You are on page 1of 8

BUILD SIMUL

DOI 10.1007/s12273-016-0295-2

An evaluation index for the control effect of the local ventilation


systems on indoor air quality in industrial buildings

Research Article
Yi Wang1 (), Yingxue Cao1, Bo Liu1, Jiaping Liu1, Yang Yang1, Qun Yu1,2

1. School of Environmental and Municipal Engineering, Xi'an University of Architecture and Technology, No. 13 Yanta RD., Xi'an, Shaanxi
710055, China
2. Shaanxi Architectural Design and Research Institute, China

Abstract Keywords
To evaluate the control effect on indoor air quality (IAQ) of the local ventilation systems in industrial evaluation index,
buildings with centralized contaminant sources, a new index, namely, normalized concentration local ventilation system,
in the target zone (NC-TZ), was proposed in this paper. According to theoretical analysis, NC-TZ is computational fluid dynamics (CFD),
non-dimensional and ranges from 0 to 1. When NC-TZ tends toward 0, the control effect of the indoor air quality (IAQ),
local ventilation system on IAQ is more satisfactory. When NC-TZ tends toward 1, the control effect contaminant concentration distribution

on IAQ is less satisfactory. The numerical simulation on a push–pull ventilation system with varying
exhaust flow rates and varying distances between push and pull hoods was performed. The
Article History
Received: 5 January 2016
results demonstrate that for the same capture efficiency, changing the local ventilation system
Revised: 12 April 2016
characteristics can change the control effect on the local environment. The results for obstacles at
Accepted: 18 April 2016
different positions also indicate that NC-TZ can clearly reflect the control effect on IAQ of the local
ventilation systems in industrial buildings.
© Tsinghua University Press and
Springer-Verlag Berlin Heidelberg
2016

1 Introduction usually evaluated by the capture efficiency of the exhaust


hood since it is a direct, quantitative measure of system
The air pollution caused by contaminants emitted from performance (Madsen et al. 1994; Ellenbecker et al. 1983).
industrial processes is strongly harmful to indoor operators. However, the capture efficiency only reflects the capture
People suffering from occupational diseases expand gradually effect of the system on contaminants, regardless of the
with industry development (Brown 2006). Simultaneously, contaminant concentration distribution in the room. Even

Indoor/Outdoor Airflow
indoor environmental quality can also obviously influence if the capture efficiency is very high, the control effect of the
and Air Quality
operating efficiency (Sundell 1996; Wargocki et al. 1999). system on IAQ could not be considered simply as desirable
Woods (1989) conducted a telephone survey, and the results as that on contaminants. When contaminants emitted from
showed that 20% of operators complained that low indoor sources diffuse into the room extensively, for example, IAQ
air quality (IAQ) reduced their operating efficiency. Great may not meet the accepted standards and operators may
attention should be paid to IAQ in industrial buildings to suffer from occupational diseases due to their large exposure,
protect operators’ health and improve operating efficiency. even if contaminants can be captured eventually. Therefore,
Compared with civil buildings, local contaminant sources both the capture efficiency and the evaluation index for
can be found more frequently in industrial buildings. Thus, IAQ should be considered to reflect the comprehensive
compared with general ventilation that removes contaminants performance of the local ventilation system in industrial
from the whole room, the effect of local ventilation that buildings.
controls contaminants directly at their source is more desirable. For traditional evaluation indices, such as the “age” of
In existing studies, local ventilation system performance is the air, the air exchange efficiency (AEE) and contamination
E-mail: wangyi6920@126.com
2 Wang et al. / Building Simulation

removal efficiency (CRE), a ventilated room is usually regarded processes are usually strongly toxic, even if the mean
as a whole to evaluate IAQ. The “age” of the air, which is contaminant concentration value of the worker’s breathing
the time air remains in the room, is a quantitative index that zone is below the accepted value, there may still be a serious
measures the freshness level of indoor air. It is independent hidden health danger when other parts of the body are
of indoor contaminants and only relies on the airflow pattern exposed to the contaminants for a long period of time (Divine
(Sandberg and Sjoberg 1983). AEE is the ratio of the mean and Hartman 2001; Koh et al. 2011). Therefore, the various
age of the room air with displacement ventilation to that of existing zones and indices may not reflect the control effect
the room with the actual ventilation system. Similar to the on IAQ of local ventilation system in industrial buildings
“age” of the air, the air exchange efficiency is also a quantitative clearly.
index which can be used to evaluate the freshness level of In this study, the target zone was defined to reflect the
indoor air (Sandberg and Sjoberg 1983; Sandberg 1983). CRE, indoor contaminant diffusion region. A new index, namely,
also known as ventilation efficiency, is an index to judge the the normalized concentration in the target zone (NC-TZ),
ability of the supply air to remove indoor contaminants. Both was proposed to evaluate the control effect of local ventilation
the airflow pattern and the indoor contaminant sources systems on IAQ in industrial buildings. Several cases were
determine the CRE (Sandberg 1981). presented to demonstrate the new index.
However, environmental parameters in the actual
building, such as temperature, velocity and contaminant 2 Normalized concentration in the target zone
concentration, often present non-uniform distributions.
It is reasonable to divide the ventilated room into several The aim of a local ventilation system is to limit the con-
control zones to reduce building energy consumption and taminant to a local area in order to reduce its effect on the
improve IAQ. For decades, many researchers had made whole environment in an industrial building. In the actual
significant contributions to calculating these traditional production process, the following phenomenon is frequently
indices at different control zones and proposing new indices. observed: for the same contaminant species and the same
Makhoul et al. (2013) applied the index at the breathing zone contaminant emission concentration, different flow field
to evaluate different cases when they discussed the improved characteristics, such as the larger supply flow rate and
performance of a ceiling-mounted personalized ventilation exhaust flow rate in Fig. 1(a) than those in Fig. 1(b), may
nozzle assisted by small desk-mounted fans to reduce the result in a difference of these contaminant concentration
effect of a thermal plume generated by the occupant. Xing distributions, as shown in Fig. 1. For these distributions,
et al. (2001) analysed the relationship of the age of air the capture efficiency of the local ventilation system has
distribution, the air exchange efficiency and the ventilation already reached the peak of 100%. The mean contaminant
effectiveness at the breathing zone and the occupied zone
(below 2 m) in a room with displacement ventilation. Cao
et al. (2014) evaluated IAQ and human comfort at the
occupied zone when they developed theoretical models to
predict the performance of a new type of air distribution
method known as protected occupied zone ventilation. Zhao
et al. (2003) proposed occupied density (OD) and evaluated
the total influence of contaminants over a finite period of
time using the integrated accessibility of contaminant source
(IACS) as the index in which the indoor occupant distribution
is considered. Kikuchi et al. (2003, 2004) proposed the
normalized concentration in the occupied zone (NC-OZ)
and calculated this index for several different ventilation
systems.
The various zones and indices above were all proposed
based on the civil construction environment and contaminant
characteristics, while zones and indices only for industrial
buildings are infrequent. However, in consideration of
the large space and centralized contaminants in industrial
buildings, dividing the occupied zone by height only for IAQ Fig. 1 Contaminant concentration distribution schematic diagram
in industrial buildings is clearly not suitable. Simultaneously, of a local ventilation system under different conditions (─ occupied
as the centralized contaminants emitted during industrial zone; ─ breathing zone)
Wang et al. / Building Simulation 3

concentrations of the breathing zone and of the occupied contaminant. When the mean contaminant concentration
zone have no significant difference, that is, the above indices in the target zone approaches the mean contaminant con-
of each region are very similar. However, due to the different centration of the whole room (Ct→1), the control effect
contaminant concentration distributions, the control effect on IAQ decreases gradually with the decentralization of the
of the local ventilation system on IAQ shown in Fig. 1(a) is contaminant.
different from that shown in Fig. 1(b). Compared with Besides a high capture efficiency, the NC-TZ should be
Fig. 1(a), the workers in Fig. 1(b) are more vulnerable to the reduced as far as possible when the contaminants are strongly
occupational diseases due to exposure to the contaminant toxic and the operation time is long, for the sake of ensuring
for a longer time on a larger area. When the flow field is the operators’ health. Conversely, when the contaminants
disturbed by obstacles, the contaminants in Fig. 1(b) have a are less toxic and the operation time is short, it is not necessary
better chance of escaping into the occupied zone than those to reduce the NC-TZ, as a low NC-TZ requires high energy
in Fig. 1(a) (Robinson and Ingham 1996). consumption.
In this paper, the concept of a target zone is defined
to describe the contaminant diffusion region in an indoor 3 Characteristics and applicability of normalized
environment. The size of the target zone can be determined concentration in the target zone (NC-TZ)
according to the spatial concentration distributions of each
case. Most of the contaminants are located in the target zone, To reveal the characteristics of NC-TZ, contaminant con-
and the contaminant concentration gradient outside the zone centration distributions under a push–pull ventilation system,
is substantially zero. Under the consideration of the same as an example of a local ventilation system, with different
contaminant emission amount, the smaller the target zone flow rates and distances between the push and pull hoods
area is, the smaller the contaminant diffusion extent is. A small are analysed using a numerical technique. This paper also
target zone also causes a high probability for the operators to discusses cases with different obstacle positions in the flow
avoid that region. Based on the target zone, the normalized field to prove its applicability and compares these cases using
concentration in the target zone (NC-TZ) is proposed to CRE, NC-OZ and capture efficiency in different cases.
evaluate the control effect of the local ventilation system in
industrial buildings on IAQ. 3.1 Numerical technique
Suppose there is a local contaminant source in an
industrial building, and that a local ventilation system is FLUENT 6.3 as the simulation tool was employed here to
employed to remove the contaminant. The normalized study the NC-TZ. To guarantee the veracity of the results,
concentration in the target zone (NC-TZ) is then defined as the method based on realizable k–ε model (Lateb et al. 2013;
Chen 1995) and semi-implicit method for pressure linked
Cs - Ca
Ct = (1) equations (SIMPLE) algorithm (Li and Peter 2011) were
Cs - C validated with the experimental data from Ojima (2002), as
shown in Fig. 2. In this experiment, the open faces of the
where Ct is the NC-TZ and it is non-dimensional; Cs is the push unit and the pull unit were 1 m (W) × 0.5 m (H) and
contaminant concentration at the source (kg/m3); Ca is the 0.9 m (W) × 1 m (H), respectively, and the distance between
mean contaminant concentration in the target zone (kg/m3); these units was 2.5 m. The vertical distance of the centre line
and C is the mean contaminant concentration of the whole of the uniform flow was 1.25 m from the floor. An aluminium
room (kg/m3). The range of Ca is C to Cs. Thus, we can working table with dimensions of 0.7 m (W) × 0.9 m (D) ×
define the following properties for the NC-TZ: 0.8 m (H) was placed in the middle of the uniform flow field,
0 £ Ct £ 1 (2) exactly midway between the push unit and the pull unit. A
welding face shield was used to represent a human head and
Cs - Cs was placed about 1.6 m in height to represent slight slouching.
lim Ct = =0 (3)
Ca Cs
Cs - C Alcohol vapour was generated from liquid ethanol with
filtered dilution air at a flow rate of 20 L/min, which was placed
Cs - C in the centre of the working table. The sampling points of
lim C t = =1 (4)
Ca  C Cs - C the ethanol concentration were ① the breathing zone (45 cm
above the working table), ② directly above the outlet for
When the mean contaminant concentration in the target the ethanol vapour (17 cm above the work table and 50 cm
zone approaches the contaminant concentration at the source from the chest of the dummy worker) and ③–⑤ on the top
(Ct → 0), the control effect on IAQ of the local ventilation plate of the pull unit. The solver settings in the validation were
system increases gradually with the centralization of the almost the same as for the research cases. The differences
4 Wang et al. / Building Simulation

of 0.2 m, exactly midway between the push hood and the


pull hood. Formaldehyde was emitted from the upper surface
of the table at a flow rate of 0.02 kg/s, that is, a velocity of
0.022 m/s. A worker of 1.7 m tall was assumed to be standing
beside the table.
During the study, the species transport model, the
realizable k–ε model and the SIMPLE algorithm were used
to simulate the contaminant motion process. All of the cases
were conducted in a steady state and room temperature,
so thermal effects were not considered here. As the model
room is a section of a whole building, the windows and the
front and back walls in yellowish were set to pressure inlet,
and the push and pull openings were set to velocity inlet in
different cases. Other building envelopes were set to wall.
Fig. 2 Validation study of the contaminant concentration distri- The turbulent intensity was set to 10% (Cao and Meyers
bution in the flow field with a push–pull ventilation system, where 2015). The second-order upwind was chosen to prevent false
C1 is the experimental contaminant concentration (kg/m3) and C2 is diffusion phenomena.
the simulation contaminant concentration (kg/m3)
The mesh of the model room was generated by the
software GAMBIT 2.4.6. Mesh independence was studied for
between the validation study and the research cases were the
the basic model with five different grid cell numbers varying
size, grid and boundary conditions, which do not impact
from 0.3 million to 2.8 million, as shown in Fig. 4. The results
the validation for the realizable k–ε model and SIMPLE
of the formaldehyde concentration curves indicated that the
algorithm. The results indicated that the deviations in the
concentration curves at 0.3 million and 0.7 million differed
contaminant concentration with a supply velocity of 0.8 m/s
from the others in various degrees and that 1.2 million to
and no flow from behind at points ①, ②, ③, ④ and ⑤
2.8 million tended to be similar. Thus 1.2 million was used
were 12.75%, 5.95%, 15.23%, 18.39% and 14.52%, respectively.
to analyse the NC-TZ.
It was observed that the concordance is great.
In this investigation, a three-dimensional room ventilated
by the push–pull ventilation system was studied as a simplified 3.2 Results and discussion
industrial building model, as shown in Fig. 3. The push
According to the flow ratio method (Howell et al. 1985),
hood and the pull hood were set opposite each other so as
the supply flow rate Qs was 1559 m3/h, and the exhaust flow
to create uniform horizontal flow between them. The open
rate Qe was 9953 m3/h under the ultimate flow ratio when
faces of them were 1 m (W) × 1 m (H), and the whole area
the distance between the push hood and the pull hood (L)
of the pull hood with a flange was 1.4 m (W) × 1.4 m (H).
was 4 m. To analyse the NC-TZ characteristics, Qe ranged
The room was 12 m (L) × 10 m (W) × 5 m (H) with windows
over the floor at a height of 1 m. A formaldehyde working
table with dimensions of 0.8 m (L) × 0.8 m (W) × 0.5 m (H)
was placed in the middle of the uniform flow field at a height

Fig. 4 Contaminant distribution in front of the pull hood of 0.1 m


Fig. 3 The simulation model schematic diagram with five grid cell numbers
Wang et al. / Building Simulation 5

from 0 m3/h to 19906 m3/h, and L ranged from 2 m to 4 m, diffusion region is the maxima. Comparing all the planes
as presented in Table 1. The region of the target zone (RTZ) in around the whole room (for both the XOY-plane and ZOY-
each case was confirmed by the contaminant concentration plane), it is found that the contaminant diffusion regions
distribution, and the capture efficiency ηCE and the NC-TZ on both (XOY-plane, Z = 0.71 m) and (ZOY-plane, X = 5 m)
Ct are also listed in Table 1. shown in Fig. 5(a) are the maxima. (2) Determine the range
In actual industrial production process, because of the of diffusion of pollutants diffusion region along X, Y, Z axis
limitation of process conditions, obstacles, including operator on typical planes. In Case 12, the contaminant range along
and facility, may be found in the flow field frequently. For X, Y axis on (XOY-plane, Z = 0.71 m) is 4.65 – 5.35 m and
the NC-TZ application study, an obstacle with dimensions 7.60 – 10.10 m, respectively. And the contaminant range
of 0.6 m (L) × 0.2 m (W) × 1.7 m (H) at the different positions along Y, Z axis on (ZOY-plane, X = 5 m) is 7.60 – 10.10 m
was considered, and Fig. 7 shows the top view of each and 0.22 – 0.91 m, respectively. Finally,the range is RTZ which
position. The RTZ for Case 19 to Case 21 were confirmed is listed in Table 1 and the target zone is shown in Fig. 5(b).
by the contaminant concentration distribution. The ηCE, the The definitions of ηCE, ηCRE and Co are listed as follows:
contamination removal efficiency (CRE) ηCRE, the normalized ηCE is defined as the fraction of contaminants captured
concentration in the occupied zone (NC-OZ) Co and the by the exhaust hood(s):
NC-TZ Ct are also listed in Table 1.
The region of the target zone in this investigation Qe
ηCE = (5)
can be determined according to the spatial concentration Q
distributions. Considering the quantity of numerical cases,
a convenient method to determine the region of the target where Qe is the mass flow rate of the contaminant directly
zone RTZ was employed here and Case 12 was presented captured by the pull hood (kg/s) and Q is the total mass
as an example (Fig. 5): (1) Find the typical planes (for both flow rate of the contaminant released from the contaminant
the XOY-plane and ZOY-plane) on which the contaminant source (kg/s).

Table 1 The specifications and the results for each case


Qs Qe L ηCE ηCRE Co RTZ Ct
(m3/h) (m3/h) (m) (%) (%) (%) (%)
X(m) Y(m) Z(m)
Case 1 1559 0 4 0 100
Case 2 1559 332 4 28.945 3.50–6.00 7.60–10.10 0.00–1.60 96.062
Case 3 1559 664 4 53.927 4.20–5.80 7.60–10.10 0.00–1.40 94.404
Case 4 1559 995 4 68.831 4.40–5.60 7.60–10.10 0.00–1.35 92.919
Case 5 1559 1327 4 82.029 4.40–5.50 7.60–10.10 0.00–1.30 91.003
Case 6 1559 1669 4 90.208 4.50–5.50 7.60–10.10 0.00–1.25 90.079
Case 7 1559 3318 4 99.634 4.60–5.40 7.60–10.10 0.00–1.10 89.164
Case 8 1559 4977 4 100 4.65–5.35 7.60–10.10 0.05–1.10 87.484
Case 9 1559 6636 4 100 4.65–5.35 7.60–10.10 0.10–1.05 86.439
Case 10 1559 8294 4 100 4.65–5.35 7.60–10.10 0.15–1.05 85.495
Case 11 1559 9953 4 100 4.65–5.35 7.60–10.10 0.20–0.92 84.658
Case 12 1559 13271 4 100 4.65–5.35 7.60–10.10 0.22–0.91 84.102
Case 13 1559 16589 4 100 4.65–5.35 7.60–10.10 0.22–0.90 83.734
Case 14 1559 19906 4 100 4.65–5.35 7.60–10.10 0.23–0.90 83.411
Case 15 1559 9953 3.5 100 4.65–5.35 7.60–9.85 0.25–0.90 82.956
Case 16 1559 9953 3 100 4.65–5.35 7.60–9.60 0.25–0.85 81.313
Case 17 1559 9953 2.5 100 4.66–5.34 7.60–9.35 0.30–0.80 80.778
Case 18 1559 9953 2 100 4.67–5.33 7.60–9.10 0.35–0.75 79.115
Case 19 1559 9953 4 100 18.904 2.512 4.65–5.35 7.60–10.10 0.20–0.92 84.658
Case 20 1559 9953 4 100 18.335 2.505 4.62–5.38 7.60–10.10 0.05–1.68 95.652
Case 21 1559 9953 4 100 18.675 2.512 4.65–5.35 7.60–10.10 0.20–0.92 85.121
Note: The centre of the contaminant source is located at (5.00, 7.20, 0.45).
6 Wang et al. / Building Simulation

Fig. 5 The size and location of the target zone in Case 12. (a) Contaminant distributions and the target zone at the typical sections (Z =
0.71 m and X = 5 m); (b) schematic diagram of the target zone. 1-Push hood; 2-Contaminant source; 3-Pull hood; 4-Contaminant; ─ The
target zone

ηCRE reflects the capacity for removing contaminants, the contaminant had already been captured completely,
and the definition formula of ηCRE can be written as follows: and the ηCE reached the peak value of 100%. After this stage,
the ηCE remained unchanged, while the Ct continued to
Ce - C c
ηCRE = (6) decrease as Qe increased. These results indicate that the
C - Cc control effect of the push–pull ventilation system on the
contaminant remained unchanged, while the control effect
where Ce is the contaminant concentration of the exhaust
on IAQ still gradually increased as the exhaust flow rate
air (kg/m3); Cc is the contaminant concentration of the supply
increased. This phenomenon occurred because the increasing
air (kg/m3); and C is the mean contaminant concentration
exhaust flow rate still centralized the contaminant. Although
of the whole room (kg/m3).
this centralization could not affect the capture efficiency in
Co is proposed to evaluate the concentration degree of
this process, it reduced the range of the contaminant effect
the occupied zone, and the definition formula of Co can be
on the environment. As the velocity decreased rapidly in the
written as follows:
confluence flow field, the increasing exhaust flow rate had a
Cn - C c tiny impact on the flow field. Thus, the NC-TZ changed
Co = (7)
C - Cc more slowly in the process than before.
Data from Cases 11, 15–18 in Table 1 were plotted in the
where Cn is the mean contaminant concentration in the curve shown in Fig. 6(b). It could be observed that when L
occupied zone (kg/m3). Occupied zone is defined as the space decreased, ηCE remained unchanged, while the Ct continued
in the room below 2 m. to decrease. These results indicate that the control effect
of the push–pull ventilation system on the contaminant
3.2.1 Analysis of the characteristics of the normalized
remained unchanged, while the control effect on IAQ still
concentration in the target zone
gradually increased as the distance decreased. Similar to the
The data from Cases 1–14 in Table 1 were plotted in the curve exhaust flow rate, decreasing the distance also centralize the
shown in Fig. 6(a). When Qs remained at 1559 m3/h, the ηCE contaminant. Although this centralization could not affect
of the push–pull ventilation system increased as Qe increased the capture efficiency in this process, it reduced the range
before reaching 4977 m3/h. Simultaneously, the Ct decreased of the contaminant effect on the environment.
as Qe increased. These results show that the control effect of In conclusion, the capture efficiency is an index to
the push–pull ventilation system on the contaminant and evaluate the control effect on contaminants. Regardless of
IAQ increased gradually as the exhaust flow rate increased. the contaminant distribution in an indoor environment,
This increase was observed because the increase of the exhaust attention is paid to whether the contaminants have been
flow rate in this process could lead to the centralization of removed by the exhaust system. However, the NC-TZ is
the contaminant. It was also beneficial for the contaminant determined by the contaminant distribution in an indoor
capture of the exhaust flow. When Qe reached 4977 m3/h, environment. Even if the contaminants are captured
Wang et al. / Building Simulation 7

Fig. 6 Comparison of the capture efficiency and the NC-TZ


versus the exhaust flow rate and the distance between the push
and the pull hoods

completely, changes in the velocity field still can change the


contaminant concentration distribution and IAQ. Thus, the
NC-TZ is an index to evaluate the control effect on IAQ.
During the ventilation design of industrial buildings, both
the capture efficiency and the evaluation index for IAQ
should be considered, especially for buildings with a toxic Fig. 7 Contaminant distributions and the target zone at the section
of X = 5 m in Cases 19–21. ─ The target zone; ▄ Obstacle
contaminant source.

3.2.2 Analysis of the normalized concentration in the target


CRE and NC-OZ were not suitable completely to reflect the
zone application
differences of the control effects of the local ventilation
The data from Cases 19–21 in Table 1 revealed that the system in industrial buildings on IAQ for these different
ηCE was 100% for the different obstacle positions, that is, cases. The NC-TZ recognized that the Ct in Case 20 was
the control effect of the push–pull ventilation system on obviously greater than that in both Case 19 and Case 21. The
the contaminant in these three cases were the same and results show that in the case with the obstacle upstream of
satisfactory. the contaminant source, the control effect of the push–pull
However, Fig. 7 clearly shows that the contaminant ventilation system on environmental quality was inferior to
concentration distributions were different in these cases, that in the case with the obstacle downstream or to the side
while the contamination removal efficiency (CRE) ηCRE and of the contaminant source. Thus, NC-TZ could evaluate
the normalized concentration in the occupied zone (NC-OZ) the control effect on IAQ of the local ventilation system in
Co were nearly the same. This observation implies that the industrial buildings more exactly.
8 Wang et al. / Building Simulation

4 Conclusions Divine BJ, Hartman CM (2001). A cohort mortality study among


workers at a 1,3 butadiene facility. Chemico-Biological Interactions,
135–136: 535–553.
According to the characteristics of industrial buildings, such
Koh D-H, Kim T-W, Yoon Y-H, Shin K-S, Yoo S-W (2011).
as large spaces, centralized contaminant sources and strongly Lymphohematopoietic cancer mortality and morbidity of workers
toxic contaminants, the various existing zones and indices in a refinery/petrochemical complex in Korea. Safety and Health
cannot clearly reflect the control effect on indoor air quality at Work, 2: 26–33.
(IAQ) of the local ventilation systems in industrial buildings. Ellenbecker MJ, Gempel RF, Burgess WA (1983). Capture efficiency
The target zone is therefore defined to describe the contaminant of local exhaust ventilation systems. American Industrial Hygiene
diffusion region in an indoor environment. Based on the Association Journal, 44: 752–755.
target zone, the normalized concentration in the target zone Howell R, Hayashi T, Shibata M, Tsuji K (1985). Industrial Ventilation
and Air Conditioning. Boca Raton, FL, USA: CRC Press.
(NC-TZ) is proposed as an evaluation index. The following
Kikuchi S, Ito K, Kobayashi N (2003). Numerical analysis of ventilation
conclusions may be drawn from this study: effectiveness in occupied zone for various industrial ventilation
i. The NC-TZ is non-dimensional and it ranges from 0 systems. In: Proceedings of 7th International Symposium on
to 1 according to its definition. When the NC-TZ tends Ventilation for Contaminant Control, Sapporo, Japan, pp. 103–108.
toward 0, the control effect of the local ventilation system on Kikuchi S, Ito K, Kobayashi N (2004). Study on normalized concentration
IAQ is more satisfactory. When the NC-TZ tends toward 1, in an occupied zone in office space. In: Proceedings of 9th
the control effect on IAQ is less satisfactory. International Conference on Air Distribution in Rooms, Coimbra,
Portugal.
ii. When the capture efficiency is 100%, NC-TZ decreases
Lateb M, Masson C, Stathopoulos T, Bédard C (2013). Comparison
as the exhaust flow rate increases or as the distance between of various types of k–ε models for pollutant emissions around a
the push and pull hoods decreases. Therefore, under the same two-building configuration. Journal of Wind Engineering and
capture efficiency, changing the characteristics of the local Industrial Aerodynamics, 115: 9–21.
ventilation system can still result in a different control effect Li Y, Nielsen PV (2011). Commemorating 20 years of indoor air CFD
on IAQ. and ventilation research. Indoor Air, 21: 442–453.
iii. NC-TZ with an obstacle upstream of the contaminant Madsen U, Breum NO, Nielsen PV (1994). Local exhaust ventilation—A
numerical and experimental study of capture efficiency. Building
source is obviously greater than that with an obstacle
and Environment, 29: 319–323.
downstream or to the side of the contaminant source, while Makhoul A, Ghali K, Ghaddar N (2013). Desk fans for the control
the capture efficiency, the contamination removal efficiency of the convection flow around occupants using ceiling mounted
(CRE) and the normalized concentration in the occupied personalized ventilation. Building and Environment, 59: 336–348.
zone (NC-OZ) under these conditions are nearly the same. Ojima J (2002). Worker exposure due to reverse flow in push–pull
This result indicates that NC-TZ can evaluate the control ventilation and development of a reverse flow preventing system.
effect on IAQ of the local ventilation system in industrial Journal of Occupant Health, 44: 391–397.
building more exactly. Robinson M, Ingham DB (1996). Recommendations for the design of
push–pull ventilation systems for open surface tanks. Annals of
Occupational Hygiene, 40: 693–704.
Acknowledgements Sandberg M (1981). What is ventilation efficiency? Building and
Environment, 16: 123–135.
This work was supported by the National Science Fund for Sandberg M (1983). Ventilation efficiency as a guide to design. ASHRAE
Distinguished Young Scholars of China (No. 51425803) and Transactions, 89(2): 455–479.
the Key Program of the National Natural Science Foundation Sandberg M, Sjoberg M (1983). The use of moments for assessing air
of China (No. 51238010). quality in ventilated rooms. Building and Environment, 18:
181–197.
Sundell J (1996). What we know, and don’t know about sick building
References syndrome. ASHRAE Journal, 38(6): 51–57.
Wargocki P, Wyon DP, Baik YK (1999). Perceived air quality, sick
Brown M (2006). Making sense of modernity’s maladies: Health and building syndrome (SBS) symptoms and productivity in an office
disease in the industrial revolution. Endeavour, 30: 108–112. with two different pollution loads. Indoor Air, 9: 165–179.
Cao G, Sirén K, Kilpeläinen S (2014). Modelling and experimental Woods JE (1989). Cost avoidance and productivity in owning and
study of performance of the protected occupied zone ventilation. operating buildings. State of the Art Reviews in Occupational
Energy and Buildings, 68: 515–531. Medicine, 4: 753–770.
Cao S-J, Meyers J (2015). Fast prediction of indoor pollutant dispersion Xing H, Hatton A, Awbi HB (2001). A study of the air quality in the
based on reduced-order ventilation models. Building Simulation, breathing zone in a room with displacement ventilation. Building
8: 415–420. and Environment, 36: 809–820.
Chen Q (1995). Comparison of different k–ε models for indoor air flow Zhao B, Li X, Li D, Yang J (2003). Revised air-exchange efficiency
computations. Numerical Heat Transfer, Part B: Fundamentals, considering occupant distribution in ventilated room. Journal of
28: 353–369. the Air & Waste Management Association, 53: 759–763.

You might also like