You are on page 1of 10

Project:

R.R. Rojo and Associates


Prepared by: Checked by: Location:

ANCHOR BOLT DESIGN


RESULT The Anchor Rod Design Is Adeq
Loadings:
Mu = 1000 kN-m.
Pu = 100 kN
Vu = 10 kN

Properties:
Concrete Strength fc' = 21 MPa
Strength of Anchor futa = 400.2 MPa
Base Plate Yield Strength fy = 248 MPa
Base Plate Cantilever m= 100 mm.
Eff. Embedment Depth hef = 240 mm.
Anchor Diameter d= 51 mm.
Type of Anchor Head Heavy Hex
Apply Seismic Load Factor? Yes
Ω= 2.5
Ase,N = 1612.9 mm^2
Ab = 3429.67056 mm^2
distance between Fastene ca1 = 300 mm
distance between Fastene ca2 = 230 mm

Anchor Bolt Location to Work Point

Bolt Number X Y
1 -8 8
2 -8 0
3 -8 -8
4 8 8
5 8 0
6 8 -8
Analysis:
Anchor Forcces Without Concrete Compression Forces Being Considered

XCG2 YCG2
0 0

Bolt Number X Y XCG2 YCG2


1 -80 80 6400 6400
2 -80 0 6400 0
3 -80 -80 6400 6400
4 80 80 6400 6400
5 80 0 6400 0
6 80 -80 6400 6400
0 0 0 0 0
0 0 0 0 0
0 0 0 0 0
0 0 0 0 0
0 0 0 0 0
0 0 0 0 0
0 0 0 0 0
0 0 0 0 0
0 0 0 0 0
0 0 0 0 0
0 0 0 0 0
0 0 0 0 0
0 0 0 0 0
0 0 0 0 0
38400 25600
Tensile Anchor Strength
Nua,1 = 46.875 kN
Nua,2 = 18.750 kN

φNsa = φAse,N(futa) = 484.112 kN > Nua = max(Nua,1:Nua,2)

Concrete Breakout Strength of Governing Anchor


φNcb = φ(ANC/ANCo)Ψec,NΨed,NΨc,NNb = φ(AN/9h2ef)Ψec,N1.0Ψc,N(24√(fc')hef1.5)
φ 0.5625
ANCo = 518400 mm^2
AN = 475200 mm^2
AN = 0 1/4 of ANCo **Conservative Value
Used AN = 475200 mm^2
Ψec,N = 1.0, for no eccentricity in the connection.
Ψc,N = 1.0, for location where concrete cracking is likely to oc
φNcb = 210.849 kN > Nua =

Concrete Breakout Strength of All Anchor


φNcbg = φ(ANC/ANCo)Ψec,NΨed,NΨc,NNb = φ(AN/9h2ef)Ψec,N1.0Ψc,N(24√(fc')hef1.5)
φ= 0.5625
ANCo = 518400 mm^2
AN = 615000 mm^2
Used AN = 615000 mm^2
Ψec,N = 1 1.0, for no eccentricity in the connection.
Ψc,N = 1 1.0, for location where concrete cracking is likely to oc
φNcbg = 272.879 kN > -Pu =

Pull out Strength of Governing Anchor


φNpn = φΨcp,N(Ab8fc')
φ= 0.5625
Ab = 3429.671
Ψcp,N = 1 for concrete cracking likely to occur
φNpn = 324.104 kN > Nua =

Side-face Blowout Strength


φNpn =φ13ca1√(Abrg)λa√(fc')
φ= 0.5625
Ab = 3429.67056 mm^2
ca1 = 300 mm.
ca2 = 230 mm.
ca2 < 3ca1
ca2/ca1 = 0.766667 0.7666666667
factor = 1
φNsb = 588.7392414063 kN > Nua =

Design Tensile Strength of Governing Anchor


φNn = min(φNsa,φNcb,φNpn,φNpn)
φNn = 210.849 kN

Shear Strength of Governing Anchor


φVsa = φ0.60*Ase,Vfuta
φ= 0.65
Ase,V = 1612.9 mm^2
φVsa = 251.738 kN > Vua =
**first factor shall be multiplied by 0.8, for built-up grout pads

Breakout Strength of Governing Anchor For Shear

φVcb = φ(AVC/AVCo)Ψec,VΨed,VΨc,VVb = φ1.0Ψec,V1.0Ψc,V(0.6(le/d)0.2√(d)√(fc')(hef)1.5


φ= 0.75
Ψec,V = 1 for no eccentricity in the connection.
Ψc,v = 1 for location where concrete cracking is likely to occur.
le/d = 8 should not exceed 8
φVcb = 82.993 kN > Vua =

Breakout Strength of All Anchor For Shear


φVcbg = φ(AVC/AVCo)Ψec,VΨed,VΨc,VVb = φ(Av/4.5(1.5hef)^2)Ψec,V1.0Ψc,V(0.6(le/d)0.2√(d)√(fc')(hef)1.5
φ= 0.75
Ψec,V = 1 for no eccentricity in the connection.
Ψc,v = 1 for location where concrete cracking is likely to occur.
le/d = 8 should not exceed 8
ca1 = 300 mm.
ca2 = 230 mm.
Av = 378000 mm^2
φVcbg = 121.0316 mm^2 > Vua =

Pryout Strength for Shear Load on Governing Fastener


φVcp = φkcp(ANC/ANCo)Ψed,NΨc,NNb = φkcp(AN/9h2ef)1.0Ψc,N(24√(fc')hef1.5)
φ= 0.75
Ψc,N = 1 for location where concrete cracking is likely to occur.
kcp = 2 for hef ≥ 2.5mm
φVcp = 421.70 kN > Vua =

Pryout Strength for Shear Load on All Fastener


φVcpg = φkcp(ANC/ANCo)Ψed,NΨc,NNb = φkcp(AN/9h2ef)1.0Ψc,N(24√(fc')hef1.5)
φ= 0.75
Ψc,N = 1 for location where concrete cracking is likely to occur.
kcp = 2 for hef ≥ 2.5mm
φVcpg = 545.76 kN > Vua =

Design Shear Strength on Governing Anchor


φVn = min(φVsa, φVcb, φVpn)
φVn = 82.99 kN

Splitting Failure Check


ca1 > 0.4hef OK!
Note: No Splitting Failure Will Occur Since The Anchor Is Far From the Edge

Shear and Tension Interaction


Nua,2 < 0.2φNn Full Strength in Shear Shall Be Per
Vua,2 < 0.2φVn Full Strength in Tension Shall Be P

Therefore, the Interaction, Equation may Be Used

Nua,2 Vua,2
+ = 0.11
φNn φVn
Description:

Date:

DESIGN
od Design Is Adequate.

BOLT GROUP
10
8
6
4
2
0
-10 -8 -6 -4 -2 0 2 4 6 8 10
-2
-4
-6
-8
-10
Nua,2 Vua
-14.583 1.667
-14.583 1.667
-14.583 1.667
-18.750 1.667
-18.750 1.667
-18.750 1.667

-100 10
Nua = max(Nua,1:Nua,2) = 46.8750 kN OK!

vative Value

connection.
ete cracking is likely to occur.
46.8750 kN OK!

connection.
ete cracking is likely to occur.
-100 kN OK!

46.8750 kN OK!

46.8750 kN OK!
4.167 kN OK!

acking is likely to occur.

4.167 kN OK!

/d)0.2√(d)√(fc')(hef)1.5

acking is likely to occur.

25.000 kN OK!

acking is likely to occur.

4.167 kN OK!

acking is likely to occur.

25.000 kN OK!
gth in Shear Shall Be Permitted
gth in Tension Shall Be Permitted

< 1.2 OK!

You might also like