You are on page 1of 20

Building Services CHAPTER 11

Chapter 11 addresses electrical fire safety, HVAC equipment, elevators, utilities, heating
appliances, rubbish chutes and incinerators, stationary generators and standby power systems,
smoke control, and emergency command centers. In the 2000 edition, this material was
--`,,`,``,,,,,,``,````,`,`,,,`-`-`,,`,,`,`,,`---

located in Chapter 6.

70:110.12 Mechanical Execution of Work. Electric equipment


11.1 Electrical Fire Safety shall be installed in a neat and workmanlike manner.
The approval of new electrical installations or approval of the (A) Unused Openings. Unused cable or raceway openings in
modifications to an existing electrical system is a function boxes, raceways, auxiliary gutters, cabinets, cutout boxes,
typically performed by an electrical inspector or other build- meter socket enclosures, equipment cases, or housings shall
ing code enforcement official using the requirements of be effectively closed to afford protection substantially equiva-
lent to the wall of the equipment. Where metallic plugs or
NFPA 70, National Electrical Code (NEC) as the basis for
plates are used with nonmetallic enclosures, they shall be
their approval. However, in many cases, prior to a building recessed at least 6 mm (1⁄4 in.) from the outer surface of the
or other facility being constructed or occupied, fire marshals enclosure.
or fire inspectors perform periodic inspections to ensure that ⯗
the premises safety systems and features are in place, are (C) Integrity of Electrical Equipment and Connections. In-
in proper working order, and have not been compromised ternal parts of electrical equipment, including busbars, wiring
or adversely modified. Electrical systems are often subject terminals, insulators, and other surfaces shall not be damaged
to this type of periodic safety inspection. In general, the focus or contaminated by foreign materials such as paint, plaster,
of this type of inspection is compliance with fundamental cleaners, abrasives, or corrosive residues . . .
electrical safety provisions that have long been required by 70:110.13 Mounting and Cooling of Equipment.
the NEC. Requirements covering the integrity of enclosures
(A) Mounting. Electric equipment shall be firmly secured to
housing electrical wiring and equipment, the proper use of the surface on which it is mounted. . . .
electrical appliances, the proper application and use of flexi-
ble cords, complete and up-to-date identification of circuit (B) Cooling. Electrical equipment that depends upon the natu-
ral circulation of air and convection principles for cooling of
disconnecting means, and the proper maintenance and opera-
exposed surfaces shall be installed so that room airflow over
tion of electrically powered emergency features such as bat- such surfaces is not prevented by walls or by adjacent installed
tery-operated emergency lighting units are among the items equipment. . . .
typically included in these periodic safety inspections.
70:110.22 Identification of Disconnecting Means. Each dis-
The following pages contain references and a brief de-
connecting means shall be legibly marked to indicate its pur-
scription of material extracted from the NEC that provide
pose unless located and arranged so the purpose is evident.
some of the most common requirements that the fire official The marking shall be of sufficient durability to withstand the
frequently follows during an inspection or a plan review. environment involved.
For the text of the full requirements of these sections, please
70:110.26 Spaces About Electric Equipment. Sufficient ac-
see the NEC.
cess and working space shall be provided and maintained
ARTICLE 110 — REQUIREMENTS FOR about all electric equipment to permit ready and safe operation
ELECTRICAL INSTALLATIONS and maintenance of such equipment. Enclosures housing elec-
trical apparatus that are controlled by lock and key shall be
70:110.11 Deteriorating Agents. Unless identified for use in
considered accessible to qualified persons.
the operating environment, no conductors or equipment shall
be located in damp or wet locations; where exposed to gases, 70:110.26(A)(1) Depth of Working Space. The depth of the
fumes, vapors, liquids, or other agents having a deteriorating working space in the direction of live parts shall not be less
effect on the conductors or equipment; nor where exposed to than that specified in Table 110.26(A)(1) unless the require-
excessive temperatures. . . . ments of 110.26(A)(1)(a), (b), or (c) are met. Distances shall

141

Copyright National Fire Protection Association


Provided by IHS under license with NFPA Licensee=Technip La Defense/5931917103
No reproduction or networking permitted without license from IHS Not for Resale, 09/10/2007 07:51:22 MDT
142 Part II • General

TABLE 110.26(A)(1) Working Spaces (2) By suitable permanent, substantial partitions or


screens. . . .
Minimum Clear Distance
Nominal Voltage (3) By location on a suitable balcony, gallery, or platform so
to Ground Condition 1 Condition 2 Condition 3 elevated and arranged as to exclude unqualified persons.
(4) By elevation of 8 ft (2.44 m) or more above the floor or
0–150 900 mm (3 ft) 900 mm (3 ft) 900 mm (3 ft) other working surface.
151–600 900 mm (3 ft) 1 m (3 1⁄2 ft) 1.2 m (4 ft)
(B) Prevent Physical Damage. In locations where electric
Note: Where the conditions are as follows: equipment is likely to be exposed to physical damage, enclo-
Condition 1—Exposed live parts on one side and no live or grounded sures or guards shall be so arranged and of such strength as
parts on the other side of the working space, or exposed live parts to prevent such damage.
on both sides effectively guarded by suitable wood or other insulating
materials. Insulated wire or insulated busbars operating at not over
(C) Warning Signs. Entrances to rooms and other guarded
300 volts to ground shall not be considered live parts. locations containing exposed live parts shall be marked with
Condition 2—Exposed live parts on one side and grounded parts on conspicuous warning signs forbidding unqualified persons to
the other side. Concrete, brick, or tile walls shall be considered as enter.
grounded.
Condition 3—Exposed live parts on both sides of the work space (not ARTICLE 300—WIRING METHODS
guarded as provided in Condition 1) with the operator between.
70:300.11(A) Secured in Place. Raceways, cable assemblies,
boxes, cabinets, and fittings shall be securely fastened in place.
be measured from the exposed live parts or from the enclosure Support wires that do not provide secure support shall not be
or opening if the live parts are enclosed. permitted as the sole support. Support wires and associated
(a) Dead-Front Assemblies. Working space shall not be fittings that provide secure support and that are installed in
required in the back or sides of assemblies, such as dead-front addition to the ceiling grid support wires shall be permitted
switchboards or motor control centers, where all connections as the sole support. Where independent support wires are used,

--`,,`,``,,,,,,``,````,`,`,,,`-`-`,,`,,`,`,,`---
and all renewable or adjustable parts, such as fuses or switches, they shall be secured at both ends. Cables and raceways shall
are accessible from locations other than the back or sides. not be supported by ceiling grids.
Where rear access is required to work on nonelectrical parts 70:300.21 Spread of Fire or Products of Combustion. Electri-
on the back of enclosed equipment, a minimum horizontal cal installations in hollow spaces, vertical shafts, and ventila-
working space of 762 mm (30 in.) shall be provided. tion or air-handling ducts shall be so made that the possible
(b) Low Voltage. By special permission, smaller working spread of fire or products of combustion will not be substan-
spaces shall be permitted where all uninsulated parts operate at tially increased. Openings around electrical penetrations
not greater than 30 volts rms, 42 volts peak, or 60 volts dc. through fire-resistant-rated walls, partitions, floors, or ceilings
shall be firestopped using approved methods to maintain the
(c) Existing Buildings. In existing buildings where elec-
fire resistance rating.
trical equipment is being replaced, Condition 2 working clear-
ance shall be permitted between dead-front switchboards, 70:300.22 Wiring in Ducts, Plenums, and Other Air-Handling
panelboards, or motor control centers located across the aisle Spaces. The provisions of this section apply to the installation
from each other where conditions of maintenance and supervi- and uses of electric wiring and equipment in ducts, plenums,
sion ensure that written procedures have been adopted to and other air-handling spaces.
prohibit equipment on both sides of the aisle from being open ARTICLE 314 — OUTLET, DEVICE, PULL, AND
at the same time and qualified persons who are authorized JUNCTION BOXES; CONDUIT BODIES; FITTINGS;
will service the installation. AND MANHOLES

70:314.28 Pull and Junction Boxes and Conduit Bodies.
(B) Clear Spaces. Working space required by this section ⯗
shall not be used for storage. When normally enclosed live (C) Covers. All pull boxes, junction boxes, and conduit bodies
parts are exposed for inspection or servicing, the working shall be provided with covers compatible with the box or
space, if in a passageway or general open space, shall be conduit body construction and suitable for the conditions of
suitably guarded. use. Where metal covers are used, they shall comply with the
⯗ grounding requirements of 250.110. An extension from the
70:110.27 Guarding of Live Parts (600 Volts, Nominal, or cover of an exposed box shall comply with 370.22, Exception.
Less). ⯗
(A) Live Parts Guarded Against Accidental Contact. Except ARTICLE 400 — FLEXIBLE CORDS AND CABLES
as elsewhere required or permitted by this Code, live parts of
electric equipment operating at 50 volts or more shall be 70:400.7 Uses Permitted.
guarded against accidental contact by approved enclosures or (A) Uses. Flexible cords and cables shall be used only for
by any of the following: the following:
(1) By enclosure that is accessible only to qualified per- (1) Pendants
sons. . . . (2) Wiring of luminaires (fixtures)

2003 NFPA 1 Uniform Fire Code Handbook

Copyright National Fire Protection Association


Provided by IHS under license with NFPA Licensee=Technip La Defense/5931917103
No reproduction or networking permitted without license from IHS Not for Resale, 09/10/2007 07:51:22 MDT
Chapter 11 • Building Services 143

(3) Connection of portable lamps, portable and mobile signs, located within sight and within 1.8 m (6 ft) of the operator’s
or appliances station. The disconnecting means shall be readily accessible
(4) Elevator cables to the operator, including when the ride is in operation. Where
(5) Wiring of cranes and hoists accessible to unqualified persons, the enclosure for the switch
(6) Connection of utilization equipment to facilitate their or circuit breaker shall be of the lockable type. A shunt trip
frequent interchange device that opens the fused disconnect or circuit breaker when
(7) Prevention of the transmission of noise or vibration a switch located in the ride operator’s console is closed shall
(8) Appliances where the fastening means and mechanical be a permissible method of opening the circuit.
connections are specifically designed to permit ready 70:525.23. Ground-Fault Circuit-Interrupter Protection for
removal for maintenance and repair, and the appliance Personnel.
is intended or identified for flexible cord connection
--`,,`,``,,,,,,``,````,`,`,,,`-`-`,,`,,`,`,,`---

(A) General-Use 15- and 20-Ampere, 125-Volt Recepta-


(9) Data processing cables as permitted by Section 645.5
cles. All 125-volt, single-phase, 15- and 20-ampere receptacle
(10) Connection of moving parts outlets that are in use by personnel shall have listed ground-
(11) Temporary wiring as permitted in Sections 527.4(B) and fault circuit-interrupter protection for personnel. The ground-
527.4(C) fault circuit interrupter shall be permitted to be an integral
(B) Attachment Plugs. Where used as permitted in part of the attachment plug or located in the power-supply
400.7(A)(3), (A)(6) and (A)(8), each flexible cord shall be cord, within 12 in. (305 mm) of the attachment plug. For the
equipped with an attachment plug and shall be energized from purposes of this section, listed cord sets incorporating ground-
a receptacle outlet. fault circuit-interrupter protection for personnel shall be per-
mitted. Egress lighting shall not be connected to the load side
Exception: As permitted in 368.8.
terminals of a ground-fault circuit-interrupter receptacle.
70:400.8. Uses Not Permitted. Unless specifically permitted
in 400.7, flexible cords and cables shall not be used for the (B) Appliance Receptacles. Receptacles supplying items, such
following: as cooking and refrigeration equipment, that are incompatible
with ground-fault circuit-interrupter devices shall not be re-
(1) As a substitute for the fixed wiring of a structure quired to have ground-fault circuit-interrupter protection.
(2) Where run through holes in walls, structural ceilings,
suspended ceilings, dropped ceilings, or floors (C) Other Receptacles. Other receptacle outlets not covered
(3) Where run through doorways, windows, or similar open- in 525.23 (A) or (B) shall be permitted to have ground-fault
ings circuit-interrupter protection for personnel, or a written proce-
(4) Where attached to building surfaces dure shall be continuously enforced at the site by one or
more designated persons to ensure the safety of equipment
Exception: Flexible cord and cable shall be permitted to be grounding conductors for all cord sets and receptacles, as
attached to building surfaces in accordance with the provis- described in 527.6(B)(2).
ions of 368.8. ⯗
(5) Where concealed by walls, floors, or ceilings or located 70:525.30 Equipment Bonding. The following equipment
above suspended or dropped ceilings. connected to the same source shall be bonded:
(6) Where installed in raceways, except as otherwise permit-
ted in this Code (1) Metal raceways and metal sheathed cable
(2) Metal enclosures of electric equipment
ARTICLE 422 — APPLIANCES (3) Metal frames and metal parts of rides, concessions, trail-
70:422.50 Cord-and-Plug-Connected Pipe Heating Assem- ers, trucks, or other equipment that contain or support
blies. Cord-and-plug-connected pipe heating assemblies in- electrical equipment.
tended to prevent freezing of piping shall be listed.
70:525.32 Grounding Conductor Continuity Assurance. The
ARTICLE 525 — CARNIVALS, CIRCUSES, FAIRS, continuity of the grounding conductor system used to reduce
AND SIMILAR EVENTS electrical shock hazards as required by 250.114, 250.138,
70:525.1 Scope. This article covers the installation of portable 406.3(C), and 527.4(D) shall be verified each time that porta-
wiring and equipment for carnivals, circuses, fairs, and similar ble electrical equipment is connected.
functions, including wiring in or on all structures.
ARTICLE 527— TEMPORARY INSTALLATIONS
70:525.6 Protection of Electrical Equipment. Electrical
70:527.1 Scope. The provisions of this article apply to tempo-
equipment and wiring methods in or on rides, concessions,
rary electrical power and lighting installations.
or other units shall be provided with mechanical protection
where such equipment or wiring methods are subject to physi- 70:527.2 All Wiring Installations.
cal damage.
(A) Other Articles. Except as specifically modified in this
70:525.21 Rides, Tents and Concessions. article, all other requirements of this Code for permanent
(A) Disconnecting Means. Each ride and concession shall be wiring shall apply to temporary wiring installations.
provided with a fused disconnect switch or circuit breaker ⯗

NFPA 1 Uniform Fire Code Handbook 2003

Copyright National Fire Protection Association


Provided by IHS under license with NFPA Licensee=Technip La Defense/5931917103
No reproduction or networking permitted without license from IHS Not for Resale, 09/10/2007 07:51:22 MDT
144 Part II • General

70:527.3 Time Constraints. Receptacles shall not be connected to the same ungrounded
(A) During the Period of Construction. Temporary electrical conductor of multiwire circuits that supply temporary lighting.
power and lighting installations shall be permitted during the (E) Disconnecting Means. Suitable disconnecting switches or
period of construction, remodeling, maintenance, repair, or plug connectors shall be installed to permit the disconnection
demolition of buildings, structures, equipment, or similar ac- of all ungrounded conductors of each temporary circuit.
tivities. Multiwire branch circuits shall be provided with a means to
(B) 90 Days. Temporary electrical power and lighting installa- disconnect simultaneously all ungrounded conductors at the
tions shall be permitted for a period not to exceed 90 days power outlet or panelboard where the branch circuit originated.
for holiday decorative lighting and similar purposes. Approved handle ties shall be permitted.

(C) Emergencies and Tests. Temporary electrical power and (F) Lamp Protection. All lamps for general illumination shall
lighting installations shall be permitted during emergencies be protected from accidental contact or breakage by a suitable
and for tests, experiments, and developmental work. fixture or lampholder with a guard.
Brass shell, paper-lined sockets, or other metal-cased
(D) Removal. Temporary wiring shall be removed immedi- sockets shall not be used unless the shell is grounded.
ately upon completion of construction or purpose for which
the wiring was installed. (G) Splices. On construction sites, a box shall not be required
for splices or junction connections where the circuit conduc-
70:527.4 General. tors are multiconductor cord or cable assemblies, provided
(A) Services. Services shall be installed in conformance with that the equipment grounding continuity is maintained with
Article 230. or without the box.
(B) Feeders. Feeders shall be protected as provided in Article (H) Protection from Accidental Damage. Flexible cords and
240. They shall originate in an approved distribution center. cables shall be protected from accidental damage. Sharp cor-
Conductors shall be permitted within cable assemblies or ners and projections shall be avoided. Where passing through
within multiconductor cords or cables of a type identified in doorways or other pinch points, protection shall be provided
Table 400.4 for hard usage or extra-hard usage. For the purpose to avoid damage.
of this section, Type NM and Type NMC cables shall be
(I) Termination(s) at Devices. Cables entering enclosures con-
permitted to be used in any dwelling, building, or structure
taining devices requiring termination shall be secured to the
without any height limitation.
box with fittings designed for the purpose.
Exception: Single insulated conductors shall be permitted (J) Support. Cable assemblies and flexible cords and cables
where installed for the purpose(s) specified in 527.3(C), where shall be supported in place at intervals that ensure that they
accessible only to qualified persons. will be protected from physical damage. Support shall be in
--`,,`,``,,,,,,``,````,`,`,,,`-`-`,,`,,`,`,,`---

(C) Branch Circuits. All branch circuits shall originate in an the form of staples, cable ties, straps, or similar type fittings
approved power outlet or panelboard. Conductors shall be installed so as not to cause damage. Vegetation shall not
permitted within cable assemblies or within multiconductor be used for support of overhead spans of branch circuits or
cord or cable of a type identified in Table 400.4 for hard feeders.
usage or extra-hard usage. All conductors shall be protected 70:527.6 Ground-Fault Protection for Personnel. Ground-
as provided in Article 240. For the purposes of this section, fault protection for personnel for all temporary wiring installa-
Type NM and Type NMC cables shall be permitted to be used tions shall be provided to comply with 527.6(A) and (B). This
in any dwelling, building, or structure without any height section shall apply only to temporary wiring installations used
limitation. to supply temporary power to equipment used by personnel
Exception: Branch circuits installed for the purposes speci- during construction, remodeling, maintenance, repair, or de-
molition of buildings, structures, equipment, or similar activi-
fied in 527.3(B) or (C) shall be permitted to be run as single
ties.
insulated conductors. Where the wiring is installed in accor-
dance with 527.3(B), the voltage to ground shall not exceed (A) Receptacle Outlets. All 125-volt, single-phase, 15-, 20-,
150 volts, the wiring shall not be subject to physical damage, and 30-ampere receptacle outlets that are not a part of the
and the conductors shall be supported on insulators at inter- permanent wiring of the building or structure and that are in
vals of not more than 3.0 m (10 ft); or, for festoon lighting, use by personnel shall have ground-fault circuit interrupter
the conductors shall be arranged so that excessive strain is protection for personnel. If a receptacle(s) is installed or exists
not transmitted to the lampholders. as part of the permanent wiring of the building or structure
and is used for temporary electric power, ground-fault circuit-
(D) Receptacles. All receptacles shall be of the grounding interrupter protection for personnel shall be provided. For the
type. Unless installed in a continuous grounded metal raceway purposes of this section, cord sets or devices incorporating
or metal-covered cable, all branch circuits shall contain a listed ground-fault circuit interrupter protection for personnel
separate equipment grounding conductor, and all receptacles identified for portable use shall be permitted.
shall be electrically connected to the equipment grounding
conductors. Receptacles on construction sites shall not be Exception: In industrial establishments only, where condi-
installed on branch circuits that supply temporary lighting. tions of maintenance and supervision ensure that only quali-

2003 NFPA 1 Uniform Fire Code Handbook

Copyright National Fire Protection Association


Provided by IHS under license with NFPA Licensee=Technip La Defense/5931917103
No reproduction or networking permitted without license from IHS Not for Resale, 09/10/2007 07:51:22 MDT
Chapter 11 • Building Services 145

fied personnel are involved, an assured equipment grounding the power source for an electric motor-driven fire pump shall
conductor program as specified in 527.6(B)(2) shall be permit- be one or more of the following.
ted for only those receptacle outlets used to supply equipment (1) Electric Utility Service Connection. A fire pump shall be
that would create a greater hazard if power was interrupted or permitted to be supplied by a separate service, or by a tap
having a design that is not compatible with GFCI protection. located ahead of and not within the same cabinet, enclosure,
(B) Use of Other Outlets. Receptacles other than 125-volt, or vertical switchboard section as the service disconnecting
single-phase, 15-, 20-, and 30-ampere receptacles shall have means. The connection shall be located and arranged so as to
protection in accordance with (1) or, the assured equipment minimize the possibility of damage by fire from within the
grounding conductor program in accordance with (2). premises and from exposing hazards. A tap ahead of the
service disconnecting means shall comply with 230.82(4). The
(1) GFCI Protection. Ground-fault circuit interrupter protec- service equipment shall comply with the labeling requirements
tion for personnel. in 230.2 and the location requirements in 230.72(B).
(2) Assured Equipment Grounding Conductor Program. A (2) On-Site Power Production Facility. A fire pump shall be
written assured equipment grounding conductor program con- permitted to be supplied by an on-site power production facil-
tinuously enforced at the site by one or more designated per- ity. The source facility shall be located and protected to mini-
sons to ensure that equipment grounding conductors for all mize the possibility of damage by fire. [NFPA 20, 6.2.1, 6.2.2,
cord sets, receptacles that are not a part of the permanent 6.2.4.4]
wiring of the building or structure, and equipment connected
by cord and plug are installed and maintained in accordance (B) Multiple Sources. Where reliable power cannot be ob-
with the applicable requirements of 250.114, 250.138, tained from a source described in 695.3(A), power shall be
406.3(C), and 527.4(D). supplied from an approved combination of two or more of
either of such sources or from an approved combination of
(a) The following tests shall be performed on all cord feeders constituting two or more power sources as covered
sets, receptacles that are not part of the permanent wiring in 695.3(B)(2), or from an approved combination of one or
of the building or structure, and cord- and plug-connected more of such power sources in combination with an on-site
equipment required to be grounded: standby generator complying with 695.3(B)(1) and (B)(3).
(1) All equipment grounding conductors shall be tested for (1) Generator Capacity. An on-site generator(s) used to com-
continuity and shall be electrically continuous. ply with this section shall be of sufficient capacity to allow
(2) Each receptacle and attachment plug shall be tested for normal starting and running of the motor(s) driving the fire
correct attachment of the equipment grounding conductor. pump(s) while supplying all other simultaneously operated
The equipment grounding conductor shall be connected load. Automatic shedding of one or more optional standby
to its proper terminal. loads in order to comply with this capacity requirement shall be
(3) All required tests shall be performed as follows: permitted. A tap ahead of the on-site generator disconnecting
a. Before first use on site means shall not be required. The requirements of 430.113
b. When there is evidence of damage shall not apply.
c. Before equipment is returned to service following (2) Feeder Sources. This section applies to multi-building
any repairs campus-style complexes with fire pumps at one or more build-
d. At intervals not exceeding 3 months ings. Where sources in 695.3(A) are not practicable, and with
the approval of the authority having jurisdiction, two or more
(b) The tests required in item (2)(a) shall be recorded feeder sources shall be permitted as one power source or as
and made available to the authority having jurisdiction. more than one power source where such feeders are connected
70:527.7 Guarding. For wiring over 600 volts, nominal, suit- to or derived from separate utility services. The connection(s),
able fencing, barriers, or other effective means shall be pro- overcurrent protective device(s), and disconnecting means for
vided to limit access only to authorized and qualified such feeders shall meet the requirements of 695.4(B).
personnel. (3) Arrangement. The power sources shall be arranged so that
⯗ a fire at one source will not cause an interruption at the other
source. [NFPA 20, 6.2.3, 6.2.4.1, 6.2.4.3, 6.6.1]
ARTICLE 695 — FIRE PUMPS
70:695.6 Power Wiring. Power circuits and wiring methods

shall comply with the requirements in 695.6(A) through (G),
70:695.3 Power Source for Electric Motor Driven Fire Pumps. and as permitted in 230.90(A), Exception No. 4; 230.94, Ex-
Electric motor-driven fire pumps shall have a reliable source ception No. 4; 230.95, Exception No. 2; 240.13; 230.208;
of power. 240.4(A); and 430.31.
(A) Individual Sources. Where reliable, and where capable of (A) Service Conductors. Supply conductors shall be physi-
carrying indefinitely the sum of the locked-rotor current of cally routed outside a building(s) and shall be installed as
the fire pump motor(s) and the pressure maintenance pump service entrance conductors in accordance with Article 230.
motor(s) and the full-load current of the associated fire pump Where supply conductors cannot be physically routed outside
accessory equipment when connected to this power supply, buildings, they shall be permitted to be routed through build-

NFPA 1 Uniform Fire Code Handbook 2003


--`,,`,``,,,,,,``,````,`,`,,,`-`-`,,`,,`,`,,`---

Copyright National Fire Protection Association


Provided by IHS under license with NFPA Licensee=Technip La Defense/5931917103
No reproduction or networking permitted without license from IHS Not for Resale, 09/10/2007 07:51:22 MDT
146 Part II • General

ings where installed in accordance with 230.6(1) or (2). Where load amperes of the fire pump motor, the conductors between
a fire pump is wired under the provisions of 695.3(B)(2), this the on-site generator(s) and the combination fire pump trans-
requirement shall apply to all supply conductors on the load fer switch controller or separately mounted transfer switch
side of the service disconnecting means that constitute the shall be installed in accordance with 695.6(B) or protected
normal source of supply to that fire pump. in accordance with 430.52.
Exception: Where there are multiple sources of supply with The protection provided shall be in accordance with the
means for automatic connection from one source to the other, short-circuit current rating of the combination fire pump trans-
the requirement shall only apply to those conductors on the fer switch controller or separately mounted transfer switch.
--`,,`,``,,,,,,``,````,`,`,,,`-`-`,,`,,`,`,,`---

load side of that point of automatic connection between (E) Pump Wiring. All wiring from the controllers to the pump
sources. motors shall be in rigid metal conduit, intermediate metal
conduit, liquidtight flexible metal conduit, or liquidtight flexi-
(B) Circuit Conductors. Fire pump supply conductors on the
ble nonmetallic conduit Type LFNC-B, or Type MI cable.
load side of the final disconnecting means and overcurrent
device(s) permitted by 695.4(B) shall be kept entirely indepen- (F) Junction Points. Where wire connectors are used in the
dent of all other wiring. They shall only supply loads that are fire pump circuit, the connectors shall be listed. A fire pump
directly associated with the fire pump system, and they shall controller or fire pump power transfer switch, where provided,
be protected to resist potential damage by fire, structural fail- shall not be used as a junction box to supply other equipment,
ure, or operational accident. They shall be permitted to be including a pressure maintenance (jockey) pump(s). A fire
routed through a building(s) using one of the following meth- pump controller and fire pump power transfer switch, where
ods: provided, shall not serve any load other than the fire pump
for which it is intended.
(1) Be encased in a minimum 50 mm (2 in.) of concrete
(2) Be within an enclosed construction dedicated to the fire (G) Mechanical Protection. All wiring from engine controllers
pump circuit(s) and having a minimum of a 1-hour fire and batteries shall be protected against physical damage and
resistive rating shall be installed in accordance with the controller and engine
(3) Be a listed electrical circuit protective system with a manufacturer’s instructions.
minimum 1-hour fire rating 70:695.12 Equipment Location.
Exception: The supply conductors located in the electrical (A) Controller and Transfer Switches. Electric motor-driven
equipment room where they originate and in the fire pump fire pump controllers and power transfer switches shall be
room shall not be required to have the minimum 1-hour fire located as close as practicable to the motors they control and
separation or fire resistance rating, unless otherwise required shall be within sight of the motors.
by 700.9(D) of this Code.
(B) Engine-Drive Controllers. Engine-drive fire pump con-
(C) Conductor Size. trollers shall be located as close as is practical to the engines
(1) Fire Pump Motors and Other Equipment. Conductors sup- that they control and shall be within sight of the engines.
plying a fire pump motor(s), pressure maintenance pumps, (C) Storage Batteries. Storage batteries for diesel engine
and associated fire pump accessory equipment shall have a drives shall be rack supported above the floor, secured against
rating not less than 125 percent of the sum of the fire pump displacement, and located where they will not be subjected
motor(s) and pressure maintenance motor(s) full-load cur- to physical damage, flooding with water, excessive tempera-
rent(s), and 100 percent of the associated fire pump accessory ture, or excessive vibration.
equipment.
(D) Energized Equipment Parts. All energized equipment
(2) Fire Pump Motors Only. Conductors supplying only a fire parts shall be located at least 300 mm (12 in.) above the floor
pump motor(s) shall have a rating not less than 125 percent level.
of the fire pump motor(s) full-load current(s).
(E) Protection Against Pump Water. Fire pump controllers
(D) Overload Protection. Power circuits shall not have auto- and power transfer switches shall be located or protected so
matic protection against overloads. Except as provided in that they will not be damaged by water escaping from pumps
695.5(C)(2), branch-circuit and feeder conductors shall be or pump connections.
protected against short circuit only. Where a tap is made to
supply a fire pump, and the tap wiring is run in accordance (F) Mounting. All fire pump control equipment shall be
with 230.6, the applicable distance and size restrictions in mounted in a substantial manner on noncombustible support-
240.21 shall not apply. ing structures.

Exception No. 1: Conductors between storage batteries and ARTICLE 700 — EMERGENCY SYSTEMS
the engine shall not require overcurrent protection or discon- 70:700.4 Tests and Maintenance.
necting means.
(A) Conduct or Witness Test. The authority having jurisdiction
Exception No. 2: For on-site standby generator(s) that pro- shall conduct or witness a test of the complete system upon
duce continuous currents in excess of 225 percent of the full- installation and periodically afterward.

2003 NFPA 1 Uniform Fire Code Handbook

Copyright National Fire Protection Association


Provided by IHS under license with NFPA Licensee=Technip La Defense/5931917103
No reproduction or networking permitted without license from IHS Not for Resale, 09/10/2007 07:51:22 MDT
Chapter 11 • Building Services 147

(B) Tested Periodically. Systems shall be tested periodically (2) Be a listed electrical circuit protective system with a
on a schedule acceptable to the authority having jurisdiction minimum 1-hour fire rating
to ensure the systems are maintained in proper operating condi- (3) Be protected by a listed thermal barrier system for electri-
tion. cal system components
(4) Be protected by a fire-rated assembly having a minimum
(C) Battery Systems Maintenance. Where battery systems or
fire rating of 1 hour
unit equipment are involved, including batteries used for start-
(5) Be embedded in a minimum of 50 mm (2 in.) of concrete
ing, control, or ignition in auxiliary engines, the authority
(6) Be a cable listed to maintain circuit integrity for a mini-
having jurisdiction shall require periodic maintenance.
mum of 1 hour when installed in accordance with the
(D) Written Record. A written record shall be kept of such listing requirements
tests and maintenance. (2) Feeder-Circuit Equipment. Equipment for feeder circuits
(E) Testing Under Load. Means for testing all emergency (including transfer switches, transformers, panelboards, etc.)
lighting and power systems during maximum anticipated load shall be located either in spaces fully protected by approved
conditions shall be provided. automatic fire suppression systems (sprinklers, carbon dioxide
systems, etc.) or in spaces with a 1-hour fire resistance rating.
FPN: For testing and maintenance procedures of emer-
gency power supply systems (EPSSs), see NFPA 110-1999, FPN: For the definition of occupancy class, see 6.1 of
Standard for Emergency and Standby Power Systems. NFPA 101-2000, Life Safety Code.

70:700.9 Wiring, Emergency System. ARTICLE 760 — FIRE ALARM SYSTEMS


(A) Identification. All boxes and enclosures (including trans- 70:760.5 Access to Electrical Equipment Behind Panels De-
fer switches, generators, and power panels) for emergency signed to Allow Access. Access to equipment shall not be
circuits shall be permanently marked so they will be readily denied by an accumulation of wires and cables that prevents
identified as a component of an emergency circuit or system. removal of panels, including suspended ceiling panels.
(B) Wiring. Wiring of two or more emergency circuits sup- 70:760.6 Mechanical Execution of Work. Fire alarm circuits
plied from the same source shall be permitted in the same shall be installed in a neat and workmanlike manner. Cables
raceway, cable, box, or cabinet. Wiring from an emergency and conductors installed exposed on the surface of ceiling and
source or emergency source distribution overcurrent protec- sidewalls shall be supported by structural components of the
tion to emergency loads shall be kept entirely independent of building in such a manner that the cable or conductors will
all other wiring and equipment, unless otherwise permitted in not be damaged by normal building use. Such cables shall be
(1) through (4): attached to structural components by straps, staples, hangers,
or similar fittings designed and installed so as not to damage
(1) Wiring from the normal power source located in transfer
the cable. The installation shall also conform with
equipment enclosures
300.4(D). . . .
(2) Wiring supplied from two sources in exit or emergency
luminaires (lighting fixtures) 70:760.10 Fire Alarm Circuit Identification. Fire alarm cir-
(3) Wiring from two sources in a common junction box, cuits shall be identified at terminal and junction locations, in
attached to exit or emergency luminaires (lighting fix- a manner that will prevent unintentional interference with the
tures) signaling circuit during testing and servicing.
(4) Wiring within a common junction box attached to unit
equipment, containing only the branch circuit supplying 11.1.1 Section 11.1 shall apply to new, existing, permanent,
the unit equipment and the emergency circuit supplied or temporary electrical appliances, equipment, fixtures, or
by the unit equipment wiring.

--`,,`,``,,,,,,``,````,`,`,,,`-`-`,,`,,`,`,,`---
(C) Wiring Design and Location. Emergency wiring circuits
11.1.1.1 Existing installations shall be permitted to be con-
shall be designed and located to minimize the hazards that
tinued in use provided the lack of conformity does not pres-
might cause failure due to flooding, fire, icing, vandalism,
and other adverse conditions. ent an imminent hazard danger.

(D) Fire Protection. Emergency systems shall meet the fol- 11.1.2 All electrical appliances, fixtures, equipment, or wir-
lowing additional requirements in assembly occupancies
ing shall be installed and maintained in accordance with
greater than 1000 persons or in buildings above 23 m (75 ft) in
NFPA 70, National Electrical Code.
height with any of the following occupancy classes: assembly,
educational, residential, detention and correctional, business,
and mercantile. 11.1.3 Permanent wiring shall be installed and maintained
in accordance with NFPA 70, National Electrical Code.
(1) Feeder-Circuit Wiring. Feeder-circuit wiring shall meet
one of the following conditions:
11.1.4 Permanent wiring abandoned in place shall be
(1) Be installed within buildings that are fully protected by tagged or otherwise identified at its termination and junction
an approved automatic fire suppression system points as ‘‘Abandoned in Place’’ or removed from all accessi-

NFPA 1 Uniform Fire Code Handbook 2003

Copyright National Fire Protection Association


Provided by IHS under license with NFPA Licensee=Technip La Defense/5931917103
No reproduction or networking permitted without license from IHS Not for Resale, 09/10/2007 07:51:22 MDT
148 Part II • General

ble areas and insulated from contact with other live electrical 11.1.5.2.2 The relocatable power taps shall be directly con-
wiring or devices. nected to a permanently installed receptacle.
No wiring should be abandoned unless it has been physically Relocatable power taps are not to be plugged into extension
disconnected at its power source. Wiring that is disconnected cords to extend their reach. If extension cords are used,
should also be tagged, noting that it is disconnected. It is the inspector should require that a permanently installed
better to remove the wiring because in most cases the wiring receptacle be installed in accordance with Section 11.1 and
will never be reused and will remain in place for extended paragraph 11.1.5.
periods, thus increasing fire load.
11.1.5.2.3 Relocatable power tap cords shall not extend
11.1.5 Extension cords shall not be used as a substitute for through walls, ceilings, or floors; under doors or floor cov-
permanent wiring. erings; or be subject to environmental or physical damage.
Extension cords should not be used as permanent wiring. If installations of power taps are found to extend through
Where extension cords are observed being used to perma- walls and floors, or under doors or rugs, the inspector should
nently power equipment, the fire official should require that require that permanent receptacles be installed according to
permanent wiring be installed in accordance with paragraph Section 11.1.
11.1.2.
11.1.5.3 Extension Cords.
11.1.5.1 Multiplug Adapters. Multiplug adapters, such as
multiplug extension cords, cube adapters, strip plugs, and 11.1.5.3.1 Extension cords shall be plugged directly into an
other devices, shall be listed and used in accordance with approved receptacle, power tap, or multiplug adapter and
their listing. shall, except for approved multiplug extension cords, serve
only one portable appliance.
11.1.5.2 Relocatable Power Taps.
11.1.5.2.1 Relocatable power taps shall be of the polarized 11.1.5.3.2 The ampacity of the extension cords shall not be
or grounded type with overcurrent protection and shall be less than the rated capacity of the portable appliance supplied
listed. by the cord.

Relocatable power taps are very common for computer use 11.1.5.3.3 The extension cords shall be maintained in good
at workstations, offices, and dormitories, where additional condition without splices, deterioration, or damage.
electrical power receptacles are needed. During inspections, 11.1.5.3.4 Extension cords shall be grounded when servic-
it should be noted whether power taps are plugged into other ing grounded portable appliances.
power taps like a daisy chain. This practice is not permitted.
Exhibit 11.1 shows an example of a listed relocatable power 11.1.5.3.5 Extension cords and flexible cords shall not be
tap. affixed to structures; extend through walls, ceilings, or
floors, or under doors or floor coverings; or be subject to
environmental or physical damage.
See the commentary following paragraph 11.1.5.2.3.

11.1.6 Temporary Wiring.


11.1.6.1 Except as modified in 11.1.6, all other requirements
of this Code and NFPA 70, National Electrical Code, for
permanent wiring shall apply to temporary installations.
[70:527.2(A)]
Temporary installations of electrical equipment must be in-
stalled in accordance with all applicable permanent installa-
tion requirements except as modified by paragraph 11.1.6.1.
For example, the requirements of 300.15 of NFPA 70, Na-
tional Electrical Code, specify that a box or other enclosure
must be used where splices are made. This rule is amended
by 527.4(G) of NFPA 70, which, for construction sites,
permits splices to be made in multiconductor cords and
EXHIBIT 11.1 Listed relocatable power tap. cables without the use of a box.

--`,,`,``,,,,,,``,````,`,`,,,`-`-`,,`,,`,`,,`--- 2003 NFPA 1 Uniform Fire Code Handbook

Copyright National Fire Protection Association


Provided by IHS under license with NFPA Licensee=Technip La Defense/5931917103
No reproduction or networking permitted without license from IHS Not for Resale, 09/10/2007 07:51:22 MDT
Chapter 11 • Building Services 149

11.1.6.2 Approval. Temporary wiring methods shall be ac- unless approved existing installation shall be permitted to
ceptable only if approved based on the conditions of use be continued in service. [101:9.2.1]
and any special requirements of the temporary installation.
For the proper installation of HVAC systems, paragraph
[70:527.2(B)]
11.2.1 refers the Code user to NFPA 90A, Standard for the
All temporary wiring methods must be approved based on Installation of Air-Conditioning and Ventilating Systems. For
criteria such as (1) length of time in service, (2) severity of occupancies with small overall volumes, such as one- and
physical abuse, (3) exposure to weather, and (4) other special two-family dwellings, the Code refers the user to NFPA
requirements. Special requirements might range from tunnel 90B, Standard for the Installation of Warm Air Heating and
construction projects and tent cities constructed after a natu- Air-Conditioning Systems.
ral disaster to flammable hazardous reclamation projects. For example, NFPA 90A addresses fire damper require-
ments for both ductwork and air transfer grilles that penetrate
11.1.6.3 During the Period of Construction. Temporary fire resistance–rated barriers. NFPA 90A also prohibits
electrical power and lighting installations shall be permitted means of egress corridors in health care, detention and cor-
during the period of construction, remodeling, maintenance, rectional, and residential occupancies from being used as a
repair, or demolition of buildings, structures, equipment, or portion of a supply, return, or exhaust air system serving
similar activities. [70:527.3(A)] adjoining areas. Exhibit 11.2 identifies some of the areas
where fire dampers and smoke dampers would be required
11.1.6.4 90 Days. Temporary electrical power and lighting by NFPA 90A.
installations shall be permitted for a period not to exceed
90 days for holiday decorative lighting and similar purposes.
11.2.2 Ventilating or Heat-Producing Equipment.
[70:527.3(B)]
Ventilating or heat-producing equipment shall be in accor-
Note that the 90-day time limit applies only to temporary
dance with NFPA 91, Standard for Exhaust Systems for Air
electrical installations associated with holiday displays.
Conveying of Vapors, Gases, Mists, and Noncombustible
Temporary wiring installation constructed in emergencies
Particulate Solids; NFPA 211, Standard for Chimneys, Fire-
and for testing is not bound by this time limit.
places, Vents, and Solid Fuel-Burning Appliances; NFPA
31, Standard for the Installation of Oil-Burning Equipment;
11.1.6.5 Emergencies and Tests. Temporary electrical NFPA 54, National Fuel Gas Code; or NFPA 70, National
power and lighting installations shall be permitted during Electrical Code, as applicable, unless approved existing
emergencies and for tests, experiments, and developmental installations shall be permitted to be continued in service.
work. [70:527.3(C)] [101:9.2.2]
11.1.6.6 Removal. Temporary wiring shall be removed im-
mediately upon completion of construction or purpose for 11.2.3 Commercial Cooking Equipment.
which the wiring was installed. [70:527.3(D)] Commercial cooking equipment shall be in accordance with
Due to modifications permitted by Article 527 of NFPA NFPA 96, Standard for Ventilation Control and Fire Protec-
70, temporary wiring installations might not meet all the tion of Commercial Cooking Operations, unless such instal-
requirements for a permanent installation. Therefore, all tem- lation are approved existing installations, which shall be
porary wiring must not only be disconnected but also be permitted to be continued in service. [101:9.2.3]
removed from the building, structure, or other location of
installation. 11.2.4 Ventilating Systems in Laboratories Using
Chemicals.
Ventilating systems in laboratories using chemicals shall
11.2 Heating, Ventilation, and Air be installed in accordance with Chapter 26 and NFPA 45,
Standard on Fire Protection for Laboratories Using Chemi-
Conditioning cals, or NFPA 99, Standard for Health Care Facilities, as
11.2.1 Heating, Ventilating Ductwork, and Related appropriate. [101:9.2.4]
Equipment.
NFPA 45, Standard on Fire Protection for Laboratories
Air conditioning, heating, ventilating ductwork, and related Using Chemicals, contains requirements for construction,
equipment shall be in accordance with NFPA 90A, Standard ventilation, and fire protection in laboratory buildings, as
for the Installation of Air-Conditioning and Ventilating Sys- well as for units and work areas in all buildings. Additional
tems, or NFPA 90B, Standard for the Installation of Warm requirements for laboratories in health care occupancies are
Air Heating and Air-Conditioning Systems as applicable, found in NFPA 99, Standard for Health Care Facilities.

NFPA 1 Uniform Fire Code Handbook 2003 --`,,`,``,,,,,,``,````,`,`,,,`-`-`,,`,,`,`,,`---

Copyright National Fire Protection Association


Provided by IHS under license with NFPA Licensee=Technip La Defense/5931917103
No reproduction or networking permitted without license from IHS Not for Resale, 09/10/2007 07:51:22 MDT
150 Part II • General

operations requirements of ASME/ANSI A17.3, Safety Code


2-hr fire for Existing Elevators and Escalators. [101:9.4.3.2]
barrier
Fire-rated roof/ceiling assembly
Because an elevator stopping at a fire floor (intentionally
or unintentionally) is an extreme hazard, the Code mandates
FD
compliance with the fire fighters’ emergency operations re-
Protection per rated
quirements of ASME A17.1, Safety Code for Elevators and
FD
roof/ceiling assembly Escalators, and ASME A17.3, Safety Code for Existing Ele-
AC AC
FD terminal vators and Escalators, in both new and existing buildings.
terminal
FD device device The fire fighters’ emergency operations requirements estab-
lish elevator recall activated by smoke detection in each
elevator lobby and in associated elevator machine rooms.
FD A three-position, key-operated switch, normally located in
FD Nonrated
ceiling the main lobby at the elevator, controls the recall function.
The requirements mandate specific functions for the ‘‘on,’’
‘‘off,’’ and ‘‘bypass’’ positions of this switch. The require-
ments also provide for emergency in-car operations or what
FD

--`,,`,``,,,,,,``,````,`,`,,,`-`-`,,`,,`,`,,`---
SD 1-hr fire barrier is often referred to as fire fighters’ service. Fire fighters’
FD Smoke
Air transfer opening FD
barrier service requires a three-position, key-operated switch in each
elevator car. The functions of the ‘‘on,’’ ‘‘off,’’ and ‘‘hold’’
positions are specified in the elevator code. For specific
Nonrated
FD partition details, refer to ASME A17.1. Explanatory material on these
FD Air transfer rules can be found in the ASME Handbook A17.1.
opening

11.3.2 Number of Cars.


SD SD FD FD The number of elevator cars permitted in a hoistway shall
Outside air be in accordance with 8.2.5.9 of NFPA 101. [101:9.4.4]
intake 2-hr fire
barrier
FD
11.3.3* Elevator Machine Rooms.
Elevator machine rooms that contain solid-state equipment
FD — Fire damper
AC — Air conditioning for elevators, other than existing elevators, having a travel
SD — Smoke damper distance exceeding 50 ft (15 m) above the level of exit
discharge or exceeding 30 ft (9150 mm) below the level of
EXHIBIT 11.2 Partition and fire barrier penetration protec- exit discharge shall be provided with independent ventilation
tion. or air-conditioning systems required to maintain temperature
during fire fighters’ operations for elevator operation (see
11.3.2 and 11.3.3). The operating temperature shall be estab-
The requirements of both documents are to be applied in lished by the elevator equipment manufacturer’s specifica-
laboratories in health care facilities. See Chapter 26 for tions. When standby power is connected to the elevator,
additional guidance. the machine room ventilation or air conditioning shall be
connected to standby power. [101:9.4.5]
A.11.3.3 Continued operation of solid-state elevator equip-
11.3 Elevators, Escalators, and Conveyors ment is contingent on maintaining the ambient temperature
in the range specified by the elevator manufacturer. If the
11.3.1 Fire Fighters’ Emergency Operations.
machine room ventilation/air conditioning is connected to
11.3.1.1 All new elevators shall conform to the fire fighters’ the general building system, and that system is shut down
emergency operations of ASME/ANSI A17.1, Safety Code during a fire, the fire department might lose the use of
for Elevators and Escalators. [101:9.4.3.1] elevators due to excessive heat in the elevator machine room.
[101: A.9.4.5]
11.3.1.2 All existing elevators having a travel distance of
25 ft (7620 mm) or more above or below the level that best The reasoning behind requiring a ventilation or air-condi-
serves the needs of emergency personnel for fire fighting or tioning system to help keep the elevator controls operable
rescue purposes shall conform to the fire fighters’ emergency is explained in paragraph 11.3.3 and paragraph A.11.3.3.

2003 NFPA 1 Uniform Fire Code Handbook

Copyright National Fire Protection Association


Provided by IHS under license with NFPA Licensee=Technip La Defense/5931917103
No reproduction or networking permitted without license from IHS Not for Resale, 09/10/2007 07:51:22 MDT
Chapter 11 • Building Services 151

For many typical installations, this can be accomplished by considered the outlet of the final pressure regulator, exclusive
installing an independent through-the-wall air-conditioning of line gas regulators, in the system.
unit. Regardless of shutdown of the building’s HVAC sys- (B) The maximum operating pressure shall be 125 psi (862
tem, the independent unit will continue to run, provided that kPa).
its power supply is not interrupted. Exception No. 1: Piping systems for gas–air mixtures within
the flammable range are limited to a maximum pressure of
11.3.4 Elevator Testing. 10 psi (69 kPa).
Exception No. 2: LP-Gas piping systems are limited to 20
Elevators shall be subject to periodic inspections and tests
psi (140 kPa), except as provided in 5.5.2 or NFPA 54.
as specified in ASME/ANSI A17.1, Safety Code for Eleva-
--`,,`,``,,,,,,``,````,`,`,,,`-`-`,,`,,`,`,,`---

tors and Escalators. All elevators equipped with fire fight- (C) Piping systems requirements shall include design, mate-
ers’ emergency operations in accordance with 11.3.1.1 and rials, components, fabrication, assembly, installation, testing,
11.3.1.2 shall be subject to a monthly operation with a written inspection, operation, and maintenance.
record of the findings made and kept on the premises as (D) Requirements for gas utilization equipment and related
required by ASME/ANSI A17.1, Safety Code for Elevators accessories shall include installation, combustion, and ventila-
tion air and venting. [NFPA 54:1.1.1.1]
and Escalators. [101:9.4.6]
NFPA 54 does not apply to the following items (refer-
It is important to provide an appropriate level of elevator
ence standards for some of which appear in Annex L of
testing to help ensure that the elevators can be used by
NFPA 54):
persons with mobility impairment and trained personnel
under fire and other emergency conditions. (1) Portable LP-Gas equipment of all types that are not
connected to a fixed fuel piping system
11.3.5 Openings. (2) Installation of farm equipment such as brooders, dehy-
drators, dryers, and irrigation equipment
Conveyors, elevators, dumbwaiters, and pneumatic con- (3) Raw material (feedstock) applications except for piping
veyors serving various stories of a building shall not open to special atmosphere generators
to an exit. [101:9.4.7] (4) Oxygen–fuel gas cutting and welding systems
(5) Industrial gas applications using such gases as acetylene
Openings in exit enclosures are strictly limited by the provi- and acetylenic compounds, hydrogen, ammonia, carbon
sions of paragraph 14.3.1 to doors necessary for access to monoxide, oxygen, and nitrogen
the exit from normally occupied spaces and for leaving (6) Petroleum refineries, pipeline compressor or pumping
the exit enclosure. Elevators and other conveyors are not stations, loading terminals, compounding plants, refin-
considered normally occupied areas. Additionally, an eleva- ery tank farms, and natural gas processing plants
tor with its associated cables, controls, and mechanical (7) Large integrated chemical plants or portions of such
equipment would introduce a quantity of combustibles into plants where flammable or combustible liquids or gases
an exit enclosure that conflicts with the objective of making are produced by chemical reactions or used in chemical
the exit enclosure a safe place that is free of combustibles. reactions
(8) LP-Gas installations at utility gas plants
(9) Liquefied natural gas (LNG) installations
(10) Fuel gas piping in power and atomic energy plants
11.4 Utilities (11) Proprietary items of equipment, apparatus, or instru-
ments such as gas generating sets, compressors, and
Equipment using fuel gas and related gas piping shall be calorimeters
installed in accordance with NFPA 54, National Fuel Gas (12) LP-Gas equipment for vaporization, gas mixing, and gas
Code, or NFPA 58, Liquefied Petroleum Gas Code. manufacturing
(13) LP-Gas piping for buildings under construction or reno-
NFPA 54, National Fuel Gas Code, applies to the installation
vations that is not to become part of the permanent
of fuel gas piping systems, fuel gas utilization equipment,
building piping system — that is, temporary fixed piping
and related accessories as outlined in (A) through (D). for building heat
(A) Coverage of piping systems shall extend from the point (14) Installation of LP-Gas systems for railroad switch heat-
of delivery to the connections with each gas utilization device. ing
For other than undiluted liquefied petroleum gas systems, the (15) Installation of LP-Gas and compressed natural gas sys-
point of delivery shall be considered the outlet of the service tems on vehicles
meter assembly or the outlet of the service regulator or service (16) Gas piping, meters, gas pressure regulators, and other
shutoff valve where no meter is provided. For undiluted lique- appurtenances used by the serving gas supplier in distri-
fied petroleum gas systems, the point of delivery shall be bution of gas, other than undiluted LP-Gas

NFPA 1 Uniform Fire Code Handbook 2003

Copyright National Fire Protection Association


Provided by IHS under license with NFPA Licensee=Technip La Defense/5931917103
No reproduction or networking permitted without license from IHS Not for Resale, 09/10/2007 07:51:22 MDT
152 Part II • General

(17) Building design and construction, except as specified (9) Refrigeration cycle equipment and LP-Gas used as a
herein refrigerant in a closed cycle
(18) Fuel gas systems on recreational vehicles manufactured (10) Those manufacturing requirements for recreational vehi-
in accordance with NFPA 1192, Standard on Recre- cle LP-gas systems that are addressed by NFPA 1192,
ational Vehicles Standard on Recreational Vehicles. [NFPA 58:1.1.2]
(19) Fuel gas systems using hydrogen as a fuel [NFPA
54:1.1.1.2] Also see Chapter 69.
NFPA 58, Liquefied Petroleum Gas Code, applies to
the operation of all LP-Gas systems including the following:
11.4.1 Existing installations shall be permitted to be contin-
(1) Containers, piping, and associated equipment, when de- ued in service, subject to approval by the AHJ.
livering LP-Gas to a building for use as a fuel gas
(2) Highway transportation of LP-Gas
(3) The design, construction, installation, and operation of
marine terminals whose primary purpose is the receipt
of LP-Gas for delivery to transporters, distributors, or 11.5 Heating Appliances
users
11.5.1 General.

--`,,`,``,,,,,,``,````,`,`,,,`-`-`,,`,,`,`,,`---
Exception No. 1: Marine terminals associated with refineries,
11.5.1.1 The installation of stationary oil-burning equipment
petrochemicals, and gas plants.
and appliances including, but not limited to, industrial-,
Exception No. 2: Marine terminals whose purpose is the de-
livery of LP-Gas to marine vessels.
commercial-, and residential-type steam, hot water, or warm
air heating plants; domestic-type range burners and space
(4) The design, construction, installation, and operation of heaters; portable oil-burning equipment, and all accessory
pipeline terminals that receive LP-Gas from pipelines equipment and control systems, whether electric, thermo-
under the jurisdiction of the U.S. Department of Transpor- static, or mechanical, and all electrical wiring connected to
tation, whose primary purpose is the receipt of LP-Gas oil-fired equipment and to the installation of oil storage
for delivery to transporters, distributors, or users. Cover- and supply systems connected to oil-fired equipment shall
age shall begin downstream of the last pipeline valve or comply with Section 11.5 and NFPA 31, Standard for the
tank manifold inlet. [NFPA 58:1.1.1]
Installation of Oil-Burning Equipment. [31:1.1.1]
NFPA 58 does not apply to the following:
11.5.1.2 Section 11.5 shall also apply to those multi-fueled
(1) Frozen ground containers and underground storage in appliances in which fuel oil is one of the optional fuels.
caverns including associated piping and appurtenances
[31:1.1.3]
used for the storage of LP-Gas
(2) Natural gas processing plants, refineries, and petrochem-
11.5.1.3* Section 11.5 shall not apply to internal combustion
ical plants
engines, oil lamps, or portable devices not specifically cov-
(3) LP-Gas (including refrigerated storage) at utility gas
plants (NFPA 59, Utility LP-Gas Plant Code)
ered in NFPA 31. (See Chapter 11 of NFPA 31 for portable
(4) Chemical plants where specific approval of construction devices that are covered in this standard.) [31:1.1.4]
and installation plans, based on substantially similar
requirements, is obtained from the authority having ju- A.11.5.1.3 Examples of portable devices not covered by this
risdiction standard are blowtorches, melting pots, and weed burners.
(5) LP-Gas used with oxygen (NFPA 51, Standard for the [31: A.1.1.4]
Design and Installation of Oxygen-Fuel Gas Systems
for Welding, Cutting, and Allied Processes, and ANSI 11.5.1.4 The installation of gas-fired heating appliances
Z49.1, Safety in Welding, Cutting, and Allied Processes, shall comply with Section 11.5 and NFPA 54, National Fuel
shall apply.) Gas Code. (See Chapter 69 for LP-Gas fuel supply and
(6) Those portions of LP-Gas systems covered by NFPA storage installations.)
54 (ANSI Z223.1), National Fuel Gas Code, where
NFPA 54 is adopted, used, or enforced NFPA 54 addresses the installation of fuel gas piping sys-
(7) Transportation by air (including use in hot air balloons), tems, fuel gas utilization equipment, and related accessories
rail, or water under the jurisdiction of the U.S. Depart- including piping systems, operating pressure, installation,
ment of Transportation (DOT) combustion, ventilation air, and venting. Although permitted
(8) Marine fire protection (NFPA 302, Fire Protection Stan- in NFPA 54, the installation of unvented fuel-fired heaters
dard for Pleasure and Commercial Motor Craft, shall is prohibited by this Code and NFPA 101 in new and existing
apply.) residential board and care facilities and new and existing

2003 NFPA 1 Uniform Fire Code Handbook

Copyright National Fire Protection Association


Provided by IHS under license with NFPA Licensee=Technip La Defense/5931917103
No reproduction or networking permitted without license from IHS Not for Resale, 09/10/2007 07:51:22 MDT
Chapter 11 • Building Services 153

health care occupancies. This Code and NFPA 101 also areas where fuel is stored, handled, or burned, and for revis-
prohibit unvented fuel-fired heaters from most occupancies, ing the classification if conditions are changed. Installation
with the exception of approved units that comply with NFPA should conform to NFPA 70, National Electrical Code. Ad-
54. ditional guidance can be obtained from NFPA 30, Flamma-
ble and Combustible Liquids Code, and NFPA 30A, Code
11.5.1.5 All heating appliances shall be approved or listed. for Motor Fuel Dispensing Facilities and Repair Garages.

11.5.1.6 Permits. Permits, where required, shall comply


with 1.12.19. 11.5.2 Kerosene Burners and Oil Stoves.
This Code requires that a permit be obtained in order to Kerosene stoves are self-contained, self-supporting, kero-
store, use, or handle LP-Gas or Class I, Class II, and Class sene-burning ranges, room heaters, or water heaters not con-
IIIA flammable or combustible liquids. nected to chimneys but equipped with integral fuel supply
tanks with a maximum capacity of 2 gal (7.6 L). Kerosene
room heaters are often referred to as cabinet heaters and
11.5.1.7 Electrical wiring and utilization equipment used in
space heaters.
connection with oil-burning appliances or equipment shall
Because these heaters are not connected to chimneys,
be installed in accordance with Section 11.1 and NFPA 70,
they can be moved rather easily, although they generally are
National Electrical Code. [31:4.4.1]
not considered portable. Each year, many serious fires result
11.5.1.8 The grade of fuel oil used in an oil burner shall be from the improper use of these heaters. Because of their
that for which the burner is approved and as stipulated by mobility, these stoves pose a hazard when placed near com-
the manufacturer. Crankcase oil, used oil, or oil containing bustible materials or where they can block an exit.
gasoline shall not be used. (For use of oil fuels other than Kerosene stoves listed by testing laboratories incorpo-
those described in this paragraph, see Section 1.3 of NFPA rate fire protection features that might be missing from stoves
31, Standard for the Installation of Oil-Burning Equipment.) that are not listed. Important features of listed stoves include
better construction materials, provision of primary control
Exception: Where acceptable to the AHJ, an oil-burning
valves, and the use of drip pans to catch any leaking fuel
appliance designed to burn crankcase oil or used oil shall
and confine it to the stove.
be permitted to be used only in commercial or industrial
occupancies. Oil-burning appliances intended for firing
crankcase oils shall be listed for use with crankcase oils. 11.5.2.1 Kerosene burners and oil stoves shall be equipped
(See Chapter 12 of NFPA 31 for appliances intended for with a primary safety control furnished as an integral part
firing used oil.) The appliances shall be installed in accor- of the appliance by the manufacturer to stop the flow of oil
dance with the manufacturers’ instructions and with the in the event of flame failure. Barometric oil feed shall not
terms of its listing. (See Section 4.6 of NFPA 31.) [31:4.5.1] be considered a primary safety control.

Section 4.6 of NFPA 31 Standard for the Installation of Oil 11.5.2.2 A conversion range oil burner shall be equipped
Burning Equipment, provides the applicable requirements with a thermal (heat-actuated) valve in the oil supply line,
for the use of crankcase and used oil as a fuel. Typical located in the burner compartment of the stove.
locations are burner areas, fuel-handling areas, fuel storage
Conversion range oil burners consist of a single-sleeve or
areas, pits, sumps, and low spots where fuel leakage or
vapors can accumulate. Chapter 5 of NFPA 70 provides double-sleeve burner assembly, regulating valves, and an
information for classifying such areas and defines require- oil supply assembly with a suitable supporting stand and
ments for electrical installations in areas so classified. seamless connecting tubing. A thermal valve located in the
burner compartment of the stove adjacent to the burner is
Crankcase oil and used oil properties can vary consider-
ably, and light volatile materials can be released during installed in the oil supply line. (See Exhibit 11.3.)
storage or handling or upon heating. Because of this charac- Range oil burners, which are found most frequently in
teristic, appropriate and adequate provisions should be made the northeastern United States, are designed to burn kero-
sene, range oil, or similar fuel. They are primarily installed
to safely handle, store, and burn crankcase oil and used oil.
in stoves or ranges originally designed to use solid fuel.
It is desirable that flexibility be built into the facility to
accommodate the expected range of properties of the fuels Range oil burners should not be mistaken for vaporizing-
--`,,`,``,,,,,,``,````,`,`,,,`-`-`,,`,,`,`,,`---

in use. Failure to observe the necessary design, installation, pot conversion oil burners that are designed for conversion
of central heating appliances.
and operating and maintenance procedures can result in fire,
explosion, or personal injury.
Extensive treatment of this subject is beyond the scope 11.5.2.3 Only listed kerosene heaters shall be used. The
of this Code. The AHJ should be responsible for classifying following safeguards shall apply:

NFPA 1 Uniform Fire Code Handbook 2003

Copyright National Fire Protection Association


Provided by IHS under license with NFPA Licensee=Technip La Defense/5931917103
No reproduction or networking permitted without license from IHS Not for Resale, 09/10/2007 07:51:22 MDT
154 Part II • General

the use of electric space heaters should be instructed to


remind employees to shut them off at the end of the day
and keep combustible material away from the heater.
³⁄₄ in. (19 mm)
In addition, because of the amount of electric current
drawn by space heaters, it is important that the heaters be
used only where they can be plugged directly into an appro-
Oil level
priate receptacle or that extension cords of adequate wire
size are used. See paragraph 11.1.5.3 for requirements deal-
ing with extension cords.
The AHJ is permitted to prohibit the use of space heaters
where an undue danger to life or property exists. The AHJ
can use past inspection findings, such as portable heaters
that were left turned on and unattended, fire incidents, and
other reasons to prohibit the use of such heaters. This Code
and the Life Safety Code specifically prohibit the use of
portable space heaters in health care and ambulatory health
EXHIBIT 11.3 Typical installation of conversion range oil care facilities, with the exception of nonsleeping staff and
burner. employee areas. In these areas, heaters are permitted, pro-
vided that the heating element cannot reach more than 212F
(100C) and that the AHJ allows such use.
(1) Provide adequate ventilation.
(2) Do not place on carpeting. 11.5.3.2 Portable electric heaters shall be designed and lo-
(3) Keep 3 ft (0.9 m) away from combustible furnishings cated so that they cannot be easily overturned.
or drapes.
11.5.3.3 All portable electric heaters shall be listed.
(4) Use only approved Type 1-K water clear kerosene.
(5) Allow to cool before refueling.
11.5.4 Vents.
Portable kerosene heaters pose a hazard similar to that of
All chimneys, smokestacks, or similar devices for conveying
kerosene stoves, since they are not connected to a chimney.
smoke or hot gases to the outer air and the stoves, furnaces,
However, the hazard is increased by their greater portability
incinerators, boilers, or any other heat-producing devices or
and subsequent misuse and improper placement. They are
appliances shall be installed and maintained in accordance
also subject to improper fueling, substitution of gasoline or
with NFPA 54, National Fuel Gas Code, and NFPA 211,
other inappropriate liquid fuel, and refueling when hot,
Standard for Chimneys, Fireplaces, Vents, and Solid Fuel-
which can produce and ignite flammable vapors. The safest
Burning Appliances.
heaters incorporate fire safety features such as special types
of latching devices and integral sheet-metal trays under the
burners to catch oil drips. They usually employ wick-type
burners that are integral with the oil reservoir. Portable kero- 11.6 Rubbish Chutes, Incinerators, and
sene heaters should include a tip-over switch that automati-
Laundry Chutes
cally snuffs the burner if the unit is jostled or tipped.
11.6.1 Enclosure.
11.5.3 Portable Electric Heater. 11.6.1.1 Rubbish chutes and laundry chutes shall be sepa-
11.5.3.1 The AHJ shall be permitted to prohibit use of porta- rately enclosed by walls or partitions in accordance with the
ble electric heaters in occupancies or situations where such provisions of Section 8.2 of NFPA 101. [101:9.5.1.1]
use or operation would present an undue danger to life or 11.6.1.2 Inlet openings serving chutes shall be protected in
property. accordance with Section 8.2 of NFPA 101. [101:9.5.1.2]
During cold weather, portable electric space heaters are used
11.6.1.3 The doors of chutes specified in 11.6.1.2 shall open
--`,,`,``,,,,,,``,````,`,`,,,`-`-`,,`,,`,`,,`---

in many locations, including under desks. Although placing


only to a room that is designed and used exclusively for
a heater under a desk or table lessens the chance of the
accessing the chute opening. [101:9.5.1.3]
heater’s being easily overturned, the heater also can easily
be forgotten. A heater that is left on for an extended time 11.6.1.4 The room used for accessing the chute opening
can overheat combustible materials that might also be stored shall be separated from other spaces in accordance with
under the desk or table. Managers of facilities that allow Section 8.4 of NFPA 101. [101:9.5.1.4]

2003 NFPA 1 Uniform Fire Code Handbook

Copyright National Fire Protection Association


Provided by IHS under license with NFPA Licensee=Technip La Defense/5931917103
No reproduction or networking permitted without license from IHS Not for Resale, 09/10/2007 07:51:22 MDT
Chapter 11 • Building Services 155

11.6.1.5 The requirements of 11.6.1.1 through 11.6.1.4 shall


not apply where otherwise permitted by the following: Chute extends above roof

(1) Existing installations having properly enclosed service


chutes and properly installed and maintained service
openings shall be permitted to have inlets open to a Fire protection– Sprinkler
corridor or normally occupied space. rated loading door
(2) Rubbish chutes and laundry chutes shall be permitted
to open into rooms not exceeding 400 ft2 (37 m2) that
are used for storage, provided that the room is protected
by automatic sprinklers. [101:9.5.1.5]
Fire-rated
Laundry chutes are often associated with a laundry/storage enclosure
room. The provision of paragraph 11.6.1.5(2) allows chutes
to open into such rooms, provided that the room does not Service opening
exceed 400 ft2 (37 m2) in area. Without this provision, the room with fire
door (typical on Sprinkler
user might interpret the words ‘‘used exclusively’’ (see para- each floor)
graph 11.6.1.3) as limiting the use of that room to serving
the chute only.
Self-closing
fire-rated door
11.6.2 Installation and Maintenance.
Rubbish chutes, laundry chutes, and incinerators shall be
installed and maintained in accordance with NFPA 82, Stan-
Gravity chute
dard on Incinerators and Waste and Linen Handling Systems
and Equipment, unless approved existing installations shall
EXHIBIT 11.4 Protection of waste and linen chutes.
be permitted to be continued in service. [101:9.5.2]
Shafts containing waste and linen chutes must be enclosed
according to the requirements for the protection of vertical closed room door. Exhibit 11.5 illustrates the measurement
openings found in Section 8.6 of NFPA 101. The installation of this clearance.
of the chute itself must meet the requirements of NFPA 82,
Standard on Incinerators and Waste and Linen Handling
Systems and Equipment.
Additional concerns regarding chutes opening to other 11.7 Stationary Generators and Standby
parts of the building need to be addressed. For convenience, Power Systems
service openings for loading are usually located to be acces- 11.7.1 Stationary Combustion Engines and Gas
sible from corridors on the upper floors of the building. Turbines Installation.
However, these corridors also serve as exit access, and a
fire in the chute with an open loading door could result in Stationary generator sets shall be installed in accordance
the obstruction of the corridor by smoke and other products with NFPA 37, Standard for the Installation and Use of
of combustion. To address this hazard, the Code and NFPA Stationary Combustion Engines and Gas Turbines and NFPA
82 require the construction of service opening rooms to form 70, National Electrical Code.
a buffer between the chute and the building space. The NFPA 37, Standard for the Installation and Use of Stationary
special hazard protection provisions in Section 8.7 of NFPA Combustion Engines and Gas Turbines, applies to stationary
101 for the separation of the service opening are referenced combustion engines and gas turbines, portable engines that
in paragraph 11.6.1.4. The result is a room that is separated remain connected for use in the same location for a period
from the rest of the building by construction with a 1-hour of one week or more, and to new installations and to those
fire resistance rating or protected with an automatic extin- portions of existing equipment and installations that are
guishing system. The door to this room is required to have changed or modified.
a 3⁄4-hour fire protection rating. Exhibit 11.4 illustrates the
protection arrangement required for waste and linen chutes
11.7.2 Emergency and Standby Power Systems.
by NFPA 82.
Additionally, NFPA 82 requires the service opening 11.7.2.1 General. Stationary generators for emergency use
room to be sized to maintain a minimum 6-in. (150-mm) or standby power required by this Code, the building code,
clearance between the open chute loading door and the or other codes and standards shall be installed in accordance

NFPA 1 Uniform Fire Code Handbook 2003


--`,,`,``,,,,,,``,````,`,`,,,`-`-`,,`,,`,`,,`---

Copyright National Fire Protection Association


Provided by IHS under license with NFPA Licensee=Technip La Defense/5931917103
No reproduction or networking permitted without license from IHS Not for Resale, 09/10/2007 07:51:22 MDT
156 Part II • General

(3) By listing for emergency service as a completely fac-


tory-assembled and factory-tested apparatus

Chute 11.7.3 Stored Electrical Energy Emergency and


Standby Power System Installation.
Stored electrical energy systems required by this Code, the
Open loading building code, or other NFPA codes and standards shall be
door
installed in accordance with NFPA 111, Standard on Stored
Electrical Energy Emergency and Standby Power Systems
Service opening and NFPA 70, National Electrical Code.
room
6 in. NFPA 111, Standard on Stored Electrical Energy Emergency
(150 mm)
and Standby Power Systems, covers performance require-
ments for stored electrical energy systems providing an alter-
nate source of electrical power in buildings and facilities in
the event that the normal electrical power source fails. Sys-
tems covered by NFPA 111 include power sources, transfer
EXHIBIT 11.5 Clearance in service opening room. equipment, controls, supervisory equipment, and accessory
equipment, including integral accessory equipment, needed
to supply electrical power to the selected circuits. It also
with NFPA 110, Standard for Emergency and Standby Power covers installation, maintenance, operation, and testing re-
Systems. quirements as they pertain to the performance of the stored
NFPA 110, Standard for Emergency and Standby Power emergency power supply system (SEPSS).
Systems, covers performance requirements for power sys- NFPA 111 does not cover the following:
tems providing an alternate source of electrical power to 1. The application of the SEPSS
loads in buildings and facilities in the event that the primary
--`,,`,``,,,,,,``,````,`,`,,,`-`-`,,`,,`,`,,`---

2. Distribution wiring
power source fails. Power systems covered in NFPA 110 3. Systems having total outputs less than 500 VA or less
include power sources, transfer equipment, controls, supervi- than 24 V or systems less than Class 0.033
sory equipment, and all related electrical and mechanical 4. Emergency lighting unit equipment
auxiliary and accessory equipment needed to supply electri- 5. Nuclear sources, fuel cells, solar systems, and wind
cal power to the load terminals of the transfer equipment. It stored-energy systems are not covered by the scope of
also covers installation, maintenance, operation, and testing this document.
requirements as they pertain to the performance of the emer- 6. Specific buildings or facilities, or both, requiring a SEPSS
gency power supply system (EPSS). 7. Specific loads to be served by the SEPSS
NFPA 110 does not cover application of the EPSS, 8. Type, class, or level to be assigned to any specific load
emergency lighting unit equipment, distribution wiring, util- (See Section 2.1 of NFPA 111)
ity service, when such service is permitted as the EPSS,
parameters for stored energy devices, and criteria for stored
energy systems. It also does not apply to specific buildings 11.7.4 Maintenance and Testing.
or facilities, or both, requiring an EPSS, specific loads to 11.7.4.1 Stationary generators used for standby power shall
be served by the EPSS, or assignment of type, class, or be tested and maintained in accordance with NFPA 37, Stan-
level to any specific load. See the commentary following dard for the Installation and Use of Stationary Combustion
paragraph 11.7.3 for a discussion of EPSS. Engines and Gas Turbines.

11.7.2.2 Acceptance. Newly installed stationary generators 11.7.4.2 Stationary generators required by this Code, the
for emergency use or for standby power for fire protection building code, or other NFPA codes and standards shall
systems and features shall demonstrate the capacity of the be maintained in accordance with NFPA 110, Standard for
energy converter, with its controls and accessories, to survive Emergency and Standby Power Systems.
without damage from common and abnormal disturbances
11.7.4.3 Stored electrical energy systems required by this
in actual load circuits by any of the following means:
Code, the building code, or other NFPA codes and standards
(1) By tests on separate prototype models shall be maintained in accordance with NFPA 111, Standard
(2) By acceptance tests on the system components as per- on Stored Electrical Energy Emergency and Standby Power
formed by the component suppliers Systems.

2003 NFPA 1 Uniform Fire Code Handbook

Copyright National Fire Protection Association


Provided by IHS under license with NFPA Licensee=Technip La Defense/5931917103
No reproduction or networking permitted without license from IHS Not for Resale, 09/10/2007 07:51:22 MDT
Chapter 11 • Building Services 157

others by partitions, floors, and doors that can be closed to


11.8* Smoke Control inhibit the movement of smoke. A smoke control zone can
The provisions of Section 11.8 do not itself require smoke consist of one or more floors, or a floor can consist of more
control systems but mandates that, if such systems are in- than one smoke control zone. Some arrangements of smoke
stalled for Code compliance, an approved maintenance and control zones are depicted in Exhibit 11.6, illustrations (a)
testing program must be provided to ensure operational in- through (e). The smoke zones are indicated by minus signs,
tegrity. A smoke control system dedicated to emergency use and pressurized spaces are indicated by plus signs. All non-
only will not be subject to the daily use of a combination smoke zones might be pressurized as in illustrations (a) and
public address system and emergency occupant notification (c), or only those nonsmoke zones that are adjacent to the
system. Therefore, maintenance and testing of smoke control smoke zone might be pressurized as in illustrations (b) and
systems are necessary. (d). In illustration (e), the smoke zone has been limited to
Some NFPA 101 requirements, such as those applicable a portion of a floor.
to atria, mandate smoke control systems via performance-
based language that requires tenable smoke conditions dur-
ing egress. Annex references are provided to advise users +
+
of material that is available to assist in the design of smoke
+ +
control systems. – { Smoke zone { –
+ +
+
A.11.8 NFPA 92A, Recommended Practice for Smoke-Con- +
trol Systems, provides guidance in implementing systems (a) (b)
using pressure differentials to accomplish one or more of
the following: +
+
(1) Maintain a tenable environment in the means of egress +
during the time required for evacuation + +
(2) Control and reduce the migration of smoke from the + +
+ +
fire area – –
(3) Provide conditions outside the fire zone that assist emer- – Smoke zone –
gency response personnel to conduct search and rescue – –
+ +
operations and to locate and control the fire
+ +
(4) Contribute to the protection of life and reduction of + +
property loss +
+
The reference documents that provide design guidance can- +
not be mandatorily referenced because they themselves do (c) (d)
not contain mandatory requirements. NFPA 92A, Recom-
mended Practice for Smoke-Control Systems, addresses + + +
smoke control management that uses barriers, airflows, and + + +
pressure differentials to confine the smoke of a fire to the + + – { Smoke
zone
+ + +
zone of fire origin and thus maintain a tenable environment + + +
in other zones. The guidelines of NFPA 92A can be used to + + +
create a smokeproof enclosure using the stair pressurization (e)
method described in 7.2.3.9 of NFPA 101. The document
also covers smoke control for elevator hoistways by em- EXHIBIT 11.6 Smoke control zone arrangement.
ploying the following methods either singly or in combina-
tion: The subject of maintaining tenable conditions within
1. Fire floor exhaust large zones of fire origin (such as atria and shopping malls)
2. Elevator lobby pressurization is addressed by NFPA 92B, Guide for Smoke Management
3. Smoketight elevator lobby construction Systems in Malls, Atria, and Large Areas. NFPA 92B pro-
4. Elevator hoistway pressurization vides technical data relevant to the design, installation, test-
ing, operation, and maintenance of smoke management
NFPA 92A also addresses, in detail, zoned smoke con- systems in buildings with large-volume spaces. These sys-
trol under which a building can be divided into a number tems manage smoke within the space where the fire exists
of smoke control zones. Each zone is separated from the or between spaces not separated by smoke barriers. The

NFPA 1 Uniform Fire Code Handbook 2003


--`,,`,``,,,,,,``,````,`,`,,,`-`-`,,`,,`,`,,`---

Copyright National Fire Protection Association


Provided by IHS under license with NFPA Licensee=Technip La Defense/5931917103
No reproduction or networking permitted without license from IHS Not for Resale, 09/10/2007 07:51:22 MDT
158 Part II • General

guidelines of NFPA 92B can be used to implement smoke


management systems that help to maintain a tenable environ- 11.9 Emergency Command Center
ment in the means of egress from large-volume building Where required, emergency command centers shall comply
spaces during the time required for evacuation. NFPA 92B with Section 11.9.
also addresses the control and reduction of the smoke migra-
tion between the fire area and adjacent spaces. This analysis 11.9.1 The location, design, and fire department access of
concerns a particular atrium building configuration in which the emergency command center shall be approved by the
the exhaust rate keeps smoke from descending from the fire department.
ceiling level to a level lower than head height of persons
on the highest floor of the building open to the atrium. The 11.9.2 The emergency command center shall be separated
summation of the exercise is generalized in Exhibit 11.7. from the remainder of the building by a fire barrier having
a fire resistance rating of not less than 1 hour.
It is important that the fire department be consulted in rela-
V tion to the location, design, and access to the emergency
12 command center, as they will be the primary users of the
11
space. The emergency command center should have easy
10
access from the outside without requiring entrance through
9
the building. The emergency command center can be placed
8
either in a room near an entrance or exit to the building or
have access from outside the building only.
7
6
5 11.9.3 The emergency command center room shall be a
4
minimum of 96 ft2 (8.9 m2) with a minimum dimension of
3
8 ft (2.4 m).
2
Floor 1 11.9.4 The following shall be provided in the emergency
command center:

EXHIBIT 11.7 Control of smoke layer. (1) The fire department communication unit
(2) A telephone for fire department use with controlled
--`,,`,``,,,,,,``,````,`,`,,,`-`-`,,`,,`,`,,`---

access to the public telephone system


Although NFPA 92A and NFPA 92B cannot be refer-
(3) Schematic building plans indicating the typical floor
enced mandatorily by this Code or NFPA 101, they should
plan and detailing the building core means of egress,
be used in the design, installation, testing, operation, and
fire protection systems, fire-fighting equipment, and fire
maintenance of smoke control systems covered by their
department access
scope statements.
(4) Work table

11.8.1 Smoke control systems shall have an approved main- The emergency command center should be sized to accom-
tenance and testing program to ensure operational integrity. modate all the equipment and supplies outlined in paragraphs
11.9.4 and 11.9.5. It should also be large enough to permit
fire department personnel adequate room to work. It should
11.8.2 All smoke control systems and devices shall be
be big enough or another room provided to store additional
maintained in a reliable operating condition and shall be
supplies required or needed by the fire department.
replaced or repaired where defective.

11.8.3 The AHJ shall be notified when any smoke control 11.9.5 Where otherwise required, the following devices or
functions shall be provided within the emergency command
system is out of service for more than 4 hours in a 24-hour
center:
period and again upon restoration of service of such systems.
(1) The emergency voice/alarm communication system
11.8.4 The AHJ shall be permitted to require the building unit
to be evacuated, or an approved fire watch to be provided (2) Fire detection and alarm system annunciator unit
for all portions left unprotected by the fire protection system (3) Annunciator visually indicating the location of the ele-
shutdown until the fire protection system has been returned vators and whether they are operational
to service. (4) Status indicators and controls for air-handling systems

2003 NFPA 1 Uniform Fire Code Handbook

Copyright National Fire Protection Association


Provided by IHS under license with NFPA Licensee=Technip La Defense/5931917103
No reproduction or networking permitted without license from IHS Not for Resale, 09/10/2007 07:51:22 MDT
Chapter 11 • Building Services 159

(5) Controls for unlocking stairway doors simultaneously NFPA 90A, Standard for the Installation of Air-Conditioning
(6) Sprinkler valve and waterflow detector display panels and Ventilating Systems, 2002 edition.
(7) Emergency and standby power status indicators NFPA 90B, Standard for the Installation of Warm Air Heat-
(8) Fire pump status indicators ing and Air-Conditioning Systems, 2002 edition.
(9) Generator supervision devices and manual start and NFPA 91, Standard for Exhaust Systems for Air Conveying of
transfer features Vapors, Gases, Mists, and Noncombustible Particulate
(10) Public address system, where specifically required by Solids, 1999 edition.
--`,,`,``,,,,,,``,````,`,`,,,`-`-`,,`,,`,`,,`---

other sections of this Code NFPA 96, Standard for Ventilation Control and Fire Protec-
(11) Controls required for smoke control tion of Commercial Cooking Operations, 2001 edition.
NFPA 99, Standard for Health Care Facilities, 2002 edition.
It makes sense to have the devices or functions listed in
NFPA 110, Standard for Emergency and Standby Power
paragraph 11.9.5 as part of the emergency command center.
Systems, 2002 edition.
The emergency command center gives the fire department
NFPA 111, Standard on Stored Electrical Energy Emergency
access to valuable communication, control, and protection
and Standby Power Systems, 2001 edition.
systems indicators. According to paragraph 11.9.1, the fire
NFPA 211, Standard for Chimneys, Fireplaces, Vents, and
department is to be consulted and should approve the design
Solid Fuel-Burning Appliances, 2003 edition.
and layout of the emergency command center, including the
layout of those devices and functions outlined in paragraphs Commentary References
11.9.4 and 11.9.5.
ANSI Z49.1, Safety in Welding, Cutting, and Allied Pro-
cesses.
11.9.6 Emergency Command Center Acceptance ASME Handbook A17.1, 1996 edition.
Testing. ASME/ANSI A17.1, Safety Code for Elevators and Escala-
Devices, equipment, components, and sequences shall be tors, 1996 edition.
individually tested in accordance with appropriate standards ASME/ANSI A17.3, Safety Code for Existing Elevators and
and manufacturers’ documented instructions. Escalators, 1996 edition.
Life Safety Code Handbook, 2003 edition.
The equipment, devices, controls, and other items installed NFPA 20, Standard for the Installation of Stationary Pumps
or provided in the emergency command center need to be for Fire Protection, 1999 edition.
tested to ensure they function properly. Testing should be NFPA 30A, Code for Motor Fuel Dispensing Facilities and
performed on the initial installation and at varying intervals Repair Garages, 2000 edition.
as required by the AHJ or appropriate standards such as NFPA 31, Standard for the Installation of Oil-Burning
NFPA 72, National Fire Alarm Code, and NFPA 20, Equipment, 2001 edition.
Standard for the Installation of Stationary Pumps for Fire NFPA 37, Standard for the Installation and Use of Stationary
Protection. Combustion Engines and Gas Turbines, 2002 edition.
NFPA 45, Standard on Fire Protection for Laboratories
REFERENCES Using Chemicals, 2000 edition.
NFPA 51, Standard for the Design and Installation of Oxy-
Code References
gen–Fuel Gas Systems for Welding, Cutting, and Allied
ASME/ANSI A17.1, Safety Code for Elevators and Escala- Processes, 2002 edition.
tors. NFPA 54, National Fuel Gas Code, 2002 edition.
ASME/ANSI A17.3, Safety Code for Existing Elevators and NFPA 58, Liquefied Petroleum Gas Code, 2001 edition.
Escalators. NFPA 59, Utility LP-Gas Plant Code, 2001 edition.
NFPA 31, Standard for the Installation of Oil-Burning NFPA 70, National Electrical Code, 2002 edition.
Equipment, 2001 edition. NFPA 72, National Fire Alarm Code, 2002 edition.
NFPA 37, Standard for the Installation and Use of Stationary NFPA 82, Standard on Incinerators and Waste and Linen
Combustion Engines and Gas Turbines, 2002 edition. Handling Systems and Equipment, 1999 edition.
NFPA 45, Standard on Fire Protection for Laboratories NFPA 90A, Standard for the Installation of Air-Conditioning
Using Chemicals, 2000 edition. and Ventilating Systems, 2002 edition.
NFPA 54, ANSI Z223.1–2002 National Fuel Gas Code, 2002 NFPA 90B, Standard for the Installation of Warm Air Heat-
edition. ing and Air-Conditioning Systems, 2002 edition.
NFPA 58, Liquefied Petroleum Gas Code, 2001 edition. NFPA 92A, Recommended Practice for Smoke-Control Sys-
NFPA 70, National Electrical Code, 2002 edition. tems, 2000 edition.
NFPA 82, Standard on Incinerators and Waste and Linen NFPA 92B, Guide for Smoke Management Systems in Malls,
Handling Systems and Equipment, 1999 edition. Atria, and Large Areas, 2000 edition.

NFPA 1 Uniform Fire Code Handbook 2003

Copyright National Fire Protection Association


Provided by IHS under license with NFPA Licensee=Technip La Defense/5931917103
No reproduction or networking permitted without license from IHS Not for Resale, 09/10/2007 07:51:22 MDT
160 Part II • General

NFPA 99, Standard for Health Care Facilities, 1999 edition. NFPA 211, Standard for Chimneys, Fireplaces, Vents, and
NFPA 101, Life Safety Code, 2003 edition. Solid Fuel-Burning Appliances, 2003 edition.
NFPA 110, Standard for Emergency and Standby Power NFPA 302, Fire Protection Standard for Pleasure and Com-
Systems, 2002 edition. mercial Motor Craft, 1998 edition.
NFPA 111, Standard on Stored Electrical Energy Emergency NFPA 1192, Standard on Recreational Vehicles, 2002 edi-
and Standby Power Systems, 2001 edition. tion.

2003 NFPA 1 Uniform Fire Code Handbook


--`,,`,``,,,,,,``,````,`,`,,,`-`-`,,`,,`,`,,`---

Copyright National Fire Protection Association


Provided by IHS under license with NFPA Licensee=Technip La Defense/5931917103
No reproduction or networking permitted without license from IHS Not for Resale, 09/10/2007 07:51:22 MDT

You might also like