You are on page 1of 4

PT PLN (PERSERO) KITSBS No.

Dokumen : DRD-SBLG-01
SEKTOR PEMBANGKITAN SEBALANG Tgl Terbit :
FORMULIR Revisi : 00

DESIGN REQUIREMENT DOCUMENT Halaman :

KKS Number : 181000TU10BCA10AA008


Description Asset : SBLG TU 10 CIRCUIT BREAKER #1 AIR COPRESSOR

1. Switchboard Rating
Standard : IEC62271-200
Rated voltage : 7.2 kV
Rated frequency : 50 Hz
Rated insulation levels (LIWV/ACWV) : 20kVp/kV
Rated normal current for main circuit : Busbar : 4kA; Incomers : 4kA; Feeders : 1250 A
Rated short time withstand for main : 40kA for 3s
and earthing circuit
Rated peak withstand current for : 125kAp
main and earthing circuits, Ip=2.5*Ik
Rated supply voltage for closing, : 220Vdc
tripping, control and indication
circuits
Rated voltage for 50Hz auxiliary : 220Vac (+-10%)
services (lighting,arrester,etc)

2. Switchboard Design Construction


Number of phases : 3
Busbar type : Cu
Insulating medium : Air
Busbar : Material Cu, 2x(100x10)mm2, insulated
Incomers : Material Cu, 2x(120x10)mm2, insulated
Feeders main circuit : Material Cu, 2x(80x10)mm2, insulated
Mean time between maintenance : 20 years

3. Switchboard testing
Partial discharge measurement : <10 pC

4. Circuit Breakers
Standard : IEC62271-200
Rated voltage : 7.2 kV
Rated frequency : 50 Hz
Rated insulation levels (LIWV/ACWV) : 20kVp/kV
Rated normal current for main circuit : Busbar : 4kA; Incomers : 4kA; Feeders : 1250 A
Rated short time withstand for main : 40kA for 3s
and earthing circuit

1
Rated peak withstand current for main : 125kAp
and earthing circuits, Ip=2.5*Ik
Rated supply voltage for closing, : 220Vdc
tripping, control and indication circuits

Rated voltage for 50Hz auxiliary : 220Vac (+-10%)


services (lighting,arrester,etc)
Rated short circuit making current (Ip) : 125 kA
Rated operating sequence O-t-CO-tCO : 0,3s
Rated time : Opening time (no load) : <50ms;
Max break time@full break capacity : <60ms
Closing time (no load): <70ms
Mech endurance : Feeders CBs : 20.000 times
Interupting medium : Vacuum
Method of closing : Motor-spring
Method of tripping : Shunt trip
Number of trip coils : 1
Rated voltage for closing and tripping : 220Vdc
Tolerance of tripping and closing : Trip operation : 70-110%;
supply voltage Close operation : 85-110%
Rated voltage for spring charging : 220Vdc
motor
Mechanical endurance class : Feeder CBs : 2000 ops

5. Earthing switches
Standard : IEC 60129
Number of poles : 3 poles
Rated normal current (minimum) : N/A
Rated short time withstand for : 40kA for 3s
earthing circuit
Rated short circuit making current for : 125kAp
earthing circuits, Ip=2.5*Ik
Earthing switch mech endurance class : 2000 ops
Earthing switch min electrical : 2 fault making ops
endurance
Operating handle : Disconnector : removable; earthing switch : fixed
Torque req for ops : 220 N.m
Interlock type between earthing : Mechanical
switch and CB
Earthing switch can be operated with : Yes
CB in test position and panel door
closed

6. Current transformer
Standard : IEC 60044-2
Type : LMZB1-10
Class : Indoor
Rated primary current : 100 A

2
Rated secondary current : 5A
Short time current rating : 40kA for 3s
Rated lightning impulse withstand : 60kV
voltage
Rated power frequency withstand : 20kV
voltage
Number of secondary windings : -
Ratio : 100/5/5A
Burden : 15/15VA
Accuracy class : 0.5/5P20

7. Voltage Transformer & HV Fuse (for incoming cubicle)


Standard : IEC 60044-2
Type : JDZXR-6C
Class : Indoor
Rated primary voltage : 6300/sqrt3
Rated secondary voltage : 100/sqrt3
Highest equipment voltage : 7,2kV
Rated lightning impulse withstand : 60kV
voltage
Rated power frequency withstand : 20kV
voltage
Number of secondary windings : 2
Ratio : 6300sqrt3/100sqrt3/100sqrt3
Burden : 60/50VA
Connection : STAR-STAR-TRIANGLE
Accuracy class : 0,5/3P
Withdrawable? : Yes
HV Fuse : Manufacture : Xian Zhenli
Type : XRNP3A-12/0,5
Rated voltage : 12kV
Rated current : 0,5A
Secondary winding cross sect area : 1.5mm2

Sebalang, 04 Juli 2018


SPV Enjiniring System Owner

Fachmi Wibowo Mochamad Umar

Asman Enjiniring

3
Muhammad Arif

You might also like