You are on page 1of 3

THE ISRAEL ELECTRIC CORPORATION LTD

ENGINEERING DIVISION SPEC: STR-1377


SUBSTATION PLANNING SECTOR Appendix № 1
REQUIRED TESTS FOR COUPLING EQUIPMENT

№ Test denomination Standard Sub Value


clause
Type & Routine tests for
1 IEC 60353 19
line-traps

1.1 Temperature rise test (Type test) IEC 60353 19.1

Measurement of radio influence


1.2 IEC 60353 19.2
voltage (Type test)

1.3 Insulation test (Type test) IEC 60353 19.3

1.4 Short time current tests (Type test) IEC 60353 19.4

Measurement of the rated inductance


1.5 of the main coil (Type & Routine IEC 60353 19.5
tests)

Measurement of power frequency


1.6 inductance of the main coil (Type & IEC 60353 19.6
Routine tests)

Measurement of blocking resistance


1.7 and blocking impedance (Type & IEC 60353 19.7
Routine tests)

Measurement of tapping loss and


1.8 tapping loss based on the blocking IEC 60353 19.8
resistance (Type & Routine tests)

Page 1 of 3
THE ISRAEL ELECTRIC CORPORATION LTD
ENGINEERING DIVISION SPEC: STR-1377
SUBSTATION PLANNING SECTOR Appendix № 1
REQUIRED TESTS FOR COUPLING EQUIPMENT
(CONT.)
№ Test denomination Standard Sub Value
clause
IEC 60358-1
2 Tests for capacitors IEC 60358-2
9-11

IEC 60358-1
2.1 Type tests 10
IEC 60358-2

2.1.1 Impulse tests IEC 60358-1 10.1

2.1.2 Wet test IEC 60358-1 10.2

2.1.3 Radio interference voltage (RIV) tests IEC 60358-1 10.3

Polarity reversal test for d.c.


2.1.4 IEC 60358-1 10.4
equipment

High frequency capacitance and


2.1.5 IEC 60358-2 10.200.1
equivalent series resistance

Measurement of the stray


2.1.6 capacitance and stray conductance of IEC 60358-2 10.200.2
the low voltage terminal

Page 2 of 3
THE ISRAEL ELECTRIC CORPORATION LTD
ENGINEERING DIVISION SPEC: STR-1377
SUBSTATION PLANNING SECTOR Appendix № 1
REQUIRED TESTS FOR COUPLING EQUIPMENT
(CONT.)
№ Test denomination Standard Sub Value
clause
2.2 Routine tests IEC 60358-1 9

2.2.1 Tightness of equipment IEC 60358-1 9.1

Capacitance and tan δ measurement


2.2.2 IEC 60358-1 9.2.2
at power-frequency

Power-frequency or d.c. withstand


2.2.3 IEC 60358-1 9.2.3
test

2.3.4 Measurement of partial discharges IEC 60358-1 9.2.4

Resistance measurement for d.c.


2.2.5 IEC 60358-1 9.2.6
equipment

2.3 Special tests IEC 60358-1 11

2.3.1 Mechanical strength test IEC 60358-1 11

3 Other tests

The offered LT and CC shall be


analyzed to prove the seismic design IEEE Std Moderate
3.1
The equipment shall be qualified 693 Level
according to…………………………

After performing the analysis the


Contractor shall submit for approval IEEE Std
3.2 the calculation that demonstrate the 693
A.1.4
anchorage requirements according to 0.3
………..

Page 3 of 3