ESAA300-CAA03 Power System
Main features
System capacity: -54Vdc / 300A Max.
AC Input: Three phases
- 380Vac, Three phases 5 wires (R, S, T, N, FG)
Operating temperature range (ambient): 0 ~ +55 degree C
DC distribution: MCB breaker (DIN rail )
-NPL breaker: 63A X 3
-PL breaker: 63A X 1, 16A X 7, extra space for C60
breaker
Battery breaker: 125A x 3 (DIN rail )
LVDS for battery and LPLD : 250A x 2
Rectifier slots: 6 max. could be for 2.9KW module
Controller: CSU 502 CANBUS
Alarm relay: 6 positions
Outline Dim.: (H*W*D): 274 x 435 x 345mm
Delta Confidential
3
ESAA300-CAA03 Power System
Delta Confidential
4
ESAA300-CAA03 Power System
0V Busbar
M4 x 0.7
screw x 17
M6 x 1
screw x 7
0V Bus bar
Delta Confidential
5
Rectifier
1. OK (Green) :
ON: operating
OFF: No AC or rectifier shut down
Blinking: Rectifier standby mode or AC out of range
2. N.L (Yellow) :
ON: Output < 5%
OFF: Output > 5%
Blinking: Current limit mode
Lock OK COM
(both side)
N.L 3. COM (Green) :
(LED) ON: Communication successfully with CSU
OFF: Communication fail
Blinking: Start up
Delta Confidential
6
Controller
LCD display
LED1
LED2
Button
Mini USB port (Up, Down, Enter and ESC)
Delta Confidential
7
Delta Power System LVDS Behavior
Power System Battery Power System Battery
Rectifier Battery Volt Battery Volt
Volt (54V) (54V) (54V)
Energy Energy Energy Energy
BLVD BLVD
Battery Low Battery Low
Voltage Rectifier Voltage
Disconnect Volt (0V) Disconnect
Current Current
BLVD Sensor Sensor
Close BLVD
Close
LVDS2 LVDS2
Close Close
PL NPL PL NPL
Output (Load)
Output (Load)
Delta Confidential
10
LCD Display Operation Use The Keypad
Delta Confidential
11
Manual tree
ESC ENTER
SMR status
Rectifier Batt. Info PeriodInfo
Properties
Parameter Manu - Test
User Sys Info Battery
Batt. Test Mode
DC V
Sys Alarm Alarm Info Temp.
Temp Status High – T
comp
Sys Config Major Linear Low - T
Boost
Minor Curve Runaway
Alarm ACV Profile
Relay
Admin ACV Boost Capacity M
Temp
DI Alarm V- Mode Mode Voltage M
Alar Reset Door O T- Mode Boost Stop Recharge M
Manu Periodic M
Event Log LVD IP Add Charg
Eff. Mgt Web IP Subnet
Buzzer Gateway
Door O FW Version
Com-F
B Test F
C-Fan F
SSM Com F
Delta Confidential 12
Manual tree
ESC ENTER
CL FLV Start T
Status
Parameter EQUV Slope
Rectifier FixVolt Cycle
Capacity StopV
Batt. Test Date
User Max. Ib
Time
Same with Battery Temp. Start T
“User”Sys Info Perios Set
comp Status Slope
Manu StopV
Alarm Set DCV Boost Coef
Test Ref T Temp
Temp StopV
DCH Mode Upper
Sys Info Sys Config ACV DCL Lower
LV2
Door O Status
Admin Setting High T
Eff. Mgt TBH Status
Rema
TBL Low T Cap
Sys Alarm TAH Mode Status
Date/Time TAL Runaway Deep Volt
Linear
Status
Delta Confidential
13
Manual tree
ESC ENTER
Alar Reset
Alarm
Contrast
Door O LCD set
Language
Password
Delta Confidential
14
Floating Voltage Setting
Delta Confidential
Confidential 15 15
Floating Voltage Setting
Delta Confidential
Confidential 16
Manual EQU
Delta Confidential
Confidential 17
Floating and EQU Charge
Current vs. Voltage
Voltage Current
電電電電
Voltage
56V
54V
電電電電
Current
42V
t
0 T1 T2
0 ~ T1 : Constant Current
T1 ~ T2 : Constant Voltage ( Boost )
T2 ~ : Constant Voltage (Floating )
Delta Confidential 18
Web Card Gui
Delta Confidential
19
Home page_Web Card Gui
Delta Confidential
20
System Operation by ARMS
- Cable Connection
ACU with USB interface
Delta Confidential
Confidential 21
System Operation by ARMS
- USB Driver Installation
Step 1: Go to
http://www.silabs.com/products/mcu/Pages/USBtoUARTBridgeVCPDrivers.aspx
to download the USB driver installation file. Choose “VPC Driver Kit”.
Delta Confidential
Confidential 22
System Operation by ARMS
- USB Driver Installation
Delta Confidential
Confidential 23
System Operation by ARMS
- USB Driver Installation
Step 3: Follow the steps in the installation wizard to complete the installation
Delta Confidential
Confidential 24
System Operation by ARMS
- USB Driver Installation
Delta Confidential
Confidential 25
System Operation by ARMS
- USB Driver Installation
Step 5: A dialog confirms that the installation has been successfully completed. Click “OK”
Delta Confidential
Confidential 26
System Operation by ARMS
- Start ARMS SW
Use the following procedure to start the communication between the computer
and the CSU 502 controller.
Step 1: Connect the computer to the CSU 502 controller with a USB cable.
Step 2: Double-click the “ARMS_V3.12B01.exe” file to start the ARMS SW.
Step 3: Select the “LOCAL” item and the connection “COM” port on Login ARMS
dialog.
Delta Confidential
Confidential 27
System Operation by ARMS
- Start ARMS SW
Step 4: Once connect to CSU is OK. Select the Account: “User” item and enter
password to login ARAM.
User User
Delta Confidential
Confidential 28
System Operation by ARMS
- ARMS Screen Layout
Main Display Area for System
Configuration / Status
Monitoring and Setting
System Status
Monitoring
Manual Charge
Button
Batt. Capacity
Test Button
Alarm/Event
List
Battery Parameter
Delta Confidential
31
ESAA300-CAA03 Power System
AC Cabling for 3 phase
AC Grounding bar
ACPDB on site
(provide by customer)
Delta Confidential
32
ESAA300-CAA03 Power System
AC Cabling for Single phase
AC Main breaker
AC Cable
L1 (3 phase -4W)
L3
L2
L1 N
N
FG
L2
AC Grounding bar L3
ACPDB on site
(provide by customer)
Delta Confidential
33
ESAA300-CAA03
Alarm
Alarm cabling Relay
PIN Alarm Setting Alarm Description
1 COM
1 2 NC DC Low DC Low
3 NO
4 COM
Delta Confidential
34
ESAA300-CAA03
Put battery temperature (TB) sensor at top of bank 2 on battery block 3
Delta Confidential
35
3 System operation & maintenance
Delta Confidential
36
4 Trouble Shooting
a) AC Fail Alarms
- No AC input to rectifier system – rectifier is OFF
- Battery is in discharge mode
Possible cause:
1) Power system AC mains breaker tripped
2) AC outage (voltmeter to measure input voltage at mains breaker)
Delta Confidential
37
Trouble shooting
Alarms and troubleshooting
Delta Confidential
38
Trouble shooting
Alarms and troubleshooting
Delta Confidential
39
Trouble shooting
Alarms and troubleshooting
Delta Confidential
40