Professional Documents
Culture Documents
DOI 10.1007/s12273-016-0295-2
Research Article
Yi Wang1 (), Yingxue Cao1, Bo Liu1, Jiaping Liu1, Yang Yang1, Qun Yu1,2
1. School of Environmental and Municipal Engineering, Xi'an University of Architecture and Technology, No. 13 Yanta RD., Xi'an, Shaanxi
710055, China
2. Shaanxi Architectural Design and Research Institute, China
Abstract Keywords
To evaluate the control effect on indoor air quality (IAQ) of the local ventilation systems in industrial evaluation index,
buildings with centralized contaminant sources, a new index, namely, normalized concentration local ventilation system,
in the target zone (NC-TZ), was proposed in this paper. According to theoretical analysis, NC-TZ is computational fluid dynamics (CFD),
non-dimensional and ranges from 0 to 1. When NC-TZ tends toward 0, the control effect of the indoor air quality (IAQ),
local ventilation system on IAQ is more satisfactory. When NC-TZ tends toward 1, the control effect contaminant concentration distribution
on IAQ is less satisfactory. The numerical simulation on a push–pull ventilation system with varying
exhaust flow rates and varying distances between push and pull hoods was performed. The
Article History
Received: 5 January 2016
results demonstrate that for the same capture efficiency, changing the local ventilation system
Revised: 12 April 2016
characteristics can change the control effect on the local environment. The results for obstacles at
Accepted: 18 April 2016
different positions also indicate that NC-TZ can clearly reflect the control effect on IAQ of the local
ventilation systems in industrial buildings.
© Tsinghua University Press and
Springer-Verlag Berlin Heidelberg
2016
Indoor/Outdoor Airflow
indoor environmental quality can also obviously influence if the capture efficiency is very high, the control effect of the
and Air Quality
operating efficiency (Sundell 1996; Wargocki et al. 1999). system on IAQ could not be considered simply as desirable
Woods (1989) conducted a telephone survey, and the results as that on contaminants. When contaminants emitted from
showed that 20% of operators complained that low indoor sources diffuse into the room extensively, for example, IAQ
air quality (IAQ) reduced their operating efficiency. Great may not meet the accepted standards and operators may
attention should be paid to IAQ in industrial buildings to suffer from occupational diseases due to their large exposure,
protect operators’ health and improve operating efficiency. even if contaminants can be captured eventually. Therefore,
Compared with civil buildings, local contaminant sources both the capture efficiency and the evaluation index for
can be found more frequently in industrial buildings. Thus, IAQ should be considered to reflect the comprehensive
compared with general ventilation that removes contaminants performance of the local ventilation system in industrial
from the whole room, the effect of local ventilation that buildings.
controls contaminants directly at their source is more desirable. For traditional evaluation indices, such as the “age” of
In existing studies, local ventilation system performance is the air, the air exchange efficiency (AEE) and contamination
E-mail: wangyi6920@126.com
2 Wang et al. / Building Simulation
removal efficiency (CRE), a ventilated room is usually regarded processes are usually strongly toxic, even if the mean
as a whole to evaluate IAQ. The “age” of the air, which is contaminant concentration value of the worker’s breathing
the time air remains in the room, is a quantitative index that zone is below the accepted value, there may still be a serious
measures the freshness level of indoor air. It is independent hidden health danger when other parts of the body are
of indoor contaminants and only relies on the airflow pattern exposed to the contaminants for a long period of time (Divine
(Sandberg and Sjoberg 1983). AEE is the ratio of the mean and Hartman 2001; Koh et al. 2011). Therefore, the various
age of the room air with displacement ventilation to that of existing zones and indices may not reflect the control effect
the room with the actual ventilation system. Similar to the on IAQ of local ventilation system in industrial buildings
“age” of the air, the air exchange efficiency is also a quantitative clearly.
index which can be used to evaluate the freshness level of In this study, the target zone was defined to reflect the
indoor air (Sandberg and Sjoberg 1983; Sandberg 1983). CRE, indoor contaminant diffusion region. A new index, namely,
also known as ventilation efficiency, is an index to judge the the normalized concentration in the target zone (NC-TZ),
ability of the supply air to remove indoor contaminants. Both was proposed to evaluate the control effect of local ventilation
the airflow pattern and the indoor contaminant sources systems on IAQ in industrial buildings. Several cases were
determine the CRE (Sandberg 1981). presented to demonstrate the new index.
However, environmental parameters in the actual
building, such as temperature, velocity and contaminant 2 Normalized concentration in the target zone
concentration, often present non-uniform distributions.
It is reasonable to divide the ventilated room into several The aim of a local ventilation system is to limit the con-
control zones to reduce building energy consumption and taminant to a local area in order to reduce its effect on the
improve IAQ. For decades, many researchers had made whole environment in an industrial building. In the actual
significant contributions to calculating these traditional production process, the following phenomenon is frequently
indices at different control zones and proposing new indices. observed: for the same contaminant species and the same
Makhoul et al. (2013) applied the index at the breathing zone contaminant emission concentration, different flow field
to evaluate different cases when they discussed the improved characteristics, such as the larger supply flow rate and
performance of a ceiling-mounted personalized ventilation exhaust flow rate in Fig. 1(a) than those in Fig. 1(b), may
nozzle assisted by small desk-mounted fans to reduce the result in a difference of these contaminant concentration
effect of a thermal plume generated by the occupant. Xing distributions, as shown in Fig. 1. For these distributions,
et al. (2001) analysed the relationship of the age of air the capture efficiency of the local ventilation system has
distribution, the air exchange efficiency and the ventilation already reached the peak of 100%. The mean contaminant
effectiveness at the breathing zone and the occupied zone
(below 2 m) in a room with displacement ventilation. Cao
et al. (2014) evaluated IAQ and human comfort at the
occupied zone when they developed theoretical models to
predict the performance of a new type of air distribution
method known as protected occupied zone ventilation. Zhao
et al. (2003) proposed occupied density (OD) and evaluated
the total influence of contaminants over a finite period of
time using the integrated accessibility of contaminant source
(IACS) as the index in which the indoor occupant distribution
is considered. Kikuchi et al. (2003, 2004) proposed the
normalized concentration in the occupied zone (NC-OZ)
and calculated this index for several different ventilation
systems.
The various zones and indices above were all proposed
based on the civil construction environment and contaminant
characteristics, while zones and indices only for industrial
buildings are infrequent. However, in consideration of
the large space and centralized contaminants in industrial
buildings, dividing the occupied zone by height only for IAQ Fig. 1 Contaminant concentration distribution schematic diagram
in industrial buildings is clearly not suitable. Simultaneously, of a local ventilation system under different conditions (─ occupied
as the centralized contaminants emitted during industrial zone; ─ breathing zone)
Wang et al. / Building Simulation 3
concentrations of the breathing zone and of the occupied contaminant. When the mean contaminant concentration
zone have no significant difference, that is, the above indices in the target zone approaches the mean contaminant con-
of each region are very similar. However, due to the different centration of the whole room (Ct→1), the control effect
contaminant concentration distributions, the control effect on IAQ decreases gradually with the decentralization of the
of the local ventilation system on IAQ shown in Fig. 1(a) is contaminant.
different from that shown in Fig. 1(b). Compared with Besides a high capture efficiency, the NC-TZ should be
Fig. 1(a), the workers in Fig. 1(b) are more vulnerable to the reduced as far as possible when the contaminants are strongly
occupational diseases due to exposure to the contaminant toxic and the operation time is long, for the sake of ensuring
for a longer time on a larger area. When the flow field is the operators’ health. Conversely, when the contaminants
disturbed by obstacles, the contaminants in Fig. 1(b) have a are less toxic and the operation time is short, it is not necessary
better chance of escaping into the occupied zone than those to reduce the NC-TZ, as a low NC-TZ requires high energy
in Fig. 1(a) (Robinson and Ingham 1996). consumption.
In this paper, the concept of a target zone is defined
to describe the contaminant diffusion region in an indoor 3 Characteristics and applicability of normalized
environment. The size of the target zone can be determined concentration in the target zone (NC-TZ)
according to the spatial concentration distributions of each
case. Most of the contaminants are located in the target zone, To reveal the characteristics of NC-TZ, contaminant con-
and the contaminant concentration gradient outside the zone centration distributions under a push–pull ventilation system,
is substantially zero. Under the consideration of the same as an example of a local ventilation system, with different
contaminant emission amount, the smaller the target zone flow rates and distances between the push and pull hoods
area is, the smaller the contaminant diffusion extent is. A small are analysed using a numerical technique. This paper also
target zone also causes a high probability for the operators to discusses cases with different obstacle positions in the flow
avoid that region. Based on the target zone, the normalized field to prove its applicability and compares these cases using
concentration in the target zone (NC-TZ) is proposed to CRE, NC-OZ and capture efficiency in different cases.
evaluate the control effect of the local ventilation system in
industrial buildings on IAQ. 3.1 Numerical technique
Suppose there is a local contaminant source in an
industrial building, and that a local ventilation system is FLUENT 6.3 as the simulation tool was employed here to
employed to remove the contaminant. The normalized study the NC-TZ. To guarantee the veracity of the results,
concentration in the target zone (NC-TZ) is then defined as the method based on realizable k–ε model (Lateb et al. 2013;
Chen 1995) and semi-implicit method for pressure linked
Cs - Ca
Ct = (1) equations (SIMPLE) algorithm (Li and Peter 2011) were
Cs - C validated with the experimental data from Ojima (2002), as
shown in Fig. 2. In this experiment, the open faces of the
where Ct is the NC-TZ and it is non-dimensional; Cs is the push unit and the pull unit were 1 m (W) × 0.5 m (H) and
contaminant concentration at the source (kg/m3); Ca is the 0.9 m (W) × 1 m (H), respectively, and the distance between
mean contaminant concentration in the target zone (kg/m3); these units was 2.5 m. The vertical distance of the centre line
and C is the mean contaminant concentration of the whole of the uniform flow was 1.25 m from the floor. An aluminium
room (kg/m3). The range of Ca is C to Cs. Thus, we can working table with dimensions of 0.7 m (W) × 0.9 m (D) ×
define the following properties for the NC-TZ: 0.8 m (H) was placed in the middle of the uniform flow field,
0 £ Ct £ 1 (2) exactly midway between the push unit and the pull unit. A
welding face shield was used to represent a human head and
Cs - Cs was placed about 1.6 m in height to represent slight slouching.
lim Ct = =0 (3)
Ca Cs
Cs - C Alcohol vapour was generated from liquid ethanol with
filtered dilution air at a flow rate of 20 L/min, which was placed
Cs - C in the centre of the working table. The sampling points of
lim C t = =1 (4)
Ca C Cs - C the ethanol concentration were ① the breathing zone (45 cm
above the working table), ② directly above the outlet for
When the mean contaminant concentration in the target the ethanol vapour (17 cm above the work table and 50 cm
zone approaches the contaminant concentration at the source from the chest of the dummy worker) and ③–⑤ on the top
(Ct → 0), the control effect on IAQ of the local ventilation plate of the pull unit. The solver settings in the validation were
system increases gradually with the centralization of the almost the same as for the research cases. The differences
4 Wang et al. / Building Simulation
from 0 m3/h to 19906 m3/h, and L ranged from 2 m to 4 m, diffusion region is the maxima. Comparing all the planes
as presented in Table 1. The region of the target zone (RTZ) in around the whole room (for both the XOY-plane and ZOY-
each case was confirmed by the contaminant concentration plane), it is found that the contaminant diffusion regions
distribution, and the capture efficiency ηCE and the NC-TZ on both (XOY-plane, Z = 0.71 m) and (ZOY-plane, X = 5 m)
Ct are also listed in Table 1. shown in Fig. 5(a) are the maxima. (2) Determine the range
In actual industrial production process, because of the of diffusion of pollutants diffusion region along X, Y, Z axis
limitation of process conditions, obstacles, including operator on typical planes. In Case 12, the contaminant range along
and facility, may be found in the flow field frequently. For X, Y axis on (XOY-plane, Z = 0.71 m) is 4.65 – 5.35 m and
the NC-TZ application study, an obstacle with dimensions 7.60 – 10.10 m, respectively. And the contaminant range
of 0.6 m (L) × 0.2 m (W) × 1.7 m (H) at the different positions along Y, Z axis on (ZOY-plane, X = 5 m) is 7.60 – 10.10 m
was considered, and Fig. 7 shows the top view of each and 0.22 – 0.91 m, respectively. Finally,the range is RTZ which
position. The RTZ for Case 19 to Case 21 were confirmed is listed in Table 1 and the target zone is shown in Fig. 5(b).
by the contaminant concentration distribution. The ηCE, the The definitions of ηCE, ηCRE and Co are listed as follows:
contamination removal efficiency (CRE) ηCRE, the normalized ηCE is defined as the fraction of contaminants captured
concentration in the occupied zone (NC-OZ) Co and the by the exhaust hood(s):
NC-TZ Ct are also listed in Table 1.
The region of the target zone in this investigation Qe
ηCE = (5)
can be determined according to the spatial concentration Q
distributions. Considering the quantity of numerical cases,
a convenient method to determine the region of the target where Qe is the mass flow rate of the contaminant directly
zone RTZ was employed here and Case 12 was presented captured by the pull hood (kg/s) and Q is the total mass
as an example (Fig. 5): (1) Find the typical planes (for both flow rate of the contaminant released from the contaminant
the XOY-plane and ZOY-plane) on which the contaminant source (kg/s).
Fig. 5 The size and location of the target zone in Case 12. (a) Contaminant distributions and the target zone at the typical sections (Z =
0.71 m and X = 5 m); (b) schematic diagram of the target zone. 1-Push hood; 2-Contaminant source; 3-Pull hood; 4-Contaminant; ─ The
target zone
ηCRE reflects the capacity for removing contaminants, the contaminant had already been captured completely,
and the definition formula of ηCRE can be written as follows: and the ηCE reached the peak value of 100%. After this stage,
the ηCE remained unchanged, while the Ct continued to
Ce - C c
ηCRE = (6) decrease as Qe increased. These results indicate that the
C - Cc control effect of the push–pull ventilation system on the
contaminant remained unchanged, while the control effect
where Ce is the contaminant concentration of the exhaust
on IAQ still gradually increased as the exhaust flow rate
air (kg/m3); Cc is the contaminant concentration of the supply
increased. This phenomenon occurred because the increasing
air (kg/m3); and C is the mean contaminant concentration
exhaust flow rate still centralized the contaminant. Although
of the whole room (kg/m3).
this centralization could not affect the capture efficiency in
Co is proposed to evaluate the concentration degree of
this process, it reduced the range of the contaminant effect
the occupied zone, and the definition formula of Co can be
on the environment. As the velocity decreased rapidly in the
written as follows:
confluence flow field, the increasing exhaust flow rate had a
Cn - C c tiny impact on the flow field. Thus, the NC-TZ changed
Co = (7)
C - Cc more slowly in the process than before.
Data from Cases 11, 15–18 in Table 1 were plotted in the
where Cn is the mean contaminant concentration in the curve shown in Fig. 6(b). It could be observed that when L
occupied zone (kg/m3). Occupied zone is defined as the space decreased, ηCE remained unchanged, while the Ct continued
in the room below 2 m. to decrease. These results indicate that the control effect
of the push–pull ventilation system on the contaminant
3.2.1 Analysis of the characteristics of the normalized
remained unchanged, while the control effect on IAQ still
concentration in the target zone
gradually increased as the distance decreased. Similar to the
The data from Cases 1–14 in Table 1 were plotted in the curve exhaust flow rate, decreasing the distance also centralize the
shown in Fig. 6(a). When Qs remained at 1559 m3/h, the ηCE contaminant. Although this centralization could not affect
of the push–pull ventilation system increased as Qe increased the capture efficiency in this process, it reduced the range
before reaching 4977 m3/h. Simultaneously, the Ct decreased of the contaminant effect on the environment.
as Qe increased. These results show that the control effect of In conclusion, the capture efficiency is an index to
the push–pull ventilation system on the contaminant and evaluate the control effect on contaminants. Regardless of
IAQ increased gradually as the exhaust flow rate increased. the contaminant distribution in an indoor environment,
This increase was observed because the increase of the exhaust attention is paid to whether the contaminants have been
flow rate in this process could lead to the centralization of removed by the exhaust system. However, the NC-TZ is
the contaminant. It was also beneficial for the contaminant determined by the contaminant distribution in an indoor
capture of the exhaust flow. When Qe reached 4977 m3/h, environment. Even if the contaminants are captured
Wang et al. / Building Simulation 7