1. GENERAL 2.3.

2 THE STRUCTURE HAS BEEN DESIGNED TO WITHSTAND TSUNAMI LOAD WITH THE FOLLOWING DESIGN
PARAMETERS:
5.17. CONCRETE COVER FOR INTERIOR 400mm WALL AT CAISSON SIDE TO BE 80mm.
1.1. STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH PROJECT SPECIFICATIONS AND ALL OTHER CONTRACT
IMPORTANCE FACTOR = 1.25
DRAWINGS.
1.2. DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. ANY DISCREPANCIES SHALL BE BROUGHT TO THE
INUNDATION ELEVATION: 4.232m
HYDROSTATIC AND HYDRODYNAMIC FORCES IN TSUNAMI PER ASCE 07/SEZ-16 CHAPTER 6
6. CONCRETE AND REINFORCING
ATTENTION OF THE ENGINEER OF RECORD BEFORE PROCEEDING WITH THE AFFECTED PART OF THE WORK.
MODELING OF POTENTIAL TSUNAMI INUNDATION LIMITS & RUN-UP AND AECOM'S REPORT DATED JUNE 14,2013.
1.3. REFER TO THE PROCESS, ARCHITECTURAL, MECHANICAL AND ELECTRICAL DRAWINGS FOR LOCATIONS AND SIZES OF 6.1. CONCRETE SHALL CONFORM TO THE REQUIREMENTS OF CAN/CSA A23.1 AND THE REQUIREMENTS OF TABLE 2:
OPENINGS AND SLEEVES NOT SHOWN ON THE STRUCTURAL DRAWINGS. HOWEVER, NO STRUCTURAL MEMBER OR 6.2. OPENINGS, SLEEVES, EMBEDDED DUCTS:
2.4. SERVICEABILITY CRITERIA
COMPONENT SHALL BE CUT, NOTCHED OR OTHERWISE ALTERED UNLESS APPROVED IN WRITING BY THE ENGINEER OF
RECORD. 6.2.1. NO SLEEVES SHALL BE PLACE VERTICALLY OR HORIZONTALLY THROUGH BEAMS UNLESS REVIEWED AND
2.4.1. TYPICAL HORIZONTAL ELEMENTS (NOT SUPPORTING CLADDING) HAVE BEEN DESIGNED SO THAT THE
1.4. THE STRUCTURE IS DESIGNED TO BE SELF-SUPPORTING, STABLE AND CAPABLE OF WITHSTANDING THE LOADING NOTED APPROVED BY THE ENGINEER OF RECORD.
THEORETICAL DEFLECTIONS WILL NOT EXCEED THE VALUES INDICATED IN TABLE 1.
AFTER THE BUILDING IS COMPLETE. IT IS THE CONTRACTOR’S RESPONSIBILITY TO DETERMINE CONSTRUCTION 6.2.2. NO OPENINGS SHALL BE MADE IN FLAT PLATE OR FLAT SLAB COLUMN STRIPS EXCEPT AS SHOWN ON PLAN
2.4.2. THE STRUCTURE HAS BEEN DESIGNED ASSUMING THAT THE INSTALLATION OF NON-STRUCTURAL
PROCEDURES AND SEQUENCE TO ENSURE SAFETY OF THE BUILDING AND ITS COMPONENTS DURING CONSTRUCTION. OR TYPICAL DETAILS OR UNLESS REVIEWED AND APPROVED BY THE ENGINEER OF RECORD.
ELEMENTS SUCH AS CLADDING, MECHANICAL AND ELECTRICAL SERVICES AND THE LIKE, WILL NOT
THIS INCLUDES INSTALLATION OF OF NECESSARY SHORING, TEMPORARY BRACING, GUYS OR TIE-DOWNS. 6.2.3. WHEN TOTAL WIDTH OF PIPES OR DUCTS CAST INTO A SLAB EXCEED 300 mm IN 600 mm OF WIDTH THEN THE
COMMENCE UNTIL AT LEAST THE DESIGN STRENGTH OF THE CONCRETE HAS BEEN ACHIEVED AND AFTER
1.5. DURING CONSTRUCTION, IT IS THE CONTRACTORS RESPONSIBILITY TO VERIFY THAT DESIGN LIVE LOADS INDICATED IN CONTRACTOR SHALL ADD A LAYER OF 10@300 mm ON CENTER ABOVE AND PERPENDICULAR TO THE
THE REINFORCED CONCRETE SLAB SUPPORTING THE NON-STRUCTURAL ELEMENTS HAS BEEN POURED
THESE NOTES IS NOT EXCEEDED. WHERE NECESSARY, THESE LOADS SHALL BE REDUCED UNTIL MATERIALS REACH THEIR DUCT/PIPE RUNS EXTENDING 300 mm BEYOND THE LAST DUCT/PIPE ON EACH SIDE.
AND THE RESHORES REMOVED.
SPECIFIED DESIGN STRENGTH.
2.4.3. NON STRUCTURAL ELEMENTS SUCH AS CLADDING, MECHANICAL AND ELECTRICAL SERVICES AND
1.6. THE CONTRACT STRUCTURAL DRAWINGS AND SPECIFICATIONS REPRESENT THE FINISHED STRUCTURE, AND DO NOT 6.3. CONSTRUCTION JOINTS:
SUPPORTS, AND THE LIKE, MUST BE DESIGNED AND DETAILED TO ACCOMMODATE THE ANTICIPATED
INDICATE THE METHOD OR MEANS OF CONSTRUCTION. THE CONTRACTOR SHALL SUPERVISE AND DIRECT THE WORK AND
MOVEMENTS NOTED ABOVE.
SHALL BE SOLELY RESPONSIBLE FOR ALL CONSTRUCTION MEANS, METHODS, PROCEDURES, TECHNIQUES, SEQUENCE 6.3.1. HORIZONTAL CONSTRUCTION JOINTS SHALL NOT BE MADE IN BEAMS, UNLESS SHOWN OR APPROVED IN
2.4.4. THE BUILDING MOVEMENT SPECIFIED HEREIN SHOULD BE CONSIDERED BY THE CONTRACTOR IN THE
AND SAFETY. WRITING BY THE ENGINEER OF RECORD.
PERFORMANCE OF THE WORK.
1.7. DIMENSIONS ARE IN MILLIMETERS UNLESS NOTED OTHERWISE; ELEVATIONS ARE IN METERS UNLESS NOTED OTHERWISE. 6.3.2. VERTICAL CONSTRUCTION JOINTS SHALL NOT BE MADE AT MID-SPAN OF BEAMS OR SLABS, UNLESS SHOWN
1.8. DO NOT SCALE DRAWINGS. OR APPROVED IN WRITING BY THE ENGINEER OF RECORD.
1.9. THIS STRUCTURE HAS BEEN DESIGNATED AS A "POST-DISASTER" STRUCTURE ACCORDING TO THE BRITISH COLUMBIA 3. FOUNDATIONS
BUILDING CODE REQUIREMENTS. 6.4. FORMS FOR STRUCTURAL CONCRETE SHALL NOT BE STRIPPED UNTIL THE CONCRETE HAS REACHED AT LEAST 75% OF
3.1. PER GEOTECHNICAL INTERPRETIVE REPORT ISSUED BY WSP DATED MAY 14, 2018, THE SITE IS CLASSIFIED AS CLASS B FOR THE SPECIFIED COMPRESSIVE STRENGTH. EARLY REMOVAL NEED ENGINEER'S REVIEW AND APPROVAL.
SEISMIC CALCULATION WITH BEDROCK STRATA AND MASS CONCRETE FILL ABOVE BEDROCK TO SUPPORT THE BUILDING 6.5. SHORING AND RESHORING SHALL BE DESIGNED BY PROFESSIONAL ENGINEER LICENSED IN THE PROVINCE OF BRITISH
2. DESIGN DATA FOUNDATION. DEPTH OF BEDROCK HAS BEEN CONFIRMED BY 3 BOREHOLES AT EAST SIDE OF THE BUILDING FOOTPRINT COLUMBIA. SHORING AND RESHORING SHALL REMAIN IN PLACE UNTIL THE TOP SLAB HAS ACHIEVED 100% DESIGN
VARYING FROM 3.4M, 7.0M AND 11.0M BELOW THE SEA LEVEL FROM EXISTING BUILDING SIDE TO NORTH END OF THE NEW STRENGTH AND SHALL BE DESIGNED TO NOT EXCEED THE DESIGN LOAD FOR THE STRUCTURE.
2.1. CODES AND STANDARDS 6.6. REINFORCEMENT SHALL CONFORM TO CSA G30 SERIES WITH A YIELD STRENGTH OF 400 MPa. WELDED WIRE FABRIC
BUILDING.
SHALL HAVE A YIELD STRENGTH OF 386 MPa.
2.1.1. SEISMIC UPGRADING OF THE EXISTING BUILDING IS TO THE GENERAL INTENT OF THE 2012 BRITISH COLUMBIA
- BEARING CAPACITY OF THE BEDROCK: 5000 KPA IN SLS, 7500 KPA IN ULS. 6.7. REINFORCING STEEL IN CONTACT WITH SOIL OR EXPOSED TO WEATHER, SALT, SALT WATER, SEAWATER, OR SPRAY FROM
BUILDING CODE (BCBC) SUPPLEMENTED BY THE USERS GUIDE -NBC 2010 STRUCTURAL COMMENTARIES.
- EARTH PRESSURE COEFFICIENT: K0 = 0.470, KA = 0.28, KP = 3.25, KAE = 0.88, KPE = 3.15. THESE SOURCES WILL BE FUSION BONDED EPOXY-COATED AND SHALL CONFORM TO THE REQUIREMENTS OF ASTM
2.1.2. ADDITION HAS BEEN DESIGNED IN ACCORDANCE WITH THE REQUIREMENTS OF THE 2012 BRITISH COLUMBIA
- DYNAMIC EARTH PRESSURE IN SEISMIC ON BUILDING WEST WALL WILL BE 116.7 KPA PER TABLE 5 OF THE REPORT. A775M. FOR DETAILS REFER TO DWGS AND CORROSION PROTECTION REPORT.
BUILDING CODE (BCBC).
- FRICTION COEFFICIENT BETWEEN MAT FOUNDATION AND MASS CONCRETE/BEDROCK: 0.5. 6.8. PROVIDE WELDED WIRE FABRIC IN FLAT SHEETS ONLY. LAP SPLICES SHALL BE A MINIMUM OF 500 mm FOR WWF 152 x 152,
2.1.3. ALL REINFORCED CONCRETE ELEMENTS HAVE BEEN DESIGNED IN ACCORDANCE WITH CAN/CSA-A23.3-14
- FRICTION COEFFICIENT BETWEEN FOUNDATION WALL AND SOIL: 0.3. 350 mm FOR WWF 102 x102 AND 250 mm FOR WWF 51 x 51.
(R2010) - DESIGN OF CONCRETE STRUCTURES.
- AVERAGE FRICTION ANGLE FOR THE SOIL: 32 DEGREE. 6.9. THE MINIMUM COVER TO MILD REINFORCEMENT SHALL BE AS NOTED IN CSA/CAN A23.1 ACCORDING TO THE SPECIFIED
2.1.4. ALL STRUCTURAL STEEL ELEMENTS HAVE BEEN DESIGNED IN ACCORDANCE WITH CAN/CSA-S16-14 – LIMIT
- AVERAGE UNIT WEIGHT OF SOIL ON SITE: 19KN/CU.M. CONCRETE MIXES IN TABLE 2.
STATES DESIGN OF STEEL STRUCTURES.
- ULTIMATE PULLOUT RESISTANCE OF 900MM DIAMETER KING PILE SOCKETED IN BEDROCK: 4240 KN/M. 6.10. ALL BARS SHALL HAVE A MINIMUM EMBEDMENT EQUIVALENT TO THE STRAIGHT TENSION EMBEDMENT LENGTH
2.1.5. ALL STRUCTURAL ALUMINUM ELEMENTS HAVE BEEN DESIGNED IN ACCORDANCE WITH
- HYDROSTATIC AND HYDRODYNAMIC PRESSURES TO BUILDING STRUCTURAL WALL SHALL BE CONSIDERED BASED CORRESPONDING TO THE SIZE OF THE BAR. DOWELS FROM WALLS TO SLABS SHALL HAVE A MINIMUM EMBEDMENT OF 600
CAN/CSA-S157-05/S157.1-05 (R2010) – STRENGTH DESIGN IN ALUMINUM.
ON TSUNAMI CONDITION. mm INTO WALLS AND SLABS UNLESS OTHERWISE NOTED OR SHOWN.
2.1.6. ALL STRUCTURAL MASONRY ELEMENTS HAVE BEEN DESIGNED IN ACCORDANCE WITH CSA-S304-04 (R2010)
6.11. PROVIDE DOWELS TO WALLS SIMILAR IN NUMBER, SIZE AND SPACING TO THE VERTICAL STEEL IN THE WALL ABOVE
– DESIGN OF MASONRY STRUCTURES. DURING CONSTRUCTION, GEOTECHNICAL ENGINEER WILL VISIT SITE TO CONFIRM THE GEOTECHNICAL INFORMATION UNLESS OTHERWISE NOTED OR SHOWN.
2.1.6 ALL WATER RETAINING CONCRETE STRUCTURES TO BE DESIGNED IN ACCORDANCE WITH ACI 350 CODE AFTER BEING EXCAVATED TO FOUNDED LEVEL. 6.12. SPLICE BARS ACCORDING TO THE REINFORCING DETAILS SHOWN. DO NOT PROVIDE ALTERNATIVE SPLICE LOCATIONS
REQUIREMENTS FOR ENVIRONMENTAL ENGINEERING CONCRETE STRUCTURES.
UNLESS REVIEWED AND APPROVED BY THE ENGINEER OF RECORD. WHERE NO SPLICE LENGTH SHOWN, PROVIDE CLASS B
2.1.7 ALL CONCRETE STRUCTURE CRACK WIDTH CONTROL TO BE DESIGNED IN ACCORDANCE TO ACI 224, 3.2. BEAR EXTERIOR FOOTINGS AND OTHER FOOTINGS EXPOSED TO FROST A MINIMUM OF 500 mm BELOW THE LOWEST TENSION SPLICE OR STANDARD HOOK AS INDICATED. FOLLOW CSA STANDARDS FOR TSB AND STD HOOK LENGTHS.
CONTROL OF CRACKING IN CONCRETE STRUCTURES. GRADE. 6.13. DO NOT DRIVE OR FORCE REBAR INTO FRESH CONCRETE. ALL REBAR TO BE SECURELY FASTENED PRIOR TO PLACING
2.1.8 ACI 350.3 "SEISMIC DESIGN FOR LIQUID-CONTAINING CONCRETE STRUCTURES". 3.3. THE LINE OF SLOPE BETWEEN ADJACENT FOOTINGS OR EXCAVATIONS OR ALONG STEPPED FOOTINGS SHALL NOT EXCEED CONCRETE.
A RISE OF 7 IN A RUN OF 10. 6.14. ALL HARD EDGES OF CAST IN PLACE CONCRETE TO HAVE 25mm CHAMFERED EDGE.
2.2 DESIGN LOADS 3.4. TEMPORARY EXCAVATION SUPPORT SYSTEM IS TO BE DESIGNED BY SHORING ENGINEER RETAINED BY THE CONTRACTOR 6.15. PVC WATERSTOPS SHOWN IN SECTION TO BE TIED TO REBAR CAGE EVERY 300mm. USE MANUFACTURER'S RECOMMENDED
AND SHALL BE INSTALLED IN ACCORDANCE WITH THE GEOTECHNICAL RECOMMENDATIONS AND INSTALLATION ANCHORING CLIPS. DO NOT PUNCTURE PVC WATERSTOP.
2.2.1 LIVE LOAD PROCEDURES CONTAINED IN THE GEOTECHNICAL REPORT.
HEADWORK/ODOUR CONTROL ROOM = 15kPa
PUMP ROOM = 15kPa 7. CHEMICAL/ADHESIVE AND MECHANICAL ANCHORS
ELECTRICAL/MECHANICAL ROOM = 6kPa 4. FOUNDATION WALLS
STAIRS = 5kPa 7.1. CHEMICAL/ADHESIVE ANCHORS SHALL BE HILTI HY-200 ADHESIVE SYSTEM, UNLESS NOTED OTHERWISE.
MEZZANINE = 10kPa 4.1. DO NOT BACKFILL AGAINST WALLS RETAINING EARTH UNTIL THE BRACING SLABS HAVE BEEN CAST AND ATTAINED 100% OF 7.2. MECHANICAL ANCHORS SHALL BE HILTI KWIK-BOLT III, UNLESS NOTED OTHERWISE.
SITE ROADS AND ACCESS = 12kPa , CL800 ITS DESIGN STRENGTH. 7.3. WHERE DETAILS NOTE EPOXY GROUT, USE HILTI HY-200 ADHESIVE SYSTEM.
ROOF LOAD: 12KPa CL800 (80 TONNE) TRUCK 4.2. WHERE THE SLAB AT GRADE IS USED TO TIE THE TOP OF A WALL RETAINING EARTH, THAT WALL SHALL BE ADEQUATELY 7.4. ALTERNATIVE ENGINEER APPROVED ANCHOR TYPES ARE PERMITTED. SUBMIT PROPOSED ANCHOR TYPE AND
RETAINING WALL SURCHARGE = 15kPa SHORED UNTIL THE SLAB ABOVE GRADE HAS BEEN CAST AND ATTAINED 100% OF ITS DESIGN STRENGTH. MANUFACUTRE’S PUBLISHED DATA INCLUDING LOAD CAPACITY, EDGE DISTANCE REQUIREMENTS AND SPACING
STRUCTURE PARTIALLY BURIED IN GROUND = 1m FILL EQUIVALENT LOAD 4.3. CARRY OUT BACKFILLING AGAINST FOUNDATION WALLS WHERE THERE IS GRADE ON BOTH SIDES IN SUCH A MANNER REQUIREMENTS FOR APPROVAL PRIOR TO USING ALTERNATIVE ANCHOR.
THAT THE LEVEL OF BACKFILLING ON ONE SIDE OF THE WALL IS NEVER MORE THAN 500 mm DIFFERENT FROM THE LEVEL 7.5. INSTALL ANCHORS IN ACCORDANCE WITH MANUFACTURERS INSTRUCTIONS.
2.2.2 SNOW LOAD ON THE OTHER SIDE OF THE WALL. 7.6. THE MANUFACTURER’S REPRESENTATIVE SHALL TRAIN INSTALLERS.
Is = 1.25 (ULS)
Is = 0.9 (SLS)
Ss = 1.1 kPa 5. CAISSON WALL 8. MASONRY
Sr = 0.2 kPa
5.1. REFER TO PROJECT SPECIFICATIONS AND DESIGN DRAWINGS FOR ALL REQUIREMENTS OF CAISSON WALL 8.1. CONCRETE MASONRY UNITS SHALL CONFORM TO CAN3-A165 SERIES, 15 MPa (2175 PSI) MINIMUM COMPRESSIVE.
S = 1.35 kPa (ULS)
CONSTRUCTION. 8.2. MORTAR SHALL CONFORM TO CSA A179 TYPE "S" FOR LOAD BEARING WALLS.
Cb = 0.8
5.2. SUPPLY AND INSTALL NECESSARY WORK FORCE AND EQUIPMENTS TO CARRY OUT THE INSTALLATION OF SECANT WALL 8.3. MASONRY GROUT SHALL CONFORM TO CSA A179, 15 MPa (2175 PSI) MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS, 250
Cw=1.0
CONSTRUCTION AS SHOWN ON THE CONTRACT DOCUMENT. THE CUT OFF DEPTH OF SECANT WALL TO BE VARIED WITH mm (10") SLUMP, MAXIMUM AGGREGATE SIZE 10 mm (3/8").
Cs = 1.0
MIN. SOCKET DEPTH OF 2.0M FROM TOP OF ROCK, REFER TO GEOTECHNICAL INVESTIGATION REPORT AND SUBSEQUENT 8.4. ALL MASONRY CONSTRUCTION SHALL CONFORM TO CSA-A371 MASONRY CONSTRUCTION FOR BUILDINGS.
Ca = 1.0
CORRESPONDENCE. 8.5. WHERE DOWELS, ANCHOR RODS, ETC. ARE SHOWN PROJECTING INTO MASONRY, BUILD THESE TIGHTLY INTO MASONRY
5.3. REFER TO GEOTECHNICAL REPORT FOR DEWATERING RECOMMENDATIONS. CONTRACTOR IS RESPONSIBLE FOR THE VOIDS WITH MASONRY GROUT.
2.3 LATERAL LOADS
METHOD OF DEWATERING . CONTRACTOR IS TO NOTE THE DAILY DEWATERING LIMITATION BASED ON REGULATORY 8.6. BENEATH STEEL AND CONCRETE BEAMS, JOISTS AND TRUSSES PROVIDE A MINIMUM DEPTH OF 400 mm (16") 100% SOLID
AGENCIES IN JURISDICTION. MASONRY UNITS PROJECTING A MINIMUM OF 200 mm (8") BEYOND THE EDGES OF BEARING PLATES, UNLESS OTHERWISE
2.3.1 THE STRUCTURE HAS BEEN DESIGNED TO RESIST THE LATERAL LOADS DUE TO EARTHQUAKE AND WIND IN
5.4. REFER TO SECANT WALL AND STRUCTURAL WALL DETAILS AND NOTES FOR THE CONSTRUCTION OF THE EXTERIOR NOTED OR SHOWN.
ACCORDANCE WITH BRITISH COLUMBIA BUILDING CODE. THE DESIGN PARAMETERS FOR WIND AND
WALLS. 8.7. PROVIDE A MINIMUM LENGTH OF 200 mm (8") AND A MINIMUM DEPTH OF 200 mm (8") OF 100% SOLID MASONRY UNITS FOR
EARTHQUAKE ARE AS NOTED BELOW:
5.5. DO NOT REMOVE THE TEMPORARY LATERAL SHORING UNTIL THE HORIZONTAL BEAMS, SLABS, AND BUILDING WALLS HAVE STEEL, CONCRETE OR REINFORCED MASONRY LINTELS.
ATTAINED THE FULL SPECIFIED DESIGN CONCRETE STRENGTH. 8.8. WHERE A CHANGE IN THICKNESS OF MASONRY OCCURS, GROUT SOLID, OR USE SOLID UNITS FOR A HEIGHT OF 200 mm (8")
a) WIND LOADS
5.6. THE MAXIMUM PERMITTED DEVIATION OF THE PILE CENTER FROM THE CENTER POINT SHOWN ON THE SETTING OUT THE THICKER PORTION AT THE CHANGE.
q= 0.57 kPa 1/50 AVERAGE HOURLY WIND PRESSURE
DRAWINGS SHALL BE 25 MM IN ANY DIRECTION. 8.9. BUILD MASONRY TIGHTLY INTO WEBS OF ALL WALL BEARING STEEL BEAMS AT THEIR POINTS OF BEARING.
Iw = 1.25
5.7. THE MAXIMUM PERMITTED DEVIATION OF THE FINISHED PILE FROM THE VERTICAL AT ANY LEVEL IS 1 IN 200. THE 8.10. MAINTAIN SUPPORT OF MASONRY LINTELS FOR A MINIMUM OF SEVEN DAYS OR UNTIL SUFFICIENT STRENGTH IS GAINED TO
IMPORTANCE CATEGORY: POST-DISASTER
CONTRACTOR SHALL DEMONSTRATE TO THE SATISFACTION OF ENGINEER THE PILE VERTICALITY IS WITHIN THE SAFELY SUPPORT LOADS IMPOSED.
ALLOWABLE TOLERANCE. 8.11. FOR NON-LOAD BEARING MASONRY PROVIDE THE FOLLOWING MINIMUM REINFORCEMENT: 15M @ 600mm
b) EARTHQUAKE LOADS
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_-Sheet - S-00A.dwg

5.8. SHOULD PILES BE INSTALLED OUTSIDE THESE TOLERANCES AFFECTING THE DESIGN AND APPEARANCE OF THE 8.12. PROVIDE COLD WEATHER PROTECTION AS REQUIRED BY CSA A371-04 "MASONRY CONSTRUCTION FOR BUILDINGS".
Ie = 1.5
STRUCTURE, THE CONTRACTOR SHALL PROPOSE AND CARRY OUT IMMEDIATE REMEDIAL MEASURE TO THE APPROVAL OF 8.13. REINFORCED MASONRY:
SEISMIC HAZARD PARAMETERS FOR LOCATION: VICTORIA, BC.
Sa(0.2) = 1.2, Sa(0.5) = 0.82, Sa(1.0) = 0.38, Sa(2.0) = 0.18 THE ENGINEER AT HIS OWN TIME AND COST.
5.9. INTERIOR 400mm THK. STRUCTURAL WALL IS TO BE 35MPa CONCRETE, LOW PERMEABLE CONCRETE WITH CRYSTALLINE 8.13.1. CELLS TO BE REINFORCED SHALL BE KEPT CLEAN OF MORTAR.
PGA = 0.61
WATERPROOFING ADMIXTURE OR EQUIVALENT FOR WATERPROOFING PURPOSES. 8.13.2. PROVIDE MINIMUM 1-20M VERTICALS FULL HEIGHT AT ALL WALL ENDS, CORNERS, INTERSECTIONS AND
SITE CLASSIFICATION FOR SEISMIC SITE RESPONSE:
5.10. THE SECANT/STRUCTURAL WALLS FORM PART OF PERMANENT STRUCTURE AND ARE DESIGNED IN ACCORDANCE WITH OPENINGS UNLESS OTHERWISE NOTED ON DRAWINGS.
CLASS = B
BCBC. 8.13.3. PROVIDE 1-20M VERTICAL FULL HEIGHT EACH SIDE OF CONTROL JOINTS.
SEISMIC RESPONSE INDEX:
5.11. MIN. OVERLAP BETWEEN THE SECANT CAISSON AND THE PRIMARY CAISSONS SHALL BE 150mm. 8.13.4. PROVIDE DOWELS FROM CONCRETE SLABS AND/OR WALLS BELOW TO MATCH VERTICAL REINFORCEMENT
IeFaSa(0.2) = 1.8
IN WALL.
5.12. THE FINAL OVERLAP SHALL BE DETERMINED BY THE FOUNDATION SPECIALITY CONTRACTOR.
8.13.5. PROVIDE MINIMUM BAR LAPS OF 300 mm FOR WIRE LADDER OR MESH, 450 mm FOR 10M BARS, 600 mm FOR
SEISMIC FORCE RESISTING SYSTEM (SFRS) FOR THE BUILDING CONSISTS OF MODERATELY DUCTILE SHEAR 5.13. ALL W610 STEEL COLUMNS MUST BE PROTECTED FROM CORROSION AND EXTEND ALL THE WAY DOWN TO SOUND
BEDROCK ELEVATION AS PER GEOTECHNICAL ENGINEER RECOMMENDATIONS. 15M BARS, 900 mm FOR 20M BARS, UNLESS NOTED OTHERWISE.
WALLS:
8.13.6. PROVIDE CLEANOUTS AT THE BASE OF THE WALL TO VERIFY PROPER PLACEMENT OF GROUT AND PLACE
Rd = 2.0 5.14. BOTTOM OF W610 STEEL COLUMN SHALL BE SOCKETED INTO SOUND BEDROCK AT LEAST 2.0m DEEP TO ACHIEVE AT LEAST
GROUT IN MAXIMUM 2000 mm (6'-6") LIFTS. IF NO CLEANOUT PROVIDED, POUR HEIGHT LIMITED TO 1200 mm
Ro = 1.4 1.0m FULLY PULLOUT RESISTANCE.
5.15. SOCKETED STEEL COLUMN SHALL BE FULLY GROUTED INTO SOUND BEDROCK BY GROUT/CONCRETE\HAVING UNCONFINED (4'-0").
8.13.7. WHEN GROUTING IS STOPPED FOR A PERIOD OF ONE HOUR OR LONGER EXCEPT AT THE TOP OF THE WALL,
COMPRESSIVE STRENGTH EQUAL OR GREATER THAN 35MPa PER GEOTECHNICAL REPORT.
FORM CONSTRUCTION JOINT BY STOPPING THE GROUT POUR MINIMUM 25 mm (1") BELOW THE UPPERMOST
5.16. TOP OF W610 STEEL COLUMN TO EXTEND TO TOP OF CAISSON WALL CAP BEAM WITH 100mm CONCRETE COVER SEE
UNIT.
DETAILS.
DATE: 24/09/2018 10:00:02 AM, Rani, Sushma

8.13.8. EMBEDDED ITEMS ARE NOT TO INTERFERE WITH THE INTEGRITY OF THE MASONRY WALL OR LOCATION OF

MR 24/09/2018 9 ISSUED FOR CONSTRUCTION


VERIFY SCALES
MR 19/07/2018 8 REISSUED FOR CONSTRUCTION - CAISSON WALL
DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM
BAR IS 20mm ON MR 15/06/2018 7 ISSUED FOR 100% DESIGN SUBMISSION SURVEYED
MR
CLOVER POINT PUMP STATION
C:\Users\ranis\Desktop\STAMP.JPG 16/05/2018 6 ISSUED FOR CONSTRUCTION - CAISSON WALL
20mm MR 26/03/2018 5 ISSUED FOR PRE-CONSTRUCTION REVIEW - CAISSON WALL DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 23/03/2018 4 ISSUED FOR 90% DESIGN SUBMISSION SCALE
CHECKED R.L. GENERAL NOTES
IF NOT 20mm ON HORIZONTAL -
THIS SHEET, ADJUST MR 19/01/2018 3 ISSUED FOR 50% DESIGN SUBMISSION
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY APPROVED
SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - NUMBER CPS-100 NUMBER CP-C01- S-00A 9 OF
REINFORCEMENT. PROVIDE FULLY GROUTED LINTEL BEAM FOR CONDUITS AND PIPES RUNNING
HORIZONTALLY WITHIN WALL. 12. PROVISIONS FOR FUTURE EXPANSION STRUCTURAL SYMBOLS 13. ABBREVIATIONS
8.13.9. PROVIDE ADEQUATE TEMPORARY BRACING TO MASONRY WALLS UNTIL ROOF DECK IS INSTALLED AND CAN & AND LT WT LIGHT WEIGHT
DEVELOP ADEQUATE DIAPHRAGM ACTION. 12.1. NO PROVISIONS HAVE BEEN MADE FOR VERTICAL OR HORIZONTAL EXPANSION. T/O CONCRETE @ AT m METRE
FINISH ELEVATION
± PLUS OR MINUS m² SQUARE METRE
8.14. PROVIDE DOVETAIL ANCHORS AT 16" C/C, UNLESS NOTED OTHERWISE, WHERE MASONRY WALLS ABUT CONCRETE SURFACES. Ø, DIA DIAMETER MAX MAXIMUM
CL CENTER LINE AB ANCHOR BOLT MC MOMENT CONNECTION
13. REMOVALS NOTES Ø DIAMETER
ABUT
ADD'L
ABUTMENT
ADDITIONAL
MECH
MEZZ
MECHANICAL
MEZZANINE
9. STRUCTURAL STEEL AEC ARCH EXPOSED CONCRETE MF MOMENT FRAME
13.1 CONTRACTOR SHALL VERIFY EXISTING SITE CONDITIONS AND SCOPE OF WORK PRIOR TO COMMENCEMENT OF AESS ARCH EXPOSED STRUCT STEEL Mf FACTORED MOMENT
9.1. STRUCTURAL WIDE FLANGE SHAPES (W) SHALL CONFORM TO CAN/CSA-G40.20/G40.21 GRADE 350W OR ASTM AFF ABOVE FINISHED FLOOR
REMOVALS. CONTRACTOR SHALL ALSO MAKE SURE THAT REMOVALS DOES NOT ENDANGER REMAINING CONCRETE
MFR MANUFACTURER
ALT ALTERNATE MIN MINIMUM
A36/A992 GRADE 50 (345 MPa). THIS INCLUDES W610 SECTION FOR KING PILE FOR CAISSON WALLS. STRUCTURES. ARCH ARCHITECTURAL MISC MISCELLANEOUS
9.2. STRUCTURAL WELDED WIDE FLANGE SHAPES (WWF) SHALL CONFORM TO CAN/CSA-G40.20/G40.21 GRADE 350W. 13.2 SITE ACCESS AND STAGING AREA FOR THE REMOVALS SHALL BE DETERMINED BY THE GENERAL ASL ADDITIONAL SNOW LOAD MJ MOVEMENT JOINT
9.3. ANGLES, PLATES AND CHANNELS (L, C) SHALL CONFORM TO CAN/CSA-G40.20/G40.21 GRADE 300W. CONTRACTOR. ASPH ASPHALT mm MILLIMETRE
EXISTING MASS CONCRETE AVG AVERAGE mm² SQUARE MILLIMETRE
9.4. HOLLOW STRUCTURAL SECTIONS (HSS) SHALL CONFORM TO ASTM A500 GRADE B. 13.3 ALL BURIED AND ABOVE GROUND SERVICES, SHALL BE IDENTIFIED AND CLEARLY MARKED BY CONTRACTOR B (BOTT) BOTTOM MOM, MOMENT
9.5. ANCHOR RODS SHALL CONFORM TO ASTM F1554 GRADE 36 WELDABLE STEEL OR 300W THREADED ROD FOR THEIR SAFE DISCONNECTION, REMOVAL OR PROTECTION PRIOR TO COMMENCEMENT OF REMOVALS. BCE BOTTOM CHORD EXTENSION MPa MEGAPASCAL
CONFORMING TO CSA G40.21-M, UNLESS OTHERWISE NOTED OR SHOWN. 13.4 ISOLATE, DISCONNECT AND/OR CAP ALL SERVICES SUCH AS WATER, GAS, ELECTRICAL, BELL, CABLES, ALARMS, BDP ELEV BOTT OF DRILLED PIER Ms SPECIFIED (UNFACTORED) MOMENT
9.6. STRUCTURAL BOLTS SHALL CONFORM TO ASTM A325M, NUTS SHALL CONFORM TO ASTM A563M. WASHERS ETC. FOR THE BUILDING AS REQUIRED. BEW BOTTOM EACH WAY N NEWTON
NEW MASS CONCRETE
BLL BOTTOM LOWER LAYER NBC NATIONAL BUILDING CODE OF CANADA
CONFORM TO ASTM F436M. 13.5 INFORM THE ENGINEER PRIOR TO COMMENCEMENT OF REMOVALS. BM BEAM NF NEAR FACE
9.7. NON-SHRINK GROUT SHALL HAVE MINIMUM STRENGTH TWICE THE BASE CONCRETE STRENGTH PER ASTM 13.6 CLEAR BUILDING INTERIOR OF ANY GARBAGE, EQUIPMENT, COMBUSTIBLES, AND OTHER ARTICLES THAT MAY BPL BEARING/BASE PLATE NIC NOT IN CONTRACT
C1107. PRESENT A PROBLEM DURING REMOVALS. 190mm CMU FULLY GROUTED BRG BEARING No NUMBER
9.8. PROVIDE MINIMUM LENGTH OF BEARING OF 200 mm (8") FOR ALL STEEL BEAMS BEARING ON MASONRY AND 13.7 REMOVALS SHALL BE DONE BY CONVENTIONAL MECHANICAL METHOD BY COMPETENT AND QUALIFIED C/W 15M @ 600 VERT. BSMT BASEMENT NOM NOMINAL
REINF/DOWEL BUL BOTTOM UPPER LAYER NTS NOT TO SCALE
CONCRETE AND A MINIMUM OF 100 mm (4") ON STRUCTURAL STEEL, UNLESS OTHERWISE NOTED OR SHOWN. PERSONNEL. C CHANNEL o/c ON CENTRE
9.9. CENTER BEARING PLATES UNDER BEAMS UNLESS OTHERWISE NOTED OR SHOWN. 13.8 SCALE/DIMENSIONS OF EXISTING BUILDINGS AND FACILITIES SHOWN ON REMOVAL SITE PLAN ARE c/c CENTRE TO CENTRE OBC ONTARIO BUILDING CODE
9.10. BEARING PLATE DIMENSION GIVEN FIRST INDICATES SIDE PARALLEL TO BEAM WEB. APPROXIMATE. SITE MEASURE/VERIFY. OPENING c/w COMPLETED WITH /CONNECT WITH OD OUTSIDE DIAMETER
CA COLUMN ABOVE
9.11. NO STRUCTURAL STEEL SHALL BE CUT IN THE FIELD UNLESS REVIEWED AND APPROVED BY THE CONSULTANT. 13.9 PRIOR TO REMOVALS, THE CONTRACTOR MUST SUBMIT A P.ENG STAMPED REMOVALS PLAN FOR REVIEW BY CAISS CAISSON
OF OUTSIDE FACE
9.12. ALL WELDS EXPOSED TO VIEW SHALL BE GROUND SMOOTH. THE ENGINEER. OPG OPENING
CANTIL CANTILEVER OPP OPPOSITE
9.13. PROVIDE SIGNED AND SEALED CALCULATIONS FOR ALL STRUCTURAL STEEL CONNECTION DESIGN. 13.10 CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS TO ENSURE THE REMAINING AREA IS FUNCTIONING CB COLUMN BELOW OWSJ OPEN WEB STEEL JOIST
EARTH CF CONCRETE FIREPROOFED
CALCULATIONS ARE TO BE SUBMITTED SIMULTANEOUSLY WITH CORRESPONDING SUBMITTAL. WITHOUT DISRUPTION. P, PL PLATE
Cf FACTORED COMPRESSION Pa PASCAL
9.14. FORCES INDICATED ARE FACTORED LOADS UNLESS OTHERWISE NOTED OR SHOWN. SUBSCRIPTS D, L. W AND Q 13.11 SCAN TO LOCATE EXISTING REBARS PRIOR TO CUTTING OR CORING EXISTING WALLS OR SLABS. CJ CONTROL JOINT PED PEDESTAL
REFER TO DEAD, LIVE, WIND AND EARTHQUAKE LOADS, RESPECTIVELY. CL CENTRE LINE, CONTROL LINE Pf FACTORED AXIAL LOAD
9.15. SPLICES SHALL BE DESIGNED TO DEVELOP THE FULL CAPACITY OF THE MEMBER AT THE POINT OF THE SPLICE. BEDROCK CMU CONCRETE MASONRY UNIT PROJ PROJECTION
MEMBERS SHALL NOT BE SPLICED AT POINTS OF MAXIMUM STRESS. NO SPLICES SHALL BE MADE UNLESS COL COLUMN Ps SPECIFIED (UNFACTORED) AXIAL LOAD
COMP COMPOSITE PVC POLYVINYL CHLORIDE
SHOWN ON THE DRAWINGS OR REVIEWED AND APPROVED BY THE CONSULTANT. CONC CONCRETE R RADIUS
9.16. PROVIDE WELDED STIFFENER PLATES ON BOTH SIDES OF THE WEB OF BEAMS AT POINTS OF CONCENTRATED GRATING CONST JT CONSTRUCTION JOINT R/W REINFORCE WITH
LOAD INCLUDING BEAMS SUPPORTING COLUMNS OR RUNNING OVER TOPS OF COLUMNS, UNLESS SHOWN BY CONT CONTINUOUS REINF REINFORCEMENT
CONT'D CONTINUED
DESIGN, THAT STIFFENERS ARE NOT REQUIRED. CP CAST IN PLATE
REV REVISION, REVISED
9.17. SHAPE AND SIZE GUSSET PLATES TO CLEAR ARCHITECTURAL FINISHES, MECHANICAL DUCTS, PIPES, ELEVATOR RL REFERENCE LINE
CPL CAP PLATE RSS RETAINED SOIL SYSTEM
SHAFTS AND THE LIKE. GRANULAR CS COMPRESSION SPLICE RW RETAINING WALL
9.18. PROVIDE ALL ANCHOR RODS, CAST IN PLATES WITH ANCHORS, AND ANCHORS REQUIRED TO CONNECT Cs SPECIFIED (UNFACTORED) COMPRESSION S STANDARD BEAM
D FIR DOUGLAS FIR SC STUB COLUMN
STRUCTURAL STEEL TO CAST-IN-PLACE CONCRETE.
9.19. LENGTH FOR ANCHOR RODS, STRAP ANCHORS AND SIMILAR DEVICES IS GIVEN FOR THE STRAIGHT LENGTH
TABLE 1 DEMOL DEMOLITION SDF STEP DOWN FOOTING
DET DETAIL
WITHOUT HOOK. PROVIDE A 75 mm (3") HOOK FOR ALL ANCHOR RODS AND A 50 mm (2") HOOK FOR ALL STRAP DEFLECTION LIMITS TABLE 2 DIM DIMENSION
SECT SECTION
SF SPRAY FIREPROOFED
DL DEAD LOAD
ANCHORS, TYPICAL UNLESS NOTED OTHERWISE. CONSTRUCTION LIVE SNOW / WIND DEAD + LIVE LONG TERM CONCRETE EXPOSURE CLASS REQUIREMENT DN
SIM SIMILAR
DOWN SL SLAB
9.20. UNLESS OTHERWISE SHOWN ON THE DRAWINGS, TYPICAL SHEAR CONNECTIONS ARE TO BE DESIGNED AS LOADING (CREEP) DP DEEP, DRILLED PIER
NOT EXPOSED EXPOSED TO FREEZING EXPOSED TO CHLORIDES SLBB SHORT LEG BACK TO BACK
FOLLOWS: DWG DRAWING SOG SLAB ON GRADE
ROOF MEMBERS: AND THAWING ONLY WITH OR WITHOUT
DWL DOWEL SP SPANDREL; SPRUCE-PINE
SUPPORTING PLASTER CEILING L / 360 L/ 360 L / 240 - FREEZING AND THAWING
· TYPICAL BEAM TO BEAM (NON-SPANDREL CONDITION) CONNECTIONS - ONE SIDED, TWO SIDED OR END PLATE EA EACH SPECS SPECIFICATIONS
SUPPORTING NONPLASTER CEILING L / 240 L/ 240 L/ 180 -

MIN COMPRESSIVE

MIN COMPRESSIVE

MIN COMPRESSIVE
EXPOSURE CLASS

EXPOSURE CLASS
STRENGTH f'c (b)

STRENGTH f'c (b)

STRENGTH f'c (b)


STRUCTURAL ELEMENTS EBF ECCENTRICALLY BRACED FRAME SS STAINLESS STEEL
CONNECTIONS. EC EPOXY COATED
FLOOR MEMBERS L/ 360 - L / 240 L / 480 ST STRAIGHT

(c,d)

(c,d)

(c,d)
· TYPICAL BEAM TO SPANDREL BEAM CONNECTIONS - TWO SIDED OR END PLATE CONNECTIONS. EE EACH END STA STATION
· TYPICAL BEAM TO COLUMN CONNECTIONS - TWO SIDED OR END PLATE CONNECTIONS. EXTERIOR WALLS AND INTERIOR PARTITIONS - L/ 360 - - EF EACH FACE STD STANDARD
EJ, EXP JT EXPANSION JOINT/MOVEMENT JOINT

SLUMP

SLUMP

SLUMP
· TYPICAL SPANDREL BEAM TO COLUMN CONNECTIONS - TWO SIDED CONNECTIONS. ALL OTHER CONDITIONS STG STAGGER

(MPa)

(MPa)

(MPa)
MEMBERS SUPPORTING CLADDING L / 720 - - - EL ELEVATION STIR STIRRUP
- TWO SIDED OR END PLATE CONNECTIONS. ELEV ELEVATOR STL STEEL
LATERAL FORCE RESISTING SYSTEM: ELEC ELECTRICAL STRUCT STRUCTURAL
NOTE: THE ADDITION OF OTHER CONNECTION FORCES (I.E. AXIAL FORCES) MAY RESULT IN DIFFERENT WIND LOADS - h / 400 - - RAFT / MAT FOUNDATION C-1/S-3 35 125±25 EMBED EMBEDMENT SYM SYMMETRICAL
SEISMIC LOADS - 0.01 hs - - ENG ENGINEER t THICKNESS
CONNECTIONS TO THOSE NOTED ABOVE. WALLS EXTERIOR C-1/S-3 35 150±25 EOD EDGE OF DECK T TOP
SUPPORT CRANE RUNWAY GIRDER: WALLS INTERIOR, EOS EDGE OF SLAB THK THICK
9.21 ALL STRUCTURAL STEEL OUTSIDE OF THE ABOVE GRADE BUILDING ENVELOPE SHALL FOLLOW PAINT - VERTICAL DEFLECTION DUE TO MAX. SLABS, RAMPS AND BEAMS A-1 35 100±25 EQ EQUAL
L / 1000 - - - T/C TOP OF CONCRETE
MANUFACTURER'S HIGH PERFORMANCE COATING SELECTION GUIDE - EXTERIOR FINISH FOR STEEL TO WHEEL LOAD WITHOUT IMPACT EW EACH WAY T/F TOP OF FOOTING
HOUSEKEEPING PADS 30 80±30 N EX, EXIST,EXG EXISTING
CORROSIVE ENVIRONMENT OR USE GALVANIZED STEEL. - LATERAL DEFLECTION L / 400 - - - T/P TOP OF PAVEMENT
EXP JT EXPANSION JOINT T/S TOP OF STEEL
MASS CONCRETE FILL 20 EXT EXTERIOR
(LOW PERMEABLE) T/W TOP OF WALL
9.22 THE CONTRACTOR SHALL COORDINATE EMBEDDED ITEMS REQUIRED FOR PROCESS, ARCHITECTURAL, f'c COMPRESSIVE STRENGTH OF CONC TDL TENSION DEVELOPMENT LENGTH
STRUCTURAL, AND MECHANICAL ELEMENTS. CONCRETE FLOORS UTILIZING UNSHORED CONSTRUCTION SHALL FD FLOOR DRAIN TDP ELEV TOP OF DRILLED PIER
TABLE 3 UNSHRINKABLE FILL MAX 0.40 170±30 FF FAR FACE TEW TOP EACH WAY
BE SCREEDED LEVEL. CONCRETE COVER REQUIREMENTS FIN FINISHED
MASONRY GROUT (e) 15 225±25 TBEW TOP AND BOTTOM EACH WAY
FL FLOOR Tf FACTORED TENSION
9.23 THE CAMBER OF STEEL MEMBERS SHALL BE VERIFIED IN THE SHOP AND THE FIELD. WHEN NO CAMBER IS FND FOUNDATION TLL TOP LOWER LAYER
CAST AGAINST EARTH 75mm SECANT CAISSONS C-1/S-3 35
ft FOOT
INDICATED, TURN THE MEMBER NATURAL CAMBER UP. FTG FOOTING
TRANS TRANSVERSE
9.24 HIGH STRENGTH BOLTS IN BEARING CONDITION SUPPORTING SIMPLE SPAN BEANS NOT SUBJECT TO AXIAL PRIMARY CAISSONS N 15 Ts SPECIFIED (UNFACTORED) TENSION
STRUCTURAL WALLS AND SLABS 60mm fy YIELD STRENGTH TSA TENSION SPLICE 'A'
LOADS MAY BE INSTALLED TO “SNUG TIGHT” CONDITION IF NORMAL, SHORT SLOTTED OR OVERSIZED HOLES GALV GALVANIZED TSB TENSION SPLICE 'B'
NOTES: GB GRADE BEAM
ARE USED. THE ENGINEER OF RECORD OTHER CONCRETE ELEMENTS 40mm
TUL TOP UPPER LAYER
a. MAXIMUM AGGREGATE SIZE IS 20mm (TYPICAL U/N). GRD GROUND
WILL BE THE ULTIMATE AUTHORITY IN THE USE OF “SNUG TIGHT” BOLTS. TYP TYPICAL
b. MINIMUM COMPRESSIVE STRENGTHS ARE AT 28 DAYS UNLESS NOTED OTHERWISE. (H) HIGH U/F UNDERSIDE OF FOOTING
9.25 WELDS SHOWN ON STRUCTURAL DRAWINGS ARE MINIMUM DESIGN REQUIREMENTS. THE FABRICATOR’S SHOP c. THE SLUMP SPECIFIED IN TABLE 1 IS THE SLUMP BEFORE THE ADDITION OF ANY SUPERPLASTICIZING HEF HORIZONTAL EACH FACE U/N UNLESS NOTED
400mm CONC. WALL AGAINST CAISSONS 80mm ADMIXTURES.
DRAWINGS SHALL REFLECT WELDS IN ACCORDANCE WITH CWS REQUIREMENTS. HVEF HORIZONTAL AND VERTICAL EACH FACE U/S UNDERSIDE
d. WHEN SUPERPLASTICIZING FLOWING CONCRETE IS USED, THE SLUMP BEFORE THE ADDITION OF HH HOOK-HOOK (HOOK EACH END)
9.26 TWENTY- FIVE PERCENT OF THE WELDS SHALL BE INSPECTED AT RANDOM UNLESS NOTED OTHERWISE SUPERPLASTICIZING ADMIXTURE SHALL BE AS SPECIFIED, OR LOWER, AND AFTER THE ADDITION OF THE
U-BAR U SHAPE BAR
ALL WET WELL CONCRETE WALL AGAINST SOIL 100mm HOR, H HORIZONTAL UPT UPTURNED
SUPERPLASTICIZING ADMIXTURES SHALL REMAIN BELOW THE POINT AT WHICH SEGREGATION WILL HP HIGH POINT V, VERT VERTICAL
OCCUR. HSL HORIZONTALLY SLOTTED CONNECTION VBF VERTICAL BRACED FRAME
10. ALUMINUM WET WELL BASEMENT AND CHANNELS 80mm e. SUPPLY MASONRY GROUT WITH A MAX W/C OF 0.55 AND MAX AGGREGATE SIZE OF 10mm HSS
ID
HOLLOW STRUCTURAL SECTION
INSIDE DIAMETER
VEF VERTICAL EACH FACE
DETAILS REFER TO MEMORANDUM REGARDING CORROSION PROTECTION ISSUED BY WSP DATED FEB 16, 2018 Vf FACTORED SHEAR
IF INSIDE FACE Vs SPECIFIED (UNFACTORED) SHEAR
10.1. STRUCTURAL ALUMINUM in INCH VSC VERTICALLY SLOTTED CONNECTION
INT INTERIOR W WIDE FLANGE BEAM
REINFORCEMENT SPLICES
10.1.1. STRUCTURAL ALUMINUM FRAMING SHALL CONFORM TO CSA HA SERIES. k KILOPOUND, kip w/ WITH
35 MPa CONCRETE, NORMAL WEIGHT k/ft kip(s) PER FOOT
10.1.2. ALL ALUMINUM MEMBERS SHALL BE FABRICATED IN ACCORDANCE WITH THE ALUMINUM DESIGN 400 MPa REINFORCING BARS w/o WITHOUT
k-ft kip FOOT WC WIND COLUMN
MANUAL, CURRENT EDITION. kg KILOGRAM WB WALL BELOW
10.1.3. ALUMINUM SHALL BE THE ALLOYS AND TEMPERS AS SPECIFIED ON THE DRAWINGS. LAP LENGTH FOR BILLET STEEL BARS (mm) LAP LENGTH FOR EPOXY COATED BARS (mm) kip KILOPOUND WP WORK POINT
kN KILONEWTON
10.1.4. THERE SHALL BE NO WELDED CONNECTIONS UNLESS ALLOWED AND SHOWN ON THE DRAWINGS. BAR SIZE WPL WALL PLATE
kN/m KILO NEWTON PER METRE WT STRUCTURAL TEE
10.1.5. PROVIDE DISSIMILAR METAL SEPARATORS AT ALL JUNCTIONS OF ALUMINUM FRAMING AND TOP BARS (mm) BOTTOM BARS (mm) DOWELS TOP BARS (mm) BOTTOM BARS (mm) DOWELS kN/m2 KILO NEWTON PER SQUARE METRE WWF WELDED WIRE FABRIC,
STRUCTURAL STEEL, CONCRETE kN-m KILO NEWTON METRE WELDED WIDE FLANGE
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_-Sheet - S-00B.dwg

AND MASONRY. CLASS A CLASS B CLASS A CLASS B A B CLASS A CLASS B CLASS A CLASS B A B kPa KILOPASCAL
kSF kip(s) PER SQUARE FOOT
10.1.6. THE CONFIGURATION OF THE PRE-ENGINEERED ALUMINUM GUARDRAILS SHALL BE AS INDICATED IN kSI kip(s) PER SQUARE INCH
10M 360 470 300 360 300 360 470 620 450 540 450 540
THE ARCHITECTURAL (L) LOW
DRAWINGS. 15M 510 670 400 510 400 510 670 880 600 770 600 770 L SINGLE ANGLE
10.1.7. GUARDRAILS AND CONNECTIONS SHALL BE DESIGNED FOR APPLICABLE LOADS AS INDICATED ON THE LB(s) POUND(s)
20M 620 810 480 620 480 620 810 1060 720 930 720 930 LG LONG/LENGTH
PLANS AND IN THE BUILDING CODE. THE LOADS SHALL BE CLEARLY INDICTED ON THE DRAWINGS. ˩L DOUBLE ANGLES
25M 1000 1300 770 1000 770 1000 1300 1690 1160 1500 1160 1500 LL LIVE LOAD
11. FIBRE REINFORCED POLYMER (FRP) 30M 1190 1550 920 1190 920 1190 1550 2020 1380 1790 1380 1790 LLBB
LLH
LONG LEG BACK TO BACK
LONG LEG HORIZONTAL
35M 1390 1810 1070 1390 1070 1390 1810 2360 1610 2090 1610 2090 LLV LONG LEG VERTICAL
11.1. SEE SPECIFICATION FOR DESIGN REQUIREMENT FOR FRP. LONG LONGITUDINAL
NOTES:
LP LOW POINT
11.2. ALL FRP ITEMS AND SUPPORTS SHALL BE DESIGNED BY A PROFESSIONAL ENGINEER LICENSED IN THE a. DOWELS ARE TO MATCH WALL REINFORCEMENT UNLESS NOTED OTHERWISE. USE CLASS A LENGTH FOR ANCHORAGE.
PROVINCE OF BRITISH COLUMBIA. ALL SHOP DRAWINGS SUBMITTED SHALL BE SIGNED AND SEALED BY THE b. TOP BARS ARE:
PROFESSIONAL ENGINEER. A) ALL BARS IN CONCRETE WITH MORE THAN 300mm CONCRETE BELOW.
B) ALL HORIZONTAL BARS IN WALLS.
c. PROVIDE CLASS B LAP UNLESS NOTED OTHERWISE
d. LAP SPLICE LENGTHS SHOWN IN THE TABLE ARE BASED ON HEAVIER CONFINED BARS.
e. TABLE APPLIES UNLESS SHOWN OTHERWISE.
f. DEVELOPMENT LENGTHS ARE EQUAL TO CLASS 'A' LAP SPLICES.
g. DEVELOPMENT LENGTHS ARE FOR UNCOATED REINFORCEMENT.
DATE: 10/08/2018 4:11:41 PM, Rani, Sushma

MR 24/09/2018 9 ISSUED FOR CONSTRUCTION


VERIFY SCALES
MR 19/07/2018 8 REISSUED FOR CONSTRUCTION - CAISSON WALL
DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM
BAR IS 20mm ON MR 15/06/2018 7 ISSUED FOR 100% DESIGN SUBMISSION SURVEYED
MR
CLOVER POINT PUMP STATION
16/05/2018 6 ISSUED FOR CONSTRUCTION - CAISSON WALL
20mm MR 26/03/2018 5 ISSUED FOR PRE-CONSTRUCTION REVIEW - CAISSON WALL DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 23/03/2018 4 ISSUED FOR 90% DESIGN SUBMISSION SCALE
CHECKED R.L. GENERAL NOTES
IF NOT 20mm ON HORIZONTAL -
THIS SHEET, ADJUST MR 19/01/2018 3 ISSUED FOR 50% DESIGN SUBMISSION
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY APPROVED
SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - NUMBER CPS-100 NUMBER CP-C01-S-00B 9 OF
2 3 4

4
5486 12802 D-104
18' - 0" 42' - 0"
457 3949 457 4052 457 4052 457 3951 457
1' - 6" 12' - 11 1/2" 1' - 6" 13' - 3 1/2" 1' - 6" 13' - 3 1/2" 1' - 6" 12' - 11 1/2" 1' - 6"

A 5 6 7 8 9

SAWCUT OPENING ON EX. CHANNEL AND


CAST OPENING IN NEW WALL. REPAIR
19' - 9"

ALL CUT AND EXPOSED REBAR WITH


6020

EPOXY REPAIR MORTAR.

EXG MOTOR RM & WET WELL FLOOR


3.609 m
2800 1200 3000 2500 3000 2000 3000 1200 2825

930
762 16764 762

600
2' - 6" 55' - 0" 2' - 6"

9' - 8"
2941
B EL. 2.450
2' - 0"
610

1411
EL. 1.850
EXG INLET CHANNEL INVERT
0.439 m

1935
EL. -0.448

3
REMOVE AND DISPOSE
EXISTING GRATING D-104

2550
UP
PANELS FROM EX. PUMP
FLOOR BASEMENT ROOM SAWCUT OPENING 1 SECTION
30' - 9"
27' - 3"

ON EXISTING WALL
9373

5435 11330
8306

5 D-101
1 : 75

700
NOTES:
1676
2144

6706
22' - 0" 1. REFER TO TYPICAL DETAILS FOR WALL OPENING CUTTING METHODS OR SEQUENCE IN EXISTING WALL.
1677

2500
2. REFER TO WALL ELEVATIONS FOR EXACT SIZE AND LOCATION OF NEW OPENINGS.
2
7' - 0 1/2"

D-104 3. NO OVERCUTTING IS ALLOWED. EXPOSED REINFORCEMENT DUE TO CUTTING SHALL BE PROTECTED BY SIKA
2145

EX. SUMP TOP ARMATEC 110 EPOCEM OR EQUIVALENT COATING.


1677

WASTE WATER CHANNEL


4. NO EXISTING WALL CUTTING IS PERMITTED BEFORE THE EARTH OUTSIDE THE WALL IS FULLY REMOVED, THE

622
ROOF/FLOOR, SLABS AND BEAMS ARE FULLY SHORED SO THAT THE RELATED LOADING IS RELEASED. SHORING
1' - 6"

1' - 6"
457

457
SYSTEM TO BE DESIGNED BY PROFESSIONAL ENGINEER. SHORING SHOP DRAWINGS SHALL BE SUBMITTED FOR
C REVIEW AND APPROVED AS SPECIFIED.
5486 180 2415 300 2115 2115 300 2415 180 762 6249 457
5. FOR MATCHING NEW CONCRETE WALL ON GRID '4', '5' AND 'C' ADDITIONAL HORIZONTAL AND VERTICAL
18' - 0" 2' - 6" 20' - 6" 1' - 6"
6' - 6"
1981

457 REINFORCEMENT, ADDITIONAL DOWELS PER TYPICAL DETAILS SHALL BE INSTALLED ON NEW WALL SIDE TO
1' - 6" STRENGTHEN THE OPENING ON EXISTING WALLS.

2820
6. SHOP DRAWINGS SHALL BE SUBMITTED FOR REVIEW FOR CUTTING METHOD, SEQUENCE, SHORING PLAN ETC.
D BEFORE ANY CUTTING.

19' - 3"
SAWCUT OPENING ON EXISTING

5871
457
WALL, SEE DWG. S-305 FOR OPENING
ELEVATIONS. REFER TO TRAY GRIT TRAY GRIT

25' - 6"
STRENGTHENING

7773
DETAIL-8 ON DWG. S-701 SEPARATOR SEPARATOR

2617
PRIOR TO SAW CUTTING WALL OPENINGS,
INSTALL DOWELS AROUND EXISTING WALL OPENING AND
CONSTRUCT NEW WALL. ANY EXPOSED REBAR TO BE

1' - 6"
COATED WITH COATING. SEE NOTE-3. SEE S-311 FOR DOWEL

457
DETAILS.
23223
35' - 4 1/2"
10786

1200 2800 1200 3000 2500 3000 2000 3000 1200 2825
1' - 6"

NEW
5' - 0"
1524
457

5' - 0" 1' - 0"


305
1524 305 1524 976
5' - 0" 1' - 0"
SCREEN
EX. INLET SANITARY CHANNEL EL. 0.439 m
3

1524
1

1' - 0"
3124 457 3124 457 3124 457 3124 457 3124 457 3124 D-103

305
D-101 10' - 3" 1' - 6" 10' - 3" 1' - 6" 10' - 3" 1' - 6" 10' - 3" 1' - 6" 10' - 3" 1' - 6" 10' - 3"
5' - 0"

NEW
1524

REMOVE PORTION OF
1' - 0"
305

EXISTING WALL SCREEN


REMOVE PORTION OF EXISTING WALL

5' - 0"
1524
EX. OVER FLOW CHANNEL EL. 0.439 m OPENING TO BASE SLAB ELEVATION
24/09/2018 6:55:35 PM

3' - 9"
1143

1866
1' - 0"
305

2
1' - 6"
1' - 0" 6' - 2 1/2" 1' - 0"

457
305

D-103
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

1890

EX. SEWER
21796
305

REMOVE PORTION OF EXISTING WALL


305 3404 305 FOR 1866mmØ WALL PENETRATION,
SEE PROCESS DWGS. FOR INVERT EL.
1' - 0" 11' - 2" 1' - 0"

LEGEND

DEMOLISH
DEMOLITION - LOWER LEVEL PLAN
1 : 75

VERIFY SCALES DESIGNED RL CORE AREA WASTEWATER TREATMENT PROGRAM


BAR IS 20mm ON SURVEYED
CLOVER POINT PUMP STATION
20mm MR 24/09/2018 3 ISSUED FOR CONSTRUCTION DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 15/06/2018 2 ISSUED FOR 100% DESIGN SUBMISSION SCALE
As indicated CHECKED J.P.
DEMOLITION - EXISTING LOWER LEVEL
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 23/03/2018 1 ISSUED FOR 90% DESIGN SUBMISSION
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-D-101 3 OF
2 3 4 5

457 17374 457


1' - 6" 57' - 0" 1' - 6"
NOTES - SEAL THE HATCH OPENINGS
A

1' - 6"
457
1. PROVIDE ALL NECESSARY SHORING FOR THE SLAB AROUND THE HATCH OPENINGS TO MAINTAIN THE STRUCTURAL
INTEGRITY DURING CONSTRUCTION.
EX. WASHROOM EX. MOTOR
EX. LUNCHROOM ELECTRICAL 2. REMOVE ALL HATCHES AND ACCESSORIES, ROUGHEN THE VERTICAL CONCRETE SURFACES.
CONTROL CENTREX
10' - 11 1/2"
ROOM (2)
(3) 3. INSTALL NEW DOWELS AROUND ALL SIDES OF HATCH OPENINGS, 15M @300 T.B.E.W (TYP. FOR ALL OPENINGS) WITH
3334
3 150mm (MIN.) EMBEDMENT HILTI HY200 ADHESIVE ANCHOR SYSTEM. DOWEL REINFORCEMENT ONLY ONE END
S-105 ANCHORING INTO EXISTING CONCRETE. MAINTAIN 520mm MIN. LAP SPLICES.

4. INSTALL FORMWORK UNDERNEATH THE OPENING, APPLY BONDING AGENT TO THE EXISTING CONCRETE SURFACES.
POUR CONCRETE TO THE OPENINGS MATCH THE EXISTING CONCRETE COVER THICKNESS AND CONCRETE FINISHES.
0' - 6"

FOR CONCRETE TYPE REFER TO GENERAL NOTES.


150

5. NO EXISTING REINFORCEMENT CAN BE DAMAGED DURING NEW REINFORCEMENT INSTALLATION.

CONTROL ROOM 6. ALL EXISTING PIPE INSERTS FOR POSTS AND SAFETY CHAIN IN EXISTING MOTOR ROOM NEEDS TO BE REMOVED AND
EXISTING 6`` HOLLOW
CONC. BLOCK OPENINGS TO BE GROUTED.
WALL

38' - 9"
11815
B

150
REMOVE AND DISPOSE
OF EXISTING DOOR AND
EX. MOTOR ROOM CMU WALL

3
36' - 7"
11152

REMOVE AND DISPOSE D-104


EXISTING HATCHES
SEAL HATCH OPENING. D C
SEE NOTES (TYP.)
SAWCUT OPENING ON
5850 1219 1216 1219 1216 1219 1216 1219 3000 EXISTING WALL, REFER TO
19' - 2 1/2" 4' - 0" 4' - 0" 4' - 0" 4' - 0" 4' - 0" 4' - 0" 4' - 0" 9' - 10" STRENGTHENING DETAIL-11
ON DWG. S-701
EL. 3.609 T/O EX. RETAINING WALL
12.478 m

7' - 2"
2180
REMOVE AND DISPOSE
2
D-104 452
OF EXISTING DOOR
1' - 6"

3' - 1"
1' - 0"

941
1015 3000
300

EXG UPPER ROOF


3' - 4" 9' - 10"
10.802 m
C
457 6249
0' - 9 1/2"

3' - 3 1/2"

457 EXG MIDDLE ROOF

8' - 0"
0' - 6"

2438
152

1000
245

1' - 6" 20' - 6" 1' - 6"


9.888 m
SAWCUT OPENING
ON EXISTING WALL
D SEE DETAIL-11

3' - 3 1/2"
ON DWG. S-701

1000
EX. WET WELL EX. WET WELL
NO.1 NO.2
2 EXTEND OPENING ABOVE
4 THE DOOR TO ACCOMMODATE

994
D-102
D-104 MECH. DUCT.
21' - 3 1/2"

9' - 6"
2890
6490

EXG MEZZANINE LEVEL


6.825 m
REMOVE AND DISPOSE OF EXISTING

1' - 6"
457
GRATING REMOVE AND DISPOSE

EX. DOOR OPENING


1168 1219 EXISTING DOOR

4702
3' - 10" 4' - 0"

12' - 2"
3714
762

5' - 0"
1524

EX. FLOOR HATCH


762
2' - 6"
1' - 6"
457

18' - 9"
5712
13' - 1 1/2"

5' - 0"
1524
4000

EXG MOTOR RM & WET WELL FLOOR


3.609 m
EX. FLOOR HATCH
WASTEWATER GRIT SEPARATOR &
SCREENING ROOM
24/09/2018 6:55:37 PM

1' - 6"
457
E 152 300
0' - 6" 1' - 0" 18751 457
61' - 6" 1' - 6" 2 SECTION
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

D-102
1 : 50

DEMOLITION - UPPER LEVEL PLAN


LEGEND
1 : 75

DEMOLISH

VERIFY SCALES DESIGNED RL CORE AREA WASTEWATER TREATMENT PROGRAM


BAR IS 20mm ON SURVEYED
CLOVER POINT PUMP STATION
20mm MR 24/09/2018 3 ISSUED FOR CONSTRUCTION DRAWN SR DATE 02/02/2018 STRUCTURAL
MR 15/06/2018 2 ISSUED FOR 100% DESIGN SUBMISSION SCALE
As indicated CHECKED J.P.
DEMOLITION - UPPER LEVEL PLAN
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 23/03/2018 1 ISSUED FOR 90% DESIGN SUBMISSION
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-D-102 3 OF
2 3 4 5

2 3 4

457 17374 457


1' - 6" 57' - 0" 1' - 6"
A A
1' - 6"

1' - 6"
457

457
EXISTING VENT TO BE
SEAL WITH CONCRETE AND
WATER PROOFING

A1

18' - 3"
5563
EX. DOOR
TO REMAIN
EL. 6.825

1016
3' - 4"

11815
B B

8357
48' - 0"
14636

REMOVE EXISTING RAILING AND


DISPOSE OFF SITE

EXHAUST STACK SUPPORT


3 DETAILS TO BE PROVIDED
D-104 BY SUPPLIER
OPEN TO BELOW

29' - 3"
8916
28' - 1"
8563
SAWCUT OPENING B1
ON EXISTING WALL

2720
D-102
2
D-104

1015 3000 1015

401
B2
C C
1' - 0"
300

W250x33 STRENGTHENING STEEL BEAMS ON TWO SIDE OF


EXISTING DOOR TO BE SLAB OPENING. STEEL BEAM TO BE ANCHORED TO EXISTING
DEMOLISHED AND DISPOSE ROOF BEAM BY 400x250x16 WALL PLATE, 4-20 DIA, HILTI HIT -
OFF SITE HY200 ADHESIVE ANCHOR, SPACING @175mm, 150mm MIN.
EMBEDMENT. INSTALL NON-SHRINK, NON-METALLIC DRY-
EXISTING DOOR OPENING TO BE PACK GROUT BETWEEN STEEL BEAM AND SLAB.
ENLARGED TO SUIT THE NEW
MECH. LOUVER. FOR DETAILS
DEMOLITION - MEZZANINE LEVEL
REFER TO DETAIL-11 ON S-701
1 : 75 EXISTING ROOF - DEMOLITION
1 : 75

8 9

4
EXG MOTOR RM & WET WELL FLOOR D-104
3.609 m
1866 EXG MOTOR RM & WET WELL FLOOR
REMOVE PORTION OF EXISTING
1524 WALL OPENING TO BASE SLAB
3.609 m
ELEVATION
REMOVE PORTION OF EXISTING WALL
FOR 1866mmØ WALL PENETRATION
24/09/2018 6:55:39 PM

REMOVE PORTION OF EXISTING WALL EL. 2.454 m


FOR 1866mmØ WALL PENETRATION,
REFER TO PROCESS DWGS.

DIAMETER
320

1866
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

4' - 8"
1422
EXG INLET CHANNEL INVERT
0.439 m
EL. 0.588 m
EXG INLET CHANNEL INVERT
0.439 m

LEGEND
2 SECTION 3 SECTION
D-101 D-101
1 : 50 1 : 50
DEMOLISH

VERIFY SCALES DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM


BAR IS 20mm ON SURVEYED
CLOVER POINT PUMP STATION
20mm MR 24/09/2018 3 ISSUED FOR CONSTRUCTION DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 15/06/2018 2 ISSUED FOR 100% DESIGN SUBMISSION SCALE
As indicated CHECKED J.P.
DEMOLITION - MEZZANINE PLAN
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 23/03/2018 1 ISSUED FOR 90% DESIGN SUBMISSION
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-D-103 3 OF
4 4
B
D C A

457
457
1' - 6"
1' - 6"
EXG UPPER ROOF EXG UPPER ROOF EXG UPPER ROOF
10.802 m 10.802 m 10.802 m
978

858 2720
SAWCUT OPENING ON EXISTING EXG MIDDLE ROOF
WALL SEE DETAIL-11 ON DWG. 9.888 m
S-701 FOR LINTEL DETAIL (TYP.)

DEMOLISH EXISTING CORBEL


3000

3000
FROM GRID B-C ALONG GRID 4 TO DEMOLISH EXISTING CORBEL
FACILITATE THE CONSTRUCTION FROM GRID B-C ALONG GRID 4 TO
1016 DEMOLISH EXISTING CORBEL FACILITATE THE CONSTRUCTION
OF NEW SPS WALL AND DOOR
3' - 4" FROM GRID B-C ALONG GRID 4 TO OF NEW SPS WALL AND DOOR

7193
EXG MEZZANINE LEVEL FACILITATE THE CONSTRUCTION EXG MEZZANINE LEVEL
OF NEW SPS WALL AND DOOR
6.825 m 6.825 m
1016

1000
2180

941
SAWCUT OPENING ON EXISTING WALL
2050

2050
2200
SEE DETAIL-11 ON DWG. S-701 FOR 1398
LINTEL DETAIL

EXG MOTOR RM & WET WELL FLOOR EXG MOTOR RM & WET WELL FLOOR EXG MOTOR RM & WET WELL FLOOR
150

150
3.609 m 3.609 m 1079 2500 700 2550 3.609 m

1057
2545
2057

SAWCUT OPENING ON EXISTING


SAWCUT OPENING ON EXISTING WALL WALL SEE DETAIL-11 ON DWG.
SEE DETAIL-11 ON DWG. S-701 FOR S-701 FOR LINTEL DETAIL (TYP.)
LINTEL DETAIL

3000
2000

2000
SAWCUT OPENING ON EXISTING WALL
SEE DETAIL-11 ON DWG. S-701 FOR
LINTEL DETAIL
EXG PUMP FLOOR EXG PUMP FLOOR
-0.448 m -0.448 m
1856

762
EXG VALVE FLOOR
2' - 6"
-2.304 m

762
2' - 6"

2 SECTION 3 SECTION 4 SECTION


D-101 D-101 D-101
1 : 75 1 : 75 1 : 75
24/09/2018 6:55:41 PM
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

LEGEND

DEMOLISH

VERIFY SCALES DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM


BAR IS 20mm ON SURVEYED
CLOVER POINT PUMP STATION
20mm MR 24/09/2018 3 ISSUED FOR CONSTRUCTION DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 15/06/2018 2 ISSUED FOR 100% DESIGN SUBMISSION SCALE
1 : 75 CHECKED J.P.
DEMOLITION - SECTIONS
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 23/03/2018 1 ISSUED FOR 90% DESIGN SUBMISSION
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-D-104 3 OF
NOTES:
1. WET WELL BASE MAT TO BE FOUNDED ON MASS CONCRETE FILL EXTENDING D0WN TO SOUND BEDROCK

2. MASS CONCRETE SURFACE TO BE ROUGHENED TO ACHIEVE THE GREATEST BONDING AND FRICTION
BETWEEN BASE MAT AND MASS CONCRETE. NO DEBRIS OR LOOSE PIECE IS ALLOWED BETWEEN THE
SURFACES.

3. WET WELL CONCRETE WALL AND SLAB CONCRETE COVER TO BE 100mm TYPICAL IF CAST RIGHT AGAINST
THE EARTH.

4. SEE TYPICAL DETAILS FOR REBAR SPLICE LENGTH REQUIREMENTS.

5. PROVIDE WIRE MESH 152x152 MW 25.8x25.8 WITH 50mm CONCRETE COVER FOR ALL BENCHING/MASS
CONCRETE INSIDE SEWAGE WET WELL OR CHANNELS FOR CRACK CONTROL.

6. CONCRETE BENCHING INSIDE SEWAGE TO BE DOWELED INTO STRUCTURAL SLABS/WALLS WITH


15M @800 EACH WAY. PROVIDE END HOOK OR DEVELOPMENT LENGTH AS REQUIRED.

H J K
S-312 S-313
S-311

4 5 6 7 8 9

6706 500 12925 500 8800 2150


22' - 0"
SEE SECTION-B2
FOR OPENING
CONC. BENCHING, SEE NOTE-5 ALUM. LADDER ALUM. LADDER
ELEVATIONs (TYP.)
FOR REINFORCEMENT. SEE STD. DETAILS SEE STD. DETAILS

500

500
B1

900
600mm THK . LP EL.-2.787 LP EL.-2.787
CONC. SLAB EL. T/B -2.512 EL. -2.914

2621
300mm 900 4498

3121
DEEP SUMP
SANITARY WET WELL
B2 2950 1205
S-304 -2.900

500
EL. -1.980
B2
STORM WET WELL

1965
1870 SLIDE GATE OPENING 1050mm THK .
EX. MASS CONCRETE EL. -1.980 1205x1205, SEE CONC. MAT

8891

9891
PROCESS DWGS.
C2 C2 C2
EL. -2.914m
S-306 H.P. EL. -2.130

500
75mm LEGGING
TEMP. SHORING
E
SLOP

5770
15M@900 EW MAX C/W HILTI 156.3 BY CONTRACTOR

HY200 EPOXY, EMBED 150.
(TYP.) ALL CONCRETE SURFACE OF WET WELL
AND CHANNEL (BASE SLAB, WALLS, UNDERSIDE -2.203

SLO
7830

PE
3305
OF TOP SLABS, BEAMS, AND COLUMNS) TO BE

SLO

PE
PROTECTED BY TWO COATS OF PROTECTIVE D1
COATING - CEM-KOTE FLEX CR OR APPROVED C2

11
EQUAL (SEE SPECIFICATIONS)

3.6
HP EL.-1.832 HP EL.-1.832


500

500
D2
24/09/2018 6:55:43 PM

NEW 400mm THK.


CONC. WALL RESTING 500 729 4796 500 8800 1050
ON MASS CONCRETE 100

D3
400
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

STORM WET WELL PLAN


1 : 75

MR 24/09/2018 7 ISSUED FOR CONSTRUCTION


VERIFY SCALES
MR 19/07/2018 6 REISSUED FOR CONSTRUCTION - CAISSON WALL
DESIGNED RL CORE AREA WASTEWATER TREATMENT PROGRAM
BAR IS 20mm ON MR 15/06/2018 5 ISSUED FOR 100% DESIGN SUBMISSION SURVEYED
MR 16/05/2018 4 ISSUED FOR CONSTRUCTION - CAISSON WALL
CLOVER POINT PUMP STATION
20mm MR 26/03/2018 3 ISSUED FOR PRE-CONSTRUCTION REVIEW - CAISSON WALL DRAWN SR DATE 02/02/2018 STRUCTURAL
MR 23/03/2018 2 ISSUED FOR 90% DESIGN SUBMISSION SCALE
1 : 75 CHECKED J.P.
STORM WET WELL PLAN - EL. -2.914m
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 19/01/2018 1 ISSUED FOR 50% DESIGN SUBMISSION
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-101 7 OF
2 3 4 5 H 6 7 8 9
G J
S-310 S-311 L
S-312
S-314

N
31981

5486 12802 6706 7900 6025 8800 2150

457 3949 457 4052 457 4052 457 3951 457 500 6206 500 24375 400
1' - 6" 12' - 11 1/2" 1' - 6" 13' - 3 1/2" 1' - 6" 13' - 3 1/2" 1' - 6" 12' - 11 1/2" 1' - 6" Sim
1500 2250 2250 2250 2250 2250 2250 2250 2250 2250 2250 2250 2250 2250 1
A S-201
CONC.
FILLER

400

400
A1

1000
F 500 CONC WALL
19' - 9"
6020

PUMP ROOM

1870
WATERPROOFING
M S-309

2550
S-315 1200mm THK .
1500 1200 CONC. SLAB

3805
1600 UP EL. -1.000 m
500mm DEEP SUMP

900
4820
UP
SEE TYP. DETAILS.

5850
900 5600 900 3057 762 SEE NOTE -2 CONC.

900
B PIPE SEE DWG. S-507 FOR
(TYP.)
SUPPORT STAIRS DETAILS (TYP.)
NATIVE
BACKFILL

1500
300 5725 3325 3035

9100
500
1 6206
30' - 9"
9373

S-702
CONC. CONC. C1 EL. -0.850 m C1 C1 C1

1935
2000

900
PIPE PIPE
SUPPORT SUPPORT 150mm THK . CONC

500
EQUIPMENT PAD
EL. -0.448

5300
EL. -.850m

4280
CONC. SEE DWGS S201 AND 202

1492

1550
BASEMENT ROOM PIPE FOR STEEL SUPPORT AND

2750
SUPPORT PLATFORM DETAILS (TYP.)

2550
1500 1100
1200
100X50mm DEEP GUTTER
12040 900 DRAIN ALONG FOOT OF
1050 A2
A1 500mm DEEP SUMP ALUM. GRATING ALUM. LADDER S-302

1300
1758 1200 13806 WALL, 1% SLOPE TO
EL. -0.448 m UP SUMP PIT (TYP.) SEE TYP. DETAILS. PLATFORM
S-301

200

500

500
B1
SANITARY WET WELL

21351
CONC. BENCHING 1500
SEE SECTION OPEN TO BELOW
1677 WASTEWATER CHANNEL ALUM. GRATING
3821

2621
500mm THK . CONC. EL. 1.559 PLATFORM
SEE NOTE -2 SLAB BELOW S-203
2 EL. -0.448 m EL. 1.559
600mm THK. SLAB B2
B1 8 S-702 ALUM.
1677

SUMP EL. -2.914m


S-303 LADDER S-304
S-701
600

601
6' - 6"

500
1981

OPEN TO BELOW
B2

6792
ALUM.
C STAIRS EL. 1.559
1534 SEE NOTE 1 NATIVE

1965
2 (TYP.) 834 75mm LEGGING
2415 300 2115 649 2115 300 2300 295
S-702
C2 BACKFILL TEMP. SHORING
C1 BY CONTRACTOR C2
10' - 0"

TRAY GRIT TRAY GRIT C2


3048

S-305 MASS CONCRETE S-306


STORM WET WELL

500

500
EX. TRENCH BELOW SEPARATOR SEPARATOR 156.3 C2

11351

5182 5182 SEE NOTE 2 10100
R10

1524
17' - 0" 17' - 0" (TYP.) 00 SCREEN

457
T/O WALL EL. 2.439
D 156.3

300
5639 305 5182 457

7773
18' - 6" 1' - 0" 17' - 0" 1' - 6" 3996 D1
30 5
30

849
5 5 1255 900 1255 900 1255 900 1255 300
30

2000
400 600 2000 4300 400mm THK .

5364

1524
12' - 3"

45 CONC. SLAB
3734

7 D

300

700
34' - 0"

2650
10363

SCREEN EL. 0.439 m


S-307

300
D2
2

200
400mm THK . EL. 0.439 m

200
ALUM INLET STORM CHANNEL CONC. SLAB

1560

1560
S-702 LADDER
1' - 0"

400 22674 700


305

E
34' - 6"
10516

S-308

400

400
1524 3962 1524 4271
1524

5' - 0" 13' - 0" 5' - 0" 14' - 0"


305 D3
457
4191
10' - 9"

1200 2800 1200 3000 2500 3000 2000 3000 1200 2825 4166
3276

5' - 0"
1524

EX. INLET SANITARY CHANNEL


1524
1' - 0"
305

2500
2
305

S-104
EX. OVER FLOW CHANNEL WEIR PLATE,
2' - 3"

2' - 3"
686

686
24/09/2018 6:55:47 PM

SEE PROCESS DWGS


7' - 10 1/2"

15 - 0"
24
1143

5'

38
2404

1866 50
1' - 0"
305

1' - 0"
305

305 2765 PIPE OPNG.

E
3' - 9"
1143

457
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

6' - 2 1/2"

21793
1890

2490

71' - 6"
23223

1533
76' - 2 1/2"

305
1' - 0"
305

1524 305 6325 2223 NOTES:


5' - 0" 1' - 0" 20' - 9" 1. ALL CONCRETE SURFACE OF WET WELL AND NEW CHANNEL (BASE SLAB, WALLS, ROOF SLABS, NEW 1500 STORM
305 3404 305 700 457 8154 305 6197 BEAMS, AND COLUMNS) TO BE PROTECTED BY TWO COATS OF PROTECTIVE COATING - CEM-KOTE K CONNECTION
1' - 0" 11' - 2" 1' -2'0"- 3 1/2"
1' - 6" 26' - 9" 1' - 0" 20' - 4" OR APPROVED EQUAL (SEE SPECIFICATIONS) S-313
2. 15M@900 EW MAX C/W HILTI HY200 EPOXY, EMBED 150.
LOWER LEVEL PLAN 1
S-105
1 : 75
MR 24/09/2018 11 ISSUED FOR CONSTRUCTION
VERIFY SCALES
MR 19/07/2018 10 REISSUED FOR CONSTRUCTION - CAISSON WALL
DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM
BAR IS 20mm ON MR 15/06/2018 9 ISSUED FOR 100% DESIGN SUBMISSION SURVEYED
MR 16/05/2018 8 ISSUED FOR CONSTRUCTION - CAISSON WALL
CLOVER POINT PUMP STATION
20mm MR 26/03/2018 7 ISSUED FOR PRE-CONSTRUCTION REVIEW - CAISSON WALL DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 23/03/2018 6 ISSUED FOR 90% DESIGN SUBMISSION SCALE
1 : 75 CHECKED J.P.
LOWER LEVEL PLAN - EL. -1.000m
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 02/03/2018 5 ISSUED FOR CONSTRUCTION - CAISSON WALL
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-102 11 OF
F G H J L
2 M 3 S-309 4 S-310 5 S-311
6 7 S-312 8 S-314 9
S-315
31981

6706 7900 6025 8800 2150


5486 12802
18' - 0" 42' - 0" 500 6206 500 24375 400
CONC. CORBEL TO SUPPORT
3750 2250 4675 400 4100 400 4100 400 4100 400 5800 BRIDGE CRANE (TYP.) UPTO
A GRID-8
19975
CONC. FILLER
SLAB OPENING
EX. WASH ROOM FOR PIPE PENETRATION
SEE PROCESS DWGS.

3
EX. LUNCH ROOM
S-105
EX. MOTOR CONTROL EX. TRANSFORMER A1
400mm THK.

770
CENTRE ROOM

400
ø 110 00
19' - 9"

0 CONC. SLAB 12
6020

CONC. PIPE
4509 4509 CONC. EL. 3.909 m SUPPORT ø
ø 1
14' - 9 1/2" 14' - 9 1/2" 1000X1000 75 CORBEL (TYP.)
300 0 900 S-107
OPENING COVERED ABOVE
BY CHECKER SLAB SLAB OPENING
PLATE OPENING UP EL. 5.909 m UP
EL. 3.609 m
CONTROL B14 B15 B16
SEE NOTE -1 2745 B12 B13 900MMØ
ROOM

970
(TYP.) 400 CAISSONS

B19

B19

B19

B19
B (TYP.)
400

9100

9100
4025
1 OPEN

9600
150mm THK. OPEN C1 C1 C1 C1 STEEL ACCESS
BELOW

4480
S-702

1593
CONC. PAD BELOW LADDER
EL. 4.059 SEE STD. DETAIL
GENERATOR
ROOM Sim
6050 1000 1522 OPEN 1.
FOR PLATFORM HEIGHTS BELOW
AND DETAIL SEE DWG GUARD RAIL (TYP.) S-202
FOR PLATFORM HEIGHTS

B18

B18

B18

B18
1219 1216 1219 1216 1219 1216 1219 3000 615 2130
1772

S-202 (TYP.) SEE STD. DETAIL


AND DETAIL SEE DWG
NEW 190mm S-202 (TYP.)
THK CMU WALL
TRANSFORMER ROOM B13 B14 B15 B16

B17
UP DN
A2

1219
ENCLOSURE 6700 400mm THK.
DN
A1 CONC. SLAB S-302
30' - 9"
9373

S-301 EL. 3.909 m


1400 2051 2400 2450

450
FILL EX. OPENING WITH 35mPa 400mm THK

2700
CONCRETE AND 20m @250 EQUIPMENT PAD

500

500
DOWELS T&B EW. MAKE GOOD
SURFACE TO MATCH EXISTING EL. 3.609 m EL. 3.759 B1
500 3165 3000 891 1400 14324 1400 855 75mm LEGGING

1100

21351
1500 TEMP. SHORING
CORRIDOR 1255

B6

B7
NEW 190mm 300mm THK. B3 B4 B5 BY CONTRACTOR

2180
THK CMU WALL

190
SLOPE CONC. SLAB

400
10720
ENCLOSURE

3121
EL. 3.909 m
1000 AHU

1330
DN
B1 6606 ROOM B2

2000
2000
541
1:20

2500

2500
S-303 STORM S-304
1200

EXIT

1093
SLOPE EL. 4.059 WETWELL

3206

3206
EL. 3.609

400
CORRIDOR DN
WET WELL ALUM. GUARDRAIL BELOW

1170
ACCESS ROOM c/w SAFETY CHAIN B2
C 2300 B11

1375
2420 190 4390 190
6' - 6"

1' - 6"
3505

996
1981

457
4572 ANCHOR CHECKER PLATE TO EXISTING B1 B2 B4 B5

1500
1829

4844 1000 3950

190

B8

B9
CONCRETE AT THIS EDGE BY 16Ø HILTI W250x85
C1 W250X58 W250X58 HIT-HY200 ADHESIVE ANCHORS, 125mm (TYP.) C2
C2

3054
1172 3000 1015

873
C2

4221
S-305 EMBEDMENT. ALL ANCHORS TO BE GALV. S-306

10951
C2
5186
4165

5080

1500

9851
1000
1224 300mm THK. 7.5 TONNE SEE DWG S-204

1524
W250X58 W250X58 CONC. SLAB TELESCOPIC FOR SUPPORT
R

20' - 0"
D

6096
1219 1219 948 B10 EL. 3.909 m MONORAIL FRAMING
S-316 ODOUR CONTROL &

3400
WASTEWATER GRIT 250 SCREENING ROOM
1500

457

6971
SEPARATOR & SCREENING 915 D1
W250X58 W250X58 150mmTHK.
ROOM

2890
2838

EQUIP. PAD

1524

2050
6059

D EL. 4.059 m
1728

915
GALV. STEEL S-307
BEAM (TYP.)
D2

945
457
300mm THK.
SHEAR WALL (SHOTCRETE) 2079 1552 300mm THK. CONC. SLAB 20mm CONSTRUCTION

1960
THICKENING (200) R/W CONC. SLAB EL. 3.909 m JOINT TYP.

915
E EL. 3.909 m
34' - 6"
10516

20M@200 EW EF

75
1826
16mm THK. 942 S-308

400
GALV. CHECKERED
D3

3' - 0" 2' - 0"


PLATE (TYP.)

914 610

400
5918
2335 3000 4090 1000 1350 2400 1400 1435

EL. 3.759 m EL. 3.609 m


NEW RETAINING WALL

4058

2400
SEE DWGS. S-104 AND
4000

S-108
ACCESS HATCH 915x915
9' - 0"
2743

305
1.5 HR FIRE RATED HATCH C/W
HINGED SAFETY GRATING OR
APPROVED EQ. (TYP. OF 2)
18751
24/09/2018 6:55:50 PM

152

400 7200 300 NEW RETAINING WALL


SEE DWGS. S-104 AND S-108
E 8200

457
1' - 6"
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

FOR CONTINUATION SEE DWG. S-104 FOR CONTINUATION SEE DWG. S-104
K
S-313

UPPER LEVEL PLAN


1 : 75

NOTES:
1. 15M@900 EW MAX C/W HILTI HY200 EPOXY, EMBED 150.

VERIFY SCALES DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM


BAR IS 20mm ON SURVEYED
CLOVER POINT PUMP STATION
20mm DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 24/09/2018 2 ISSUED FOR CONSTRUCTION SCALE
1 : 75 CHECKED J.P.
UPPER LEVEL PLAN - EL. +3.909
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 02/02/2018 1 ISSUED FOR CAISSON WALL TENDER
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-103 2 OF
4 5 6 7 8 4 9
S-108

300 1160 300 2800

2590
914 FOR CONTINUATION SEE DWG. S-103
3' - 0"
EL. 3.909 m

300 945 300


D3

3' - 0" 2' - 0"


914 610

4' - 6"
1372

2800
4058
1700 2720 3065
2100
686 600 2335 3000 4090 1000 1350 2400
3 NEW RETAINING WALL FOUNDATION

9' - 0"
2743
2' - 3"
7200 S-104 ELEVATION MATCH EXISTING RETAINING WALL
AT THIS LOCATION. NEW RETAINING WALL

963

7030
HORIZONTAL REBARS TO DOWEL INTO

305
EXISTING FOUNDATION/WALL, FULLY EPOXY

25 mm
C.J.
GROUTED, 125mm EMBEDMENT.

0
R-157
1
E

2000
8200

00
33
5' - 0"
1524

R
EL. 4.009
400mm CONC. SLAB
2750

5280

5255
1 1
S-108
2350

9780 400 RETAINING WALL PROFILE 'R2'


SEE DWG S-108
2
1
S-104

° 18.0

900mm CAISSON
W410X114 SOCKET INTO
.00

BEDROCK 1.5m DEEP.


18

GROUTED WITH 35MPa


CONCRETE.
2

'R1'

UPPER LEVEL - RETAINING WALL


.0

5
18

G S OFILE
D3 D2
R-

S-108
1 : 75
R7

-1 0 8
R
430

S EE W AL L P

10235
3

DW
TOPSOIL
R- R

T/O RETAINING WALL

NG
9780

GRADE ( REFER TO CIVIL DWGS) 11.800 m


AINI

820
FOR DETAIL
PROFILE SEE ARCH .
RE T
4 REF. ARCH DWGS.
DWGS FOR DETAILS ROOF PUMP ROOM
EL. 2.609 10.902 m
ROCK T/O WALL EL. 9.600
445 T/O WALL EL. 10.000
ANCHORS
300mm WALL EXTERIOR FINISH
R/W 15M @300 HVEF REF. ARCH DWGS.
350mm THK. TAPERED DRAIN 300mm WALL
CONC. SUPPORTING
EX. POINT 'A'

TOPSOIL R/W 15M @300 HVEF


WALL (TYP.)

820
CONSTRUCTION GRADE
JOINT (TYP.)
EXISTING PROFILE
WALL TO REMAIN 300mm THK.
CONC. WALL
400mm THK. CONC.
WALL
NILEX NUDRAIN WD10 OR
GEOFOAM
EQUIVALENT BEHIND ALL
BACKFILL
9175 RETAINING WALL (TYP.)

GEOFOAM BACKFILL
20M @200 HEF NILEX NUDRAIN WD10 OR
400mm THK. EQUIVALENT BEHIND ALL
CONC. WALL 15M @200 VEF
6"Ø DRAIN PIPE c/w 6'' FILTER RETAINING WALL (TYP.)
25M @200 HEF ALL AROUND, TO MATCH AND
CONNECT TO EXISTING
6"Ø DRAIN PIPE c/w 6'' FILTER
20M @200 VEF ALL AROUND, TO MATCH AND
CONNECT TO EXISTING
4X2-25M
BOTTOM HORZ. UPPER LEVEL - NEW PUMP ROOM
CONTINOUS EARTH TO BE STABLIZED
T/O OF ASPHALT 3.759
20M @200 (VERIFY WITH CIVIL DWGS) 3.909 m

45.
TBEW BY GEOGRIDS

00°

45.
400

00°
EXG MOTOR RM & WET WELL FLOOR EXG MOTOR RM & WET WELL FLOOR
24/09/2018 6:55:50 PM

3.609 m 3.609 m
900mm DIA. CAISSON,
W410x114SOCKETED
TO BEDROCK, 1500mm 400 1700 (TYP.) EXISTING CHANNEL EARTH BACKFILL TO
DEEP, GROUTED WITH BE STABLIZED BY GEOGRIDS.
(TYP.)
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

35MPa CONCRETE EXISTING PIPE


DESIGN LOAD FOR ROCK ANCHORS (UNFACTORED)
20M @200 TLL BUL
CAISSON SHEAR FORCE TENSILE FORCE
20M @200 TUL
(HORIZONTAL) (FOR ROCK ANCHORS)
25M @150 BLL
1 2110 kN 2890 kN
EXG INLET CHANNEL INVERT EXG INLET CHANNEL INVERT

400
2 1682 kN 1945 kN 0.439 m 0.439 m

3 1362 kN 1336 kN 400 2590

4 1100 kN 910 kN 2 SECTION 3 SECTION


S-104
1 : 50 S-104
1 : 50
MR 24/09/2018 10 ISSUED FOR CONSTRUCTION
VERIFY SCALES
MR 19/07/2018 9 REISSUED FOR CONSTRUCTION - CAISSON WALL
DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM
BAR IS 20mm ON MR 15/06/2018 8 ISSUED FOR 100% DESIGN SUBMISSION SURVEYED
MR 16/05/2018 7 ISSUED FOR CONSTRUCTION - CAISSON WALL
CLOVER POINT PUMP STATION
20mm MR 23/03/2018 6 ISSUED FOR 90% DESIGN SUBMISSION DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 02/03/2018 5 ISSUED FOR CONSTRUCTION - CAISSON WALL SCALE
As indicated CHECKED J.P.
UPPER LEVEL - RETAINING WALL
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 02/02/2018 4 ISSUED FOR CAISSON WALL TENDER
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-104 10 OF
6

2 M 3 4 5
S-315

N
190 5000 457 500 6206 500

F G
S-309 S-310

700
1150
1300

EQ
4' - 3"
W310X60 W310X60 W310X60

400
3

2000
FUEL
S-105 STORAGE
A1

EQ
16' - 8"
ROOM-2
5080

3000

2000
W310X60 T/O OF PLATFORM EL. 7.409

590
EL. 6.825
DN

EQ
2000
W310X60 W310X60 W310X60
CORBEL EXTENDED OVER
FUEL PLATFORM
1515

B STORAGE

EQ
DN ELEC. RM ACCESS/BRIDGE CRANE
ROOM-1
MAINTENANCE PLATFORM

9100
1

1664
S-702 17374 ELECTRICAL
ROOM

7100
300mm THK.
REMOVABLE GUARDRAIL, BOLTED TO CONC. SLAB
8572 114mm CONC. SLAB OVER WALL WITH ADHESIVE ANCHORS.
38mm STEEL DECKING PROVIDE P.ENG STAMPED SHOP DWGS
W310x39

W310x39

EL. 7.409
FOR REVIEW AND APPROVAL (TYP.) BRIDGE CRANE
CORBEL SUPPORT
3603 GENERATOR ROOM (TYP.)

A1 BELOW
S-301 W310x28 38mm THK. GALV. 3000
STEEL GRATING 114mm CONC. SLAB OVER

500

500
38mm STEEL DECKING
SILENCER AND EXHAUST FAN
WEIGHT 26kN B1
W310x28

300mm THK.

2721

2721

2721
10530
CONC. SLAB
W310x28 EL. 6.825 LADDER
B1 SEE STD. DETAIL
1390

S-303 T/O ROOF EL. 6.837


1200

CORRIDOR
W310x28

400

400
BELOW
B2
C 8 9

5600

6706 400

SEE DWG S-102 FOR CONTINUATION

MEZZANINE LEVEL
1 : 75 D3

250 LG DOUBLE ANGLE CLIP


L102x102x6.4 BOLTED BY 3-20Ø MODIFIED OPENINGS
A325 BOLTS SEE SECTION-3 ON D-103
FOR OPENING SIZE
EXISTING SLAB NON-SHRINK DRY
PACK GROUT EXG MEZZANINE LEVEL
NEW WEIR
6.825 m

1524
SEE PROCESS DWGS

2
S-104
75

W310X60 W310X60 MASS CONCRETE FILL


75

TO DIRECT THE FLOW EXISTING PIPE


OF WATER

EXISTING BEAM PL 350x300x20


WALL PLATE
24/09/2018 6:55:53 PM

4-25M HILTI HIT-HY200 ADHESIVE ABANDONED EXISTING


ANCHORING, 150mm MIN. EMBEDMENT. STORM PIPE
SPACING OF ANCHOR: 175mm c/c V
100mm c/c H

CAISSON FOR RETAINING WALL


S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

300mm THK. NEW CONC. WALL SEE DWG. S-104


R/W 15M@200 HVEF, 15M NEW PIPE CONNECTION
BARS TO BE DOWELLED INTO SEE SECTION-2 ON DWG D-103
EXISTING CONCRETE WALL
BY HILTI HIT HY200 ADHESIVE
3 SECTION ANCHORING SYSTEM MAKE
GOOD SURFACE, APPLY NEW
NEW PIPE

SEALENT OR COATING AS NOTE:


S-105
1 : 10 SPECIFIED. 1. SEE PROCESS DWGS FOR PIPE SIZES.

1 NEW STORM CONNECTION - LOWER LEVEL


S-105
1 : 50

MR 24/09/2018 10 ISSUED FOR CONSTRUCTION


VERIFY SCALES
MR 19/07/2018 9 REISSUED FOR CONSTRUCTION - CAISSON WALL
DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM
BAR IS 20mm ON MR 15/06/2018 8 ISSUED FOR 100% DESIGN SUBMISSION SURVEYED
MR 16/05/2018 7 ISSUED FOR CONSTRUCTION - CAISSON WALL
CLOVER POINT PUMP STATION
20mm MR 26/03/2018 6 ISSUED FOR PRE-CONSTRUCTION REVIEW - CAISSON WALL DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 23/03/2018 5 ISSUED FOR 90% DESIGN SUBMISSION SCALE
As indicated CHECKED J.P.
MEZZANINE LEVEL PLAN - EL. +6.825
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 15/02/2018 4 ISSUED FOR PRECAST ROOF SLAB
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-105 10 OF
2 3 4 5 6 7 8 9

N
G J K
H S-312
L
S-310 S-313 S-314
S-311
EXIST NEW 1.5 TONNE MONORAIL
(S250X38) BETWEEN
DOUBLE TEE RIBS
(CENTERED)
32756
A
6706 13925 8800 2150

CL DRAG STRUT

180
EXISTING
VENT A1
TYP 6
3 S-701
S-701
DRAG STRUT HSS127x127x7.9 T/O WALL EL. 12.300
DESIGN HORIZONTAL DIAPHRAGM ACCESS HATCH
LOAD (UNFACTORED)

150kN/m (E-W)
DIAPHRAGM
FORCES (TYP.)
B

0.5% SLOPE OF CONC. TOPPING (TYP.)

10625
350mm THK 100kN/m (N-S)
CONC. SLAB

9600
CAST IN PLACE PRECAST DOUBLE TEE 3120x721 DEEP
c/w MIN. 100mm THICK CONCRETE
EL. 10.902m TOPPING AND 152x152mm
25.8X25.8mm WELDED WIRE FABRIC.
EL. 10.902 M

EXHAUST STACK SUPPORT


DETAILS TO BE PROVIDED
BY SUPPLIER 300 300 A2
A1 SEE D-103 SEE STRENGTHENING S-302
BEAM DETAIL

200
S-301

300
TYP 6 B1
75mm LEGGING
CL DRAG STRUT

0.5% SLOPE OF CONC. TOPPING (TYP.)


3 S-701 TEMP. SHORING
ROOF BEAM BELOW
S-701 BY CONTRACTOR
3000 RB3 350x900
RB1 RB2

2821
DRAG STRUT HSS127x127x7.9
RB3 305mm THICK PRECAST CORESLAB
c/w MIN. 100mm THICK CONCRETE
B1 TOPPING AND 152x152mm B2

300
S-303 25.8X25.8mm WELDED WIRE FABRIC. S-304
240kN/m (E-W)
B2
C 195kN/m (N-S)
T/O WALL EL. 11.702
EL. 9.988 M
C1 C2
S-305 S-306

11201
RB4 RB5 RB6

D 305mm THICK PRECAST CORESLAB

0.5% SLOPE OF CONC. TOPPING (TYP.)


c/w MIN. 100mm THICK CONCRETE
TOPPING AND 152x152mm
EL. 10.000m 25.8X25.8mm WELDED WIRE FABRIC.
D1
240kN/m (E-W)

D 195kN/m (N-S)
S-307
EL. 9.988 M
D2
1.0 TONNE MONORAIL
(S200x34) ATTACHED TO
E RB7
UNDERSIDE OF
HOLLOWCORE SLAB
S-308

300
D3

99
14
250mm THK 1.0 TONNE

R
CAST-IN-PLACE MONORAIL (S200x34) 20mm EXPANSION
CONCRETE SLAB ATTACHED TO CORE JOINT
EL. 9.364m EL. 9.888 M SLAB, SEE STD. DETAIL
24/09/2018 6:55:55 PM

E
EL. 9.126 M

EL. 9.126 M 250mm THK SEE CIVIL DWGS


NOTES:
EXISTING ROOF CAST-IN-PLACE FOR TOP SURFACE
2 CONCRETE SLAB
DOUBLE TEE ROOF SLAB AREA,
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

S-320 LIVE LOAD ON ROOF: 12.0 KPA, CL800 (80 TONNE) TRUCK
GEOFOAM AND LANDSCAPING TOP SOIL ON ROOF: 6.0 KPA
100MM CONCRETE TOPPING: 2.4KPA.
ELECTRICAL/MECHANICAL ALLOWANCE: 1.5KPA.
SELF WEIGHT OF DOUBLE TEE IS EXCLUDED IN THE LOADING ABOVE.

HOLLOW CORE ROOF SLAB AREA,


LIVE LOAD ON ROOF: 12.0 KPA, CL800 (80 TONNE) TRUCK
GEOFOAM AND LANDSCAPING TOP SOIL ON ROOF: 6.0 KPA
3 6712 100MM CONCRETE TOPPING: 2.4KPA.
S-320 ELECTRICAL/MECHANICAL ALLOWANCE: 1.5KPA.
12951 SELF WEIGHT OF CORE SLAB IS EXCLUDED IN THE LOADING ABOVE.

ROOF PLAN 4 1
S-320 S-320

MR 24/09/2018 10 ISSUED FOR CONSTRUCTION


VERIFY SCALES
MR 19/07/2018 9 REISSUED FOR CONSTRUCTION - CAISSON WALL
DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM
BAR IS 20mm ON MR 15/06/2018 8 ISSUED FOR 100% DESIGN SUBMISSION SURVEYED
MR 16/05/2018 7 ISSUED FOR CONSTRUCTION - CAISSON WALL
CLOVER POINT PUMP STATION
20mm MR 26/03/2018 6 ISSUED FOR PRE-CONSTRUCTION REVIEW - CAISSON WALL DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 23/03/2018 5 ISSUED FOR 90% DESIGN SUBMISSION SCALE
1 : 75 CHECKED J.P.
ROOF PLAN - EL. +10.902
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 15/02/2018 4 ISSUED FOR PRECAST ROOF SLAB
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-106 10 OF
A1 9 A1
S-107
8 9 15M @300 DOWELS
PILE CAP, 2250 (MAX.) TYP. 2250 15M @300 DOWELS 150 1025
SEESECTION 3-15M (CONT.) 8-25M (CONT.) 3-15M (CONT.)
EXTERIOR 150 150 REMOVE EXISTING CONCRETE ON CAISSON 8-25M (CONT.) 1025
W610x217
MIN. MIN. WALL AS SHOWN AND WATER BLAST INTERIOR 100 CONC. TOPPING
(TYP.) WATERPROOFING
SURFACE OF SECANT WALL TO REMOVE SOIL 100MM CONC. TOPPING WATERPROOFING OVER DOUBLE TEE
900mmØ SECANT CAISSONS (TYP.)
AND CONC. DEBRIS. OVER DOUBLE TEE
ROOF PUMP ROOM ROOF PUMP ROOM
10.902 m 10.902 m
CONC.

775
PILE CAP CONC.
PILE CAP

900

900
8-25M (CONT.)

650
125

275 125
150

400

80
A1 8-25M (CONT.)
INTERIOR PRECAST DOUBLE 2-10M @300

300

300
PRECAST DOUBLE 2-10M @300 TEE 3120x720 STIRRUPS
TEE 3120x720 STIRRUPS
ADDITIONAL 20M CONT.
20M @200 VEF 3-15M, 2000mm LONG
PRIMARY 4-15M, 2000 LONG BETWEEN KING PILE
4 25M @150 HEF BETWEEN KING PILE 400mm THK.
CAISSON
CONC.WALL

2250 (MAX.) (TYP.)


S-107
400mm THK.
P CONC.WALL 900mmØ 900mmØ
275 125 CAISSON PILE CAISSON PILE
S-107
EXTERIOR 20M DOWELS WELDED TO 400
FLANGE OF KING PILE AT W610
W610 SPACING OF 400mm KING PILE @2.25m
400
SLAB OPENING KING PILE @2.25m VERTICALLY ALL THE WAY
FOR PIPE DOWN TO BOTTOM
ELEVATION OF PUMP ROOM
BASE SLAB.

MIN.
150
(SEE DETAIL-4 ON S-107)

N SECTION W610 KING PILE

400
WELD 20M, DOWELS WITH END HOOKS
ONTO W610 @400 c/c VERT. FULLY WELDED TO W610
S-107
1 : 20
FLANGE . TIE DOWELS TO WALL REINFORCEMENT
SECURELY. REMOVE ANY COATING, RUST, DEBRIS OR
CONTAINMENTS BY GRINDER PRIOR TO WELDING
THE DOWELS.
25M @150 HEF
20M @200 VEF
W610X217 LOWER LEVEL- NEW PUMP ROOM
N
S-107 FLANGE TYP. -1.000 m
B-U4a-FC

(TYP.)
6
B

1 UPPER LEVEL PART PLAN 450X450X12


SPLICE PLATE
S-107
1 : 25

DETAIL - SPLICE OF KING PILES


1 : 20 (CONNECTION DETAILS BY OTHERS)

NOTE:
SPLICE LOCATION SHOULD BE WITHIN A RANGE FROM
ELEVATION 5.1m TO 8.88m TO AVOID HIGH SHEAR STRESS.
300

W610

A1
10(4) 250 150 250 BEDROCK PROFILE P SECTION
DOUBLE FLARE BEVEL (GROOVE) TO BE CONFIRMED ONSITE
WELDS FULLY WELDED
10(4) S-107
1 : 20
TO W610 FLANGE TYP.

4 DETAIL
S-107
1 : 25
24/09/2018 6:55:58 PM

2000 MIN.
TYP.
FULLY GROUTED TO SOUND
BEDROCK BY GROUT/CONCRETE
HAVING UNCONFINED
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

COMPRESSIVE STREGNTH EQUAL


OR GREATER THAN 35MPa PER
GEOTECHNICAL REPORT.

DETAIL - KING PILE SOCKET


1 : 20 (IF SPLICE CANNOT BE AVOIDED)

MR 24/09/2018 8 ISSUED FOR CONSTRUCTION


VERIFY SCALES
MR 19/07/2018 7 REISSUED FOR CONSTRUCTION - CAISSON WALL
DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM
BAR IS 20mm ON MR 15/06/2018 6 ISSUED FOR 100% DESIGN SUBMISSION SURVEYED
MR 16/05/2018 5 ISSUED FOR CONSTRUCTION - CAISSON WALL
CLOVER POINT PUMP STATION
20mm MR 26/03/2018 4 ISSUED FOR PRE-CONSTRUCTION REVIEW - CAISSON WALL DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 23/03/2018 3 ISSUED FOR 90% DESIGN SUBMISSION SCALE
As indicated CHECKED J.P.
CAISSON PILES - DETAILS
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 02/03/2018 2 ISSUED FOR CONSTRUCTION - CAISSON WALL
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-107 8 OF
GROUND
T/O RETAINING WALL 250

2' - 3 1/2"
11.800 m

700
DRAIN PIPE 100 150
SEE CIVIL DWGS
10.400

2' - 7"
787
T/O WALL EL. 9.400
TOP OF ASPHALT 3.759

4' - 0"
1219
6"Ø DRAIN PIPE C/W 6"
FILTER ALL AROUND
T/O WALL EL. 8.400

EXG LOWER ROOF


8.364 m
T/O WALL EL. 7.398

T/O WALL EL. 6.400 T/O WALL EL. 6.725

1 SECTION
T/O WALL EL. 5.400
S-108
1 : 20
EXISTING T/O WALL EL. 4.546
WALL
PROFILE NEW WALL T/O WALL EL. 4.859
PROFILE
T/O OF ASPHALT EL. 3.759
2' - 7"
787

250

EXG MOTOR RM & WET WELL FLOOR


3.609 m

RETAINING WALL PROFILE 'R1'


1 : 50

T/O WALL EL. 6.725 300mm CONC.


WALL
D3
15M @200 VEF
20M @ 200 HEF

CONC. WALL 350mm

SEE CIVIL DWGS FOR T/O WALL EL.


T/O RETAINING WALL R/W 15M @20 H.V.E.F
T/O WALL EL. 11.100

HEIGHT OF WALL VARIES


2' - 3 1/2"

11.800 m
700

NILEX NUDRAIN WD10 OR


EQUIVALENT BEHIND ALL
RETAINING WALL (TYP.)

EARTH BACKFILL
T/O WALL EL. 9.600

400
6"Ø DRAIN PIPE c/w 6'' FILTER
CONSTRUCTION JOINT ALL AROUND, TO MATCH AND
CONNECT TO EXISTING
TOP OF ASPHALT
T/O WALL EL. 8.100
EL. 3.759

EXG MOTOR RM & WET WELL FLOOR


2"
- 3 00
1/
7

3.609 m
T/O WALL EL. 6.600 CABLES TO ROCK
2'

ANCHORS BY OTHERS
24/09/2018 6:55:59 PM

CONSTRUCTION 15M @200 T.B.E.W


JOINT
EL. 3.959
1 TO MATCH EXISTING CHANNEL
T/O WALL EL. 4.396 FOUNDATION ELEVATION

400
S-108
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

UPPER LEVEL - NEW PUMP ROOM MATCH TO


3.909 m EXISTING WALL
PROFILE
3' - 1"
937

TOP OF
ASPHALT
EXG MOTOR RM & WET WELL FLOOR 2000
2771
3.609 m

4 RETAINING WALL PROFILE 'R2' 5 SECTION


S-108
1 : 50 S-108
1 : 25

VERIFY SCALES DESIGNED RL CORE AREA WASTEWATER TREATMENT PROGRAM


BAR IS 20mm ON SURVEYED
CLOVER POINT PUMP STATION
20mm DRAWN SR DATE 02/02/2018 STRUCTURAL
MR 24/09/2018 2 ISSUED FOR CONSTRUCTION SCALE
As indicated CHECKED J.P.
RETAINING WALLS - PROFILES
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 15/06/2018 1 ISSUED FOR 100% DESIGN SUBMISSION
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-108 2 OF
B
1 S-200 2 B
1 S-200 2

6360
1
380 5600 380 1098
6360
1700 190 1820 190 1700
5600

750 1175 750 1010 750 1175 750 750 5.640 m


500
750

380

500
750
A
U/S OF CORESLAB
935

7.840 m

1710
140mm FULLY GROUTED
SLAB EDGE CONCRETE BLOCK WALL,
THICKENING CONNECTED TO EXTERIOR
750

LOAD BEARING WALL BY


4930

MASONRY CONNECTORS

190
4400

500

4930
5.440 m

4400
RIGID INSULATION TO
250mm THK. SLAB ON GRADE EXTEND 500mm 150mm THK. SLAB ON GRADE
A T/O OF WALL 5240.00
T/O CONC. 5.040 m FINISHED FLOOR
S-200 A A

700
5.040 m
S-200 S-200
5.240 m

B
C
B

540 150
FOUNDATION

740
740

S-200 WALL C
T/O CONC. 5.040 m
S-200 150mm THK. SLAB ON GRADE

380
380 5.240 m 380

B
S-200 B
S-200 C SECTION
FOUNDATION PLAN -
1 : 50
1 : 50
FLOOR PLAN @ GROUND FLOOR
1 : 50

A B 1
1 2 390

R/W 15M@250 HVEF


JOINT FILLER C/W WITH SEALANT

150 TO 600mm
ON FINISH FLOOR SURFACE
203mm HALLOW CORE SLAB WITH
203mm HALLOW CORE SLAB WITH TYPICAL ALL AROUND SLAB ON
100mm CONCRETE TOPPING AND
100mm CONCRETE TOPPING AND GRADE
152x152mm, 25.8x25.8 WELDED WIRE

SEE PLAN (VARIES)


152x152mm, 25.8x25.8 WELDED WIRE
FABRIC (TYP.)
FABRIC (TYP.)

U/S OF CORESLAB U/S OF CORESLAB


15M@250
7.840 m 7.840 m TBEW
190mm FULLY REINFORCED AND
190mm FULLY REINFORCED AND GROUTED CONCRETE BLOCK 15M @ FINISHED FLOOR

450
GROUTED CONCRETE BLOCK 15M @ 200 VERT. 2-15M BOND BEAM AT TOP
FILE PATH: S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\0.0 Xref\BIM\Clover Pt SPS_MEP_R15.rvt27/07/2018 5:11:37 PM

5.040 m

250
200 VERT. 2-15M BOND BEAM AT AND MID HEIGHT OF WALL. LADDER
TOP AND MID HEIGHT OF WALL. REINFORCEMENT EACH COURSE 2-
LADDER REINFORCEMENT EACH 3.66 @200
COURSE 2-3.66 @200 STEPPED FOOTING 15M@200 15M @250 TBEW
CONSTRUCTION STIRRUPS

200
JOINT 5040.00
75 665 3-15M BOT. 500
500 CONTINUOUS
500
450

250mm S.O.G R/w


600
600

15M @250 TBEW (TYP.)

200
FINISHED FLOOR RIGID INSULATION FINISHED FLOOR

150
TO EXTEND BEYOND SLAB UNDERSLAB SHEET WATERPROOFING
5.040 m 5.040 m
MEMBRANE
50mm RIGID INSULATION (TYP) 75mm INSULATION, EMBEDDED 50mm RIGID INSULATION (TYP)
75mm INSULATION, EMBEDDED IN CONC. AS SHOWN (TYP.)
IN CONC. AS SHOWN (TYP.) 380 500 BELOW GRADE INSULATION
MIN. R-10 (TYP.)
UNDERSLAB SHEET WATERPROOFING MEMBRANE.
ENGINEERED FILL PER RECOMMENDATIONS BY
3 GEOTECHNICAL INTERPRETIVE REPORT. BEARING
S-200 CAPACITY OF ENGINEERED FILL 150kPa (SLS), 225kPa
UNDERSLAB SHEET WATERPROOFING MEMBRANE. (ULS)
ENGINEERED FILL PER RECOMMENDATIONS BY
GEOTECHNICAL INTERPRETIVE REPORT. BEARING
CAPACITY OF ENGINEERED FILL 150kPa (SLS),
225kPa (ULS)

A SECTION B SECTION TYPICAL FOOTING DETAIL


- -
1 : 50 1 : 50 1 : 25

NOTES:
1. FOUNDATION DESIGN TO BE REVIEWED WHEN SOIL TESTING PIT RESULTS ARE AVAILABLE.
2. HIGH STRENGTH XPS EXTRUDED POLYSTYRENE INSULATION TO BE INSTALLED.

VERIFY SCALES DESIGNED S.R. CORE AREA WASTEWATER TREATMENT PROGRAM


BAR IS 20mm ON SURVEYED
CLOVER POINT PUMP STATION
20mm MR 24/09/2018 3 ISSUED FOR CONSTRUCTION DRAWN PR DATE 02/02/2018 STRUCTURAL
MR 15/06/2018 2 ISSUED FOR 100% DESIGN SUBMISSION SCALE
As indicated CHECKED J.P.
PLANS AND SECTIONS
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 23/03/2018 1 ISSUED FOR 90% DESIGN SUBMISSION
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-200 3 OF
5 6 7 8 9
5
24375
S-201

4500 5200 5000 5000 2150

400

TYP.

400
A1 A1 W250x58

45.
00°
2. PL 400x400x20

1450

1450
1605

400
S-201
4-HSS 102X102X6.4

1870
950 STEEL PIPE SUPPORT STEEL POST TYP. 4-HILTI SS HAS RODS
SEE DETAIL (TYP.) M20 W/ HIT-HY200 ADHESIVE
966 (MIN. EMBED = 125mm)
4

3805
BASE PLATE
875

900
S-201 SEE DETAIL
UP
(TYP. OF 10)

900

989
UP
PUMP ROOM 25mm NON-SHRINK GROUT

340
T/O CONC. SLAB
EL. -1.000

810
W250X45 (TYP.)

B B

4 DETAIL - BASE PLATE (TYP. OF 10)

2850

1440
C1 C1 C1 C1
S-201
1 : 10

150mm THK . CONC

5295
W250X58 EQUIPMENT PAD
BP1 (TYP. FOR ALL) EL. -0.850

3855
2600 2960 2165

3206
EXG PUMP FLOOR
1200 1055 1250
-0.448 m
255
W250x58
PL 400x400x20
500mm DEEP SUMP
4-HILTI SS HAS RODS
M20 W/ HIT-HY200 ADHESIVE
(MIN. EMBED = 125mm)

B1 B1 25mm NON-SHRINK GROUT

LOWER LEVEL- NEW PUMP ROOM


-1.000 m
PLATFORM BASE PLAN
1 : 50
A1
5 SECTION
S-201
1 : 10
SEE PROCESS
FOR PIPE SIZE

CONC. WALL

W310X74

A1 500X500X16
WALL PLATE
45.

500X500X16 EL. 2.102


00°

WALL PLATE 400X400X16


WALL PLATE
° W250x33
DIAGONAL .00
135 TIE BEAM
BRACING
W250X33
24/09/2018 6:56:02 PM

W250X33
W310X39

400X400X16
WALL PLATE
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

W250X33
TIE BEAM
12
6.2

3.

S-201

2. DETAIL- PIPE SUPPORT - PLAN 3. DETAIL - PIPE SUPPORT - SECTION


S-201
1 : 20 S-201
1 : 20

VERIFY SCALES DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM


BAR IS 20mm ON SURVEYED
CLOVER POINT PUMP STATION
20mm MR 24/09/2018 3 ISSUED FOR CONSTRUCTION DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 15/06/2018 2 ISSUED FOR 100% DESIGN SUBMISSION SCALE
As indicated CHECKED J.P.
PLATFORM - BASE PLATE PLAN
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 23/03/2018 1 ISSUED FOR 90% DESIGN SUBMISSION
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-201 3 OF
KEYNOTES:
5 6 7 8 9
A TYPE HD 30-102 38x9.5 BAR SIZE NUCOR GRATING OR EQUIALENT
24375 400

B TYPE 30-102, 45x4.8 BAR SIZE NUCOR GRATING OR EQUIVALENT FOR GENERAL AREA. TYPICAL FOR
1350 5900 900 4775 900 2475 900 2135 900 2940 1200 FLOOR OR PLATFORM. U.N.O.
6575

A1
2295 7950 3940
Sim 9 RUNS @ 255 1500 2050 2150 2150 2295
ELECTRICAL ROOM 4
RISER = 200mm 9 RUNS @ 255 SEE SECTION -3
ACCESS PLATFORM S-203

2000
RAILING
KNEE BRACE EL. 7.409 T/O CONC. SLAB 5 RISER = 200mm
EL. 3.909 S-202
L89X89X9.5
KB KB KB KB
(TYP. FOR ALL A
PLATFORM)
T/O PLATFORM W250X33 T/O PLATFORM T/O OF PLATFORM EL. 5.909

W250X22

W250X22

W250X22

W250X22

W250X22

1500
1200
ALL FRAMING EL. 5.909 UP EL. 7.990 SEE PLAN FOR
5225 UP
MEMBERS B GRATING TYPE
W250X45 W250X33 A
3 W250X33
KB KB KB KB KB KB
S-202
W250X45

50
KB KB KB

1586
KB

1250
T/O PLATFORM
B EL. 3.909 W250X22

2500
1200

W250X45
T/O PLATFORM T/O PLATFORM T/O PLATFORM T/O PLATFORM

3000
A

3655
CONC. CONC.

3100
EL. 2.100 EL. 2.100 ALL FRAMING PIPE EL. 3.909 EL. 3.909 PIPE HSS 102X102X7.9
5400

MEMBERS SUPPORT SUPPORT


W250X45 A A
B B

1600

1600

4450
W250X45

4480
KB KB KB KB
50 50 HILTI HIT HY200 ADHESIVE
ANCHORING SYSTEM
KB KB REMOVABLE KB REF. STD DETAIL FOR OPEN TO OPEN TO 4-20M HAS RODS,

1980
GRATING OPEN GRATING SEATING (TYP.) BELOW BELOW 150MM EMBEDMENT.
155 900 1500 700 OPEN TO PANEL (TYP.) BELOW 400X400X20 WALL (TYP.)PLATE
700 700 OPEN TO BELOW
50 3300 BELOW 4 1547
50 3150 1575 900 2475 900 2135 900 1836 PL250X250X20
S-202
826 1550 700 1550

UPPER LEVEL - NEW PUMP ROOM


T/O GRATING T/O GRATING 3.909 m
EL. 3.909 T/O CONC. SLAB
950
1700

DN EL. 3.909 T/O CONC. SLAB


EL. 3.909 400mm CONC. SLAB
EL. 3.909

2250
B B B A A
KB

KB

KB

KB

B B

5 SECTION
500

B1 S-202
1 : 20
295 1055
1 2 REF. STD DETAIL FOR
S-202 GRATING SEATING (TYP.)
S-202
500 1350 5900 1670 1450 760 1450 1245 1750 1624 2135 901 1680 2460

UPPER LEVEL - PLATFORM FRAMING PLAN


1 : 50
NOTE:
DESIGN LIVE LOAD PLATFORMS = 5KPa
DESIGN LIVE LOAD FLOOR GRATING = 15KPa U/N 9
B1
B1 TYPE HD 30-102
38x9.5 BAR SIZE
NUCOR GRATING OR EQUI.

1000 T/O PLATFORM EL. 2.100


(TYP.) 1000
250X45 W250X45

TYPE 30-102, 45x4.8 W250X45


TYPE 30-102, 45x4.8
BAR SIZE NUCOR BAR SIZE NUCOR
GRATING OR GRATING OR

(TYP.)

(TYP.)
1000

1000
L8
EQUIVALENT FOR

.5
EQUIVALENT FOR

9X
X9
GENERAL AREA PIPE OPENING

89
89
GENERAL AREA

X9
BEYOND

9X
(10kPa LIVE LOAD)

.5
L8
(10kPa LIVE LOAD)

UPPER LEVEL - NEW PUMP ROOM UPPER LEVEL - NEW PUMP ROOM TYPE HD 30-102, CONC. WALL
38x9.5 BARSIZE,
3.909 m 3.909 m NUCOR GRATING 1200
OR EQUIVALENT 500X500X16
HSS152X102X7.9 WALL PLATE KNEE BRACING
W310X39
24/09/2018 6:56:10 PM

6-20M SS HAS RODS


HSS152X102X7.9
STRINGER C310x37 W250x33 W/ HILTI HIT HY 200
EXTENDED TO WALL TIE BEAM ADHESIVE ANCHORS.
MIN 200MM EMBEDMENT

W250X58

W250X58
7.9

L102x102x6.4
6X

Sim
X7

W250X33
02

5
S1
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

HS

HILTI HIT HY200 S-201


ADHESIVE ANCHORING SYSTEM 400X400X16
00°
4-20M HAS RODS, 150. 45. WALL PLATE
EMBEDMENT400X400X20 WALL 300x300x20 WALL PLATE
(TYP.)PLATE 4-20M SS HAS RODS
4-20M SS HAS ROADS w/ HILTI HIT HY 200 W/ HILTI HIT HY 200
ADHESIVE, MIN. 200MM EMBEDMENT CONC. PAD
ADHESIVE ANCHORS.
MIN 200MM EMBEDMENT

150
LOWER LEVEL- NEW PUMP ROOM
-1.000 m
Sim
5

SECTION SECTION 3 SECTION S-201

SECTION
1 2 4
S-202
1 : 25 S-202
S-202
1 : 25 S-202
1 : 25 1 : 25
VERIFY SCALES DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM
BAR IS 20mm ON SURVEYED
CLOVER POINT PUMP STATION
20mm MR 24/09/2018 3 ISSUED FOR CONSTRUCTION DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 15/06/2018 2 ISSUED FOR 100% DESIGN SUBMISSION SCALE
As indicated CHECKED J.P.
PLATFORM FRAMING - PLAN
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 23/03/2018 1 ISSUED FOR 90% DESIGN SUBMISSION
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-202 3 OF
7

5 6 7

7244 500 300 1200 1000 UPPER LEVEL - NEW PUMP ROOM
400x300x16mm ALUM. WALL PLATE 3.909 m
400x300x16mm ALUM. WALL PLATE
ANCHORED TO CONCRETE BY 4-M16 ANCHORED TO CONCRETE BY 4-M16
ALUM. ANCHORS, 150mm EMBEDMENT ALUM. ANCHORS, 150mm EMBEDMENT
ALUM. LADDER (TYP.)
(TYP.) SEE STD. DETAILS ALUM. LADDER
ALUM. LADDER SEE STD. DETAIL
SEE STD. DETAILS
400mm CONC. WALL
ALUM. GUARDRAIL
SEE STD. DETAIL

38mm THK.
B1 B1 T/O OF EL. GRATING 1.559

300
ALUM. GRATING

521
I10 I10

1100
KB

45.
1500
I10

I8X7.02
ALUM. STAIRS I10 KB

I10

00°
1320
ALUM. GRATING I10 SEE STAIR-DETAILS KB KB

1200
38mm THK.
I10

I10

T/O OF GRATING 1.559


KB

°
1521

.00
I10 I10 400x300x16mm ALUM. WALL PLATE

1001

135
ALUM. GUARDRAIL 1500 1000 ANCHORED TO CONCRETE BY 4-M16
900

900
SEE STD. DETAILS ALUM. ANCHORS, 150mm EMBEDMENT
(TYP.) KB
2

2900
I10 S-203
B2

299
1200 4844 ALUM. GRATING
C KB KB 38mm THK. ALUM. GUARDRAIL
SEE STD. DETAILS

980

I10
T/O OF GRATING 1.559 (TYP.)

I10 EXG WET WELL INVERT


C2 C2 C2 -2.914 m

2700

NOTES:

1. ALUMINUM PLATFORM LIVE LOAD = 4.8kPa

2. MEMBER AND ANCHORAGE SIZE IS FOR REFERENCE ONLY. MANUFACTURER TO DESIGN PLATFORMS.
SHOP DRAWING SHALL BE SUBMITTED WITH P.ENG. SEAL.
2 SECTION
WET WELL- ALUM. PLATFORM S-203
1 : 50
1 : 50

A1

5 6445

1289
1289 1289 1289 1289

SEE PLAN FOR


GRATING TYPE
L102x102X7.9 CONTINUOUS
REMOVABLE
ANGLE ANCHORED TO
GUARDRAIL
CONCRETE WALL BY 20M
HAS RODS @500c/c
BY HILTI HIT HY200
ADHESIVE ANCHORS, MIN.
200mm EMBEDMENT (TYP.)

500X500X16
A1 WALL PLATE
6-20M SS HAS RODS
W/ HILTI HIT HY 200
ADHESIVE ANCHORS.
DIAGONAL MIN 200MM EMBEDMENT
ELECTRICAL ROOM
BRACING
ACCESS PLATFORM
W250X33 (TYP.) W310X39
EL. 7.409
W310X39

W310X39

W310X39

W310X39

W310X39

2000
24/09/2018 6:56:13 PM

1135
A
W250X33

DIAGONAL BRACING
W250X33 W250X33 W250X33 W250X33 W250X33 W250X33
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

L102x102X7.9 CONTINUOUS ANGLE ANCHORED


TO CONCRETE WALL BY 20M HAS RODS @500c/c 4-20M SS HAS RODS
BY HILTI HIT HY200 ADHESIVE ANCHORS, MIN. 200mm W/ HILTI HIT HY 200
EMBEDMENT (TYP.) ADHESIVE ANCHORS.
1 MIN 200MM EMBEDMENT
S-203 400X400X16
WALL PLATE
4 PLATFORM - ELEC. RM ACCESS
S-203
1 : 25
1 SECTION
S-203
1 : 25
KEYNOTE:

A TYPE HD 30-102 38x9.5 BAR SIZE NUCOR GRATING OR EQUIALENT

VERIFY SCALES DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM


BAR IS 20mm ON SURVEYED
CLOVER POINT PUMP STATION
20mm MR 24/09/2018 3 ISSUED FOR CONSTRUCTION DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 15/06/2018 2 ISSUED FOR 100% DESIGN SUBMISSION SCALE
As indicated CHECKED J.P.
PLATFORM FRAMING - PLAN, SECTION AND DETAILS
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 23/03/2018 1 ISSUED FOR 90% DESIGN SUBMISSION
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-203 3 OF
5 6 7 8 9

B1
37' Span

1750
W250X101

7.5 TONNE

1750
TELESCOPIC
B2 MONORAIL
W250X101
4.
C S-318

1750
C2 C2
C2
C2 S-306

W250X101
3.
S-318

1750
5080 2270 150
W250X101
2.
D1 S-318

W250X131
S200x34
5790

1750
S200x34

W250X101

D2 1.0 TONNE MONORAIL


BEAM ANCHORED TO HOLLOW

1750
Sim CORE ROOF SLAB. REFER TO
1. MONORAIL FIXING DETAIL-1
S-318 ON DWG. S-316
W250X101

D3
m
0m
50

1.0 TONNE MONORAIL


R1

BEAM ANCHORED TO
HOLLOW CORE ROOF
SLAB. SEE SECTION
S2
00

DETAILS ON DWG. S-316


x3
4
24/09/2018 6:56:15 PM

MONORAIL BEAM FRAMING


1 : 50
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

VERIFY SCALES DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM


BAR IS 20mm ON SURVEYED
CLOVER POINT PUMP STATION
20mm MR 24/09/2018 3 ISSUED FOR CONSTRUCTION DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 15/06/2018 2 ISSUED FOR 100% DESIGN SUBMISSION SCALE
1 : 50 CHECKED J.P.
MONORAIL BEAM FRAMING - PLAN
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 23/03/2018 1 ISSUED FOR 90% DESIGN SUBMISSION
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-204 3 OF
2 3 4 5

NEW ROOF SLAB WATERPROOFING MEMBRANE


TO OVERLAP WITH EXISTING ROOF MEMBRANE
PER MANUFACTURER'S REQUIREMENT AND DETAILS.
OVERBURDEN ON EXISTING ROOF TO BE REMOVED
LOCALLY AND REINSTATE FOR THIS OVERLAPPING.
TYP. FOR LOCATIONS NEW ROOF SLAB TO JOIN EXISTING ROOF PUMP ROOM
ROOF SLAB
500 10.902 m
25M @150

350
TUL & BLL
EXG UPPER ROOF

100

350
10.802 m
15M @900 E.W. MAX C/W HILTI
HY200 EPOXY, EMBED 150 (TYP. 20M @150
ALONG EXISTING AND NEW TLL & BUL
INTERFACE ALONG GRID '4', 'B2'
AND '5')

1
S-301
ELECTRICAL ROOM
TOP AND MID GALV. STEEL GUARDRAIL,
BOLTED TO WALL WITH ADHESIVE ANCHORS.
190MM CMU FULLY PROVIDE P.ENG STAMPED SHOP DWGS FOR 7.409
MECH. UNIT REINFORCED REVIEW AND APPROVAL (TYP.) 20M @200

300
AND GROUTED

535
TUL & BLL
114mm CONC. TOPPING

535
ON 38mm STEEL DECKING

20M @250
TLL & BUL

STRUCTURAL SUPPORT FOR MECH. 20M @200HEF 20M @200HEF


UNIT, SEE DWG.S-105 AND S-315
20M @200VEF 25M @200VEF

GENERATOR ROOM TRANSFORMER ROOM

20M @200
GENERATOR CONC. PAD TUL & BLL

400
15M @250 T.B.E.W
UPPER LEVEL - NEW PUMP ROOM
400

400
3.909 m

229
20M @200

957
TLL & BUL

828
500

1757
REFER TO TYPICAL DETAILS FOR
ADDITIONAL REINFORCEMENT AT OPENINGS

FILL EX. OPENING WITH 35mPa SAWCUT OPENING


CONCRETE AND 20m @250 IN EXISTING WALL
DOWELS T&B EW. MAKE GOOD BASEMENT CORRIDOR
SURFACE TO MATCH EXISTING

3000

3000
900 BASEMENT ROOM 900 900

2200
CONC. PIPE SUPPORT
1087

1087

1087
20M @200
TUL & BLL

500
LOWER LEVEL- NEW PUMP ROOM

20M @200 VEF -1.000 m


20M @250
20M @200 HEF TLL & BUL

MASS CONCRETE FILL

TYPICAL BASE SLAB ASSEMBLY


• UNDERSLAB WATERPROOFING SYSTEM BY W. R.
500 MEADOWS 'PRECON' OR APPROVED EQUAL
NEW CONCRETE WALL TO BE FOUNDED ON MASS • MUD SLAB 5
CONCRETE, TO MATCH THE ELEVATION OF • MASS CONCRETE/ROCK BEYOND
EXISTING WALL FOOTING. NO EXISTING WALL
FOOTING CAN BE UNDERMINED.

20M @150 100


TUL & BLL
ROOF PUMP ROOM

100
10.902 m
24/09/2018 6:56:17 PM

350
A1 SECTION

720
S-102 25M @150
1 : 50 TLL & BUL
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

DOUBLE TEE
20M @200 HEF EXG MIDDLE ROOF
9.888 m
25M @200 VEF

1 DETAIL
S-301
1 : 20

VERIFY SCALES
MR 24/09/2018 6 ISSUED FOR CONSTRUCTION
DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM
BAR IS 20mm ON MR 15/06/2018 5 ISSUED FOR 100% DESIGN SUBMISSION SURVEYED
MR 23/03/2018 4 ISSUED FOR 90% DESIGN SUBMISSION
CLOVER POINT PUMP STATION
20mm MR 19/01/2018 3 ISSUED FOR 50% DESIGN SUBMISSION DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 08/12/2017 2 ISSUED FOR 30% DESIGN SUBMISSION SCALE
As indicated CHECKED J.P.
SECTION 'A1' AND DETAILS
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 16/08/2017 1 ISSUED FOR RFP SUBMISSION
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-301 6 OF
TYPICAL ROOF ASSEMBLY
• SEEDING/GROUNDCOVER
5 6 7 • 230~250mm TOPSOIL 8 9
ACCESS HATCH
• 500~850mm GEOFOAM
• DRAINAGE BOARD T/O CONC. EL. 12.300
• 50mm HIGH STRENGTH EXTRUDED POLYSTYRENE INSULATION PROTECTION SHEET
• REINFORCED TWO COAT FLUID-APPLIED WATERPROOFING MEMBRANE 12.150
• 100mm CONC. TOPPING c/w 152X152 MW25.8X25.8 WELDED WIRE MESH
1.5 TONNE MONORAIL (W250X38)
• 3120X721 DOUBLE TEE
BETWEEN DOUBLE TEE RIBS Sim
(CENTERED) (T/O GRADE SEE CIVIL DWGS )
N
S-107

ROOF PUMP ROOM


10.902 m

7.5 TONNE REMOVABLE


BRIDGE CRANE GUARDRAIL
SEE STD. DETAIL
3000

DOWELS (TYP.)

1200
19225

ø 1200
TOTAL LENGTH OF CORBEL PIPE OPENING
ELECTRICAL ROOM 900
ACCESS PLATFORM GUARD RAIL CONC. CORBEL TO SUPPORT SEE PROCESS DWGS
SEE STD. DETAILS BRIDGE CRANE (UPTO GRID-8)
STEEL. LADDER

20M @200HEF 25M @150 HEF


20M @200 VEF
20M @200VEF GUARD RAIL
SEE STD. DETAILS

20M @200
20M @200 T.B.E.W
T.B.E.W UPPER LEVEL - NEW PUMP ROOM
3.909 m

B17

400
BEAM B19, SEE B19 B19 B19 B19
STEEL LADDER BEAM DETAIL FOR 900MM DIA. CAISSON PILE
REINFORCEMENT C1 C1 BEAM B19 C1 C1
(TYP.)
2200

20M @300 TLL & BUL


100X50mm DEEP GUTTER DRAIN
FOR STEEL PLATFORMS AND 25M @200 TUL & BLL
ALONG FOOT OF WALL, 1% SLOPE
SUPPORTS SEE DWGS S-201, 150mm THK TO SUMP PIT (TYP.)
S-202 AND S-203 CONT. PUMP PAD
15M @300
TEW
LOWER LEVEL- NEW PUMP ROOM
-1.000 m

1200mm CONC. SLAB

125

NATIVE BACKFILL

TYPICAL BASE SLAB ASSEMBLY


• UNDERSLAB WATERPROOFING SYSTEM BY W. R.
MEADOWS 'PRECON' OR APPROVED EQUAL
• MUD SLAB
• NATIVE BACKFILL

EACH W610 KING PILE TO BE SOCKETED


INTO SOUND BEDROCK ATLEAST 2.0m
DEEP AND FULLY GROUTED WITH MIN.
35MPa UNCONFINED COMPRESSIVE
STRENGTH GROUT/CONCRETE.
24/09/2018 6:56:19 PM

ROCK PROFILE AT GRID 9 AND


A1 IS ASSUMED TO BE -11.0M
AS PER GEOTECHNICAL
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

A2 SECTION REPORT

S-102
1 : 50

MR 24/09/2018 9 ISSUED FOR CONSTRUCTION


VERIFY SCALES
MR 19/07/2018 8 REISSUED FOR CONSTRUCTION - CAISSON WALL
DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM
BAR IS 20mm ON MR 15/06/2018 7 ISSUED FOR 100% DESIGN SUBMISSION SURVEYED
MR 26/03/2018 6 ISSUED FOR PRE-CONSTRUCTION REVIEW - CAISSON WALL
CLOVER POINT PUMP STATION
20mm MR 23/03/2018 5 ISSUED FOR 90% DESIGN SUBMISSION DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 02/03/2018 4 ISSUED FOR CONSTRUCTION - CAISSON WALL SCALE
1 : 50 CHECKED J.P.
SECTION 'A2' AND DETAILS
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 02/02/2018 3 ISSUED FOR CAISSON WALL TENDER
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-302 9 OF
2 3
4

ROOF PUMP ROOM

EXG UPPER ROOF 10.902 m

10.802 m
20M @200 VEF

EX. MONORAIL 20M @200 HEF

EX. SUPPORTING
STEEL BEAM
3000x3000mm OPENING
FOR MECH. DUCT IN
114mm CONCRETE TOPPING NEW WALL
38mm STEEL DECKING EX. CORBEL BESIDE
COLUMNS

3000
OVER STAIR EXIT MECH DUCT
SEE MECH. DWGS

114mm CONCRETE TOPPING


MECH. UNIT 38mm STEEL DECKING

EXG MEZZANINE LEVEL


6.825 m
SEE SECTION - M 20M @200 HEF
FOR DETAILS 190MM CMU
FULLY GROTED 20M @200 VEF
SEE NOTE-2 ON S-304

FILL EX. OPENING WITH 35mPa


CONCRETE AND 20m @250
DOWELS T&B EW. MAKE GOOD

2050
SURFACE TO MATCH EXISTING
RAMP
SEE ARCH. DWGS EL. 3.759
EL. 3.609
UPPER LEVEL - NEW PUMP ROOM
EXG MOTOR RM & WET WELL FLOOR 3.909 m
3.609 m

20M @200 HEF

2207
SEE NOTE 2

1828
1200 20M @200 VEF
SEE NOTE 1
NEW OPENING INTO
EXISTING EXTERIOR WALL
450 CONC WALL R/W TO FIT THE DOOR
20M@200 H.V.E.F
2400

2000

2000
300MM CONC. SLAB R/W
CONC. BENCHING 15M @200 T.B.E.W
SEE NOTE-3

20M DOWELS
@600MM C/C
1856

MASS CONC. FILL MASS CONC. FILL 20M @200 HEF


IN EX. TRENCH IN EX. TRENCH

2771
20M @200 VEF

EXG VALVE FLOOR


-2.304 m

VERTICAL REINFORCEMENT TO BE DOWELLED INTO NEW CONCRETE WALL TO BE FOUNDED ON MASS


EXISTING CONCRETE MAT, 150MM EMBEDMENT CONCRETE, TO MATCH THE ELEVATION OF EXISTING
FULLY APOXY GROUTED WALL FOOTING. NO EXISTING WALL FOOTING CAN BE
UNDERMINED.

B1 SECTION
S-102
1 : 50
24/09/2018 6:56:21 PM
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

NOTES:
1. NEW WALL REBAR TO BE ANCHORED INTO EXISTING SLAB, DRILL IN 200mm, FULLY EPOXY
GROUTED BY HILTI HIT HY200 ADHESIVE ANCHOR SYSTEM. TYPICAL FOR NEW WALL CONNECTION
TO EXISTING STRUCTURE.

2. ALL CONCRETE SURFACE OF WET WELL AND CHANNEL (BASE SLAB, WALLS, ROOF SLABS, BEAMS,
AND COLUMNS) TO BE PROTECTED BY TWO COATS OF PROTECTIVE
COATING - CEM-KOTE OR APPROVED EQUAL (SEE SPECIFICATIONS).

3. PROVIDE WIRE MESH 152x152 MW 25.8x25.8 WITH 50mm CONCRETE COVER FOR ALL
BENCHING/MASS CONCRETE INSIDE SEWAGE WET WELL OR CHANNELS FOR CRACK CONTROL.

4. CONCRETE BENCHING INSIDE SEWAGE TO BE DOWELED INTO STRUCTURAL SLABS/WALLS WITH


15M @800 EACH WAY. PROVIDE END HOOK OR DEVELOPMENT LENGTH AS REQUIRED.

VERIFY SCALES DESIGNED J.P. CORE AREA WASTEWATER TREATMENT PROGRAM


BAR IS 20mm ON SURVEYED
CLOVER POINT PUMP STATION
20mm MR 24/09/2018 3 ISSUED FOR CONSTRUCTION DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 15/06/2018 2 ISSUED FOR 100% DESIGN SUBMISSION SCALE
1 : 50 CHECKED J.P.
SECTION 'B1' AND DETAILS
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 23/03/2018 1 ISSUED FOR 90% DESIGN SUBMISSION
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-303 3 OF
4 5 6 7 8 9
TYPICAL ROOF ASSEMBLY
• SEEDING/GROUNDCOVER
• 230~250mm TOPSOIL
1 • 500~850mm GEOFOAM
S-304 • DRAINAGE BOARD
• 50mm HIGH STRENGTH EXTRUDED POLYSTYRENE INSULATION
PROTECTION SHEET
• REINFORCED TWO COAT FLUID-APPLIED WATERPROOFING MEMBRANE
• 100mm CONC. TOPPING c/w 152x152 MW 25.8x25.8 WELDED WIRE MESH
• 305mm CORE SLAB
(SEE CIVIL DWGS.) . T/O OF GRADE EL. 11.200
ROOF PUMP ROOM

350
10.902 m
RB1 RB2

1319
969
ROOF BEAM
2720x3000mm OPENING RB3 20M @ 200HEF
FOR MECH. DUCT IN

1484
25M @ 200VEF
NEW WALL MECH UNIT.
SEE MECH DWGS. 1831 750 1475
3000

190MM CMU WALL


FULLY GROUTED 190 CMU WALL DUCT OPENING
5600 SEE NOTE-2

750
SEE NOTE 2 SEE MECH.
250mm CONC. SLAB W250x101
FOR MECH. DUCT, SEE
MECH. DWGS. 7.5 TONNE TELESCOPIC
CABLETRAY OPENING MONORAIL W250X131
891 1400 570
2400 650
WATERPROOFING
MEMBRANE

200
20M @200 HEF
20M @200 VEF DOOR DOOR
OPENING OPENING

3000
2400

2200

2200
2050

3000 CURB DETAIL


20M @200 TUL & BLL REFER TO TYP. DETAIL 15M @200 TlL & BUL
150mm THK. CONC.
15M @200 TLL & BUL EQUIPMENT PAD ON DWG. S-505 20M @200 TUL & BLL

300
300
UPPER LEVEL - NEW PUMP ROOM
3.909 m
B6 B8 B9
B7 24
15M DOWELS SEE NOTE 1 ø3 SEE NOTE 1
900MM DIA.
@900MM C/C ø ALUM. LADDER CAISSON BEYOND
91
4 ø2 20M @200 HEF

2050
19
375

1850
20M @200 VEF 20M @ 200 HOF
ALUM. LADDER
203
1455 525
25M @ 200 VOF
EL. 1.559 25M @150 VIF
STORM WET WELL 25M @200 HIF SEE STANDARD DETAILS FOR
ADDITIONAL REINFORCEMENT
2812

2230 3310 2210 1070 1300 3375 3025 1100 AROUND THE PIPE OPENINGS
20M @200 TUL & BLL (TYP.)
WALL OPENING
2000

500
25M @200 TLL & BUL FOR PIPES ø ø ø
10 10 10
SEE PROCESS 50 50 50
ø ø (TYP.) ø7 ø7
75 75 50 50
0 0

1215
CONC. BENCHING
795

795
SEE NOTE 3 ALUM.
500mm CONC. SLAB SAN WET WELL LADDER
LOWER LEVEL- NEW PUMP ROOM
-1.000 m
20M @200 HEF
20M @200 VEF 20M @200 TUL & BLL
MASS CONC.
20M @200 HEF 20M @250 TLL & BUL PROTECTIVE COATING CONC. BENCHING
SEE NOTE 1
20M @200 VEF
25M @200 T.B.E.W

EXG WET WELL INVERT


-2.914 m
600

1050
MASS CONCRETE
BEDROCK PROFILE
TO BE CONFIRMED ONSITE

300 500 2000 500

EXHAUST VENT
TYP. ON ALL 4-SIDES
CEDAR DECK, SEE LANDSCAPE
DWGS FOR DECK DETAILS
24/09/2018 6:56:23 PM

SECTION
200

3-20M B, ADD'L
ABOVE OPENING 300mm THK. CONC. WALL R/W 15M @200 HVEF B2
(TYPICAL) (TYP. FOR ALL 4-SIDES). REFER TO STD. DETAILS
S-101
FOR ADDITIONAL REINFORCEMENT AT OPENING 1 : 50
800

400

T/O OF GRADE EL. 11.200


S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

200

NOTES:
ROOF PUMP ROOM
1. ALL CONCRETE SURFACE OF NEW WET WELL AND CHANNEL (BASE SLAB, WALLS, ROOF SLABS,
10.902 m BEAMS, AND COLUMNS) TO BE PROTECTED BY TWO COATS OF PROTECTIVE COATING - CEM-KOTE
CONSTRUCTION JOINT C/W FLEX CR OR APPROVED EQUAL (SEE SPECIFICATIONS)
WATER STOP
2. 190mm THICK CONCRETE BLOCK WALL REINFORCED WITH 15M @600 VERTICAL IN GROUTED CELL,
RB1 RB2 4.75mm@200 HORZ. LADDER. BOND BEAM EVERY 2000mm MAX. REINFORCED WITH 2-15M
HORIZONTAL BARS. ONE BEAM ON TOP OF WALL. 1200mm LONG AT 600 SPACING DOWEL, 600mm
DOWEL INTO FOUNDATION WALLS OR BEAMS TO MATCH SPACING OF WALL VERTICAL
300 3000 300 REINFORCEMENT AT BOTTOM TO SPLICE WITH WALL REINFORCEMENT PROPERLY.
OPENING SEE PLAN
3. PROVIDE WIRE MESH 152x152 MW 25.8x25.8 WITH 50mm CONCRETE COVER FOR ALL
BENCHING/MASS CONCRETE INSIDE SEWAGE WET WELL OR CHANNELS FOR CRACK CONTROL.

1 EXHAUST VENT DETAIL 4. CONCRETE BENCHING INSIDE SEWAGE TO BE DOWELED INTO STRUCTURAL SLABS/WALLS WITH
15M @800 EACH WAY. PROVIDE END HOOK OR DEVELOPMENT LENGTH AS REQUIRED.
S-304
1 : 20
VERIFY SCALES DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM
BAR IS 20mm ON MR 24/09/2018 5 ISSUED FOR CONSTRUCTION SURVEYED
MR 19/07/2018 4 REISSUED FOR CONSTRUCTION - CAISSON WALL
CLOVER POINT PUMP STATION
20mm MR 15/06/2018 3 ISSUED FOR 100% DESIGN SUBMISSION DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 16/05/2018 2 ISSUED FOR CONSTRUCTION - CAISSON WALL SCALE
As indicated CHECKED J.P.
SECTION 'B2' AND DETAILS
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 23/03/2018 1 ISSUED FOR 90% DESIGN SUBMISSION
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-304 5 OF
2 3 4 5

EXG MIDDLE ROOF


9.888 m

ROOF
8.959 m

HSS305X102X9.5
10 TYP BOTH
S-701 ENDS

3000
20M @ 200HEF
20M @ 200VEF
3708

UPPER LEVEL - NEW PUMP ROOM


3.909 m

SEE DETAIL-8/DWG.-S701 FOR


1651

ADDITIONAL REINFORCEMENT
AROUND THE WALL OPENINGS NEW WALL OPENINGS NEW WALL OPENINGS
IN EXISTING WALL, IN EXISTING WALL,
T/O OPENING 1.780 SEE PROCESS SEE PROCESS NATIVE BACKFILL
750

B/O OPENING 1.030

180 2415 300 2115 649 2115 300 2415 180


3944

305
1' - 0"
5' - 0"
1524
20M @ 200HEF
2591 2591
20M @ 200VEF
8' - 6" 8' - 6"

NEW CONCRETE WALL TO BE FOUNDED


ON MASS CONCRETE, TO MATCH THE EXG WET WELL INVERT
ELEVATION OF EXISTING WALL FOOTING. -2.914 m
NO EXISTING WALL FOOTING CAN BE
3' - 0"
914

UNDERMINED.
-3.828
24/09/2018 6:56:25 PM

2438 6707 2895


8' - 0" 22' - 0" 9' - 6"
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

C1 SECTION
S-102
1 : 50

VERIFY SCALES DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM


BAR IS 20mm ON SURVEYED
CLOVER POINT PUMP STATION
20mm MR 24/09/2018 3 ISSUED FOR CONSTRUCTION DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 15/06/2018 2 ISSUED FOR 100% DESIGN SUBMISSION SCALE
1 : 50 CHECKED J.P.
SECTION 'C1' AND DETAILS
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 23/03/2018 1 ISSUED FOR 90% DESIGN SUBMISSION
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-305 3 OF
5 6 7 8

TYPICAL ROOF ASSEMBLY


• SEEDING/GROUNDCOVER
• 230~250mm TOPSOIL
• 500~850mm GEOFOAM
• DRAINAGE BOARD
• 50mm HIGH STRENGTH EXTRUDED POLYSTYRENE L102XL102X79, 175mm ANGLE LONG SPACED @1200
INSULATION PROTECTION SHEET EACH SIDE STAGGERED. ANCHORED TO CONCRETE
• REINFORCED TWO COAT FLUID-APPLIED WATERPROOFING AND HOLLOW CORE SLAB BY HILTI ADHESIVE
MEMBRANE ANCHORS 2-20M@100 PER ANGLE, 125 EMBEDMENT
T/O CONC. EL. 10.902
• 100mm CONC. TOPPING c/w 152x152 MW 25.8x25.8 WELDED SEE STANDARD DETAIL (TYP.)
RB3 (SEE BEAM DETAILS FOR WIRE MESH
REINFORCEMENT) GRADE (SEE CIVIL DWGS.) • 305mm CORE SLAB

T/O ROOF EL. 9.988

RB4 RB5 RB6


STEEL BEAM TO BE SUPPORTED BY MASONRY

675
450
WALL POCKET, TWO BLOCKS UNDERSIDE THE
DUCT OPENINGS DUCT BEAM TO BE SOLID AND FULLY GROUTED
450 SEE MECH . DWGS. 650 OPENINGS
SEE MECH . T/O STEEL 7.615
DWGS. 400x400x25 WALL PLATE
4-25Ø, HILTI HIT-HY200 ADHESIVE ANCHOR, 200mm EMBEDMENT,
C2 C2 C2 SPACING @175 c/c V, 100c/c H. CONNECT STEEL BEAM TO WALL
190mm CMU WALL W250X101
PLATE BY 2-L102X102X6.4 CLIP ANGLES, 3-25Ø
FULLY GROUTED A325 BOLTS CONNECT BEAM TO ANGLE
SEE NOTE 2
7.5 TONNE TELESCOPIC
1000 MONORAIL W250x131

4675
PUMP ROOM SEE MANUF. DETAILS

4585
20M @ 200HEF
ACCESS
20M @ 200VEF
25M @ 200VEF
25M @ 200HEF

2200
WATERPROOFING
MEMBRANE
20M @200 TUL & BLL
20M @200 TUL & BLL

300
15M @250 TLL & BUL

300
15M @250 TLL & BUL

300
UPPER LEVEL - NEW PUMP ROOM
3.909 m
B8 B9
B7

500
20M @ 200 HOF

COMPACTED T/O OF PLATFORM EL. 1.559 25M @ 200 VOF


25M @150 VIF
NATIVE BACKFILL

25M @200 HEF 25M @200 HIF

CONC. COLUMN 'C2' TO BE CONSTRUCTED 20M @200 VEF


ON MASS. CONCRETE OR ROCK SEE DWG. S-203 FOR
CONC. COLUMN 'C2' SEATED 1205 ALUM. FRAMING DETAILS STORM WET
ON 1050mm THK. STORM WET WELL
WELL CONC. SLAB
C2
WALL OPENING FOR
SLIDE GATE. SEE STD.

1205
NEW 400mm THK. CONC. WALL. MATCH DETAILS FOR ADD'L
BOTTOM OF NEW WALL TO EXISTING REINFORCEMENT FOR
WALL BOTTOM ELEVATION WALL OPENINGS

20M @ 200HEF 500


20M @ 200VEF
SEE STD. DETAILS FOR CONCRETE BENCHING 25M @200
DOWELS REQUIREMENTS (TYP.) SEE PROCESS DWGS. T.B.E.W

EXG WET WELL INVERT

EX. MASS -2.914 m


1050

1050
CONCRETE

1050

MASS CONCRETE FILL


24/09/2018 6:56:26 PM

C2 SECTION
S-306
1 : 50
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

NOTES:
1. ALL CONCRETE SURFACE OF NEW WET WELL AND CHANNEL (BASE SLAB, WALLS, ROOF SLABS,
BEAMS, AND COLUMNS) TO BE PROTECTED BY TWO COATS OF PROTECTIVE COATING - CEM-KOTE
FLEX CR OR APPROVED EQUAL (SEE SPECIFICATIONS)

2. 190mm THICK CONCRETE BLOCK WALL REINFORCED WITH 15M @600 VERTICAL IN GROUTED CELL,
4.75mm@200 HORZ. LADDER. BOND BEAM EVERY 2000mm MAX. REINFORCED WITH 2-15M
HORIZONTAL BARS. ONE BEAM ON TOP OF WALL. 1200mm LONG AT 600 SPACING DOWEL, 600mm
DOWEL INTO FOUNDATION WALLS OR BEAMS TO MATCH SPACING OF WALL VERTICAL
REINFORCEMENT AT BOTTOM TO SPLICE WITH WALL REINFORCEMENT PROPERLY.

3. PROVIDE WIRE MESH 152x152 MW 25.8x25.8 WITH 50mm CONCRETE COVER FOR ALL
BENCHING/MASS CONCRETE INSIDE SEWAGE WET WELL OR CHANNELS FOR CRACK CONTROL.

4. CONCRETE BENCHING INSIDE SEWAGE TO BE DOWELED INTO STRUCTURAL SLABS/WALLS WITH


15M @800 EACH WAY. PROVIDE END HOOK OR DEVELOPMENT LENGTH AS REQUIRED.

VERIFY SCALES DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM


BAR IS 20mm ON MR 24/09/2018 5 ISSUED FOR CONSTRUCTION SURVEYED
MR 19/07/2018 4 REISSUED FOR CONSTRUCTION - CAISSON WALL
CLOVER POINT PUMP STATION
20mm MR 15/06/2018 3 ISSUED FOR 100% DESIGN SUBMISSION DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 16/05/2018 2 ISSUED FOR CONSTRUCTION - CAISSON WALL SCALE
1 : 50 CHECKED J.P.
SECTION 'C2' AND DETAILS
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 23/03/2018 1 ISSUED FOR 90% DESIGN SUBMISSION
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-306 5 OF
TYPICAL ROOF ASSEMBLY
• SEEDING/GROUNDCOVER
• 230~250mm TOPSOIL
• 500~850mm GEOFOAM
• DRAINAGE BOARD
5 6 7 • 50mm HIGH STRENGTH EXTRUDED POLYSTYRENE 8 9
INSULATION PROTECTION SHEET
• REINFORCED TWO COAT FLUID-APPLIED
WATERPROOFING MEMBRANE
• 100mm CONC. TOPPING c/w 152x152 MW 25.8x25.8
400 WELDED WIRE MESH
305mm CORE SLAB
700

EXG MIDDLE ROOF


9.888 m

SEE SECTION-3
ON DWG. S-316 SEE MONORAIL FIXING
DETAIL-1 ON S-316 25M @200VEF
1.0 TONNE MONORAIL
25M @200HEF
20M @200HEF 190mm CMU WALL
FULLY GROUTED
20M @200VEF SEE NOTE-2
W250X101

WATERPROOFING
7.5 TONNE MEMBRANE
TELESCOPIC
MONORAIL

ACCESS HATCH
SCREEN OPENINGS
SEE PROCESS DWGS

20M @200 TUL & BLL 150mm CONC. PAD 300MM CONC. 20M @200 TUL & BLL
SLAB
15M @250 TLL & BUL 15M @250 TLL & BUL

300
UPPER LEVEL - NEW PUMP ROOM
EXG MOTOR RM & WET WELL FLOOR 3.909 m
3.609 m B8 B9
B10
2000
SEE NOTE 1 T/O WALL EL. 2.439 SEE NOTE 1

WALL OPENING
FULL HEIGHT 25M @150 VIF 20M @200 HOF

2000
FULL HEIGHT 25M @200 HIF 25M @200 VOF
CONC. BENCHING
20M @200 TUL BLL SLAB OPENING (TYP.) 1050
SEE PROCESS DWGS 20M @200 TUL BLL (TYP.)
20M @300 TLL BUL 20M @300 TLL BUL (TYP.)
EXG INLET CHANNEL INVERT 400mm CONC. SLAB

400
0.439 m

SEE NOTE 1
20M @200 HEF
25M @200 VEF CONC. BENCHING
500mm THK. CONC. SEE PROCESS DWGS.
25M @200
STORM WET SEE NOTE-3
T.B.E.W
WALL BEYOND

500

MASS CONCRETE
EXG WET WELL INVERT OR ROCK BEYOND
-2.914 m

1050
1050

D SECTION
S-102
1 : 50
24/09/2018 6:56:28 PM

NOTES:
1. ALL CONCRETE SURFACE OF NEW WET WELL AND CHANNEL (BASE SLAB, WALLS, ROOF SLABS,
BEAMS, AND COLUMNS) TO BE PROTECTED BY TWO COATS OF PROTECTIVE COATING - CEM-KOTE
FLEX CR OR APPROVED EQUAL (SEE SPECIFICATIONS)
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

2. 190mm THICK CONCRETE BLOCK WALL REINFORCED WITH 15M @600 VERTICAL IN GROUTED CELL,
4.75mm@200 HORZ. LADDER. BOND BEAM EVERY 2000mm MAX. REINFORCED WITH 2-15M
HORIZONTAL BARS. ONE BEAM ON TOP OF WALL. 1200mm LONG AT 600 SPACING DOWEL, 600mm
DOWEL INTO FOUNDATION WALLS OR BEAMS TO MATCH SPACING OF WALL VERTICAL
REINFORCEMENT AT BOTTOM TO SPLICE WITH WALL REINFORCEMENT PROPERLY.

3. PROVIDE WIRE MESH 152x152 MW 25.8x25.8 WITH 50mm CONCRETE COVER FOR ALL
BENCHING/MASS CONCRETE INSIDE SEWAGE WET WELL OR CHANNELS FOR CRACK CONTROL.

4. CONCRETE BENCHING INSIDE SEWAGE TO BE DOWELED INTO STRUCTURAL SLABS/WALLS WITH


15M @800 EACH WAY. PROVIDE END HOOK OR DEVELOPMENT LENGTH AS REQUIRED.

VERIFY SCALES DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM


BAR IS 20mm ON SURVEYED
CLOVER POINT PUMP STATION
20mm MR 24/09/2018 3 ISSUED FOR CONSTRUCTION DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 15/06/2018 2 ISSUED FOR 100% DESIGN SUBMISSION SCALE
1 : 50 CHECKED J.P.
SECTION 'D' AND DETAILS
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 23/03/2018 1 ISSUED FOR 90% DESIGN SUBMISSION
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-307 3 OF
8 7 6 5
TYPICAL ROOF ASSEMBLY
• SEEDING/GROUNDCOVER
• 230~250mm TOPSOIL
• 500~850mm GEOFOAM
• DRAINAGE BOARD
T/O RETAINING WALL • 50mm HIGH STRENGTH EXTRUDED POLYSTYRENE INSULATION
11.800 m PROTECTION SHEET
• REINFORCED TWO COAT FLUID-APPLIED WATERPROOFING MEMBRANE

1200
• 100mm CONC. TOPPING c/w 152x152 MW 25.8x25.8 WELDED WIRE MESH
• 305mm CORE SLAB

SEE CIVIL DWGS FOR GRADE 10.600

522
1226 1350 1.0 TONNE MONORAIL
ROOF ATTACHED TO UNDERSIDE
OF CORESLAB
8.959 m 1.0 TONNE MONORAIL

750
190mm CMU WALL
FULLY GROUTED 3000
SEE NOTE-2
400

1140
3x2-25M ADDT'L
3x2-25M ADDT'L
20M @200 VEF
2-20M (TYP.) 20M @200 HEF
700 2400 1000
2-20M

2x2-25M ADDT'L

2x2-25M ADDT'L
686

3350
2' - 3"

3000
25M @200 HEF
25M @200 VEF

2200
ACCESS
15M @200 T & B 20M @200 TUL & BLL HATCH

4' - 9"
1448
20M @200 TUL & BLL 15M @250 T&B
UPPER LEVEL - NEW PUMP ROOM
3.909 m
B9 B8 ALUM. LADDER

1200 2800
2825 1200 3000 2000 3000 2500 3000
EL. 2.450

EL. 1.850

20M @200 TUL BLL NEW ALUM. LADDER


SEE STD. DETAIL
20M @300 TLL BUL

400
EXG INLET CHANNEL INVERT
0.439 m

700
MASS CONCRETE/ROCK
LOWER LEVEL- NEW PUMP ROOM
-1.000 m

SAWCUT OPENING ON EX. CHANNEL AND CAST


OPENING IN NEW WALL. REPAIR ALL CUT AND
EXPOSED REBAR WITH EPOXY REPAIR MORTAR (TYP.
OF 5 OPENINGS) AND LINE 4 SIDES OF OPENING WITH
6MM STAINLESS STEEL PLATE WITH LIP ON EXISTING
SIDE, GROUT THE PLATE IN PLACE

E SECTION
S-102
1 : 50
24/09/2018 6:56:30 PM

NOTES:
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

1. ALL CONCRETE SURFACE OF NEW WET WELL AND CHANNEL (BASE SLAB, WALLS, ROOF SLABS,
BEAMS, AND COLUMNS) TO BE PROTECTED BY TWO COATS OF PROTECTIVE COATING - CEM-KOTE
FLEX CR OR APPROVED EQUAL (SEE SPECIFICATIONS)

2. 190mm THICK CONCRETE BLOCK WALL REINFORCED WITH 15M @600 VERTICAL IN GROUTED CELL,
4.75mm@200 HORZ. LADDER. BOND BEAM EVERY 2000mm MAX. REINFORCED WITH 2-15M
HORIZONTAL BARS. ONE BEAM ON TOP OF WALL. 1200mm LONG AT 600 SPACING DOWEL, 600mm
DOWEL INTO FOUNDATION WALLS OR BEAMS TO MATCH SPACING OF WALL VERTICAL
REINFORCEMENT AT BOTTOM TO SPLICE WITH WALL REINFORCEMENT PROPERLY.

3. PROVIDE WIRE MESH 152x152 MW 25.8x25.8 WITH 50mm CONCRETE COVER FOR ALL
BENCHING/MASS CONCRETE INSIDE SEWAGE WET WELL OR CHANNELS FOR CRACK CONTROL.

4. CONCRETE BENCHING INSIDE SEWAGE TO BE DOWELED INTO STRUCTURAL SLABS/WALLS WITH


15M @800 EACH WAY. PROVIDE END HOOK OR DEVELOPMENT LENGTH AS REQUIRED.

VERIFY SCALES DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM


BAR IS 20mm ON SURVEYED
CLOVER POINT PUMP STATION
20mm MR 24/09/2018 3 ISSUED FOR CONSTRUCTION DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 15/06/2018 2 ISSUED FOR 100% DESIGN SUBMISSION SCALE
1 : 50 CHECKED J.P.
SECTION 'E' AND DETAILS
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 23/03/2018 1 ISSUED FOR 90% DESIGN SUBMISSION
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-308 3 OF
E D C B A

PROVIDE DOWELS 2 ROWS OF 15M@900 TO EXISTING PROVIDE DOWELS 15M@900 TO EXISTING CONC WALL, EMBED 150
CONC WALL, EMBED 150, 300. FROM WALL ENDS. 300 FROM WALL ENDS
.

T/O EX. RETAINING WALL


12.478 m
7
STEEL STRUT, REFER TO DETAIL-3 S-702
ON DWG. S-701, (TYP.)

EXG UPPER ROOF


10.802 m
190mm CMU WALL

EXG MIDDLE ROOF


NEW NEW 9.888 m
FUEL STORAGE FUEL STORAGE
11 ROOM-1 ROOM-2
SHEAR WALL (SHOTCRETE)
EXISTING 5 TON S-702
THICKENING (200) R/W
20M@200 EW EF TRAVELLING
CRANE HOIST
EXG LOWER ROOF
8.364 m
8
• 114mm CONC. TOPPING S-702 150mm HIGH CURB FOR
L102XL102X79 CONTINOUS ANGLE ANCHORED TO • 38mm STEEL DECKING OIL CONTAINMENT
• 114mm CONC. TOPPING
CONCRETE AND HOLLOW CORE SLAB BY HILTI
• 38mm STEEL DECKING
ADHESIVE ANCHORS M20@800, 100 EMBEDMENT

150
W310X60 W310X60 W310X60
190mm CMU FULLY
REINFORCED AND
GROUTED (TYP.)
NEW GENERATOR

3228

3216
ROOM 8
S-702

100MM EQUIPMENT PAD REFER TO TYP. DETAILS SIM


CONC. 15M @250 T.B.E.W FOR DOWELS INTO
TOPPING EXISTING SLAB

400
EXG MOTOR RM & WET WELL FLOOR
3.609 m

SEE NOTE 2 SEE NOTE 1 11 SIM


S-702

1651
350 CONC WALL R/W 450 CONC WALL R/W
NEW OPENING IN 20M@200 VERT EF 20M@200 VERT EF
EXISTING WALL 20M@200 HORIZ EF 20M@200 HORIZ EF
450 NATIVE BACKFILL

750
300MM CONC. SLAB R/W
15M @200 T.B.E.W 2000
120 EMBEDMENT FULLY EXG INLET CHANNEL INVERT
350 EPOXY GROUTED 0.439 m

1087
BENCHING CONC. PIPE
SUPPORT
EXG PUMP FLOOR
-0.448 m

3334
MASS CONCRETE MASS CONCRETE FILL

EXG VALVE FLOOR


-2.304 m

MASS CONCRETE
EXG WET WELL INVERT
-2.914 m
VERTICAL REINFORCEMENT TO BE DOWELLED INTO
EXISTING CONCRETE MAT, 150MM EMBEDMENT
24/09/2018 6:56:33 PM

FULLY APOXY GROUTED

F SECTION
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

S-102
1 : 50

NOTES:
1. NEW WALL REBAR TO BE ANCHORED INTO EXISTING SLAB, DRILL IN 200mm, FULLY EPOXY
GROUTED BY HILTI HIT HY200 ADHESIVE ANCHOR SYSTEM. TYPICAL FOR NEW WALL CONNECTION
TO EXISTING STRUCTURE.

2. ALL CONCRETE SURFACE OF WET WELL AND CHANNEL (BASE SLAB, WALLS, ROOF SLABS, BEAMS,
AND COLUMNS) TO BE PROTECTED BY TWO COATS OF PROTECTIVE COATING - CEM-KOTE OR
APPROVED EQUAL (SEE SPECIFICATIONS)

VERIFY SCALES DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM


BAR IS 20mm ON SURVEYED
CLOVER POINT PUMP STATION
20mm MR 24/09/2018 3 ISSUED FOR CONSTRUCTION DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 15/06/2018 2 ISSUED FOR 100% DESIGN SUBMISSION SCALE
1 : 50 CHECKED J.P.
SECTION 'F' AND DETAILS
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 23/03/2018 1 ISSUED FOR 90% DESIGN SUBMISSION
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-309 3 OF
C B2 B1 B TYPICAL ROOF ASSEMBLY A1 A
• SEEDING/GROUNDCOVER
• 230~250mm TOPSOIL
• 500~850mm GEOFOAM
• DRAINAGE BOARD
ALUM. • 50mm HIGH STRENGTH EXTRUDED
GRATING POLYSTYRENE INSULATION PROTECTION
TIMBER DECK, SEE LANDSCAPE SHEET
DWGS FOR DETAILS • REINFORCED TWO COAT FLUID-APPLIED
T/O WALL EL. 11.702
WATERPROOFING MEMBRANE
• 350mm CONC. SLAB

800
GRADE (SEE CIVIL DWGS.)
ROOF PUMP ROOM

350

350

350
10.902 m

25M @150 TUL BLL


20M @200 VEF 20M @150 TLL BUL
20M @200 HEF

400 CAISSON PILE


20M @200 VEF ELECTRICAL ROOM
20M @250 TUL & BLL 25M @150 HEF
20M @200 HEF
20M @200 VEF
20M @200 TLL & BUL
T/O SLAB EL. 7.409

20M @200 TUL & BLL T/O CONC. SLAB EL. 7.409

300

300
584
20M @250 TLL & BUL
EL. 6.825

800
250
25M @150 HEF

TRANSFORMER ROOM 20M @200 VEF

3200
2400
20M @250 TUL & BLL
20M @200 TLL & BUL
1000x1000mm
CHECKERED PLATE
150mm CONC. PAD

400
UPPER LEVEL - NEW PUMP ROOM

300

400
3.909 m

20M @200 VEF


15M @200
20M @200 VEF 20M @200 HEF HVEF

300
20M @200 HEF
ALUM. LADDER
TO ACCESS 500 500 500
CHANNEL
20M @200 VEF
15M @200
20M @200 HEF 300 TBEW

4306
BENCHING SEE 500mm THK. TYPICAL BASE SLAB ASSEMBLY
PROCESS DWGS 25M @200 TUL & BLL WALL BEYOND • UNDERSLAB WATERPROOFING SYSTEM BY W. R.
20M @200 TLL & BUL MEADOWS 'PRECON' OR APPROVED EQUAL
• MUD SLAB
2000

• NATIVE BACKFILL
CONC. PIPE B/O CONC. WALL EL. -0.448
SUPPORT
EXG PUMP FLOOR
-0.448 m

500
NATIVE BACKFILL

500mm THK.
WALL BEYOND

BEDROCK PROFILE TO
BE CONFIRMED ONSITE
24/09/2018 6:56:35 PM

G SECTION
S-102
1 : 50
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

NOTES:
1. ALL CONCRETE SURFACE OF NEW WET WELL AND CHANNEL (BASE SLAB, WALLS, ROOF SLABS,
BEAMS, AND COLUMNS) TO BE PROTECTED BY TWO COATS OF PROTECTIVE COATING - CEM-KOTE
FLEX CR OR APPROVED EQUAL (SEE SPECIFICATIONS)

2. 190mm THICK CONCRETE BLOCK WALL REINFORCED WITH 15M @600 VERTICAL, 4.75mm@200
HORZ. LADDER. BOND BEAM EVERY 2000mm MAX. REINFORCED WITH 2-15M HORIZONTAL BARS.
ONE BEAM ON TOP OF WALL. 1200mm LONG AT 600 SPACING DOWEL, 600mm DOWEL INTO
FOUNDATION WALLS OR BEAMS TO MATCH SPACING OF WALL VERTICAL REINFORCEMENT AT
BOTTOM TO SPLICE WITH WALL REINFORCEMENT PROPERLY.

3. PROVIDE WIRE MESH 152x152 MW 25.8x25.8 WITH 50mm CONCRETE COVER FOR ALL
BENCHING/MASS CONCRETE INSIDE SEWAGE WET WELL OR CHANNELS FOR CRACK CONTROL.

4. CONCRETE BENCHING INSIDE SEWAGE TO BE DOWELED INTO STRUCTURAL SLABS/WALLS WITH


15M @800 EACH WAY. PROVIDE END HOOK OR DEVELOPMENT LENGTH AS REQUIRED.

VERIFY SCALES
MR 24/09/2018 6 ISSUED FOR CONSTRUCTION
DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM
BAR IS 20mm ON MR 19/07/2018 5 REISSUED FOR CONSTRUCTION - CAISSON WALL SURVEYED
MR 15/06/2018 4 ISSUED FOR 100% DESIGN SUBMISSION
CLOVER POINT PUMP STATION
20mm MR 16/05/2018 3 ISSUED FOR CONSTRUCTION - CAISSON WALL DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 26/03/2018 2 ISSUED FOR PRE-CONSTRUCTION REVIEW - CAISSON WALL SCALE
1 : 50 CHECKED J.P.
SECTION 'G' AND DETAILS
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 23/03/2018 1 ISSUED FOR 90% DESIGN SUBMISSION
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-310 6 OF
TYPICAL ROOF ASSEMBLY
• SEEDING/GROUNDCOVER
E D3 D2 D1 • 230~250mm TOPSOIL
B2 B1 B A1
• 500~850mm GEOFOAM
1
• DRAINAGE BOARD S-312
• 50mm HIGH STRENGTH EXTRUDED Sim
POLYSTYRENE INSULATION PROTECTION P
SHEET S-107
• REINFORCED TWO COAT FLUID-APPLIED
WATERPROOFING MEMBRANE ROOF PUMP ROOM
15M @200 TUL • 100mm CONC. TOPPING c/w 152x152 MW
10.902 m
15M @300 TLL & BUL 25.8x25.8 WELDED WIRE MESH
20M @150 BLL • 305mm CORE SLAB
T/O GRADE
20M @200 T&B. E.W. EXG MIDDLE ROOF
SEE CIVIL DWGS.
9.888 m

250

855

243
800
RB6 EL. 8.783

500
7.5 TONNE
BRIDGE CRANE
700 1200
1.5 TONNE MONORAIL
1.0 TONNE MONORAIL BETWEEN DOUBLE TEE RIBS
SEE DWGS S204 S200X36 4.
(TYP.) 550x600 RB3 RB4 RB5
AND S-508 FOR DETAILS S-318
20M @200 TLL BUL T/O OF PLATFORM EL. 7.409
20M @200 HEF 2. 20M @200 HEF 20M @300 VEF
20M @200 TUL BLL ODOUR CONTROL S-318
COLUMN 'C2' AHU
AND SCREENING ROOM 20M @200 VEF 25M @150 HEF
190mm CMU WALL
ROOM FULLY GROUTED
20M @200 VEF SEE NOTE-2 900MM CAISSONS
(TYP.)

CONC. PIPE SUPPORT

150mm 25M @200


ADDITIONAL 5-25M
thk. TUL BLL

1189
20M @250 20M @250 CONTINOUS
CONC.. 20M @200
TUL & BLL 400 300 457 500 PAD TUL & BLL
15M @250 T&B 15M @250 TLL BUL
T&B UPPER LEVEL - NEW PUMP ROOM

300

400
EXG MOTOR RM & WET WELL FLOOR 400mm CONC. SLAB 3.909 m
3.609 m

500
20M @200 VEF B2 B3 400MM THK. WALL
SEE NOTE 1 (CONTAINING CRYSTALLING
20M @200 HEF WATERPROOFING ADDITIVE IN
20M @200 VEF 20M @200 VEF 25M @200 VEF EL. 2.100
EL. 2.450 NEW PUMP EL. 2.100 THE CONCRETE MIX)
20M @200 HEF 20M @200 HEF
20M @200 HEF ROOM
NEW WEIR
PLATE EL. 1.850
CONC. COLUMN PIPE SUPPORT
'C2' TO BE
SEATED ON
MASS. CONC.
500 WET WELL 500 20M @200 VEF
20M @200

2200
EXG INLET CHANNEL INVERT T&B. E.W. 25M @150 HEF
SEE NOTE 1 150mm THK CONC.

400
0.439 m 25M @150 VIF PAD FOR PUMPS CONC. 100X50mm DEEP GUTTER
PIPE 20M @300 DRAIN ALONG FOOT OF

1489
1000
25M @150HIF SUPPORT TLL & BUL WALL, 1% SLOPE TO SUMP
PIT (TYP.)
B/O CONC. WALL EL. -0.709 400mm THK. NEW CONC. 25M @200

402
WALL ON GRID '5' SITTING TUL & BLL
LOWER LEVEL- NEW PUMP ROOM

150
EXISTING MASS ON MASS CONCRETE
15M @200 DOWELS TO BE INSTALLED TO BENCHING
CONCRETE (MATCH THE PROFILE OF NEW CONC. -1.000 m
EXISTING CHANNEL WALL ALL AROUND THE
PROPOSED NEW WALL OPENINGS, BY HILTI HIT WALL TO EXISTING WALL)

1200
25M @200 VOF
HY200 ADHESIVE ANCHORING SYSTEM, 150mm 1200mm CONC. SLAB
MIN. EMBEDMENT TYP.
20M @200 HOF SEE NOTE-3
ASSUMED ROCK B/O CONC. WALL EL. -2.304
LINE
125

1314
EXG WET WELL INVERT
-2.914 m

600
UNDISTURBED
25M @200 NATIVE TYPICAL BASE SLAB ASSEMBLY
SOIL • UNDERSLAB WATERPROOFING SYSTEM BY W. R.
1314 MEADOWS 'PRECON' OR APPROVED EQUAL
20M @200 T&B • MUD SLAB
25M @200 T&B • NATIVE BACKFILL

ROCK PROFILE AT GRID 9 AND


A1 IS ASSUMED TO BE -11.0M
AS PER GEOTECHNICAL
REPORT

H SECTION
S-101
1 : 50
24/09/2018 6:56:37 PM

NOTES:
1. ALL CONCRETE SURFACE OF NEW WET WELL AND CHANNEL (BASE SLAB, WALLS, ROOF SLABS,
BEAMS, AND COLUMNS) TO BE PROTECTED BY TWO COATS OF PROTECTIVE COATING - CEM-KOTE
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

FLEX CR OR APPROVED EQUAL (SEE SPECIFICATIONS)

2. 190mm THICK CONCRETE BLOCK WALL REINFORCED WITH 15M @600 VERTICAL IN GROUTED CELL,
4.75mm@200 HORZ. LADDER. BOND BEAM EVERY 2000mm MAX. REINFORCED WITH 2-15M
HORIZONTAL BARS. ONE BEAM ON TOP OF WALL. 1200mm LONG AT 600 SPACING DOWEL, 600mm
DOWEL INTO FOUNDATION WALLS OR BEAMS TO MATCH SPACING OF WALL VERTICAL
REINFORCEMENT AT BOTTOM TO SPLICE WITH WALL REINFORCEMENT PROPERLY.

3. PROVIDE WIRE MESH 152x152 MW 25.8x25.8 WITH 50mm CONCRETE COVER FOR ALL
BENCHING/MASS CONCRETE INSIDE SEWAGE WET WELL OR CHANNELS FOR CRACK CONTROL.

4. CONCRETE BENCHING INSIDE SEWAGE TO BE DOWELED INTO STRUCTURAL SLABS/WALLS WITH


15M @800 EACH WAY. PROVIDE END HOOK OR DEVELOPMENT LENGTH AS REQUIRED.

VERIFY SCALES
MR 24/09/2018 6 ISSUED FOR CONSTRUCTION
DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM
BAR IS 20mm ON MR 19/07/2018 5 REISSUED FOR CONSTRUCTION - CAISSON WALL SURVEYED
MR 15/06/2018 4 ISSUED FOR 100% DESIGN SUBMISSION
CLOVER POINT PUMP STATION
20mm MR 16/05/2018 3 ISSUED FOR CONSTRUCTION - CAISSON WALL DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 26/03/2018 2 ISSUED FOR PRE-CONSTRUCTION REVIEW - CAISSON WALL SCALE
1 : 50 CHECKED J.P.
SECTION 'H' AND DETAILS
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 23/03/2018 1 ISSUED FOR 90% DESIGN SUBMISSION
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-311 6 OF
B1

TYPICAL ROOF ASSEMBLY


• SEEDING/GROUNDCOVER
D3 D2 D1 B2 B1 • 230~250mm TOPSOIL A1
Sim • 500~850mm GEOFOAM
100mm THK. TYPICAL ROOF ASSEMBLY
• DRAINAGE BOARD
CONC. TOPPING • SEEDING/GROUNDCOVER 1 • 50mm HIGH STRENGTH EXTRUDED POLYSTYRENE INSULATION PROTECTION SHEET
• 230~250mm TOPSOIL S-312 • REINFORCED TWO COAT FLUID-APPLIED WATERPROOFING MEMBRANE
• 500~850mm GEOFOAM
ROOF PUMP ROOM • DRAINAGE BOARD
• 100mm CONC. TOPPING c/w 152X152 MW25.8X25.8 WELDED WIRE MESH
T/O RETAINING WALL • 3120X721 DOUBLE TEE Sim
10.902 m • 50mm HIGH STRENGTH EXTRUDED
305mm HOLLOW 11.800 m POLYSTYRENE INSULATION P
CORE SLAB PROTECTION SHEET S-107

1200
• REINFORCED TWO COAT FLUID-APPLIED
.) ROOF PUMP ROOM
100mm THK. DOUBLE TEE
EE C IVIL DWGS WATERPROOFING MEMBRANE
CONC. TOPPING 100 GRADE (S • 100mm CONC. TOPPING c/w 152x152 MW 10.902 m
150 25.8x25.8 WELDED WIRE MESH
• 305mm CORE SLAB

100
305 100

305
CRANE RAIL
16mm STEEL PLATE c/w RAIL CLIP MONORAIL BEAM S200X36, 550x600 RB3 RB4 RB5
4-M20 HILTI ANCHOR BOLTS, SEE MONORAIL FIXING
MIN. EMBEDMENT = 130mm DETAIL-1 ON DWG. S-508
AT DISTANCE CONFIRMED 400 190mm CMU BLOCK
BY CRANE SUPPLIER 9.000 T/O CORBEL FULLY GROUTED
20mm NON-SHRINK 5
400
300

GROUT C2 20M @200 VEF S-202 20M @200 VEF


EXIT
800

CORRIDOR 20M @200 HEF 25M @150 HEF

20M @250 HEF 500

EL. 5.909
25M H 3-25M, H 20M @250 VEF
CONTINUOUS CONTINUOUS

25M @300

2200

2000
CONC. PIPE
WEIR PLATE 25M @200 TUL SUPPORT ADD'L 5-25M
SEE PROCESS DWGS BLL TYP. CONC PIPE CONTINOUS
150mm CONC. PAD 20M @200 TLL SUPPORT
BUL
UPPER LEVEL - NEW PUMP ROOM

300

400
1 DETAIL 3.909 m

25M @200 VEF B10 B5


20M @200 VEF B5
S-312
1 : 25

1160

970
980

20M @200 HEF ALUM. LADDER SEE BEAM DETAIL 20M @200 VEF
20M @200 HEF 25M @200 VEF 'B19'
EL. 2.450
20M @200 HEF 25M @150 HEF
300

600
300
750

EL. 1.850 INLET 15M @200 VEF


EL. 1.559
STORM 20M @200 HEF
CHANNEL C1 100X50mm DEEP GUTTER

2000
400 C2
DRAIN ALONG FOOT OF
EX. OVER EX. INLET 20M @300 TUL & BLL

1410
WALL, 1% SLOPE TO SUMP
FLOW SANITARY 20M @300 TLL & BUL
100X50mm DEEP GUTTER PIT
CHANNEL CHANNEL 20M @200
DRAIN ALONG FOOT OF
T&B E W SANITARY WALL, 1% SLOPE TO SUMP
WET WELL PIT

400
150mm THK. CONC. T/O CONC. -0.850
ADD'L PAD FOR PUMPS 20M @300 TLL & BUL

150
EXISTING MASS CONCRETE
A1 500 3x2-25M BTM. 100 25M @200 TUL & BLL
MASS LOWER LEVEL- NEW PUMP ROOM
20M DOWELS WELDED TO CONCRETE 20M @250 VEF
FLANGE OF KING PILE AT FILL -1.000 m
SPACING OF 400mm 20M @200 HEF 2

1200
VERTICALLY ALL THE WAY EL. -1.832 25M @200 TUL & BLL 1200mm CONC. SLAB S-312
SEE NOTE-2
DOWN TO BOTTOM
25M @200 TLL & BUL
ELEVATION OF PUMP ROOM
BASE SLAB. SEE NOTE 1 1050mm THK. MAT
(SEE DETAILS ON S-107) 125
400

W610 KING PILE EXG WET WELL INVERT

1764
-2.914 m
1050

25M @200
200 3-20M NATIVE SOIL
CONT.
LOWER LEVEL- NEW PUMP ROOM
1764 TYPICAL SUBGRADE
-1.000 m • UNDERSLAB WATERPROOFING SYSTEM BY W. R.
EQ

MEADOWS 'PRECON' OR APPROVED EQUAL


• MUD SLAB
• NATIVE BACKFILL
TYPICAL BASE SLAB ASSEMBLY
TEMPORARY SHORING
EQ

• CAST STRUCTURE ON
24/09/2018 6:56:40 PM

• MUD SLAB
• MASS CONCRETE
EQ

EXG VALVE FLOOR BEDROCK PROFILE TO


S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

BE CONFIRMED ON SITE
-2.304 m NOTES:
1. ALL CONCRETE SURFACE OF NEW WET WELL AND CHANNEL (BASE SLAB, WALLS, ROOF SLABS,
2-20M 1000 LONG DOWELS BEAMS, AND COLUMNS) TO BE PROTECTED BY TWO COATS OF PROTECTIVE COATING - CEM-KOTE
ANCHORED TO EACH FLEX CR OR APPROVED EQUAL (SEE SPECIFICATIONS)
PRIMARY CAISSON AT PUMP
ROOM BASE SLAB LEVEL AT 2. 190mm THICK CONCRETE BLOCK WALL REINFORCED WITH 15M @600 VERTICAL IN GROUTED CELL,
HORIZONTAL SPACING OF 4.75mm@200 HORZ. LADDER. BOND BEAM EVERY 2000mm MAX. REINFORCED WITH 2-15M
750mm. HILTI HI HY 200 HORIZONTAL BARS. ONE BEAM ON TOP OF WALL. 1200mm LONG AT 600 SPACING DOWEL, 600mm
ADHESIVE ANCHOR SYSTEM, DOWEL INTO FOUNDATION WALLS OR BEAMS TO MATCH SPACING OF WALL VERTICAL
200mm EMBEDMENT MIN. REINFORCEMENT AT BOTTOM TO SPLICE WITH WALL REINFORCEMENT PROPERLY.
FULLY GROUTED
3. PROVIDE WIRE MESH 152x152 MW 25.8x25.8 WITH 50mm CONCRETE COVER FOR ALL
BENCHING/MASS CONCRETE INSIDE SEWAGE WET WELL OR CHANNELS FOR CRACK CONTROL.

2 DETAIL 4. CONCRETE BENCHING INSIDE SEWAGE TO BE DOWELED INTO STRUCTURAL SLABS/WALLS WITH J SECTION
15M @800 EACH WAY. PROVIDE END HOOK OR DEVELOPMENT LENGTH AS REQUIRED.
S-101
S-312
1 : 25 1 : 50

MR 24/09/2018 7 ISSUED FOR CONSTRUCTION


VERIFY SCALES
MR 19/07/2018 6 REISSUED FOR CONSTRUCTION - CAISSON WALL
DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM
BAR IS 20mm ON MR 15/06/2018 5 ISSUED FOR 100% DESIGN SUBMISSION SURVEYED
MR 16/05/2018 4 ISSUED FOR CONSTRUCTION - CAISSON WALL
CLOVER POINT PUMP STATION
20mm MR 26/03/2018 3 ISSUED FOR PRE-CONSTRUCTION REVIEW - CAISSON WALL DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 23/03/2018 2 ISSUED FOR 90% DESIGN SUBMISSION SCALE
As indicated CHECKED J.P.
SECTION 'J' AND DETAILS
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 15/02/2018 1 ISSUED FOR PRECAST ROOF SLAB
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-312 7 OF
D3 D2
TYPICAL ROOF ASSEMBLY B1 D3
1 • SEEDING/GROUNDCOVER
S-313 • 230~250mm TOPSOIL
• 500~850mm GEOFOAM
• DRAINAGE BOARD SEE ARCH. DWGS
• 50mm HIGH STRENGTH EXTRUDED POLYSTYRENE FOR DETAIL
T/O RETAINING WALL INSULATION PROTECTION SHEET Sim
• REINFORCED TWO COAT FLUID-APPLIED 1
11.800 m WATERPROOFING MEMBRANE T/O RETAINING WALL
S-312
• MIN. 100mm CONC. TOPPING c/w 152x152 MW

1200
11.800 m
25.8x25.8 WELDED WIRE MESH
• 305mm CORE SLAB ROOF PUMP ROOM
SEE CIVIL DWGS FOR GRADE 10.600 10.902 m 150mmØ PERFORATED PIPE
SUBDRAIN WRAPPED WITH
GEOTEXTILE

2300
HEIGHT TO BE CONSISTENT
WITH POSITIVE DRAINAGE
550x600 RB3 RB4 RB5 150 OF SUBDRAIN.
SEE CIVIL DWGS

750

150
W250X101
(TYP. OF 7)
20M @200 VEF EXG MIDDLE ROOF

1140
20M @200 HEF 9.888 m

S250X131

7.5 TON TELESCOPIC


MONORAIL 1 DETAIL

3000
S-313
1 : 25

300
400X700 B9 UPPER LEVEL - NEW PUMP ROOM
3.909 m

25M @250 VEF 20M @200 VEF


20M @200 HEF SEE NOTE 1
EL. 2.450 20M @200 HEF 25M @200 VEF
20M @200 HEF

EL. 1.850 300 300


15M @200 VEF
STORM400
WET WELL 20M @200 HEF
20M @300

2000
TUL & BLL 20M @300
20M @300 T&B E W
TLL & BUL
SEE PROCESS DWGS
FOR PIPE OPENING
SIZES
SLAB OPENING ADD'L
500 SEE PLAN 3x2-25M BTM.

LOWER LEVEL- NEW PUMP ROOM


-1.000 m
EL. -1.832
CONC. BENCHING
SEE NOTE-3
25M @200 TUL & BLL

NEW 1050 SLAB 25M @200 TLL & BUL

EXG WET WELL INVERT


-2.914 m
1050

MASS
CONCRETE TEMPORARY SHORING

ASSUMED
ROCK-LINE
24/09/2018 6:56:42 PM

K SECTION
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

NOTES:
S-101
1 : 50 1. ALL CONCRETE SURFACE OF NEW WET WELL AND CHANNEL (BASE SLAB, WALLS, ROOF SLABS,
BEAMS, AND COLUMNS) TO BE PROTECTED BY TWO COATS OF PROTECTIVE COATING - CEM-KOTE
FLEX CR OR APPROVED EQUAL (SEE SPECIFICATIONS)

2. 190mm THICK CONCRETE BLOCK WALL REINFORCED WITH 15M @600 VERTICAL IN GROUTED CELL,
4.75mm@200 HORZ. LADDER. BOND BEAM EVERY 2000mm MAX. REINFORCED WITH 2-15M
HORIZONTAL BARS. ONE BEAM ON TOP OF WALL. 1200mm LONG AT 600 SPACING DOWEL, 600mm
DOWEL INTO FOUNDATION WALLS OR BEAMS TO MATCH SPACING OF WALL VERTICAL
REINFORCEMENT AT BOTTOM TO SPLICE WITH WALL REINFORCEMENT PROPERLY.

3. PROVIDE WIRE MESH 152x152 MW 25.8x25.8 WITH 50mm CONCRETE COVER FOR ALL
BENCHING/MASS CONCRETE INSIDE SEWAGE WET WELL OR CHANNELS FOR CRACK CONTROL.

4. CONCRETE BENCHING INSIDE SEWAGE TO BE DOWELED INTO STRUCTURAL SLABS/WALLS WITH


15M @800 EACH WAY. PROVIDE END HOOK OR DEVELOPMENT LENGTH AS REQUIRED.

MR 24/09/2018 8 ISSUED FOR CONSTRUCTION


VERIFY SCALES
MR 19/07/2018 7 REISSUED FOR CONSTRUCTION - CAISSON WALL
DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM
BAR IS 20mm ON MR 15/06/2018 6 ISSUED FOR 100% DESIGN SUBMISSION SURVEYED
MR 16/05/2018 5 ISSUED FOR CONSTRUCTION - CAISSON WALL
CLOVER POINT PUMP STATION
20mm MR 26/03/2018 4 ISSUED FOR PRE-CONSTRUCTION REVIEW - CAISSON WALL DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 23/03/2018 3 ISSUED FOR 90% DESIGN SUBMISSION SCALE
As indicated CHECKED J.P.
SECTION 'K' AND DETAILS
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 02/03/2018 2 ISSUED FOR CONSTRUCTION - CAISSON WALL
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-313 8 OF
TYPICAL ROOF ASSEMBLY 200mm THK CONC . WALL
• SEEDING/GROUNDCOVER R/W 15M @200 HVM (TYP.)
• 230~250mm TOPSOIL VERT. REBAR DOWELS IN
B1 • 500~850mm GEOFOAM
B ACCESS DOUBLE TEE SLAB BY HILTI
A1
• DRAINAGE BOARD HATCH HIT-HY200, 125mm
• 50mm HIGH STRENGTH EXTRUDED POLYSTYRENE EMBEDMENT
T/O WALL EL. 12.300 INSULATION PROTECTION SHEET GRADE (SEE CIVIL DWGS.)

200
• REINFORCED TWO COAT FLUID-APPLIED
WATERPROOFING MEMBRANE
• 100mm CONC. TOPPING c/w 152X152 MW25.8X25.8 Sim

1398
WELDED WIRE MESH P
• 3120X721 DOUBLE TEE S-107

ROOF PUMP ROOM


10.902 m
PILE CAP

Sim 4-25M T BTW PILES, ABOVE PIPE OPENINGS

1045
1 10 @300
S-312 4-25M B BTW PILES

SEE PROCESS
1200mmØ
1100mmØ
PROCESS PIPE

20M @200 VEF NEW PUMP ROOM


20M @200 HEF UPPER LEVEL LINTEL BEAM ABOVE OPENING
(900mm DEEP BEAM IN FILLER PILE)
500 WALL OPENING THRU CONC. WALL
AND SECANT WALL, SEE
PROCESS FOR PIPE INVERT EL.

20M @200 VEF

25M @150 HEF


25M @200
TUL & BLL
ADD'L 5-25M
20M @200 CONTINOUS
TLL & BUL

400
UPPER LEVEL - NEW PUMP ROOM
3.909 m

B16 B16

25M @200 VEF


20M @200 VEF

20M @200 HEF 25M @150 HEF


NEW PUMP ROOM
LOWER LEVEL
100X50mm DEEP GUTTER
DRAIN ALONG FOOT OF
WALL, 1% SLOPE TO SUMP
PIT (TYP.)
20M @300
TLL & BUL
15M @300 T.E.W 25M @200
TUL & BLL
LOWER LEVEL- NEW PUMP ROOM
-1.000 m

1200
125

EXG WET WELL INVERT

1764
-2.914 m
25M @200
3-20M TYPICAL SUBGRADE
CONT. • UNDERSLAB WATERPROOFING SYSTEM BY
W. R. MEADOWS 'PRECON' OR APPROVED
1764 EQUAL
• MUD SLAB
• NATIVE BACKFILL
TEMPORARY SHORING

MASS CONCRETE
UNDISTURBED
NATIVE
SOIL
24/09/2018 6:56:45 PM

SOCKET PILES INTO


BEDROCK (TYP.)
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

BEDROCK PROFILE
TO BE CONFIRMED
ROCK PROFILE AT GRID 9 AND
ONSITE
A1 IS ASSUMED TO BE -11.0M
AS PER GEOTECHNICAL
REPORT

L SECTION
S-102
1 : 50
MR 24/09/2018 7 ISSUED FOR CONSTRUCTION
VERIFY SCALES
MR 15/06/2018 6 ISSUED FOR 100% DESIGN SUBMISSION
DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM
BAR IS 20mm ON MR 16/05/2018 5 ISSUED FOR CONSTRUCTION - CAISSON WALL SURVEYED
MR 26/03/2018 4 ISSUED FOR PRE-CONSTRUCTION REVIEW - CAISSON WALL
CLOVER POINT PUMP STATION
20mm MR 23/03/2018 3 ISSUED FOR 90% DESIGN SUBMISSION DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 02/03/2018 2 ISSUED FOR CONSTRUCTION - CAISSON WALL SCALE
1 : 50 CHECKED J.P.
SECTION ' L'
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 02/02/2018 1 ISSUED FOR CAISSON WALL TENDER
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-314 7 OF
A C

T/O EX. RETAINING WALL


12.478 m

NEW INFILL WALL BETWEEN THE BEAMS TO


EXG UPPER ROOF MATCH THE WALL BELOW
10.802 m

EXG MIDDLE ROOF


9.888 m

EXTEND TO OPENING ABOVE


THE DOOR TO ACCOMODATE
SILENCER AND EXHAUST MECH. DUCT.
FAN UNITS SUPPORTING
FRAME. TYPICAL WALL PLATE FROM STEEL BEAM TO EXISTING
WEIGHT OF UNIT=26kN CONCRETE WALL (TYP. OF 3) 450x300x20 WALL
4-19M HILTI HIT HY200 PLATE ANCHORED TO EXISTING AND CONC. WALL OR
NEW CMU WALL ANCHORS 150mm BEAM BY 4-25Ø HILTI HIT-HY200 ADHESIVE ANCHOR,
EMBEDMENT (TYP.) STEEL GRATING 150mm EMBEDMENT, 250 LG 2-L102x102x6.4 CLIP ANGLE
EXG MEZZANINE LEVEL CONNECT BEAM AND WALL PLATE BY 3-20Ø
A325 BOLTS
6.825 m
W310x60 W310x60 W310X39

W310X28
NEW CMU

DOOR HEIGHT
WALL

3000
2678
METAL STUD WALL NEW DOOR
SEE ARCH. DWGS SEE ARCH. DWGS

EXG MOTOR RM & WET WELL FLOOR


3.609 m

1428
450 CONC WALL R/W
20M @200 VERT EF
20M@200 HORIZ EF

2400
EXG PUMP FLOOR
-0.448 m

MASS CONCRETE

EXG VALVE FLOOR


-2.304 m
24/09/2018 6:56:46 PM
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

M SECTION
S-102
1 : 50

VERIFY SCALES DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM


BAR IS 20mm ON SURVEYED
CLOVER POINT PUMP STATION
20mm MR 24/09/2018 3 ISSUED FOR CONSTRUCTION DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 15/06/2018 2 ISSUED FOR 100% DESIGN SUBMISSION SCALE
1 : 50 CHECKED J.P.
SECTION 'M' AND DETAILS
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 23/03/2018 1 ISSUED FOR 90% DESIGN SUBMISSION
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-315 3 OF
3 4

CUTOFF 250X150, 285 DEEP WALL


EXG MIDDLE ROOF POCKET ON TOP OF EXISTING
9.888 m CONC. WALL AT BEAM SUPPORT 16mm THICK GALV. CHECKERED PLATE SUPPORTED ON
LOCATION. GALV. STEEL BEAM (TYP.) CHECKERED PLATE TO BE
WELDED TO EDGE OF TOP FLANGE OF 250 BY FILLET WELD:
ANCHOR THE BEAM'S BOTTOM 6mm THICK, 50mm LG @ 1200mM ON BOTH SIDES.
FLANGETO CONCRETE BY 2-16 HILTI
HIY-HY200 ADHESIVE ANCHORS,
150mm EMBEDMENT. FULLY GROUT
EXG MOTOR RM & WET WELL FLOOR
THE WALL POCKET BY 35 MPa 3.609 m
CONCRETE. TYP. FOR ALL SUPPORTS

285 (TYP.)
W250x58

150

16mm THICK GALV. CHECKERED 16mm THICK GALV. CHECKERED


PLATE SUPPORTED ON GALV. PLATE SUPPORTED ON GALV.
STEEL BEAM (TYP.) STEEL BEAM (TYP.)

EXG MOTOR RM & WET WELL FLOOR


3.609 m

W250x58 W250x58
150
1 DETAIL
150
ALUMINUM OPTION:
S-316
1 : 25
ALUMINUM BEAM AND ALUM. CHECKERED
1 PLATE DESIGN TO BE PROVIDED BY SUPPLIER.
S-316 P.ENG. STAMPED SHOP DWGS SHALL BE
SUBMITTED FOR REVIEW.

LIVE LOAD FOR CHECKERED PLATE ARE = 15kPa.

EXG WET WELL INVERT


-2.914 m

EXG LWR WET WELL INVERT


-3.828 m
24/09/2018 6:56:48 PM

R SECTION
S-316
1 : 50
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

VERIFY SCALES DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM


BAR IS 20mm ON SURVEYED
CLOVER POINT PUMP STATION
20mm DRAWN S.R. DATE 02/02/2018 STRUCTURAL
SCALE
As indicated CHECKED J.P.
SECTION 'R' AND DETAIL
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 24/09/2018 1 ISSUED FOR CONSTRUCTION
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-316 1 OF
8 5
5

A1 A1 A1
4- HSS102X102X6.4 STEEL
POST (TYP.) WITH
250x250x20 BASEPLATE 4-
20M HILTI HIT HY200
ADHESIVE ANCHORS,
150mm MIN. EMBEDMENT T/O ELEC. RM ACCESS PLATFORM
TYP. FOR ALL POSTS. EL. 7.409

1870

310X39
975 1960

950 7 RUNS @ 280


C250x25 (TYP.) RISER = 175 3360 919

12 RUNS @ 280 966


RISER = 175
250X33
T/O LANDING
875
900

900
UP C250x25
EL. 0.403
T/O LANDING

900

989

1000
GRATING (TYP.) UP EL. 1.104
C250x25

580 GRATING (TYP.)

HANDRAIL TO HANDRAIL TO
EXTEND 580mm EXTEND 580mm MIN. 4- HSS102X102X6.4
STEEL POST, TYP.
1097

MIN.
LOWER LVL. PUMP RM. LOWER LEVEL PUMP RM
EL. -1.000 EL. -1.000

B B B
C310 DEEP ALUMINIUM OR GALV. STEEL
STRINGER CHANNEL (TYP.) TO BE DESIGNED
BY STAIR MANUFACTURER. PROFESSIONAL
ENGINNER STAMPED DRAWING SHALL BE
SUBMITTED FOR REVIEW AND APPROVAL.

19 RUNS @ 280
REFER TO TYPICAL DETAILS FOR MORE

RISER = 180
INFORMATION

5320
2089

16 RUNS @ 280
19 RUNS @ 280
RISER = 175

RISER = 175
4480
5320

300

900

900
HANDRAIL TO TIE
INTO HANDRAIL OF HANDRAIL TO TIE INTO
PLATFORM GUARDRAIL UP
ADJACENT
HANDRAIL TO TIE
STAIR HANDRAIL TO TIE EXTEND HANDRAIL INTO ADJACENT STAIR
INTO PLATFORM UPPER LEVEL PUMP RM 580mm MIN.
GUARDRAIL EL. +3.909
900 UPPER LEVEL PUMP RM
EL. +3.909
UPPER LVL. PUMP RM.
24/09/2018 6:56:50 PM

EL. 3.909
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

STAIR 1 STAIR 2 STAIR 3


1 : 25 1 : 25 1 : 25

VERIFY SCALES DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM


BAR IS 20mm ON SURVEYED
MR 24/09/2018 4 ISSUED FOR CONSTRUCTION (S-507)
CLOVER POINT PUMP STATION
20mm MR 15/06/2018 3 ISSUED FOR 100% DESIGN SUBMISSION DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 23/03/2018 2 ISSUED FOR 90% DESIGN SUBMISSION SCALE
1 : 25 CHECKED J.P.
STAIRS DETAIL
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 19/01/2018 1 ISSUED FOR 50% DESIGN SUBMISSION
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-317 4 OF
SUITE THE CORE CONCRETE TOPPING
PATCH BLOWOUT WITH 100mm THK. CONC. TOPPING 300x100x13mm
PROPRIETRY NON-SHRUNK THICK PLATE
CORE SLAB PATCH GROUT (TYP.)
2-20 DIA. BOLTS WITH LOCK PATCH BLOWOUT WITH
250 PROPRIETRY NON-SHRUNK
NUTS AND WASHERS
PATCH GROUT (TYP.)

GROUT SOLID PRECAST


CORESLAB

GROUT SOLID

HSS 76x76x6.4 HSS 89x89x89x89.5


HSS 89x89x89x89.5 600mm LG
600mm LG
DRILL THROUGH
PRECAST AT CORES
HSS 76x76x6.4 2-20 DIA. A325 BOLTS WITH
2L75x75x6.4 DIAGONAL BEVELED WASHERS-CHIP
BRACING ON EACH SIDE HSS 89x89, 9.5mm THICK,
2L75x75x6.4 DIAGONAL THREADS 300mm LONG
BRACING ON EACH SIDE
HSS 76x76x6.4 MONORAIL BEAM. CUTOFF IN HSS
800

S200x34
HSS 76x76x6.4 HSS 89x89x89x89.5
600mm LG SUPPORT DETAIL AT HOLLOW CORE SLAB

50 (TYP.)
NOTE:
MAXIMUM SPACING OF MONORAIL BEAM SUPPORT SHALL BE
1200 o/c AND MAXIMUM FROM EACH END OF MONORAIL BEAM.
HSS 89x89x89x89.5
600mm LG

INSTALL SUPPORTS
PRECAST CORESLAB @ MAX600mm FROM EACH
2-20 DIA. A325 BOLTS S200x34 END OF MONORAIL BEAM AND
WITH BEVELED @ MAX 1200mm
WASHERS-CHIP THREADS PRECAST CORESLAB
SPACING ELSEWHERE
600
S200x34
GROUT SOLID

1. DETAIL 2. SECTION HSS 89x89, 9.5mm THICK,


S-204 S-204 300mm LONG
1 : 10 1 : 10
6

MONORAIL BEAM.
S200x36

STOPPER
20mm THICK PLATE

S200x34 300(MIN.)

100 MIN.
STOPPER
DETAIL

MONORAIL FIXING DETAIL-1


B 400
PATCH BLOWOUT WITH NTS
SUITE THE CORE PROPRIETRY NON-SHRUNK
PATCH GROUT (TYP.)
CORE SLAB NOTE:
MONORAIL BEAM SIZE TO BE S250x38 FOR 1.5 TONNE CAPACITY AT ELECTRICAL
ROOM PLATFORM.
GROUT
SOLID

HSS 76x76x6.4 HSS 89x89x89x89.5 HSS 89x89x89x89.5


150mm LONG 600mm LG 600mm LG
600
150
HSS 76x76x6.4 HSS 76x76x6.4

HSS 76x76x6.4
IN THE MIDDLE
800

2L75x75x6.4 DIAGONAL
HSS 76x76x6.4 BRACING ON EACH SIDE
HSS 76x76x6.4
IN THE MIDDLE
24/09/2018 6:56:53 PM

HSS 89x89x89x89.5 HSS 89x89x89x89.5


600mm LG 600mm LG
2-20 DIA. A325 BOLTS
WITH BEVELED
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

WASHERS-CHIP
THREADS S200x34

S200x34
2-20 DIA. A325 BOLTS WITH
BEVELED WASHERS-CHIP
3. SECTION THREADS
4. DETAIL
S-204 S-204
1 : 10 1 : 10

VERIFY SCALES DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM


BAR IS 20mm ON SURVEYED
CLOVER POINT PUMP STATION
20mm DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 24/09/2018 2 ISSUED FOR CONSTRUCTION (S-508) SCALE
As indicated CHECKED J.P.
MONORAIL DETAILS
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 15/06/2018 1 ISSUED FOR 100% DESIGN SUBMISSION
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-318 2 OF
2 3 4 5 6 7 8 9
2 3 4 5 6 7 8 9

A A

A1 A1
Z2 Z5 Z4 Z2 Z5 Z4

UP UP UP
Z1
B B
Z1 Z1 Z1 Z1 Z1

Z3 Z3

Z3 Z3 Z10 Z3 Z3 Z10
Z2 Z2
Z9 Z5 Z9 B1 B1
Z9
Z8 Z7 Z8 Z8 Z3 Z7 Z8 Z3 Z4
Z2
C B2 C Z8 Z3 B2
Z3

D1 D D1
D
D2 D2
Z4 Z8 Z3
Z9 Z9
D3 D3

E Z8 Z8 E Z4 Z4

LOWER LEVEL ZONE KEY PLAN UPPER LEVEL ZONE KEY PLAN
1 : 200 1 : 200

CONCENTRATED (ZONE) REINFORCEMENT SCHEDULE


ZONE TYPE Z1 Z2 Z3 Z4 Z5 Z6 Z7 Z8 Z9 Z10

ROOF

SHEAR WALL NOTES

1. FOR GENERAL NOTES AND TYPICAL DETAILS SEE S-00 AND S-500 SERIES DRAWINGS.

2. FOR SHEAR WALL AND ZONE STEEL LOCATIONS, SEE ZONE KEY PLANS.

3. UNLESS OTHERWISE NOTED ON SHEAR WALL ELEVATIONS, SEE SPECS FOR CONCRETE COMPRESSIVE STRENGTH.
UPPER LEVEL
300 4. FOR CONCENTRATED (ZONE) REINFORCEMENT, SEE TC-WALL-42 AND ZONE REINFORCEMENT SCHEDULE(S) ON
150 150 150 150 150 300 DRAWING S-319.

5. TIE ZONE REINFORCEMENT AS COLUMNS, REFER TO TYPICAL DETAIL TC-COL-02.


≤ 400

≤ 400

≤ 400
≥ 450

≥ 450

≥ 450
300 300

> 750
6. UNLESS OTHERWISE NOTED IN ZONE REINFORCEMENT SCHEDULES, ELEVATIONS OR DETAILS, TIE SIZE AND

≤ 700
150

150

SPACING TO BE SAME AS SPECIFIED FOR COLUMNS. FOR RECTANGULAR END ZONES, “MINIMUM COLUMN

≤ 400
DIMENSION” (WHICH DETERMINES MAXIMUM TIE SPACING) IS EQUAL TO THE SHORTER ZONE DIMENSION; FOR “T”
150
AND “L” SHAPED ZONES, THAT “MINIMUM COLUMN DIMENSION” IS EQUAL TO THE THICKNESS OF THE THINNEST
WALL IN THE ZONE.
≤ 400
≥ 450 ≥ 450 ≤ 400 ≥ 450 ≤ 400
7. PROVIDE 1.5 x ld LAPS FOR ALL REINFORCEMENT. DO NOT OFFSET BEND ANY REINFORCEMENT DO NOT USE
6-15MV 8-25MV 8-25MV 8-25MV 8-20MV 10-20MV 8-20MV 6-20MV 8-25MV 12-25MV REBAR LARGER THAN SHOWN ON DRAWINGS.
10M@200 TIES 10M@200 TIES 10M@200 TIES 10M@200 TIES 10M@200 TIES 10M@200 TIES 10M@200 TIES 10M@200 TIES 10M@200 TIES 10M@100 TIES
FOOTING 8. UNLESS NOTED OTHERWISE, SPLICE VERTICAL REINFORCEMENT IMMEDIATELY ABOVE TOPS OF SUPPORTED
SLABS. FOR WALLS THAT ARE UNBRACED FOR TWO OR MORE STOREYS, EITHER PROVIDE CONTINUOUS VERTICAL
REINFORCEMENT FOR THE ENTIRE UNSUPPORTED HEIGHT OR USE MECHANICAL TENSION COUPLERS.
24/09/2018 6:56:57 PM

9. WHERE VERTICAL REINFORCEMENT CHANGES, LAP LENGTH TO SUITE LARGER BARS.

10. WHERE DISTRIBUTED WALL REINFORCEMENT IS NOT SHOWN IN WALL SCHEDULE OR ELEVATIONS, PROVIDE
COLUMN SCHEDULE MINIMUM WALL REINFORCEMENT AS SHOWN IN CONCRETE REINFORCEMENT GENERAL NOTES.

11. FOR WALL PANELS WHERE END ZONE REINFORCEMENT IS NOT SPECIFIED, PROVIDE 4-15 EACH END AND TIE PER
400
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

COLUMN SCHEDULE NOTES.


8-25M VERTICAL 12. CARRY ALL WALLS REINFORCEMENT TO BOTTOM OF FOOTINGS.
400

C1 400x400 COLUMN 3-10M @300 TIES


10M @ 100 TIES AT TOP & BOTTOM 13. UNLESS NOTED OTHERWISE, PROVIDE DOWELS FROM FOOTING TO WALL TO MATCH CONCENTRATED AND
1200mm OF COLUMN DISTRIBUTED VERTICAL WALL REINFORCEMENT. EXTEND ALL DOWELS TO BOTTOM OF FOOTINGS, MATS OR PILE
CAPS AND TERMINATE WITH 90° HOOKS.

14. UNLESS NOTED OTHERWISE PROVIDE “L” DOWELS FROM WALL INTO SLAB AT TOPS OF WALLS TO MATCH SIZE AND
600 SPACING OF DISTRIBUTED WALL REINFORCEMENT. CARRY ALONG FULL LENGTH OF WALL (INCLUDING THE ZONES).
10-20M VERTICAL PROVIDE CLASS 'B' TENSION LAP WITH SLAB AND WALL REINFORCEMENT.
400

C2 400x600 COLUMN 2-10M @300 TIES


10M @100 TIES AT TOP & BOTTOM
1200mm OF COLUMN

VERIFY SCALES DESIGNED M.S. CORE AREA WASTEWATER TREATMENT PROGRAM


BAR IS 20mm ON SURVEYED
CLOVER POINT PUMP STATION
20mm MR 24/09/2018 3 ISSUED FOR CONSTRUCTION DRAWN J.G. DATE 02/02/2018 STRUCTURAL
MR 15/06/2018 2 ISSUED FOR 100% DESIGN SUBMISSION SCALE
As indicated CHECKED A.P.
ZONE SCHEDULE
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 23/03/2018 1 ISSUED FOR 90% DESIGN SUBMISSION
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-319 3 OF
E

4 5

NEW GUARD RAIL


SEE STD. DETAILS 305
51 152
FOR FINISH SEE 0' - 2" 0' - 6"
ARCH. DWGS
100 20M @200 T. B. E. W.
0' - 4" T/O GRADE (SEE CIVIL DWGS)
9.583 (SEE CIVIL DWGS)

2' - 0"
610
ROOF
8.959 m

250
303

2' - 6"
762
1' - 0"

250
203 EXG LOWER ROOF
0' - 8"
8.211
8' - 6"
2588

8.364 m
229

0' - 9"
228
0' - 9"

300
20M @200

1' - 9"
530
0' - 9"
229

51
0' - 2" 204 2-20M CONTINOUS
20M @200 T. B. E. W. 300

0' - 9" 0' - 9"


229 229
0' - 8"
7.225

305

610
2' - 0"

1 SECTION
ELEVATION OF HEAD WALL OF OUTLET STRUCTURE S-106
1 : 25
1 : 50

5
NEW GUARD RAIL
FOR FINISH SEE SEE STD. DETAILS
ARCH. DWGS

T/O GRADE (SEE CIVIL DWGS)


9.583

OR PRECAST SHAFT BY

2' - 0"
MANUFACTURER (TYP.) 9.126

610
ROOF
20M @200 TBEW 8.959 m
250

2' - 0"
250

610
9.126

EXG LOWER ROOF


8.364 m
15M @200HVEF
EXISTING EXHAUST SHAFT EXISTING EXHAUST SHAFT NEW SHAFT
24/09/2018 6:56:59 PM

250

20M @200 TBEW


8.290
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

2 SECTION
S-106 4 SECTION THRU EX. SHAFT
1 : 25 S-106
1 : 25

VERIFY SCALES DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM


BAR IS 20mm ON SURVEYED
CLOVER POINT PUMP STATION
20mm MR 24/09/2018 3 ISSUED FOR CONSTRUCTION DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 15/06/2018 2 ISSUED FOR 100% DESIGN SUBMISSION SCALE
As indicated CHECKED J.P.
NEW EXHAUST SHAFT DETAIL
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 23/03/2018 1 ISSUED FOR 90% DESIGN SUBMISSION
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-320 3 OF
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_-Sheet - S-401 402 403 BEAM DETAILS.dwg
DATE: , 10/08/2018 Rani, Sushma

VERIFY SCALES DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM


BAR IS 20mm ON SURVEYED
MR 24/09/2018 4.
CLOVER POINT PUMP STATION
ISSUED FOR CONSTRUCTION
20mm MR 18/05/2018 3. ISSUED FOR 100% DESIGN SUBMISSION DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 23/03/2018 2. ISSUED FOR 90% DESIGN SUBMISSION SCALE BEAM SECTIONS AND DETAILS (1)
IF NOT 20mm ON HORIZONTAL CHECKED R.L.
MR 19/01/2018 1. ISSUED FOR 50% DESIGN SUBMISSION -
THIS SHEET, ADJUST
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY APPROVED
SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - NUMBER CPS-100 NUMBER CP-C01- S-401 4 OF
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_-Sheet - S-401 402 403 BEAM DETAILS.dwg
DATE: , 10/08/2018 Rani, Sushma

VERIFY SCALES DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM


BAR IS 20mm ON SURVEYED
MR 24/09/2018 4.
CLOVER POINT PUMP STATION
ISSUED FOR CONSTRUCTION
20mm MR 18/05/2018 3. ISSUED FOR 100% DESIGN SUBMISSION DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 23/03/2018 2. ISSUED FOR 90% DESIGN SUBMISSION SCALE BEAM SECTIONS AND DETAILS (2)
IF NOT 20mm ON HORIZONTAL CHECKED R.L.
MR 19/01/2018 1. ISSUED FOR 50% DESIGN SUBMISSION -
THIS SHEET, ADJUST
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY APPROVED
SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - NUMBER CPS-100 NUMBER CP-C01- S-402 4 OF
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_-Sheet - S-401 402 403 BEAM DETAILS.dwg
DATE: , 10/08/2018 Rani, Sushma

VERIFY SCALES DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM


BAR IS 20mm ON SURVEYED
MR 24/09/2018 4.
CLOVER POINT PUMP STATION
ISSUED FOR CONSTRUCTION
20mm MR 18/05/2018 3. ISSUED FOR 100% DESIGN SUBMISSION DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 23/03/2018 2. ISSUED FOR 90% DESIGN SUBMISSION SCALE BEAM SECTIONS AND DETAILS (3)
IF NOT 20mm ON HORIZONTAL CHECKED R.L.
MR 19/01/2018 1. ISSUED FOR 50% DESIGN SUBMISSION -
THIS SHEET, ADJUST
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY APPROVED
SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - NUMBER CPS-100 NUMBER CP-C01- S-403 4 OF
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_-Sheet - S-403 404 BEAM DETAILS.dwg
DATE: , 14/09/2018 Rani, Sushma

VERIFY SCALES DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM


BAR IS 20mm ON SURVEYED
CLOVER POINT PUMP STATION
20mm DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 24/09/2018 2 ISSUED FOR CONSTRUCTION SCALE
CHECKED R.L. BEAM SECTIONS AND DETAILS (4)
IF NOT 20mm ON HORIZONTAL -
THIS SHEET, ADJUST MR 18/05/2018 1 ISSUED FOR 100% DESIGN SUBMISSION
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY APPROVED
SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - NUMBER CPS-100 NUMBER CP-C01- S-404 2 OF
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_-Sheet - S-403 404 BEAM DETAILS.dwg
DATE: , 14/09/2018 Rani, Sushma

VERIFY SCALES DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM


BAR IS 20mm ON SURVEYED
CLOVER POINT PUMP STATION
20mm DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 24/09/2018 2 ISSUED FOR CONSTRUCTION SCALE
CHECKED R.L. BEAM SECTIONS AND DETAILS (5)
IF NOT 20mm ON HORIZONTAL -
THIS SHEET, ADJUST MR 18/05/2018 1 ISSUED FOR 100% DESIGN SUBMISSION
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY APPROVED
SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - NUMBER CPS-100 NUMBER CP-C01- S-405 2 OF
CONCRETE WALL CORNERS AND INTERSECTIONS TC-WALL-01 CONCRETE WALL AT SLAB SUPPORT TC-WALL-02 DISCONTINUITIES IN CONCRETE WALL TC-WALL-12
ADD MIN 3-15T U/N OTHERWISE ADD MIN 3-15T U/N
CORNER BARS SAME SIZE AND ON PLAN OR SHEAR WALL OTHERWISE ON PLAN OR
ELEVATIONS. EXTEND MIN 1200 600 (2'-0") SHEAR WALL ELEVATIONS. 600 (2'-0")
SPACING AS HORIZONTAL 213 2083

(4'-0") PAST WALL ENDS; HOOK MIN EXTEND MIN 1200 (4'-0") PAST MIN
REINFORCEMENT. ALTERNATIVE: TURN
ALTERNATIVE: BEND ONE WALL'S CONT STD KEY DOWELS INTO WALL ABOVE WHERE NOT POSSIBLE WALL ENDS; HOOK WHERE
HORIZONTAL BARS AND LAP WITH (TYP) 10@300 (12") DOWELS NOT POSSIBLE
CONT EXTERNAL PVC (UNLESS OTHERWISE
THE OTHERS AS SHOWN ADD BAR AT WATERSTOPS IF
HOR BAR BEND NOTED)

CLASS 'B' LAP


CLASS 'B' CONSTRUCTION
(TYPICAL) SEE PLAN
7492

LAP SPLICE CLASS 'B' JOINT BELOW GRADE, ADDED BARS IF ADDED BARS IF U/N OTHERWISE
FOR SLAB
3192

LAP SPLICE REFER TO

CLASS
'B' LAP
270
U/N OTHERWISE DOWELS

CLASS
'B' LAP
REINFORCING. SHOWN ON PLAN SHOWN ON DOWELS

287

287
SPECIFICATIONS TO MATCH UNIFORMLY

153
0
EXTEND ALL OR SHEAR WALL PLAN TO MATCH UNIFORMLY

10
DISTRIBUTED WALL

0
STANDARD BARS TO THE ELEVATIONS OR SHEAR WALL DISTRIBUTED WALL
HOOK VERTICALS; AT SHEAR ELEVATIONS VERTICALS; AT SHEAR
END OF KEY

LAP SPLICE
WALLS, CONTINUE OVER WALLS, CONTINUE OVER

CLASS 'B'
CONT STD KEY ADD 2-15 CONT ZONES WITH CONCENTRATED ZONES WITH

2947
U/N (ZONE) REINFORCEMENT CONCENTRATED (ZONE)
DOWELS SAME SIZE AND SPACING 150 (6")
205

DOWELS IF SHOWN ON 600 (2'-0") REINFORCEMENT


MIN TOP OF WALL

900 (3'-0")
AS HORIZONTAL REINFORCEMENT.
237

DRAWINGS (15@400 (16") (TYP)

(TYP)
308
ALTERNATIVE: 75 (3") FORMED
MIN IF SLAB EXISTS AT
EXTEND HORIZONTAL KEY U/N
40

ONE SIDE OF WALL ONLY) 'U' BARS TO MATCH WALL


REINFORCEMENT INTO ALTERNATIVE:
INTERSECTING WALL AND SWELLABLE VERTICAL REINFORCEMENT
t ALTERNATIVE:
HOOK AS SHOWN. WATERSTOP 31

ADDED BARS IF SHOWN ON PLAN


IF t ≥ 225 (9") MIN 30 (1 1/4") DEEP KEY
OR SHEAR WALL ELEVATION
CREATED BY STAY FORM,
WITH 10@300 (12") 750 (2'-6")
DRAPE SLAB BOTTOM BARS
CLASS 'B' LAP (UNLESS LONGER LAP FOR SHEAR

782
PRE-INSTALLED BLIND OVER ADDED BARS, AND
DOWELS CARRY TO FAR END OF WALL WALL IS SPECIFIED IN SHEAR WALL NOTES)
OUTSIDE CORNER BARS
SAME SIZE AND SPACING AS
HORIZONTAL REINFORCEMENT.
ALTERNATIVE: BEND ONE WALL'S
ADD BAR AT

750 (2'-6")
HORIZONTAL BARS AND LAP 15@400 (16") DOWELS
HOR BAR BEND PLACE TIGHT TO SLAB
WITH ADD MIN 3-15B U/N OTHERWISE ON PLAN OR
(TYPICAL) CLASS 'B' EDGE FORM
THE OTHERS AS SHOWN CLASS 'B' SHEAR WALL ELEVATIONS. EXTEND MIN 1200 (4'-0")

(TYP)
750 (2'-6")
0452

01
LAP SPLICE
0852

0
LAP SPLICE PAST WALL ENDS; HOOK WHERE NOT POSSIBLE.

CLASS 'B'
SEE PLAN FOR SLAB

01
BOTTOM OF WALL

LAP
REINFORCING. EXTEND ALL

081
BARS TO THE END OF KEY

CLASS 'B'
LAP SPLICE

LAP
CLASS 'B'

8971
352
STANDARD CONT STD KEY
HOOK (TYP) 150 (6")
STANDARD DOWELS SAME SIZE AND SPACING 720

CLASS 'B' LAP (UNLESS LONGER LAP FOR SHEAR

081
CONT EXTERNAL PVC WATERSTOPS IF U/N ADD 1-15H
HOOK (TYP) AS HORIZONTAL REINFORCEMENT. WALL IS SPECIFIED IN SHEAR WALL NOTES)
ALTERNATIVE: WALL BELOW GRADE, REFER TO
t ROUGHEN JOINT TO
EXTEND HORIZONTAL SPECIFICATIONS 13

MIN 5 (3/16") AMPLITUDE


REINFORCEMENT INTO
INTERSECTING WALL AND INTERNAL PVC WATERSTOP
ALTERNATIVE:
HOOK AS SHOWN. SWELLABLE WATERSTOP BAR
367
- IF BAR OFFSET EQUAL OR LESS THAN 150 (6"),
IF t ≥ 300 (12") OFFSET PROVIDE CLASS 'B' LAP (UNLESS LONGER LAP FOR

081
DOWELS TO MATCH SHEAR WALL IS SPECIFIED IN SHEAR WALL NOTES);
NOTES: VERTICAL REINFORCEMENT - IF BAR OFFSET IS MORE THAN 150 (6"), INCREASE TO 2 x
ℓd

JUNE 2017
1. IF WALLS ARE NOT PERPENDICULAR TO EACH OTHER, ALL BAR BENDS TO MATCH THE WALL INTERSECTION ANGLE.
JUNE 2017

- FOR WALLS OTHER THAN SHEAR WALLS, IF BAR OFFSET


2. FOR SHEAR WALL CORNER AND INTERSECTION DETAILS, SEE CHANGE IN THICKNESS EQUAL OR LESS THAN 75 (3"), LOWER WALL
BARS CAN BE OFFSET BENT INTO THE UPPER WALL

CONSTRUCTION JOINT IN WALL TC-WALL-21 KEYED EXPANSION JOINT IN WALL TC-WALL-23 CONSTRUCTION GAP (CLOSURE STRIP) IN WALL TC-WALL-24

CONTINUOUS PVC WATERSTOP IF


CONSTRUCTION JOINT BELOW GRADE,
REFER TO SPECIFICATIONS. FACE(S) NOT EXPOSED TO VIEW:
ALTERNATIVE: ASPHALT IMPREGNATED SPACING OF VERTICAL
SWELLABLE WATERSTOP IF t ≥ 225 (9") FIBRE BOARD WALL REINFORCEMENT
CONT PVC WATERSTOP IF AS SHOWN ON DRAWINGS REINFORCEMENT
CONT STD KEY CONT 225 (9") PVC 25 (1") 85

CONSTRUCTION GAP BELOW AS SPECIFIED ON DWG


WATERSTOP IN CONT

10 (3/8")
5
GRADE,REFER TO SPECIFICATIONS. 100 100 100 100
89x89 (3 1/2" x 3 1/2") KEY

GAP
708 708 176 694 694

ALTERNATIVE: (4") (4") (4") (4")


(IF EXP JOINT IS BELOW GRADE) SWELLABLE WATERSTOP
t 3041

IF t ≥ 225 (9")

t 5641
20 (3/4") DEEP REGLET FOR 75 (3") 75 (3")
CAULKING ON FACE(S)
46 436

CONT STD KEY (TYP) SHOWN ON PLAN


EXPOSED TO VIEW
STOP ALL HORIZONTAL
3167

LAP IN SAME PLANE


HORIZONTAL REINFORCEMENT REINFORCEMENT FACE(S) EXPOSED TO VIEW: 20 (3/4") DEEP REGLET FOR
CONT THROUGH JOINT (OR BACKING & CAULKING CAULKING ON FACE(S)
SPLICED WITH CLASS 'B' LAP)
EXPOSED TO VIEW

NOTE:
JUNE 2017

JUNE 2017

DO NOT PLACE CONSTRUCTION JOINTS IN ANY SHEAR WALLS.


24/09/2018 6:57:01 PM
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

VERIFY SCALES DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM


BAR IS 20mm ON MR 24/09/2018 5 ISSUED FOR CONSTRUCTION SURVEYED
MR 15/06/2018 4 ISSUED FOR 100% DESIGN SUBMISSION
CLOVER POINT PUMP STATION
20mm MR 23/03/2018 3 ISSUED FOR 90% DESIGN SUBMISSION DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 19/01/2018 2 ISSUED FOR 50% DESIGN SUBMISSION (S-401) SCALE
1 : 100 CHECKED J.P.
STANDARD DETAILS (1)
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 16/08/2017 1 ISSUED FOR RFP SUBMISSION
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-501 5 OF
GUIDELINES FOR WALL OPENINGS LARGER GUIDELINES FOR WALL SLEEVES AND OPENINGS
TC-WALL-32 TC-WALL-31
A THAN 400 x 400 (16" x 16") / 400 (16")Ø LESS THAN 400 x 400 (16" x 16") / 400 (16")Ø
-
"B" BAR SEE NOTE 1 TYPICAL WALL BARS AT
SPACING SPECIFIED ON PLAN;
HALF THE AREA CUT AT OPENING
OF "A" BARS CUT
BY OPENING ADD 1 - 15Mx1200 DIAG
UNLESS NOTED AT EACH CORNER FOR
OTHERWISE

MIN

MIN

MIN b3
EACH LAYER OF REINF

b2

b5
MIN b4

53
b4 MIN b4
584

130
1538 1568

MIN
MIN b3 b3

1593
437

MIN b
b5 140 140

400 (16")
b2

10 IN
296

4")
400 (16")

MIN
MIN b1 b1
50

b5

M
HALF OF AREA OF "B" BARS,
756

0(
MAX

140
60

140 140

140
CUT ON EACH SIDE OF
WIDTH OF
DOORWAY OPENING W/ MATCHING WIDTH OF 178

400 (16") 400 (16") BEARING PLATE


2400mm DOWELS, EXTEND FULL STORY CONCRETE BEAM / 178 1076

b
260

MIN MIN OR WALL PLATE


HEIGHT UNLESS NOTED BASE PLATE / TREAT AS EQUIVALENT SINGLE

6")
"A" BAR
320

MAX 900 (3'-0") MIN

") 0 x1
OTHERWISE BEARING PLATE / OPENING IF CLEAR SPACING
054

'-4 00 6"
WIDTH TO END OF WALL 400 (16")

x3 x1 (1

400 (16")
WALL PLATE SUPPORTED BETWEEN MULTIPLE SLEEVES ADDITIONAL OPENINGS OF EQUAL

-4" 00 00
140

MIN
IF OPENING LOCATED ABOVE

X
MIN TO

(3' 10 0x4

MA
ON THE WALL HEIGHT OR SMALLER ACCEPTABLE IF

1459
2 IS LESS THAN 400 (16")

TO 4 0
SLAB ON GRADE, 15M DIAG ADD 1-15EF END OF HORIZONTALLY ALIGNED WITH

G
FLOOR 1

IN
EF REQD AND HALF THE x900 (3'-0") LG WALL

EN
ADJACENT OPENING AND KEEPING
SLAB AREA OF "A" BARS CUT MAX

OP
'U' BARS TO MATCH 140

MIN 400 (16") CLEAR SPACING


REQD BELOW OPENING. INTERRUPTED STEEL 400 (16")
PROVIDE MATCHING DOWELS 2 x ℓd
FROM LOWER LEVEL WALLS 672

(TYP) ADDITIONAL OPENINGS OF EQUAL WIDTH OR


ALL OPENINGS WIDER
241

FOR WINDOW FOR


THAN 400 (16") MUST SMALLER ACCEPTABLE IF VERTICALLY ALIGNED
AND LOUVRES ELEVATED FLOOR LEVEL
CLEAR THIS ZONE WITH OPENING ABOVE / BELOW AND KEEPING
SEE STD-S036 50 TYP. ALL AROUNDOPENINGS MIN 400 (16") CLEAR SPACING

ELEVATION ADD STEEL EQUAL TO 1/2 OF INTERRUPTED


CLASS 'B' LAP STEEL AT EACH SIDE OF OPENING (1-15 EF MIN)
CAPPING BARS TO (TYP)
MATCH "B" BARS
NOTES:
"A" BAR 1. SUBMIT COMPOSITE SLEEVING DRAWINGS SHOWING SIZE AND LOCATION OF ALL WALL SLEEVES AND OPENINGS.

ADDITIONAL 2. THIS DRAWING SHOWS ONLY GENERAL GUIDELINES FOR PLACING SLEEVES AND OPENINGS THROUGH WALLS. FOR ANY SPECIFIC
HORIZONTAL NOTES: JOB, OPENINGS AS SHOWN ON THIS DETAIL MAY NOT BE ACCEPTABLE OR MAY REQUIRE ADDITIONAL REINFORCING. DO NOT
BARS INSTALL ANY SLEEVES AND OPENINGS PRIOR TO REVIEWING RETURNED SLEEVING DRAWINGS.
1. AT SHEAR WALL, ONLY THE OPENINGS INDICATED AT SHEAR WALL ELEVATIONS ARE ACCEPTABLE.

NOTES:
SECTION A 2. SUBMIT COMPOSITE SLEEVING DRAWINGS SHOWING SIZE AND LOCATION OF ALL WALL SLEEVES AND OPENINGS.
3. RESPACE WALL REINFORCEMENT AS REQUIRED TO CLEAR OPENINGS.

N.T.S. - 4. NO OPENING CAN INTERFERE WITH ANY REINFORCEMENT SHOWN TO BE IN ADDITION TO UNIFORMLY DISTRIBUTED WALL
1. PROVIDE MINIMUM CLASS B LAP 3. THIS DRAWING SHOWS ONLY GENERAL GUIDELINES FOR PLACING OPENINGS THROUGH WALLS. FOR ANY SPECIFIC JOB,
TYPICAL FOR ALL OPENINGS IN ABOVE GROUND REINFORCEMENT.
OPENINGS AS SHOWN ON THIS DETAIL MAY NOT BE ACCEPTABLE OR MAY REQUIRE ADDITIONAL REINFORCING. DO NOT
BUILDING CONCRETE WALLS UNLESS INDICATED INSTALL ANY OPENINGS PRIOR TO REVIEWING RETURNED SLEEVING DRAWINGS.
OTHERWISE ON PLANS. 5. AT SHEAR WALLS, ALL OPENINGS TO STAY MIN. 1000 (3’-4”) CLEAR OF CONCENTRATED (ZONE) REINFORCEMENT.

2. DO NOT WELD REINFORCEMENT TO PIPE SLEEVES AND INSERTS. 4. MINIMUM SPACING BETWEEN ADJACENT OPENINGS NOT TO BE LESS THAN THE WIDTH OF THE LARGER OF THE OPENINGS. 6. SUM OF THE WIDTHS OF ALL SLEEVES AND OPENINGS IN ANY 3000 (10’) LONG WALL SEGMENT NOT TO EXCEED 750 (2’-6”), EXCEPT
AT SHEAR WALLS WHERE THAT SUM SHOULD NOT EXCEED 400 (16”).
5. NO OPENING CAN INTERFERE WITH ANY REINFORCEMENT SHOWN TO BE IN ADDITION TO UNIFORMLY DISTRIBUTED WALL
REINFORCEMENT. 7. FOR ADDITIONAL REINFORCEMENT AT DUCT BANK SLEEVES, SEE TC-WALL-32.
WALL OPENING ADDITIONAL REINFORCEMENT

EXTRA REINFORCING BARS AT DWG. No. REV.

WALL OPENINGS ABOVE SLABS STD-S037


CONTROL JOINT IN WALL TC-WALL-22

CONT EXTERNAL PVC WATERSTOP IF CONTROL JOINT


BELOW GRADE, REFER TO SPECIFICATIONS. OMIT IF
SAW CUTTING OF EXISTING SLAB OR WALL TC-SL-71 HOT APPLIED WATERPROOFING IS PROVIDED. SEE ALSO
ARCH. SPECS AND DETAILS.

INTERMEDIATE SAWCUTS
AS REQUIRED

G
TIN
EXIS
IN L 20 (3/4") DEEP REGLET EACH FACE.
NING R WAL
E BO
OP
C UT E SLA CARRY ADDITIONAL HORIZONTAL BARS (IF SHOWN AT TOP AND BOTTOM
SAW CRET OF WALL) CONTINUOUSLY THROUGH JOINT. STOP 50% OF ALL OTHER
N SIZE AND NUMBER OF
CO HORIZONTAL BARS 75 (3") EACH SIDE OF CONTROL JOINT
CORE HOLES TO SUIT
CUTTING EQUIPMENT
SLAB
SAW CUTTING PROCEDURE:
NOTES:
1. OBTAIN ENGINEER'S APPROVAL BEFORE CUTTING ANY OPENINGS. IF REQUESTED,
LOCATE REINFORCEMENT USING A NON- DESTRUCTIVE METHOD.
2. DESIGN AND PROVIDE SHORING AND BRACING AS REQUIRED. CONTINUOUS TOP BARS
3. CORE HOLES AT EACH CORNER AND AT ENDS OF EACH INTERMEDIATE SAWCUT. (IF SHOWN ON DRAWINGS)
STOP EVERY 2nd
4. SAWCUT AND DO NOT OVERCUT.
BAR AT JOINT
5. EXTEND SAWCUTS THROUGH FULL CONCRETE THICKNESS. WALL
JUNE 2017

6. CHIP CORNERS SQUARE.


CONTROL JOINT
CONTINUOUS BOTTOM BARS
(IF SHOWN ON DRAWINGS)
24/09/2018 6:57:03 PM

WALL ELEVATION
DO NOT LOCATE CONTROL JOINTS IN ANY SHEAR WALLS NOR IN BASEMENT WALL SEGMENTS SPANNING HORIZONTALLY AND
HIGHLIGHTED THUS ON PLAN BELOW (h IS BASEMENT WALL CLEAR HEIGTH)
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

600 (24")
BASEMENT WALL BELOW
120

MIN SLAB OPENING

600 (24")
INTERSECTING

ℓ≤h
120

815

MIN ℓ≤h
CONCRETE
1735

WALLS BELOW
NO CONTROL JOINTS
600 (24")
120
IN THESE AREAS
MIN
SLAB AT TOP OF WALL

PLAN (NTS)

VERIFY SCALES DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM


BAR IS 20mm ON MR 24/09/2018 5 ISSUED FOR CONSTRUCTION SURVEYED
MR 15/06/2018 4 ISSUED FOR 100% DESIGN SUBMISSION
CLOVER POINT PUMP STATION
20mm MR 23/03/2018 3 ISSUED FOR 90% DESIGN SUBMISSION DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 19/01/2018 2 ISSUED FOR 50% DESIGN SUBMISSION (S-402) SCALE
As indicated CHECKED J.P.
STANDARD DETAILS (2)
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 16/08/2017 1 ISSUED FOR RFP SUBMISSION
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-502 5 OF
TIES FOR CONCRETE COLUMNS, WALLS, BORED
COLUMN AND PIER CAST INTEGRALLY WITH WALL TC-COL-21 OPTION: DOWELS TO CONCRETE COLUMNS AND PIERS REINFORCED AS COLUMNS TC-COL-01 TC-COL-02
CONCRETE PILES AND PIERS REINFORCED AS COLUMNS
167

MATCH VERTICALS U/N

100 (4") AT
AT SLAB

BEAMS
75 (3")
CLASS 'B' LAP "D"
COLUMN (PIER), SEE PLAN OR SCHEDULE 821
"D" 840
"D" 840

CARRY WALL HORIZONTAL

75 (3")
862
REINFORCING THROUGH; DRAPE ALTERNATIVE: ℓd

"D"

"D"
048

048
BEHIND COLUMN (PIER) VERTICALS DISCONTINUE WALL REINFORCING AND
ADD MATCHING BARS (WITH

2176
S/2 MAX
IF INTERFERING
081

MAX 50 (2")
CLASS 'B' LAP EACH SIDE) THROUGH BOTTOM STEEL OR

DRAPE
OR BEHIND COLUMN (PIER) CAGE

CLASS 'B' LAP


564

WHENEVER SLAB OPENINGS EXIST ADJACENT

MAX S/2

5603
LOCATE CONSTRUCTION JOINT IN 4 BARS 6 BARS 8 BARS

FOR AEC)
TO COLUMNS, CARRY TIES THROUGH THE

(ZERO
25(1")
SLAB THICKNESS AS SHOWN FOR PERIMETER COLUMN 25 (1") BELOW SLAB / DROP / CAP.
COLUMNS EXCEPT FOR ARCHITECTURALLY EXPOSED

385
DROP (IF APPLICABLE) CORNER COLUMN "D"

71
CONCRETE (AEC) COLUMNS, WHERE JOINT IS
982

a
218

COMPRESSION LAP SPLICE


ADD TIES TO MATCH SIZE NOTED OTHERWISE (REFER TO TO BE AT U/S OF SLAB / DROP / CAP CONSTRUCTION JOINT
CONCRETE OPTIONAL DOWELS TO MATCH COLUMN VERTICALS
AND SPACING OF COLUMN TIES;

"D"
COLUMN SCHEDULE & NOTES)

"D"
WALL
647

048
STAY FORM COMPRESSION LAP SPLICE (UNLESS OTHERWISE NOTED IN COLUMN

2401
OMIT IF a ≤ 100 (4")

SEE SCHEDULE
S/2 MAX

(TIE SPACING)
EXTERNAL PVC UNLESS NOTED OTHERWISE SCHEDULE) FOR ALL BARS IN HATCHED
WATERSTOP AT
243

(REFER TO COLUMN AREAS EQ EQ

S
60 840

167

BASEMENT WALLS 6 SLOPE SCHEDULE & NOTES) 583

MAX S/2
1

EQ EQ
350

75 (3") TO

PORTION
NOTE:

06
SLOPED
TOP OF
342

06
IF DIFFERENT CONCRETE MIXES ARE SPECIFIED FOR COLUMN (PIER) AND WALL, USE CONCRETE
10 BARS 12 BARS 12 BARS
JUNE 2017

OF HIGHER STRENGTH AND MORE STRINGENT EXPOSURE CLASSIFICATION FOR BOTH.

SLOPED PORTION
75 (3") TO TOP OF
≤S
051

ALTERNATIVELY, PROVIDE STAY FORM AND POUR COLUMN AND WALL SEPARATELY. 374

≤S BOTTOM STEEL "D"

S/2 MAX

FOR AEC)
802

(ZERO
25(1")
74

≤S PERIMETER
REDUCED SIZE TIE

FOR AEC)
COLUMN

(ZERO
25(1")
07

≤S EQ EQ

109
74

"D"
U/N OTHERWISE, PROVIDE MIN. THREE TIES AT 75 (3"),

140
60 60

053

JUST BELOW SLOPED PORTION. OMIT WHERE


CLASS B
71

CONSTRUCTION JOINT SLOPED PORTION STARTS MIN 50 (2") ABOVE U/S OF

S (TIE SPACING)
SEE SCHEDULE
LAP SLAB OR DROP. CARRY TIES THROUGH SLAB / 6 SLOPE
COMPRESSION DEVELOPMENT LENGTH DROP / BEAM. REDUCE SIZE AS 1
COMPRESSION LAP SPLICE REQUIRED
0541

(MEASURED FROM UNDERSIDE OF SLAB / DROP)


UNLESS NOTED OTHERWISE
CLASS "B"

IF COLUMN FACE OFFSET IS 75 (3") OR MORE USE CONSTRUCTION JOINT PERIMETER


(REFER TO COLUMN
LAP

DOWEL SPLICE. CARRY ALL VERTICALS INTO COLUMN


SCHEDULE & NOTES) U/N OTHERWISE, PROVIDE MIN. 14 BARS
053

UPPER COLUMN WHERE POSSIBLE

SLOPED PORTION
THREE TIES AT 75 (3"),

75 (3") TO TOP OF
JUST BELOW SLOPED PORTION. PLAN

WHICHEVER IS GREATER. DOWEL


14 BARS
06

MAX S/2

DOWELS TO MATCH REBARS IN

385
LENGTH TWICE THE REQUIRED

MAX S/2
COLUMN ABOVE OR BELOW,

26
MAX 75 (3")
COMPRESSION LAP SPLICE
ADD MINIMUM OF
342

X X "D" "D"
X X

75(3")

LENGTH + 75 (3")
743

80 80

2-25M DOWELS OR
BEAM TO MATCH TOP
762

REINFORCING

207
BARS WHICHEVER IS

"D"

"D"
4125

048 048

LARGER
BOX OUT THROUGH 6
WALL FOR FULL
1 SLOPE OF BARS IF

THIS ZONE NOT


TIE SPACING IN
DEPTH OF BEAM STANDARD HOOK OR

TO EXCEED
COLUMN FACE OFFSET

392
156

150 (6")
8403
IS LESS THAN 75 (3")
WALL TIES NOT REQUIRED ONLY

75 (3")
MAX
CONCRETE WALL REINFORCEMENT SEE IN ZONE WHERE COLUMN
STRUCTURAL SECTION LATERALLY SUPPORTED U/N OTHERWISE, PROVIDE MIN THREE

27
BY BEAMS OR CONTINUOUS TIES AT 75 (3"), JUST BELOW SLOPED PORTION. (6")

MAX 75 (3")
SECTION IF BEAMS DO NOT EXIST AT ALL FOUR SIDES OF 50 RED
3801

≤S
1

761
DROPS ON ALL FOUR SIDES COLUMN, PROVIDE TIES AS SHOWN FOR BEAMS MIN GGE
CONCRETE BEAM TO WALL CONNECTION
REDUCED SIZE TIES AT PERIMETER COLUMNS BEAM (IF APPLICABLE) 16 BARS STA OUND
AR
BARS NOT CONTINUED IN COLUMN ABOVE "D"

062
CONSTRUCTION JOINT AT UNDERSIDE OF BEAMS "D" "D"
(TYP)
860

BEND ALL VERTICALS AT SAME LEVEL. DO NOT


U/N OTHERWISE, PROVIDE MIN. THREE TIES AT 75 BEND VERTICALS IN ROUND COLUMNS IF COLUMN
3 ADDITIONAL STIRRUPS @100 (3"), JUST BELOW SLOPED PORTION. OMIT WHERE ABOVE IS THE SAME DIAMETER AND THE

"D"
568

mm C/C AT EACH SIDE OF BEAM BEAMS EXIST AT ALL 4 SIDES OF COLUMN AND MINIMUM CLEARANCE BETWEEN BARS INDICATED
JUNCTION (SIZE TO MATCH BEAM SLOPED PORTION STARTS MIN 50 (2") ABOVE U/S IN SECTION X-X IS MET

06
MAX S/2
STIRRUPS) OF THE SHALLOWEST BEAM

60
MAX S/2

"D"
MAIN TOP OF FOUNDATION, NARROW COLUMN (OR WALL) ROUND
TOP OF FOUNDATION, PIER OR CAP
BEAM
PIER OR CAP

INTERIOR COLUMN PERIMETER / CORNER COLUMN 135° HOOKS STD.90°


135° HOOKS HOOK
NOTES: MORE THAN 16 BARS
BEAM MINIMUM CLEARANCE LARGER OF 40 (1 1/2")
SECONDARY

REINFORCEMENT SEE OR 1.5 BAR DIA; OTHERWISE, OFFSET BEND

h
1. SEE TC-COL-02 FOR TYPICAL TIE ARRANGEMENT. UPPER BAR (TYP)

483
STRUCTURAL SECTION BEAM LOWER BARS INTO COLUMN AS SHOWN FOR NOTES: h 46
h 135°
BEAM

REINFORCEMENT SEE SQUARE COLUMNS


96

51

2. IF COLUMNS ARE CAST INTEGRALLY WITH SHEAR WALLS, ALL VERTICAL BARS TO HAVE LAPS AS HOOK
STRUCTURAL SECTION LOWER 1. DRAWINGS SHOW SIZE AND SPACING OF TIE SETS.
SPECIFIED FOR SHEAR WALL CONCENTRATED REINFORCEMENT. HOOP CIRCULAR TIE CROSS TIE
BAR (TYP) "TIE" ON DRAWINGS MEANS TIE SET.
2. PROVIDE TIES FOR EVERY OTHER VERTICAL BAR. h=6 x TIE DIA., 60 (2 3/8") MIN U/N
3. IF COLUMNS ARE CAST INTEGRALLY WITH SHEAR WALLS IN WHICH BENT CONCENTRATED
3. IF CLEAR SPACING BETWEEN ADJACENT VERTICALS IF Rd ≥ 2.0 (SEE DESIGN DATA NOTES), INCREASE 'h' TO
REINFORCEMENT IS PROHIBITED, PROVIDE DOWELS BETWEEN COLUMN LIFTS INSTEAD OF USING OFFSET BENT VERTICALS.
PLAN "D" IS MORE THAN 150 (6"), ADD TIES SHOWN DASHED.

R
100 (4") MIN FOR COLUMNS CAST INTEGRALLY WITH SHEAR

VE
4. PLACE SUCCESSIVE CROSS TIES WITH 135° HOOKS

CO
CONCRETE BEAM TO BEAM JUNCTION 4. INCREASE TIES ADDED BELOW SLOPED PORTION OF VERTICAL BARS TO 4-10 FOR 45 BARS, AND TO 4-15 FOR 55 BARS. WALLS AND FOR SHEAR WALL ZONE REINFORCING.
COVER ALTERNATING FROM SIDE TO SIDE OF COLUMN / PIER.

341
C
V
O
E
R

5. ALTERNATE TIE ARRANGEMENTS MAY BE ACCEPTABLE


TYPICAL TIE SHAPES

JUNE 2017
JUNE 2017

5. FOR COLUMNS IN MOMENT FRAMES, ALL VERTICAL BARS TO HAVE CLASS 'B' TENSION LAP SPLICES SQUARE/RECTANGULAR ROUND COLUMN WITH
SUBJECT TO THE CONSULTANT'S REVIEW.
COLUMN CIRCULAR TIES
SECTION X - X 6. SEE COLUMN SCHEDULE FOR SPECIAL TIE ARRANGEMENTS.

ADDITIONAL REINFORCING IN CONCRETE BEAMS DWG. No. REV.

STD-S017
24/09/2018 6:57:06 PM
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

VERIFY SCALES DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM


BAR IS 20mm ON MR 24/09/2018 5 ISSUED FOR CONSTRUCTION SURVEYED
MR 15/06/2018 4 ISSUED FOR 100% DESIGN SUBMISSION
CLOVER POINT PUMP STATION
20mm MR 23/03/2018 3 ISSUED FOR 90% DESIGN SUBMISSION DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 19/01/2018 2 ISSUED FOR 50% DESIGN SUBMISSION (S-403) SCALE
As indicated CHECKED J.P.
STANDARD DETAILS (3)
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 16/08/2017 1 ISSUED FOR RFP SUBMISSION
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-503 5 OF
BOND BEAM AT VERT. BAR IN 2 WIRE LADDER 3.66mm
TOP OF WALLS GROUTED CORE DIAMETER EVERY 2 GROUT ALL CELLS
AND AT ALL ROOF AS SHOWN COURSES (400mm) WITHIN SHADED
AND FLOOR BOUNDARY AREA
LEVELS

LINTEL
DEPTH
"A" BARS IN
LINTEL BLOCK
SEE NOTE 3
TYPICAL WALL
72 BAR DIA
TYP. VERTICAL LAP. TYP.
REINFORCEMENT SEE NOTE 2
"C" BARS EACH
SIDE, SEE NOTE 2
VERT. BAR IN (ONE CENTERED
CMU OPENING GROUTED CORE PER CELL IN 200MM

"H"
600 MIN. TYP REINF SEE DETAIL AS SHOWN WALLS. TWO
(1EF)PER CELL
IN 250MM WALLS)
"B" BARS IN
TYP. HORIZONTAL BOND BEAM
REINFORCEMENT SEE NOTE 3
2 WIRE LADDER 3.66mm
48 BAR DIAMETER EVERY 2
DIA LAP. COURSES (400mm) TYP.
SEE NOTE 2
SEE NOTE
8 HORIZ BAR IN
FIRST COURSE
DOWELS JAMB JAMB
SEE NOTE 4 WIDT "W" WIDT
AT WALL CORNER
H H

WALL PIER OR
COLUMN. SEE NOTE 7
NOTES:

1. FOR TYPICAL WALL REINFORCING, SEE WALL SECTIONS AND DETAILS FOR EACH FACILITY FOR MINIMUM CMU OPENING REINF SCHEDULE
REINFORCING REQUIREMENTS, SEE GENERAL STRUCTURAL NOTES. 190mm WALLS
2. LAP VERTICAL REINFORCEMENT WITH WALL DOWELS 48 BAR DIAMETERS (600mm MIN) LAP ALL OTHER VERTICAL W LINTEL STIRRUP "A" "B" "C" JAMB
BARS 72 BAR DIAMETERS. DEPTH SIZE.SPG BARS BARS BARS WIDT
2 WIRE LADDER 3.66mm H
3. STAGGER SPLICES IN ADJACENT HORIZONTAL BARS IN THE SAME COURSE BY 600mm. DIAMETER EVERY 2 < 800 200mm - 1 1 1 200mm
VERT. BAR IN
COURSES (400mm) GROUTED CORE >800<1200 400mm - 2 1 1 200mm
4. PROVIDE DOWEL BARS IN FOUNDATION TO MATCH ALL VERTICAL REINFORCING. (TYP) AS SHOWN
<1200<1800 600mm 10M@200 2 1 2 400mm
5. FOR ADDED REINFORCING AT WALL INTERSECTIONS AND CORNERS, SEE STD DETAIL '19'. >1800<2400 800mm 10M@400 2 2 3 600mm

6. GROUT EACH SIDE OF OPENING AS NOTED IN TYPICAL REINFORCING, SEE STD DETAIL '18'. >2400<3000 1200mm 10M@600 2 2 3 600mm

7. FOR HORIZONTAL REINFORCING AT OPENINGS SEE COLUMN AND PIER DETAILS.

8. DO NOT PLACE VERTICAL CONDUIT IN THE SAME CELL AS VERTICAL REINFORCING. AT WALL JUNCTION
CMU OPENING REINFORCING DETAIL
REINFORCED CMU MASONRY WALL DETAIL NTS
NTS NTS

50mm INSULATION PLUG


1000 IN EACH CORE SLAB
MAXIMUM LINTEL SPANING BETWEEN CONCRETE BLOCK
CLEAR 15M BAR IN EACH 450
BREAK OPEN CORE AND WALL ON BOTH SIDES. GROUT JOINT.
SPAN GROUT
GROUT BAR IN SOLID BY
400 PRECAST CONTRACTOR CORESLAB
50mm INSULATION
PLUG L152x203x13 (LLH) FOR
GROUT

50
GROUT 2- SUPPORTING FACE CONCRETE TOPPING

200
1000mm
20M
2- BRICK.
20M HALF BLOCK

SECURE ANGLE TO LINTEL WITH M12 HILTI HVA


ADHESIVE ANCHOR AT 600 C/C (3 MIN) EMBED =
110mm
CONTINUOUS BEARING
PAD AS PER
10M BAR CAST 15M@250 STIRRUPS PRECASTERS
INTO BEAM 1- (DOUBLE LEG)

400
AT CORES AWAY FROM THE 10M BAR IN RECOMMENDATION
GROUTED END OR PLACE CONC.ROOF EACH GROUT 25M TYP.

400
BEAM 2000mm
STYROFOAM PLUGS AT FACE OF L152x203x13 (LLH) FOR
THE CONCRETE 2- SUPPORTING FACE LINTEL BLOCK
CONC. 25M BRICK.
BEARING PADS 75x150 (2 PER ROOF BEAM BLOCK WALL 20M CONT'D
SLAB BY PRECAST CONTRACTOR) SECURE ANGLE TO LINTEL WITH M12 HILTI HVA WITH 180° HOOK AT ENDS TYP.
ADHESIVE ANCHOR AT 600 C/C EMBED =110mm WALL VERTICAL
REINFORCEMENT BAR

1- 15M@250 STIRRUPS
25M (DOUBLE LEG)
50mm INSULATION

600
PLUG AS REQUIRED 10M BAR x1200LG IN GROUT 3000mm
GROUT 50mm
JOINTS WHEN JOINTS L152x203x13 (LLH) FOR
ALIGN OR GROUTED INTO INSULATION PLUG CORESLAB
SUPPORTING FACE
CORE WHEN JOINTS DO 2- BRICK.

50
24/09/2018 6:57:08 PM

NOT ALIGN BY PRECAST 25M CONCRETE TOPPING


CONTRACTOR
SECURE ANGLE TO LINTEL WITH M12 HILTI HVA
ADHESIVE ANCHOR AT 600 C/C EMBED =110mm

GROUT CORE
LINTEL SCHEDULE NOTES
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

CONC. BEAM/
EXCEPT AT 10M BAR WALL CONTINUOUS BEARING
LOCATIONS PLACE STYROFOAM 1. PROVIDE LINTELS OVER ALL OPENINGS, COORDINATE WITH PAD AS PER
GROUT 15M BAR 600LG PLUGS CLOSE TO END OF MECHANICAL, ARCHITECTURAL, PROCESS AND ELECTRICAL PRECASTERS

400
DRAWINGS FOR LOCATIONS. 10M@400
WITH 100 PROJ SPACED SLAB RECOMMENDATION
AT 600 O/C OR TO TYP.
2. PROVIDE 200mm MINIMUM SOLID BEARING AT BOTH SIDES OF 20M CONT'D
MATCH WALL REINF,
CONC. BEAM/ LINTEL. LINTEL BLOCK WITH 180° HOOK
WHICHEVER IS LESS
WALL AT ENDS TYP.
3. LINTEL BLOCKS TO BE NOMINAL 400mm LONG UNITS OF BOND
BEAM PROFILE. BLOCK WALL
4. FOR INTERIOR LINTELS, OMIT SUPPORTING ANGLES.

CORE SLAB @ ROOF BEAM CORE SLAB CONNECTION DETAIL


NTS NTS TYPICAL LINTEL SCHEDULE CORESLAB CONNECTION DETAIL
NTS NTS
VERIFY SCALES DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM
BAR IS 20mm ON MR 24/09/2018 5 ISSUED FOR CONSTRUCTION SURVEYED
MR 15/06/2018 4 ISSUED FOR 100% DESIGN SUBMISSION
CLOVER POINT PUMP STATION
20mm MR 23/03/2018 3 ISSUED FOR 90% DESIGN SUBMISSION DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 19/01/2018 2 ISSUED FOR 50% DESIGN SUBMISSION (S-404) SCALE
As indicated CHECKED J.P.
STANDARD DETAILS (4)
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 16/08/2017 1 ISSUED FOR RFP SUBMISSION
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-504 5 OF
CORESLAB LATERAL SUPPORT OF MASONRY PARTITION
PD-01 1 LAYER LIGHT GAUGE
AT FORMED CONCRETE STRUCTURE 100 TK 10M @300 S.S. PLATE
TOPPING EACH WAY ATTACHED ON
ONE SIDE
MASONRY DEFLECTION GAP PROVIDE STYROFOAM PLUGS
IN EACH CORE SET HOLLOW CORESLAB SEE
U/S CORESLAB 25 (1") UNLESS OTHERWISE POURED IN
10 (3/8")Ø DCA 10 (3/8")Ø DCA 100mm BACK FROM END OF SLAB PLAN
SHOWN ON PLANS + MAX 10 CONCRETE PLACE WALL
(3/8") AT BOLT HEAD TOPPING DOUBLE
25
TEE SLAB 15M DOWELS @200 TYP.
12 DIA. HILTI ANCHORS T/O CORESLAB

MIN
100
MATCH SPACING OF
@ 300 (CONCRETE) OR ELEVATION
791
200 MIN. WALL REINFORCEMENT
WHICHEVER IS LESS
25mm THICK FIRE L100x150x6 (LLV) x 175mm LONG@2000 MAX. MASONRY DEFLECTION

100 (4") MIN


CLIP L102x76x6.4 (LLV) 38 (1 1/2") 5 (3/16") BENT PLATE 800
RATED JOINT SPACING, EACH SIDE STAGGERED. FASTEN GAP 25 (1") UNLESS
FILLER TO UNDERSIDE OF STRUCTURE WITH 2-M16 x 150 (6") LG @ 1200 (4'-0") 52

x 150 (6") LG AT 1200 (4'-0")


OTHERWISE SHOWN ON 800
(TYP) HILTI KWIK BOLTS @100 PER ANGLE. MIN EACH SIDE (STAGGERED)
PLANS + MAX 10 (3/8") DOUBLE
150mm EMBEDMENT
543

FIRE STOP BY OTHERS FLEXIBLE BEARING PAD


10M @300 TEE SLAB
BOND BEAM (IF SHOWN 15M DOWEL BARS AT SUCH AS NEOPRENE
FIRE STOP BY OTHERS EW AFTER
DRYPACK GROUT
ONE LAYER OF SOLID MIN. 200mm OR REINFORCED WITH
ON DRAWINGS) CAN ALIGNING THE SLABS
BLOCK BELOW MATCH SPACING OF FIBRES
BE LOWERED MAX 1
CORESLAB WALL REINFORCEMENT BEARING PADS
COURSE BELOW TOP
WHICHEVER IS LESS 75x150- 2 PER SLAB
OF WALL. FOR REINFORCED
WALLS, CARRY ALL VERTICALS 800
TO TOP OF WALL. 800

AUGUST 2017
200mm BOND BEAM C/W
20M A
CONT'D WITH 180° AT ENDS -

PROVIDE 10M BARS @600 O/C


GROUTED TIGHT
INTO THE PARAPET
CONNECTION HARDWARE CONC CAST-IN 100x102x350 S.S.
15M@600 VERTICAL REINF.

PARAPET
IN GROUTED CORES AND WELD BY PRECAST TOPPING HOLLOW CORESLAB SEE WITH 4-20∅ ANCHORS
CONTRACTOR PLAN + 40x12x40 END PLATES
ABOVE DOOR/LOUVRE

CONCRETE

100
TOPPING
T/O CORESLAB SECTION A

MIN
100
2400

ELEVATION
WELD OPPOSING STEMS N.T.S. -
ON SAME AND ADJACENT
TEE SLABS. WELD ON
STEM EACH END OF SLAB
15M x1200LG. @600 DOWELS
TOP FLANGE OF
D/TEE PROVIDE 100 THK DECK ON
FLANGE 15M DOWEL BARS AT
THE DOUBLE TEE SLAB DRYPACK GROUT AFTER
CONNECTION MIN. 200mm OR
UNLESS OTHERWISE NOTED ALIGNING THE SLABS
MATCH SPACING OF
800

WALL REINFORCEMENT BEARING PADS


ALL PRECAST DOUBLE TEE CONNECTIONS WHICHEVER IS LESS 75x150- 2 PER SLAB 6 50
TO BE DESIGNED AND STAMPED BY
±200 CONCRTE CURB PRECAST MANUFACTURER'S ENGINEER 800
GROUND FLOOR TYP. FOR ALL CMU WALL 800
FOR RESERVOIRS AND SIMILAR STRUCTURES
200

NOTE: SEE STRUCTURAL DRAWINGS


FOR CORESLAB DIAPHRAGM
FORCES.
300

TYPICAL CONNECTION BETWEEN DOUBLE-TEE DWG. No. REV. TYPICAL CONNECTION FOR CORESLAB TO CONC. SUPPORT DWG. No. REV. TYPICAL CONNECTION FOR EA. DOUBLE-TEE DWG.No. REV.

STD-S032 STD-S033 STD-S030a


400mm EMBEDMENT
FOR CAST IN. 15M @ 250 BOT
FOR POST DRILL IN,
USE HILTI HIT-HY200 3-15M BOT
SYSTEM WITH 300 600 300 20∅ THREAD RODS @800 VERTICAL SLIP CONNECTION BY
200mm EMBEDMENT
O/C EPOXY GROUTED PRECAST CONCRETE MANUFACTURER
FILL CORE SOLID BY 150mm INTO PRECAST SLAB FOR PANELS BASED ON
PRECAST CONTRACTOR AND A MINIMUM OF 100mm REQUIREMENTS OF SLAB
(APPLICABLE TO CONCRETE BEAM SUPPORTED MASONRY WALL TOO) PRECAST
WITH NUT INTO THE POURED SEE MANUFACTURER
PANEL PRECAST DOUBLE TEE
RING BEAM STD-S032
SLABS
MINIMUM WIDTH CONCRETE RING BEAM
INTERIOR 190mm CMU FULLY GROUTED OF EXTERIOR MINIMUM 125 WIDE GALVANIZED BENT PLATE
SLAB =1000mm 150x150x6mmx3000 LONG WITH VERTICAL
NTS LEG. CONNECTED TO WALL WITH 2-20mm
DRILL-IN ANCHORS

15M CONTINUOUS BAR

BEARING PAD
ADJUSTABLE ANGLE
15M @ EACH REINFORCE DETAIL DESIGNED BY AND
1 SUPPLIED BY PANEL
CORE IN THE WALL WITH N.T.S. -
150 PROJECTION ABOVE MANUFACTURER
THE TOP OF THE WALL
CENTER AXIS
300
OF D/TEES
REINFORCED MASONRY WALL

900 15M DRILL-IN FOR


ANCHORS W/HORIZ CONNECTION
SLOTS (TYP) SEE DETAIL '1'
24/09/2018 6:57:09 PM

PRECAST
15M BENT BARS PRECAST PANEL PRECAST
CONCRETE
PRECAST HOLLOWCORE SLABS DOUBLE DOUBLE
LOCALLY BREAK OPEN CORE WALL
CONC TEE TEE
AND FILL SOLID GROUT BY
WALL
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

PRECAST CONTRACTOR

REINFORCED NEOPRENE
ALL PRECAST DOUBLE TEE CONNECTIONS BEARING PAD.
TO BE DESIGNED AND STAMPED BY (NO CONNECTION)
PRECAST MANUFACTURER'S ENGINEER

ANTI-ROTATION CONNECTION DETAIL DETAIL 2 DETAIL 3


N.T.S. - N.T.S. -

EXTERIOR MASONRY WALL AT CORESLAB DETAIL DWG. No. REV. TYPICAL CONNECTION FOR E. DOUBLE-TEE DWG.No. REV. TYPICAL CONNECTION FOR DOUBLE-TEE DWG.No. REV.

STD-S049 STD-S030 STD-S031a

VERIFY SCALES DESIGNED Designer CORE AREA WASTEWATER TREATMENT PROGRAM


BAR IS 20mm ON SURVEYED
MR 24/09/2018 4 ISSUED FOR CONSTRUCTION
CLOVER POINT PUMP STATION
20mm MR 19/07/2018 3 REISSUED FOR CONSTRUCTION - CAISSON WALL DRAWN Author DATE 02/02/2018 STRUCTURAL
MR 23/03/2018 2 ISSUED FOR 90% DESIGN SUBMISSION SCALE
As indicated CHECKED Checker
STANDARD DETAILS (5)
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 19/01/2018 1 ISSUED FOR 50% DESIGN SUBMISSION (S-405)
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-505 4 OF
LATERAL SUPPORT OF PERIMETER NON-LOAD LATERAL SUPPORT OF PERIMETER NON-LOAD LATERAL SUPPORT OF MASONRY PARTITIONS
TM-LATS-01 TM-LATS-02 TM-LATS-12
BEARING MASONRY WALLS AT FORMED CONCRETE BEARING MASONRY WALL AT STEEL STRUCTURE AT STEEL STRUCTURE
WALL ABOVE OR PARAPET (IF
APPLICABLE) FULLY GROUT PARAPET. PLATE 125x6 (5"x1/4")
L102x76x6.4 x150 (6") LG
SEE ARCHITECTURAL DRAWINGS LENGTH TO SUIT DECK
WITH 1-10 (3/8")Ø HILTI KB-3
SEE ARCH DRAWINGS PROFILE + 2-10 (3/8")Ø HILTI KB-3
CONCRETE SLAB (WHERE APPLICABLE) WITH 64 (2 1/2") EMBEDMENT
WITH 64 (2 1/2") EMBEDMENT
@ 1200 (4'-0")
MIN 80 (3 1/8") FILL DECK FLUTES UNDER WALL WITH @ 1200 (4'-0")
CONCRETE 563

GROUT (IF NO CONCRETE SLAB)


SLAB MAX 110 (4 3/8")
2-12 (1/2")Ø DCA 100 (4") APART REFER TO ARCHITECTURAL

125
6 (1/4") THICK BENT PLATE DRAWINGS AND SPECIFICATIONS

127
150 (6") LG @ 1200 (4'-0") FOR BACK UP SUPPORT DETAILS MASONRY DEFLECTION GAP 38 (1 1/2") MASONRY DEFLECTION
L102x76x6.4 (LLV)
WIDTH TO SUIT WALL THICKNESS (WHERE REQUIRED) DO NOT USE 25 (1") UNLESS OTHERWISE
190

GAP 25 (1") UNLESS


521

x150 (6") LG WELD


MASONRY. SHOWN ON PLANS OTHERWISE SHOWN ON
MASONRY DEFLECTION GAP TO PLATE

100 (4")
PLANS + MAX 10 (3/8")

MIN
25 (1") UNLESS OTHERWISE SHOW + MAX 10 (3/8")
BOND BEAM (IF SHOWN ON DRAWINGS)
ON PLANS + MAX 10 (3/8") MASONRY DEFLECTION GAP
563

CAN BE LOWERED MAX 1 COURSE


581

BOTTOM FLANGE LATERAL


25 (1") UNLESS OTHERWISE

100 (4")
BOND BEAM (IF SHOWN ON DRAWINGS) BRACING IF SHOWN ON PLANS BELOW TOP OF WALL. (TYP U/N)

MIN
CAN BE LOWERED MAX 1 COURSE SHOWN ON PLANS + MAX 10(3/8") FOR REINFORCED WALLS, CARRY
ALL VERTICALS TO TOP OF WALL (TYP)
873

BELOW TOP OF WALL. FOR REINFORCED


WALLS, CARRY ALL VERTICALS TO TOP BOND BEAM (IF SHOWN ON DRAWINGS) 6 (1/4") THICK BENT PLATE (OR STEEL ANGLE) WALL PERPENDICULAR TO FLOOR DECK FLUTES WALL PARALLEL TO FLOOR DECK FLUTES
OF WALL. CAN BE LOWERED MAX 1 COURSE x 125 (5") LG @ 600 (24"), ALTERNATE SIDES, OR

AUGUST 2017

AUGUST 2017
BELOW TOP OF WALL. FOR REINFORCED 6(1/4") THICK " ∏ " SHAPED BENT PLATE x 125(5") LG.
059
MIN 190 WALLS, CARRY ALL VERTICALS TO TOP @ 1200 (48") HSS 102x76x4.8 (LSH)
(8") WALL OF WALL. BETWEEN JOISTS
JOISTS OR BEAMS MASONRY DEFLECTION MASONRY DEFLECTION
@ MAX 3200 GAP 25 (1") UNLESS OTHERWISE GAP 25 (1") UNLESS OTHERWISE
SHOWN ON PLANS + MAX 10 (3/8") SHOWN ON PLANS + MAX 10 (3/8")

041
5 (3/16") BENT PLATE

631

041
x 150 (6") LG

h<4xb
GAP ALL AROUND
STEEL EQUAL TO @ 1200 (4'-0") WELD

h≥4xb
071

LATERAL SUPPORT OF MASONRY PARTITION

052
LATERAL SUPPORT OF MASONRY PARTITIONS TO STEEL

071
DEFLECTION GAP
TM-LATS-11

0392
TM-LATS-14

071
GAP ALL AROUND
AT FORMED CONCRETE STRUCTURE AT PRECAST STRUCTURE

071
51
521

STEEL EQUAL TO

581
DEFLECTION GAP

521
5 (3/16") BENT TREADED INSERT BY P/C 2-10 (3/8")Ø HILTI HDI-P DROP 5 (3/16") BENT PLATE 200 (8") DEEP L 102x76x6.4 (LLV)
MASONRY DEFLECTION GAP PLATE SUPPLIER FOR IN ANCHORS AT 75 (3") x 150 (6") LG AT 1200 (4'-0") BOND BEAM x 150 (6") LG
25 (1") UNLESS OTHERWISE REINFORCED BOND BEAM
x 150 (6") LG AT 1200 2-10 (3/8")Ø BOLTS AT 100 (4") WELD TO STEEL
10 (3/8")Ø DCA SHOWN ON PLANS + MAX 10 10 (3/8")Ø DCA 60 (2 3/8") WITH 2-15 CONT (IF SHOWN ON
(4'-0") 452

(3/8") AT BOLT HEAD MIN DRAWINGS)


b
950
b950

521
100 (4")
OR JOIST DEPTH LESS THAN 4 x WALL THICKNESS JOIST DEPTH EQUAL OR LARGER THAN 4 x WALL THICKNESS

100 (4")
62

MIN
5 (3/16") BENT PLATE
OR
197

TO SUITE WEB

573
MASONRY DEFLECTION WALL PERPENDICULAR TO ROOF JOISTS OR BEAMS

100 (4") MIN


CLIP L102x76x6.4 (LLV) 38 (1 1/2") 5 (3/16") BENT PLATE PROFILE
GAP 25 (1") UNLESS

81
x 150 (6") LG @ 1200 (4'-0") 52

x 150 (6") LG AT 1200 (4'-0") 1-12 (1/2")Ø THROUGH BOLT


OTHERWISE SHOWN ON L 89x89x6.4 BRACE

100 (4")
EACH SIDE (STAGGERED) THIS DETAIL ALSO APPLICABLE
PLANS + MAX 10 (3/8") (LOCATE P/T CABLES BEFORE - FOR JOIST FRAMING, PROVIDE AT EACH BENT PLATE
MASONRY DEFLECTION WHERE WALL IS
DRILLING AND ADJUST LOCATION
345

GAP 25 (1") UNLESS PERPENDICULAR TO PRECAST - FOR BEAM FRAMING, PROVIDE WHERE SHOWN ON PLAN

563
BOND BEAM (IF SHOWN TO CLEAR)
OTHERWISE SHOWN ON MASONRY DEFLECTION SPAN. FOR THAT CASE
ON DRAWINGS) CAN PLANS + MAX 10 (3/8") GAP 25 (1") UNLESS PROVIDE 25 (1") CLEAR
BE LOWERED MAX 1 AT BOLT HEAD OTHERWISE SHOWN BETWEEN WALL AND ALL
COURSE BELOW TOP PRECAST WEBS RUNNING

100 (4")
ON PLANS + MAX 10
563

OF WALL. FOR REINFORCED (3/8") THROUGH IT


WALLS, CARRY ALL VERTICALS AT BOLT HEAD
TO TOP OF WALL.
52

MASONRY DEFLECTION GAP 25 (1")


AUGUST 2017

BOND BEAM (IF SHOWN ON DRAWINGS)

AUGUST 2017
UNLESS OTHERWISE SHOWN ON PLANS
CAN BE LOWERED MAX 1 COURSE BELOW
+ MAX 10 (3/8")
TOP OF WALL. FOR REINFORCED WALLS,
CARRY ALL VERTICALS TO TOP OF WALL (TYP) 5 (3/16") BENT PLATE x 150 (6") LG
AT 1200 (4'-0") WELD TO STEEL

WALL IN LINE WITH ROOF JOISTS OR BEAMS


MASONRY DEFLECTION
LATERAL SUPPORT OF MASONRY PARTITIONS LATERAL SUPPORT OF MASONRY PARTITIONS
TM-LATS-15 TM-LATS-13 L89x89x6.4 MASONRY DEFLECTION GAP 25 (1") HSS 102x102x4.8
GAP 25 (1") UNLESS
AT TIMBER STRUCTURE AT HOLLOWCORE STRUCTURE AT EACH PAIR UNLESS OTHERWISE SHOWN ON @ 1200 (4'-0")
OTHERWISE SHOWN ON
PLANS + MAX 10 (3/8")
OF ANGLES PLANS + MAX 10 (3/8")
MASONRY DEFLECTION PROVIDE SOLID WOOD BLOCKING

931
561
GAP 25 (1") UNLESS EACH SIDE AT EACH SUPPORTING

h<4xb

h≥4xb
OTHERWISE SHOWN ON POINT LOCATE TO CLEAR 2-10 (3/8")Ø HILTI HDI-P
PLAN + 10 (3/8") 60 (2 3/8") DROP IN ANCHORS AT 75 (3")

052

052
MASONRY DEFLECTION GAP P/T STRANDS 435

L102x76x6.4 (LLV)
MIN 071

PROVIDE 25 (1") GAP 25 (1") UNLESS OTHERWISE x 150 (6") LG


WOOD JOIST
AGAINST EACH JOIST SHOWN ON PLAN + 10 (3/8")
461

L89x89x6.4
L102x76x6.4 (LLV) - FOR JOIST FRAMING, PROVIDE AT EACH

18
x 150 (6") LG PAIR OF ANGLES

100 (4")
5 (3/16") BENT PLATE
50 (2") x 150 (6") LG AT 1200 (4'-0") @ 1200 (4'-0") - FOR BEAM FRAMING, PROVIDE WHERE
50 (2") 250

073

SHOWN ON PLAN
25 (1") BOND BEAM (IF SHOWN

380
021

MASONRY DEFLECTION b GAP ALL AROUND STEEL EQUAL b


++ ++ BOND BEAM (IF SHOWN ON DRAWINGS) ON DRAWINGS) 950 950

GAP 25 (1") UNLESS OTHERWISE TO DEFLECTION GAP


CAN BE LOWERED MAX 1 COURSE
25 (1")

SHOWN ON PLANS + MAX 10 (3/8") JOIST DEPTH EQUALS OR LARGER THAN


L102x76x6.4 (LLV) L51x51x4.8 WITH GAP ALL AROUND STEEL BELOW TOP OF WALL. FOR REINFORCED JOIST DEPTH LESS THAN 4 x WALL THICKNESS
AT BOLT HEAD

AUGUST 2017
WALLS, CARRY ALL VERTICALS TO TOP 4 x WALL THICKNESS
EQUAL TO DEFLECTION
128

x 150 (6") LG 2 -L51x51x4.8 100x100x5 (4"x4"x3/16")


@ 1200 (4'-0") END PLATES AND 2 -6 (1/4") GAP OF WALL.
x 500 (1'-8") LG WALL PARALLEL TO ROOF JOISTS OR BEAMS
WITH 4 -6 (1/4") THROUGH BOLTS @ 50 (2")
L102x76x6.4 (LLV)
THROUGH BOLTS EACH END
x 150 (6") LG @ 1200 (4'-0")
BOND BEAM (IF SHOWN ON DRAWINGS).
FOR REINFORCED WALLS, CARRY ALL
VERTICALS TO TOP OF WALL (TYP)
WALL PARALLEL TO WOOD JOISTS
AUGUST 2017

AUGUST 2017
24/09/2018 6:57:12 PM

WALL PERPENDICULAR TO WOOD JOISTS NOTE:


2-L51x51 CAN BE LOCATED ANYWHERE ALONG JOIST HEIGHT
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

VERIFY SCALES DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM


BAR IS 20mm ON SURVEYED
MR 24/09/2018 4 ISSUED FOR CONSTRUCTION
CLOVER POINT PUMP STATION
20mm MR 15/06/2018 3 ISSUED FOR 100% DESIGN SUBMISSION DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 23/03/2018 2 ISSUED FOR 90% DESIGN SUBMISSION SCALE
1 : 100 CHECKED J.P.
STANDARD DETAILS (6)
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 19/01/2018 1 ISSUED FOR 50% DESIGN SUBMISSION
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-506 4 OF
WELDED CAPS (TYP.)

42 DIA. SCH 40 1500 MAX. 1500 MAX. SAFETY HANDLE LADDERRAIL "LADDER UP #
PIPE RAILING EQ. EQ. 3" ALUMINUM OR STAINLESS STEEL (FOR
(TYP) POTABLE WATER APPLICATIONS). SAFETY
POST BY BILCO OR APPROVED EQUAL
48 DIA. SCH 80
PIPE POST (TYP)

535
1070

535
TOC T/O CONC. 75
TYP

TYP
300

50 TYP
50 TYP
140x6MIN. KICK 48 DIA. SCH 80
PLATE AT LOCATIONS PIPE POST (TYP)
150

TYP
WITHOUT CONCRETE

50
TYP 42 DIA. SCH 40
CURB.
SEE DETAIL 1 PIPE RAILING
(ONLY AT VALVE CHAMBER)
(TYP)
45
KICK PLATE TYP
(ONLY VALVE CHAMBER)
WELDED ALL
100x125x10 100x125x10 AROUND
16M S.S. FLOOR
PLATE PLATE 12mm THICK 0.00
SEE DETAIL2 ANCHORS BRACKET (TYP)

1200 TYP
FOR 16mm 13x64 SIDE RAILS ALUM. SOCKET
S.S. ANCHORS SEE DETAIL 1
EMBED = 150mm

TYP
300
FALL ARREST SYSTEM SLIP FIT SLEEVE
DETAIL DETAIL SET IN

TYP
300
1 2 NON-SHRINK
T/O CONC. NON-FERROUS
NOTES: GROUT

100
1. ALL ROUGH EDGES AND WELDS OF ASSEMBLIES SHALL BE GROUND SMOOTH.

100
2. ALL 90° CORNERS SHALL BE MITERED USE MIN. RADIUS BEND FOR ALL OTHER
FRONT SIDE VIEW
CORNERS AND CURVES.
VIEW NON SHRINK GROUT
3. ALL CONNECTIONS SHALL BE WELDED. EDGE OF HATCH
4. WHEN GUARDRAIL POSTS ARE EMBEDDED IN SLEEVES OR CONNECTED TO
BRACKETS NOTES:
5. BELOW FLOOR LEVEL, POSTS SHALL BE ADJUSTED IN LENGTH. ENSURE TIGHT FIT
6. 140mm HIGH x 6mm THICK KICK PLATES SHALL BE PROVIDED WHERE THERE IS NO 1. CONNECTIONS OF SUPPORT BRACKETS TO STRUCTURES: - REINFORCED CONC - M20 DRILLED BETWEEN POST
CURB AND AT ALL STAIR FLIGHTS AND LANDINGS LOCATIONS. ANCHORS (MIN. EMBED=170). POST PLAN VIEW DETAIL 1 AND PIPE SLEEVE
7. GUARDRAIL IN NON-SUBMERGED CONDITION TO BE ALUMINUM (UNO) 2. PROVIDE A FALL ARREST SYSTEM FOR ALL LADDERS EXCEEDING 5m IN HEIGHT.
8. GUARDRAIL IN SUBMERGED CONDITION OR AT EXTERIOR OF BUILDING TO BE 3. RUNG SPACING SHALL BE UNIFORM.
STAINLESS STEEL (UNO) 4. LAYOUT OF LADDER RUNGS SHALL START FROM LANDING ELEVATION. NOTE:
9. GUARDRAILS IN CONTACT WITH DISSIMILAR METAL STRUCTURE SHALL BE FASTENED 5. ALL DIMENSIONS IN MILLIMETRES UNLESS OTHERWISE SPECIFIED.
COMPLETE WITH A NEOPRENE ISOLATION GASKET. 6. TERMINATE FALL ARREST SYSTEM 1m ABOVE FLOOR. • REMOVABLE SAFETY CHAIN TO BE
10. GUARDRAIL LOADS TO MEET THE REQUIREMENTS OF 4.1.5.15 OF THE 2006 ONTARIO 7. MATERIAL AS SPECIFIED ON STRUCTURAL DRAWINGS. INSTALLED AT OPENING SIDE OF
BUILDING CODE. ACCESS HATCH.
• FOR INTERIOR APPLICATION ONLY.

TYPICAL TOP MOUNTED GUARDRAIL S.S. LADDER C/W LADDER UP SAFETY POST HOT DIPPED GALV. REMOVABLE GUARDRAIL DETAIL
NTS NTS NTS

HANDRAIL SEE DETAIL

C200x28 FRAME
WITH ALUMINUM CONCRETE WALL
GRATING
38x5 TIED DOWN
16mm CONC.
FASTENERS
T/O GRATING
@750 C/C OR AT LEAST
3 NOS. AND EQ. SPACED
6 15
20mm DIA x 70mm ROD
SEAL 35 20 3mm THICK x 35mm C150x19 ANGLE BRACES
WELD CONT @ 1500mm MAX. C/C
6 COVER PLATE
NEOPRENE GASKET CL OF WITH 250x150 PLATE TO
25mmx70mm WALL & 4-20mm
SLOTTED HOLE CONC. FASTENERS. 1200
SIMILAR TO DETAIL 'A'
SEAL
TUBE 76x76x4.8
WELD 6 60mm LONG
0 TYP PLATFORM CONNECTION TO WALL DETAIL
30 AL SPACER TYPE "C"
PL 3mmx30x CONT COVER PL
6.4mmx76mmx76mm
50

PLATE, GRIND 150mm LG L50x75x10


AL PL 10mmx76mm x CONT, 6mm STAINLESS CORNERS TO 200 CLIP ANGLE WELDED
STOP 6mm FROM FACE OF STEEL MATCH RADIUS OF TO MOUNTING PLATE
SUPPORT ANGLE EA END, FLAT HEAD SCREWS SECTION
SPACE @300

CORNERS ON TUBE c/w 2-18mm DIA HOLES


DRILL & TAP FOR 6mm @ FOR 16mm DIA BOLTS
50

C200x28
(TYP.)

STAINLESS STEEL 300 CENTERS


SCREWS

175 NOTE: NOTE:

65
20 20
0
ST m m THIS DETAIL APPLIES AT TYPE "C" COVERS AND OTHER AIRTIGHT COVERS. THE DETAIL IS APPLICABLE TO TYPE "C" COVERS AND OTHER AIR TIGHT COVERS.
L50x75 C200x28
(TY AINL DIA.
PE ES BA
EDGE PLATE DETAIL
300

31 S S RS

70
LIFTING EYE TYPE "B"
24/09/2018 6:57:13 PM

6L T E

250

170
) EL

65
40
COVER 25 RECESS PLATE @ NOTE: 6
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

PLATE LIFTING LOCATION 18x40mm


1. STIFFENERS TO BE PLACED LONG LEG VERTICAL 40 120 6 LONG
20mm DIA. 2. SPAN DIRECTION OF PLATE TO BE PARALLEL TO STIFFENERS, AND SHALL SLOTS IN
EQ.

x100mm BE SHORT DIMENSIONS OF OPENING UNLESS NOTED OTHERWISE ON C200x17


75

LONG ROD PLANS. 16mm THK PLATE c/w


3. ALLOWABLE UNIFORM DESIGN PLATE THICKNESS LOAD = 15kPa. 4 HOLES THRU TO
EQ.

4. MAXIMUM WEIGHT OF COVER PLATE TO BE 35kg. ACCOMODATE


NOTE; 5. COVER PLATES AND STIFFENERS ARE ALUMINUM PLATES AND ANGLES. 16mm DIA CONC FASTENERS
TYP 6. ALL COVER PLATES TO HAVE A MINIMUM OF TWO EYES AS SHOWN c/w NUTS AND WASHERS
LADDER RUNG TO EXTEND 2100mm HIGH OF BASKET SCREEN PLATFORM ELEVATION. 5 IN LIFTING EYE DETAILS.
LIFTING EYE 7. ALL CHECKERED FLOOR PLATE TO BE AIR TIGHT UNO. (STRUCTURAL STEEL TO BE GALVANIZED)
DETAIL 'A'

LADDER RUNG DETAILS ALUM. CHECKER PLATE DETAIL METAL PLATFORM TO WALL CONNECTION
NTS NTS NTS

VERIFY SCALES DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM


BAR IS 20mm ON SURVEYED
MR 24/09/2018 4 ISSUED FOR CONSTRUCTION
CLOVER POINT PUMP STATION
20mm MR 15/06/2018 3 ISSUED FOR 100% DESIGN SUBMISSION DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 23/03/2018 2 ISSUED FOR 90% DESIGN SUBMISSION SCALE
1:1 CHECKED J.P.
STANDARD DETAILS (7)
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 19/01/2018 1 ISSUED FOR 50% DESIGN SUBMISSION
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-507 4 OF
RUN, SEE DWGS 1 90 STAIR WIDTH VARIES
FOR WIDTH, TYP. STRINGERS,
-
SEE TYP
25 L75x75x6 W/ PLANS
100 GRATING, SEE
MIN. 16mm WEDGE GRATING THICKNESS
ANCHORS @ TABLE FOR SIZE
CONNECTION BY STAIR FABRICATOR 300 OC 25

49
TY
P
16mm MB'S@300 TO
STRINGERS, 2 MIN
RISER, SEE DWGS
FOR HEIGHT TYP. STRINGER SIZE AS NOTED STAIR L50x50x6 GRATING
ON DWGS (SEE NOTE 4) EMBED.=150 mm TYP. STRINGERS SUPPORT
BEYOND
W/ STD BOLTED TYP
SAFETY TREAD
CONN,
ALUM. HANDRAILING ONE SIDE
TYP 50mm STD PIPE COLUMN,
SEE STD. DETAIL 5 FOR LOCATION SEE PLANS
TREAD MANUFACTURER TO STRINGER TO (U.N.O)
VERIFY HOLE LOCATION FOR CONC WALL
2-M16 HILTI HVA ADHESIVE PL 12x100x200 BASE
BOLTED CONNECTIONS CONN SIM TO 25+/- GROUT
65 125 ANCHORS, (TYP) 316 S.S. W/ 2 - 16mm EXPANSION
TOP CONN DETAIL
ANCHORS (U.N.O)
TYPICAL STAIR DETAIL

2-M16 HILTI HVA ADHESIVE ANCHORS


STAIR BOTTOM CONNECTION
CONNECTION BY EMBED.=150 mm 316 STAINLESS STEEL
RUN EQUALS STAIR WIDTH STRINGERS,
STAIR FABRICATOR
TYP OR AS SHOWN ON PLANS TYP
FULLY WELDED TOP OF CONCRETE SEE PLAN FOR VARIES TYP
STAIR WIDTH
C310 DEEP ALUM. OR G
GALV. STEEL
STRINGER CHANNEL 25

125
DWGS
RISER
SEE
25± NON-SHRINK SIDE MOUNTED
TREAD GROUT CONNECTION BY 12
STAIR FABRICATOR CL CONNECTIONS BY
STAIR FABRICATOR
CONNECTIONS BY
STAIR FABRICATOR BEAM BTWN
NOSING STRINGERS SEE PLAN
SIM TO
TREADS
TYP
GRATING, SEE PIPE COLUMN, 1
STAIR TOP CONNECTION GRATING EA END OF BEAM
THICKNESS 25+/- GROUT (U.N.O) 75∅x7 THK.
NOTES : TABLE FOR SIZE
1. TREAD TO BE SIZED IN ACCORDANCE WITH LIVE LOAD CHANNEL OR PL 12x100x200 BASE
SHOWN ON STRUCTURAL PLANS AND NOTES. W-BEAM SEE NOTE: W/ 2 - 16mm CONC
2. STAIRS HANDRAIL NOT SHOWN FOR CLARITY. PLAN ANCHORS AS
3. ALL METAL TO BE HOT-DIP GALVANIZED OR ALUMINUM AS
ELEVATI0N 1-1 STAIR HANDRAIL NOT SHOWN. SPECIFIED
NOTED ON STRUCTURAL DWGS.
4. UNLESS NOTED OTHERWISE STRINGERS TO BE C310x31 METAL STAIR LANDING WITH SUPPORTS
GALVANIZED STEEL.

STANDARD STEEL STAIR DETAIL (1) DWG. No.

STD-S060
REV.
STANDARD STEEL STAIR DETAIL (2) DWG. No.

STD-S061
REV. STAIR LANDING WITH SUPPORT DWG. No.

STD-S067
REV.

125
1200
FULLY WELDED MAX. TYP. HANDRAIL &
T/O CONC.
POST
C310 DEEP ALUM. OR ALUMINUM
GALV. STEEL A SAFETY CHAIN
-
STRINGER CHANNEL OR SWING GATE

ALUMINIUM
TREAD SNAP-HOOKS

535
ALUMINIUM 25∅ EYES
SECURED WITH NUT
AND LOCK WASHER

2-M16 HILTI HVA


ADHESIVE ANCHORS 140x6
LINE OF FACE OF EMBED.=150 mm 316 KICKPLATE
CONCRETE STAINLESS STEEL
24/09/2018 6:57:15 PM

AT LOCATIONS

535
WITHOUT
WEB OF STRINGER CONCRETE CURB
CHANNEL
FIN. FLOOR
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

REMOVABLE RAILING DETAIL


PLAN SECTION A-A

STANDARD STEEL STAIR DETAIL (1) DWG. No.

STD-S060
REV.
REMOVABLE SAFETY CHAIN DETAIL DWG.No.

STD-S064
REV.

VERIFY SCALES DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM


BAR IS 20mm ON SURVEYED
CLOVER POINT PUMP STATION
20mm MR 24/09/2018 3 ISSUED FOR CONSTRUCTION DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 15/06/2018 2 ISSUED FOR 100% DESIGN SUBMISSION SCALE
1:1 CHECKED J.P.
STANDARD DETAILS (8)
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 23/03/2018 1 ISSUED FOR 90% DESIGN SUBMISSION
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-508 3 OF
COVEX COVEX

MITER CORNERS OF VERTICAL


JOINTS & WELD SIMILAR AS
SHOWN BELOW FOR IN-PLANE
JOINTS FILL SOLID WITH FILL SOLID WITH 30MPa
STRUCTURAL STRUCTURAL CONCRETE
CONCRETE

15M@200 ALL AROUND


(MIN. 8 DOWELS) IN HILTI HY150 MAX
SD ADHESIVE ANCHORS.
EMBED = 190mm INTO EXISTING
SLAB.

1500

1500
NOTE:
HSS 219mm HSS 219mm ODx6.35mm HOT
WHERE EXISTING SLAB IS < 250 ODx6.35mm DIPPED GALVANIZED POST
THICK USE 10mm WITH 115mm HOT DIPPED WELDED TO 350x350x16 HOT
VERTICAL ELL VERTICAL CROSS VERTICAL TEE AT PERIMETER EMBEDMENT GALVANIZED DIPPED GALVANIZED PLATE
POST
SAWCUT & REMOVE
TOPPING ROUGHEN 10M@200mm
SLAB ± 10mm TIES AROUND
SECOND WELD SECOND FIRST (MIN. 2 TIES) 4-M20 DRILLED-IN HEAVY
WELD WELD DURY EXPANSION ANCHORS
FIRST WELD (ZINC PLATED)

25
T/O GRADE T/O CONC.

EXTEND TO FROST LINE AS PER


GEOTECNICAL INVESTIGATION
PADS LESS THAN 1000 HIGH

CONCRETE SLAB
THIRD WELD 25mm NON-SHRINK
NON-FERROS GROUT

1000
REPORT
NOTE: GRANULAR 'B'
COMPACTED TO
FLAT ELL FLAT CROSS FLAT TEE 1. REMOVE ANY TOPPING DOWN TO STRUCTURAL SLAB. 100% SPMDD
ROUGHEN EXISTING FLOOR SLAB FINISHED EL. TOP OF PAD
AND GROUT FROM LAYOUTS, GENERALLY 25mm OF GROUT.
2. DIMENSIONS OF BASES, ANCHOR BOLTS, SIZES AND
NOTE: LOCATIONS TO SUIT EQUIPMENT SUPPLIED AS STIPULATED BY STRUCTURAL
EQUIPMENT MANUFACTURER. CONCRETE
ALL WELDS SHALL BE PER WATERSTOP MANUFACTURER'S 3. ANCHOR BOLT SIZE, EMBEDMENT DETAILS, PRESTRESSING, BASE
RECOMMENDATIONS. ETC AS REQUIRED BY EQUIPMENT MANUFACTURER.

400

WATERSTOP JOINTS CONCRETE PAD DETAIL BOLLARD DETAIL


NTS NTS NTS

EQ. EQ. EQ. TYPICAL OPENING REINF CONSTRUCTION


AROUND PIPE JOINT.
(SEE DETAIL STD-6 DWG S-9-008)
SLAB THK.

EXTEND ENCASEMENT
VERTS AND BEND 300mm
INTO TOP OF SLAB

3 5 6 3
4 4
100 TYP

2-15M EACH SIDE


2 600 300 300
2
TYP.
40mm

BOTTOM "U" SECTION HYDROPHILIC WATERSTOP


1 OF TIES CONT TO END CONTINUOUS ALL AROUND
OF ENCASEMENT IN ALL CONSTRUCTION
JOINTS
1
TYPICAL PIPE
ENCASEMENT REINF

BEND & LAP PIPE


ENCASEMENT
REINF 300mm, TYP.
SECTION SECTIONAL PLAN
(IN WALLS) (IN WALLS)

PROVIDE LEVEL BEARING


AREA BELOW VERT PIPE
RISER EQUAL TO
ENCASEMENT GROSS END
ENCASEMENT RISER
1 150mmx10mm P.V.C. WATERSTOP. AREA
24/09/2018 6:57:17 PM

2 2 CONTINUOUS 10M REINF. BARS TIED TO WATERSTOP


AT 300mm C/C AND TIED TO MAIN REINF. AT 600mm
C/C. 200 MIN. ALL AROUND
1
3 CLEAN FIRST POUR SURFACE THOROUGHLY OF ALL
CONTAMINANTS LAITANCE OR INFERIOR CONCRETE 15M TIES @ 300
2 3 5 BEFORE SECOND POUR AND ROUGHEN TO FULL 5mm
AMPLITUDE. LAP LENGTH SEE
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

4 75mm CLEAR (TYP) GENERAL STRUCTURAL


4 13mm DEEP 20mm WIDE REGLET FOR EXTERIOR FACE
ONLY. APPLY CAULKING TO REGLET AFTER WALL COATING. NOTES
5 LEAVE SURFACE ROUGH BETWEEN POUR AT HORIZONTAL 7-15M
90mm JOINTS. CONTINUOUS
6 FORM JOINTS AT VERTICAL AND SLOPING JOINTS.

7 ITEMS 1 AND 2 MAY BE OMITTED WHERE SPECIFIED.


SECTION
NOTES:
SECTION
1. SECTION APPLIES TO PIPES W/ DIAMETERS OF 500mm AND SMALLER.

CONSTRUCTION JOINT DETAIL


NTS PIPE ENCASEMENT FOR PIPE < 500mmØ ±
NTS
VERIFY SCALES DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM
BAR IS 20mm ON SURVEYED
CLOVER POINT PUMP STATION
20mm MR 24/09/2018 3 ISSUED FOR CONSTRUCTION DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 15/06/2018 2 ISSUED FOR 100% DESIGN SUBMISSION SCALE
As indicated CHECKED J.P.
STANDARD DETAILS (9)
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 23/03/2018 1 ISSUED FOR 90% DESIGN SUBMISSION (S-405)
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-509 3 OF
PIPE ENCASEMENT A B
TABLE -
FOR WALL SLAB RIENFORCEMENT -
PIPE DIA. H=3000mm H=6000mm H=9000mm H=12000mm RIENFORCEMENT SEE SECTIONS SEE DWGS FOR GRATING DETAILS
(mm) TYPICAL SEE SECTIONS SEE STD DETAILS FOR SEATING
"t" (mm) REINF "t" (mm) REINF "t" (mm) REINF "t" (mm) REINF AS NOTED
FOOTING/SLAB DETAIL
500 THRU 750 200 15M@300 250 15M@300 250 15M@300 250 20M@300 EXTENSION AS
900 THRU 1050 250 15M@300 250 20M@300 250 25M@300 250 20M@150 WIDTH NOTED
FOR SLAB
1200 THRU 1400 250 20M@300 250 25M@300 250 25M@150 300 25M@150 RIENFORCEMENT
UP TO 1500 20M@300 250 25M@150 350 25M@150 WALL JOINT
250 25M@150 SEE SECTIONS SEE PLANS

HEAVY DARK LINE INDICATES BREAK BETWEEN ONE LAYER OF REINFORCING

SECTIONS
AND TWO. SEE NOTE 2.

SEE
t
BOTTOM OF SLAB

t
50mm COVER, TYP

45°
MIN.
"REINF" T&B, SEE TABLE.

100
TOP AND SIDES POURED WITH
SEE NOTE 2 FOR "t"=200mm FILL WITH
UNCOMPACTED THE WALL
t d
GRANULAR

A SIDE OF

TYP.
"t"

CLR
EXCAVATION TO

40
-
REINFORCEMENT: SAME

SEE GENERAL
STRUCTURAL
BE COVERED

LAP LENGTH
AS BOTTOM SLAB. EXTEND BASE

NOTES.
SLAB TO SUIT B WITH 10ML
POLYETHALENE

PIPE OD TYP
-
REINFORCEMENT: SAME

EACH FACE
SHALLOW SUMP DETAIL
AS BOTTOM SLAB.
SEE
NOTE 4 DEEP SUMP DETAIL
"REINF" TYP EACH SIDE
SUMP PIT BEYOND
15M@300
LONGITUDAL

50

"t"
WALL JOINT TYPICAL WALL
TYP. ALL AROUND TYPICAL FOOTING THICKNESS
EXTENSION

CLR
75
"REINF" T&B
"t"
OPTIONAL CONSTRUCTION

d
TYP EA SIDE JOINT

t
NOTES:
45°

t
1. THIS DETAIL APPLIES TO PIPE DIAMETER OF 500mm AND LARGER. FOR
SMALLER THAN 500mm SEE DETAIL STD-S025.
SUMP
2. FOR "t"=200mm REINFORCING SHALL BE ONE LAYER AND CENTERED FOOTING t t
IN SLABS OR WALLS. EXTENSION
3. "H" IS FILL HEIGHT OR WATER DEPTH OR COMBINATION ABOVE PIPE.
4. HYDROPHILIC WATERSTOP CONTINUOUS ALL AROUND IN ALL
CONSTRUCTION JOINTS.
SECTION A
N.T.S. -

SECTION B
N.T.S. -

PIPE ENCASEMENT FOR PIPE > 500∅ DWG. No.

STD-S024
REV.
TYPICAL SHALLOW SUMP DETAIL DWG. No.

STD-S022
REV.
TYPICAL DEEP SUMP DETAIL DWG. No.

STD-S022a
REV.

PIPE OUTSIDE DIAMETER


50mm CLEAR: +300
-DRY CONDITION 150
SUSPENDED RAILING POST
SLAB (TYP.) FORMED RECESS DIA. SHALL
50mm CLEAR:
PIPE SIZE AS BE RAILING POST OD + 20mm
-LIQUID
-AIR OVER LIQUID SHOWN OR STRAP WHERE REQUIRED
-EARTH SPECIFIED BY SEALANT ALL
BY MECHANICAL/PROCESS
-WEATHER PROCESS DRAWINGS AROUND
DIVISIONS 20mm CHAMFER
NON-SHRINK (TYP.) 250
50mm CLEAR FOR
20mm AGGREGATE: NON-FERROUS
-LIQUID GROUT, AS REQUIRED 2-15M
-AIR OVER LIQUID CONTINUOUS

150
A

200
-EARTH

75
-WEATHER
-
FILL WITH

TO SUIT PIPE ELEVATION


60MM CLEAR FOR
40MM AGGREGATE: FLOWABLE
EPOXY GROUT

10M@300 TIES
-LIQUID WALL BEAMS & 15M@300 WITH MATCHING

(MINIMUM 1 TIE)
-AIR OVER LIQUID COLUMNS GROUTED OR CAST-IN
-EARTH CLEARANCE DOWELS AROUND
-WEATHER TO TIES OR PERIMETER SUPOPRT
SEE NOTE 1 50mm CLEAR: (4-15M MINIMUM PER
STIRRUPS
-DRY CONDITION 300

600
SUPPORT)
75mm CLEAR: -LIQUIDS 10M @400
POUR AGAINST EARTH -EARTH
-WEATHER

75

200
40∅ RAILING DESIGNED
FOR RAILING POST AT 1200
24/09/2018 6:57:18 PM

O/C SPACING 4-10∅ EPOXY BONDED SS


ANCHORS WITH 100
50mm CLEAR EMBEDMENT
50mm CLEAR: 20mm CHAMFER
SLAB THICKNESS

-DRY CONDITION (TYP.) 250


SEE PLAN

MECHANICALLY ROUGHEN
75mm CLEAR: 50mm CLEAR: SURFACE AND
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

POURED AGAINST EARTH -LIQUID THOROUGHLY CLEAN 2-15M


250
-AIR OVER LIQUID CONTINUOUS

150
200
-EARTH
75
SLAB ON GRADE, MAT -WEATHER
FOUNDATIONS, FOOTINGS BASE PLATE
AND PILES CAPS REFER TO PROCESS 125x125x10
DWGS PLATE
FOR DIMENSIONS

75
NOTE:
1. PROVIDE 50mm CLEARANCE ON FACE EXPOSED TO DRY
SECTION A
CONDITION N.T.S. - 300
10M @400

CONCRETE COVER TO REINFORCEMENT DWG. No. REV. TYPICAL CONCRETE PIPE SUPPORT DWG. No.

STD-S027
REV. RAILING POST SET IN CURB DWG. No.

STD-S038
REV.

STD-S015

VERIFY SCALES DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM


BAR IS 20mm ON SURVEYED
CLOVER POINT PUMP STATION
20mm MR 24/09/2018 3 ISSUED FOR CONSTRUCTION DRAWN S.R. DATE 02/02/2018 PROCESS
ARCHITECTURAL
ELECTRICAL
MECHANICAL
MR 15/06/2018 2 ISSUED FOR 100% DESIGN SUBMISSION SCALE
1:1 CHECKED J.P.
STANDARD DETAILS (10)
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 23/03/2018 1 ISSUED FOR 90% DESIGN SUBMISSION
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-510 3 OF
40

50

15
PLAN VIEW

9.5mm-16 x 127mm
THREADS SS WELDED
WIRE EYEBOLT & HILTI HY
HINGE MCMASTER CAR 150 EPOXY
#1528A23 WELDED TO
FLAT BAR

SS FLAT BAR
9.5mm x 50mm 56

2-6.4mm S.S.
COUNTERSUNK MACHINE
SCREW AND HILTI HY 150
EPOXY

HATCH SECURITY BAR

HATCH SECURITY BAR C/W PADLOCK DWG. No.

STD-S069
REV.

FINISH
FLOOR
GRATING AS
SPECIFIED

TO SUIT DEPT
OF GRATING
30 .
MIN
24/09/2018 6:57:19 PM

10∅ STUD ANCHOR OR EQUIVALENT


x100mm LONG (MIN.) @ 400 O.C.
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

WITH A MIN. OF 2 PER SIDE

NOTES:
1. L FRAME CORNERS ARE TO BE MITRED WELDED & GROUND
SMOOTH.
2. MIN. SEATING L THICKNESS TO BE 4mm MIN.

3. L FRAME & GRATING TO BE OF SAME


MATERIAL.

TYPICAL GRATING SEATING DETAIL DWG. No.

STD-S083
REV.

VERIFY SCALES DESIGNED R.L. CORE AREA WASTEWATER TREATMENT PROGRAM


BAR IS 20mm ON SURVEYED
CLOVER POINT PUMP STATION
20mm MR 24/09/2018 3 ISSUED FOR CONSTRUCTION DRAWN S.R. DATE 02/02/2018 STRUCTURAL
MR 15/06/2018 2 ISSUED FOR 100% DESIGN SUBMISSION SCALE
1:1 CHECKED J.P.
STANDARD DETAILS (11)
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 23/03/2018 1 ISSUED FOR 90% DESIGN SUBMISSION
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-511 3 OF
FIELD VERIFY

150 EQ EQ 150 7
25 GROUT
ALLOW TYP S-701
EXIST ROOF EXIST ROOF
Tf=Cf+1100 kN Tf=Cf+1100 kN Tf=Cf+1100 kN
120 120 EXIST ROOF EXIST ROOF
100

DRAG STRUT
HSS127x127
4 5 HSS127x127

100

100
DRAG STRUT S-701 S-701
HSS127x127 DYWIDAG BARS

100
L127x89x7.9x100 LG LLV
PLATE 45x200x400 TYP C/W 16Ø HILT HAS ROD & EXIST WALL
C/W 2-43Ø DYWIDAG HILTI HIT-RE500V3 EPOXY, 25 GROUT
fy/fu-517/690MPa HSS127x127 EMBED 80 ALLOW TYP

3 TYPICAL DRAG STRUT DETAIL 4 SECTION 5 SECTION 6 DRAG STRUT ANCHOR DETAIL
S-106 S-106
1 : 20 S-701
1 : 10 S-701
1 : 10 1 : 20

80 120 80 EXIST ROOF

100

80
10

140
HSS127x127

3 ROWS 3-20M @50

80
PLATE 45x280x300 C/W 3-36Ø
DYWIDAG, EMBED 4000 INTO
STIFFENER 40 NEW CONC WALL
PLATE 10 (TYP) fy/fu-517/690MPa

3 ROWS 2-25Ø
NOTE:
DYWIDAG DOWELS
LOCATION AT BAYLINE A1: AS SHOWN
LOCATION AT BAYLINE B1: OPPOSITE

4 3
9
S-701
20M @150 EF C/W
DOWELS TO MATCH 7 SECTION 9 DETAIL
DOWELS TO MATCH VERT C/W
HILTI HY200 EPOXY, EMBED 100
S-701
1 : 10 S-701
1 : 20
20M @200
INTO CONC SLAB. HOOK DOWELS
U-BARS T&B INTO NEW CONC INFILL, TYP
EXG MOTOR RM & WET WELL FLOOR
3.609 m

C
9 11
S-702 S-701

EXIST CONC
WALL EXIST
EXIST STONE CONC WALL
Z8
Z8

Z8

Z7

Z8

Z2

VENEER

100
EXIST
20M @200 H1E EF
REINFORCING

GROUT SOLID 15M @250 H1E EF


C/W HILTI HIT-HY200
24/09/2018 6:57:22 PM

EPOXY, EMBED 150


20M @200 EF

HSS305x102x9.5

100
GROUT SOLID

15M EF
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

2
0
5

EXG VALVE FLOOR


-2.304 m HSS305x102x9.5
C/W 16Ø x80 LG
LOUVER NELSON STUDS @
200 O.C.
LAP 1.5 ld, TYP

8 SECTION 10 DETAIL
S-701
1 : 10
S-701
1 : 50 11 SECTION
S-701
1 : 10

VERIFY SCALES DESIGNED M.S. CORE AREA WASTEWATER TREATMENT PROGRAM


BAR IS 20mm ON SURVEYED
CLOVER POINT PUMP STATION
20mm MR 24/09/2018 3 ISSUED FOR CONSTRUCTION DRAWN J.G. DATE 02/02/2018 STRUCTURAL
MR 15/06/2018 2 ISSUED FOR 100% DESIGN SUBMISSION SCALE
As indicated CHECKED A.P.
DETAILS
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 23/03/2018 1 ISSUED FOR 90% DESIGN SUBMISSION
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-701 3 OF
2 3 4 NOTES:
1. SEE DRAWING S-319 FOR SHEAR WALL NOTES
800
5 2. DYWIDAG RODS fy/fu=517/690 MPa
300 ± (SITE VERIFY TO CLEAR 1OM TIES SETS 3. CUTTING OF EXIST REINFORCING NOT PERMITTED
S-702 NEW INFILL WALL BETWEEN 25mm GAP, TOP & EA
EXIST COL EXIST COL BEAMS TO MATCH THE WALL EXIST COL SIDE TYP. EXISTING PIPING/ELECTRICAL)
BELOW (TYP.)
6
1
0 0
6 0
6

EXG UPPER ROOF

600
10.802 m 20-25Ø H1E DYWIDAG
RODS C/W NUTS &
WASHERS

EXIST BEAM
8 3

914

4
1
9
S-702 S-702
SIM

11 HS

HSS 114x114x9.5
.5 S
Cf 114
4x9 kN

HSS 114x114x9.5
25mm GAP (TYP.)

HSS 114x114x9.5
S-702 1 = T x1
x1 0
DETAIL

HSS 114x114x9.5
f = 14x SEE TYP. DETAIL FOR
S 114 f = 78 78 9.5 LATERAL SUPPORT 2
0k
HS f = T N
8 C S-102
SIM 1 : 20
S-702
11
S-702 EXG MEZZANINE LEVEL
6.825 m

EXIST
BEAM
610
SIM GROUT POCKET
8 AT GUSSET FOR HOOKED DOWELS
S-702 .5 LOCATION, TYP SEE DWG S-103

HSS 114x114x9.5
4x9 N .5
4x9 kN

HSS 114x114x9.5
11
4x 0 k x11 0 1OM @300 TIES SETS
11 = 78 14 78

HSS 114x114x9.5
S 20 GAP, FIRE STOP
S 1 Tf =

HSS 114x114x9.5
HS = Tf BY OTHERS. TYP S
H f= 15M @600 DOWELS 800mm LG,
Cf EACH SIDE OF NEW C ANCHOR INTO EXISTING BEAM
CMU WALL BY HILTI-HY200 ADHESIVE ANCHORING
SYSTEM, MIN. 200mm EMBEDMENT
(TYP.)
MASS CONCRETE
EXG MOTOR RM & WET WELL FLOOR
3.609 m

DYWIDAG RODS C/W


NUTS & WASHERS

NOTE: 190 CMU WALL EXIST CONC WALL

100 TYP
CUTTING OF EXIST REINFORCING IS NOT PERMITTED, ADJUST ANCHOR LOCATIONS AS REQ'D

305
1 SECTION 70 70
PLATE 10x320x340
C/W 4-25Ø HILTI
3 S-102 HAS-E RODS, &
1 : 50 HILTI HIT-HY200

Vf=240kN
7 FOR REINFORCEMENT

40
EPOXY, EMBED 110

100
(E) CONC. SLAB SEE ZONE SCHEDULE BEDROCK
S-702

L152x102x9.5 ALL AROUND HSS305x102


3 SECTION

220
EXG UPPER ROOF
3-20Ø DYWIDAG
S-702
1 : 20
10.802 m

40
DOWELS
Hf=50kN PLATE 10x340x75
3-25Ø HILTI SUPER HAS
RODS C/W HILTI HY200 DETAIL
250

6 EPOXY, EMBED 250 4


S-702 S-702
1 : 20 9 SECTION
250

S-702
1 : 10
EXG MIDDLE ROOF
9.888 m 10 75 250 75 B
S-702 3
25mm NON-SHRINK
GROUT (4 SIDES)

NOTE: FIELD VERIFY ANCHOR LAYOUT DIMENSIONS,


B 6-25Ø THREADED RODS
FABRICATOR TO SCAN EXISTING CONC. COLUMNS
100 100 C/W HILTI HY200 EPOXY 100mm TYP.
200 200 AND BEAMS FOR PROPOSED ANCHOR LAYOUT
152 EMBED 250 300-GL 4 (SEE ELEV.) 200 MIN 200 MIN 200 MIN 75
8-25Ø THREADED RODS PRIOR TO THE COMMENCEMENT OF WORK.
(E) CONC BEAM
EXG UPPER ROOF C/W HILTI HY200 EPOXY PROCEED WITH WRITTEN ENGINEERING
EMBED 250 APPROVAL AND MATCH DRILL GUSSET PLATES TO
5 DETAIL 10.802 m SUIT IN-SITU ANCHOR LAYOUT. CUTTING OF
EXISTING REBAR IS NOT PERMITTED.
ROOF ROOF
S-702
1 : 20
8.959 m 8.959 m
100

(E) ROOF (E) CONC COLUMN


25mm PLATE
L152x102 HSS 114x114
200

200
HSS 114X114
8
PLATE 30x150x300 C/W 2-
25Ø THREADED RODS HILTI
200

200
25mm NON-SHRINK PLATE 4
(E) 381x914 DP HAS-E C/W HILTI HY200
GROUT (4 SIDES)
24/09/2018 6:57:25 PM

(E) CONC BEAM R/C BEAM EPOXY, EMBED 200.


L152x102 (E) CONC
75

100
PLATE 10, CORBEL
L152x102 EXG LOWER ROOF EXG LOWER ROOF EXG MEZZANINE LEVEL
TYP
8.364 m 8.364 m 6.825 m

GROUT
TYP
6 50-150 6

25
(E) COLUMN HSS114x114
S:\MA\17\171-15492-00 CRD Clover Pump Station\6.0 Dwg\6.2 Detail design\5.0 Structural\CPS_STRC_R18.rvt

EXG MIDDLE ROOF HSS 114X114


(E) CONC WALL (E) CONC BEAM
9.888 m
PLATE 4
200

CJP
SECTION 10 SECTION
114 TYP 11 8 SECTION
S-702
1 : 10
S-702
1 : 10
100

3-25Ø HILTI SUPER HAS


RODS C/W HILTI HY200 NOTE: FIELD VERIFY ANCHOR LAYOUT DIMENSIONS,
S-702
1 : 10
EPOXY, EMBED 250 FABRICATOR TO SCAN EXISTING CONC. COLUMNS
AND BEAMS FOR PROPOSED ANCHOR LAYOUT
6 SECTION (E) 533x914 DP R/C BEAM PRIOR TO THE COMMENCEMENT OF WORK.
PROCEED WITH WRITTEN ENGINEERING
S-702
1 : 10 APPROVAL AND MATCH DRILL GUSSET PLATES TO
SUIT IN-SITU ANCHOR LAYOUT. CUTTING OF
7 SECTION EXISTING REBAR IS NOT PERMITTED.

S-702
1 : 10

VERIFY SCALES DESIGNED M.S. CORE AREA WASTEWATER TREATMENT PROGRAM


BAR IS 20mm ON MR 24/09/2018 5 ISSUED FOR CONSTRUCTION SURVEYED
MR 19/07/2018 4 REISSUED FOR CONSTRUCTION - CAISSON WALL
CLOVER POINT PUMP STATION
20mm MR 15/06/2018 3 ISSUED FOR 100% DESIGN SUBMISSION DRAWN J.G. DATE 02/02/2018 STRUCTURAL
MR 16/05/2018 2 ISSUED FOR CONSTRUCTION - CAISSON WALL SCALE
As indicated CHECKED A.P.
DETAILS
IF NOT 20mm ON HORIZONTAL
THIS SHEET, ADJUST MR 23/03/2018 1 ISSUED FOR 90% DESIGN SUBMISSION
SCALE CONTRACT DRAWING ISSUE SHT. No.
SCALES ACCORDINGLY SEAL BY DATE No. REVISION ENG. No. DATE ISSUE VERTICAL - APPROVED NUMBER CPS-100 NUMBER CP-C01-S-702 5 OF

You might also like