Storage tank coil sizing

MT-1/T2/T3

Tank working capacity KL 447.3


Diameter of tank M 7.5
Height of tank M 11.25
o
Tank operating temperature T C 110
Tank insulation thickness mm 100
o
Ambient temperature Ta C 20
Emmisivity Є 0.9
Specific heat of Bitumen Kcal/KgoC 0.45
Hot oil Kg/cm2g 3
o
Hot oil supply C 260
o
Hot oil return C 230
Specific heat of oil Kcal/KgoC 0.6
Hot oil density Kg/M3 800

A Heat loss calculations:

Assume Tank surface temperature Ts oC 22.559

Heat loss by conduction Q / A ) Cond = 0.09765 x ( T - Ts ) Btu/Ft2Hr , T ,Ts : oF

QCd = 15.37 Btu/Ft2Hr

Heat loss by radiation QR = 0.174 x Є x ( Ts 4 - Ta 4 ) x 10^-8 ; Ts , Ta : oR

QR = 4.30 Btu/Ft2Hr

Heat loss by free convection QFC= 0.7944 x ( 1 / ( Ts + Ta )/2 )^ 0.181 x ( Ts - Ta ) ^1.266 Btu/Ft2Hr

Ts , Ta : oR
= 1.76 Btu/Ft2Hr
Forced convection heat transfer QC= QFC x ( 1 + 1.277 V )^0.5 Btu/Ft2Hr

V: Avg wind velocity : 30 Ft/sec

Q C= 11.07 Btu/Ft2Hr

CHECK QCd = QR + QC
15.370 = 15.37

So Heat loss = 15.37 Btu/Ft2Hr

Now,Tank surface area = 353.3844 M2


= 3803.80 Ft2

Heat loss = 58459.81 Btu/Hr


14731.87 Kcal/Hr
Consider 50% extra margin in heat losses

Then Heat loss = 22097.81 Kcal/Hr

B Preheating case: Intial 90oC liquid is preheated to 110 deg C in 36 Hrs

Preheating load 111825.0 Kcal/Hr Not controlling case

C Temperature drop during night when plant/TFH is not in operation


Consider time during plant is shut during night 8 Hrs
Heat loss 22097.81 Kcal/Hr
Total heat loss during night 176782.47 Kcal
o
Temperature drop during night after 8 hrs 109.12 C
During day start up liquid is heated back to 110 deg C in about 100 min
So, Intial preheating load 106069.5 Kcal/Hr

Maximum heat load per tank 106069.5 Kcal/Hr

D Coil design
Total heat load 128167.29 Kcal/Hr
Hot oil requirement = 7120.40 Kg/Hr

Coil diameter : 45.81 mm

Select coil 50 NB x 1 Nos


OD 60.452 mm

Consider OHTC Kcal/M2HroC 20


o
LMTD C 134.443

Coil Surface area M2 47.67


Coil Length M 250.99
say 260 M
Coil size NB 50
Pitch mm ~150 to suit
Diameter of tank M 7.5
Storage tank coil sizing
T-4

Tank working capacity 135 KL


Diameter of tank M 4.4
Height of tank M 9.5
o
Tank operating temperature T C 135
Tank insulation thickness mm 100
o
Ambient temperature Ta C 20
Emmisivity Є 0.9
Hot oil Kg/cm2g 3
o
Hot oil supply C 260
o
Hot oil return C 250
Specific heat of oil Kcal/KgoC 0.6
Hot oil density Kg/M3 800
Operation : to heat maintain temperature at 135oC

A Heat loss calculations:

Assume Tank surface temperature Ts oC 23.144

Heat loss by conduction Q / A ) Cond = 0.09765 x ( T - Ts ) Btu/Ft2Hr , T ,Ts : oF

QCd = 19.66 Btu/Ft2Hr

Heat loss by radiation QR = 0.174 x Є x ( Ts 4 - Ta 4 ) x 10^-8 ; Ts , Ta : oR

QR = 5.30 Btu/Ft2Hr

Heat loss by free convection QFC= 0.7944 x ( 1 / ( Ts + Ta )/2 )^ 0.181 x ( Ts - Ta ) ^1.266 Btu/Ft2Hr

Ts , Ta : oR
= 2.29 Btu/Ft2Hr
Forced convection heat transfer QC= QFC x ( 1 + 1.277 V )^0.5 Btu/Ft2Hr

V: Avg wind velocity : 30 Ft/sec

Q C= 14.36 Btu/Ft2Hr

CHECK QCd = QR + QC
19.661 = 19.66

So Heat loss = 19.66 Btu/Ft2Hr

Now,Tank surface area = 161.7137729 M2


= 1740.67 Ft2

Heat loss = 34222.26 Btu/Hr


8624.01 Kcal/Hr
Consider 50% extra margin in heat losses

Then Heat loss = 12936.02 Kcal/Hr

Max heat load 12936.02 Kcal/Hr


Hot oil requirement = 2156.00 Kg/Hr

Coil diameter : 25.21 mm

Select coil 40 NB x 1 Nos


OD 48.26 mm
Consider OHTC Kcal/M2HroC 20
o
LMTD C 119.931

Coil Surface area M2 5.39


Coil Length M 35.57
say M 40
Coil NB 40
Pitch mm 125-150 to suit
Tank Diameter M 4.4
Storage tank coil sizing
T-5

Tank working capacity 135 KL


Diameter of tank M 4.4
Height of tank M 9.5
o
Tank operating temperature T C 150
Tank insulation thickness mm 100
o
Ambient temperature Ta C 20
Emmisivity Є 0.9
Hot oil Kg/cm2g 3
o
Hot oil supply C 260
o
Hot oil return C 250
Specific heat of oil Kcal/KgoC 0.6
Hot oil density Kg/M3 800
Operation : to heat maintain temperature at 135oC

A Heat loss calculations:

Assume Tank surface temperature Ts oC 23.484

Heat loss by conduction Q / A ) Cond = 0.09765 x ( T - Ts ) Btu/Ft2Hr , T ,Ts : oF

QCd = 22.24 Btu/Ft2Hr

Heat loss by radiation QR = 0.174 x Є x ( Ts 4 - Ta 4 ) x 10^-8 ; Ts , Ta : oR

QR = 5.89 Btu/Ft2Hr

Heat loss by free convection QFC= 0.7944 x ( 1 / ( Ts + Ta )/2 )^ 0.181 x ( Ts - Ta ) ^1.266 Btu/Ft2Hr

Ts , Ta : oR
= 2.61 Btu/Ft2Hr
Forced convection heat transfer QC= QFC x ( 1 + 1.277 V )^0.5 Btu/Ft2Hr

V: Avg wind velocity : 30 Ft/sec

Q C= 16.35 Btu/Ft2Hr

CHECK QCd = QR + QC
22.238 = 22.235

So Heat loss = 22.24 Btu/Ft2Hr

Now,Tank surface area = 161.7137729 M2


= 1740.67 Ft2

Heat loss = 38706.15 Btu/Hr


9753.95 Kcal/Hr
Consider 50% extra margin in heat losses

Then Heat loss = 14630.93 Kcal/Hr

Max heat load 14630.93 Kcal/Hr


Hot oil requirement = 2438.49 Kg/Hr

Coil diameter : 26.81 mm

Select coil 40 NB x 1 Nos


OD 48.26 mm
Consider OHTC Kcal/M2HroC 20
o
LMTD C 104.921

Coil Surface area M2 6.97


Coil Length M 45.99
say M 50
Coil NB 40
Pitch mm 125-150 to suit
Tank Diameter M 4.4
Storage tank coil sizing
T-6/7/8/9

Tank working capacity 100 KL


Diameter of tank M 4
Height of tank M 8.4
o
Tank operating temperature T C 185
Tank insulation thickness mm 100
o
Ambient temperature Ta C 20
Emmisivity Є 0.9
Hot oil Kg/cm2g 3
o
Hot oil supply C 260
o
Hot oil return C 230
Specific heat of oil Kcal/KgoC 0.6
Hot oil density Kg/M3 800

A Heat loss calculations:

Assume Tank surface temperature Ts oC 24.252

Heat loss by conduction Q / A ) Cond = 0.09765 x ( T - Ts ) Btu/Ft2Hr , T ,Ts : oF

QCd = 28.25 Btu/Ft2Hr

Heat loss by radiation QR = 0.174 x Є x ( Ts 4 - Ta 4 ) x 10^-8 ; Ts , Ta : oR

QR = 7.21 Btu/Ft2Hr

Heat loss by free convection QFC= 0.7944 x ( 1 / ( Ts + Ta )/2 )^ 0.181 x ( Ts - Ta ) ^1.266 Btu/Ft2Hr

Ts , Ta : oR
2
= 3.35 Btu/Ft Hr

Forced convection heat transfer QC= QFC x ( 1 + 1.277 V )^0.5 Btu/Ft2Hr


V: Avg wind velocity : 30 Ft/sec

Q C= 21.03 Btu/Ft2Hr

CHECK QCd = QR + QC
28.255 = 28.25

So Heat loss = 28.25 Btu/Ft2Hr

Now,Tank surface area = 130.6775132 M2


= 1406.60 Ft2

Heat loss = 39736.50 Btu/Hr


10013.60 Kcal/Hr
Consider 50% extra margin in heat losses

Then Heat loss = 15020.40 Kcal/Hr

Tank liquid is also heated from 135 deg C to 185 deg C in 6 Hrs

Preheating load 300000 Kcal/Hr


Total heat load 315020.40 Kcal/Hr

Total heat load 315020.40 Kcal/Hr


Hot oil requirement = 17501.13 Kg/Hr

Coil diameter : 71.82 mm

Select coil 50 NB x 2 Nos


OD 60.452 mm

Consider OHTC Kcal/M2HroC 100


o
LMTD C 84.600

Coil Surface area M2 37.236


Total Coil Length M 196.068
say 200 M
Coil size NB 50
No of coils 2
Length /coil M 100
Pitch 150 to suit
Tank diameter M 4
Storage tank coil sizing

T-10/11

Tank working capacity 50 KL


Diameter of tank M 3.3
Height of tank M 6.65
o
Tank operating temperature T C 185
Tank insulation thickness mm 100
o
Ambient temperature Ta C 20
Emmisivity Є 0.9
Hot oil Kg/cm2g 3
o
Hot oil supply C 260
o
Hot oil return C 230
Specific heat of oil Kcal/KgoC 0.6
Hot oil density Kg/M3 800

A Heat loss calculations:

Assume Tank surface temperature Ts oC 24.253

Heat loss by conduction Q / A ) Cond = 0.09765 x ( T - Ts ) Btu/Ft2Hr , T ,Ts : oF

QCd = 28.25 Btu/Ft2Hr

Heat loss by radiation QR = 0.174 x Є x ( Ts 4 - Ta 4 ) x 10^-8 ; Ts , Ta : oR

QR = 7.21 Btu/Ft2Hr

Heat loss by free convection QFC= 0.7944 x ( 1 / ( Ts + Ta )/2 )^ 0.181 x ( Ts - Ta ) ^1.266 Btu/Ft2Hr

Ts , Ta : oR
= 3.36 Btu/Ft2Hr
Forced convection heat transfer QC= QFC x ( 1 + 1.277 V )^0.5 Btu/Ft2Hr

V: Avg wind velocity : 30 Ft/sec

Q C= 21.04 Btu/Ft2Hr

CHECK QCd = QR + QC
28.255 = 28.25

So Heat loss = 28.25 Btu/Ft2Hr

Now,Tank surface area = 86.03955078 M2


= 926.12 Ft2

Heat loss = 26166.58 Btu/Hr


6593.98 Kcal/Hr
Consider 50% extra margin in heat losses

Then Heat loss = 9890.97 Kcal/Hr

Tank liquid is also heated from 135 deg C to 185 deg C in 6 Hrs

Preheating load 150000 Kcal/Hr


Total heat load 159890.97 Kcal/Hr
Consider OHTC 100 Kcal/M2HroC
o
LMTD 84.6 C

Hot oil requirement = 8882.83 Kg/Hr

Coil diameter : 51.17 mm

Select coil 50 NB x 1 Nos


OD 60.452 mm

Coil Surface area 18.90 M2


Coil Length 99.52 M
say 100 M
Coil dia 50 NB
Tank diameter 3.2 M
Pitch 150 mm to suit
Storage tank coil sizing

Energy balance across Premix tank : Assumed same as Gowahati


3
Premix working capacity 16 M
o
Bitumen at 135 C is fed to Premix tank where other RMs about 12%
o
are fed at room temp and whole mass is heated and maintained at 185 C in 2 Hrs
Preheating load 250400 Kcal/Hr
Assume 5% heat loss 12520 Kcal/Hr
Total heat load 262920 Kcal/Hr
Hot oil circulation 14606.67 Kg/Hr
3
Hot oil circulation 18.26 M /Hr
Hot oil supply line 56.82 mm
50 NB
o
LMTD 95.74 C
OHTC 100 Kcal/M2HroC
Coil surface area 27.462 M2
Select Coil 1.5"x 2 Nos
Coil OD 48.26 mm
Total coil length 181.13 M
Helical coil diameter 1.9 M
No of helical turns 30.35 Nos
Say 1.5" sch 40 x 1.7 M helical dia x 15 Turns /coil x 2 Nos coils