conductor shall be 
bonded to the main 
conductor where they cross 
the conductor unless 
inherently bonded through 
construction at that location. 
 
Chapter 6 pg 30  Protection for Heavy‐Duty Stacks
2014 Edition  2017 Edition  Comments 
No changes   
 
Protection for Structures Containing 
Flammable Vapors, Flammable Gases, 
Chapter 7 pg 30 
or Liquids That Can Give Off Flammable 
Vapors 
2014 Edition  2017 Edition  Comments 
7.1 Reduction of Damage.  7.1* Applicability. 
   
7.1.1* Application.  7.1.1 This chapter shall apply 
The entire chapter was 
  to the protection of structures 
rewritten 
7.1.1.1 This chapter shall  containing flammable vapors, 
apply to the protection of  flammable gases, or liquids 
structures containing  that give off flammable 
flammable vapors, flammable  vapors. 
gases, or liquids that give off   
flammable vapors.  7.1.2* The retroactivity 
  requirements of Section 1.4 
7.1.1.2 For the purpose of this  shall be permitted to be 
chapter, the term structure  applicable to the 
shall apply to any outdoor  requirements of this chapter. 
vessel, tank, or other   
container where this material  7.2 Principles of Protection. 
is contained.  Protection of structures 
  containing flammable vapors, 
7.1.2 Certain types of  flammable gases, or liquids 
structures used for the  that give off flammable 
storage of liquids that  vapors and their contents 
produce flammable vapors or  from lightning damage shall 
used to store flammable gases  be required to comply with 
are essentially self‐protecting  7.2.1 through 7.2.3. 
against damage from lightning   
strokes and shall need no  7.2.1* Minimization of 
additional protection.  Exposure to Hazardous 
  (Classified) Locations. A 
7.1.2.1 Metallic structures  primary means to reduce the 
that are electrically  ignition of flammable vapors 
continuous; tightly sealed to  shall be to minimize the 
prevent the escape of liquids,  exposure of locations that 
vapors, or gases; and of 3⁄16  experience a direct strike or 
in. (4.8 mm) thickness or  secondary arcing. Flammable 
greater to withstand direct  air–vapor mixtures shall be 
strikes in accordance with  prevented, to the greatest 
7.3.2 shall be considered to be  possible extent, from 
inherently self‐protecting.  accumulating outside such 
  structures. 
7.1.2.2 Protection of other   
structures shall be achieved  7.2.1.1 Openings where 
by the use of strike  flammable concentrations of 
termination devices.   vapor or gas escape to the 
  atmosphere shall be closed or 
7.1.3* Because of the nature  otherwise protected against 
of the contents of the  the entrance of flame. 
structures considered in this   
chapter, extra precautions  7.2.1.2 Structures and all 
shall be taken.  appurtenances (e.g., gauge 
  hatches, vent valves, floating 
7.2 Fundamental Principles of  roof seals) shall be 
Protection. Protection of  maintained in operating 
these structures and their  condition. 
contents from lightning   
damage shall require  7.2.2 Inherent Protection. 
adherence to the principles of  Metallic structures that are 
7.2.1 through 7.2.5.  electrically continuous; tightly 
  sealed to prevent the escape 
7.2.1 Liquids that give off  of liquids, vapors, or gases; 
flammable vapors shall be  and of 3⁄16 in. (4.8 mm) 
stored in essentially gastight  thickness or greater to 
structures.  withstand direct strikes shall 
  be considered to be 
7.2.2 Openings where  inherently self‐protecting. 
flammable concentrations of   
vapor or gas escape to the  7.2.3 Lightning Protection 
atmosphere shall be closed or  System. Structures not 
otherwise protected against  meeting the requirements 
the entrance of flame.  of7.2.2 shall be provided with 
  protection in accordance with 
7.2.3 Structures and all  the requirements of Section 
appurtenances (e.g., gauge  7.3 except as modified for 
hatches, vent valves) shall be  specific types of structures 
maintained in operating  (see Section 7.4). 
condition.   
  7.3 Protective Measures. 
7.2.4 Flammable air–vapor   
mixtures shall be prevented,  7.3.1 Materials and 
to the greatest possible  Installation. Conductors, 
extent, from accumulating  strike termination devices, 
outside such structures.  surge protection, and 
  grounding connections shall 
7.2.5 Potential spark gaps  be selected and installed in 
between conductive surfaces  accordance with the 
shall not be allowed at points  requirements of Chapter 4 
where flammable vapors  except as modified in this 
escape or accumulate.  chapter. 
   
7.3 Protective Measures.  7.3.2 Zone of Protection. The 
  zone of protection for 
7.3.1 Materials and  structures containing 
Installation. Conductors,  flammable vapors, flammable 
strike termination devices,  gases, or liquids that can give 
surge protection, and  off flammable vapors shall be 
grounding connections shall  based on a striking distance of 
be selected and installed in  100 ft (30 m) or less. 
accordance with the   
requirements of Chapter 4  7.3.3 Strike Termination 
and as described in this  Devices. 
chapter.   
  7.3.3.1 Strike termination 
7.3.2 Zone of Protection for  devices shall be in accordance 
Masts and Overhead Ground  with Section 4.6. 
Wires.   
  7.3.3.2* The placement of 
7.3.2.1 The zone of protection  strike termination devices 
of a lightning protection mast  shall take into consideration 
shall be based on the striking  that it is possible for sparks or 
distance of the lightning  damaging impact to occur at 
stroke.  the attachment point. 
   
7.3.2.2 Since the lightning  7.3.4 Down Conductors. 
stroke can strike any   
grounded object within the  7.3.4.1 Down conductors shall 
striking distance of the point  be installed in accordance 
from which final breakdown  with 4.9.9 except as modified 
to ground occurs, the zone of  in this chapter. 
protection shall be defined by   
a circular arc concave upward,  7.3.4.2 Down conductors shall 
shown in part (a) of Figure  be installed external to the 
7.3.2.2.  hazardous (classified) location 
  where practicable. 
7.3.2.3 The radius of the arc is   
the striking distance, and the  7.3.4.3* Where it is not 
arc shall pass through the tip  practicable to install down 
of the mast and be tangent to  conductors external to the 
the ground.  hazardous location, it shall be 
  ensured that the autoignition 
7.3.2.4* Where more than  temperature of the gas or 
one mast is used, the arc shall  vapor causing the hazardous 
pass through the tips of  environment is not exceeded. 
adjacent masts, as shown in   
part (b) of Figure 7.3.2.2 and  7.3.5 Bonding. The potential 
in Figure 7.3.2.4. The distance  equalization system design 
can be determined  and minimum installation 
analytically for a 100 ft (30 m)  requirements of Section 4.14 
striking distance with the  through Section 4.16 shall be 
following equation (units shall  exceeded as required to 
be consistent, ft or m):  ensure there are no melting 
  or spraying effects except at 
d =  1 2 1 the lightning attachment 
2 2 point. 

   
where:  7.3.6 Surge Protection. 
   
d = horizontal protected  7.3.6.1 Surge protection shall 
distance  be provided for equipment 
h1 = height of the higher mast  and services in accordance 
R = rolling sphere radius [100  with the requirements of 
ft (30 m)]  Section 4.20 and NFPA 70. 
h2 = height of the lower mast   
  7.3.6.2 Surge protective 
7.3.2.5 The zone of protection  devices shall be positioned 
shall be based on a striking  outside a hazardous area 
distance of 100 ft (30 m) or  where practicable. 
less.   
  7.3.6.3 Surge protective 
7.3.2.6 Overhead Ground  devices positioned inside a 
Wire.  hazardous Area 
7.3.2.6.1 The zone of   
protection of an overhead  7.3.7* Grounding. 
ground wire shall be based on   
a striking distance of 100 ft  7.3.7.1 A ground ring 
(30 m) and defined by 100 ft  electrode or ground loop 
(30 m) radius arcs concave  conductor supplemented by 
upward. [See part (b) of Figure  grounding electrodes as 
7.3.2.2.]  identified in 4.13.2 through 
  4.13.7 shall be provided for 
7.3.2.6.2 The supporting  structures containing 
masts shall have a clearance  flammable vapors, flammable 
from the protected structure  gases, or liquids that can give 
in accordance with 4.6.5.  off flammable vapors. 
   
7.3.2.6.3 The masts or  7.3.7.2 A metal tank shall be 
overhead ground wires shall  grounded by one of the 
be grounded and  following methods: 
interconnected with the   
grounding system of the  (1) A tank shall be connected 
structure to be protected.  without insulated joints to a 
  grounded metallic piping 
7.3.2.6.4 The grounding  system. 
requirements of Chapter 4   
(2) A vertical cylindrical tank 
shall apply.  shall rest on earth or concrete 
  and shall be at least 20 ft (6 
7.3.2.7 Alternative Grounding  m) in diameter, or shall rest 
Methods.  on bituminous pavement and 
  shall be at least 50 ft (15 m) in 
7.3.2.7.1 Masts of wood, used  diameter. 
either separately or with   
ground wires, shall have an air  (3) A tank shall be grounded 
terminal extending at least 2  through a minimum of two 
ft (0.6 m) above the top of the  grounding electrodes, as 
pole, attached to the pole as  described in Section 4.13, at 
in Figure 7.3.2.7.1, and  maximum 100 ft (30 m) 
connected to the grounding  intervals along the perimeter 
system.  of the tank. 
   
7.3.2.7.2 As an alternative, an  (4) A tank installation using an 
overhead ground wire or a  insulating membrane beneath 
down conductor, extending  for environmental or other 
above or across the top of the  reasons shall be grounded as 
pole, shall be permitted to be  in 7.3.7.2(3). 
used.   
  7.4 Protection of Specific 
7.3.2.7.3 In the case of an  Classes of Structures. 
overhead ground wire system,   
the pole guy wire shall be  7.4.1 Operating Facilities 
permitted to be used as the  (Nonstorage Applications). 
down conductor, provided the   
guy meets the requirement of  7.4.1.1 Structures containing 
7.3.1.  hazardous (classified) 
  locations used in nonstorage 
7.3.2.7.4 For grounded  applications shall comply with 
metallic masts, the air  the requirements of Section 
terminal and the down  7.3 unless justified by a 
conductor shall not be  lightning risk assessment. 
required.   
  7.4.1.2* For structures in 
7.4 Protection of Specific  which the hazardous 
Classes of Structures.  (classified) location exists in 
  only one part of the structure, 
7.4.1 Aboveground Tanks at  it shall be permitted for a risk 
Atmospheric Pressure  assessment to utilize the 
Containing Flammable  lightning protection zone 
Vapors or Liquids That Give  (LPZ) concept in accordance 
Off Flammable Vapors.  with IEC 62305‐2, Protection 
  Against Lightning—Part 2: Risk 
7.4.1.1* Fixed Roof Tanks  Management. 
(Metallic) and Tanks with   
Internal Floating Roofs.  7.4.2 Storage Tanks Under 
Shunts or bypass conductors  Pressure. 
shall not be mandatory for   
lightning protection for fixed  7.4.2.1 Sealed metallic tanks, 
roof and internal floating roof  vessels, and process 
tanks.  equipment that contain 
  flammable or combustible 
7.4.1.2* External Floating  liquids or flammable gases 
Roof Tanks.  under pressure are 
  considered to be inherently 
7.4.1.2.1 Shunt Placement.  selfprotecting provided the 
  vessel is grounded — either 
7.4.1.2.1.1 The shunt‐to‐shell  inherently or by external 
contact point shall be  means — and the walls of the 
submerged at least 1 ft (0.3  vessel are greater than 3∕16 
m) below the surface of the  in. (4.8 mm) thick to prevent 
liquid product.   puncture by a direct strike in 
  accordance with 7.2.2. 
7.4.1.2.1.2 The shunt shall   
have as short and direct a  7.4.2.2 The exposure of any 
path as possible from the  valves or other appurtenances 
conductive floating roof to the  to a direct strike or secondary 
tank shell.  arcing shall be considered in 
  the determination of the need 
7.4.1.2.1.3 The shunts shall be  for protection. 
spaced at intervals no greater   
than 10 ft (3 m) around the  7.4.3 Aboveground Tanks at 
perimeter of the floating roof.  Atmospheric Pressure 
  Containing Flammable 
7.4.1.2.1.4 Above‐deck shunts  Vapors or Liquids That Give 
shall be removed when  Off Flammable Vapors. 
retrofitting existing tanks with   
submerged shunts.  7.4.3.1* Fixed Roof Tanks 
  (Metallic) and Tanks with 
7.4.1.2.2 Shunt Description.  Internal Floating Roofs. 
  Sliding or fixed contact 
7.4.1.2.2.1 The shunts shall  conductors shall not be 
consist of a flexible stainless  mandatory for lightning 
steel conductor of at least  protection for fixed roof and 
0.031 in.2 (20 mm2) cross‐ internal floating roof tanks. 
sectional area or of other 
material conductors of   
equivalent current‐carrying  7.4.3.2 External Floating Roof 
capacity and corrosion  Tanks. 
resistance.   
  7.4.3.2.1* Sliding Contacts. 
7.4.1.2.2.2 The minimum  Sliding contacts shall consist 
width of the shunt shall be 2  of either metallic primary 
in. (50 mm).  shoe seals or shunts. 
   
7.4.1.2.2.3 The shunts shall be  7.4.3.2.1.1 Metallic primary 
of the minimum length  shoe seals shall be electrically 
necessary to permit the  bonded to the floating roof 
function of the floating roof  either inherently through 
assembly.  design and construction or by 
  a minimum of one Class I 
7.4.1.2.2.4 The shunts shall be  lightning protection 
of the minimum length  conductor or equivalent at 
necessary to remain in  each end of each shoe. 
contact with the shell during   
the full horizontal and vertical  7.4.3.2.1.2* If nonconductive 
design movement of the  primary seals are installed, 
floating roof.  shunts shall be installed as 
  follows: 
7.4.1.2.2.5* The shunts and   
terminations shall be of  (1) The shunts shall consist of 
sufficient flexibility, cross‐ a flexible stainless steel 
sectional area, and corrosion  conductor of at least 0.031 
resistance to maximize service  in.2 (20 mm2) cross‐sectional 
life.  area or of other material 
7.4.1.3* Bypass Conductors.  conductors of equivalent 
  current‐carrying capacity and 
7.4.1.3.1 The tank’s floating  corrosion resistance. 
roof shall be bonded to the   
tank shell by direct electrical  (2) The minimum width of the 
connection.   shunt shall be 2 in. (50 mm). 
   
7.4.1.3.2 Each conductor,  (3) The shunts shall be spaced 
including connections, shall  at intervals no greater than 10 
have a maximum end‐to‐end  ft (3 m) around the perimeter 
electrical resistance of 0.03  of the floating roof. 
ohm.   
  (4) The shunt shall have as 
7.4.1.3.3 The bypass  short and direct a path as 
conductor shall be of the  possible from the conductive 
minimum length necessary to  floating roof to the tank shell. 
permit full movement of the   
floating roof.  (5) The shunts shall be of the 
  minimum length necessary to 
7.4.1.3.4 A minimum of two  permit the function of the 
bypass conductors shall be  floating roof assembly. 
evenly spaced not more than   
every 100 ft (30 m) around  (6) The shunts shall be of the 
the tank circumference.  minimum length necessary to 
  remain in contact with the 
7.4.1.3.5* The bypass  shell during the full horizontal 
conductors and terminations  and vertical design movement 
shall be positioned and of  of the floating roof. 
sufficient flexibility, cross‐  
sectional area, and corrosion  (7)* The shunts and 
resistance to maximize service  terminations shall be of 
life.  sufficient flexibility, cross‐
  sectional area, and corrosion 
7.4.1.4 Parallel Conducting  resistance to maximize service 
Paths (Seal Assembly from  life. 
the Floating Roof Tank).   
  (8) The shunt‐to‐shell contact 
7.4.1.4.1 Any non–fully  point shall be submerged at 
submerged conductive seal  least 1 ft (0.3 m) below the 
assembly components,  surface of the liquid product. 
including springs, scissor   
assemblies, and seal  (9) Above‐deck shunts shall be 
membranes, shall be  removed when retrofitting 
electrically insulated from the  existing tanks with submerged 
tank roof.  shunts. 
   
7.4.1.4.2 The insulation level   
shall be rated 1 kV or greater.  7.4.3.2.2* Fixed Contacts. 
   
7.4.1.5 Insulation of Gauge or  7.4.3.2.2.1 The tank’s floating 
Guide Poles.  roof shall be bonded to the 
  tank shell by direct electrical 
7.4.1.5.1 Any gauge or guide  connection using a bypass 
pole components or  conductor with a minimum 
assemblies that penetrate the  cross‐sectional area 
tank’s floating roof shall be  equivalent to that of a main‐
electrically insulated from the  size conductor. 
tank’s floating roof.   
  7.4.3.2.2.2 Each conductor, 
7.4.1.5.2 The insulation level  including connections, shall 
shall be rated 1 kV or greater.  have a maximum end‐to‐end 
  electrical resistance of 0.03 
7.4.1.6 Metallic Tanks with  ohm.  
Nonmetallic Roofs. Metallic   
tanks with wooden or other  7.4.3.2.2.3 The bypass 
nonmetallic roofs shall not be  conductor shall be of the 
considered self‐protecting,  minimum length necessary to 
even if the roof is essentially  permit full movement of the 
gastight and sheathed with  floating roof. 
thin metal and with all gas   
openings provided with flame  7.4.3.2.2.4 Bypass conductors 
protection.  shall be installed as follows: 
   
7.4.1.6.1 Such tanks shall be  (1) A minimum of two bypass 
provided with strike  conductors shall be installed. 
termination devices.   
  (2) Bypass conductors shall be 
7.4.1.6.2 Such strike  installed for every 100 ft (30 
termination devices shall be  m) of tank perimeter or 
bonded to each other, to the  portion thereof. 
metallic sheathing, if any, and   
to the tank shell.  (3) Conductors shall be evenly 
  spaced around the tank 
7.4.1.6.3 Isolated metal parts  circumference. 
shall be bonded as required   
by Section 4.16.  7.4.3.2.2.5 Where there is a 
  rolling ladder, one of the 
7.4.1.6.4 Any of the following  required bypass conductors 
strike termination devices  shall be installed along and 
shall be permitted to be used:  bonded to the rolling ladder. 
(1) Conducting masts   
(2) Overhead ground wires  7.4.3.2.2.6 The bypass 
(3) Combination of masts and  conductor bonded to the 
overhead ground wires  rolling ladder shall be a 
  continuous conductor bonded 
7.4.1.7 Grounding Tanks.  at one end to the floating roof 
  and at the other end to the 
7.4.1.7.1 Tanks shall be  tank shell. 
grounded to conduct away   
the current of direct strokes  7.4.3.2.2.7* The bypass 
and the buildup and potential  conductors and terminations 
that cause sparks to ground.  shall be positioned and of 
  sufficient flexibility, cross‐
7.4.1.7.2 A metal tank shall be  sectional area, and corrosion 
grounded by one of the  resistance to maximize service 
following methods:  life. 
   
(1) A tank shall be connected  7.4.3.2.3 Parallel Conducting 
without insulated joints to a  Paths (Seal Assembly from 
grounded metallic piping  the Floating Roof Tank). 
system.   
  7.4.3.2.3.1 Any non–fully 
(2) A vertical cylindrical tank  submerged conductive seal 
shall rest on earth or concrete  assembly components, 
and shall be at least 20 ft (6  including springs, scissor 
m) in diameter, or shall rest  assemblies, and seal 
on bituminous pavement and  membranes, shall be 
shall be at least 50 ft (15 m) in  electrically insulated from the 
diameter.  tank roof. 
   
(3) A tank shall be bonded to  7.4.3.2.3.2 The insulation 
ground through a minimum of  level shall be rated 1 kV or 
two grounding electrodes, as  greater. 
described in Section 4.13, at   
maximum 100 ft (30 m)  7.4.3.2.4 Insulation of Gauge 
intervals along the perimeter  or Guide Poles. 
of the tank.   
  7.4.3.2.4.1 Any gauge or 
(4) A tank installation using an  guide pole components or 
insulating membrane beneath  assemblies that penetrate the 
for environmental or other  tank’s floating roof shall be 
reasons shall be grounded as  electrically insulated from the 
in 7.4.1.7.2(3).  tank’s floating roof. 
   
7.4.2 Earthen Containers at  7.4.3.2.4.2 The insulation 
Atmospheric Pressure  level shall be rated 1 kV or 
Containing Flammable  greater. 
Vapors or Liquids That Give   
Off Flammable Vapors.  7.4.3.3 Metallic Tanks with 
  Nonmetallic Roofs. Metallic 
7.4.2.1 Lined or unlined  tanks with wooden or other 
earthen containers with  nonmetallic roofs shall not be 
combustible roofs that  considered self‐protecting, 
enclose flammable vapors or  even if the roof is essentially 
liquids that can give off  gastight and sheathed with 
flammable vapors shall be  thin metal and with all gas 
protected by air terminals,  openings provided with flame 
separate masts, overhead  protection. 
ground wires, or a   
combination of these devices.  7.4.3.3.1 Such tanks shall be 
  provided with strike 
7.4.2.2 Aboveground  termination devices. 
nonmetallic tanks shall be   
protected as described in  7.4.3.3.2 Such strike 
7.3.2.  termination devices shall be 
bonded to each other, to the 
metallic sheathing, if any, and 
to the tank shell. 
 
7.4.3.3.3 Metal bodies shall 
be bonded as required by 
Section 4.16. 
 
7.4.4 Earthen Containers at 
Atmospheric Pressure 
Containing Flammable 
Vapors or Liquids That Give 
Off Flammable Vapors. 
 
7.4.4.1 Lined or unlined 
earthen containers with 
combustible roofs that 
enclose flammable vapors or 
liquids that can give off 
flammable vapors shall be 
protected by air terminals, 
separate masts, overhead 
ground wires, or a 
combination of these devices. 
 
7.4.4.2 Aboveground 
nonmetallic tanks shall be 
protected as described in 
Section 7.3. 
 
 
Chapter 8 pg 34  Protection of Structures Housing 
  Explosive Materials 
2014 Edition  2017 Edition  Comments 
8.3.2 Single or Multiple  8.3.3* Single or Multiple 
Masts. Mast‐type systems  Masts. Mast‐type systems 
shall be designed as specified  shall be designed as specified 
in 4.6.5, using a striking  in 4.6.3 and 4.6.5, using a 
distance of 100 ft (30 m)  striking distance as specified 
radius.  in 8.2.1. 
   
8.3.2.1* Mast Lightning  8.3.3.1 Nonmetallic masts 
Protection System. A mast‐ shall have a strike termination 
type lightning protection  device or metal cap with a 
system shall be permitted to  minimum thickness of 3∕16 
be remote from the structure  in. (4.8 mm) connected to 
in order to provide a primary  ground by at least one down 
attachment point for a  conductor. 
lightning discharge.   
  8.3.3.2* Mast guy wires shall 
8.3.2.1.1 Metallic masts shall  not be used as the only down 
be a minimum diameter of  conductors for a mast.  
5⁄8 in. (15 mm).   
  8.3.3.3 Each metallic guy 
8.3.2.1.2 Nonmetallic masts  cable shall be interconnected 
shall have a strike termination  at its lower end to the 
No significant changes 
device or metal cap with a  grounding electrode(s) for the 
minimum thickness of 3⁄16 in.  down conductor. 
(4.8 mm) connected to   
ground by at least one down  8.3.3.4 Metallic guy wires 
conductor.  shall be provided with a main‐
  size conductor to establish 
8.3.2.1.3 For nonmetallic  electrical continuity with 
masts using a pole guy wire as  metallic masts or the down 
a down conductor, the guy  conductor system for 
wire shall be a continuous  nonmetallic masts at the top 
metal cable without any  of the guy. 
ceramic or insulating sections.   
  8.5.7* Railroad Tracks. All 
8.3.2.1.4 Each metallic guy  railroad tracks (including 
cable shall be bonded at its  siding tracks) that are located 
lower end to the grounding  within 6 ft (1.8 m) of a facility 
electrode(s).  housing explosives shall be 
  bonded to the lightning 
8.5.7 Railroad Tracks. All  protection system ground ring 
railroad tracks that are  electrode using a main‐size 
located within 6 ft (1.8 m) of a  conductor buried a minimum 
facility housing explosives  of 18 in. (450 mm) below 
shall be bonded to the  grade (see Figure 8.5.7). 
lightning protection system   
ground ring electrode.  8.5.7.1 At the point where 
  railroad tracks enter a facility, 
8.5.8 Where railroad tracks  they shall be bonded to the 
provide electrical signaling,  frame of the structure or 
insulated joints shall be  facility or the ground loop 
provided to isolate railroad  conductor. 
siding tracks from the main   
railroad track.  8.5.7.2 Where railroad tracks 
  are used for electrical 
8.5.8.1 Siding tracks shall  signaling, insulating joints 
provide external bonds for  shall be provided to isolate 
bonding to the facility’s  railroad siding tracks from the 
ground ring electrode.  main railroad track. 
   
8.5.8.2 Where railroad tracks  8.5.7.3 The insulating joints 
enter a facility, they also shall  shall be located between any 
be bonded to the frame of the  bond to the lightning 
structure or facility.  protection system and 
  connection to the main track. 
8.7.1.2 Tall air terminals in the   
center of the magazine  8.7.1.2 Air terminals shall be 
headwall and roof shall be  permitted but are not 
permitted in lieu of perimeter  required for portions of the 
air terminals only if they  magazine where a minimum 
provide adequate protection  earth cover of 2 ft (0.6 m) is 
in accordance with 8.2.1.  maintained. 
   
8.7.2.2 The mast or catenary  8.7.2.2 The mast or catenary 
system shall be  system shall be 
interconnected with a ground  interconnected with a deck‐
ring conductor.  level potential equalization 
  network. 
8.7.2.3 An additional   
conductor shall be installed  8.7.2.3 The deck‐level 
along the pier or wharf for  potential equalization 
bonding of all permanently  network shall consist of 
installed metal objects on the  interconnected cables or 
pier  conductors running along 
  these structures to provide 
  interconnection of all 
  permanently installed metal 
  objects on the wharf. 
   
8.7.2.4 All pier and wharf  8.7.2.4* The deck‐level 
ground ring conductors shall  potential equalization 
be interconnected.  network shall be provided 
  with multiple paths to ground 
8.7.2.5 A path to earth  using main‐size conductors or 
consisting of a metal plate  equivalent, spaced no greater 
bonded to the additional  than 100 ft (30 m) average 
ground ring conductor shall  intervals. 
be permitted to create a low‐  
resistance path by  8.7.2.5 A grounding electrode 
submerging in water.  shall be provided for each 
  down conductor. 
8.7.3 Cranes. All cranes shall   
be provided with inner and  8.7.2.5.1 Approved grounding 
outer ground ring conductors  electrodes shall be ground 
interconnected with each  rods as described in 4.13.2 or 
other.  ground plate electrodes as 
  described in 4.13.6. 
8.7.3.1 The crane shall be   
bonded to the inner ground  8.7.2.5.2 The grounding 
ring conductor.  electrodes shall be installed in 
  the earth at the base of 
8.7.3.2 Cranes shall be  pilings. 
relocated into the lightning   
protection zone of protection  8.7.2.5.3* Where it is not 
at the approach of a  practicable to install the 
thunderstorm.  approved grounding 
  electrodes in accordance with 
8.7.3.3 Boom and cable lifting  8.7.2.5.2, it shall be permitted 
shall be bonded to the outer  to create a grounding path by 
ground ring conductor.  submerging the electrodes in 
  water. 
Exception: Metal lifting hooks   
on cranes equipped with hook  8.7.2.6 Cranes shall be 
insulating links shall not be  bonded to the deck‐level 
required to be bonded to any  potential equalization 
of the ground ring conductors.  network. 
 
Chapter 9 pg 38  Protection for Wind Turbines 
2014 Edition  2017 Edition  Comments 
  No changes   
   
Chapter 10 pg 39  Protection for Watercraft 
2014 Edition  2017 Edition  Comments 
  No changes   
 
Chapter 11 pg 42  Protection for Airfield Lighting Circuits
2014 Edition  2017 Edition  Comments 
  No changes   
 
Chapter 12 pg 42  Protection for Solar Arrays 
2014 Edition  2017 Edition  Comments 
12.2.2 Protection shall be  12.2.2 Protection shall be 
provided by one or more of  provided by either of the 
the following methods:  following methods: 
   
(1) Direct mounting of strike  (1) Direct mounting of strike 
termination devices to the  termination devices to the 
solar panel  solar array rack as shown in 
  Figure 12.2.2(a) 
(2) Direct mounting of strike   
termination devices to the  (2) Locating strike termination 
solar panel framing  devices (including air 
  terminals, masts, and 
(3) Locating strike termination  overhead ground wires) 
devices (including air  adjacent to the solar panels in 
terminals, masts, and  such a manner as to place the 
Criteria is now more 
overhead ground wires)  solar panels in a zone of 
specific. 
adjacent to the solar panels in  protection as defined in 
such a manner as to place the  Section 4.8 and shown in 
solar panels in a zone of  Figure 12.2.2(b). 
protection as defined in   
Section 4.8  12.3.1 Strike termination 
  devices shall not be required 
12.3.1 Strike termination  for solar panels or arrays that 
devices shall extend a  are located within a zone of 
minimum of 10 in. (254 mm)  protection provided in 
vertically above the apex of  accordance with Section 4.8. 
the solar panel.   
  12.3.2 Strike termination 
12.3.2 Strike termination  devices shall be required in 
devices shall be located at the  accordance with 12.3.2.1 
ends of the uppermost edge  through 12.3.2.3 for solar 
or nearest support of pitched  panels or arrays not located in 
solar panels or panel arrays  a zone of protection. 
not to exceed 2 ft (0.6 m)   
from the end of the panel or  12.3.2.1 Sloped solar panels 
array unless the uppermost  or arrays having a horizontal 
edge or nearest support is  distance (run) of 40 ft (12 m) 
within a zone of protection.  or less and a slope of 1∕8 or 
  greater and solar panels or 
12.3.3 Strike termination  arrays having a horizontal 
devices shall be located along  distance (run) of more than 
the uppermost edge of solar  40 ft (12 m) and a slope of  
panels or panel arrays at  1∕4 or greater shall have 
intervals not exceeding 20 ft  strike termination devices 
(6 m) unless the panel arrays  located as follows: 
are within a zone of   
protection.  (1) Strike termination devices 
  shall be located such that they 
12.3.4 Solar panels or panel  extend a minimum of 10 in. 
arrays that have a slope of  (254 mm) vertically above the 
less than 1⁄8 shall have strike  uppermost edge of the solar 
termination devices located  panel or array. 
within 2 ft (0.6 m) of the   
outermost corners and at  (2) Strike termination devices 
intervals not exceeding 20 ft  shall be located such that they 
(6 m) along all edges unless  are within 2 ft (0.6 m) of the 
the corners or edges are  ends of the apex of the solar 
within a zone of protection.  panel or array. 
   
12.3.4.1 Solar panel arrays  (3) Strike termination devices 
that exceed 50 ft (15 m) in  shall be located within 2 ft 
width or length shall comply  (0.6 m) of the apex of the 
with one of the following:  solar panel or array. 
   
(1) Strike termination devices  (4) Strike termination devices 
located at intervals not to  shall be located at intervals 
exceed 50 ft (15 m) on the  not exceeding 20 ft (6 m) 
solar panel arrays, similar to  along the apex of the solar 
Figure 4.7.5(a) and Figure  panel or array. 
4.7.5(b) (2) Strike termination   
devices that create zones of  (5) Strike termination devices 
protection using the rolling  that extend 2 ft (0.6 m) or 
sphere method so the sphere  more above the apex of the 
does not contact the solar  solar panel or array shall be 
panel arrays  permitted to be placed at 
  intervals not exceeding 25 ft 
12.3.5 Solar panels or panel  (7.6 m) along the uppermost 
arrays that have a slope of  edge of the solar panel or 
less than 1⁄4 and the distance  array. 
from the uppermost edge to   
the lowermost edge along the  12.3.2.2 Solar panels or arrays 
face of the panel or array  that have a slope of less than 
exceeds 20 ft (6 m) shall have  ¼ and the distance from the 
strike termination devices  uppermost edge to the 
located within 2 ft (0.6 m) of  lowermost edge along the 
the outermost corners and at  face of the panel or array 
intervals not exceeding 20 ft  exceeds 20 ft (6 m) shall have 
(6 m) along all edges unless  strike termination devices 
the corners or edges are  located as follows: 
within a zone of protection.   
  (1) Strike termination devices 
12.3.6 Strike termination  shall be located within 2 ft 
devices shall not be secured  (0.6 m) of the outermost 
directly to the panels or panel  corners of the solar panel or 
frames of photovoltaic panels  array unless those corners are 
and arrays.  within a zone of protection. 
   
12.3.7 Where practicable, the  (2) Strike termination devices 
location of strike termination  shall be located at intervals 
devices shall minimize the  not exceeding 20 ft (6 m) 
effects of shadowing the solar  along all edges of the solar 
panels.  panel or array unless those 
edges are within a zone of 
protection. 
 
(3) Strike termination devices 
that extend 2 ft (0.6 m) or 
more above the edges of the 
solar panel or array shall be 
permitted to be placed at 
intervals not exceeding 25 ft 
(7.6 m) along the edges of the 
solar panel or array. 
 
12.3.2.3 Solar panels or arrays 
that have a slope of less than 
¼ and exceed 50 ft (15 m) in 
width and length shall comply 
with one of the following: 
 
(1) Strike termination devices 
located at intervals not to 
exceed 50 ft (15 m) on the 
solar array as illustrated in 
Figure 4.7.5.1(a) and Figure 
4.7.5.1(b). 
 
(2) Strike termination devices 
that create zones of 
protection using the rolling 
sphere method so the sphere 
does not contact the solar 
array. 
 
Annex A pg 48  Explanatory Material 
2014 Edition  2017 Edition  Comments 
Reflects updates to the 
  No significant changes. 
standard. 
   
Annex B pg 63  Principles of Lightning Protection
2014 Edition  2017 Edition  Comments 
  No changes.   
 
Annex C pg 66  Explanation of Bonding Principles
2014 Edition  2017 Edition  Comments 
  No changes   
 
Inspection and Maintenance of 
Annex D pg 68  Lightning 
Protection Systems 
2014 Edition  2017 Edition  Comments 
  No changes 
 
Annex E pg 69  Ground Measurement Techniques
2014 Edition  2017 Edition  Comments 
  No changes 
   
Annex F pg 70  Protection for Trees 
2014 Edition  2017 Edition  Comments 
  No changes 
 
Protection for Picnic Grounds,
Annex G pg 71  Playgrounds, Ball Parks, and Other 
Open Places 
2014 Edition  2017 Edition  Comments 
  No changes. 
 
Annex H pg 72  Protection for Livestock in Fields
2014 Edition  2017 Edition  Comments 
  No changes   
 
Annex I pg 72  Protection for Parked Aircraft 
2014 Edition  2017 Edition  Comments 
  No changes 
   
Annex J pg 73  Protection of Smart Structures
2014 Edition  2017 Edition  Comments 
Due to the high degree of 
electrical interconnection, 
particularly data wiring, 
there are many more ways 
for surges to enter the most 
sensitive parts of the 
This Annex is new  equipment.  Additional 
 
measures, beyond those 
specified in NFPA 780, are 
suggested for enhanced 
protection of smart 
structures equipment 
under lightning conditions. 
 
Guide to International Standards 
Annex K pg 78  Dealing with the Selection of SPDs for 
Use on Photovoltaic (PV) Installations 
2014 Edition  2017 Edition  Comments 
The purpose of this annex is 
to provide the installer with 
a reference to other 
international standards that 
  This Annex is new 
deal with the protection of 
photovoltaic installations 
from the effects of 
lightning. 
 
Annex L pg 80  Lightning Risk Assessment  
2014 Edition  2017 Edition  Comments 
Revised to provide greater 
clarity and correlation of 
  No significant changes  requirements with other 
lightning protection 
standards. 
 
Guide for Personal Safety from
Annex M pg 93 
Lightning 
2014 Edition  2017 Edition  Comments 
  No changes   
Annex N pg 94  Reserved
2014 Edition  2017 Edition  Comments 
  No changes   
 
Annex O pg 94  Informational References 
2014 Edition  2017 Edition  Comments 
  No changes   
 
 
 
 
 
 
Answer the following questions in a generic sense: 

1. Will adoption of the new edition require additional funding or resources not currently in
the scope? (e.g., Does a change apply retroactively to an existing design that requires
funding or resources to comply that are not part of normal business?)
An increase in funding may be necessary depending on AHJ’s inspection or
testing interval requirements. Inspection or testing intervals are at the AHJ’s discretion.
(1.5.3 and 1.6.1)

2. Will adoption of the new edition require changes to procedures, manuals, programs, etc.
to remain in compliance with the changes (e.g., Is there a change to administrative
requirements that will result in a change to an existing procedure, which is generally part
of implementing the newly adopted code or standard?)?

AHJ ITM requirements will drive administrative changes.

3. Are there changes in methodologies, calculations, procedures, etc. that need to be


communicated to a select group within the organization to ensure proper implementation,
other than what is required for the above two questions?

Annex L, “Lightning Risk Assessment”, has been revised to correlate with other
lightning protection standards

3) REVIEW AND APPROVALS 
 
REVIEW AND APPROVAL FOR SIGNATURES

Title/Group/DOESite Name Signature Date

Originator, Ryan Lehnert GSP, CFPS _________ 09/08/2017


Facility Maintenance Supervisor
Fire Protection Operations
KC NSC

Independent Technical Reviewer Craig Miller CSP, CFPS 09/11/2017


Fire Protection Specialist
Health Safety & Environmental
KC NSC 

You might also like