You are on page 1of 1

Ademco Contact ID®

The Ademco Contact ID® Reporting Format comprises the following:


4-digit or 10-digit subscriber number (depending on format selected).
1-digit event qualifier (“new” or “restore”).
3-digit event code.
2-digit Partition No.
3-digit zone number, user number, or system status number (see the following page).
Ademco Contact ID® Reporting takes the following format: CCCC(CCCCCC) Q EEE GG ZZZ
where:
CCCC(CCCCCC) =Customer (subscriber) ID
Q = Event qualifier, where:
E = new event , and R = restore
EEE = Event code (3 hexadecimal digits)
Note: For a complete list of event codes, refer to the central office
receiver manual.
GG = Partition Number (system messages show “00”)
ZZZ = Zone/contact ID number reporting the alarm, or user number for
open/close reports. System status messages (AC Loss, Walk Test, etc.)
contain zeroes in the ZZZ location.

TABLE OF CONTACT ID EVENT CODES


(some event codes may not apply to certain control panels)

Code Definition Code Definition


110 Fire Alarm 381 RF Sensor Supervision
121 Duress 382 Supervision Auxiliary Wire Zone
122 Alarm, 24-hour Silent 383 RF Sensor Tamper
123 Alarm, 24-hour Audible 384 RF Sensor Low-battery
131 Alarm, Perimeter 393 Clean Me
132 Alarm, Interior 401 Disarmed, Armed AWAY, Armed
134 Alarm, Entry/Exit MAXIMUM
135 Alarm, Day/Night 403 Schedule Arm/Disarm AWAY
143 Alarm, Expansion Module 406 Cancel by User
145 ECP Module cover tamper 407 Remote Arm/Disarm (Downloading)
146 Silent Burglary 408 Quick Arm AWAY
150 Alarm, 24-Hour Auxiliary/Monitor zone 409 Keyswitch Arm/Disarm AWAY
162 Carbon Monoxide 441 Disarmed/Armed STAY/INSTANT,
301 AC Power Quick-Arm STAY/INSTANT
302 Low System Battery/Battery Test Fail 442 Keyswitch Arm/Disarm STAY
305 System Reset (Log only) 459 Recent Closing
309 Battery Test Failure 570 Bypass
321 Bell/Siren Trouble 601 Manually Triggered Dialer Test
333 Trouble, Expansion Mod. Supervision 602 Periodic Test
341 Trouble, ECP Cover Tamper 606 AAV to Follow
344 RF Receiver Jam 607 Walk Test Entered/Exited
351 Telco Line Fault 623 Event Log 80% Full
353 Long Range Radio Trouble 625 Real-Time Clock was Changed (log only)
373 Fire Loop Trouble 627 Program Mode Entry (log only)
374 Exit Error Alarm 628 Program Mode Exit (log only)
380 Global Trouble, Trouble Day/Night 642 Latch Key (log only)
750 - Reserved for Configurable Zone Type
789 report codes (check with central station
when using these codes)