HVAC Load Analysis


for

COSAPI

Prepared By:

Gutierrez Castillo Ingenieros S.A.C


Av. La Molina 644 Interior 1A.
Lima

10 de Enero de 2019
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Polideportivo Oficina Antidopping
Hell

Building Summary Loads


Building peaks in January at 10pm.
Bldg Load Area Sen %Tot Lat Sen Net %Net
Descriptions Quan Loss Loss Gain Gain Gain Gain
Roof 0 0 0.00 0 0 0 0.00
Wall 518 0 0.00 0 6,227 6,227 5.39
Glass 0 0 0.00 0 0 0 0.00
Floor Slab 0 0 0.00 0 0 0 0.00
Skin Loads 0 0.00 0 6,227 6,227 5.39
Lighting 4,024 0 0.00 0 14,410 14,410 12.48
Equipment 6,250 0 0.00 0 22,094 22,094 19.13
People 69 0 0.00 14,160 17,700 31,860 27.59
Partition 5,768 0 0.00 0 16,020 16,020 13.87
Cool. Pret. 0 0 0.00 0 0 0 0.00
Heat. Pret. 0 0 0.00 0 0 0 0.00
Cool. Vent. 551 0 0.00 18,200 6,656 24,856 21.53
Heat. Vent. 0 0 0.00 0 0 0 0.00
Cool. Infil. 0 0 0.00 0 0 0 0.00
Heat. Infil. 0 0 0.00 0 0 0 0.00
Draw-Thru Fan 0 0 0.00 0 0 0 0.00
Blow-Thru Fan 0 0 0.00 0 0 0 0.00
Reserve Cap. 0 0 0.00 0 0 0 0.00
Reheat Cap. 0 0 0.00 0 0 0 0.00
Supply Duct 0 0 0.00 0 0 0 0.00
Return Duct 0 0 0.00 0 0 0 0.00
Misc. Supply 0 0 0.00 0 0 0 0.00
Misc. Return 0 0 0.00 0 0 0 0.00
Building Totals 0 0.00 32,360 83,106 115,466 100.00

Building Sen %Tot Lat Sen Net %Net


Summary Loss Loss Gain Gain Gain Gain
Ventilation 0 0.00 18,200 6,656 24,856 21.53
Infiltration 0 0.00 0 0 0 0.00
Pretreated Air 0 0.00 0 0 0 0.00
Zone Loads 0 0.00 14,160 76,450 90,610 78.47
Plenum Loads 0 0.00 0 0 0 0.00
Fan & Duct Loads 0 0.00 0 0 0 0.00
Building Totals 0 0.00 32,360 83,106 115,466 100.00

Check Figures
Total Building Supply Air (based on a 21° TD): 3,268 CFM
Total Building Vent. Air (16.86% of Supply): 551 CFM
Total Conditioned Air Space: 1,727 Sq.ft
Supply Air Per Unit Area: 1.8921 CFM/Sq.ft
Area Per Cooling Capacity: 179.5 Sq.ft/Ton
Cooling Capacity Per Area: 0.0056 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 9.62 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Polideportivo Oficina Antidopping
Hell

Air Handler #1 - Area De Preparación - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
1 Zona 1 570 0 24,196 2,760 None 7.5/P, 0.06/ft²
10pm January 12 0 1,098 0 0 124
6,359 0.00 1.92 0 0 124
Zone Peak Totals: 570 0 24,196 2,760
Total Zones: 1 12 0 1,098 0 0 124
Unique Zones: 1 6,359 0.00 1.92 0 0 124
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Polideportivo Oficina Antidopping
Hell

Air Handler #1 - Area De Preparación - Total Load Summary


Air Handler Description: Area De Preparación Constant Volume - Sum of Peaks
Sensible Heat Ratio: 0.90 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 10pm in January.
Outdoor Conditions: Clg: 86° DB, 75° WB, 113.39 grains
Indoor Conditions: Clg: 75° DB, 50% RH
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 0 Btuh
Heating Supply Air: 0 / (.999 X 1.08 X 0) = 0 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Zone space sensible gain: 24,196 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 24,196 Btuh
Cooling Supply Air: 24,196 / (.999 X 1.1 X 20) = 1,098 CFM
Summer Vent Outside Air (11.3% of supply) = 124 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 1,501 Btuh 124 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 1,501 Btuh
Total sensible gain on air handling system: 25,697 Btuh
Zone space latent gain: 2,760 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 4,104 Btuh
Total latent gain on air handling system: 6,864 Btuh
Total system sensible and latent gain: 32,561 Btuh

Check Figures
Total Air Handler Supply Air (based on a 20° TD): 1,098 CFM
Total Air Handler Vent. Air (11.32% of Supply): 124 CFM
Total Conditioned Air Space: 570 Sq.ft
Supply Air Per Unit Area: 1.9247 CFM/Sq.ft
Area Per Cooling Capacity: 210.2 Sq.ft/Ton
Cooling Capacity Per Area: 0.0048 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 2.71 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Polideportivo Oficina Antidopping
Hell

Air Handler #2 - Cuarto De Proceso 1 - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
2 Zona 2 113 0 5,190 1,000 None 7.5/P, 0.06/ft²
10pm March 5 0 221 0 0 44
1,039 0.00 1.95 0 0 44
Zone Peak Totals: 113 0 5,190 1,000
Total Zones: 1 5 0 221 0 0 44
Unique Zones: 1 1,039 0.00 1.95 0 0 44
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Polideportivo Oficina Antidopping
Hell

Air Handler #2 - Cuarto De Proceso 1 - Total Load Summary


Air Handler Description: Cuarto De Proceso 1 Constant Volume - Sum of Peaks
Sensible Heat Ratio: 0.84 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 10pm in March.
Outdoor Conditions: Clg: 86° DB, 75° WB, 113.39 grains
Indoor Conditions: Clg: 75° DB, 50% RH
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 0 Btuh
Heating Supply Air: 0 / (.999 X 1.08 X 0) = 0 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Zone space sensible gain: 5,190 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 5,190 Btuh
Cooling Supply Air: 5,190 / (.999 X 1.1 X 21) = 221 CFM
Summer Vent Outside Air (20.1% of supply) = 44 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 535 Btuh 44 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 535 Btuh
Total sensible gain on air handling system: 5,725 Btuh
Zone space latent gain: 1,000 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 1,463 Btuh
Total latent gain on air handling system: 2,463 Btuh
Total system sensible and latent gain: 8,188 Btuh

Check Figures
Total Air Handler Supply Air (based on a 21° TD): 221 CFM
Total Air Handler Vent. Air (20.07% of Supply): 44 CFM
Total Conditioned Air Space: 113 Sq.ft
Supply Air Per Unit Area: 1.9528 CFM/Sq.ft
Area Per Cooling Capacity: 165.6 Sq.ft/Ton
Cooling Capacity Per Area: 0.0060 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 0.68 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Polideportivo Oficina Antidopping
Hell

Air Handler #3 - Cuarto De Proceso 2 - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
3 Zona 3 113 0 5,190 1,000 None 7.5/P, 0.06/ft²
10pm March 5 0 221 0 0 44
1,039 0.00 1.95 0 0 44
Zone Peak Totals: 113 0 5,190 1,000
Total Zones: 1 5 0 221 0 0 44
Unique Zones: 1 1,039 0.00 1.95 0 0 44
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Polideportivo Oficina Antidopping
Hell

Air Handler #3 - Cuarto De Proceso 2 - Total Load Summary


Air Handler Description: Cuarto De Proceso 2 Constant Volume - Sum of Peaks
Sensible Heat Ratio: 0.84 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 10pm in March.
Outdoor Conditions: Clg: 86° DB, 75° WB, 113.39 grains
Indoor Conditions: Clg: 75° DB, 50% RH
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 0 Btuh
Heating Supply Air: 0 / (.999 X 1.08 X 0) = 0 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Zone space sensible gain: 5,190 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 5,190 Btuh
Cooling Supply Air: 5,190 / (.999 X 1.1 X 21) = 221 CFM
Summer Vent Outside Air (20.1% of supply) = 44 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 535 Btuh 44 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 535 Btuh
Total sensible gain on air handling system: 5,725 Btuh
Zone space latent gain: 1,000 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 1,463 Btuh
Total latent gain on air handling system: 2,463 Btuh
Total system sensible and latent gain: 8,188 Btuh

Check Figures
Total Air Handler Supply Air (based on a 21° TD): 221 CFM
Total Air Handler Vent. Air (20.07% of Supply): 44 CFM
Total Conditioned Air Space: 113 Sq.ft
Supply Air Per Unit Area: 1.9528 CFM/Sq.ft
Area Per Cooling Capacity: 165.6 Sq.ft/Ton
Cooling Capacity Per Area: 0.0060 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 0.68 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Polideportivo Oficina Antidopping
Hell

Air Handler #4 - Cuarto De Proceso 3 - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
4 Zona 4 113 0 5,190 1,000 None 7.5/P, 0.06/ft²
10pm March 5 0 221 0 0 44
1,039 0.00 1.95 0 0 44
Zone Peak Totals: 113 0 5,190 1,000
Total Zones: 1 5 0 221 0 0 44
Unique Zones: 1 1,039 0.00 1.95 0 0 44
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Polideportivo Oficina Antidopping
Hell

Air Handler #4 - Cuarto De Proceso 3 - Total Load Summary


Air Handler Description: Cuarto De Proceso 3 Constant Volume - Sum of Peaks
Sensible Heat Ratio: 0.84 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 10pm in March.
Outdoor Conditions: Clg: 86° DB, 75° WB, 113.39 grains
Indoor Conditions: Clg: 75° DB, 50% RH
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 0 Btuh
Heating Supply Air: 0 / (.999 X 1.08 X 0) = 0 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Zone space sensible gain: 5,190 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 5,190 Btuh
Cooling Supply Air: 5,190 / (.999 X 1.1 X 21) = 221 CFM
Summer Vent Outside Air (20.1% of supply) = 44 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 535 Btuh 44 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 535 Btuh
Total sensible gain on air handling system: 5,725 Btuh
Zone space latent gain: 1,000 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 1,463 Btuh
Total latent gain on air handling system: 2,463 Btuh
Total system sensible and latent gain: 8,188 Btuh

Check Figures
Total Air Handler Supply Air (based on a 21° TD): 221 CFM
Total Air Handler Vent. Air (20.07% of Supply): 44 CFM
Total Conditioned Air Space: 113 Sq.ft
Supply Air Per Unit Area: 1.9528 CFM/Sq.ft
Area Per Cooling Capacity: 165.6 Sq.ft/Ton
Cooling Capacity Per Area: 0.0060 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 0.68 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Polideportivo Oficina Antidopping
Hell

Air Handler #5 - Cuarto De Proceso 4 - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
5 Zona 5 153 0 6,661 1,000 None 7.5/P, 0.06/ft²
10pm March 5 0 294 0 0 47
1,406 0.00 1.92 0 0 47
Zone Peak Totals: 153 0 6,661 1,000
Total Zones: 1 5 0 294 0 0 47
Unique Zones: 1 1,406 0.00 1.92 0 0 47
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Polideportivo Oficina Antidopping
Hell

Air Handler #5 - Cuarto De Proceso 4 - Total Load Summary


Air Handler Description: Cuarto De Proceso 4 Constant Volume - Sum of Peaks
Sensible Heat Ratio: 0.87 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 10pm in March.
Outdoor Conditions: Clg: 86° DB, 75° WB, 113.39 grains
Indoor Conditions: Clg: 75° DB, 50% RH
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 0 Btuh
Heating Supply Air: 0 / (.999 X 1.08 X 0) = 0 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Zone space sensible gain: 6,661 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 6,661 Btuh
Cooling Supply Air: 6,661 / (.999 X 1.1 X 21) = 294 CFM
Summer Vent Outside Air (15.9% of supply) = 47 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 564 Btuh 47 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 564 Btuh
Total sensible gain on air handling system: 7,225 Btuh
Zone space latent gain: 1,000 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 1,542 Btuh
Total latent gain on air handling system: 2,542 Btuh
Total system sensible and latent gain: 9,767 Btuh

Check Figures
Total Air Handler Supply Air (based on a 21° TD): 294 CFM
Total Air Handler Vent. Air (15.90% of Supply): 47 CFM
Total Conditioned Air Space: 153 Sq.ft
Supply Air Per Unit Area: 1.9215 CFM/Sq.ft
Area Per Cooling Capacity: 187.7 Sq.ft/Ton
Cooling Capacity Per Area: 0.0053 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 0.81 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Polideportivo Oficina Antidopping
Hell

Air Handler #6 - Cuarto De Proceso 5 - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
6 Zona 6 94 0 5,003 1,000 None 7.5/P, 0.06/ft²
10pm March 5 0 211 0 0 43
861 0.00 2.26 0 0 43
Zone Peak Totals: 94 0 5,003 1,000
Total Zones: 1 5 0 211 0 0 43
Unique Zones: 1 861 0.00 2.26 0 0 43
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Polideportivo Oficina Antidopping
Hell

Air Handler #6 - Cuarto De Proceso 5 - Total Load Summary


Air Handler Description: Cuarto De Proceso 5 Constant Volume - Sum of Peaks
Sensible Heat Ratio: 0.83 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 10pm in March.
Outdoor Conditions: Clg: 86° DB, 75° WB, 113.39 grains
Indoor Conditions: Clg: 75° DB, 50% RH
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 0 Btuh
Heating Supply Air: 0 / (.999 X 1.08 X 0) = 0 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Zone space sensible gain: 5,003 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 5,003 Btuh
Cooling Supply Air: 5,003 / (.999 X 1.1 X 22) = 211 CFM
Summer Vent Outside Air (20.4% of supply) = 43 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 521 Btuh 43 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 521 Btuh
Total sensible gain on air handling system: 5,524 Btuh
Zone space latent gain: 1,000 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 1,424 Btuh
Total latent gain on air handling system: 2,424 Btuh
Total system sensible and latent gain: 7,948 Btuh

Check Figures
Total Air Handler Supply Air (based on a 22° TD): 211 CFM
Total Air Handler Vent. Air (20.41% of Supply): 43 CFM
Total Conditioned Air Space: 94 Sq.ft
Supply Air Per Unit Area: 2.2572 CFM/Sq.ft
Area Per Cooling Capacity: 141.3 Sq.ft/Ton
Cooling Capacity Per Area: 0.0071 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 0.66 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Polideportivo Oficina Antidopping
Hell

Air Handler #7 - Recepción - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
7 Zona 7 484 0 20,218 5,400 None 5/P, 0.06/ft²
10pm March 27 0 802 0 0 164
4,455 0.00 1.66 0 0 164
Zone Peak Totals: 484 0 20,218 5,400
Total Zones: 1 27 0 802 0 0 164
Unique Zones: 1 4,455 0.00 1.66 0 0 164
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Polideportivo Oficina Antidopping
Hell

Air Handler #7 - Recepción - Total Load Summary


Air Handler Description: Recepción Constant Volume - Sum of Peaks
Sensible Heat Ratio: 0.79 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 10pm in March.
Outdoor Conditions: Clg: 86° DB, 75° WB, 113.39 grains
Indoor Conditions: Clg: 75° DB, 50% RH
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 0 Btuh
Heating Supply Air: 0 / (.999 X 1.08 X 0) = 0 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Zone space sensible gain: 20,218 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 20,218 Btuh
Cooling Supply Air: 20,218 / (.999 X 1.1 X 23) = 802 CFM
Summer Vent Outside Air (20.5% of supply) = 164 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 1,982 Btuh 164 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 1,982 Btuh
Total sensible gain on air handling system: 22,200 Btuh
Zone space latent gain: 5,400 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 5,420 Btuh
Total latent gain on air handling system: 10,820 Btuh
Total system sensible and latent gain: 33,020 Btuh

Check Figures
Total Air Handler Supply Air (based on a 23° TD): 802 CFM
Total Air Handler Vent. Air (20.46% of Supply): 164 CFM
Total Conditioned Air Space: 484 Sq.ft
Supply Air Per Unit Area: 1.6561 CFM/Sq.ft
Area Per Cooling Capacity: 176.0 Sq.ft/Ton
Cooling Capacity Per Area: 0.0057 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 2.75 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Polideportivo Oficina Antidopping
Hell

Air Handler #8 - Oficina De Manager - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
8 Zona 8 87 0 4,803 1,000 None Direct
10pm March 5 0 201 0 0 40
802 0.00 2.31 0 0 40
Zone Peak Totals: 87 0 4,803 1,000
Total Zones: 1 5 0 201 0 0 40
Unique Zones: 1 802 0.00 2.31 0 0 40
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Polideportivo Oficina Antidopping
Hell

Air Handler #8 - Oficina De Manager - Total Load Summary


Air Handler Description: Oficina De Manager Constant Volume - Sum of Peaks
Sensible Heat Ratio: 0.83 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 10pm in March.
Outdoor Conditions: Clg: 86° DB, 75° WB, 113.39 grains
Indoor Conditions: Clg: 75° DB, 50% RH
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 0 Btuh
Heating Supply Air: 0 / (.999 X 1.08 X 0) = 0 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Zone space sensible gain: 4,803 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 4,803 Btuh
Cooling Supply Air: 4,803 / (.999 X 1.1 X 22) = 201 CFM
Summer Vent Outside Air (19.9% of supply) = 40 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 483 Btuh 40 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 483 Btuh
Total sensible gain on air handling system: 5,286 Btuh
Zone space latent gain: 1,000 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 1,322 Btuh
Total latent gain on air handling system: 2,322 Btuh
Total system sensible and latent gain: 7,608 Btuh

Check Figures
Total Air Handler Supply Air (based on a 22° TD): 201 CFM
Total Air Handler Vent. Air (19.87% of Supply): 40 CFM
Total Conditioned Air Space: 87 Sq.ft
Supply Air Per Unit Area: 2.3102 CFM/Sq.ft
Area Per Cooling Capacity: 137.5 Sq.ft/Ton
Cooling Capacity Per Area: 0.0073 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 0.63 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Polideportivo Oficina Antidopping
Hell

Zone Detailed Loads (At Zone Peak Times)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Zone 1-Zona 1 peaks (sensible) in January at 10pm, Air Handler 1 (Area De Preparación), Group 0, 53.0 x
10.8, Construction Type: 1 (Light)
Wall-2-SSE-A-D 382 1 25.0 0.420 4,007 7.140 2,725
Wall-3-ENE-A-D 137 1 24.5 0.420 1,408 7.140 977
Partition-1-1 570.28 10/0 0.270 1,540 0.000 0
Partition-4-1 531 10/0 0.270 1,434 0.000 0
Lights-Prof=0 1,329 1.000 4,534
Equipment-Prof=0 1,500 1.000 5,118 0
People-Prof=0 12.0 1.000 3,000 2,400
Sub-total 21,040 2,400 0
Safety factors: +15% +15% +0%
--------- --------- ---------
Total w/ safety factors: 24,196 2,760 0

Zone 2-Zona 2 peaks (sensible) in March at 10pm, Air Handler 2 (Cuarto De Proceso 1), Group 0, 10.5 x
10.8, Construction Type: 1 (Light)
Partition-1-1 112.98 10/0 0.270 305 0.000 0
Partition-2-1 381.6 10/0 0.270 1,030 0.000 0
Lights-Prof=0 263 1.000 898
Equipment-Prof=0 500 1.000 1,706 0
People-Prof=0 5.0 1.000 1,250 1,000
Sub-total 5,190 1,000 0
Safety factors: +0% +0% +0%
--------- --------- ---------
Total w/ safety factors: 5,190 1,000 0

Zone 3-Zona 3 peaks (sensible) in March at 10pm, Air Handler 3 (Cuarto De Proceso 2), Group 0, 10.5 x
10.8, Construction Type: 1 (Light)
Partition-1-1 112.98 10/0 0.270 305 0.000 0
Partition-2-1 381.6 10/0 0.270 1,030 0.000 0
Lights-Prof=0 263 1.000 898
Equipment-Prof=0 500 1.000 1,706 0
People-Prof=0 5.0 1.000 1,250 1,000
Sub-total 5,190 1,000 0
Safety factors: +0% +0% +0%
--------- --------- ---------
Total w/ safety factors: 5,190 1,000 0

Zone 4-Zona 4 peaks (sensible) in March at 10pm, Air Handler 4 (Cuarto De Proceso 3), Group 0, 10.5 x
10.8, Construction Type: 1 (Light)
Partition-1-1 112.98 10/0 0.270 305 0.000 0
Partition-2-1 381.6 10/0 0.270 1,030 0.000 0
Lights-Prof=0 263 1.000 898
Equipment-Prof=0 500 1.000 1,706 0
People-Prof=0 5.0 1.000 1,250 1,000
Sub-total 5,190 1,000 0
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Polideportivo Oficina Antidopping
Hell

Zone Detailed Loads (At Zone Peak Times) (cont'd)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Safety factors: +0% +0% +0%
--------- --------- ---------
Total w/ safety factors: 5,190 1,000 0

Zone 5-Zona 5 peaks (sensible) in March at 10pm, Air Handler 5 (Cuarto De Proceso 4), Group 0, 14.2 x
10.8, Construction Type: 1 (Light)
Partition-1-1 152.792 10/0 0.270 413 0.000 0
Partition-2-1 453.6 10/0 0.270 1,225 0.000 0
Lights-Prof=0 356 1.000 1,215
Equipment-Prof=0 750 1.000 2,559 0
People-Prof=0 5.0 1.000 1,250 1,000
Sub-total 6,661 1,000 0
Safety factors: +0% +0% +0%
--------- --------- ---------
Total w/ safety factors: 6,661 1,000 0

Zone 6-Zona 6 peaks (sensible) in March at 10pm, Air Handler 6 (Cuarto De Proceso 5), Group 0, 8.7 x
10.8, Construction Type: 1 (Light)
Partition-1-1 93.612 10/0 0.270 253 0.000 0
Partition-2-1 388.8 10/0 0.270 1,050 0.000 0
Lights-Prof=0 218 1.000 744
Equipment-Prof=0 500 1.000 1,706 0
People-Prof=0 5.0 1.000 1,250 1,000
Sub-total 5,003 1,000 0
Safety factors: +0% +0% +0%
--------- --------- ---------
Total w/ safety factors: 5,003 1,000 0

Zone 7-Zona 7 peaks (sensible) in March at 10pm, Air Handler 7 (Recepción), Group 0, 45.0 x 10.8,
Construction Type: 1 (Light)
Partition-1-1 484.2 10/0 0.270 1,307 0.000 0
Partition-2-1 1182.6 10/0 0.270 3,193 0.000 0
Lights-Prof=0 1,128 1.000 3,850
Equipment-Prof=0 1,500 1.000 5,118 0
People-Prof=0 27.0 1.000 6,750 5,400
Sub-total 20,218 5,400 0
Safety factors: +0% +0% +0%
--------- --------- ---------
Total w/ safety factors: 20,218 5,400 0

Zone 8-Zona 8 peaks (sensible) in March at 10pm, Air Handler 8 (Oficina De Manager), Group 0, 8.1 x
10.8, Construction Type: 1 (Light)
Partition-1-1 87.15601 10/0 0.270 235 0.000 0
Partition-2-1 340.2 10/0 0.270 919 0.000 0
Lights-Prof=0 203 1.000 693
Equipment-Prof=0 500 1.000 1,706 0
People-Prof=0 5.0 1.000 1,250 1,000
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Polideportivo Oficina Antidopping
Hell

Zone Detailed Loads (At Zone Peak Times) (cont'd)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Sub-total 4,803 1,000 0
Safety factors: +0% +0% +0%
--------- --------- ---------
Total w/ safety factors: 4,803 1,000 0
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Polideportivo Oficina Antidopping
Hell

Air System #1 (Area De Preparación) Psychrometric Analysis


System Load Analysis Latent Grains Sensible Temp CFM
Leaving Coil Condition 61.030 54.930
Draw-Thru Fan 0 0.000 0
Misc Load on Supply Side 0 0.000 0
Supply Air Duct 0 0.000 0
Zone Loads 2,760 3.703 24,196 20.070 1,098
Sensible Reserve 0 0.000 0
Zone Condition 2,760 64.733 24,196 75.000 1,098
Return Air Duct 0 0.000
Return Air Plenum 0 0.000
Misc Load on Return Side 0 0.000
Vent Air 124 CFM 4,104 5.507 1,501 1.245
Blow-Thru Fan 0 0.000
Entering Coil Condition 6,864 70.240 25,697 76.245 1,098

General Psychrometric Equations Used In Analysis:


PR = (Barometric pressure of site / Standard ASHRAE pressure of 29.921)
TSH = PR x 1.10 x CFM x (DB entering - DB leaving)
TLH = PR x 0.68 x CFM x (Grains entering - Grains leaving)
GTH = PR x 4.50 x CFM x (Enthalpy entering - Enthalpy leaving)

TSH = 0.999 x 1.10 x 1,098 x( 76.245 - 54.930 )= 25,697 Btuh


TLH = 0.999 x 0.68 x 1,098 x( 70.240 - 61.030 )= 6,864 Btuh
----------
SUM = 32,561 Btuh
GTH = 0.999 x 4.50 x 1,098 x( 29.287 - 22.648 )= 32,743 Btuh
Total System Load = 32,561 Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM = 32,743 / ( 10.00 x 500 ) = 6.5 GPM
Heating GPM = 0 /( 20.00 x 500 ) = 0.0 GPM
Steam Req. = 0 / 970 = 0.0 lb./hr

Entering Cooling Coil Conditions Entering Heating Coil Conditions


Dry bulb temperature: 76.24 Dry bulb temperature: 75.00
Wet bulb temperature: 64.13
Relative humidity: 51.98
Enthalpy: 29.29 Btu/lbm

Leaving Cooling Coil Conditions Leaving Heating Coil Conditions


Dry bulb temperature: 54.93 Dry bulb temperature: 75.00
Wet bulb temperature: 54.11
Relative humidity: 95.00
Enthalpy: 22.65 Btu/lbm
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Polideportivo Oficina Antidopping
Hell

Air System #2 (Cuarto De Proceso 1) Psychrometric Analysis


System Load Analysis Latent Grains Sensible Temp CFM
Leaving Coil Condition 58.062 53.584
Draw-Thru Fan 0 0.000 0
Misc Load on Supply Side 0 0.000 0
Supply Air Duct 0 0.000 0
Zone Loads 1,000 6.675 5,190 21.416 221
Sensible Reserve 0 0.000 0
Zone Condition 1,000 64.738 5,190 75.000 221
Return Air Duct 0 0.000
Return Air Plenum 0 0.000
Misc Load on Return Side 0 0.000
Vent Air 44 CFM 1,463 9.765 535 2.208
Blow-Thru Fan 0 0.000
Entering Coil Condition 2,463 74.503 5,725 77.208 221

General Psychrometric Equations Used In Analysis:


PR = (Barometric pressure of site / Standard ASHRAE pressure of 29.921)
TSH = PR x 1.10 x CFM x (DB entering - DB leaving)
TLH = PR x 0.68 x CFM x (Grains entering - Grains leaving)
GTH = PR x 4.50 x CFM x (Enthalpy entering - Enthalpy leaving)

TSH = 0.999 x 1.10 x 221 x( 77.208 - 53.584 )= 5,725 Btuh


TLH = 0.999 x 0.68 x 221 x( 74.503 - 58.062 )= 2,463 Btuh
----------
SUM = 8,187 Btuh
GTH = 0.999 x 4.50 x 221 x( 30.189 - 21.860 )= 8,257 Btuh
Total System Load = 8,188 Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM = 8,257 / ( 10.00 x 500 ) = 1.7 GPM
Heating GPM = 0 /( 20.00 x 500 ) = 0.0 GPM
Steam Req. = 0 / 970 = 0.0 lb./hr

Entering Cooling Coil Conditions Entering Heating Coil Conditions


Dry bulb temperature: 77.21 Dry bulb temperature: 75.00
Wet bulb temperature: 65.33
Relative humidity: 53.36
Enthalpy: 30.19 Btu/lbm

Leaving Cooling Coil Conditions Leaving Heating Coil Conditions


Dry bulb temperature: 53.58 Dry bulb temperature: 75.00
Wet bulb temperature: 52.78
Relative humidity: 95.00
Enthalpy: 21.86 Btu/lbm
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Polideportivo Oficina Antidopping
Hell

Air System #3 (Cuarto De Proceso 2) Psychrometric Analysis


System Load Analysis Latent Grains Sensible Temp CFM
Leaving Coil Condition 58.062 53.584
Draw-Thru Fan 0 0.000 0
Misc Load on Supply Side 0 0.000 0
Supply Air Duct 0 0.000 0
Zone Loads 1,000 6.675 5,190 21.416 221
Sensible Reserve 0 0.000 0
Zone Condition 1,000 64.738 5,190 75.000 221
Return Air Duct 0 0.000
Return Air Plenum 0 0.000
Misc Load on Return Side 0 0.000
Vent Air 44 CFM 1,463 9.765 535 2.208
Blow-Thru Fan 0 0.000
Entering Coil Condition 2,463 74.503 5,725 77.208 221

General Psychrometric Equations Used In Analysis:


PR = (Barometric pressure of site / Standard ASHRAE pressure of 29.921)
TSH = PR x 1.10 x CFM x (DB entering - DB leaving)
TLH = PR x 0.68 x CFM x (Grains entering - Grains leaving)
GTH = PR x 4.50 x CFM x (Enthalpy entering - Enthalpy leaving)

TSH = 0.999 x 1.10 x 221 x( 77.208 - 53.584 )= 5,725 Btuh


TLH = 0.999 x 0.68 x 221 x( 74.503 - 58.062 )= 2,463 Btuh
----------
SUM = 8,187 Btuh
GTH = 0.999 x 4.50 x 221 x( 30.189 - 21.860 )= 8,257 Btuh
Total System Load = 8,188 Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM = 8,257 / ( 10.00 x 500 ) = 1.7 GPM
Heating GPM = 0 /( 20.00 x 500 ) = 0.0 GPM
Steam Req. = 0 / 970 = 0.0 lb./hr

Entering Cooling Coil Conditions Entering Heating Coil Conditions


Dry bulb temperature: 77.21 Dry bulb temperature: 75.00
Wet bulb temperature: 65.33
Relative humidity: 53.36
Enthalpy: 30.19 Btu/lbm

Leaving Cooling Coil Conditions Leaving Heating Coil Conditions


Dry bulb temperature: 53.58 Dry bulb temperature: 75.00
Wet bulb temperature: 52.78
Relative humidity: 95.00
Enthalpy: 21.86 Btu/lbm
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Polideportivo Oficina Antidopping
Hell

Air System #4 (Cuarto De Proceso 3) Psychrometric Analysis


System Load Analysis Latent Grains Sensible Temp CFM
Leaving Coil Condition 58.062 53.584
Draw-Thru Fan 0 0.000 0
Misc Load on Supply Side 0 0.000 0
Supply Air Duct 0 0.000 0
Zone Loads 1,000 6.675 5,190 21.416 221
Sensible Reserve 0 0.000 0
Zone Condition 1,000 64.738 5,190 75.000 221
Return Air Duct 0 0.000
Return Air Plenum 0 0.000
Misc Load on Return Side 0 0.000
Vent Air 44 CFM 1,463 9.765 535 2.208
Blow-Thru Fan 0 0.000
Entering Coil Condition 2,463 74.503 5,725 77.208 221

General Psychrometric Equations Used In Analysis:


PR = (Barometric pressure of site / Standard ASHRAE pressure of 29.921)
TSH = PR x 1.10 x CFM x (DB entering - DB leaving)
TLH = PR x 0.68 x CFM x (Grains entering - Grains leaving)
GTH = PR x 4.50 x CFM x (Enthalpy entering - Enthalpy leaving)

TSH = 0.999 x 1.10 x 221 x( 77.208 - 53.584 )= 5,725 Btuh


TLH = 0.999 x 0.68 x 221 x( 74.503 - 58.062 )= 2,463 Btuh
----------
SUM = 8,187 Btuh
GTH = 0.999 x 4.50 x 221 x( 30.189 - 21.860 )= 8,257 Btuh
Total System Load = 8,188 Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM = 8,257 / ( 10.00 x 500 ) = 1.7 GPM
Heating GPM = 0 /( 20.00 x 500 ) = 0.0 GPM
Steam Req. = 0 / 970 = 0.0 lb./hr

Entering Cooling Coil Conditions Entering Heating Coil Conditions


Dry bulb temperature: 77.21 Dry bulb temperature: 75.00
Wet bulb temperature: 65.33
Relative humidity: 53.36
Enthalpy: 30.19 Btu/lbm

Leaving Cooling Coil Conditions Leaving Heating Coil Conditions


Dry bulb temperature: 53.58 Dry bulb temperature: 75.00
Wet bulb temperature: 52.78
Relative humidity: 95.00
Enthalpy: 21.86 Btu/lbm
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Polideportivo Oficina Antidopping
Hell

Air System #5 (Cuarto De Proceso 4) Psychrometric Analysis


System Load Analysis Latent Grains Sensible Temp CFM
Leaving Coil Condition 59.720 54.343
Draw-Thru Fan 0 0.000 0
Misc Load on Supply Side 0 0.000 0
Supply Air Duct 0 0.000 0
Zone Loads 1,000 5.016 6,661 20.657 294
Sensible Reserve 0 0.000 0
Zone Condition 1,000 64.736 6,661 75.000 294
Return Air Duct 0 0.000
Return Air Plenum 0 0.000
Misc Load on Return Side 0 0.000
Vent Air 47 CFM 1,542 7.734 564 1.749
Blow-Thru Fan 0 0.000
Entering Coil Condition 2,542 72.471 7,225 76.749 294

General Psychrometric Equations Used In Analysis:


PR = (Barometric pressure of site / Standard ASHRAE pressure of 29.921)
TSH = PR x 1.10 x CFM x (DB entering - DB leaving)
TLH = PR x 0.68 x CFM x (Grains entering - Grains leaving)
GTH = PR x 4.50 x CFM x (Enthalpy entering - Enthalpy leaving)

TSH = 0.999 x 1.10 x 294 x( 76.749 - 54.343 )= 7,225 Btuh


TLH = 0.999 x 0.68 x 294 x( 72.471 - 59.720 )= 2,542 Btuh
----------
SUM = 9,767 Btuh
GTH = 0.999 x 4.50 x 294 x( 29.759 - 22.302 )= 9,837 Btuh
Total System Load = 9,767 Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM = 9,837 / ( 10.00 x 500 ) = 2.0 GPM
Heating GPM = 0 /( 20.00 x 500 ) = 0.0 GPM
Steam Req. = 0 / 970 = 0.0 lb./hr

Entering Cooling Coil Conditions Entering Heating Coil Conditions


Dry bulb temperature: 76.75 Dry bulb temperature: 75.00
Wet bulb temperature: 64.76
Relative humidity: 52.71
Enthalpy: 29.76 Btu/lbm

Leaving Cooling Coil Conditions Leaving Heating Coil Conditions


Dry bulb temperature: 54.34 Dry bulb temperature: 75.00
Wet bulb temperature: 53.52
Relative humidity: 95.00
Enthalpy: 22.30 Btu/lbm
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Polideportivo Oficina Antidopping
Hell

Air System #6 (Cuarto De Proceso 5) Psychrometric Analysis


System Load Analysis Latent Grains Sensible Temp CFM
Leaving Coil Condition 57.761 53.444
Draw-Thru Fan 0 0.000 0
Misc Load on Supply Side 0 0.000 0
Supply Air Duct 0 0.000 0
Zone Loads 1,000 6.970 5,003 21.556 211
Sensible Reserve 0 0.000 0
Zone Condition 1,000 64.731 5,003 75.000 211
Return Air Duct 0 0.000
Return Air Plenum 0 0.000
Misc Load on Return Side 0 0.000
Vent Air 43 CFM 1,424 9.930 521 2.245
Blow-Thru Fan 0 0.000
Entering Coil Condition 2,424 74.661 5,524 77.245 211

General Psychrometric Equations Used In Analysis:


PR = (Barometric pressure of site / Standard ASHRAE pressure of 29.921)
TSH = PR x 1.10 x CFM x (DB entering - DB leaving)
TLH = PR x 0.68 x CFM x (Grains entering - Grains leaving)
GTH = PR x 4.50 x CFM x (Enthalpy entering - Enthalpy leaving)

TSH = 0.999 x 1.10 x 211 x( 77.245 - 53.444 )= 5,524 Btuh


TLH = 0.999 x 0.68 x 211 x( 74.661 - 57.761 )= 2,425 Btuh
----------
SUM = 7,948 Btuh
GTH = 0.999 x 4.50 x 211 x( 30.223 - 21.779 )= 8,017 Btuh
Total System Load = 7,948 Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM = 8,017 / ( 10.00 x 500 ) = 1.6 GPM
Heating GPM = 0 /( 20.00 x 500 ) = 0.0 GPM
Steam Req. = 0 / 970 = 0.0 lb./hr

Entering Cooling Coil Conditions Entering Heating Coil Conditions


Dry bulb temperature: 77.24 Dry bulb temperature: 75.00
Wet bulb temperature: 65.37
Relative humidity: 53.39
Enthalpy: 30.22 Btu/lbm

Leaving Cooling Coil Conditions Leaving Heating Coil Conditions


Dry bulb temperature: 53.44 Dry bulb temperature: 75.00
Wet bulb temperature: 52.64
Relative humidity: 95.00
Enthalpy: 21.78 Btu/lbm
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Polideportivo Oficina Antidopping
Hell

Air System #7 (Recepción) Psychrometric Analysis


System Load Analysis Latent Grains Sensible Temp CFM
Leaving Coil Condition 54.827 52.045
Draw-Thru Fan 0 0.000 0
Misc Load on Supply Side 0 0.000 0
Supply Air Duct 0 0.000 0
Zone Loads 5,400 9.918 20,218 22.955 802
Sensible Reserve 0 0.000 0
Zone Condition 5,400 64.745 20,218 75.000 802
Return Air Duct 0 0.000
Return Air Plenum 0 0.000
Misc Load on Return Side 0 0.000
Vent Air 164 CFM 5,420 9.953 1,982 2.250
Blow-Thru Fan 0 0.000
Entering Coil Condition 10,820 74.698 22,200 77.250 802

General Psychrometric Equations Used In Analysis:


PR = (Barometric pressure of site / Standard ASHRAE pressure of 29.921)
TSH = PR x 1.10 x CFM x (DB entering - DB leaving)
TLH = PR x 0.68 x CFM x (Grains entering - Grains leaving)
GTH = PR x 4.50 x CFM x (Enthalpy entering - Enthalpy leaving)

TSH = 0.999 x 1.10 x 802 x( 77.250 - 52.045 )= 22,200 Btuh


TLH = 0.999 x 0.68 x 802 x( 74.698 - 54.827 )= 10,819 Btuh
----------
SUM = 33,019 Btuh
GTH = 0.999 x 4.50 x 802 x( 30.230 - 20.983 )= 33,317 Btuh
Total System Load = 33,020 Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM = 33,317 / ( 10.00 x 500 ) = 6.7 GPM
Heating GPM = 0 /( 20.00 x 500 ) = 0.0 GPM
Steam Req. = 0 / 970 = 0.0 lb./hr

Entering Cooling Coil Conditions Entering Heating Coil Conditions


Dry bulb temperature: 77.25 Dry bulb temperature: 75.00
Wet bulb temperature: 65.38
Relative humidity: 53.41
Enthalpy: 30.23 Btu/lbm

Leaving Cooling Coil Conditions Leaving Heating Coil Conditions


Dry bulb temperature: 52.04 Dry bulb temperature: 75.00
Wet bulb temperature: 51.26
Relative humidity: 95.00
Enthalpy: 20.98 Btu/lbm
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Polideportivo Oficina Antidopping
Hell

Air System #8 (Oficina De Manager) Psychrometric Analysis


System Load Analysis Latent Grains Sensible Temp CFM
Leaving Coil Condition 57.416 53.283
Draw-Thru Fan 0 0.000 0
Misc Load on Supply Side 0 0.000 0
Supply Air Duct 0 0.000 0
Zone Loads 1,000 7.315 4,803 21.717 201
Sensible Reserve 0 0.000 0
Zone Condition 1,000 64.731 4,803 75.000 201
Return Air Duct 0 0.000
Return Air Plenum 0 0.000
Misc Load on Return Side 0 0.000
Vent Air 40 CFM 1,322 9.667 483 2.185
Blow-Thru Fan 0 0.000
Entering Coil Condition 2,322 74.398 5,286 77.185 201

General Psychrometric Equations Used In Analysis:


PR = (Barometric pressure of site / Standard ASHRAE pressure of 29.921)
TSH = PR x 1.10 x CFM x (DB entering - DB leaving)
TLH = PR x 0.68 x CFM x (Grains entering - Grains leaving)
GTH = PR x 4.50 x CFM x (Enthalpy entering - Enthalpy leaving)

TSH = 0.999 x 1.10 x 201 x( 77.185 - 53.283 )= 5,286 Btuh


TLH = 0.999 x 0.68 x 201 x( 74.398 - 57.416 )= 2,322 Btuh
----------
SUM = 7,608 Btuh
GTH = 0.999 x 4.50 x 201 x( 30.167 - 21.686 )= 7,673 Btuh
Total System Load = 7,608 Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM = 7,673 / ( 10.00 x 500 ) = 1.5 GPM
Heating GPM = 0 /( 20.00 x 500 ) = 0.0 GPM
Steam Req. = 0 / 970 = 0.0 lb./hr

Entering Cooling Coil Conditions Entering Heating Coil Conditions


Dry bulb temperature: 77.19 Dry bulb temperature: 75.00
Wet bulb temperature: 65.30
Relative humidity: 53.31
Enthalpy: 30.17 Btu/lbm

Leaving Cooling Coil Conditions Leaving Heating Coil Conditions


Dry bulb temperature: 53.28 Dry bulb temperature: 75.00
Wet bulb temperature: 52.48
Relative humidity: 95.00
Enthalpy: 21.69 Btu/lbm
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Polideportivo Oficina Antidopping
Hell

Air System #1 (Area De Preparación) Psychrometric Chart


ZC Zone Condition OC Outdoor Condition
LC Leaving Coil Condition EC Entering Coil Condition
SD Supply Duct Temperature Rise RD Return Duct Temperature Rise
DTF Draw Through Fan Sensible Gain BTF Blow Through Fan Sensible Gain
RE Reserve or Reheat Sensible Gain PL Return Air Plenum Sensible Gain
SM Supply Side Miscellaneous Sensible Gain RM Return Side Miscellaneous Gain
PRE Pretreated Air Condition HRV Heat Recovery Ventilator Condition
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Polideportivo Oficina Antidopping
Hell

Air System #2 (Cuarto De Proceso 1) Psychrometric Chart


ZC Zone Condition OC Outdoor Condition
LC Leaving Coil Condition EC Entering Coil Condition
SD Supply Duct Temperature Rise RD Return Duct Temperature Rise
DTF Draw Through Fan Sensible Gain BTF Blow Through Fan Sensible Gain
RE Reserve or Reheat Sensible Gain PL Return Air Plenum Sensible Gain
SM Supply Side Miscellaneous Sensible Gain RM Return Side Miscellaneous Gain
PRE Pretreated Air Condition HRV Heat Recovery Ventilator Condition
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Polideportivo Oficina Antidopping
Hell

Air System #3 (Cuarto De Proceso 2) Psychrometric Chart


ZC Zone Condition OC Outdoor Condition
LC Leaving Coil Condition EC Entering Coil Condition
SD Supply Duct Temperature Rise RD Return Duct Temperature Rise
DTF Draw Through Fan Sensible Gain BTF Blow Through Fan Sensible Gain
RE Reserve or Reheat Sensible Gain PL Return Air Plenum Sensible Gain
SM Supply Side Miscellaneous Sensible Gain RM Return Side Miscellaneous Gain
PRE Pretreated Air Condition HRV Heat Recovery Ventilator Condition
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Polideportivo Oficina Antidopping
Hell

Air System #4 (Cuarto De Proceso 3) Psychrometric Chart


ZC Zone Condition OC Outdoor Condition
LC Leaving Coil Condition EC Entering Coil Condition
SD Supply Duct Temperature Rise RD Return Duct Temperature Rise
DTF Draw Through Fan Sensible Gain BTF Blow Through Fan Sensible Gain
RE Reserve or Reheat Sensible Gain PL Return Air Plenum Sensible Gain
SM Supply Side Miscellaneous Sensible Gain RM Return Side Miscellaneous Gain
PRE Pretreated Air Condition HRV Heat Recovery Ventilator Condition
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Polideportivo Oficina Antidopping
Hell

Air System #5 (Cuarto De Proceso 4) Psychrometric Chart


ZC Zone Condition OC Outdoor Condition
LC Leaving Coil Condition EC Entering Coil Condition
SD Supply Duct Temperature Rise RD Return Duct Temperature Rise
DTF Draw Through Fan Sensible Gain BTF Blow Through Fan Sensible Gain
RE Reserve or Reheat Sensible Gain PL Return Air Plenum Sensible Gain
SM Supply Side Miscellaneous Sensible Gain RM Return Side Miscellaneous Gain
PRE Pretreated Air Condition HRV Heat Recovery Ventilator Condition
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Polideportivo Oficina Antidopping
Hell

Air System #6 (Cuarto De Proceso 5) Psychrometric Chart


ZC Zone Condition OC Outdoor Condition
LC Leaving Coil Condition EC Entering Coil Condition
SD Supply Duct Temperature Rise RD Return Duct Temperature Rise
DTF Draw Through Fan Sensible Gain BTF Blow Through Fan Sensible Gain
RE Reserve or Reheat Sensible Gain PL Return Air Plenum Sensible Gain
SM Supply Side Miscellaneous Sensible Gain RM Return Side Miscellaneous Gain
PRE Pretreated Air Condition HRV Heat Recovery Ventilator Condition
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Polideportivo Oficina Antidopping
Hell

Air System #7 (Recepción) Psychrometric Chart


ZC Zone Condition OC Outdoor Condition
LC Leaving Coil Condition EC Entering Coil Condition
SD Supply Duct Temperature Rise RD Return Duct Temperature Rise
DTF Draw Through Fan Sensible Gain BTF Blow Through Fan Sensible Gain
RE Reserve or Reheat Sensible Gain PL Return Air Plenum Sensible Gain
SM Supply Side Miscellaneous Sensible Gain RM Return Side Miscellaneous Gain
PRE Pretreated Air Condition HRV Heat Recovery Ventilator Condition
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Polideportivo Oficina Antidopping
Hell

Air System #8 (Oficina De Manager) Psychrometric Chart


ZC Zone Condition OC Outdoor Condition
LC Leaving Coil Condition EC Entering Coil Condition
SD Supply Duct Temperature Rise RD Return Duct Temperature Rise
DTF Draw Through Fan Sensible Gain BTF Blow Through Fan Sensible Gain
RE Reserve or Reheat Sensible Gain PL Return Air Plenum Sensible Gain
SM Supply Side Miscellaneous Sensible Gain RM Return Side Miscellaneous Gain
PRE Pretreated Air Condition HRV Heat Recovery Ventilator Condition