CLIENT : CONSULTANT :
Municipal Corporation Singrauli Egis
prior permission writing
Contractor: KK Spun India Limited
PROJECT: 11` MLD Seawage Treatment Plant at Singrauli
JOB No. TOTAL NO. OF PAGES 2 TITLE : NAME SIGN DATE DSGN AD CHKD AB CAPACITOR SIZE CALCULATIONS APPD Contractor's Consultants CODE REV. DOCUMENT No. KKSIL/SINIGURALI/STP-11/3A/E03 R0 Unique Consultants
RELEASED FOR P PRELIMINARY TENDER INFORMATION APPROVAL CONSTRUCTION
: DOCUMENT NO REV DATE PROJECT 11 MLD STP AT SINGURALI KKSIL/SINGURALI/STP-11/E-03 R0 04/11/2018 : PREPARED CHECKED APPROVED SHEET TITLE Capacitor Size Calculations AD AB
1 Total load on transformer in kW = 484.04 kW
2 Total load on transformer in kVA = 408.60 KVA
3 System power factor (Cos Ø1 = kW/kVA)) = 0.80
4 Reactive power absorbed (kVA x sin Ø1) = 245.16 KVAr1
5 Improved power factor (Cos Ø2) = 0.98
6 Reactive power at improved power factor (kW x tan Ø2) = 98.29 KVAr2
7 Capacitor bank required (KVAr1-kVAr2) = 146.87 kVAr