Performance Specification
`
Customer: Date: 2018-06-05
Proposal No.:
Email: Run No.: 2335843
Cust. Reference: Item No.:
Technician:
Model: GLP-009-M-4-NX-32 Units Required: 1

Intended End Use: Heat exchanger water/gliycol

Hot Side Cold Side


Fluid Name Water 40% PropGlycol (aq)

OPERATING DATA Inlet Outlet Inlet Outlet


Total Liquid flow m³/h 5,00 5,00 8,92 8,92 m³/h
Operating Temperature °C 26,00 16,00 6,00 12,00 °C
Pressure drop (allowed / calc.) kPa 30,00 / 4,06 30,00 / 15,94 kPa
Total Heat Exchanged kW 58
U-Service W/(m²·°C) 1 765
Total Heat Transfer Area m² 2,76
LMTD °C 11,89
Surface Margin % 20

FLUID PROPERTIES Inlet Outlet Inlet Outlet


Specific Gravity - 1,00 1,00 1,04 1,04
Specific Heat kJ/(kg·°C) 4,18 4,18 3,74 3,75
Thermal Conductivity W/(m·°C) 0,61 0,59 0,42 0,42
Viscosity (avg.) cP 0,87 1,11 7,61 5,76

CONNECTIONS
Position S4 S3 S2 S1
Type THREADED THREADED THREADED THREADED
Size R 1 1/2" R 1 1/2" R 1 1/2" R 1 1/2"
Material 1.4401 1.4401

CONSTRUCTION
Pass Arrangement 1 1
Channel Arrangement 6M+9L 6M+10L
A-Dimension / C-Dimension mm 92,8 / 380
Plate Material (Material/Thickness) 1.4401 / 0.4 mm
Gasket Material (Hot/Cold) NBR(Clip-On) NBR(Clip-On)
No. of Plates 32
Tightening Bolts/Nuts/Finish 8.8 / 8 / FZB
Pressure (design / test) MPa(g) 1,00 / 1,43 1,00 / 1,43
Temperature (min / design) °C -10,00 / 80,00 -10,00 / 80,00
Volume (per Side) l 3,30 3,52
Weight empty / flooded (per unit) kg 101 / 108
Pressure vessel code PED

Remarks:

The performance guarantee, if applicable, is based on the accuracy of the data presented above,
and the customers ability to supply product and operating conditions in conformance with the above.
Tranter International AB ul. Podolska 18 Nysa, 48-303
2018-06-05 Phn: 77 433 05 95 Fax: 77 433 05 95 Email: anna.krzeszowska@tranter.com 3.0.0.253
SUPERCHANGER ASSEMBLY
GLP-009-M-4-NX-32

Sizing Number
000000

Dimensions are for reference purposes only and are not to be used for construction.
Property of Tranter International AB and not to be reproduced without their consent nor used in any manner detrimental to the interest of Tranter International AB.